09 differential protection

Upload: mannuazad

Post on 08-Apr-2018

235 views

Category:

Documents


3 download

TRANSCRIPT

  • 8/7/2019 09 Differential Protection

    1/30

    Differential Protection

  • 8/7/2019 09 Differential Protection

    2/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Measuring Principle

    Basis is the first Kirchhoffs law e.g. Transformer

    The currents to a nodeare positive defined.

    Internal fault(nfeed from two sides) External fault

    I1 = I1,FI2 = I2,FI= II1,F + I2,FI

    trip

    I1 = IFI2 = -IFI= IIF - IFI = 0

    no trip

    I= II1 + I2I

    In the case of load:I1 = ILI2 = -IL

    I= 0}

    1 2

    I

    I=0I

    I1

    I2

    IL

    2

    1

  • 8/7/2019 09 Differential Protection

    3/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Peculiarity of the Transformer Differential Protection

    1. Vector group (e. g. Yd5) 2. Different CTs,tap changer, magnetising current

    vector group adaptation restraint function (stabilising) is necessary

    3. Dynamic currents

    I= f (Irestr.)

    Irestr. = |I1| + |I2|

    inrush current overflux (overexcitation)

    CT saturation duringexternal faults

    blocking via harmonics

    saturation detector

    trip region

    -

    I2

    I1

    150

    current transformer

    tap changer,

    CT adaptation(will be eliminated)

    magnetising current

    I

    I

    ITr, IRestr.

  • 8/7/2019 09 Differential Protection

    4/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Differential Currents with Harmonics

    energising

    Y y

    D y

    T2

    T1

    t = 0

    t = 0

    i2

    i1

    i1

    even,

    2nd harm.

    i

    i

    i

    20 40 60 80 100ms t

    iDiff = i1

    iDiff = i1

    iDiff = i2

    20 40 60 80 100ms t

    20 40 60 80ms t

    energising

    paralleling(energising transformer T1)

    even

    2ndharm.

    evenand

    odd

    2ndharm.

  • 8/7/2019 09 Differential Protection

    5/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Differential Currents with Harmonics

    i1

    i1

    i1 i2 ~ 0

    i2

    i2

    20 40 60 80ms t

    20 40 60 80ms t

    20 40 60 80ms t

    i

    i

    i

    iDiff = i1 - i2

    iDiff = i1 - i2

    iDiff = i1

    odd

    3rd and5thharm.

    evenandodd

    evenandodd

    Over-excitationUTr > UN

    External short circuit withsaturation of the CTs at thelow-voltage side

    internal short circuit with

    saturation of the CTs at thehigh-voltage side

  • 8/7/2019 09 Differential Protection

    6/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Differential Protection for Generators and MotorsBasic principle can be nearly direct used.

    1. Stabilising characteristic

    2. Transients sensitive settings

    generators: external short circuit with largedc time constants

    motors: start-up currents

    transient transfer features of a CT

    are important (dc component)

    Insensitive settings at

    matching transformersin the secondary circuit

    different primary CTs

    different burden

    Trip area I

    I

    IRestr.

    Error currents

    via CT

    identically current transformers

    sensitive setting is possible

  • 8/7/2019 09 Differential Protection

    7/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Devices with Differential Protection Functions

    7UM62 and7UT6xx -Family

    7UT613 for protection objects with threeends

    7UM621 and 7UM622for protection objects with two ends(machines)

    7UT612 for protection objects with twoends

    7UT633 for protection objects with threeends

    7UT635 for protection objects up to fiveends

  • 8/7/2019 09 Differential Protection

    8/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Applications

    7UM 62

    7UT612

    7UT613

    7UT6

    Trans-former

    Two winding transformer2 or 3phases

    1 1/2 circuit breaker applicationwith two winding transformer

    Short lines2 ends

    7UT613

    7UM 62

    7UT612

    7UT613

    Generator/Motor longitudinal ortransversal differential protection

    GS3~

    Three winding transformer2 or 3phases

    Short lines3 ends

  • 8/7/2019 09 Differential Protection

    9/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Connection Example

    Side 2(Winding 2)

    Side 3(Winding 3)

    Side1(Winding1)

    7UT613; 633

    7UM 62

    7UT 612 )*

    )* direct zero sequence currentalso possible

    direct connection to the main CTs

    no matching transformers / no

    matching connections

    numerical vector group adaptationwithout zero sequence currentcorrection depending of the type ofearthing of the winding.

    increased sensitivity by 33% bymeasuring of the zero sequencecurrent (7UT6) for single-polefaults.

