EIGERFLEX ® -Cold water pipe Description CPE 4.0 01.09.2006 4.0 Table of contents 4.1 System description 4.100 System description DN 20-100, Ø Carrier pipe 25-110 mm 4.110 EIGERFLEX ® pipe DN 20-40, Ø Carrier pipe 25-50 mm 4.115 EIGERFLEX ® pipe DN 50-100, Ø Carrier pipe 63-110 mm Structure, dimensions, weights and supplied lengths 4.2 Planning, design engineering 4.200 Pressure loss 4.205 Heat losses 4.210 Connection to end of frost protection strip 4.215 Sleeve joint – frost protection strip 4.220 T-piece-frost protection strip 4.3 Components 4.300 Joint sleeve Fitting the T-piece 4.310 Insulating material 4.320 Screwed PE joint PE T-piece 4.330 End cap 4.340 Wall sealing ring Pipe warning tape 4.345 Wall sealing ring 4.5 Underground construction work, assembly 4.500 Trench dimensions Pipe entry into buildings Openings in walls

Upload: others

Post on 24-Jul-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Description · EIGERFLEX®-Cold water pipe Description CPE 4.0 01.09.2006 4.0 Table of contents 4.1 System description 4.100 System description DN 20-100, Ø Carrier pipe 25-110 mm

EIGERFLEX®-Cold water pipe

Description

CPE

4.0

01.09.2006

4.0 Table of contents

4.1 System description

4.100 System description DN 20-100, Ø Carrier pipe 25-110 mm4.110 EIGERFLEX® pipe DN 20-40, Ø Carrier pipe 25-50 mm4.115 EIGERFLEX® pipe DN 50-100, Ø Carrier pipe 63-110 mm

Structure, dimensions, weights and supplied lengths

4.2 Planning, design engineering

4.200 Pressure loss4.205 Heat losses4.210 Connection to end of frost protection strip4.215 Sleeve joint – frost protection strip4.220 T-piece-frost protection strip

4.3 Components

4.300 Joint sleeve Fitting the T-piece

4.310 Insulating material4.320 Screwed PE joint

PE T-piece4.330 End cap4.340 Wall sealing ring

Pipe warning tape4.345 Wall sealing ring

4.5 Underground construction work, assembly

4.500 Trench dimensionsPipe entry into buildingsOpenings in walls

Page 2: Description · EIGERFLEX®-Cold water pipe Description CPE 4.0 01.09.2006 4.0 Table of contents 4.1 System description 4.100 System description DN 20-100, Ø Carrier pipe 25-110 mm

EIGERFLEX®-Cold water pipe

System descriptionFlexible pipe system with frost

protection strip

CPE

4.100

01.09.2006

1. Medium pipe

Material: Polyethylene class PE100 with high density, to DIN EN ISO 12162Life expectancy: 50 years at 20 °C (16 bar) resp. 30 °C (13.5 bar) acc. DIN 8074 (SF 1.25)Characteristics: Suitable for cold water and sewage/waste water pipes

3. Heat insulation

Material: CFC-free, 100% CO2 -driven polyurethane foam (PUR)

PE100 medium pipe

DensityHeat conductivityUltimate tensile strength (tearing resistance)Modulus of elasticityLinear expansion coefficientCrystallite melting range

Ref.

temperature °C

–40-46

202020–

Value

952-9600.43

321000

1.8 · 10 E-4130-135

kg/m3

W/mKN/mm3

N/mm3

1/K°C

Test standard

DIN 53479DIN 52612DIN 53455DIN 53457DIN 52328

PUR-insulation

DensityHeat conductivityClosed cellular structureWater absorption after 24 hrs.

Ref.

temperature °C

–50––

Value

> 60≤ 0.032

≥ 90≤ 10

kg/m3

W/mK%%

Test standard

DIN 53420DIN 52612

–EN 253

4. Enveloppe de protection

Material: Linear polyethylene of low density (LLD-PE), seamless extrudedPurpose: Protection against mechanical effects and moisture

LLD-PE-protective casing

DensityHeat conductivity Crystallite melting range

Ref.

temperature °C

–––

Value

918-9220.33122

kg/m3

W/mK°C

Test standard

ISO 1183DIN 52612

ISO 11357-3

Frost protection strip,

selfregulating power output

DimensionsMinimum bending radiusOperating voltageMax. operating temperature poweredMax. operating temperature unpoweredMax. heating circuit length:

Power delivery (W/m at 10∞C)

25-50 mm

Power delivery 11 W/m

Width 7.7 mm, Thickness 5.3 mm20 mm230 V AC 50 HzContinuous operation 65 °C, short periods 85 °C, to -30°C128 m / 16 A bei 10 °C100 m / 10 A bei 10 °C11 W/m

To protect people and equipment, we basically specify a 30 mA residual

current-operated device (FI).

