BY STEVE TURNER, Beckwith Electric Company, Inc. FEATURE Theory, Application, and Commissioning of Generator 100 Percent Stator Ground Fault Protection Using Low Frequency Injection Detect a stator ground when the winding insulation first starts to break down and trip the unit before catastrophic damage occurs Be set to trip in the order of cycles since the 20 Hz signal is decoupled from the 50 or 60 Hz power system Detect grounds close to the machine neutral or even right at the neutral thus providing 100 percent coverage of the stator windings Detect grounds when the machine is starting up or offline Reliably operate with the generator in various operating modes such as a synchronous condenser and at all levels of real and reactive power output. Special steps should be taken in the design of this protection as there are cases when it is difficult to distinguish between normal operating conditions and an actual ground fault. e protection must reject fundamental frequency (50 or 60 Hz) voltage and current signals that are present during ground faults on the stator windings. A real life example for a pump storage facility is included. STATOR GROUND FAULTS ROOT CAUSES In-service stator winding failure to ground is a common generator failure, and there are many possible causes such as mechanical damage to the ground wall insulation (category #1) and fracturing of the current carrying conductor that result in the ground wall insulation burning away (category #2). Examples of category #1 failures: ground wall insulation wear-through from a foreign object or loose component This paper covers practical considerations for proper application and commissioning of this special protection. The total capacitance to ground of the generator stator windings, bus work, and delta-connected unit transformer windings is a very important factor as will be shown. This protection can: 68 SUMMER 2014 64S PROTECTION GUIDE PROTECTION 64S GUIDE The InterNational Electrical Testing Association Journal

Upload: lydien

Post on 17-May-2018

234 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: FEATURE 64S PROTECTION GUIDE - netaworld.org Application, ... 68 • SUMMER 2014 64S PROTECTION GUIDE 64S PROTECTION GUIDE ... CT. It is important to note that the relay does

BY STEVE TURNER, Beckwith Electric Company, Inc.

FEATURE

Theory, Application, and Commissioning of Generator 100 Percent Stator Ground Fault Protection Using Low Frequency Injection

• Detect a stator ground when the winding insulation fi rst starts to break down and trip the unit before catastrophic damage occurs

• Be set to trip in the order of cycles since the 20 Hz signal is decoupled from the 50 or 60 Hz power system

• Detect grounds close to the machine neutral or even right at the neutral thus providing 100 percent coverage of the stator windings

• Detect grounds when the machine is starting up or offl ine

• Reliably operate with the generator in various operating modes such as a synchronous condenser and at all levels of real and reactive power output.

Special steps should be taken in the design of this protection as there are cases when it is diffi cult to distinguish between normal

operating conditions and an actual ground fault. Th e protection must reject fundamental frequency (50 or 60 Hz) voltage and current signals that are present during ground faults on the stator windings. A real life example for a pump storage facility is included.

STATOR GROUND FAULTS ROOT CAUSESIn-service stator winding failure to ground is a common generator failure, and there are many possible causes such as mechanical damage to the ground wall insulation (category #1) and fracturing of the current carrying conductor that result in the ground wall insulation burning away (category #2).

Examples of category #1 failures: • ground wall insulation wear-through from

a foreign object or loose component

This paper covers practical considerations for proper application and commissioning of this special protection. The total capacitance to ground of the generator stator windings, bus work, and delta-connected unit transformer windings is a very important factor as will be shown. This protection can:

68 • SUMMER 2014 64S PROTECTION GUIDE

PROTECTION 64S GUIDE

NETA_InteriorPages_SUM14.indb 68 5/21/14 1:27 PM

The InterNational Electrical Testing Association Journal

Page 2: FEATURE 64S PROTECTION GUIDE - netaworld.org Application, ... 68 • SUMMER 2014 64S PROTECTION GUIDE 64S PROTECTION GUIDE ... CT. It is important to note that the relay does

NETAWORLD • 6964S PROTECTION GUIDE NETAWORLD • 69

FEATURE

• fracture of the ground wall due to a sudden short circuit

• de cient ground wall insulation system• partial discharge combined with vibration• vibration sparking, inadvertent damage

during maintenance• wet insulation due to strand header water

leak, bar vibration in the slot

Examples of category #2 failures:• fracture of stator bar copper conductors

due to high cycle fatigue associated with vibration

• fracture of bar copper due to gross overheating of the copper

• core iron melting, failure of a bolted connection

• failure of a brazed or welded joint• failure of a series or phase connection

Category #1 failures are typically benign, unless a second ground occurs, in which case there is massive arcing. Category #2 failures are always highly destructive to the generator. Current will temporarily continue to flow uninterrupted within the stator bar ground wall insulation (i.e., welding arc) when a conductor breaks and the heat generated is extremely high. This current will flow inside the insulation until it is mechanically destroyed. Experience has shown that the copper is vaporized for perhaps 8 to 12 inches before the internal arcing breaks through the insulation wall and arcs to ground as shown in Figures 1-3.

