Page 1: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

1 | P a g e

TECHNICAL SPECIFICATION

OF

ELECTRICAL MATERIALS

Insulators & Lightening Arrestors

“GROUP – A”

Tender Notice No. NESCO Utility / MR Materials / 19 /17-18/ 13002 , dtd.09.10.17

Page 2: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

2 | P a g e

GROUP – A Insulator & LA

Sl No. Description of Materials Unit Qty required

1 33kV LA, 10KA Nos. 200

2 33kV Post Insulator Nos. 500

3 33kV Pin Insulator Nos. 2500

4 33kV Disc Insulator (B&S) 70KN Set 500

5 33kV Disc Insulator (B&S) 90KN Set 500

6 11kV LA, 10KA Nos. 500

7 11kV Post Insulator Nos. 1000

8 11kV Pin Insulator Nos. 5000

9 11kV Disc Insulator (T&C) 45KN Nos. 3000

10 11kV Disc Insulator (B&S) 70KN Nos. 1000

NB: 1. Bidders should put their authorized signature with office seal on each page of the documents.

2. Bidders should put their offer in the Guaranteed particulars column furnished in the tender documents. 3. Purchaser reserves the right to increase or decrease the above quantities during placement of purchase order or may cancel any item/items without assigning any reason thereof .

General Manager (C&P) NESCO Utility, Balasore, Odisha

Page 3: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

3 | P a g e

TECHNICAL SPECIFICATION OF INSULATORS

TECHNICAL SPECIFICATIONS OF 33 KV POST TYPE INSULATOR 1. Scope of Work: This Specification covers design, engineering, manufacture, assembly,

stage testing, inspection & testing before supply and delivery at site of the 33 KV post type insulator

2.0 INSULATORS 2.1 General Requirements

2.1.1 The Porcelain shall be sound, free from defects, thoroughly vitrified and smoothly glazed. 2.1.2 Unless otherwise specified, the glaze shall be brown in colour. The glaze shall cover all the porcelain parts of the insulator except those areas which serve as supports during firing or are left unglazed for the purpose of assembly. 2.1.3 The design of the insulator shall be such that stresses due to expansion and contraction in any part of the insulator shall not lead to deterioration. The porcelain shall not engage directly with hard metal. 2.1.4 Cement used in the construction of the insulator shall not cause fracture by expansion or loosening by contraction and proper care shall be taken to locate the individual parts correctly during cementing. The cement shall not give rise to chemical reaction with metal fittings, and its thickness shall be as uniform as possible.

3.0 Tests: The insulators shall comply with the following tests as per IS:2544-1973 & IS: 5350(PT – III)-1971.

3.1 Type tests

a) Visual examination b) Verification of dimensions c) Visible discharge test d) Impulse voltage withstand test. e) Wet power-frequency voltage withstand test. f) Temperature cycle test. g) Electro-mechanical failing load test. h) Mechanical failing load test (for those of type B strin insulator units to which electro

mechanical failing load test (g) is not applicable. i) Twenty four hours mechanical strength test (for string insulators only when specified

by the purchaser). j) Puncture test k) Porosity test and

Page 4: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

4 | P a g e

l) Galvanising test.

3.2 Acceptance Tests The test samples after having withstood the routine tests shall be subjected to the following acceptance test in the rder indicated below:

a) Verification of dimensions. b) Temperature cycle test. c) Twenty four hours mechanical strength test(for string insulator units only when specified by

the purchaser) d) Electro-Mechanical failing load test. e) Puncture test f) Porosity test and g) Galvanising test.

3.3 Routine Test

a) Visual examination. b) Mechanical routine test(for string insulator units only) and c) Electrical routine test(for string insulator units only)

3.4 Marking

3.4.1 Each Insulator shall be legibly and indelibly marked to show the following.

a) Name and trade mark of the manufacturer. b) Month and year of manufacture c) Minimum failing load in Newtons d) Country of the manufacturer and e) ISI Certification mark, if any. f) Specific Parameters & Layout Conditions.

3.4.2 Marking on porcelain shall be printed and shall be applied before firing. 3.5 Packing

All insulators (without fittings) shall be packed in wooden crates suitable for easy but rough handling and acceptable for rail transport. Where more than one insulator are packed in a crate, wooden separators shall be fixed between the insulators to keep individual insulators in position without movement within the crate.

Page 5: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

5 | P a g e

GUARANTEED TECHNICAL PARTICULARS FOR 33 KV POST INSULATOR

Slno. Description Unit Specified Bidder’s Offer UNIT STACK

1

Manufacture Name To be Submitted by Bidder

2

Address of Manufacture To be Submitted by Bidder

3

Reference Standard (s) of Insulator

IS: 2544-1973 & IS:5350(PT-III)-1971

4 Height mm 254 508

5 Insulating Part Diameter mm

192

192

6 Pitch Circle Diameter

a) Top Metal Fitting mm 76

76

b) Bottom Metal Fitting mm

76

76

7

Minimum creepage Distance

mm 450

900

8 Cantilever Strength

a) Upright Kgf

900

459

b) Inverted Kgf 700

340

9 Tensile Strength Kgf

3060

3060

10 Torsional Strength Kgfm 70 70

10 Compression Strength Kgf

4600

4600

11 Nominal System Voltage KV(rms) 22 33

12

Highest System Voltage

KV(rms) 24

36

13 r frequency withstand voltage

(Dry)

KV(rms)

75

140

14 r frequency withstand voltage

(Wet)

KV(rms)

55

90

15 Impulse-withstand test Voltage (1.2x50 microsecond wave)

Caps Padestal

a)

Positive

KVP

125

190

b)

Negative

KVP 125

190

16 Material of Cap Aluminium Alloy Cap

17 Drawing & Sample To be submitted by bidder

NB- Every insulator should bear the marking of manufacturer’s name & Purchaser’s name and ISI mark.

Page 6: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

6 | P a g e

Name & Signature of Bidder with seal

TECHNICAL SPECIFICATION 11 KV POST INSULATOR

1. Scope- This specification covers the manufacture, testing and works supply and delivery of 11KV post insulators. The Porcelain insulators shall conform to IS: 731-1971 amended upto date. Small fittings like spring washers, nuts etc may be electro-galvanised.

Frequency : ( 50 ± 3%)Hz Nominal System Voltage : 11 K V Maximum System Voltage : 12 KV No. of phases : 3 Power frequency one minute withstand(Dry) : 75 KV Neutral Earthing arrangement System : Effectively Earthed

3.Requirements:

The post type insulators shall be suitable for outdoor use and cap & base type. Caps & base shall have plain machined faces & zigs shall be used for drilling bolt holes on the cap & in the base for easy & perfect assembly. Regarding Test for Mechanical strength for post Insulators, all the necessary tests are as per 9.6.5.1, 9.6.5.2, & 9.6.5.3 of IS:2544-1973 with latest amendments are to be carried out at the manufacturer‟s premises. For each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows :

i. Requisite numbers of set Screws & Spring Washers for assembling the Post Insulator unit. ii. Requisite numbers of set screws & spring washers for fixing bus-bar Support to the cap in the

top Post Insulator. iii. One set of Bolts, Nuts & Washers or Lock nuts & plain washers for mounting the Insulators on

the support steel structures of bus support. iv. 5% spare Nuts & Bolts with washers shall have to be supplied of no extra cost by the purchaser with each consignment.

4. Creepage Distances :

The minimum creepage distance shall 30 mm/KV.

5. Tests:

Suitable number of individual units shall be subject to the following tests in accordance with IS:731/1971 with its latest amendments

6. Test Certificate :

The Bidder shall furnish detailed type test reports of the offered post Insulators at the NABL approved laboratories to prove that the Disc Insulators offered meet the requirements of the specification. These Type Tests should have been carried out within five years prior to the date of opening of this tender. i) Their offered Insulators are already fully type tested at approved Laboratory within five

Page 7: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

7 | P a g e

years prior to the date of opening of this tender. ii) There is no change in the design of type tested Insulators and those offers against this

tender.

7. Testing Facilities :

The Bidder must clearly indicate what testing facilities are available in the works of the manufacturer and whether facilities are adequate to carry out all Routine & acceptance Tests. These facilities should be available to Purchaser’s Engineers if deputed or carry out or witness the tests in the manufacturer works. If any test cannot be carried out at the manufacturer's work, the reasons should be clearly stated in the tender. The insulators shall be tested in accordance with the procedure detailed in IS-731/1971 amended up to date.

8. Drawings :

The tender shall be accompanied with the detailed drawings showing the dimensions of the

individual insulator, giving all the design dimensions of various component parts. Generally it

shall be as per IS.

9. Markings :

Each insulator shall be legibly and indelibly marked to show the following:

a) Name or trade mark of the manufacturer. b) Voltage Type c) Month and year of manufacturing. d) Country of Manufacturer e) ISI certificate mark

10. Packing : All insulators shall be packed in crates or boxes suitable for rough handling. Packing shall be

marked with the strength and KV rating.

Page 8: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

8 | P a g e

GUARANTEED TECHNICAL PARTICULARS FOR 11 KV POST INSULATOR

Slno. Description Specified Bidder’s Offer

1 Name of Manufacturer. & Address

To be specified by the bidder

2 Location of type testing To be specified by the bidder 3 Applicable standard IS-731/1971 with latest

amendment

4 Nominal System Voltage 11 KV 5 Highest System voltage 12 KV 6 Visible discharge Test voltage

(Minimum) 9 KV

7 Impulse withstand voltage +(1.2/50 microsecond wave)

90 KVp (+ve) and 105 KVp(-ve)

8 Impulse flashover voltage+(1.2/50

microsecond wave)

95 KVp (+ve) and 120 KVp (-ve)

9 1min. power frequency flashover Voltage kV. (Dry)

70 KV

10 1min. power frequency flashover Voltage kV.(Wet)

45 KV

11 Cantilever strength a. Upright 65 Kg(Min) b. Inverted 400 Kg(Min) 12 Tensile strength 2050 Kg 13 Torsion strength 34 m-Kg 14 Compression strength 3600 Kg 15 Conforming standard As per IS 16 Drawing & Sample To be submitted by Bidder

NB- Every insulator should bear the marking of manufacturer’s name & Purchaser’s name and ISI mark.

Name & Signature of Bidder with seal

Page 9: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

9 | P a g e

TECHNICAL SPECIFICATIONS OF 33 KV PIN INSULATOR 1.0 Scope of Work:

This Specification covers design, engineering, manufacture, assembly, stage testing, inspection & testing before supply and delivery at site of the 33KV Pin Insulator.

2.0 APPLICABLE STANDARDS

Unless otherwise stipulated in this specification, the insulators shall comply with the Indian standard specification IS:731-1971 and the insulator fittings with IS:2486(Pt . I )-1971 and IS:2486(Pt . II)-1974 or the latest version thereof.

3.0 INSULATORS 3.1 General Requirements

3.1.1 The Porcelain shall be sound, free from defects, thoroughly vitrified and smoothly glazed.

3.1.2 Unless otherwise specified, the glaze shall be brown in colour. The glaze shall cover all the

porcelain parts of the insulator except those areas which serve as supports during firing or are left unglazed for the purpose of assembly.