63-110 mm

Power delivery 18 W/m

Width 7.7 mm, Thickness 5.3 mm20 mm230 V AC 50 HzContinuous operation 65 °C, short periods 85 °C, to -30°C102 m / 16 A bei 10 °C60 m / 10 A bei 10 °C18 W/m

2. Frost protection strip

Material:

Outer casing

Screened protective braidingInsulation

Conductive heating elementCopper conductor

Page 3: Description · EIGERFLEX®-Cold water pipe Description CPE 4.0 01.09.2006 4.0 Table of contents 4.1 System description 4.100 System description DN 20-100, Ø Carrier pipe 25-110 mm

EIGERFLEX®-Cold water pipe

EIGERFLEX®-PipeDN20 - DN40

with frost protection strip

CPE

4.110

01.09.2006

s1

d

D

s

LLD-PE casing, corrugated

PE-Foil

PUR-Foam

Aluminium foil,50 mm wide

Frost protectionstrip, 11 W/m

Aluminium foil,50 mm wide

PE Medium pipe

Frost protection strip:Power delivery 11 W/m

EIGERFLEX®-Pipe

type DN Inches

[“]

Carrier pipe

d x s

mm

Out. casing

D x s1

mm

Min. bendingradius

m

Capacity

l/m

Weight

kg/m

max. delivery length

Jumbo-Coil Maxi-Coil

m m

25/7632/7640/9150/91

20

25

32

40

3/4"1"11/4"11/2"

25 x 2.332 x 2.940 x 3.750 x 4.6

78 x 2.078 x 2.093 x 2.293 x 2.2

0.70.70.80.8

0.3270.5390.8351.307

0.901.001.391.54

On request:

- Special dimensions as of 500 m and exceeding on request.

- Larger lengths on request.

- Ring dimensions: Jumbo Coil with outer diameter 2800 mm x 800 mm (width)

Maxi Coil with outer diameter 2800 mm x 1200 mm (width)

760760560560

520520377377

Page 4: Description · EIGERFLEX®-Cold water pipe Description CPE 4.0 01.09.2006 4.0 Table of contents 4.1 System description 4.100 System description DN 20-100, Ø Carrier pipe 25-110 mm

EIGERFLEX®-Cold water pipe

EIGERFLEX®-PipeDN50 - DN100

with frost protection strip in channel

CPE

4.115

01.09.2006

s1

d D

s

LLD-PE casing, corrugated

PE-Foil

PUR-Foam

Aluminium foil,102 mm wide

Frost protectionstrip, 17 W/m

Aluminium foil,102 mm wide

Plastic channel

PE Medium pipe

EIGERFLEX

Frost protection strip channel

Frost protection strip:Power delivery 18 W/m

18

8

EIGERFLEX®-Pipe

Type DN Inches

[“]

Carrier pipe

d x s

mm

Out. casing

D x s1

mm

Min. bendingradius

m

Capacity

l/m

Weight

kg/m

max. delivery length

Jumbo-Coil Maxi-Coil

m m

63/12675/12690/162110/162

50

65

80

100

2"21/2"3"4"

63 x 5.875 x 6.890 x 8.2

110 x 10.0

128 x 2.7128 x 2.7163 x 3.2163 x 3.2

1.01.01.21.2

2.0912.9614.2546.362

2.602.754.565.69

192 280192 28092 14492 144

On request:

- Special dimensions as of 500 m and exceeding on request.

- Larger lengths on request.

