chapter 4 experimental investigation -...
TRANSCRIPT
47
CHAPTER 4
EXPERIMENTAL INVESTIGATION
4.1 GENERAL
This chapter discusses the experimental programme, materials used
and the specimens tested in the current research project. The experimental
work conducted in this project is on the seismic behaviour of exterior beam-
column joints under simulated cyclic and reverse cyclic loading. Comparison
of conventional reinforced concrete joint, seismic reinforced joint, steel fibre
reinforced concrete (SFRC) joint and the hybrid fibre reinforced (HFRC)
joints were performed based on the experimental results on seven beam-
column joint units.
The main objective of this study is to investigate the suitable
percentage of hybrid fibre combination (steel and synthetic fibre) which
gives more load carrying capacity, more energy dissipation capacity, more
joint shear stress and ductility factor.
4.2 EXPERIMENTAL PROGRAMME
Experimental works were carried out in three phases. In the first
phase 18 cubes [150 mm x150 mm x150 mm], 18 cylinders [150 mm
diameter and 300mm hieght] and 28 beam-column joint specimens were cast
by using M20 concrete as per Table 4.1. In the second phase 18 cubes,
18 cylinders and 28 beam-column joint specimens were cast by using M25
48
Figure 4.1 Flowchart – Experimental Programme
Studies on Hybrid Fibre Reinforced Beam-Column Joints Under Reverse Cyclic Loading
Experimental Work
Analytical work Using
ABAQUS
M60M25M20
28-BCJ 18-Cubes 12- Cylinders12-Cubes 10-BCJ18- Cylinders
Reverse Cyclic load TestCyclic load Test Compression Test Reverse Cyclic load Test
F.C, 1.5% S.F+0.2% P.F
F.C, 1.5% S.F+0.4% P.F
F.C, 1.5% S.F+0.6% P.F
F.C,1.5% P.F
O.C JointO.C + SeismicDetailing
F.C 1.5% S.F
O.C - Ordinary ConcreteF.C - Fibre ConcreteS.F - Steel FibreP.F - Polypropylene Fibre
B.C.J - Beam-Column Joint
49
concrete as per Table 4.2. In the third phase 12 cubes, 12 cylinders and
10 beam-column joint specimens were cast by using M60 concrete. In first
two phases normal strength concrete was used and in third phase high strength
concrete was used. Figure 4.1 shows the flow chart of the experimental
programme.
In phase I and II seven types of exterior beam-column joints were
cast by using M20 and M25 concrete. All the specimens were designed as per
IS 456:2000. The first specimen was reinforced accordingly, without
considering the seismic requirement. The second specimen was detailed as
per IS 13920:1993 for seismic requirements. The remaining five specimens
were similar to the first one but various combinations of hybrid fibre were
mixed with concrete in the joint region. Out of five fibrous specimens four
specimens were cast by using constant 1.5% of steel fibre and 0 to 0.6% of
polypropylene fibre with an increment of 0.2% by volume fraction. The fifth
fibre reinforced specimen was cast by using only 1.5 % of polypropylene
fibre. Tables 4.1 and 4.2 show the details of specimens cast by using M20 and
M25 concrete.
Table 4.1 Specimens with Various Combinations of Hybrid Fibres in
M20 Concrete
Sl.No
Specimen
Identification
Fibre Volume
Fraction No of
BCJCyclic
Load
Reverse Cyclic
LoadingSteel
Polypro
pylene
1 I O1 I O2 - - 4
2 I S1 I S2 - - 4
3 I F11 I F12 1.5% 0% 4
4 I F21 I F22 1.5% 0.2% 4
5 I F31 I F32 1.5% 0.4% 4
6 I F41 I F42 1.5% 0.6% 4
7 I F51 I F52 - 1.5% 4
50
Table 4.2 Specimens with Various Combinations of Hybrid Fibres in
M25 Concrete
Sl.No
Specimen IdFibre Volume
Fraction No of
BCJCyclic
Load
Reverse Cyclic
LoadingSteel
Polypr
opylene
1 II O1 II O2 - - 4
2 II S1 II S2 - - 4
3 II F11 II F12 1.5% 0% 4
4 II F21 II F22 1.5% 0.2% 4
5 II F31 II F32 1.5% 0.4% 4
6 II F41 II F42 1.5% 0.6% 4
7 II F51 II F52 - 1.5% 4
In phase III five types of exterior beam-column joints were cast
using M60 concrete. All the specimens were designed as per IS 456:2000. The
first specimen was reinforced accordingly, without considering the seismic
requirement. The second specimen was detailed as per IS 13920:1993 for
seismic requirements. The remaining three specimens were similar to the first
one but various combinations of hybrid fibre reinforeced concrete in the joint
region (constant 1.5% of steel fibre and 0 to 0.4 % of polypropylene fibre
with an increment of 0.2% by volume fraction) were used. The details of
specimen cast using M60 concrete is presented in Table 4.3
51
Table 4.3 Specimens with Various Combinations of Hybrid Fibres in
M60 Concrete
Sl.