    1A/5A main CTs adaptation in therelay

    permissible ratio CT nominal currentto transformer nominal current up to1 : 8

  • 8/7/2019 09 Differential Protection

    10/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Functional Diagram of the Differential Protection

    i1P

    i2P

    i3P

    i1A*

    i2A*

    i3A*

    iDIFF = i1A* + i2A* + i3A*basic wavefiltering IDiff

    iStab = | i*1A | +| i*2A | + | i*3A |rectified mean value

    IStab fast tripping withevaluation of

    IDiff and iDiff

    iDIFF>> Stage

    tripping by IDIFF>>

    Blockingbyharmonics

    tripping by IDIFF>

    &

    trippinglogic TRIP-

    command

    TRIP L1

    TRIP L2

    TRIP L3>1

    IDiff

    IDiff>

    IStabmeasured valuepreprocessingwinding 1

    measured valuepreprocessingwinding 2

    measured valuepreprocessingwinding 3

    tripping characteristicand saturat. detection

    harmonics analysiscrossblock

    blocking by2nd harmonicsand 3rd or 4th.or 5th harmonics

    i1P, i2P, i3P sampling values from winding 1, 2, 3i*1A, i*2A, i*3A values after vector group and CT matchingIDiff basic wave contents in the differential currentiDiff differential currentIStab rectified mean value of the stabilising currentiStab stabilising current

  • 8/7/2019 09 Differential Protection

    11/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Measuring Pre-processing, Example for CT Matching (Part 1)

    IP1 = 500A(load current)

    IP2 = 1833A(load current)

    1000/1A 2000/1A

    UN1 = 110kV UN2 = 30kV

    SN = 100MVA

    Side 1 Side 2

    7UM 627UT6

    IDiff = ?IRestr. = ?

    IN, Trafo = 525A IN, Trafo = 1924A

    IS1 = 0,5A IS2 = - 0,92A

    measuredsecondary currents

  • 8/7/2019 09 Differential Protection

    12/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Measuring Pre-processing, Example for CT Matching

    (Part 2)

    1. Calculation of the transformer nominal current INTrafo =

    2. Correction factor kW =

    3. Correction nominal current I= kW IS

    4. Calculation of the differential and stabilising current Idiff= |I1' + I2' | Istab = |I1' | + |I2' |

    Calculation example:

    SN = 100MVA; UN1 = 110kV; UN2 = 30kV; IN1CT = 1000A; IN2CT = 2000A

    Correction factors: kW1 = 1,9; kW2 = 1,04 Idiff = 0A

    Load conditions: Ip1 = 500A; Ip2 = 1833A IStab= 1,9A

    Secondary currents: Is1 = 0,5A; Is2 = 0,92A Idiff = 0 IN Trafo

    Matched currents: I1' = 0,95A; I2' = 0,95A Istab = 1,9IN Trafo

    S

    3

    N

    N U

    NTrafo

    NCT

    I

    I

  • 8/7/2019 09 Differential Protection

    13/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Measuring Preprocessing: Vector Group Adaptation)