- Ring dimensions: Jumbo Coil with outer diameter 2800 mm x 800 mm (width)

Maxi Coil with outer diameter 2800 mm x 1200 mm (width)

Page 5: Description · EIGERFLEX®-Cold water pipe Description CPE 4.0 01.09.2006 4.0 Table of contents 4.1 System description 4.100 System description DN 20-100, Ø Carrier pipe 25-110 mm

EIGERFLEX®-Cold water pipe

Pressure loss

CPE

4.200

01.09.2006

Water temperature 20 °C

Roughness ε = 0.01 mm (PE100)(1 mmWS = 9.81 Pa)

110/90

(DN 100)

90/73

(DN 80)

75/61.4

(DN 65)

163/51.4

(DN 50)

50/40.8

(DN 40)

40/32.6

(DN 32)

32/26.2

(DN 25)

25/20.4

(DN 20)

2.0

m/s

3.0

m/s

1.5

m/s1

.0 m

/s0.7

5m

/s0.5

m/s

0.4

m/s

0.3

m/s

Water speed

Flo

w in m

[kg/h

]

Pressure loss p [Pa/m]

20300

500

1000

2000

3000

5000

4000

10000

20000

30000

40000

30

40

50

80

100

120

140

160

180

1200

1400

1600

1800

200

300

400

500

600

1000

2000

Page 6: Description · EIGERFLEX®-Cold water pipe Description CPE 4.0 01.09.2006 4.0 Table of contents 4.1 System description 4.100 System description DN 20-100, Ø Carrier pipe 25-110 mm

EIGERFLEX®-Cold water pipe

Heat losses

CPE

4.205

01.09.2006

Heat losses at different external temperatures or surface temperatures of thecasing pipe.

The frost protection strip can no longer compensate for a heat loss of more than 10 W/m, and there is a danger of freezing.

If the pipes are laid underground (covered height of0.6 m), the heat losses are reduced by at least 20%.

Tmed = 2 °C

surface temperatures

surface temperature of the

outher casing[°C]

25/76 32/76 40/91

EIGERFLEX® Pipe-dimensions

q W/m Medium temperature: 2°C

50/91 63/126 75/126 90/162 110/162

-1

-2

-3

-4

-5

-6

-7

-8

-9

-10

-11

-12

-13

-14

-15

-16

-17

-18

-19

-20

-21

-22

-23

-24

-25

-26

-27

-28

-29

-30

-31

-32

-33

-34

-35

-36

-37

-38

-39

-40

0.60.81.01.11.31.51.71.92.12.32.52.72.93.03.23.43.63.84.04.24.44.64.84.95.15.35.55.75.96.16.36.56.76.87.07.27.47.67.88.0

0.71.01.21.41.71.92.22.42.62.93.13.43.63.84.14.34.64.85.05.35.55.86.06.26.56.77.07.27.47.77.98.28.48.68.99.19.49.69.810.1

0.81.01.31.61.82.12.32.62.93.13.43.63.94.24.44.74.95.25.55.76.06.26.56.87.07.37.57.88.18.38.68.89.19.49.69.910.110.410.710.9

1.11.41.82.22.52.93.23.64.04.34.75.05.45.86.16.56.87.27.67.98.38.69.09.49.7

10.110.410.811.211.511.912.212.613.013.313.714.014.414.815.1

0.91.21.61.92.22.52.83.13.43.74.04.34.75.05.35.65.96.26.56.87.17.47.88.18.48.79.09.39.69.910.210.510.911.211.511.812.112.412.713.0

1.21.62.02.52.93.33.74.14.54.95.35.76.16.67.07.47.88.28.69.09.49.810.210.711.111.511.912.312.713.113.513.914.314.815.215.616.016.416.817.2

1.11.41.82.22.52.93.23.64.04.34.75.05.45.86.16.56.87.27.67.98.38.69.09.49.7

10.110.410.811.211.511.912.212.613.013.313.714.014.414.815.1

1.72.22.83.43.94.55.05.66.26.77.37.88.49.09.5

10.110.611.211.812.312.913.414.014.615.115.716.216.817.417.918.519.019.620.220.721.321.822.423.023.5

Page 7: Description · EIGERFLEX®-Cold water pipe Description CPE 4.0 01.09.2006 4.0 Table of contents 4.1 System description 4.100 System description DN 20-100, Ø Carrier pipe 25-110 mm

EIGERFLEX®-Cold water pipe

Connection and endFrost protection strip

CPE

4.210

01.09.2006

1. Technical data

3. Installation procedure

• Electrical installation according to local regulations• Only to be connected by an authorised electrical installer• 30 mA residual current-operated device (FI)-required by regulations!• Automatic fuse, C-characteristic

2. Preparation

35-40 cm

Shorten as described in fittinginstructions

Remove 35-40 cm of insulation at the ends and carefully expose the strip. Then shorten theinner pipe to length according to the fittinginstructions.

