SIMATIC Technical Support Extended Diagnostics in PCS 7and WinCC Plants
Diagnostic tools May 2011
Warranty and Liability
2 Extended Diagnostics in PCS 7and WinCC Plants
V 2.5.1 Entry ID: 48698507
Siemens AG, Sector Industry, Industry Automation, Automation Systems
This entry is from the Technical Support of Siemens AG, Industry Automation.
If you have any questions regarding this entry, please contact us at the following e-mail address:
Warranty and Liability The conditions of use specified there apply (www.siemens.com/terms_of_use).
Contents
Extended Diagnostics in PCS 7and WinCC Plants V 2.5.1, Entry ID:48698507 3
Contents Warranty and Liability ................................................................................................. 2 1 Overview............................................................................................................. 4
1.1 Motivation ............................................................................................. 4 1.2 Overview of Diagnostics Options ......................................................... 4 1.3 Requirements for Extended Diagnostics of PCS 7 and WinCC Plants 6 1.3.1 Software Components.......................................................................... 6
2 Configuration of Diagnostics ........................................................................... 8 2.1 Dr. Watson ........................................................................................... 8 2.2 User Mode Process.............................................................................. 9 2.2.1 Processes to be monitored ................................................................ 14 2.3 Script Diagnostics (APDIAG) ............................................................. 16 2.4 Windows Performance Monitor .......................................................... 18 2.5 SIMATIC Batch Trace ........................................................................ 26
3 Tools ................................................................................................................. 30 3.1 SIMATIC Diagnostics Tool ................................................................. 30 3.1.1 Install the SIMATIC Diagnostics Tool................................................. 30 3.1.2 Configure the SIMATIC Diagnostics Tool Locally .............................. 31 3.1.3 Configure the SIMATIC Diagnostics Tool Centrally ........................... 34
4 Archiving the Diagnostics .............................................................................. 39 4.1 Acquisition of Local Diagnostics Data ................................................ 39
5 Literature .......................................................................................................... 41 5.1 Bibliography........................................................................................ 41 5.2 Internet Links...................................................................................... 41
6 History............................................................................................................... 42 6.1 Version Overview ............................................................................... 42
1 Overview
4 Extended Diagnostics in PCS 7and WinCC Plants
V 2.5.1 Entry ID: 48698507
1 Overview
1.1 Motivation
Proper evaluation of qualified status data is necessary for successful diagnostics and resulting actions. The aim is to improve the quality diagnostics results and therefore their comparability by applying automatic, uniform diagnostics. The advantages of this diagnostics concept are the following:
Standardized and automatic acquisition of diagnostics data
Permanent and comprehensive diagnostics
Integration of the diagnostics tool without causing interference of production operations
The diagnostics data is available as soon as an event occurs
Diagnostics of the Windows process level
1.2 Overview of Diagnostics Options
The following figure shows an overview of the tools to be configured.
Figure 1-1
1 Overview
Extended Diagnostics in PCS 7and WinCC Plants V 2.5.1, Entry ID:48698507 5
Dr. Watson
Dr. Watson logs data after a program error.
Creating a log file
Creating a crash memory dump
User Mode Process
The "User Mode Process Dumper" monitors the processes set and creates a memory dump in the event of an error.
Script Diagnostics (APDIAG)
Diagnostics tool for in-depth and effective analysis of script errors.
Runtime monitoring for determining script errors.
Support in analyzing errors and performance problems.
Windows Performance Monitor
The system monitor (performance monitor) integrated in the Windows operating system is designed to detect resource bottlenecks in the system.
Detailed monitoring of the operating system resources used.
Cyclic recording of system resources.
SIMATIC Batch Trace
After activation, a log of the batch processes is stored continuously.
SIMATIC Diagnostics Tool
The "SIMATIC Diagnostics Tool" acquires diagnostics and system data for service, support and maintenance. The tool can be run locally on a computer, but can also acquire diagnostics data from other computers via remote access in distributed systems.