No
Specimen
Id
Fibre Volume Fraction
No of
BCJSteel Polypropylene
1 III O2 - - 2
2 III S2 - - 2
3 III F12 1.5% 0% 2
4 III F22 1.5% 0.2% 2
5 III F32 1.5% 0.4% 2
4.3 SPECIMEN DETAILS
4.3.1 General
The test sub assemblage is an exterior beam-column joint in the
ground storey of a five storied RC building situated in a place falling under
seismic zone III as per IS 1893: (Part 1 2002). The structure was analysed
using STADD.Pro (2004) software to determine the shear forces, bending
moments and axial forces around the exterior beam-column joint due to
earthquake loading. The specimens were designed as per IS 456-2000. The
second specimen was detailed as per IS 13920: 1993.
4.3.2 Details of Test Specimen and Reinforcement
Test specimen was reduced to a scale (Bayasi 2002) to suit the
loading frame and testing facilities. Original joint design had contained beam
and column sections of 380 mm X 450 mm and 380 mm X 380 mm
respectively. The test specimen joint design includes beam and column with
90 mm X 110 mm and 90 mm X 90 mm respectively. Original joint beam
52
reinforcement at top was 1.52 % and at bottom was 1% of gross area. Original
column reinforcement of the joint is 2.4 %. These percentages of steel
reinforcement ratio were also used for the model. Percentage of reinforcement
of hoops at the joint was 2.13 % and other portion was 1.07 %. Figures 4.2
and 4.3 show seismic joint and ordinary & fibrous joint respectively. For
seismic joint this hoop spacing is 20 mm for a distance of 180 mm (2*db)
(db=effective depth of beam) from the face of the column in the beam and at a
distance of 90 mm (db) from the bottom and top of the beam in the column.
The fibrous joints were cast by using fibre reinforced concrete in the joint
region for a distance of two times effective depth from the face of column on
beam and one time the effective depth from the face of the beam on either
side of the column. The effective cover for main reinforcement is 20 mm.
Figure 4.2 Seismic Detailed Joint
53
Figure 4.3 Fibre Reinforced Joint
4.4 PROPERTIES OF MATERIALS
4.4.1 General
The properties of materials used for preparing the different grades
of (M20, M25 and M60) concrete will be described in the following sections.
The types of concrete being analysed are normal strength concrete, high
strength concrete, steel fibre reinforced concrete and hybrid fibre reinforced
concrete.
4.4.2 Materials Used
Cement, fine aggregate, coarse aggregate, steel fibre, polypropylene
fibre, fly ash, silica fume, superplasticizer and water were used in this
investigation. The following are the properties of the materials used.
54
4.4.2.1 Cement
Ordinary portland cement of grade–53 conforming to Indian
standard IS: 12269-1987 has been used in the present study. The specific
gravity of cement used is 3.15.
4.4.2.2 Fine Aggregate
Sand that is available in nearby locality has been used as fine
aggregate. Other foreign matter present in the sand has been separated before
use. The specific gravity of sand used in this investigation is 2.42.
4.4.2.3 Coarse Aggregate
Crushed stone aggregate of maximum size 10mm available from
local area has been used. Coarse aggregate has been sieved through IS:150-
micron sieve to remove dirt and other foreign materials. The specific gravity
of coarse aggregate used is 2.65.
4.4.2.4 Steel Fibre
For improving the mechanical bond between the fibre and matrix,
indented, crimped, machined and hook ended fibres are normally produced.
