    DIFFERENTIAL PROTECTION

    PROTECTION OF AC MACHINESAGAINST INTERNAL FAULTS

    Document BySANTOSH BHARADWAJ REDDYE mail: [email protected]

    More Papers and Presentations available on above site

  • 7/29/2019 47764564 Differential Protection

    2/26

    INTERNAL & EXTERNAL FAULTS

    Why a normal O/C relay is inadequate ?

    TR 1

  • 7/29/2019 47764564 Differential Protection

    3/26

    DIFFERENTIAL RELAY

    - SHOULD TRIP INSTANTANEOUSLYFOR AN INTERNAL FAULT

    - SHOULD NOT TRIP FOR AN EXTERNAL FAULT

    - NORMAL SETTINGS FOR DIFFERENTIAL PICK UP = 15%

  • 7/29/2019 47764564 Differential Protection

    4/26

    Differential Protection

    ProtectedEquipment

    50 Ie2 - Iel

    Ip

    Ip - Iel Ip - Ie2

    IpTA TA

  • 7/29/2019 47764564 Differential Protection

    5/26

    Differential Protection

    ProtectedEquipment

    IL IR IL IR

    T.A T.A

  • 7/29/2019 47764564 Differential Protection

    6/26

    PRINCIPLE OF OPERATION OF DIFFERENTIAL RELAYS

    CIRCULATING CURRENT PRINCIPLE

    G1

  • 7/29/2019 47764564 Differential Protection

    7/26

    INTERNAL / EXTERNAL FAULTS

    I1 I2 Id

    100 100 0 NORMAL LOAD

    500 500 0 THROUGH FAULT (500%)

    500 300 200 INTERNAL FAULT (200%)

    100 80 20 INTERNAL FAULT (20%)

    NOTE :1. THROUGH FAULT CONDITION HAS TO BE DETECTED BY

    NORMAL O/C RELAY (SINCE FAULT CURRENT ISHIGHER THAN 100%)

    2. INTERNAL FAULT HAS TO BE CLEARED BY DIFFERENTIALRELAY - SINCE FAULT CURRENT IS LESS THAN FULL LOAD,NORMAL O/C RELAY WILL NOT PICK UP

  • 7/29/2019 47764564 Differential Protection

    8/26

    MOTTO OF A DIFFERENTIAL RELAY

    SHOULD OPARATE FOR INTERNAL FAULT

    SHOULD NOT OPERATEFOR EXTERNAL FAULT

    SATABILITY OFDIFFERENTIAL RELAY

  • 7/29/2019 47764564 Differential Protection

    9/26

    TYPES OF DIFFERENTIAL RELAYS

    CIRCULATING CURRENT(HIGH IMPEDANCE)

    PERCENTAGE BIASED(LOW IMPEDANCE)

  • 7/29/2019 47764564 Differential Protection

    10/26

    CIRCULATING CURRENTHIGH IMPEDANCE DIFFERENTIAL RELAY

    I1 - I2 RELAY OPERATINGCURRENT

    TRIP IN TERMS OFSETTING CT PRIMARY

    (20% OF In)

    RELAY WILL TRIP IF I1-I2 ISGREATER THAN 20% 0F In(In = RATING OF CT PRIMARY)

  • 7/29/2019 47764564 Differential Protection

    11/26

    CIRCULATING CURRENTHIGH IMPEDANCE DIFFERENTIAL RELAY

    Id

    Is =20%

    Average current Ir /In=((I1 +I2)/2)/In

    0.5 1.51.0 2.52.0

    RELAY TRIP AREA

  • 7/29/2019 47764564 Differential Protection

    12/26

    CIRCULATING CURRENTHIGH IMPEDANCE DIFFERENTIAL RELAY

    DISADVANTAGES :

    DUE TO CT CHARACTERISTICS MISMATCH,RELAY CAN DETECT A CONDITION WHEREI1-I2 EXCEEDS SET VALUE

    A) UNDER NORMAL OPERATRING CONDITIONSB) UNDER THROUGH FAULT CONDITIONS

    C) WHENEVER THE TAPS ARE CHANGED INTRANSFORMERS

    THIS IS MAINLY DUE TO :DC OFFSET EFFECT ANDASSYMMETRIC CT RESPONSE UNDER LARGETHROUGH FAULT CURRENTS.

  • 7/29/2019 47764564 Differential Protection

    13/26

    CIRCULATING CURRENT(HIGH IMPEDENCE) DIFFERANTIAL RELAY

    ADD ASTABILISING RESISTOR TO IMPROVEPERFORMANCE

  • 7/29/2019 47764564 Differential Protection

    14/26

    CIRCULATING CURRENTHIGH IMPEDANCE DIFFERENTIAL RELAY

    STABILISING RESISTOR

    WILL IMPROVE PERFORMANCE OF RELAYFOR CT CHARACTERISTICS MISMATCH- TO CERTAIN LIMITS

    BUT RELAY HAS BECOME INSENSITIVE

    DUE TO ADDITION OF RESISTOR.RELAY MAY NOT TRIP FOR A REALINTERNAL FAULT.