Acquisition of diagnostics data.
Acquisition of system data.
Archiving of acquired data sorted according to computer in the ZIP format.
Transfer of central data via the integrated ftp service.
1 Overview
6 Extended Diagnostics in PCS 7and WinCC Plants
V 2.5.1 Entry ID: 48698507
1.3 Requirements for Extended Diagnostics of PCS 7 and WinCC Plants
1.3.1 Software Components
Standard software components
Table 1-1
Components Version Note
Windows 2000 Windows XP Windows Server 2003
PCS 7 V6 V 6.x Includes WinCC V 6.0
PCS 7 V7.0 V 7.0 Includes WinCC V 6.2
PCS 7 V7.1 V 7.1 Includes WinCC V 7.0
WinCC V6 V 6.x
WinCC V7 V 7.x
Tools and diagnostics software
Table 1-2
Components Version Note
User Mode Process Dumper 8.1 Link: User Mode Process Dumper
APDIAG ..\Siemens\WinCC\utools\apdiag.exe
Performance Monitor ..\Windows\system32\perfmon.exe
Templates (Performance Monitor) "DiagAllCountersClient.htm" "DiagAllCountersServer.htm" "CPUPeakCheck.htm"
Trace Configuration Editor ..\Program Files\ SIEMENS\Common\bin\ pcs7commontracecontrolx.exe
SIMATIC Diagnostics Tool Edition 2010 DVD SIMATIC PCS 7 V7.1 incl. SP2 ..\Additional_Products\SDT_2010_1\ or Link: SIMATIC Diagnostics Tool
Templates (SIMATIC Diagnostics Tool)
"remote.xml" "local.xml"
PsExec (required for SIMATIC Diagnostics Tool)
V1.98 Link: PsExec
1 Overview
Extended Diagnostics in PCS 7and WinCC Plants V 2.5.1, Entry ID:48698507 7
User rights and releases
The user requires administrator rights on the target system for installation and setting up.
Hard disk space
At least 3 GB of memory are required on your hard disk for the diagnostics data.
The storage path is defined as "D:\Siemens\Diagnostics". This storage path is used by the "User Mode Process" and "Windows Performance Monitor" tools and the "SIMATIC Diagnostics Tool".
Limitation
This diagnostics concept does not include a description of the
Engineering tools PCS 7 and WinCC
Basic knowledge of these topics is prerequisite.
2 Configuration of Diagnostics
8 Extended Diagnostics in PCS 7and WinCC Plants
V 2.5.1 Entry ID: 48698507
2 Configuration of Diagnostics To fulfill the requirements for comprehensive diagnostics it is recommended to make all the settings described in this chapter.
2.1 Dr. Watson
Below we describe how to set "Dr. Watson" as the default debugger.
Table 2-1
No. Procedure
1. Execute Start > Run.... Enter DRwtsn32 -i and start the procedure with OK.
2. Again select Start > Run... and again enter DRwtsn32 and again start the procedure with OK.
3. Set the crash dump to Full.
2 Configuration of Diagnostics
Extended Diagnostics in PCS 7and WinCC Plants V 2.5.1, Entry ID:48698507 9
2.2 User Mode Process
The instructions below are for installing and using the User Mode Process Dumper in WinCC and PCS 7.
After activation, a memory dump of a process is made in the event of an error.
Table 2-2
No. Procedure
1. Download the User Mode Process Dumper version V8.1 from the Microsoft internet site and install the user dump tool in "C:\kktools\userdump8.1".
2. Switch to the "C:\kktools\userdump8.1" directory. Start the "setup.exe" of the User Mode Process Dumper from the folder corresponding to your operating system (ia64, x64 or x86). In the next window you click the "Next" button.
2 Configuration of Diagnostics
10 Extended Diagnostics in PCS 7and WinCC Plants
V 2.5.1 Entry ID: 48698507
3. In the "Terminate Mode" window you select the option "Disable "Dump on Process
Termination" feature" and confirm with the "Next" button.