Conventional neutral overvoltage protection (59N) cannot detect grounds in the last 5 to 10 percent of the stator winding. If a failure occurs in a lower voltage portion of the winding near the neutral, a generator trip will not typically occur until some other relay protection detects there is a problem, (e.g., arcing becomes so wide-spread that other portions of the winding become involved). There has been recent experience with four such failures in large generators that demonstrate the lack of proper protection can be disastrous. Each of the four failures caused massive damage

Figure 1: Typical Winding Damage Resulting from Broken Stator Winding Conductor

Figure 2: Typical Core and Winding Damage Resulting from a Burned Open Bar in a Slot

Figure 3: Burned Away Copper–Fractured Connection Ring

PROTECTION

NETA_InteriorPages_SUM14.indb 69 5/21/14 1:27 PM

Page 3: FEATURE 64S PROTECTION GUIDE - netaworld.org Application, ... 68 • SUMMER 2014 64S PROTECTION GUIDE 64S PROTECTION GUIDE ... CT. It is important to note that the relay does

to the generator and collectively had a total cost, including repair and loss of generation, close to $500,000,0001. This demonstrates that failure of stator windings in the last five percent of the winding is not uncommon.

One hundred percent stator ground fault protection is provided by injecting a 20 Hz voltage signal (64S) into the secondary of the generator neutral grounding transformer through a band-pass filter. The band-pass filter passes only the 20 Hz signal and rejects out of band signals. The main advantage of this protection is it provides 100 percent protection of the stator windings for ground faults–including when the machine is off-line (provided that the 20 Hz signal is present).

APPLICATIONFigure 4 illustrates a typical application. A 20 Hz voltage signal is impressed across the grounding resistor (RN) by the 20 Hz signal

generator. e band-pass lter only passes the 20 Hz signal and rejects out of band signals. e voltage across the grounding resistor is also connected across the voltage input (VN) of the 64S function. e current input (IN) of the 64S function measures the 20 Hz current owing on the secondary side of the grounding transformer and is stepped down through a CT. It is important to note that the relay does not measure the 20 Hz current owing through the grounding resistor; it measures the 20 Hz current owing into the power system. e 20 Hz current magnitude increases during ground faults on the stator winding and an overcurrent element that operates on this low frequency current provides the protection.

20 Hz Voltage and Current 64S Relay MeasurementsThe following method shows how to calculate the 20 Hz voltage and current measured by the 64S function.

70 • SUMMER 2014 64S PROTECTION GUIDE

FEATURE

Figure 4: 20 Hz Injection Grounding Network

NETA_InteriorPages_SUM14.indb 70 5/21/14 1:27 PM

Page 4: FEATURE 64S PROTECTION GUIDE - netaworld.org Application, ... 68 • SUMMER 2014 64S PROTECTION GUIDE 64S PROTECTION GUIDE ... CT. It is important to note that the relay does

NETAWORLD • 71

FEATURE

64S PROTECTION GUIDE

Grounding Transformer Turns Ratio (N)Assume that the turns ratio of the grounding transformer is equal to:

(1)N = 8,000 240

Capacitive Reactance e total capacitance to ground of the generator stator windings, bus work, and delta connected transformer windings of the unit transformer is expressed as C0. Generator step up transformers have delta connected windings facing the generator so capacitance on the high side is ignored. e corresponding capacitive reactance is calculated as follows:

XCO=

12π foCo

(2)

Assume the capacitance to ground is 1 microfarad:

XCO= 1

2•π • (20Hz)• (10−6F)

= 7,958Ω primary

Re ect the capacitive reactance to the secondary of the grounding transformer:

XCO=

7,958ΩN 2 =

7,958Ω8,000

240( )2

= 7.162Ω secondary

Grounding Resistor (RN) e ohmic value of the grounding resistor can be sized as follows so as to avoid high transient overvoltage due to ferroresonance2:

RN = Xc0

3 (3)

RN =

7.162Ωsec

3

= 2.387Ω secondary

A value of 2.5 ohms secondary is used for this example.