The aspect ratio of fibres which have been employed vary from about 30 to
250. Fibres made from mild steel drawn wire conforming to IS: 280-1976
with the diameter of wire varying from 0.3 to 0.5 mm has been practically
used in India. The efficiency of fibre distribution depends on the geometry of
the fibre, the fibre content, the mixing and compaction technique, the size and
shape of the aggregates and the mix proportions. The fibre used in this study
was crimped steel fibre shown in Figure 4.4. As provided by the manufacturer
(Fibre mesh, Product manual, SI Concrete Systems,USA.) the properties of
crimped steel fibre used are given in Table 4.4.
55
Table 4.4 Properties of Fibre
Sl.NoProperties Steel fibre
(Crimped)
Polypropylene
Fibre
1. Length 30 mm 20 mm
2. Diameter 0.50 mm 0.008 mm
3. Aspect ratio 60 2500
4 Specific
Gravity
7.850 0.91
4.4.2.5 Polypropylene Fibre
Table 4.4 shows physical properties of polypropylene fibre used in
this study. Figure 4.4 shows the polypropylene fibre used in this investigation.
Figure 4.4 Crimped Steel Fibre and Polypropylene Fibre
4.4.2.6 Flyash
Fly ash which is a by-product of the thermal power plant poses
serious problems of its dumping to the environmentalists. Utilization of flyash
in concrete as partial replacement of cement not only solves the problems of
dumping to some extent but also it is used as mineral admixture in concrete
and helps to attain reduction in cost of concrete by saving cement. This
56
pozzolana is beneficially used to attain certain properties in concrete such as
lower water demand for similar workability, reduced bleeding and lower
evolution of heat. The specific gravity of flyash used is 2.32. It has been used
particularly in mass concrete applications and large volume placement to
control expansion due to heat of hydration and also helps in reducing cracking
at early ages. In addition, the chemical reaction that creates Portland cement
produces CO2 as a by-product. By displacing a large percentage of the cement
in concrete, fly ash significantly reduces the associated environmental impacts
of CO2 production and air pollution. Therefore for higher strengths, silica
fume must be used in conjunction with fly ash. For the preparation of high
strength concrete, flyash is used at a dosage of 15 % of cement content.
4.4.2.7 Silica Fume
Silica fume is a waste by-product of the production of silicon and
silicon alloys. Silica fume is available in different forms, of which the most
commonly used is in a densified form. In developed countries it is already
available in blended with cement. With silica fume it is easier to make HPC
of strengths between 60-98 Mpa. In the present study silica fume content of
about 10 % by weight of cement for partial replacement of cement was mixed
to obtain high strength concrete.
4.4.2.8 Water
According to IS: 456-2000 water used for preparing concrete
should be of potable quality. In this investigation ordinary tap water, which is
fit for drinking, has been used in preparing all concrete mixes and curing.
57
4.4.2.9 Super Plasticizers
Plasticizers help us to increase the workability of concrete without
addition of extra quantity of water. It means that we can use less water
without reducing the workability at the same cement content. This is added to
avoid formation of flakes, due to less quantity of water. Use of plasticizers is
economical as the cost incurred on them is less than the cost of cement saved.
Use of super plasticizers becomes essential for designing mix to achieve HPC
and also for the preparation of fibre reinforced concrete to increase
workability. Super plasticizer used in this study was Sulphonate Naphthalene
Polymer. (Conplast SP 430).
4.4.2.10 Steel
The main reinforcement used for the specimen was tor steel of
diameter 8 mm. The shear reinforcement was of mild steel of diameter
3.3 mm. The yield stress of steel reinforcement is 420 N/mm2.
4.5 CONCRETE MIX DESIGN
4.5.1 General
The selection of suitable ingredients of concrete and the
determination of their relative proportion were done with an aim to produce
concrete of required strength and durability as economical as possible. Based
on the properties of cement, fine aggregate, coarse aggregate and water, the
mix proportion was calculated as per IS 10262-1982.
4.5.2 Mix Proportion
The mix design for fibre reinforced concrete has been done
according to Indian Standard method by taking into account the quantity of
58
fibre (Shetty 1996). Tables 4.5 to 4.7 show the proportions of mix for M20,
M25 and M60 concrete respectively.