4. Now, in the "Confirmation" window you click the "Finish" button to complete the installation.
5. Acknowledge the next message with "Yes" to open the configuration of the "User Mode Process Dumper".
2 Configuration of Diagnostics
Extended Diagnostics in PCS 7and WinCC Plants V 2.5.1, Entry ID:48698507 11
6. In the "User Mode Process Dumper Properties" window you open the default rules and requirements window with the "Default Settings…" button.
2 Configuration of Diagnostics
12 Extended Diagnostics in PCS 7and WinCC Plants
V 2.5.1 Entry ID: 48698507
7. In the "Default Exception Rules" window you set the rules as shown in the screenshot below and define the storage path of the dump as "D:\Siemens\Diagnose\Dumps". It might be necessary to create a new directory.
Close the window with "OK". Note: These settings are used for all processes in which no "Custom Rules" are activated. The "dump files" are acquired by the "SIMATIC Diagnose Tool" from this predefined storage path.
2 Configuration of Diagnostics
Extended Diagnostics in PCS 7and WinCC Plants V 2.5.1, Entry ID:48698507 13
8.
In the "User Mode Process Dumper Properties" window you use the "New" button to add a new item.
9. In the "Add Application to Monitor for Excepti…" window you enter the process name of the application in Table 2-3 respectively 2-4 that you wish to monitor in the “Application name:” field.
Close the window with “OK”.
10. Continue likewise with all the processes listed in Table 2-3 respectively 2-4. Here, a difference is made as to whether the configuration is made on the OS server or OS client.
11. Once you have defined all the processes, you quite the “User Mode Process
Dumper” with “OK”. 12. You must restart the process concerned in each case for the settings to become
effective. For this you restart the PC.
2 Configuration of Diagnostics
14 Extended Diagnostics in PCS 7and WinCC Plants
V 2.5.1 Entry ID: 48698507
2.2.1 Processes to be monitored
When selecting the processes, a difference is made between OS server and OS client.
OS server
With the OS server you add the following processes to the User Dump Tool.
Table 2-3
Process Description
CCAgent.exe Monitors the network in which the WinCC station is located. Used by NetCC.
CCAlgRtServer.exe WinCC Alarm Logging Runtime Server
CCArchiveManager.exe WinCC Archive Manager
CCDeltaLoader.exe Logs the changes made in a project.
CCEClient.exe Central communication.
CCEServer.exe Central communication.
CCLicenseService.exe License monitoring
CCProjectMgr.exe Project Manager
CCPtmRTServer.exe Picture Tree Manager
CCRtsLoader.exe Loader for WinCC Data Manager
CCSsmRTServer.exe Base data management for Runtime
CCTextServer.exe Text Server
CCTlgServer.exe WinCC Tag Logging Runtime Server
CCWriteArchiveServer.exe Archive Server called at least three times for ALG, TLG fast and TLG2 slow archiving.
Gscrt.exe Global Script - Runtime
PdlRt.exe Graphics - Runtime
Rebootx.exe PCS7 Reboot Box
RedundancyControl.exe WinCC Redundancy Control
RedundancyState.exe WinCC Redundancy State
script.exe Background processing of actions / functions
WARNING In the case of blocking, manual dumps of the processes “PdlRt.exe” and “script.exe” must be made before restarting the computer. More information on generating manual dumps is available in our Entry ID: http://support.automation.siemens.com/WW/view/en/45020870
2 Configuration of Diagnostics
Extended Diagnostics in PCS 7and WinCC Plants V 2.5.1, Entry ID:48698507 15
OS client
With the OS server you add the following processes to the User Dump Tool.
Table 2-4
Process Description
CCDmIVarProxyServer.exe Ivar2 Proxy – data manager access
CCEClient.exe Central communication.
CCEServer.exe Central communication.