3.1.3 The design of the insulator shall be such that stresses due to expansion and contraction in any

part of the insulator shall not lead to deterioration. The porcelain shall not engage directly with hard metal.

3.1.4 Cement used in the construction of the insulator shall not cause fracture by expansion or

loosening by contraction and proper care shall be taken to locate the individual parts correctly during cementing. The cement shall not give rise to chemical reaction with metal fittings, and its thickness shall be as uniform as possible.

3.2 Creepage Distance The minimum creepage distance shall be as under:

Highest System Voltage

Normal and Moderately Polluted Atmospheres(total)

Heavily polluted Atmospheres(Total)

(1) (2) (3) 36 KV 580 mm 840 mm

Note: For insulator used in an approximately vertical position the values given in col.(2) or (3) shall apply. For insulators used in an approximately horizontal position, the value given in col. (2) shall apply but the value in Col.(3) may be reduced by as much as 20%.

3.3 Tests: The insulators shall comply with the following tests as per IS:731-1971.

3.3.1 Type tests

Page 10: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

10 | P a g e

a) Visual examination b) Verification of dimensions c) Visible discharge test d) Impulse voltage withstand test. e) Wet power-frequency voltage withstand test. f) Temperature cycle test. g) Electro-mechanical failing load test. h) Mechanical failing load test (for those of type B strin insulator units to which

electro mechanical failing load test (g) is not applicable. i) Twenty four hours mechanical strength test (for string insulators only when specified by the purchaser). j) Puncture test k) Porosity test and l) Galvanising test.

3.3.2 Acceptance Tests The test samples after having withstood the routine tests shall be subjected to the following acceptance test in the rder indicated below:

a) Verification of dimensions. b) Temperature cycle test.

c) Twenty four hours mechanical strength test(for string insulator units only when specified by the purchaser)

d) Electro-Mechanical failing load test. e) Puncture test f) Porosity test and g) Galvanizing test.

3.3.3 Routine Test a)Visual examination. b) Mechanical routine test (for string insulator units only) and c) Electrical routine test (for string insulator units only)

3.4 Marking 3.4.1 Each Insulator shall be legibly and indelibly marked to show the following.

a) Name and trade mark of the manufacturer. b) Month and year of manufacture c) Minimum failing load in Newtons d) Country of the manufacturer and e) ISI Certification mark,if any. f) Specific Parameters & Layout Conditions.

3.4.2 Marking on porcelain shall be printed and shall be applied before firing. 3.5 Packing

All insulators (without fittings) shall be packed in wooden crates suitable for easy but rough handling and acceptable for rail transport. Where more than one insulator are packed in a crate, wooden separators shall be fixed between the insulators to keep individual insulators

Page 11: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

11 | P a g e

in position without movement within the crate.

GURANTEED TECHNICAL PARTICULARS OF 33KV PIN INSULATOR Sl.No.

Description

Specified

Bidder's offer

1

Manufacture Name

2 Address of Manufacture

3 Normal working voltage

33KV(rms)

4

High system voltage 36KV(rms)

5 Visible Discharge Voltage dry

PF

27KV(rms)

6 Dry Power frequency 1

Minute withstand voltage

95KV(rms)

7

Wet Power frequency 1 Minute withstand voltage

75KV(rm

s)

8

PF puncture withstand voltage 180KV(rms)

9 Impulse withstand voltage 170 KV 11 Minimum failing load 10KN 12 Minimum creepage distance 580mm 13 Colour of glaze Brown 14 Weight per unit To be submitted by bidder 15 Size of Insulator

a) Height To be submitted by bidder b) Diameter To be submitted by bidder

16 Material of thimble Lead 17 Steel head Larg

e

18 Standard IS: 731/1971

19

Tolerance Tolerance will be allowed as per

IS:731/1971 or latest amendments if any.

20

Drawing & Sample

To be submitted by bidder

PACKING: All insulators shall be packed in wooden crates suitable for easy but rough handling &

acceptable for road transport. Where more than one insulator are packed in a crate, Separator shall be fixed between the insulators to keep individual insulator in position without movement in the crate.

NB- Every insulator should bear the marking of manufacturer’s name & Purchaser’s name and ISI mark.

Page 12: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

12 | P a g e

Name & Signature of Bidder with seal

11 KV PIN INSULATOR

1.SCOPE :

The specification cover the manufacture, testing at works supply and delivery of Porcelain insulators for overhead power lines with a nominal voltage below 12KV . Both Pin and Shackle type insulators are covered. 2.APPLICABLE STANDARDS:

Except when they conflict with the specific requirements of this specification, the insulators shall

comply with IS : IS:731 & IS: 3188 or the latest version thereof.

3.GENERAL REQUIREMENTS:

The porcelain shall be sound, free from defects, thoroughly vitrified and smoothly glazed. The design

of the insulators shall be such that the stresses due to expansion and contraction in any part of the

insulator shall not lead to its deterioration. The glaze shall be brown in color for insulators. The glaze

shall cover the entire porcelain surface parts except those areas that serve as supports during firing.

The insulators shall be suitable for use with all Aluminum Conductor or Copper conductor or ACSR

upto 100 sq.mm. The insulators should withstand the conductor tension the reversible wind load as

well as the high frequency vibrations set due to wind.

4.SYSTEM CONDITIONS:

Frequency : 50 Hz

Nominal System Voltage : 11KV Maximum System Voltage LT System : 12 KV Minimum LT Voltage : 11KV

Power frequency one minute withstand Voltage(wet): 35KV

5. TYPE OF INSULATORS:

The standard Pin insulators shall be of designation Type –B of IS : 731 or its latest revision.

6. TESTS:

6.1 Type tests:

a) Visual examination

b) Verification of dimensions

c) Temperature cycle test

d) Dry one minute power frequency withstand test

Page 13: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

13 | P a g e

e) Wet one minute power frequency withstand test

f) Mechanical strength test

g) Porosity test

6.2 Acceptance test:

The insulators, after having withstood the routine test shall be subjected to the following

acceptance tests in the order given below:

a) Verification of Dimensions.

b) Temperature cycle test

c) Mechanical strength test

d) Porosity test

6.3 Routine tests:

ii) Visual examination

7.TESTING FACILITIES:

a. The Bidder must clearly indicate what testing facilities are available in the works of the

manufacturer and whether the facilities, are adequate to carry out all the routine as well as type tests.

These facilities should be made available to Purchaser‟s Engineers if deputed to carry out or witness

the tests. If any tests cannot be carried out at the manufacturer‟s works, the reasons should be clearly

stated in the tender.

b. The Bidder shall furnish detailed type test reports of the offered 11KV Pine insulator as per

clause 6.1 of this specification. All the above Type Tests shall be carried out at laboratories, which are

accredited, by the National Accreditation Board of Testing and Calibration Laboratories (NABL) of

Government of India to prove that the insulators offered meet the requirements of the specification.

These Type Tests should have been carried out within five years prior to the date of opening of this

tender. c. There offered L.T. shackle Insulators & pin insulators are already fully Type Tested at Laboratories

accredited by the National Accreditation Board of Testing and Calibration Laboratories (NABL) within

five years prior to the date of opening of the tender.

There is no change in the design of Type tested L.T. shackle Insulators and those offers against this

tender.

8. Drawings :

The tender shall be accompanied with the detailed drawings showing the dimensions of the

Page 14: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

14 | P a g e

individual insulator, giving all the design dimensions of various component parts. Generally it

shall be as per IS.

9. MARKING:

a. Each insulator shall be legibly and indelibly marked to show the

following:

i) Name of Purchaser- NESCO

ii)Name or trade mark of the manufacturer

iii) Year of manufacturer

iv) ISI certificate, mark, if any.

b. Marking on porcelain shall be applied before firing.

10. Packing :

All insulators shall be packed in crates or boxes suitable for rough handling. Packing shall be marked with the strength and voltage rating.

Page 15: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

15 | P a g e

GUARANTEED TECHNICAL PARTICULARS 11 KV PIN INSULATOR

Sl. No.

Description Specific Requirement Bidders offer

Name of Manufacturer. & Address To be specified by the bidder

Location of type testing To be specified by the bidder

Applicable standard IS: 731,IS 3188 or the latest version thereof

1 Normal working voltage 11 Kv (rms) 2 High system voltage. 12 Kv (rms) 3 Visible Discharge voltage dry PF. 9 Kv (rms) 4 1 Minute withstand voltage wet PF. 65 Kv (rms) 5 1 Minute withstand voltage................. 35 Kv (rms) 6 PF puncture withstand voltage. 110 Kv (rms) 7 Impulse withstand voltage :

(+ ve) 80 Kv peak (- ve) 80 Kv peak 8 Impulse flashover voltage :

(+ ve) 90 Kv peak (- ve) 120 Kv peak 9 Minimum failing load. 5 KN. 10 Minimum creepage distance. 240 mm. 11 Colour of glaze. Brown. 12 Weight per unit. 1.4 Kg. (Apprx.) 13 Size of insulator. (Height) 125 mm.

(Diameter)

125 mm. 14 Material of thimble. Lead. 15 Steel head. Small head. 16 Standard. IS : 731/1971. 17 Tolerance. Tolerance will be allowed as per IS :

731/1971 or latest amendments if any. 18 Drawing To be submitted

19 Conforming standard As per IS

NB- Every insulator should bear the marking of manufacturer’s name & Purchaser’s name and ISI mark.

Page 16: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

16 | P a g e

Name & Signature of Bidder with seal

TECHNICAL SPECIFICATION OF 70KN (B&S) DISC INSULATOR TECHNICAL SPECIFICATION OF 90KN (B&S) DISC INSULATOR SCOPE: This specification provides for design, manufacture, engineering, inspection and testing before dispatch packing and delivery FOR (destination) for Indian manufacturers of disc. Insulators as per technical requirements furnished in this specification.

These insulators are to be used in suspension and tension insulators strings for the suspension and anchoring of the bus-bar conductors.

Following is the list of documents constituting this package.

(i) Technical specification.

(ii) Technical data sheet.

(iii) Drawings of insulators

All the above volumes along with amendments there of shall be read and interpreted together. However, in case of a contradiction between the ―Technical Specification and any other volume, the provisions of this volume will prevail.

The insulators shall conform in all respects to high standards of engineering, design workmanship and latest revisions of relevant standards at the time of offer and purchaser shall have the power to reject any work or material which in his judgment, is not in full accordance therewith.

STANDARDS:

Except as modified in this specification, the disc insulators shall conform to the following Indian Standards, which shall mean latest revisions and amendments. Equivalent International and Internally recognized standards to which some of these standards generally correspond are also listed below.

Sl. No. Indian

Standard

Title. International

Standard

1. IS: 206 Method for Chemical Analysis of Slab Zinc.

2. IS: 209 Specification for Zinc. BS: 3436

3. IS: 731 Porcelain insulators for overhead

power lines with a normal voltage greater than 1000V

BS: 137(I&II);

IEC 274 IEC 383

4. IS: 2071

Part-(I) Part-(II) Part-(III)

Method of High Voltage Testing.

Page 17: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

17 | P a g e

5. IS: 2121

(Part-I)

Specification of Conductors and Earth wire Accessories for

Overhead Power lines. Armour Rods, Binding wires and tapes

for conductor.