    FOR TOTAL IMPROVEMENT

    USE PERCENTAGE BIASED RELAY

  • 7/29/2019 47764564 Differential Protection

    15/26

    BIASED DIFFERENTIAL

    I1 - I2 RELAY OPERATINGCURRENT

    (I1+I2)/2 RELAY RESTRAININGCURRENT

    TRIP SETTING = (I1- I2)

    (I1 +I2)/2(BIAS %)

    NORMALLY BIAS % = 20%

    RELAY WILL TRIP WHEN(2*(I1 - I2)/(I1+I2))*100

    VALUE EXCEEDS TRIP SETTING

  • 7/29/2019 47764564 Differential Protection

    16/26

    BIASED DIFFERENTIAL

    Refer excel sheet

  • 7/29/2019 47764564 Differential Protection

    17/26

    PERCENTAGE BIASED DIFFERENTIAL RELAY

    INTERNAL FAULTEXTERNAL FAULT

    BIAS PERCENTAGE

  • 7/29/2019 47764564 Differential Protection

    18/26

    PERCENTAGE BASED DIFFERENTIAL RELAY BIASE CHARECTERSTICS

    I1+I22

    %Id

    ( I1-I2)

    RELAY NOT TO OPERATE

    RELAY OPERATES

    SUM CURRENT

    DIFFERENCE

    CURRENT

    MIN I1-I2SLOPE

    DUAL SLOPE ?

  • 7/29/2019 47764564 Differential Protection

    19/26

    DIFFERENTIAL RELAYS

    INTERPOSING CTs

    IN TRANSFORMER DIFFERENTIAL RELAYS

    FOLOWING COMPENSATIONS WILL BEREQUIRED FOR:

    A) PROVIDING MAGNITUDE COMPENSATION

    B) PHASE ANGLE COMPENSATION DUETO VECTOR GROUP SHIFT BETWEENPy & Sy

  • 7/29/2019 47764564 Differential Protection

    20/26

    DIFFERENTIAL RELAYS

    INTERPOSING CTs

    INELECTROMECHANICAL / SOLIDSTATE RELAYSINTERPOSING CTs ARE USED FOR PROVIDINGTHE MAGNITUDE AND VECTOR COMPENSATION

    IN NUMERICAL RELAYS THE SOFTWARE INSIDEINSIDE THE RELAY TAKES CARE OF THESE

    COMPENSATION

  • 7/29/2019 47764564 Differential Protection

    21/26

    TRANSFORMER VECTOR GROUPS

    1. YY0

    2. YY6

    3. YD1

    4. YD11

    R

    YB

    R

    YB

    R

    YB

    R

    YB

    R

    YB

    YB

  • 7/29/2019 47764564 Differential Protection

    22/26

    PHASE ANGLE COMPENSATIONTHROUGH INTERPOSING CTS

  • 7/29/2019 47764564 Differential Protection

    23/26

    CONNECTION DIAGRAM MD32-T RELAY

    WHY REF ?

  • 7/29/2019 47764564 Differential Protection

    24/26

    RESTRAINTS IN DIFFERENTIAL RELAYS

    2ND HARMONIC RESTRAINT

    WHEN A TRANSFORMER IS SWITCHED ON,

    THE DIFFERENTIAL RELAY MAY SENSE ADIFFERENTIAL CURRENT AND INITIATE TRIP.

    THIS IS DUE TO THE MAGNETISING CURRENTINRUSH ON ONE SIDE OF THE TRANSFORMER.THIS WILL RESULT IN A LARGE VALUE OFI1-I2 FOR ABOUT 4 OR 5 CYCLES.

    RELAY IS RESTRAINED FROM OPERATIONAT THE TIME OF SWTICH ON BY THE2ND HARMONIC RESTRAINT FEATURE.

  • 7/29/2019 47764564 Differential Protection

    25/26

    RESTRAINTS IN DIFFERENTIAL RELAYS

    5TH HARMONIC RESTRAINT

    WHEN OVER FLUXING OCCURS IN A TRANSFORMER

    THE DIFFERENTIAL RELAY MAY SENSE ADIFFERENTIAL CURRENT AND INITIATE TRIP.

    THIS IS DUE TO THE HIGH LEVEL OF FLUXPRESENT IN THE CORE CAUSING AN ARTIFICIALI1-I2 FOR A SHORT TIME.

    RELAY IS RESTRAINED FROM OPERATIONAT THE TIME OF OVER FLUXING BY THE5TH HARMONIC RESTRAINT FEATURE.

  • 7/29/2019 47764564 Differential Protection

    26/26

    SALIET FEATURES OF MD32 T

    1. PERCENTAGE BIASED2. DUAL SLOPE3. DISPLAYS OF Id4. VECTOR/AMPLITUDE

    COMPENSATION(W/O ICTs)

    5. 2ND HARMONIC RESTRAINT

    6. 5TH HARMONIC RESTRAINT7. WAVE FORM CAPTURE8. INBUILT REF