CCNSInfo2Provider.exe
CCPtmRTServer.exe Picture Tree Manager
CCSsmRTServer.exe Base data management for Runtime
gscrt.exe Global Script - Runtime
PassDBRT.exe User Administrator - Runtime
PdlRt.exe Graphics - Runtime
RedundancyState.exe WinCC Redundancy State
script.exe Background processing of actions / functions
SFCRT.exe Visualization of SFCs
Sopcsrvrwincc.exe SIMATIC OPC Server
WARNING In the case of blocking, manual dumps of the processes “PdlRt.exe” and “script.exe” must be made before restarting the computer. More information on generating manual dumps is available in our Entry ID: http://support.automation.siemens.com/WW/view/en/45020870
Note Using the User Mode Process described does not affect the normal operation of the software and hardware. However, when using a dump event, might lead to temporary loss of performance and changes to the system timing.
2 Configuration of Diagnostics
16 Extended Diagnostics in PCS 7and WinCC Plants
V 2.5.1 Entry ID: 48698507
2.3 Script Diagnostics (APDIAG)
The instructions below are for installing and using “ApDiag.exe” in WinCC and PCS 7.
After activation, in the event of an error the diagnostics data is stored in a file via a default function of WinCC.
Table 2-5
No. Procedure
1. Open “Apdiag.exe” in the “..\Siemens\WinCC\Utools” folder.
2. In the menu bar click “Diagnostics”, and then in the drop-down menu click “Start”. Enable the option “Start automatically with start of WinCC” and then select “LEVEL_3”. In this way diagnostics is started each time you open a project.
Close the window with “OK”.
2 Configuration of Diagnostics
Extended Diagnostics in PCS 7and WinCC Plants V 2.5.1, Entry ID:48698507 17
3. In the menu bar you click “Diagnostics”, and then in the drop-down menu click “OnFile”.
Make the settings as below.
With the “OnErrorExecute -> Error in File” parameter you set that the output of an OnErrorExecute is made in the “OnErrorN.txt “ file in the “..\Siemens\WinCC\Diagnose” directory. Close the window with “OK”.
2 Configuration of Diagnostics
18 Extended Diagnostics in PCS 7and WinCC Plants
V 2.5.1 Entry ID: 48698507
2.4 Windows Performance Monitor
The instructions below are for installing and using the Performance Monitor in WinCC and PCS 7.
After activation, a performance log is stored continuously.
Here, the storage, handle and CPU time of the performance indicators defined in the templates “DiagAllCountersClient.htm” and “DiagAllCountersServer.htm” are used.
The incorporation of the “CPUPeakCheck.htm” template generates an event entry when the CPU load of 95% is exceeded.
Table 2-6
No. Action Remark
1. Start the Performance Monitor with Start > Run… . Enter “perfmon” and start the procedure with OK.
2. Open the menu item “New Log Settings From…”in the “Counter Logs” submenu.
Use the appropriate templates (*.htm files) for the log settings in Table 1-2 .
3.
2 Configuration of Diagnostics
Extended Diagnostics in PCS 7and WinCC Plants V 2.5.1, Entry ID:48698507 19
No. Action Remark
4. Select the profile concerned from the prepared templates in accordance with the type of computer. “DiagAllCountersClient.htm” for a WinCC client. “DiagAllCountersServer.htm” for a WinCC server.
Close the dialog box with “Open”.
5. Accept the specified name for the setting.
Confirm the entry with “OK”.
DiagAllCountersServer DiagAllCountersClient
2 Configuration of Diagnostics
20 Extended Diagnostics in PCS 7and WinCC Plants
V 2.5.1 Entry ID: 48698507
No. Action Remark
The import makes the basic settings below. Storage path for the log file: “D:\Siemens\Diagnostics\DiagAllCountersServermmddmmhh.blg
The log files are acquired by the SIMATIC Diagnose Tool from this predefined storage path.
6.
Tab: “General”
2 Configuration of Diagnostics
Extended Diagnostics in PCS 7and WinCC Plants V 2.5.1, Entry ID:48698507 21
No. Action Remark
Tab: “Log Files”
7. In the “Configure Log Files” dialog the limit of the log files is set to “1024 MB”.
Click “OK” to close the settings.