4. Installing the temperature sensor on the pipe

EIGERFLEX

Temperature sensor cable

Shrinkdown tube Filling adhesive S1113, 60 mm long Shrinkdown tube

ca. 10 cm

ca. 7 c

m

Temperature sensor

The temperature sensor has to be installed on the medium pipe opposite the heating strip.It must be fitted at the coldest point on the pipe (outside the building). For this purpose,cut open a 10x7 cm area of the outer casing and peel back, cut out 10x7cm foam, and fixthe temperature sensor on the inner pipe with adhesive tape. Fill the hole with the insula-ting material that is provided: apply filling adhesive S1113 below and above the tempera-ture sensor cable (see sketch), seal with shrinkdown tube.

230 V

Thermostat UTR 15

End closure EA-H

Frost protection strip

Temperature sensor on pipe

Protect the heating strip againstmoisture

Sensor cable length 3 m;

can be extended to a max. of100m with screened cable, 1.5mm

Connection box (provided by the customer)

Connection: Heating strip/cold lead A-H/K

max. 100 m

2

Frostprotecting cable: based on switch-on temperature of 10°C:• 16 A max. 100 m • 10 A max. 80 m

Regulation: Thermostat UTR15• adjustment range: –5°C to +15 °C• pipe contact thermostat

Page 8: Description · EIGERFLEX®-Cold water pipe Description CPE 4.0 01.09.2006 4.0 Table of contents 4.1 System description 4.100 System description DN 20-100, Ø Carrier pipe 25-110 mm

EIGERFLEX®-Cold water pipe

Sleeve jointFrost protection strip

CPE

4.215

01.09.2006

1. Planning

2. Preparation

40 cm Figure 1

Shorten as shown in illustration 2

3. Sleeve joint

15 cm15 cm

Figure 2

SupplyEnd closureEA-H

Connection Frost protection strip/frost protection strip V-H/H

max. 100 m

L ≤ 100 mContinuous joint

Remove 40 cm of insulationat the ends and carefully ex-pose the strip. Then shortenthe inner pipe to length asshown in illustration 2.

Protect heating strip against moisture

Continuous joint

L ≤ 100 m

SeparationL > 100 m

Connection Frost protection strip/frost protection strip V-H/H

30 cm

Screwed joint or welded sleeve

30 cm

30 cm

End closure EA-H

max. 100 m max. 100 m

L > 100 mSeparation

Supply Supply

• seal with sleeve set, see CPE 4.300 + CPE 4.310• connect the cables according to the installation instructions

Page 9: Description · EIGERFLEX®-Cold water pipe Description CPE 4.0 01.09.2006 4.0 Table of contents 4.1 System description 4.100 System description DN 20-100, Ø Carrier pipe 25-110 mm

EIGERFLEX®-Cold water pipe

T-pieceFrost protection strip

CPE

4.220

01.09.2006

1. Planning

2. Preparation

3. Fitting T-piece with T-junction

Screwed T-piece or electro welded T

T-Piece Micro Uni Clip MUC

End closureEA-H

T-piece Micro Uni Clip MUC

End closureEA-H

End closure EA-H

Connection V-H/H

End closureEA-H

L 100 m

Connection V-H/H

End closure EA-H

L 100 m

Supply (usingconnection A-H/K)

Supply (usingconnection A-H/K)

Example 1: total lenght ≤ 100 m

Example 3: total lenght > 100 m

Example 2: total lenght ≤ 100 m

Supply (usingconnection A-H/K)

Protect heating strip against moisture

Remove 50 cm of insulation at the ends and carefullyexpose the strip. Then shorten the inner pipe to lengthaccording to the fitting instructions.

30 cm

At the T-junction, make sure that the sum of the connected pipes is not more then 100 m

Page 10: Description · EIGERFLEX®-Cold water pipe Description CPE 4.0 01.09.2006 4.0 Table of contents 4.1 System description 4.100 System description DN 20-100, Ø Carrier pipe 25-110 mm

EIGERFLEX®-Cold water pipe

Joint sleeveFitting the T-piece

CPE

4.300

01.09.2006

Joint sleeved1

d2

1 2 3 4

Fitting the T-piece

1 3 2 4 5

max.