6. IS: 2486 Specification for Insulator fittings

for overhead power lines with a nominal voltage greater than

1000V. Part – I General Requirement and Tests. BS: 3288 Part – II Dimensional Requirements. IEC: 120 Part – III Locking devices. IEC: 372

7. IS: 2629 Recommended practice for Hot Dip Galvanisation for iron and steel.

8. IS: 2633 Testing for Uniformity of Coating of Zinc coated articles.

9. IS: 3138 Hexagonal Bolts & Nuts. ISO/R 947 & ISO/R272

10. IS: 3188 Dimensions for Disc Insulators. IEC: 305 11. IS: 4218 Metric Screw Threads ISO/R 681969

R 261963,

R 262-1969 & R965-1969

12. IS: 6745 Determination of weight of zinc

coating on zinc coated iron and steel articles.

13. IS: 8263 Methods of RIV Test of HV

insulators.

IEC 437 NEMA

Publication No.107/1964

CISPR

14. IS: 8269 Methods for switching impulse test on HV insulators.

IEC: 506

15. Thermal mechanical performance test and mechanical performance

test on string insulator units.

IEC: 575

16. IEC Long Rod Insulators IEC-433

The standards mentioned above are available from:

Reference. Abbreviation. Name & Address:

Page 18: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

18 | P a g e

BS British Standards, British Standards

Institution, 101, Pentonvile Road, N-19

IEC /

CISPR

International Electro technical commission

Electro Technique International. 1, Rue de verembe Geneva SWITZERLAND. IS Bureau of Indian Standards, Manak Bhavan,

9 Bahadurshah Zafar Marg, New Delhi-

ISO International Organisation for

Standardization. Danish Board of Standardization Dansk Standardizing Sraat Aurehoegvej-12 DK-2900 Helleprup

DENMARK. NEMA National Electric Manufacturers Association

1`55, East 44th. Street New York, NY 10017

PRINCIPAL PARAMETERS.

DETAILS OF DISC INSULATORS:

The Insulator strings shall consist of standard discs for use in three phases, 50 Hz 33/11KV S/S, 33 KV & 11KV Lines of NESCO Utility in a moderately polluted atmosphere. The discs shall be cap and pin, ball and socket type, radio interference and have characteristics as shown in Table-I and all ferrous parts shall be hot dip galvanized as per the latest edition of IS 2629. The zinc to be used for making sleeves shall be 99.95 % pure.

The size of disc insulator, minimum creepage distance the number to be used in different type of strings, their electromechanical strength and mechanical strength of insulator string along with hardware shall be as follows:

Sl.

No

Type of

String.

Size of disc.

Insulator

(mm)

Minimum

creepage distance of

each disc(mm)

No. of

standard discs

33KV

Electro-mechanical strength of insulator string fittings (KN)

1. Single

suspension

255x145 430 1x3 70KN/90KN Antifog Insulator

2. Double

suspension

-do- -do- 2x3 70KN/90KN Antifog Insulator

3. Single Tension 280x170 320 1x4 70KN/90KN Normal Insulator

4. Double

Tension

-do- -do- 2x4 70KN/90KN Normal Insulator

Page 19: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

19 | P a g e

SPECIFICATION DRAWINGS:

The specification in respect of the disc insulators are described. These specification for information and guidance of the Bidder only. The drawings to be furnished by the supplier shall be as per his own design and manufacture and in line with the specification.

GENERAL TECHNICAL REQUIREMENTS:

Porcelain:

The porcelain used in the manufacture of the shells shall be ivory white nonporous of high dielectric, mechanical and thermal strength, free from internal stresses blisters, laminations, voids, forgone matter imperfections or other defects which might render it in any way unusable for insulator shells. Porcelain shall remain unaffected by climatic conditions ozone, acid, alkalis, zinc or dust. The manufacturing shall be by the wet process and impervious character obtained by through verification.

The insulator shall be made of highest grade, dense, homogeneous, wet-process porcelain, completely and uniformly vitrified throughout to produce uniform mechanical and electrical strength and long life service. The porcelain shall be free from warping, roughness, cracks, blisters, laminations, projecting points foreign particles and other defects, except those within the limits of standard accepted practice. Surfaces and grooves shall be shaped for easy cleaning. Shells shall be substantially symmetrical.

Porcelain glaze:

Surface to come in contact with cement shall be made rough by stand glazing. All other exposed surfaces shall be glazed with ceramic materials having the same temperature coefficient of expansion as that of the insulator shell. The thickness of the glaze shall be uniform throughout and the colour of the glaze shall be brown. The Glaze shall have a visible luster and smooth on surface and be capable of satisfactory performance under extreme tropical climatic weather conditions and prevent ageing of the porcelain. The glaze shall remain under compression on the porcelain body throughout the working temperature range.

METAL PARTS:

(i) Cap and Ball Pins:

Ball pins shall be made with drop forged steel caps with malleable cast iron. They shall be in one single piece and duly hot dip galvanized. They shall not contain parts or pieces joined together welded, shrink fitted or by any other process from more than one piece of materials. The pins shall be of high tensile steel, drop forged and heat-treated. The caps shall be cast with good quality black heart malleable cast iron and annealed. Galvanizing shall be by the hot dip process with a heavy coating of zinc of very high purity. The bidder shall specify the grade composition and mechanical properties of steel used for caps and pins. The cap and pin shall be of such design that it will not yield or distort under the specified mechanical load in such a manner as to change the relative spacing of the insulators or add other stresses to the shells. The insulator caps shall be of the socket type provided with nonferrous metal or stainless steel cotter pins and shall provide positive locking of the coupling.

(ii) Security Clips:

The security clips shall be made of phosphor bronze or of stainless steel.

FILLER MATERIAL:

Cement to be used, as a filler material be quick setting, fast curing Portland cement. It shall not cause

Page 20: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

20 | P a g e

fracture by expansion or loosening by contraction. Cement shall not react chemically with metal parts in contact with it and its thickness shall be as small and as uniform as possible.

MATERIALS DESIGN AND WORKMANSHIP:

GENERAL:

All raw materials to be used in the manufacture of these insulators shall be subject to strict raw material quality control and to stage testing/ quality control during manufacturing stage to ensure the quality of the final end product. Manufacturing shall conform to the best engineering practices adopted in the field of extra high voltage transmission. Bidders shall therefore offer insulators as are guaranteed by them for satisfactory performance on Transmission lines.

The design, manufacturing process and material control at various stages be such as to give maximum working load, highest mobility, best resistance to corrosion, good finish elimination of sharp edges and corners to limit corona and radio interference voltages.

INSULATOR SHELL:

The design of the insulator shells shall be such that stresses due to expansion and contraction in any part of the insulator shall not lead to deterioration. Shells with cracks shall be eliminated by temperature cycle test followed by mallet test. Shells shall be dried under controlled conditions of humidity and temperature.

METAL PARTS:

i. The twin ball pin and cap shall be designed to transmit the mechanical stress to the shell by compression and develop uniform mechanical strength in the insulator. The cap shall be circular with the inner and outer surfaces concentric and of such design that it will not yield or distort under loaded conditions. The head portion of the pinball shall be suitably designed so that when the insulator is under tension the stresses are uniformly distributed over the pinhole portion of the shell. The pinball shall move freely in the cap socket either during assembly of a string or during erection of a string or when a string is placed in position.

ii. Metal caps shall be free from cracks, seams, shrinks, air holes, blowholes and rough edges. All metal surfaces shall be perfectly smooth with no projecting part or irregularities, which may cause corona. All load bearing surfaces shall be smooth and uniform so as to distribute the loading stress uniformly. Pins shall not show any microscopically visible cracks, inclusions and voids.

GALVANIZING:

All ferrous parts, shall be hot dip galvanized in accordance with IS: 2629. The zinc to be used for galvanizing shall conform to grade Zn 99.5 as per IS: 209. The zinc coating shall be uniform, smoothly adherent, reasonably light, continuous and free from impurities such as flux, ash, rust stains, bulky white deposits and blisters. Before ball fittings are galvanized, all die flashing on the shank and on the bearing surface of the ball shall be carefully removed without reducing the designed dimensional requirements.

CEMENTING:

The insulator design shall. Be such that the insulating medium shall not directly engaged with hard metal. The surface of porcelain and coated with resilient paint to offset the effect of difference in thermal expansions of these materials. High quality Portland cement shall be used for cementing the

Page 21: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

21 | P a g e

porcelain to the cap & pin.

SECURITY CLIPS (LOCKING DEVICES)

The security clips to be used as locking device for ball and socket coupling shall be ‗R‘shaped hump type to provide for positive locking of the coupling as per IS: 2486 (Part-IV). The legs of the security clips shall allow for spreading after installation to prevent complete withdrawal from the socket. The locking device shall resilient corrosion resistant and of sufficient mechanical strength. There shall be no possibility of the locking device to be displaced or be capable of rotation, which placed in position, and under no circumstances shall it allow separation of insulator units and fittings. ‗W‘type security clips are also acceptable. The hole for the security clip shall be counter sunk and the clip shall be of such design that the eye of the clip may be engaged by a hot line clip puller to provide for disengagement under energized conditions. The force required for pulling the clip into its unlocked positions shall not be less than 50 N (5 kg.) or more than 500 N (50 kgs.).

MARKING:

Each insulator shall have the rated combined mechanical and electrical strength marked clearly on the porcelain surface. Each insulator shall also bear symbols identifying the manufacturer, month, and year of manufacture. Marking on porcelain shall be printed, not impressed, and shall be applied before firing.

BALL AND SOCKET DESIGNATION:

The dimensions of the ball and sockets for 70 and 90 KN discs shall be of 16 mm and for 120

KN and 160 KN discs shall be of 20 mm designation in accordance with the standard dimensions stated in IS: 2486 (Part-II).

DIMENSIONAL TOLERANCE OF INSULATOR DISCS:

It shall be ensured that the dimensions of the disc insulators are within the limits specified below:

a) Diameter of Disc (mm)

Standard Maximum Minimum

70 KN Disc 255 266 244

90 KN Disc 255 266 244

b)Ball to Ball spacing Between Discs (mm)

Standard Maximum Minimum

70 KN Disc 145 149 141

90 KN Disc 145 149 141

INTERCHANGEABILITY:

The insulators inclusive of the ball and socket fittings shall be of standard design suitable for use with hardware fittings of any make conforming to relevant Indian Standards.

Page 22: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

22 | P a g e

FREEDOM FROM DEFECTS:

Insulators shall have none of the following defects:

1) Ball pin shake.

2) Cementing defects near the pin like small blow holes, small hair cracks lumps etc.

3) Sand fall defects on the surface of the insulator.

INSULATOR STRINGS:

TYPE AND RATING:

The insulator strings shall be formed with standard discs described in this specification for use on 3 phases 33 KV 50 Hz effectively earthed systems in an atmosphere with pollution level as indicated in project synopsis. Suspension insulator strings for use with suspension/tangent supports are to be fitted with discs 70 KN EMS rating while tension insulator strings for use with Anchor / Tension towers are to be fitted with discs of 90 KN EMS level rating.

