characteristics of different techniques: fact & fiction · frank angelini cutler-hammer power...

8
1 Eaton Corporation Eaton Presentation On Power System Grounding – Generator Grounding - Winding Pitch Factors, Hybrid Grounding IEEE Nashville Date: February 3, 2015 Characteristics of Different Power System Grounding techniques: Fact & Fiction By David Shipp Cutler-Hammer Frank Angelini Cutler-Hammer Power System Grounding Abstract Most Misunderstood Element of Power System design Introduction • History Solidly Grounded • Ungrounded Present Practice Industrial / Commercial NEC Art. 250-1 Scope Grounded to Limit Voltages due to; – Lightning – line Surges – Unintentional Contact with Higher Voltages – Stabilize V LG During Normal Operation NEC Article 250-5 • (b) AC Systems 50V-1000V - Shall be Grounded –V LG < 150V – 3 phase/4 wire – 3 phase/4 wire Delta

Upload: others

Post on 05-Sep-2019

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Characteristics of Different techniques: Fact & Fiction · Frank Angelini Cutler-Hammer Power System Grounding Abstract • Most Misunderstood Element of Power System design Introduction

1

Eaton Corporation

Eaton Presentation On Power System Grounding

– Generator Grounding - Winding Pitch Factors,

Hybrid Grounding

IEEE Nashville

Date: February 3, 2015

Characteristics of Different

Power System Grounding

techniques: Fact & Fiction

By

David Shipp Cutler-Hammer

Frank Angelini Cutler-Hammer

Power System Grounding

Abstract

• Most Misunderstood Element of Power

System design

Introduction

• History

• Solidly Grounded

• Ungrounded

Present Practice

• Industrial / Commercial

• NEC Art. 250-1 Scope

• Grounded to Limit Voltages due to;

– Lightning

– line Surges

– Unintentional Contact with Higher Voltages

– Stabilize VLG During Normal Operation

NEC Article 250-5

• (b) AC Systems 50V-1000V - Shall be

Grounded

– VLG < 150V

– 3 phase/4 wire

– 3 phase/4 wire Delta

Page 2: Characteristics of Different techniques: Fact & Fiction · Frank Angelini Cutler-Hammer Power System Grounding Abstract • Most Misunderstood Element of Power System design Introduction

2

NEC Article 250-5

• (b) Continued

– Exception 5 High Impedance Grounded Shall

be Permitted

– Qualified Maintenance Personnel Only

– Service Continuity Required

– VL-N Loads Not Served

NEC Article 250-5

• [c] AC Systems > 1KV

– Where Such Systems Are Grounded, They

Shall Comply With Article 250

Definitions (IEEE “Green Book”)

• Ungrounded System

• Grounded System

• Grounded Solidly

• Resistance Grounded

• Effectively Grounded

What Comprises a Ground

System? Figure 1

Figure 2: Ground Fault on an

Ungrounded System

Figure 3: Voltages During Ground Fault

on an Ungrounded System

Page 3: Characteristics of Different techniques: Fact & Fiction · Frank Angelini Cutler-Hammer Power System Grounding Abstract • Most Misunderstood Element of Power System design Introduction

3

Figure 4: Ground Fault on a

Solidly Grounded System

Figure 5: Voltage Profiles for

Solidly Grounded System

a) No Ground Fault b) Ground Fault

Table I

Solid Grounded vs. Ungrounded S y s t e m G r o u n d e d U n g r o u n d e dV o l t a g e P h a s e A t o P h a s e C 4 8 0 4 8 0

P h a s e A t o P h a s e B 4 8 0 / 3 4 8 0

P h a s e C t o P h a s e B 4 8 0 / 3 4 8 0

P h a s e A t o G r o u n d 4 8 0 / 3 4 8 0

P h a s e B t o G r o u n d 0 0

P h a s e C t o G r o u n d 4 8 0 / 3 4 8 0

F a u l t C u r r e n t - A m p e r e s

P h a s e B 2 9 , 2 0 0 1 . 0 4 P h a s e C 0 . 6 P h a s e A 0 . 6

To Ground the System or Not to

Ground

• VLN Loads Served?

• Service Continuity Importance?

Solidly-Grounded Systems

Figure 6:(Industrial/Commercial)Ungrounded Systems

• Multiple Ground Faults

• Resonant Conditions

• Transient Overvoltages

Page 4: Characteristics of Different techniques: Fact & Fiction · Frank Angelini Cutler-Hammer Power System Grounding Abstract • Most Misunderstood Element of Power System design Introduction

4

Figure 7: Series Resonant CircuitFig. 8: Transient Overvoltage

from Restriking Ground Fault

TVSS Failure Due to Arcing

Ground Fault

MOTOR STARTER

FAILURE DUE TO

ARCING GROUND

FAULT

MOTOR STARTER FAILURE DUE TO ARCING

GROUND FAULT

SWGR TAP BOX FAILURE DUE TO ARCING

GROUND FAULT

Page 5: Characteristics of Different techniques: Fact & Fiction · Frank Angelini Cutler-Hammer Power System Grounding Abstract • Most Misunderstood Element of Power System design Introduction