20 Hz Signal Generator and Band-pass Filter Characteristics e 20 Hz signal generator output is 25 volts RMS and the band-pass lter has a resistance equal to eight ohms.

Vsource = 25∠0° volts (4)

RFilter = 8Ω secondary (5)

Stator Insulation Resistance (RS)RS is the total insulation resistance from the stator windings to ground. A typical value for nonfault conditions is 50,000 ohms primary. Re ect the insulation resistance to the secondary of the grounding transformer.

Rs = 50,000Ω pri

N 2 = 50,000Ω pri

8,000240( )2

= 45Ω secondary

Current Transformer e current input (IN) of the 64S function measures the 20 Hz current owing on the grounded side of the grounding transformer and is stepped down through a CT.

CTR = 400/5 = 80/1 (6)

Grounding Network ese are all of the elements needed to mathematically derive the grounding network and determine the 20 Hz signals measured by the 64S function. Figure 5A shows the insulation resistance and the stator windings referred to the primary of the grounding transformer. Figure 5B shows the insulation resistance and the stator windings re ected to the secondary of the grounding transformer.

NETA_InteriorPages_SUM14.indb 71 5/21/14 1:27 PM

Page 5: FEATURE 64S PROTECTION GUIDE - netaworld.org Application, ... 68 • SUMMER 2014 64S PROTECTION GUIDE 64S PROTECTION GUIDE ... CT. It is important to note that the relay does

FEATURE

20 Hz Current (IN) Measured by 64S Function e current input (IN) of the 64S function measures the 20 Hz current owing in the secondary of the grounding transformer and is stepped down through a CT. As noted previously the relay does not measure the 20 Hz current owing through the grounding resistor.

Total 20 Hz Current Supplied by Signal Generator – e 20 Hz signal generator looks into the band pass lter resistance (RFilter) which is in series with the parallel combination of the following:

• ZCO

• Rs

• RN

erefore, the total loop impedance of the 20 Hz grounding network can be expressed as follows:

ZT = RFilter + RN •

RS • ZCORS + ZCO

RN +RS • ZCORS + ZCO

⎜⎜⎜⎜

⎟⎟⎟⎟

(7)

ZT = 8 + 2.5( ) / / 45( ) / / − 7.162 j( ) = 10.135 – 0.706 j Ω secondary

e total 20 Hz current supplied by the signal generator is determined as follows:

IT = VCTR• ZT

(8)

IT = 25∠0°V801• (10.135 − 0.706 j Ω)

= 30.759 mA

20 Hz Current Measured by 64S Function (IN) during Nonfaulted Conditions

The 20 Hz current measured by the 64S function is the ratio of the total current that flows into the primary side of the grounding network (ZCO

//Rs):

72 • SUMMER 2014 64S PROTECTION GUIDE

Figure 5A: 20 Hz Grounding Network – Referred to Grounding Transformer Primary

Figure 5B: 20 Hz Grounding Network – Re ected to Grounding Transformer Secondary

XC = total capacitance to ground

Rstator = stator insulation resistance to ground

RN = neutral resistor

RFilter = band-pass lter resistance

VN = voltage drop across RN

IN = current from system

IBANK = current ow in RN

IT = IBANK + IN

NETA_InteriorPages_SUM14.indb 72 5/21/14 1:27 PM

Page 6: FEATURE 64S PROTECTION GUIDE - netaworld.org Application, ... 68 • SUMMER 2014 64S PROTECTION GUIDE 64S PROTECTION GUIDE ... CT. It is important to note that the relay does

IN = IT •RN

RN +ZCo • RSZCo + RS

(9)

IN = 30.579• 2.52.5 + (−7.162 j) / /(45)

= 9.779 mA Nonfaulted( )

20 Hz Current Measured by 64S Function (IN) during Ground Fault on Stator Windings

A typical value to represent the insulation resistance of the stator windings when it is breaking down during a ground fault is 5,000 ohms primary. If the calculations for equations 7 through 9 are repeated for a fault resistance equal to 5,000 ohms primary (4.5 ohms secondary), then the 20 Hz current measured by the relay is as follows:

|IN| = 13.486 mA (5,000 ohm primary ground fault)

If the calculations for equations 7 through 9 are repeated for a fault resistance equal to 1,000 ohms primary (0.9 ohms secondary), then the 20 Hz current measured by the relay is as follows:

|IN| = 26.640 mA (1,000 ohm primary ground fault)

Table 1 summarizes the 20 Hz current measured by the relay for nonfaulted and faulted conditions. Often the 64S protection can detect the ground for insulation resistance is much higher than 5,000 ohms primary.

e 64S function can easily distinguish between nonfault and stator ground faults for this example. Set the pickup of the 64S, 20 Hz tuned, overcurrent element above the current measured during normal operating conditions but below the current measured for a stator ground fault equal to 5,000 ohms primary.