STRING SIZE:

The sizes of the disc insulator, the number to be used in different types of strings, their electro- mechanical strength and minimum nominal creep age distance shall be as given in this specification

Insulator units after assembly shall be concentric and coaxial within limits as permitted by Indian

Standards.

The strings design shall be such that when units are coupled together there shall be contact between the shell of one unit and metal of the adjacent unit.

DIMENSIONAL TOLERANCE OF INSULATORS DISCS

It shall be ensured that the dimensions of the long rod insulators are within the limits as per relevant IEC/ISS.

TESTS (FOR DISC INSULATORS) :

The following tests shall be carried out on the insulator string and disc insulators.

TYPE TEST:

This shall mean those tests, which are to be carried out to prove the design, process of manufacture and general conformity of the material and product with the intents of this specification. These tests shall be conducted on a representative number of samples prior to commencement of commercial production. The Bidder shall indicate his schedule for carrying out these tests.

ACCEPTANCE TESTS:

This shall mean these tests, which are to be carried out on samples taken from each lot offered for pre-dispatch inspection for the purpose of acceptance of the lot.

Page 23: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

23 | P a g e

ROUTINE TESTS:

This shall mean those tests, which are to be carried out on each insulator to check the requirements, which are likely to vary during production.

TESTS DURING MANUFACTURE:

Stage tests during manufacture shall mean those tests, which are to be carried out during the process of manufacture to ensure quality control such that the end product is of the designed quality conforming to the intent of this specification.

TEST VALUE:

For all type and acceptance tests the acceptance values shall be the value guaranteed by the bidder in the guaranteed technical particulars of the acceptance value specified in this specification of the relevant standard whichever is more stringent for that particular test.

TEST PROCEDURE AND SAMPLING NORMS:

The norms and procedure of sampling for the above tests shall be as per the relevant Indian

Standard or the internationally accepted standards. This will be discussed and mutually agreed to between the supplier and purchaser before placement of order. The standards and normal according to which these tests are to be carried out are listed against each test. Where a particular test is a specific requirement of this specification, the norms land procedure for the same shall be as mutually agreed between the supplier and the purchaser in the quality assurance programme.

TYPE, ROUTINE & ACCEPTANCE TESTS:

The following type test shall be conducted on a suitable number of individual unit components, materials or complete strings.

1.On complete insulator string with hardware fittings Standards BS:137(Part-I) IEC: 383

a) Power frequency voltage withstand test with

corona control rings and under wet condition.

b) Impulse voltage withstand test under dry condition.

c) Mechanical strength test. As per this specification.

2. On Insulators:

a) Verification of dimensions. :IS: 731

b) Thermal mechanical performance test: : IEC:575

c) Power frequency voltage withstand and flashover i) dry ii) wet :BS:173 d) Impulse voltage withstand flashover test (dry) : IEC: 383

e) Visible discharge test (dry) : IS:731

Page 24: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

24 | P a g e

All the type tests given under clause No.5.14 above shall be conducted on single suspension and Double Tension insulator string along with hardware fittings.

3. ACCEPTANCE TESTS: For insulator:

a) Visual examination : IS:731

b) Verification of dimensions. : IS:731

c) Temperature cycle test. : IS:731

d) Galvanizing test. : IS:731

e) Mechanical performance test. : IEC:575

f) Test on locking device for ball and socket coupling. :IEC-372

g) Eccentricity test.

h) Electro-mechanical strength test : As per this specification.

i) Puncture test. : IS:731

j) Porosity test. : IS:731

4. ROUTINE TESTS: For insulators:

a) Visual inspection. : IS:731

b) Mechanical routine test.

c) Electrical routine test. : IEC:383

ADDITIONAL TESTS:

The purchaser reserves the right for carrying out any other tests of a reasonable nature at the works of the supplier/ laboratory or at any other recognized laboratory/ research institute in addition to the above mentioned type, acceptance and routine tests at the cost of the purchaser to satisfy that the material complies with the intent of this specification.

CO-ORDINATION FOR TESTING:

For insulator strings, the supplier shall arrange to conduct testing of their disc insulators with the hardware fittings to be supplied to the purchaser by other suppliers. The supplier is also required to guarantee overall satisfactory performance of the disc insulator with the hardware fittings.

NOTE:

In respect of electrical tests on a complete string consisting of insulators and hardware guarantee of values of responsibility of testing shall be with hardware manufacturer of RIV corona and voltage distribution test and with insulator manufacturer for all other tests.

TEST CHARGES AND TEST SCHEDULE:

TYPE TEST:

The insulator offered shall be fully type tested as per this specification. In case the equipment of the type and design offered, has already been type tested in an independent test laboratory. The bidder

Page 25: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

25 | P a g e

shall furnish four sets of type test reports along with the offer. These tests must not have been conducted earlier than five years. The purchaser reserves the right to demand repetition of some or all type tests in the presence of purchasers‘ carrying representative. For this purpose the bidder may quote unit rates for carrying out each type test. These prices shall be taken into consideration for bid evaluation. For any change in the design/type already type tested and the design/type offered against this specification, purchaser reserves the right to demand repetition of tests without any extra cost.

ACCEPTANCE AND ROUTINE TEST:

All acceptance and routine tests as stipulated herein shall be carried out by the supplier in the presence of purchaser‘s representative.

Immediately after finalization of the programme of type/ acceptance/ routine testing, the supplier shall give sufficient advance intimation to the purchaser to enable him to depute his representative for witnessing the tests.

For type tests involving tests on a complete insulator string with hardware fittings, the purchaser will advice the supplier of the hardware fittings to provide the necessary fittings to the place of the test.

In case of failure of the complete string in any type tests, the supplier whose product has failed in the tests shall get the tests repeated at his cost. In case of any dispute, assessment of the purchaser as to the items that has caused the failure in any of the type tests shall be final and binding.

VOLTAGE DISTRIBUTION TEST:

a) The voltage across each insulator unit shall be measured by sphere gap method. The result obtained shall be converted into percentage and proportionate correction be applied as to give a total of 100% distribution.

b) The complete insulator string along with its hardware fitting excluding arcing horn corona controlling/grading ring and suspension assembly/dead end assembly shall be subject to a load equal to 50% of the specified minimum ultimate tensile strength (UTS) which shall be increased already rate to 68% of the minimum UTS specified. The load shall be held for five minutes and then removed. After removal of the load, the string components shall not show any visual deformation and it shall be possible to disassemble them by hand,. Hand tools may be used to remove cotter pins and loosen the nuts initially. The string shall then be reassembled and loaded to 50% of UTS and the load shall be further increased at a steady rate till the specified minimum UTS and held for one minute. No fracture should occur during this period. The applied load shall then be increased until the failing loads reached and the value recorded.

VIBRATION TEST:

The suspension string shall be tested in suspension mode, and tension string in tension mode

itself in laboratory span of minimum 30 meters. In the case of suspensions string a load equal to

600 Kg. shall be applied along with the axis of the suspensions string by means of turn buckle. The insulators string along with hardware fittings and two sub conductors throughout the duration of the test vibration dampers shall not be used on the test span. Both the sub- conductors shall be vertically vibrated simultaneously at one of the resonance frequencies of the insulator string (more than 10Hz) by means of vibration inducing equipment. The amplitude of vibration at the antipode point nearest to the string shall be measured and the same shall not be less than 120.4 being the frequency of vibration. The insulator strings shall be vibrated for five million cycles then rotated by 90 deg and

Page 26: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

26 | P a g e

again vibrated for 5 million cycles without any failure, after the test, the disc insulators shall be examined for looseness of pins and cap or any crack in the cement. The hardware fittings shall be examined to fatigue fatter and mechanical strength test. There shall be no deterioration of properties of hardware components and disc insulators after the vibration test. The disc insulators shall be subjected to the following tests as per relevant standards.

Test. Percentage of disc to be tested

a)Temperature cycle test followed by 60

Mechanical performance test.

b)Puncture test (for porcelain insulator only) 40

INSPECTION:

i. Purchaser and its representative shall at all times be entitled to have access to the works and to all places of manufacturer where insulators are manufactured and the supplier shall afford all facilities to them for unrestricted inspection of the works, inspection of materials, inspection of manufacturing process of insulators and for conducting necessary tests as specified herein.

ii. The supplier shall keep the purchaser informed in advance of the time of starting and of progress of manufacture of insulators in its various stages so that arrangements could be made for inspection.

iii.No material shall be dispatched from its point of manufacture unless the materials has been satisfactorily inspected and tested.

iv. The acceptance of any quantity of insulators shall in no way relieve the supplier of his responsibility for meeting all the requirement of this specification and shall not prevent subsequent rejection, if such insulators are later found to be defective.

IDENTIFICATION MARKING:

a) Each unit of insulator shall be legibly and indelibly marked with the trade mark of the supplier, the year of manufacture, the guaranteed combined mechanical and electrical strength in kilo-Newton abbreviated by ‗KN‘ to facilitate easy identification and proper use.

b) The marking shall be on porcelain for porcelain insulators. The marking shall be printed and not impressed and the same shall be applied before firing.

QUALITY ASSURANCE PLAN:

The bidder here under shall invariably furnish following information along with his offer, failing which the offer shall be liable for rejection.

a. Statement giving list of important raw materials, names of sub-suppliers for the raw materials, list of standards according to which the raw material are tested, list of tests normally carried out on raw materials in presence of bidder‘s representative, copies of test certificates.

b. Information and copies of test certificates as in (i) above in respect of bought out materials.

c. List of manufacturing facilities available.

Page 27: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

27 | P a g e

d. Level of automation achieved and lists of area where manual processing exists.

e. List of areas in manufacturing process, where stage inspections are normally carried out in quality control and details of such tests and inspection.

f. Special features provided in the equipment to make it maintenance free.

g. List of testing equipping available with the bidder for final testing of equipment specified and test plant limitation, if any, vis-à-vis the type, special, acceptance and routine tests specified in the relevant standards. These limitations shall be very clearly brought out in schedule of deviations from specified test requirements.

The supplier shall within 15 days of placement of order submit the following information to the owner.

List of raw material and the names of sub-suppliers selected from those furnished along with the offer.

CHEMICAL ANALYSIS OF ZINC USED FOR GALVANIZING.

Samples taken from the zinc ingot shall be chemically analyzed as per IS: 209. The purity of zinc shall not be less than 99.95%.

TESTS FOR FORGINGS:

The chemical analysis hardness tests and magnetic particle inspection for forgings will be as per the internationally recognized procedures for these tests. The sampling will be based on heat number and heat treatment batch. The details regarding test will be as discussed and mutually agreed to by the supplier and purchaser in quality assurance programme.

TESTS ON CASTING:

The chemical analysis mechanical and metallographic tests and magnetic particle inspection for castings will be as per the internationally recognized procedures for these tests. The samplings will be based on heat number and heat treatment batch. The details regarding test will be as discussed and mutually agreed to by the supplier and purchaser in quality assurance programme.

HYDRAULIC INTERNAL PRESSURE TEST ON SHELLS:

The test shall be earned out on 100% shells before assembly. The details regarding test will be as discussed and mutually agreed to by the suppliers and purchaser in Quality Assurance Programme.