49

0 m

m

d1

645 mm

d1

d1

1.PE joint, see sheet CPE 4.3202. Insulation material, see sheet CPE 4.3103.Shrinkdown sleeve pipe4.Shrinkdown tube

d2

7691

126162

76x

91

x

126

x

162

x

d1

Ø d1 Ø d3

25/76-25/7632/76-32/7640/91-40/9140/91-32/7650/91-50/9150/91-40/9163/126-63/12663/126-50/9175/126-75/12675/126-63/12690/162-90/16290/162-75/126110/162-110/162110/162- 90/162

25/76x

x

x

x

x

x

x

x

x

x

x

x

x

x

32/76

x

x

x

x

x

x

x

x

x

x

x

x

x

40/91

x

x

x

x

x

x

x

x

x

x

x

50/91

x

x

x

x

x

x

x

x

x

x

Junction, Ø d2

63/126

x

x

x

x

x

x

x

75/126

x

x

x

x

x

90/162

x

x

x

110/162

x

1.T-piece, see sheet CPE 4.320

2.GFK half-shells3. Insulating material,

see sheet CPE 4.3104.Reducer ring5.Special sealing compound

all Ø dimensions in mm

Page 11: Description · EIGERFLEX®-Cold water pipe Description CPE 4.0 01.09.2006 4.0 Table of contents 4.1 System description 4.100 System description DN 20-100, Ø Carrier pipe 25-110 mm

EIGERFLEX®-Cold water pipe

Insulation materialPE-foam hose, PUR-foam pack

CPE

4.310

01.09.2006

PUR-foam package for T-piece sets and sockets

The required volume of polyurethane foam is supplied in the appropriate fo-am packing sizes for the various sockets and T-pieces. The clip (splitting thecomponents) must be removed by pulling it away. The two components aremixed together by shacking.

PUR-foam bagCO2-blown, CFC-free PUR-Foam

Security requirement for thefoam insulation

plastic gloves

eye protection

Sockets

Polyethylene foam hose Pipe-extruded insulation of closed cell, high-quality polyethylene, ideally suited forinsulating CALPEX sockets. Various insulation coating thicknesses for the mostcommon pipe diameters.

The insulating material (thickness and length) is supplied for the relevant socket types.The hoses should be adapted exactly to the sockets on the building site.

Page 12: Description · EIGERFLEX®-Cold water pipe Description CPE 4.0 01.09.2006 4.0 Table of contents 4.1 System description 4.100 System description DN 20-100, Ø Carrier pipe 25-110 mm

EIGERFLEX®-Cold water pipe

ConnectionsCoupler, T-piece

CPE

4.320

01.09.2006

Connection Coupling Material: brass all dimensions in mm

L

Ø75

Ø90

L

Screwed PE T-piece Material: brass all dimensions in mm

Ø75

Ø90

d2

d2

d1

d1

d3

d3

Alternative types of joint

L

Ø75

Ø90

L

Ø d1 Ø d3

25 x 2.3-25 x 2.3

32 x 2.9-32 x 2.9

40 x 3.7-40 x 3.7

40 x 3.7-32 x 2.9

50 x 4.6-50 x 4.6

50 x 4.6-40 x 3.7

63 x 5.8-63 x 5.8

63 x 5.8-50 x 4.6

75 x 6.8-75 x 6.8

75 x 6.8-63 x 5.8

90 x 8.2-90 x 8.2

90 x 8.2-75 x 6.8

110x10.0 -110x10.0

110 x10.0-90 x 8.2

Junction, Ø d2

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

25 x

2.3

32 x

2.9

40 x

3.7

50 x

4.6

63 x

5.8

75 x

6.8

90 x

8.2

110

x 10

Electro-welded PE sleeve Alternative types of joint (not held in stock)

• Electro-welded PE sleeve• Electro-welded T, PE-T with

welded sleeve• Pipe coupling Straub or Norma

PE pipe coupling

PE-Pipe

25 x 2.332 x 2.940 x 3.750 x 4.663 x 5.875 x 6.890 x 8.2

110 x 10.0

type

25 x 2.3-3/4“32 x 2.9-1“

40 x 3.7-11/4“50 x 4.6-11/2“

63 x 5.7-2“75 x 6.8-21/2“

90 x 8.2-3“110 x 10.0-4“

L

53636771809292102

type

25 x 2.332 x 2.940 x 3.750 x 4.663 x 5.875 x 6.890 x 8.2

110 x 10.0

L

606771758189130130

Page 13: Description · EIGERFLEX®-Cold water pipe Description CPE 4.0 01.09.2006 4.0 Table of contents 4.1 System description 4.100 System description DN 20-100, Ø Carrier pipe 25-110 mm

EIGERFLEX®-Cold water pipe

End cap

CPE

4.330

01.09.2006

Heat shrinkable end cap

Frost protection strip

Data table

Type

25/7632/7640/9150/9163/12675/12690/162110/162

Shrink end cap

6103161031610318630086326863266099963340

• The end cap is shrunk on by applying a gas flame or hot airjet• Within dry rooms its application is not absolutely necessary.