2 Configuration of Diagnostics
22 Extended Diagnostics in PCS 7and WinCC Plants
V 2.5.1 Entry ID: 48698507
No. Action Remark
8. In the “Schedule” tab the “Start log” time is to be set in the past and the “Stop log” time is to be set in the future.
Click “OK” to close the settings.
9. The performance log is started automatically. The icon changes to green.
2 Configuration of Diagnostics
Extended Diagnostics in PCS 7and WinCC Plants V 2.5.1, Entry ID:48698507 23
Event log entries
How to parameterize the settings of an event log entry is described below.
Table 2-7
No. Action Remark
1. Open the menu item “New Alert Settings From…” in the “Alerts” submenu.
2. Open the menu item “New Alert Settings From…”.
Use the template “CPUPeakCheck.htm” for the log settings in Table 1-2.
3. Accept the specified name for the setting.
Confirm the entry with “OK”.
CPUPeakCheck
2 Configuration of Diagnostics
24 Extended Diagnostics in PCS 7and WinCC Plants
V 2.5.1 Entry ID: 48698507
No. Action Remark
4. Accept the settings with “OK”.
5. The alarm configuration starts automatically, the icon changes to green.
The icon changes to green.
6. Close the Performance Monitor.
2 Configuration of Diagnostics
Extended Diagnostics in PCS 7and WinCC Plants V 2.5.1, Entry ID:48698507 25
WARNING The performance log and the alarm configuration are restarted automatically when the PC is restarted. A new log file is created. Note that this occupies additional hard disk space. You can delete log files that are no longer needed in “D:\Siemens\Diagnostics”. If you terminate the performance log or alarm configuration manually with the “STOP” button, the preset times for logging are set to “Manual”. Then you must the times again as in Table 2-6 No. 8, otherwise the logging is not restarted automatically.
2 Configuration of Diagnostics
26 Extended Diagnostics in PCS 7and WinCC Plants
V 2.5.1 Entry ID: 48698507
2.5 SIMATIC Batch Trace
The instructions below are for installing and using SIMATIC Batch Trace in WinCC and PCS 7 with the SIMATIC Batch option.
Depending on the installation, the “Trace Configuration Editor” is in one of the program paths below.
..\Program Files\CommonFiles\SIEMENS\bin
..\Program Files\SIEMENS\Common\bin
Table 2-8
No. Action Remark
In the Windows Explorer double-click “pcs7commontracecontrolx.exe” to start the Trace Configuration Editor.
The Trace Control Panel opens. 1.
2 Configuration of Diagnostics
Extended Diagnostics in PCS 7and WinCC Plants V 2.5.1, Entry ID:48698507 27
No. Action Remark
Activate “Enable Log” and click “Switches…”. The Trace Configuration Editor opens. 2.
Select the “API – Batch Api” item >> right-click >> “Modify Selection (recursive)”.
Now the Trace Source Settings box opens.
3.
2 Configuration of Diagnostics
28 Extended Diagnostics in PCS 7and WinCC Plants
V 2.5.1 Entry ID: 48698507
No. Action Remark
Activate the option “Enable, E, W, I, C, D”. Close the dialog with “OK”.
4.
Save the settings in the Trace Configurator with “Store”. Acknowledge the message with “OK”.
5.
2 Configuration of Diagnostics
Extended Diagnostics in PCS 7and WinCC Plants V 2.5.1, Entry ID:48698507 29
No. Action Remark
6. Close the Trace Control Panel with “OK”.
7.
3 Tools
30 Extended Diagnostics in PCS 7and WinCC Plants
V 2.5.1 Entry ID: 48698507
3 Tools The archiving tool presented here is to be stored on the PC and so that it can be activated as required.
3.1 SIMATIC Diagnostics Tool
3.1.1 Install the SIMATIC Diagnostics Tool
Below we describe how to install the SIMATIC Diagnostics Tool on your Engineering Station or on the target computer.