    L1

    L2

    L3

    Ip IsYN d5

    IE

    Protection

    IpL1

    IpL3 IpL2IsL1

    IsL2

    IsL3

    I

    I

    I

    I

    I

    I

    I

    I

    I

    *

    *

    *

    1 0 0

    0 1 0

    0 0 1

    +1

    3

    pL1

    pL2

    pL3

    pL1

    pL2

    pL3

    E

    E

    E

    =

    I

    I

    I

    I

    I

    I

    *

    *

    *

    1

    3

    2 -1 -1

    -1 2 -1

    -1 - 1 2

    pL1

    pL2

    pL3

    pL1

    pL2

    pL3

    =

    1-10

    01-1

    101-

    3

    1

    *

    *

    *

    sL3

    sL2

    sL1

    sL3

    sL2

    sL1

    =

    I

    I

    I

    I

    I

    I

    1-10

    01-1

    101-

    3

    1

    *

    *

    *

    sL3

    sL2

    sL1

    sL3

    sL2

    sL1

    =

    I

    I

    I

    I

    I

    I

    standard setting

    increasing of thesensitivity via theconnection of IE-CT(only at 7UT6 possible)

    zero sequence elimination

    additional earth current measurement (I0-correction)

  • 8/7/2019 09 Differential Protection

    14/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Example Calculation: Vector Group Correction

    Situation: Single Phase Fault, No Load

    Source

    Ynd1F1 F2

    ISC ISC/3

    ISC/3

    ISC

    F1 F2

    IL1 = -ISC IL1 = 0IL2 = 0 IL2 = 0

    IL3 = 0 IL3 = 0

    IE = ISC IE = ISC

    Il 1 = ISC /3Il 2 = - ISC /3Il 3 = 0

    L1

    L2

    L3

  • 8/7/2019 09 Differential Protection

    15/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Example Calculation: Vector Group Correction

    I Zero Elimination

    I*L1

    I*L2I*L3

    = 1/3

    2 -1 -1

    -1 2 -1-1 -1 2

    - ISC

    00

    F1 F2

    0

    00

    I*l 1

    I*l 2I*l 3

    = 1/3

    1 -1 0

    0 1 -1-1 0 1

    ISC /3

    - ISC /30

    I*L1 = -2/3 ISC 0

    I*L2 = 1/3 ISC 0I*L3 = 1/3 ISC 0

    I*l 1

    = 1/3 ISC

    + 1/3 ISC

    = 2/3 ISC

    I*l 2 = 0 - 1/3 ISC = -1/3 ISCI*l 3 = -1/3 ISC + 0 = -1/3 ISC

    IDIFF1 = I*L1 + I*l 1 = 0 2/3 ISC

    IDIFF2 = I*L2 + I*l 2 = 0 1/3 ISCIDIFF3 = I*L3 + I*l 3 = 0 1/3 ISC

    We see in all three phases adifferential current; this mustbe considered during asingle phase testUse only the trip signalfrom the tested phase!

  • 8/7/2019 09 Differential Protection

    16/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Example Calculation: Vector Group Correction

    I Zero Correction

    I*L1I*L2I*L3

    =

    1 0 0

    0 1 0

    0 0 1

    - ISC0

    0

    F1 F2

    0

    0

    0

    I*l 1I*l 2I*l 3

    13

    1 -1 0

    0 1 -1

    -1 0 1

    I*L1 = -2/3ISC 1/3 ISC

    I*L2 = 1/3 ISC 1/3 ISC

    I*L3 = 1/3 ISC 1/3 ISC

    IDIFF1 =I*L1 + I*l 1 = 0 ISCIDIFF2 =I*L2 + I*l 2 = 0 0IDIFF3 =I*L3 + I*l 3 = 0 0

    1/3 ISC1/3 ISC1/3 ISC

    + =

    ISC

    /3- ISC /30

    I*l = 1/3 ISC + 1/3 ISC = 2/3 ISCI*l 2 = 0 - 1/3 ISC = -1/3 ISC

    I*l 3 = -1/3 ISC + 0 = -1/3 ISC

    We see only in the faultyphase the currents

  • 8/7/2019 09 Differential Protection

    17/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Tripping Characteristic

    flexible adaptation to various transformers, e.g. with tap changer or different main CTs

    high stability against external faults with CT saturation

    fast tripping for solid short-circuits within one period

  • 8/7/2019 09 Differential Protection

    18/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Recommendation for voltage setting:

    U = 2U U

    U + U= U (1 - cN, New

    max min

    max min

    N

    2)

    c: steps of tap changer (p.u.)