THERMAL MECHANICAL PERFORMANCE TEST:

The thermal mechanical performance test shall be carried out on minimum 15 number of disc insulators units as per the procedure given in IEC 575. The performance of the insulator unit shall be determined by the same standard.

ECCENTRICITY TEST:

The insulator shall be vertically mounted on a future using dummy pin and socket. A vertical scale with horizontal slider shall be used for the axial run out. The pointer shall be positioned in contact with the bottom of the outermost petticoat of the disc. The disc insulators shall be rotated with reference to the fixture and the slider shall be allowed to move up and down on the scale but always maintaining contact with the bottom of the outer most petticoats. After one full rotation of the disc the maximum and minimum position the slider has reached on the scale can be found out. Difference between the above two readings shall satisfy the guaranteed value for axial run out.

Page 28: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

28 | P a g e

Similarly using a horizontal scale with veridical slider the radial run out shall be measured. The slider shall be positioned on the scale to establish contact with the circumstance of the disc insulator and disc insulator rotated on its future always maintaining the contact. After one full rotation of the disc the maximum and minimum position the slider has reached on the scale can be found out. Difference between the above two readings shall satisfy the guaranteed value for axial run out.

CRACK DETECTION TEST:

Crack detection test shall be carried out on each ball and pin before assembly of disc unit. The supplier shall maintain complete record of having conducted such tests on each and every piece of ball pin The bidder shall furnish full details of the equipment available with him for crack test and also indicate the test procedure in detail.

DISC INSULATOR (B&S) Type: Bidder should offer 11KV/33 KV Disc Insulator (B & S type) suitable for overhead power line Conforming to IS:731/1971 (2nd Revision), (Amendments - 6), Reaffirmed – 1991 & Guaranteed Technical Particulars. Type test certificates from CPRI or accredited NABL laboratory should be furnished

GUARANTEED TECHNICAL PARTICULARS DISC INSULATOR B & S TYPE

Sl. No.

Description Unit 70KN. 90 KN Bidder’s Offer

1. Manufacture’s Name & Address

To be specified by bidder

To be specified by bidder

2. Type of Insulator Ball T Socket Ball T Socket 3 Size of Ball & Socket 16B 16B 4 Dimensions a) Disc Diameter mm 255 255 b) Unit spacing mm 145 145 c) Creepage distance of single

insulator mm 430 430

5 Electromechanical strength of single insulator

KN 70 90

6 Materials of Shell Porcelain Porcelain 7 Dry one minute power 80 80 6 Wet one minute power

Kv(rms) 45 45

7 Dry power frequency flashover. Kv(rms) 85 85 8 Wet power frequency flashover. Kv(rms) 50 50 9 Dry impulse withstand positive

& negative. Kv

(Peak) 170 170

10 Impulse flashover 1.2 x 50 microsecond (Positive)

Kv (Peak)

125 125

Page 29: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

29 | P a g e

11 Impulse flashover 1 x 50 microsecond (Negative)

Kv (Peak)

125 125

12 Power frequency puncture voltage

Kv 1.3 times the actual drive flashover voltage of the

1.3 times the actual drive

flashover voltage of

13 High system voltage. Kv 36 36 14 Visible Discharge voltage. Kv 27 27 15 Weight/Unit. Kg. To be specified by

bidder To be specified by

bidder

16 Marking :-- Each insulator will be legibly marked to show the following :

(a) Name of the Purchaser :-- NESCO

(b) Name or trademark :-- (c) Month & year of manufacturing :-- (d) Minimum failing load. PACKING: -- All insulators shall be packed suitably for easy but rough handling &

acceptable for road transport. Where more than one insulator is packed in a crate, separator shall be fixed between the insulators to keep individual insulator in position without movement in the crate.

NB- Every insulator should bear the marking of manufacturer’s name & Purchaser’s name and ISI mark.

Name & Signature of Bidder with seal

Page 30: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

30 | P a g e

11 KV Disc insulator 45 KN (T&CType)

TECHNICAL SPECIFICATION FOR 11 KV 45 KN DISC INSULATORS

1. SCOPE : This specification covers the manufacture, testing and works supply and delivery of 11 KV Disc insulators. The Porcelain insulators shall conform to IS:731-1971ammended upto date. Insulators shall be of Tongue & Clevis type (T&C).Disc insulators made of glazed porcelain shall be used as insulators on dead ends or on suspension type lines of 11 KV and above. Tongue & Clevis type (T & C) disc insulators of mechanical strength not less than 45KN shall be used confirming to IS: 731/1971. These shall be mounted on metallic cross-arms with the help of suitable non-magnetic galvanised iron hardware fittings. Small fittings like spring washers, nuts etc may be electro-galvanised.

2. SERVICE CONDITIONS :

The insulators to be supplied against this specification shall be suitable for satisfactory continuous operation under the following tropical conditions.

2.1.1 Maximum ambient temperature (Degree C) … 50 2.1.2 Minimum ambient temperature (Degree C) … 3.5 2.1.3 Relative Humidity (%) … 10 to 100 2.1.4 Maximum Annual Rainfall (mm) … 1450 2.1.5. Maximum Wind pressure (kg/m.sq.) … 150 2.1.6 Maximum wind velocity (km/hour) … 45 2.1.7 Maximum altitude above mean sea level (meter) … 1000 2.1.8 Isoceraunic level (days/year) … 50 2.1.9 Seismic level (Horizontal acceleration) … 0.3 g 2.1.10 Moderately hot and humid tropical climate

conductive to rust and fungus growth

3. System Particulars :

a) Nominal System Voltage

11 KV b) Corresponding highest system Voltage

c) Frequency d) Number of phase e) Neutral earthing f) Min. Impulse withstand voltage

12 KV 50 Hz with 3% tolerance 3 effectively grounded. 75 KV

4. Standards :

Unless otherwise specified elsewhere in the specifications insulators shall confirm to the latest

Page 31: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

31 | P a g e

revisions of all relevant standards .

5. General Requirements

i) The Porcelain insulators shall generally conform to IS:731-1971 and any amendments up to date to the same .

ii) Conductors :

The Disc Insulators will be used on lines on which the conductors will be A.A.A.

Conductor of size up to 100 sq. mm. The insulators should withstand the conductor

tension, the reversible wind load as well as the high frequency vibrations due to wind.

iii) Type

a) Insulator shall be suitable for both the suspension and strain type of load & shall be of Tongue and Clevis type. The insulators shall conform to Type ‘B’ of IS:731-1971.

b) Diameter of porcelain disc insulator shall be 255mm . The center to center distance between

Tongue and Clevis shall be 145mm.

c) Insulator Ends.

Disc Insulators shall have Tongue and Cleave ends. The security clips will have to be provided as per fig. 25 of I.S. 2486 (Part-2) 1989 ( amended up to date) REC Specification 3/1971(Revised 1993).

d) The colour of the units shall be brown for 45 KN Disc Insulators .

e) The number of units to be used both on suspension and tension strings shall be as given below :

Voltage Class Suspension Strings Tension Strings.

Single Double Single Double 33 3 3x2 3 3x2 22 2 2x2 2 2x2 11 1 1x2 1 1x2

iv). Electromechanical & Mechanical Strength :

The mechanical and electromechanical strength of the individual and the complete Disc shall be 45 KN.

v) Creepage Distances :

The minimum creepage distance for each 11KV disc Insulator shall 320mm.

6.0 Tests :

Suitable number of individual units and complete string shall be subject to the following tests in accordance with IS:731/1971 with its latest amendments.

Page 32: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

32 | P a g e

i) Type Tests :

Following Type test shall be carried out on porcelain insulators as specified in IS: 731 /971 amended up to date. 1. Visual Examination. 2. Verification of dimensions. 3. Visible Discharge Test. 4. Impulse voltage withstand test. 5. Impulse voltage flashover test. 6. Wet one Minute Power Frequency withstand test and West Flashover test. 7. Temperature Cycle test. 8. Electromechanical failing load test. 9. Power frequency puncture withstand test. 10. Porosity test. 11. Galvanizing test.

ii) Acceptance Tests :

The test samples after having withstood the routine test shall be subject to the following acceptance tests in order indicated below: 1. Verification of dimensions. 2. Temperature Cycle test. 3. Twenty four hour mechanical test. 4. Electromechanical failing load test. 5. Power Frequency puncture withstand test. 6. Porosity test. 7. Galvanizing test.

iii) Routine Tests:

1.Visual Examination 2. Mechanical test 3. Electrical test 4. Twenty four hours mechanical test 5. Electro mechanical failing load test

7 Test Certificate :

The tenderer shall furnish detailed type test reports of the offered Disc Insulators as per clause 6.1 of the Technical Specifications at the NABL approved laboratories to prove that the Disc Insulators offered meet the requirements of the specification. These Type Tests should have been carried out within five years prior to the date of opening of this tender. i) Their offered Disc Insulators are already fully type tested at approved Laboratory CPRI/NABL within five years prior to the date of opening of this tender. ii) There is no change in the design of type tested Disc Insulators and those offers

against this tender. iii) Such tenderers complying (i) and (ii) above shall furnish an undertaking in the format

schedule.

Page 33: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

33 | P a g e

The purchaser reserves right to demand repetition of some or all the Type Test in presence of purchaser’s representative at purchaser’s cost. For this purpose, the tenderer shall quote unit rates for carrying out each Type Test. However, such unit rates will not be considered for evaluation of the offer. In case the unit fails in the Type Tests, the complete supply shall be rejected.

8. Testing Facilities :

The tenderer must clearly indicate what testing facilities are available in the works of the manufacturer and whether facilities are adequate to carry out all Routine & acceptance Tests. These facilities should be available to Board's Engineers if deputed or carry out or witness the tests in the manufacturer works. If any test cannot be carried out at the manufacturer's work, the reasons should be clearly stated in the tender. The insulators shall be tested in accordance with the procedure detailed in IS-731/1971 amended up to date.

9. Material Quality and Workmanship :

The quality of porcelain and hardware in case of porcelain insulators and core & housing in case of polymeric insulators shall be of the highest grade and best workmanship such as is suitable and customary for extra high tension lines and shall conform to current IS or IEC (only in absence of the relevant I.S.S.). The porcelain shall be sound, free from defect, thoroughly vitrified and smoothly glazed and brown in colour.

Unless otherwise specified the glaze shall cover all exposed porcelain parts of the insulator.

Glazing shall be uniform and free from defects. Small and isolated defects in the insulator glaze of a total surface less than 0.5 sq.cm. will however be ignored. Deviation on this account may be supported by relevant IS.

10 Mechanical Design :

The design shall be such that stresses due to expansion and contraction in any part of insulator shall not lead to deterioration.

Cement used in manufacture of the insulators shall not cause fracture due to expansion or loosening due to contraction.

11. Drawings :

The tender shall be accompanied with the detailed drawings showing the dimensions of the individual Disc giving all the design dimensions of various component parts. The drawing for Insulators should clearly show the method of cementing the porcelain to the metal caps and balls. Generally it shall be as per IS.

12. Markings: 12.1 Each insulator shall be legibly and indelibly marked to show the following :

a) Name or trade mark of the manufacturer.

b) Voltage Type

c) Month and year of manufacturing.