The latest version of the SIMATIC Diagnostic Tool is available at this link:
http://support.automation.siemens.com/WW/view/en/44029135
The SIMATIC Diagnostics Tool “Edition 2010” is available on the DVD SIMATIC PCS 7 V7.1 incl. SP2 ..\Additional_Products\SDT_2010_1\
Table 3-1
No. Procedure
1. Copy the Zip archive “SDT_2010_1.zip” to you Engineering Station or target computer and unpack the archive on you drive in this path: “..\Program Files\Siemens\WinCC\uTools”. For this use the password: “12345678”.
2. Copy all the xml files supplied with this diagnostics concept into the directory created: “..\Program Files\Siemens\WinCC\uTools\SDT_2010_1\bin”
3. Download the “PsTools” (PsExec) from the Microsoft internet site at:
http://technet.microsoft.com/en-us/sysinternals/bb897553.aspx
and copy it into this subfolder: “..\Program Files\Siemens\WinCC\uTools\SDT_2010_1\bin”
4. Unpack the Zip archive “PSTools.zip” on your in drive in this path: “..\Program Files\Siemens\WinCC\uTools\SDT_2010_1\bin”
5. Download the “User Mode Process Dumper “ tool from the Microsoft internet site. Link: User Mode Process Dumper Version 8.1 and unpack the User Dump tool in “C:\kktools\userdump8.1”.
3 Tools
Extended Diagnostics in PCS 7and WinCC Plants V 2.5.1, Entry ID:48698507 31
3.1.2 Configure the SIMATIC Diagnostics Tool Locally
The instructions below are for installing and using the SIMATIC Diagnostics Tool in WinCC and PCS 7.
Installation and acquisition of data are performed locally on a single system.
Figure 3-1
3 Tools
32 Extended Diagnostics in PCS 7and WinCC Plants
V 2.5.1 Entry ID: 48698507
Table 3-2
No. Procedure
1. Start the “Settings Manager” by double-clicking “SettingsManager.exe” in “..\Program Files\Siemens\WinCC\uTools\SDT_2010_1”
2. Click the “Open File” button to open the profile supplied: “local.xml”.
3. Under “Computer Usage” you select an appropriate designation or enter a designation of your choice.
3 Tools
Extended Diagnostics in PCS 7and WinCC Plants V 2.5.1, Entry ID:48698507 33
No. Procedure
Specify a storage path for the diagnostics data. This is preset as “D:\Siemens\”.
Large volumes of data might be involved depending on the configuration. Therefore you should select a drive with enough free memory.
4.
5. Save the configuration with a new file name (plant designation) via File -> Save File As.
6. Then quit the “Settings Manager” with the Exit button.
This completes the configuration for acquiring all the local diagnostics data.
3 Tools
34 Extended Diagnostics in PCS 7and WinCC Plants
V 2.5.1 Entry ID: 48698507
3.1.3 Configure the SIMATIC Diagnostics Tool Centrally
The instructions below are for installing and using the SIMATIC Diagnostics Tool in WinCC and PCS 7 in distributed systems. Installation and acquisition of data are performed remotely via an Engineering Station, for example.
When diagnostics data is acquired via remote access, existing mechanisms for protecting against unauthorized access remain on the PCs.
Abbildung 3-2
Requirements
In order for the “SIMATIC Diagnostics Tool” to be able to acquire data from target computers in the network, specific requirements must be fulfilled on the target computers.
Standard release of C:\ is activated: C$
Administrative account is known: User + Password
Target computer is accessible: “Start” > “Run…” > “ping computer name”
3 Tools
Extended Diagnostics in PCS 7and WinCC Plants V 2.5.1, Entry ID:48698507 35
Table 3-3
No. Procedure
1. Start the “Settings Manager” by double-clicking “SettingsManager.exe” in “..\Program Files\Siemens\WinCC\uTools\SDT_2010_1”
2. Click the “Open File” button to open the profile supplied: “remote.xml”.
3 Tools
36 Extended Diagnostics in PCS 7and WinCC Plants
V 2.5.1 Entry ID: 48698507
No. Procedure
3. Add the data of the target computer under “Manage Computer Profiles”. Under “Computer Usage” you select an appropriate designation or enter a designation of your choice.