PRACTICAL CONSIDERATIONSHere are three important aspects to consider when applying 100 percent stator ground fault protection by 20 Hz injection:

• slight change in fault current measured by relay

• rejection of fundamental frequency (50 or 60 Hz) voltage and current signals

• under-frequency inhibition

Slight Change in Fault CurrentA very large capacitance to ground (C0) coupled with a small value for the grounding resistor (RN) can result in very little margin between the fault and nonfault current measured by the 64S function. Generator windings and isophase bus work (see Figure 6) are both sources of high capacitance to ground (ex., a long run of bus from the generator to the step-up transformer).

NETAWORLD • 73

FEATURE

64S PROTECTION GUIDE

Table 1: 20 Hz Current Measurements

Figure 6: Iso-Phase Bus Work

RS (primary) |IN| (secondary)

50,000 Ω 9.779 mA

5,000 Ω 13.486 mA

1,000 Ω 26.640 mA

NETA_InteriorPages_SUM14.indb 73 5/21/14 1:27 PM

Page 7: FEATURE 64S PROTECTION GUIDE - netaworld.org Application, ... 68 • SUMMER 2014 64S PROTECTION GUIDE 64S PROTECTION GUIDE ... CT. It is important to note that the relay does

74 • SUMMER 2014 64S PROTECTION GUIDE

Figure 7: Primary Side Current Distribution

Table 2: 20 Hz Current Measurements for High Capacitance

Figure 8: Current Flow in Secondary Network

RS (primary) |IN| (secondary)

50,000Ω 12.465 mA5,000Ω 12.096 mA1,000Ω 12.863 mA

Figure 7 illustrates why there is not a signi cant change in the magnitude of the total neutral current when there is high capacitance. If the capacitive reactance is low enough, then only a small portion of the total neutral current ows through the insulation resistance. To overcome this challenge, calculating the real component of the total neutral current can reliably detect a stator ground fault for such a system.

Consider the following grounding network parameters:

N = 8,000240

C0 = 10µF → ZCO = -0.716j Ω secondary

RN = 0.25 Ω secondary

Determine the 20 Hz current measured by the 64S function for nonfaulted and stator ground fault conditions using the equations presented in the previous application section as shown in Table 2 below.

e 64S 20 Hz tuned overcurrent element pickup cannot be set such that it reliably discriminates between nonfaulted and stator ground fault conditions. e solution is for the relay to calculate the real component of the 20 Hz current with respect to the neutral voltage. To do so, rst determine the 20 Hz voltage measured by the relay voltage input (VN). e 20 Hz voltage is equal to the drop across the grounding resistor due to the portion of the total current owing through this branch of the grounding network (i.e., IBANK). Use Figure 8 above to determine the corresponding equations (10 – 13).

20 Hz Current Flowing through the Grounding Transformer

IBank = IT – IN (10)

20 Hz Voltage Drop Across the Grounding Resistor

VN = IBank•RN (11)

Real Component of 20 Hz Current Measured by 64S FunctionCalculate the real component of the relay current based upon the angle between the relay neutral voltage (VN) and current (IN) as shown in Table 3.

∅ = ∠VN − ∠IN (12)

IReal = IN iCOS(∅) (13)

FEATURE

NETA_InteriorPages_SUM14.indb 74 5/21/14 1:27 PM

Page 8: FEATURE 64S PROTECTION GUIDE - netaworld.org Application, ... 68 • SUMMER 2014 64S PROTECTION GUIDE 64S PROTECTION GUIDE ... CT. It is important to note that the relay does

NETAWORLD • 7564S PROTECTION GUIDE

A 20 Hz tuned overcurrent element that operates on the real component of 20 Hz current measured by the 64S function can reliably distinguish between nonfaulted and stator ground fault conditions when there is high-capacitive coupling to ground on the stator winding. A good rule of thumb is to use the real component of 20-Hz current for sensitive protection if C0 is greater than 1.5 microfarads and the grounding resistor is less than 0.3 ohms secondary. e user can follow the commissioning instructions that appear at the end of this paper to determine the total capacitance to ground (C0). If the values for RN and C0 do not clearly fall under the category de ned by this rule of thumb, then use the equations provided earlier in this paper to determine if use of the real component of neutral current is necessary.