    Problem: The tap changer modifies the transformer ratio

    additional error in the differential current

    Example: tap changer c = 16%

    res

    resdiff

    0,16=c

    cc

    I,I

    II

    diff 0870

    2

    =m

    Relay Settings

    Influence of the Tap Changer

    If IN.Tr. is flowing the additional Idiff is approx. 17,5% of the transformercurrent. With slope 1 = 0,25 there is the pick-up threshold at 50%. Thesecurity margin is for steady state conditions high enough. Consideringtransient conditions (CT-influence) a small increasing of slope 1 (to 0,3) isrecommended.

  • 8/7/2019 09 Differential Protection

    19/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Pick up of Differential Protection

    For triggering of internal tasks, events and fault records the differential protectionfunction needs a pickup information. This pickup becomes active, if thedifferential current or the restraint current is over an internal threshold (dottedline). Each external large current leads to a pickup.

    Pickup doesnt always means internal failure!

  • 8/7/2019 09 Differential Protection

    20/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    IDiff / IRestr.- Areas for Short Circuit / Normal Operation

    1

    2 4

    NTr

    diff

    I

    I

    NTr

    Restr.

    I

    I

    limiting curve

    internalshort circuit/Inrush

    external short

    circuit withCT saturation

    external shortcircuit witha high current

    externalshort circuit (low current)

    normal operation(nominal current)

  • 8/7/2019 09 Differential Protection

    21/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Rush Stabilisation

    Recognise inrush condition by evaluating the ratio 2nd harmonic I2HAR to basicwave IDiff.

    Time limit for cross-block. Reliable reaction to the inrush condition with cross-block.Trip of a short circuit after the set time delay.

    Recognise over-excitation by evaluating the ratio 3rd or 5th harmonic to basic wave

    filter window1 cycle L1-block

    L2-block

    L3-block

    Cross-block = No (phase separate blocking)

    Cross-block = Yes (blocking of all phases)

    Idiff, L2 > trip blocking

    O R 1

    t

    t1P 2P 3P

    iRUSH = iDiff

    15 % setting value

    block

    no block

    I2HARIdiff

    Inrush currentin one phase

    L1-block

    L2-block

    L3-block

    Idiff, L1 > trip blocking

    Idiff, L3 > trip blocking

    IDiff > trip blocking for a limited time

    &

    &

    &

  • 8/7/2019 09 Differential Protection

    22/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Example of an Inrush CurrentA unit transformer (IN = 396 A) was switched on from the high voltage side

  • 8/7/2019 09 Differential Protection

    23/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Stabilising at Motor StartingTypical for motor starting is the starting current and the superimposed dc componentwith a large time constant. The current transformers (ct) transfer different this dccomponent. The result is a differential current and the risk of an over-function is given.

    Detection of motor starting:Increases the pick-up values for a restricted time

    Criterion:

    Supervision ofrestraint current

    Istab > I-Restr. Startup(until 2 I/InO)

    than theStart-Factor (max. 2)is active for a restrictedtime

    T Start Max(Duration of dynamicalincreasing of pickup)

  • 8/7/2019 09 Differential Protection

    24/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Setting RecommendationsPower System Data 1The setting of this parameters are important, because they are necessary for thescaling and direction definition of the measurands. At the protection objecttransformer the setting for star point Solid Earthed leads to a zero sequenceelimination. Isolated leads to a direct current comparison(without zero sequenceconsideration). This setting is only allowed at a really free star point (no over voltagearrester, no Peterson coil).At the protection object generator always the direct current comparisonmethodis active (no zero sequence elimination).

    Setting values:Under normal conditions the factory settings correspond with the practical experiences.Its not necessary to change these parameters.At transformers with tap changer the inclination of SLOPE 1 should be increased. Thesetting for the inrush detection can be final select during the primary test. If we are onthe limits (low setting value) an activation of CROSSBL. 2. Harm. is recommended.If are current transformer operates on their limit the pickup value Idiff > and die slope 1should be increased.The Idiff >> - stage must be set over the maximum inrush current.

    At generators and motors SLOPE 1 can be reduced (to 0,15), if the currenttransformers are identical. At generators the Idiff>>-stage must be set over thetransient fault current (3 to 7 IN,G).