5

ESP MOTOR FAILURE DUE TO ARCING

GROUND FAULT

ESP MOTOR WYE POINT FAILURE

DUE TO ARCING GROUND FAULT

UNGROUNDED GENERATOR

Arcing Ground Fault – 2 PH to GroundGround Fault on L.C. 81

Ground Fault on L.C. 81 Ground Fault on L.C. 81

Page 6: Characteristics of Different techniques: Fact & Fiction · Frank Angelini Cutler-Hammer Power System Grounding Abstract • Most Misunderstood Element of Power System design Introduction

6

Figure 9

• Inductance

Grounded

Figure 10: Resistance Grounded

• L.R.-200A to 1000A

• H.R.-Less than 10A

Figure 11: Grounding

Transformers

Fig. 12: The Effect of Grounding

Impedance on Transient Overvoltages

Table II

X0 / X1 and R0 / X0 for

Low Transient Overvoltages• Ungrounded

• Solid Grounded

• Reactance Grounded

• No Ratios Available

• Produces High

Vtransients

• X0/X1 Very Low

Unless Wye-Wye

• X0/X1 < 3.0

Table II

X0 / X1 and R0 / X0 for

Low Transient Overvoltages• Low Resistance

Grounded

• High Resistance

• R0/X0 > 2.0

• X0/X1 < 20

• I0R > I0C

Page 7: Characteristics of Different techniques: Fact & Fiction · Frank Angelini Cutler-Hammer Power System Grounding Abstract • Most Misunderstood Element of Power System design Introduction

7

Other Factors

• Mechanical Stress in Generators

• Selective Relaying

• Surge Protection

Table III:System Characteristics

With Various Grounding MethodsUngrounded Essentially solid grounding Reactance

grounding

Ground-fault

neutralizer

Resistance Grounding

Solid Low-value reactor High-value reactor Low

resistance

High

resistance

Current forphase-to-ground faultin percent of

three-phasefault current

Less than 1% Varies, may be100% or greater

Usually designedto produce 60 to100%

5 to 25% Nearly zero faultcurrent

5 to 20% Less than1%

Transientover-voltages

Very high Not excessive Not excessive Very high Not excessive Not excessive Notexcessive

Automaticsegregationof faultedzone

No Yes Yes Yes No Yes No

Lightningarresters

Ungroundedneutral type

Grounded-neutraltype

Grounded-neutraltype if current is60% or greater

Ungroundedneutral type

Ungroundedneutral type

Ungroundedneutral type

Ungrounded neutraltype

Remarks Notrecommendeddue to overvoltages andnonsegregation offault

Generally used on system (1) 600 voltsand below and (2) over 15kV

Not used due toexcessive over-voltages

Best suited forhigh-voltage over-head lines wherefaults may be self-healing

Generally used onindustrial systemsof 2.4 to 15kV

Generallyused onsystems5kV andbelow

Practicable System Grounding

Selections

• L. Voltage (< 1000V)

– Solid

– H. Resistance

• H. Voltage (>15 KV)

– Solid

• M. Voltage

– Solid

• 3 PH / 4 W

• Aerial Lines

• Unshielded Cables

Practicable System Grounding

Selections

• Medium Voltage

– L. Resistance

• Motors / Generators

• Shielded Cables

• No VLN Loads

• Medium Voltage

– H. Resistance

• < 5 KV-No Tripping

• > 5 KV - Tripping

• No VLN Loads

Ground Fault Protection Using

Fuses

52

X1

H1

A B CN

A

B

C

N

Residual Ground Fault Detection

3 Wire

IG

A

B

C

AI

IB

CI

GPPP

Page 8: Characteristics of Different techniques: Fact & Fiction · Frank Angelini Cutler-Hammer Power System Grounding Abstract • Most Misunderstood Element of Power System design Introduction

8

Residual Ground Fault Detection

4 Wire

IG

A

B

C

AI

IB

CI

GPPP

NI

N

Source Neutral Ground Detection

IG

A

B

C

AI

IB

CI

PPP

G

N

NI

Zero Sequence

IG

A

B

C

AI

IB

CI

PPPG

NI

N

H. Resistance / Pulsing Contactor

• NEC Art. 230-95

• L.V. Ground Fault

Protection

Coordination

TX Inrush

1000 KVA

CLE-200E

1000 KVA

DS1200A 510LSG

GRND-A

GRND-B

DS600A RMSLSG

1010 100 1K 10K0.01

0.10

1

10

100

1000

CURRENT IN AMPERES

APPADS.tcc Ref. Voltage: 480 Current Scale X 10^1

TIM

E I

N S

EC

ON

DS

Zone Interlocking

1

ZONE 1

8

9

10

11GFR

M

GFR

9

F111

10

8

GFR

8

10

11F2

9

GFRZONE 2

8

10

11B1

9

8

11

10

B3

GFR

9

GFR11

10

B2

9

8

1

1

TIME DELAY INPUT

COMMON

1

2

3

3

ZONE 3

1

CO

MM

ON

TIM

E D

ELA

Y

INP

UT