Page 34: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

34 | P a g e

d) Electromechanical strength in KN

e) Property of NESCO.

12.2 The “W” clip shall be marked with/punched with the ball and socket sizes for which it is meant e.g.16B,20 etc.

12.3 Marking on porcelain shall be printed and shall be applied before firing.

13 Packing :

All insulators shall be packed in crates or boxes suitable for rough handling. Packing shall be marked with the strength and KV rating.

GUARANTEED TECHNICAL PARTICULARS FOR 45 KN DISC. INSULATOR ( T&C TYPE)

Sl. No

Particulars

Specific Requirement

Bidders offer

1. Name of Manufacturer. & Address To be specified by the bidder

2. Location of type testing To be specified by the bidder

3 Applicable standard IS-731/1971 with latest amendment

4 Type of insulator T&C type Disc insulator

5 Nominal System Voltage 11 KV 6 Highest System voltage 12 KV 7 Visible discharge Test voltage (Minimum) 9 KV 8 Dry Impulse withstand voltage +(1.2/50 microsecond wave) 75 KV 9 Dry Impulse flashover voltage+(1.2/50 microsecond wave) 90 KV 10. Dry 1 min. power frequency withstand Voltage kV. 60 KV 11 Wet 1 min. power frequency withstand Voltage . 35 KV 12 1 min. power frequency flashover Voltage kV. (Dry) 65 KV 13. 1 min. power frequency flashover Voltage kV.(Wet) 45KV 14 Power frequency puncture voltage 105 KV 15 Mechanical Routine test load 18 KN 16 Mechanical impact strength 45 KN 17 Shattered strengths (Glass) .. KV 18 Electromechanical Failing Load 45 KN 19 Safe working load 18 KN 20 Minimum Failing Load 45 KN 21 Creepage Distance 320 mm 22 Type and Grade of Materials :

Page 35: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

35 | P a g e

i) Insulators Porcelain ii) Cap Malleable Casting or S.G

iii) Pin Forged pin iv) Locking Split pin v) Cement Portland

23 Type of semi conducting Glaze Ceramic 24 Colour of Insulators Dark Brown 25 Weight of single disc. kg. 4 Kg(Approx.) 26 Number of Insulators per crate 4 nos./ 6 nos.

27 Cross weight of Loaded crate 20 – 30 Kg 28 Whether drawing showing dimensional details have

been furnished along with bid. To be enclosed by bidder

NB : Every insulator should bear the marking of Purchaser’s name/ Manufacturer’s name and ISI mark.

Name & Signature of Bidder with seal

11KV (LIGHTNING ARRESTERS)

TECHNICAL SPECIFICATION FOR 11 KV 10 KA DISTRIBUTION CLASS HEAVY DUTY SURGE ARRESTERS (LIGHTNING ARRESTERS)

1.0 SCOPE:

1.1 This specification provides for the design, engineering, manufacture, assembly, stage testing,

inspection and testing before despatch, packing, forwarding and delivery of Metal Oxide (gapless) Surge Arresters complete with accessories 11 KV system as specified hereunder.

1.2 It is not the intent to specify completely herein all the details of design and construction of

Surge Arresters, However, Surge Arresters shall conform in all respects to the high standard of design and workmanship and be capable of performing in continuous commercial operation up to Bidder's guarantee in a manner acceptable to Purchaser, who will interpret the meanings of drawings and specifications and shall have the power to reject any work or material which in his judgment are not in accordance therewith. The Arresters offered shall be complete with all parts, necessary for their effective and trouble free operation. Such components shall be deemed to be within the scope of supply, irrespective of whether they are specifically brought out in the commercial order or not.

2.0 STANDARDS:

Page 36: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

36 | P a g e

2.1 The Surge Arresters shall conform to the latest editions and amendments available at the

time of supply, of the standards listed hereunder:

S. No.

Standard Ref No.

Title

1. IEC 99-4 Specification Part. 4 for Surge Arresters without gap for AC system.

2 IS:3070 (Part-III)

Specification for Lightning Arresters for alternating current System

3 IS:2629 Recommended practice for hot dip galvanising of iron and steel.

4 IS:2633 Method for testing uniformity of coating on Zinc coated articles.

5 IS:5621 Specification for large hollow porcelain for use in electrical installation.

6 IS:2147 Degree of protection provided by enclosures for low voltage switchgear and control gear.

7. Indian Electricity Rules 1956.

Note: i) For the purpose of this specification all technical terms used hereinafter shall have the meaning as

per IEC specification. ii) For the parameters of the Arrester which are not specified in IEC specification for

Surge Arresters, the provisions of ISS 3070 (Part.III) shall be applicable. 2.2 Surge Arresters meeting with the requirements of other authoritative standards, which ensure

equal or better quality than the standards mentioned above shall also be acceptable. Where the equipment offered by the Bidder conforms to other standards, salient points of difference between the standards adopted and the specified standards shall be clearly brought out in the offer. Four (4) copies of the reference standards in English language shall be furnished along with the offer.

3.0. CLIMATIC CONDITIONS:

3.1 The Surge Arresters and accessories shall be suitable for continuous satisfactory operation under

climatic conditions listed below.

1. Maximum ambient Air 50 °C Temperature in shade (deg.C).

2. Minimum Ambient Air (-) 5 °C Temperature in

shade(deg.C).

3. Maximum daily average ambient air temperature 40°C

4. Maximum relative humidity(%) 100%

Page 37: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

37 | P a g e

5. Height above mean sea level 1000M

6. Maximum wind pressure 260 Kg m²

7. Average No. of thunder Storm 70 days. Days / annum.

8. Average annual rainfall (mm) 1500 mm

9. Average No. of months of 4 tropical monsoon condition p.a.

All the electrical devices shall be given tropical and fungicidal treatment to enable their satisfactory operation in the above climatic conditions.

4.0 PRINCIPAL PARAMETERS:

The Surge Arresters offered under this specification shall conform to the parameters given below.

S. No Particulars System parameters

for 12 KV Distribution type

1 Nominal system voltage (kv rms) 11 2 Highest system voltage (kv rms) 12 3 1.2/50 microsecond impulse voltage with stand level

a Transformer and reactors (kvp) 75 b Other equipment and lines (kvp) 75 4 Minimumprospective symmetrical fault current for 1

second at Arrester location (KA rms) 10

5 Anticipated levels of temporary over voltage and its duration.

a Voltage(p.u.) 1.5 b Duration(Seconds) 1/10 6 System frequency(Hz) 50 + / - 1.5

7 Neutral Grounding Effectively earthed

8 Number of Phases Three Note 1. 1 p.u. = 12 x √2KV peak

/√3

5.0 GENERAL TECHNICAL REQUIREMENTS:

5.1 The Surge Arresters shall conform to the technical requirements as per Annexure-A.

5.2 The energy handling capability of each rating of Arrester offered, supported by calculations, shall

Page 38: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

38 | P a g e

be furnished in the offer. 5.3.1 The Station Type Surge Arresters shall be fitted with pressure relief devices and arc diverting

ports and shall be tested as per the requirements of IEC specification for minimum prospective symmetrical fault current as specified in Annexure-A.

5.3.2 The grading ring on each complete Arrester for proper stress distribution shall be provided if

required for attaining all the relevant technical parameters. 5.4 PROTECTIVE LEVELS:

The basic insulation levels and switching impulse withstand levels of the lines and equipment to be protected have been specified in clause 4.0, "Principal Parameters".

The protective characteristics of the Arresters offered shall be clearly specified in the schedule of guaranteed technical particulars.

5.6 GENERAL REQUIREMENTS:

5.6.1 The materials and components not specifically stated in this specification but which are

necessary for satisfactory operation of the equipment are deemed to be included in the scope of supply unless specifically excluded.

5.6.2 Unless otherwise brought out separately by the Bidder in the schedule of deviations the Surge

Arresters offered shall conform to the specification scrupulously. All deviations from the specification shall be brought out in the schedule of deviations. The discrepancies between the specification and the catalogues or literature submitted as part of the offer shall not be considered as valid deviations unless specifically brought out in the schedule of deviations.

5.6.3 Any deviation which has not been specifically brought out in the schedule of deviations of the Bid

Proposal Sheets, shall not be given effect to. The deviations brought out in the schedule shall be supported by authentic documents, standards and other references.

5.6.4. Each individual unit of Surge Arresters shall be hermetically sealed and fully protected against

ingress of moisture. The hermetic seal shall be effective for the entire life time of the Arrester and under the service conditions as specified. The Bidder shall furnish sectional view of the Arrester, showing details of sealing employed.

5.6.5 The bidder shall furnish in the offer, a sectional view of pressure relief device employed in the Station

type Surge Arresters offered. 5.6.6 The Surge Arresters shall be suitable for hot line washing.

5.7 Construction: 5.7.1 All the units of Arresters of same rating shall be interchangeable without adversely affecting the

performance. 5.7.2 The Surge Arresters shall be outdoor and suitable for pedestal/ clamp type mounting.

5.7.3 All the necessary flanges, bolts, nuts, clamps etc., required for assembly of complete Arrester

with accessories and mounting on support structure to be supplied by the Purchaser shall be included in Bidder's scope of supply.

Page 39: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

39 | P a g e

5.7.4 The drilling details for mounting the Arrester on Purchaser's support shall be supplied by the

Supplier. 5.7.5 The minimum permissible separation between the Surge Arrester and any earthed object shall be

indicated by the Bidder in his offer. 5.8. PORCELAIN / POLYMERIC HOUSING:

5.8.1 The housing may be of Porcelain or Polymeric.

5.8.2 Where the bidders are quoting for Surge Arresters with Porcelain Housing, all porcelain housings

shall be free from lamination cavities or other flaws affecting the maximum level of mechanical and electrical strengths.

5.8.3 The porcelain shall be well vitrified and nonporous.

5.8.4 The creepage distance of the Arrester housing shall be as per Annexure-A.

5.8.5 The porcelain petticoat shall be preferably of self cleaning type (Aerofoil design).

The details of the porcelain housing such as height, angle of inclination, shape of petticoats, gap between the petticoats, diameter (ID and OD) etc., shall be indicated by the Bidder in his offer in the form of a detailed drawing.

5.8.6 The Arrester housing shall conform to the requirements of IEC specification.

5.9. GALVANISATION, NICKEL PLATING ETC.:

5.9.1. All ferrous parts exposed to atmosphere shall be hot dip galvanised as per IS:2629 as amended from time to time. Tinned copper / brass lugs shall be used for internal wiring. Screws used for electrical connections shall be either made of brass or nickel plated.

5.9.2. Ground terminal pads and name plate brackets shall be hot dip galvanised.

5.9.3 The material shall be galvanised only after completing all shop operations.

5.10. ACCESSORIES AND FITTINGS:

5.10.1 All necessary accessories and earthing connection leads shall be in the Bidder's scope of supply.

5.10.2 Terminal connector conforming to IS: 5561 shall be supplied along with the arrester.

5.11. The grounding terminal shall be suitable for accommodating Purchaser's grounding connection

to steel earth mat. 5.12. Name Plate:

The arrester shall be provided with non-corrosive legible name plate indelibly marked with the following information:

1. Purchaser’s Name : NESCO 2. Order No.:

Page 40: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

40 | P a g e

3. Manufacturer's name, address, trade mark and identification no. of the Arrester being supplied.

4. Rated Voltage. 5. Maximum continuous operating voltage. 6. Type. 7. Rated Frequency. 8. Nominal discharge current. 9. Line discharge class. 10. Pressure relief current in kA rms. 11. B.I.L. of the equipment to be protected. 12. Year of manufacture. 13. Date of despatch. 14. Date of Expiry of Warranty.