NOTEIf the 64S function uses the real component, it should also use the total neutral current as a backup for the case of a solid short circuit located right at the machine neutral (i.e., the real component equals zero for this case since there is no reference voltage).

Rejection of Fundamental Frequency (50 or 60 Hz) Voltage and Current SignalsFundamental component voltage and current present at the relay measuring inputs during stator ground faults can prevent the 64S function from operating properly unless they are well rejected. Note that these signals are not eliminated by the band-pass lter since they are due to the fundamental voltage drop across the secondary of the grounding transformer.

Figure 9 illustrates the fundamental voltage drop (50 or 60 Hz) across the grounding resistor as a function of the ground fault location along the stator windings. Table 4 shows the voltage drop as the fault location moves from the neutral end of the stator windings to the output terminals. egrounding transformer is rated 110 volts secondary; the grounding resistor is sized 0.32 ohms secondary; and the CT ratio is 400:5 (80:1). e corresponding fundamental component circulating current is shown as well. If the fundamental current is not well rejected, then high magnitude circulating current can saturate the neutral current input and, as a result, the protection will measure a value of 20 Hz current less than the actual value. Saturation causes the following problems:

• delayed operation or, even worse, no operation at all

• less than 100% coverage of the stator windings as the ground fault location moves towards the generator output terminals.

NOTESaturation is most likely to occur when the grounding resistor is sized less than one ohm secondary.

Table 3: 20 Hz Current Measurements for High Capacitance Including Real Component

RS (primary) |IN| (secondary) Re(IN)

50,000Ω 12.465 mA 0.198 mA

5,000Ω 12.096 mA 1.900 mA

1,000Ω 12.863 mA 8.001 mA

FEATURE

Figure 9: Fundamental Voltage across RN as Function of Ground Fault Location

NETA_InteriorPages_SUM14.indb 75 5/21/14 1:27 PM

Page 9: FEATURE 64S PROTECTION GUIDE - netaworld.org Application, ... 68 • SUMMER 2014 64S PROTECTION GUIDE 64S PROTECTION GUIDE ... CT. It is important to note that the relay does

76 • SUMMER 2014 64S PROTECTION GUIDE

Fault Location VS IS IS/CTR

100% (phase side) 110 V (110 V)/0.32 Ω = 343.75 amps 4.297 amps

90% 99 V (99 V)/0.32 Ω = 309.375 amps 3.867 amps

80% 88 V (88 V)/0.32 Ω = 275 amps 3.438 amps

70% 77 V (77 V)/0.32 Ω = 240.625 amps 3.008 amps

60% 66 V (66 V)/0.32 Ω = 206.25 amps 2.578 amps

50% 55 V (55 V)/0.32 Ω = 171.875 amps 2.148 amps

40% 44 V (44 V)/0.32 Ω = 137.5 amps 1.719 amps

30% 33 V (33 V)/0.32 Ω = 103.125 amps 1.289 amps

20% 22 V (22 V)/0.32 Ω = 68.75 amps 0.859 amps

10% 11 V (11 V/0.32 Ω = 34.375 amps 0.430 amps

0% (neutral side) 0 0 0

Table 4 provides magnitudes of the variables at various fault locations along the winding.

Underfrequency InhibitionSometimes it is necessary to block the 64S function during conditions such as startup when the system voltage measured by the relay is 40 Hz or lower. e third harmonic of 7 Hz is very close to 20 Hz during startup when the generator is transitionally through the lower frequencies and can cause unwanted operation.

COMMISSIONING INSTRUCTIONSFigure 10 illustrates how to configure the 64S protection for commissioning.

NOTEUse the 20 Hz signals captured during normal operating conditions to determine appropriate overcurrent pickup settings. Determine the

total capacitance to ground and calculate the overcurrent pickup setting based upon these eld measurements as a check.