EIGERFLEX®

Page 14: Description · EIGERFLEX®-Cold water pipe Description CPE 4.0 01.09.2006 4.0 Table of contents 4.1 System description 4.100 System description DN 20-100, Ø Carrier pipe 25-110 mm

EIGERFLEX®-Cold water pipe

Wall sealing ring Pipe warning tape

CPE

4.340

01.09.2006

50

DDa

ACHTUNG !

FERNWÄRM

ELEITUNG

Wall sealing ring

Pipe warning tape

EIGERFLEX®

Type CPE

32/76, 25/7640/9150/9163/12675/12690/162110/162

Da118133133168168203203

Outher casing pipeD

789393128128163163

• tape for laying under ground.• standard length: 250 m• laying depth; see page CPE 4.500

Page 15: Description · EIGERFLEX®-Cold water pipe Description CPE 4.0 01.09.2006 4.0 Table of contents 4.1 System description 4.100 System description DN 20-100, Ø Carrier pipe 25-110 mm

EIGERFLEX®-Cold water pipe

Wall ductCore drilling

CPE

4.345

01.09.2006

DR

1

Exte

rnal

Cellar/

sh

aft

(In

tern

al)

3

4

DR

1

Cellar/

sh

aft

(In

tern

al)

Exte

rnal

2

4

3

Standard sealing ring Centering ring (as a additional)

Caption:

1. EIGERFLEX®-cold water pipe

2. single sealing, large 1 x 40 mm

3. double sealing, large 2 x 40 mm,Hardness 35

4. Pipe liner made of fibre cement orcoated core drill hole

* Suitability against pressurised water

Core drill holes

Prerequisites for installation are perfect drill holes.Since hairline cracks can exist in concrete or canarise as a result of the work, we recommendsealing the drill hole walls over the entire lengthswith a sealant (e. g. AQUAGARD).

We cannot guarantee a good seal if theserecommendations are not observed.

R

Outer diameterEIGERFLEX®

Ø mm 7691111126142162182

D

Pipe linerCore drill hole

Ø mm 150150200200250250300

Ø D internal, mm7893113128143163183

Sealing ring dimension

Ø D external, mm150150200200250250300

Page 16: Description · EIGERFLEX®-Cold water pipe Description CPE 4.0 01.09.2006 4.0 Table of contents 4.1 System description 4.100 System description DN 20-100, Ø Carrier pipe 25-110 mm

EIGERFLEX®-Cold water pipe

Trench dimensionsBuilding entry

CPE

4.500

01.09.2006

Trench section, 1 CPE pipe

Building entry

80 80DA

A

D

1 2 3

D

B

T

10

Measures (cm)

10D

1030

min

60

10

1. Pipe warning tape; see page CPE 4.3402. Excavated material3. Sand washed, grain size 0-3/4 mm

SLW 30 = 50 kN wheel load, resp. 300 kNtotal load according to DIN 1072. Forbigger loads (i.e. SLW 60) a load distribu-tion superstructure according RStO75 isrequired.Without traffic load the minimum coveringhight may be reduced by 20 cm.

Covering hight maximum covering hight: 2.6 mThe higher covering needs our according.

Outhercasing

Ø D mm7693113128143163

min. bendingradius

m0.70.80.91.01.11.2

LargeB

cm253030353535

Depthcm80808585859090

ca 80 mm

60 mm 80 mm

PE-connecting piece, see page CPE 4.320

End cap; see page CPE 4.330 Wall sealing ring, see page CPE 4.340

Pipe, see page CPE 4.110

D

Wall breakthrough Breakthrough boredOuthercasing

Ø D mm

78

93

113

128

163

Amm

240

250

270

290

320

Outhercasing

Ø D mm

78

93

113

128

163

Dmm

180

200

220

240

280