Table 4.5 Concrete Mix Proportions (M20)
Material UnitPlain Concrete
1:1.76:2.69
Fibre concrete
1:1.64:2.5 +1.5%
Cement kg/m3
378 378
Fine Aggregarte (Sand) kg/m3
665.6 619.70
Coarse Aggregate
( 6mm to 10mm)kg/m
31020 968.15
Water (0.55) kg/m3
208 208
Steel Fibre (1.5 %) kg/m3
- 117.75
Polypropylene Fibre
(0, 0.2, 0.4, 0.6 and 1.5%)kg/m
3-
(0,1.82,3.64, 5.46
and 13.65)
Table 4.6 Concrete Mix Proportions (M25)
Material UnitPlain Concrete
1:1.57:2.4
Fibre concrete
1:1.46:2.23+1.5%
Cement kg/m3
416 416
Fine Aggregarte (Sand) kg/m3
652.60 607.33
Coarse Aggregate ( 6mm to
10mm)kg/m
31001.70 929.2
Water (0.50) kg/m3
208 208
Steel Fibre (1.5 %) kg/m3
- 117.75
Polypropylene Fibre
(0, 0.2, 0.4, 0.6 and 1.5%)kg/m
3-
(0,1.82,3.64, 5.46
and 13.65)
59
HPC mix proportion for M60 grade concrete was obtained based on
the guidelines given in modified ACI 211 method suggested by the author
M.S. Shetty. Portion of the cement was replaced by micro fillers such as silica
fume and flyash. In this study 10% replacement of cement by silica fume and
15% by fly ash were considered. To increase the workability of concrete
superplasticiser was added. The ratio of HPC mix was
1:0.2:0.11:1.4:2.14:0.35:0.02 (cement : fly ash : silica fume : sand : C.A : water:
superplasticiser). The ratio of HPFRC mix was 1:0.2:0.11:1.3:2:0.35:0.024 +
1.5% fibre. Table 4.7 presents the characteristics of two different concrete
mixes used to cast the test specimens.
Table 4.7 Concrete Mix Proportions (M60)
Material UnitPlain
ConcreteFibre Concrete
Cement kg/m3
449 449
Fly Ash kg/m3
88 88
Silica fume kg/m3
50 50
Fine Aggregarte (Sand) kg/m3
630 583
Coarse Aggregate
( 6mm to 10mm)kg/m
3963 891
Water Water binder
ratio (0.35)kg/m
3209 207
Superplasticiser Lit/ m3
10.00 11.75
Steel Fibre (1.5 %) kg/m3
- 117.75
Polypropylene
Fibre (0, 0.2 and 0.4%)kg/m
3- (0,1.82 and 3.64)
60
4.6 CASTING AND CURING
The mould was arranged properly and placed over a smooth
surface. The sides of the mould exposed to concrete were oiled well to
prevent the side walls of the mould from absorbing water from concrete and
to facilitate easy removal of the specimen. Figure 4.5 shows the
reinforcements which were tied for casting, seismic reinforced joint and
ordinary and fibre reinforced joint. The reinforcement cages were placed in
the moulds and the cover between cage and form were maintained as 10 mm.
The concrete contents such as cement, sand, aggregate and water were
weighed accurately and mixed. Fibres were carefully mixed with concrete
without balling of fibre. The mixing was done till uniform mix was obtained.
The concrete was placed into the mould immediately after mixing and well
compacted. Figure 4.6 shows the fibrous concrete placed in the joint region.
After placing the fibrous concrete in the joint region the ordinary concrete
was placed in the remaining portion. Control cubes and cylinders were
prepared for all the mixes along with concreting. The test specimens were
removed from the mould at the end of 24 hours of casting. Identification
marks were marked on the specimens. They were cured in water for 28 days.
After 28 days of curing the specimens were dried in air and white washed.
Figure 4.5 Reinforcement Cage of Seismic Detailed Joint and Fibrous
Joint
61
Figure 4.6 Fibrous Concrete Placed in the Joint Region and Ordinary
Concrete in the Remaining portion
4.7 TESTING PROCEDURE
The testing of cubes, cylinders and beam-column specimens have
been done after 28 days of curing. The following tests were performed in the
present research work:
Stress strain behaviour of concrete by conducting compression
test on cylinder
Compression test on concrete cubes.