6.0. TESTS:

6.1 TEST BEFORE DESPATCH:

The Surge Arrester of various rating and accessories shall be subjected at maker's works before despatch, to the following tests as per relevant standards.

A) ROUTINE TEST ON EACH UNIT AS PER RELEVANT STANDARDS: 1. Measurement of reference voltage. 2. Residual voltage test. 3. Satisfactory absence from partial discharges and contact noises. 4. For arrester units with sealed housing leakage check shall be made on each unit. 5. Current distribution test for multi Column arrester.

6.2 TYPE TESTS:

6.2.1 The bidder shall furnish valid and authenticated type test reports from a Govt. approved / Govt.

recognized / NABL Accredited laboratory of similar rating and design of tendered material along with detailed dimensional drawing duly signed & verified by testing agency also showing size & numbers of blocks dimensions contained in the housing along with bid as per requirement of the Tender Specification. Such type test certificates should not be older than 5 years as on the date of bid opening. For this purpose date of conducting type test will be considered. The type test certificates shall be furnished either in original or copy duly attested by notary.

The bidder should furnish documentary evidence in support of the laboratory whose type test

have been furnished, that the said laboratory is a Govt. / a Govt. approved / a Govt. recognized / NABL accredited laboratory / ILAC accredited (in case of foreign laboratory).

The bids of only those bidders shall be considered to be meeting the type test criteria who

furnishes complete type test certificate with the bid as per above provision. 6.2.2: Following type tests shall be conducted on one unit of each rating as per relevant standard.

1. Insulation withstand test. 2. Residual voltage test. 3. Bending test on arrester housing assembly.

Page 41: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

41 | P a g e

4. Long duration current impulse withstand test. 5. Operating duty test. 6. Pressure relief test (Only for station type) 7. Test of arrester disconnectors (For 9 KV Feeder Type) 8. Artificial pollution test on porcelain. 9. Partial discharge test. 10. Housed arresters.

a) Temperature cycle test. b) Porosity test.

11. Galvanising test on exposed ferrous metal parts. 12. Any other type test which are not specified above but covered as per amendment/latest edition of relevant IS/IEC.

6.3 TEST ON BOUGHT OUT ITEMS:

Tests are not required to be performed on bought out equipments/items like, Terminal connector etc. at the works of manufacturer. Furnishing Test Certificate of bought out items from the original equipment manufacturers shall be deemed to be satisfactory evidence. Inspection of the tests at Sub- contractors works will be arranged by the supplier whenever required.

6.4 ROUTINE/ACCEPTANCE TESTS:

The following tests shall be got conducted in presence of purchaser's representative, as per stipulation of the relevant standards. Acceptance tests whenever possible shall be conducted on the complete arrester unit. No. of samples to be selected for acceptance tests shall be nearest lower whole number to the cube root of the number of arresters to be supplied.

1. Measurement of power frequency reference voltage on the complete arrester at the reference current

measured at the bottom of the arrester. 2. Lightning Impulse residual voltage. 3. Partial discharge test. 4. Visual inspection & verification of dimension. 5. Special thermal stability test. 6. Galvanising test on Ferrous metal parts. 7. Any other tests as per IS.

6.5 TOLERANCE ON TEST RESULTS:

As per relevant standards/specifications.

6.6. CHECKING AT STORES (TEST AT CTL):

One out of every 50 nos. Surge Arresters will be selected for checking at Store for visual, dimensional, weight, marking etc. as per relevant ISS/GTP/approved drawing.

7.0 INSPECTION:

All the tests (as mentioned at Clause 6.4) and Inspection shall be made at the place of manufacturer unless otherwise especially agreed upon by the bidder and purchaser at the time of purchase. The bidder shall afford the inspection officer(s) representing the purchaser all reasonable facilities without charges, to satisfy him that the material is being supplied in accordance with this specification. The purchaser has the right to have the tests carried out at his own cost by an independent

Page 42: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

42 | P a g e

agency whenever there is a dispute regarding the quality of supply.

The Inspection may be carried out by the purchaser at any stage of manufacture/before despatch as per relevant standard.

Inspection and acceptance of any material under the specification by the purchaser, shall not relieve the bidder of his obligation of furnishing material in accordance with the specification and shall not prevent subsequent rejection if the material is found to be defective. The Bidder shall keep the purchaser informed in advance, about manufacturing programe so that arrangements can be made for inspection. The purchaser reserves the right to insist for witnessing the acceptance/routine testing of the bought out items.

Page 43: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

43 | P a g e

GUARANTEED TECHNICAL PARTICULARS FOR METAL OXIDE (GAPLESS) SURGE ARRESTERS

S. No.

Particulars Requirement of parameters

Bidder’s offer

1 Name of Manufacturer. & Address To be specified by the bidder

2 Location of type testing To be specified by 3 Applicable standard IS:3070 (Part-III) or

the latest version thereof

4 Rated arrester voltage (KV) 11

5 Maximum continuous operating voltage (MCOV) KV (rms)

12

6 Installation Outdoor

7 Class Distribution Class

8 Type of construction Single column, single phase

9 Nominal discharge current corresponding to 8 / 20 micro second wave shape (KA peak)

10

10 Type of mounting Pedestal 11 Connection (between phase to earth) /

(between phase to phase) Phase to Earth

12 Line discharge class 2 13 Ratio of switching impulse residual

voltage to rated voltage of arrester

As per provision of IEC – 99 – 4 (latest amended)

14 Minimum prospective symmetrical fault current for pressure relief test (KA rms)

40

15 a)

Terminal connector suitable for the conductor

Up to 100 mm² single

b) Take off For both vertical & horizontal

16 Voltage (corona extinction) (KV rms) Rated voltage of arrester

17 Partial discharge As per provision of IEC – 99 – 4 (latest amended)

18 Whether insulating base and discharge counter with milli ammeter are required

No

19 Minimum creepage distance of arrester housing

300 mm

20 Drawing To be submitted by bidder

Name & Signature of Bidder with seal

Page 44: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

44 | P a g e

TECHNICAL SPECIFICATION OF 33KV LIGHTNING ARRESTOR

SCOPE

14.1 This Specification provides for the design, manufacture, inspection and testing before dispatch, packing and delivery F.O.R. (destination) of metal oxide (gapless) Surge Arresters with discharge counters, insulating base, terminal connectors and other accessories as specified here in.

Following is the list of documents constituting this Specification. :

(i) Technical Specification (TS)

(ii) Check-List. Annexure-B

(iii) Calibration Status of testing equipments and meters/ Instruments. Annexure-C (iv) Check-list towards Type Test Reports. Annexure-D

Note : Annexure-B,C,& D are to be filled up by the Bidder.

All the above along with amendments thereof shall be read and interpreted together. However, in case of a contradiction between the Technical Specification and any other volume, the provisions of this volume will prevail.

14.2 The Surge Arrester shall conform in all respects to high standards of engineering, design, workmanship and latest revisions of relevant standards at the time of offer and purchaser shall have the power to reject any work or materials, which in his judgment is not in full accordance therewith.

14.3 STANDARDS:-

Except to the extent modified in the Specification, the Surge Arrester shall conform to the latest editions and amendments of the standards listed hereunder.

Sl. No. Standard

Ref. No.

Title.

1 IEC-99-4 Specification for Surge Arresters without gap for AC

System. 2 IS:2147 Degree of protection, provided by enclosures for low voltage

switchgear and control. 3 IS:2629 Recommended practice for hot dip galvanization of iron and

steel. 4 IS:2633 Method for testing uniformity of coating on zinc coated

articles. 5 IS:3070 Specification for surge arresters for alternating current

system. 6 IS:5621 Specification for large hollow porcelain for use in electrical & IEC-621155 installation.

7 IEC-60-1 High-Voltage Test technique. 8 IEC-270 Partial discharge measurements. 9 IEC-99-1 Non-linear resistor type gapped arresters for a.c. systems.

10 Indian Electricity Rules, 1956. 11 IEC-60815 Shed profile of hollow porcelain Insulator.

Page 45: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

45 | P a g e

14.4 Surge Arresters with the requirement of other authoritative standards, which ensure equal or better quality than the standards, mentioned above shall also be acceptable. Where the equipment offered by the supplier conforms to other standards, salient points of difference between the standards adopted and the specified standards shall be clearly brought out in the offer. 2 (Two) copies of the reference standards in English language shall be furnished along with the offer.

14.5 GENERAL TECHNICAL REQUIREMENTS:

14.5.1 The Surge Arrester shall confirm the technical requirements

14.5.2 The energy handling capability of each rating of Arrester offered, supported by calculations, shall be furnished with the offer.

14.5.3 The Surge Arresters shall be fitted with pressure relief devices and arc diverting paths and shall be tested as per the requirements of IEC for minimum prospective symmetrical fault current as specified in Appendix-I.

14.5.4 A grading ring shall be provided if required, (for attaining all the relevant technical parameters)

on each complete Surge Arrester.

14.6 PROTECTIVE LEVELS:

Surge Arresters shall be capable of providing protection to sub-station equipments, designed for the withstand levels, given in the following table.

Sl.

No.

Equipment to be protected Insulation Level of 36KV System

L.I. Level (KVP) 1 Power Transformers. 170 2 Instrument Transformers. 170 3 Reactors 170 4 Circuit Breakers/Isolators. (i) Phase to ground. 170

Surge arrester shall be suitable for the following duty cycles of circuit breaker at the following system voltages:

36 KV Circuit Breaker 0-0.3 sec-co-3 min-co

14.7 DUTY REQUIREMENT:

14.7.1 Surge Arresters shall be of heavy-duty station class and gapless type without any series or shunt gaps.

i. Surge Arresters shall be capable of discharging over voltages occurring during switching of un- loaded transformers, lines, capacitors and reactors.

ii. The Surge Arresters shall be capable of discharging lightning and switching surges and temporary power frequency over-voltages.

iii. The Surge Arresters shall be capable of discharging the energy equivalent to class 3 of IEC-99-4.

Page 46: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

46 | P a g e

14.7.2 The reference current of the arrester shall be high enough to eliminate the influence of grading and stray capacitance on the measured reference voltage. The supplier shall submit values and the supporting evidence along with calculations on above.

14.7.3 Surge Arresters shall be fully stabilized thermally to give a life expectancy as per standard under site conditions.

14.7.4 Surge Arresters shall be able to withstand maximum wind load of 260 Kg./sq.m.

14.7.5 Surge Arresters shall be capable of withstanding effects of direct solar radiation

14.7.6 Surge arresters shall be capable of spark over on severe switching Surges and multiple strokes.

14.7.7 The Surge Arrester should be adequately designed to operate satisfactorily under temporary power frequency over-voltage as given in specific technical requirements, after discharging two shots of respective long duration surges.