Specify a storage path for the diagnostics data. This is preset as “D:\Siemens\”.
Large volumes of data might be involved depending on the configuration. Therefore you should select a drive with enough free memory.
4.
5. Use Profile -> Copy Profile to copy the configure profile.
3 Tools
Extended Diagnostics in PCS 7and WinCC Plants V 2.5.1, Entry ID:48698507 37
No. Procedure
6. Add the data of the target computer under “Manage Computer Profiles”. Under “Computer Usage” you select an appropriate designation or enter a designation of your choice.
7. Copy and create a new profile for each target computer as in Steps 5 and 6.
8. Save the configuration with a new file name (plant designation) via File -> Save File As.
3 Tools
38 Extended Diagnostics in PCS 7and WinCC Plants
V 2.5.1 Entry ID: 48698507
No. Procedure
9. Then quit the “Settings Manager” with the Exit button.
This completes the configuration for acquiring all the remote diagnostics data.
4 Archiving the Diagnostics
Extended Diagnostics in PCS 7and WinCC Plants V 2.5.1, Entry ID:48698507 39
4 Archiving the Diagnostics
4.1 Acquisition of Local Diagnostics Data
Below we describe how to use the SIMATIC Diagnostics Tool to acquire data. Data acquisition can be done locally on a single system.
Table 4-1
No. Procedure
1. Start the “SIMATIC Diagnostics Tool” by double-clicking “SimaticDiagnosticsTool.exe” in “..\Program Files\Siemens\WinCC\uTools\SDT_2010_1”
2. Use the “Open File” button to download the configuration created in Chapter 3.
3. Click the “Get Information” button to start acquiring all the configured data.
The acquisition procedure starts and the status is displayed.
4 Archiving the Diagnostics
40 Extended Diagnostics in PCS 7and WinCC Plants
V 2.5.1 Entry ID: 48698507
No. Procedure
4. The message below indicates that the acquisition procedure has been completed successfully.
5. The data packets are located in the storage path “D:\Siemens\”.
5 Literature
Extended Diagnostics in PCS 7and WinCC Plants V 2.5.1, Entry ID:48698507 41
5 Literature
5.1 Bibliography
This list is by no means complete and is only a selection of relevant literature.
Table 5-1
Subject area Title
/1/ PCS 7 Diagnostics
SIMATIC Process Control System PCS 7 V7.0 PCS 7 – Service Support and Diagnostics
/2/
5.2 Internet Links
This list is by no means complete and is only a selection of relevant information.
Table 5-2
Subject area Title
\1\ Reference to entry
http://support.automation.siemens.com/WW/view/en/22089969
http://support.automation.siemens.com/WW/view/en/23486418
\2\ Siemens Customer Support
http://support.automation.siemens.com
\3\ SIMATIC Diagnostics Tool
http://support.automation.siemens.com/WW/view/en/44029135
6 History
42 Extended Diagnostics in PCS 7and WinCC Plants
V 2.5.1 Entry ID: 48698507
6 History
6.1 Version Overview
Table 6-1
Version Date Change
V2.0 07.12.2010 Second edition
V2.1 19.01.2011 Maintenance in compliance with system test
V2.2 28.01.2011 Inclusion of review comments
V2.3 01.02.2011 Section 2.2.1 changed
V2.4 01.04.2011 Redundancy Control removed
V2.5 15.04.2011 Chapter 2.2.1 added with link on entry 45020870
V2.5.1 25.05.2011 English screenshots added .NET component deselected for the SIMATIC Diagnose Toolxml profiles changed