Cyclic load test on beam-column joint
Reverse cyclic load test on beam-column joint
4.7.1 Compressive Strength Test
Compressive strength measurements are primarily concerned in
testing the strength of concrete. Cube specimens were tested using the 3000
kN capacity Automatic Compression Testing Machine (ACTM). This
62
machine fulfills the entire requirement for compression testing as per IS: 516-
1959. Cube specimens were placed centrally in the machine in such a manner
that the load is applied perpendicular to the casting faces. The load was
applied in a continuous and uniform fashion without shock. In this test the
maximum load carried by each specimen has been recorded. Compressive
strength is calculated by dividing the maximum load obtained by the cross-
sectional area of the specimen. To get the compressive strength, average value
of three specimens has been used.
4.7.2 Stress Strain Behaviour of Concrete
To get the stress strain behaviour, cylindrical specimens have been
tested in the servo controlled 100 Tonne capacity Universal Testing Machine.
Specimens after the required curing have been tested for compression after
their surfaces became dry. Surface water and grit had been wiped off from the
specimens. The bearing surfaces of the testing machine was wiped clean and
loose sand or other material were removed. Cylindrical specimens were
placed centrally in the machine. The load was applied in a continuous and
uniform fashion without shock with the help of a computer attached to the
machine. The data and graphs saved in computer were used for preparing
stress strain curves. The results displayed on the computer screen were
recorded at the failure of specimens.
4.8 EXPERIMENTAL SETUP
4.8.1 Cyclic loading
Seven beam-column specimens each from M20 and M25 grade
concretes were tested in Universal Testing machine of 100T capacity for
cyclic load test. The test setup is shown schematically in Figure 4.7.
Figure 4.8 shows the photograph of test setup. The specimen was mounted
63
such that the column is in vertical position. A constant axial load of 60 kN
was applied to the column to keep it in the vertical position and to stimulate
column axial load. A hydraulic jack was used to apply the load at a distance
of 50 mm from the free end of the beam. To record the load precisely a
proving ring was used. The beam was loaded gradually up to 5mm deflection,
unloaded and reloaded for next increment of deflection and this pattern of
loading was continued for each increment of deflection until failure. The
deflection of the beam at the point of loading during the test was measured by
a dial gauge with a least count of 0.01mm. Strain gauges were fixed on the
beam and column reinforcements to measure the strain in reinforcement.
Figure 4.7 Schematic Diagram of the Experimental Setup-Cyclic Load
64
Figure 4.8 Experimental Setup for Cyclic Loading
4.8.2 Reverse Cyclic Load Testing
Seven beam-column specimens each from M20 and M25
concrete and five beam-column specimens from M60 concrete were tested
under reverse cyclic loading which is similar to the seismic loading. The test
setup is shown schematically in Figure 4.9. The Figure 4.10 shows the
photograph of forward and reverse loading. The specimen was mounted such
that the column is in vertical position and beam is in horizontal position. For
strain controlled testing screw jack and hydraulic jack were used to apply
displacement at a distance of 50mm from the beam end. The hydraulic jack
was fixed at the strong floor and screw jack was fixed to the loading frame at
the top.
LVDT
65
Figure 4.9 Schematic Diagram of Reverse Cyclic Loading Test set-up
To record the load precisely, proving rings were used. The dial
gauges were used to measure the deflection. Each displacement cycle
consisted of a cycle of upward and downward displacement of beam end
position. Dial gauges were fixed at a distance of db and 2db (db = effective
depth of the beam) from the column face on the beam to measure the beam
deflections. Strain gauges were fitted in the beam top and bottom
reinforcement and column reinforcement to measure the reinforcement strain.
By using these load and displacement values strength, ductility, shear and
energy dissipation capacity were calculated.
66
Figure 4.10 Photograph of Forward and Reverse Loading
4.9 INSTRUMENTATION
Figure 4.11 shows the photograph of various instruments fitted on
the specimen during testing. Following are the name of instruments fitted.
Figure 4.11 Photograph Showing the Various Instruments
1
2 34
5
6
7
LVDT
67
1 Proving ring
2 Dial gauge used to measure beam deflection at 50 mm from
the beam end
3 Dial gauge used to measure beam deflection at a distance of
2db from the face of the column
4 Dial gauge used to measure beam deflection at a distance db
from the face of the column
5 Strain gauge to measure the column reinforcement strain
6 Strain gauge to measure the beam top reinforcement strain
7 Strain gauge to measure the beam bottom reinforcement strain
4.9.1 Measurement of Load and Deflection
For measuring the load, proving ring was fixed and for measuring
deflection at the free end dial gauge was fixed at a distance of 50 mm from
the free end.