Stator Ground Fault at Machine NeutralConfigure the power system as follows:

• High side breaker is open. • e generator is o ine. • Generator terminals are connected to delta windings of the generator step up transformer. • Switch F1 is closed. • Switch F2 is open. • 20 Hz signal generator is online.

Place a single line-to-ground fault at location F1 (switch F1 closed) and measure the 20 Hz IN. is measurement corresponds to a short circuit applied at the neutral of the machine (see Figure 11 on the following page).

e total 20 Hz neutral current (IN) should be very close in magnitude to 39 mA.

Table 4: Fundamental Voltage Drop Across Grounding Resistor and Circulating Current (RN = 0.32 Ω)

FEATURE

NETA_InteriorPages_SUM14.indb 76 5/21/14 1:27 PM

Page 10: FEATURE 64S PROTECTION GUIDE - netaworld.org Application, ... 68 • SUMMER 2014 64S PROTECTION GUIDE 64S PROTECTION GUIDE ... CT. It is important to note that the relay does

NETAWORLD • 7764S PROTECTION GUIDE

Figure 10: 20 Hz Grounding Network for Commissioning

Isc = 25

8ohmsX 4005

= 39mA

NOTE is is the rst step and is a quick check to see if all the wiring is correct.

Normal Operating ConditionsConfigure the power system as follows:

• High side breaker is open. • Generator terminals are connected to delta windings of the generator step up transformer. • Switch F1 is open. • Switch F2 is open.

• 20 Hz signal generator is online. • Preferably the generator is online.

Measure the following 20 Hz signals:

• VN (neutral voltage) • IN (neutral current) • Re(IN)(real component of neutral current)

These signals correspond to normal operating conditions.

VN and IN are the 20 Hz signals applied to the relay inputs. Record VN, IN, and Re(IN). Modern numerical generator relays can meter these values. e signals recorded in Figure 11 were captured while commissioning a large pumped storage hydroelectric unit while operating in the motoring (pumping) mode.

FEATURE

Figure 11: Short Circuit at Machine Neutral

Figure 12: Numerical Generator Relay 20 Hz Metering

NETA_InteriorPages_SUM14.indb 77 5/21/14 1:27 PM

Page 11: FEATURE 64S PROTECTION GUIDE - netaworld.org Application, ... 68 • SUMMER 2014 64S PROTECTION GUIDE 64S PROTECTION GUIDE ... CT. It is important to note that the relay does

78 • SUMMER 2014 64S PROTECTION GUIDE

CONCLUSIONS is special protection provides 100 percent coverage of the stator windings for ground faults under all operating conditions including variable real and reactive power output and when o -line. Grounds on the last ve percent of the stator windings do occur and can be disastrous if not quickly detected. Traditional protections (59N, 27TH, 27D) may not reliably operate for faults in the last ve percent of the stator winding.

e total capacitance-to-ground of the generator stator windings, bus work, and delta-connected unit transformer windings is a very important factor and must be known to ensure the protection settings are correctly determined. is value can be determined during commissioning.

ere are cases when it is di cult to distinguish between normal operating conditions and an actual stator ground fault unless special steps are taken in the design of this protection. A good rule of thumb to decide if the real component of 20 Hz current is necessary is when C0 is greater than 1.5 microfarads and the grounding resistor is less than 0.3 ohms secondary. Use the real component of the 20 Hz current measured by the relay for these cases.

The protection must reject fundamental frequency (50 or 60 Hz) voltage and current

signals that are present at the relay measuring inputs during ground stator ground faults.

Use an under-frequency element that operates on the system voltage to block the 64S function if nuisance tripping occurs during either startup or shutdown of the generator.

REFERENCES1. Maughan, Clyde V., “Stator Winding Ground Protection

Failures”, ASME POWER 98151-2013

2. Macon, Russell C., “ e Art and Science of Protective Relaying”, Wiley 209-210, 1956

Steve Turner is a Senior Applications Engineer at Beckwith Electric Company, Inc. His previous experience includes working as an application engineer with GEC Alstom for fi ve years, an application engineer in the international market for SEL, focusing on transmission line protection applications. Steve worked for

Progress Energy, where he developed a patent for double-ended fault location on transmission lines and was in charge of all maintenance standards in the transmission department for protective relaying.

Steve has both a BSEE and MSEE fr om Virginia Tech University. He has presented at numerous conferences including Georgia Tech Protective Relay Conference, Western Protective Relay Conference, ECNE, and Doble User Groups, as well as various international conferences. Steve Turner is also a senior member of the IEEE.