    Additional at generators its also recommended an activation of increasing the pickupthreshold during starting or at external faults (Start-Factor > 1).

  • 8/7/2019 09 Differential Protection

    25/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Earth Current Differential Protection in the 7UM62The earth current differential protection (restricted earth fault protection - REF) offersa higher sensitivity at single phase faults (approx. 5 %) against the conventionalprotection. Its used at generators with low ohmic star point or at earthed Wyeconnected transformer windings .

    protection

    object

    protection

    object

    Connection 1 Connection 2At connection 1 the zerosequence current is calculatedfrom the phase currents and

    direct measured on the starpoint(transformer application)

    At connection 2 the zero

    sequence current is calculatedonly from the phase currents.(generator application, wheremore than one generator feedsinto the busbar)

  • 8/7/2019 09 Differential Protection

    26/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Measuring Principle of Earth Current Differential Protection in

    the 7UM62

    iL1S1

    iL2S1

    iL3S1

    iL1S2

    iL2S2

    iL3S2

    iee2

    protection object:generator

    1

    3I023I01

    I0Diff

    I0Stab

    I/InO

    I/InO

    1

    1

    I-EDS>

    Stabilizing rangeRange not possible

    Tripping range0201Diff0 I3I3I +=

    0201Stab0 I3I3I +=

    L3S1L2S1L1S101 III3I ++=

    L3S2L2S2L1S202 III3I ++=

    EE202 I3I =or

  • 8/7/2019 09 Differential Protection

    27/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Earth Current Differential Protection in the 7UM62

    Stabilizing against Overfunction

    90

    | | = 0180

    65115

    I.

    II.

    III.IV.

    2104 EDS || I MIN>

    Direction of zero sequence current:

    I. internal fault

    III. external fault

    IV. direction not consideredII. measuring repetition

    ( Imax (max. 2.5 IN), than blocking

    Main problem are external faults:Transient conditions with large time constants; Short current circuitswith current transformer saturation

    Release at zero sequence voltage:A release of zero sequence current measurement is be caused by a measured zero

    sequence voltage (can be switched off).

  • 8/7/2019 09 Differential Protection

    28/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Restricted Earth Fault Protection (REF) in the 7UT6

    i1i2

    i3

    i'0

    i"0 = i1 + i2 + i3

    i0" + i0' = iF

    iF

    Trip

    0

    Trip = I0' - k SStab < 0 Trip = I0' Trip - tripping quantity

    Stab 0 Stab - I0 angle-dependentstabilization

    IEDF- pick-up valve

    Stab = I I '0 - I " 0| - | I ' 0 + I " 0|

    restrictedearth faultprotection7UT6

    fault currentagainst earth

    stabilizationarea

    tripping area

    calculation of the basic wave and the complex vectors of I0' and I0"

    insensitive against DC components and CT saturation

    evaluation of the modulus and angle between I0' and I0"

    sensitive fault detection starting with 5% transformer nominal current

  • 8/7/2019 09 Differential Protection

    29/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Commissioning with Browser- Support

    Currents on the highand low voltage side

    Tripping characteristicwith actualoperating points

  • 8/7/2019 09 Differential Protection

    30/30

    / Copyright Siemens Australia & NZ 2007. All rights reserved. Siemens. Innovation for generations.

    Benefits for the Customer

    Protection relay with flexible adaptation to the transformer/generator/motoror short line. Programming of the device data in the relay.

    Reduced amount of wiring by direct connection to the main CTs.

    No matching transformers and therefore no wiring errors.

    Zero sequence current can be measured (in the 7UT6).Sensitivity for single-pole faults in the transformer increased by 33% .

    Flexible adaptation of the tripping characteristic to various main CTs,

    tapped transformers.

    Exact discrimination between the short circuit condition and the inrushcondition by on-line analysis of the harmonics. Fast tripping forhigh-current faults. Saturation detector for external faults.

    Thermal monitoring of two transformer windings. Back-up DMTL/IDMTL with reverse blocking for one winding.

    Sensitive short circuit protection for faults winding against earth.

    Manifold commissioning aids.