4.9.2 Measurement of Joint Distortion
Two LVDTs mounted diagonally on the rear face on the joint were
used to measure the distortion of the interior core of the joint.
4.9.3 Measurement of Strains
Demec strain gauges were used to measure strain in the reinforcement
bars. Gauge length of demec strain gauge is 100 mm. Demec points were
fixed for the measurement of strain. While casting two small pieces of rods of
length equal to clear cover were welded on the main reinforcement at spacing
of 100mm such that they are projected up to concrete top surface. While
68
curing that reinforcement surfaces were covered with water proofing tape.
While testing the strain gauge tips were fixed on the rod surface and thereby
the strain in reinforcement could be measured.
4.10 PROPERTIES OF COMPANION SPECIMEN
4.10.1 Compression Test
The cylinder compressive strength and cube compressive strength
of various grades of concrete such as M20, M25 and M60 with different
proportions of hybrid fibre combinations are presented in Tables 4.8 to 4.10
respectively. It is evident from these tables that the increase in percentage of
polypropylene fibre reduces the compressive strength of fibre reinforced
concrete of grades M20, M25 and M60. Maximum decrease in compressive
strength was observed in the specimen cast by using 1.5 percent of
polypropylene fibre alone in the proportions tried. The specimen in the F1
series (with 1.5% of steel fibre) gave the maximum compressive strength.
Table 4.8 28 days Cube and Cylindrical Compressive Strength of M20
grade Concrete
Sl.
NoType of Fibre
Specimen Identification
I O1 I F11 I F21 I F31 I F41 I F51
1 Steel fibre in % 0 1.5 1.5 1.5 1.5 0
2Polypropylene
Fibre in %0 0 0.2 0.4 0.6 1.5
3Cube compressive
strength in N/mm2
35.4 41.42 39.42 37.95 32.71 15.24
4Cylinder Compressive
Strength in N/mm2
27.26 29.08 28.245 25.88 22.28 10.97
69
Table 4.9 28 days Cube and Cylindrical Compressive Strength of M25
Grade Concrete
Sl.
NoType of Fibre
Specimen Identification
II O1 II F11 II F21 II F31 II F41 II F51
1 Steel fibre in % 0 1.5 1.5 1.5 1.5 0
2Polypropylene
Fibre in %0 0 0.2 0.4 0.6 1.5
3Cube compressive
strength in N/mm2 38.4 44.5 43.26 37.53 33.86 22
4Cylinder Compressive
Strength in N/mm2
31.28 35.13 33.50 27.52 24.34 15.31
Table 4.10 28 days Cube and Cylindrical Compressive Strength of M60
Grade Concrete
Sl. No. Name of FibreSpecimen Identification
III O2 III F12 III F22 III F32
1 Steel fibre in % 0 1.5 1.5 1.5
2Polypropylene
Fibre in %0 0 0.2 0.4
3Cube compressive
strength in N/mm2
76.5 84.5 82.6 78.30
4Cylinder Compressive
Strength in N/mm2 61.2 69.3 66.9 62.8
4.10.2 Stress Strain Curve
Compression test on cylindrical specimens cast with M20, M25 and
M60 grade concretes, were conducted using computerised UTM. Figure 4.12
70
shows the load Vs cross head travel curves which were obtained during
testing of IIO2 and II F22 specimens cast using M25 concrete. Tables 4.10 to
4.12 show the cylinder compressive strength of concrete of all the specimens
cast using M20, M25 and M60 respectively.
Figure 4.12 Typical Load Vs Cross Head Travel Curve of II O2 and II
F22 Specimen cast using M25 Concrete obtained from UTM
Figure 4.13 Original Stress Strain Curve of II O2 and II F22 Specimen
cast M25 Concrete
The graph in Figure 4.12 which is obtained during testing is
converted to stress strain curve and is shown in Figure 4.13. The above stress
strain curve is used for the ABAQUS Finite Element Analysis.
71
4.11 SUMMARY
The properties of various materials used and experimental setup of
cyclic and reverse cyclic loading were described. The details of test specimen,
various combinations of fibres used for casting the specimens, their mix
design, testing methods and various instruments used for testing were also
specified. The compression test results of cubes and cylinders show that the
addition of steel fibre increases the compressive strength while the addition of
polypropylene fibre decreases the compressive strength.