1 Industrial Systems BUS2000 Busbar Differential Protection System Differential overcurrent system with percentage restraint protection

Upload: others

Post on 19-Jul-2020

23 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

1

Industrial Systems

BUS2000 Busbar Differential Protection SystemDifferential overcurrent system with

percentage restraint protection

Page 2: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

2

Industrial Systems

Typical Busbar Arrangements– Single Busbar– Double Busbar with Coupler– Breaker and a Half– Double Breaker– Double Busbar with Transfer Bar– Segregated Busbars with Coupler

Page 3: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

3

Industrial Systems

Typical Single BusbarArrangement

Page 4: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

4

Industrial Systems

Typical Double Busbarwith Coupler Arrangement

Page 5: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

5

Industrial Systems

Typical Breaker and a Half Arrangement

Page 6: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

6

Industrial Systems

Typical Double BreakerBusbar Arrangement

Page 7: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

7

Industrial Systems

Typical Double Busbarwith Transfer Bar

Page 8: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

8

Industrial Systems

Typical Segregated Busbarwith Coupler

Page 9: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

9

Industrial Systems

Types of Protection Schemes

–Low Impedance–High Impedance

• Medium Values• High Values

Page 10: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

10

Industrial Systems

Low Impedance Protection

Page 11: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

11

Industrial Systems

Saturation of the AuxiliaryCTs

• A. Primary Fault Current• B. Secondary Current from the Source CTs• C. Secondary Current in the Faulty CT• D. Differential Current

Page 12: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

12

Industrial Systems

Low Impedance Protection Current Detection + Second

Criteria–Time-delayed Overcurrent Relays–Directional Overcurrent Relays –Restraint Overcurrent relays–CT Saturation Detectors

Page 13: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

13

Industrial Systems

High Impedance ProtectionScheme

Page 14: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

14

Industrial Systems

High Impedance Protection

•• WHERE:• RL= CONNECTION WIRES RESISTANCE• IF = SECONDARY RMS CURRENT VALUE IN TI3

• VR = DIFFERENTIAL RELAY VOLTAGE• VS = CT MINIMUM SATURATION VOLTAGE• VOP = OPERATION VOLTAGE

• VR = IF x (2RL + RS)• VOP > VR Stability Criteria• VS > VOP Operation Criteria• TI3 Totally Saturated• RS CT Secondary Winding R Value

Page 15: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

15

Industrial SystemsDifferential Overcurrent Relay with Percentage Restraint & Stabilizing

Resistor

Page 16: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

16

Industrial Systems

BUS2000-External Fault

Page 17: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

17

Industrial Systems

BUS2000-Internal Fault

Page 18: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

18

Industrial Systems

BUS2000 - Differential Unit Block Diagram

Page 19: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

19

Industrial Systems

BUS2000-Sensitivity Algorithm (1)

Page 20: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

20

Industrial Systems

BUS2000-Sensitivity Algorithm (2)

Page 21: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

21

Industrial Systems

BUS2000-Sensitivity Algorithm (3)

Page 22: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

22

Industrial Systems

External Fault with CT Saturation

Page 23: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

23

Industrial Systems

BUS2000-Stability Algorithm

Page 24: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

24

Industrial Systems

BUS2000-Stability Limit

Page 25: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

25

Industrial Systems

BUS2000-Operation Characteristic

Page 26: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

26

Industrial Systems

BUS2000-Auxiliary CT. Magnetizing Curve of the Secondary Side

Page 27: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

27

Industrial Systems

BUS2000-Alarm Unit Block Diagram

Page 28: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

28

Industrial Systems

Breaker Failure Block Diagram

Page 29: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

29

Industrial Systems

Numerical Monitoring Module– Differential and Restraint Currents Metering Information– Full Human-Machine Interface (Keypad + Graphic

Display)– IRIG-B Time Synchronization– Alarm Treatment– Differential Protection Outputs Status

Page 30: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

30

Industrial Systems

Numerical Monitoring Module (cont)

– Oscillography Waveform Capture– Event Record– RS232 or fiber optics Communications– Configurable I/O– Undervoltage Supervision

Page 31: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

31

Industrial Systems

BUS2000-Single Busbar(6 feeders) Differential Protection

Page 32: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

32

Industrial Systems

BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection

Page 33: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

33

Industrial Systems

BUS2000-Test Rack

Page 34: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

34

Industrial Systems

BUS2000-Numerical Monitoring Module

Page 35: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

35

Industrial Systems

External Connections Diagram of Single Busbar BUS2000

System

Page 36: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

36

Industrial Systems

BUS2000-Settings–K for Sensitivity–K and RE as low as possible–RE for CT requirements for

Overvoltage Conditions

Page 37: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

37

Industrial Systems

Key Advantages

– Flexibility– Independent setttings for K and RE done in the field

without any additional changes– Wide Setting Range

– Suitable for all kinds of installations

– Measurement Units Supervision

– Current Circuits Supervision

Page 38: BUS2000 Busbar Differential Protection System · (6 feeders) Differential Protection. 32 Industrial Systems BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection. 33 Industrial

38

Industrial Systems

Key Advantages (cont’d)

– Single-Three Phase Breaker Failure– Test Rack Independent from the protection– Easy Commisioning (accesible terminal blocks)– Suitable for updating of old Substations– Operating Principles well proven in the field– Numerical Monitoring Module