14.7.8 Unless otherwise brought out separately by the Bidder in the schedule of deviations, the Surge Arresters, offered shall conform to the specification scrupulously. All deviations from the specification shall be brought out in the schedule of deviations. The discrepancies between the specification and the catalogues or literature, submitted as part of the offer shall not be considered as valid deviations unless specifically brought out in the schedule of deviations.

14.8 CONSTRUCTION:

14.8.1 Non linear blocks shall be sintered metal oxide material. These shall be provided in such a way as to obtain robust construction with excellent electrical and mechanical properties even after repeated operations.

14.8.2 All the units of arresters of same rating shall be inter-changeable without adversely affecting the performance.

14.8.3 The Surge Arresters shall be suitable for pedestal type mounting.

14.8.4 All the necessary flanges, bolts, nuts, clamps etc. required for assembly of complete arrester with accessories and mounting on support structure to be supplied by the purchaser, shall be included in supplier‘s scope of supply.

14.8.5 The drilling details for mounting the Arrester on owner‘s support shall be supplied by the supplier.

14.8.6 The minimum permissible separation between the Surge Arrester and any earthed object shall be indicated by the Bidder in his offer.

14.8.7 Surge Arresters shall be designed to incorporate pressure relief devices and arc diverting paths to prevent shattering of the blocks or the porcelain housing, following prolonged current flow or internal flash over and providing path for flow of rated fault currents in the event of arrester failure.

14.8.8 Surge Arresters shall incorporate anti-contamination feature to prevent arrester failure, caused by uneven voltage gradient across the stack, resulting from contamination of the arrester porcelain.

14.8.9 Seals shall be provided in such a way that these are always effectively maintained even when discharging rated lightning current.

14.8.10The heat treatment cycle details along with necessary quality checks used for individual blocks along

Page 47: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

47 | P a g e

with insulation layer, formed across each block are to be furnished. Metalised coating thickness for reduced resistance between adjacent discs is to be furnished along with the procedure for checking the same. Details of thermal stability test for current distribution of current on individual disc is to be furnished.

14.8.11Each individual unit of Surge Arresters shall be hermetically sealed and fully protected against ingress of moisture. The hermetic seal shall be effective for the entire lifetime of the arrester and under the service conditions as specified. The supplier shall furnish sectional view of the arrester showing details of sealing employed.

14.8.12 The Surge Arresters shall be suitable for hot line washing.

14.9 PORCELAIN HOUSING :

14.9.1 All porcelain Housings shall be free from lamination cavities or other flaws, affecting the maximum level of mechanical and electrical strengths.

14.9.2 The porcelain shall be well vitrified and non-porous.

14.9.3 The minimum creep age distance of the arrester housing shall be as per Cl 7.21 of the TS.

14.9.4 The porcelain petticoat shall be preferably of self-cleaning type (Aerofoil design). The details of the porcelain housing such as height, angle of inclination, shape of petticoats, gap between the petticoats, diameter (ID and OD) etc. shall be indicated by the Bidder in his offer in the form of detailed drawing.

14.9.5 Porcelain housings shall be so co-coordinated that external flash over will not occur due to application of impulse or switching Surge voltages up to the maximum design value for arrester.

14.10 GALVANISATION, NICKEL PLATING ETC.:

14.10.1 All ferrous parts exposed to atmosphere shall be hot dip galvanized as per IS: 2629, as amended from time to time. Tinned copper/brass lugs shall be used for internal wiring of discharge counter. Screws used for electrical connections shall be either made of brass or shall be nickel-plated.

14.10.2 Ground terminal pads and nameplate brackets shall be hot dip galvanized.

14.10.3 The material shall be galvanized only after completing all shop operations

14.11 ACCESSORIES AND FITTINGS:

14.11.1 Surge Counters

14.11.2A self- contained Surge counter, suitably enclosed for outdoor use and requiring no auxiliary of battery supply for operation shall be provided for each unit. The surge counter shall be operated by the discharge current, passed by the surge arrester and shall be suitable for mounting on the support structure of the Arrester.

14.11.3 Surge counters shall be of the Electro-mechanical type and designed for continuous service.

14.11.4 The cyclometer counter shall be visible through an inspection window from ground level. The counter terminals shall be robust and adequate size and shall be so located that the incoming and outgoing connections are made with minimum possible bends.

Page 48: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

48 | P a g e

14.11.5 Internal parts shall be unaffected by atmospheric conditions at site. Alternatively, a weather proof housing to IP 55 shall be provided and this shall be designed to allow the recording device to be read from ground level without exposing the internal parts to the atmosphere.

14.11.6 The Surge Counter shall be connected in the main earth lead from the arrester in such a manner that the direction of the earth lead is not changed or its surge impedance materially altered. A bolted link shall be provided so that the surge counter may be short circuited and removed without taking the arrester out of service.

14.11.7 All necessary accessories and earthing connection leads between the bottom of the Arrester and discharge counter shall be in the supplier‘s scope of supply.

14.12 LEAKAGE CURRENT METERS: ( In case of 33 Kv surge arrester only)

14.12.1 Leakage current meters (suitable milli-ammeter) shall be connected in the earthing path of the surge arresters to measure the resistor grading leakage current. Meters shall be designed for continuous service.

14.12.2 The ammeter shall be suitable for mounting on the support structure of the arrester. The push buttons shall be mounted such that it can be operated from the ground level.

14.12.3 The internal parts shall be fully weather - proof to IP 55 or better with a transparent cover to provide an unobstructed view of the ammeter.

14.12.4 Arresters shall be complete with insulating base having provision for bolting to flat surface of the structure.

14.12.5 The grounding terminals shall be suitable for accommodating purchaser‘s grounding connection to steel earth mat.

14.12.6 The Bidder has to quote unit rates of the insulting base and the surge counter separately. The purchaser reserves its option to procure insulting base and surge counter.

14.12.7 Clamp type terminal connector, suitable for 33KV-AAA Panther-up Conductor shall be provided having both horizontal and vertical take-off.

14.12.8 Two clamp type ground terminal connectors, suitable for G. I. Strip (50 x 6) or (50 x 8) should be provided.

14.12.9 All interconnecting hardware such as nuts, bolts, spring washers etc. with 5% spares shall be supplied for different units

14.12.10 Pollution Shunt (Copper braid) shall be supplied along with each surge Arrester for by-passing the surface current.

Other standard accessories, which are specifically not mentioned, but are usually provided with Surge Arrester of such type and rating for efficient and trouble free operation should be supplied.

14.13 NAME PLATE:

Each single pole Arrester shall be provided with non-corrosive legible name plate, at the base bearing thereon, voltage rating of the complete pole and the number of demountable sections with the following data, indelibly marked

Page 49: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

49 | P a g e

i) NESCO

ii) Purchase order No. & Date.

iii) Name of device.

iv) Manufacturer‘s name and trademark and identification no. of the arrester being supplied.

v) Year of manufacture

vi) Rated voltage

vii) Rated Frequency

viii) Maximum continuous operating voltage.

ix) Type

x) Nominal discharge current.

xi) Long duration discharge class.

xii) Pressure relief current in KA(rms)

xiii) Energy discharge capability ( KJ / KV rating).

14.14 TEST :

14.14.1 Type Tests:

The surge Arrester offered should have been subjected to the following type tests in an independent Government approved test laboratory. The bidder shall furnish four sets of type test reports along with the offer. These tests must not have been conducted earlier than five years from the date of opening of technical bid. For any change in the design, type already type tested and the design type offered against this specification, the purchaser reserves the right to demand repetition of some or all type tests without any extra cost to NESCO in the presence of Purchaser‘s representative at the cost of the supplier.

1 Insulation withstands tests:

(a) Lightning Impulse Voltage Test.

2 Residual voltage tests.

3 Long duration current impulse withstands tests.

4 Operating duty tests.

5 Pressure relief tests.

(a) High current test.

(b) Low current test.

6 Power frequency voltage vs. time curve. (Temporary over voltage test)

Page 50: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

50 | P a g e

7 Contamination test. (Artificial pollution test).

8 Seismic withstand test.

9 IP-55 test on surge counter.

10 Minimum current operation tests of the surge counter.

11 Maximum current withstand test of the surge counter.

12 Mechanical terminal load test on bushing.

13 Partial discharge test.

N.B. :-Even if the condition i.e. the dry arcing distance or the sum of the partial dry arcing distances is larger than the test voltage divided by 500 KV/m‘, the lightning impulse voltage test must have been conducted or is to be conducted without any financial liability to NESCO.

Even if the type test reports are found to be valid as per this specification, the purchaser reserves the right to demand the repetition of some or all the type tests in the presence of purchaser‘s representative. For this purpose, the bidder shall quote unit rates for carrying out each type test. These prices, if necessary, will be taken into consideration for bid evaluation.

14.14.2 ROUTINE TESTS:

The following routine tests shall be conducted at the supplier‘s cost on each surge arrester and shall be submitted along with or before offering for inspection for purchaser‘s approval.

(a) Measurement of reference voltage.

(b) Residual voltage tests.

(c) Measurement for partial discharge and contact noise.

(d) Sealing test for units with sealed housings.

14.14.3 ACCEPTANCE TESTS:

The following tests, considered as acceptance tests, shall be conducted in the presence of purchasers representative for which no charges will be payable by NESCO. The acceptance tests, whenever possible shall be conducted on the complete arrester unit. The number of samples to be subjected to acceptance test shall be decided by the purchaser at the time of actual testing.

I Temperature Cycle Test on Housing.

II Measurement of Power Frequency Voltage at the reference current.

III Measurement of leakage current and capacitive current at M.C.O.V.

IV Lightning Impulse Residual Voltage Test at N.D.C., 50% of N.D.C. & 200% of N.D.C.

V Partial Discharge Tests on complete arresters/units at 1.05 times M.C.O.V.

VI Special Thermal stability test.

Page 51: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

51 | P a g e

VII Porosity test on porcelain components.

VIII Galvanization test on metal parts.

IX The functional (operational) test on the Surge Counter by way of checking its operation at following nominal discharge currents:

a) 100 Amps with 8/20 micro second wave shape.

b) 10 KA with 8/20 micro second wave shape.

X Check of calibration of leakage current meters.

14.15 INSPECTION:

I The purchaser shall have access at all time to the works and all other places of manufacture, where the Surge Arresters are being manufactured and the supplier shall provide all facilities for unrestricted inspection of the supplier‘s works, raw materials, manufacture of all the accessories and for conducting the necessary tests.

II The supplier shall keep the purchaser informed in advance of the time of starting and the progress of manufacture of equipment in its various stages so that arrangements could be made for inspection.

III No material shall be dispatched from its point of manufacture unless the material has been satisfactorily inspected tested and dispatch schedule attached to this specification.

IV The acceptance of any quantity of equipment shall in no way relieve the supplier of his responsibility for meeting all the requirements of this specification and shall not prevent subsequent rejection, if such equipments are later found to be defective.

14.16 QUALITY ASSURANCE PLAN:

14.16.1 The Bidder shall invariably furnish following information along with his offer, failing which the offer shall be liable for rejection.

(i) Statement giving list of important raw materials, names of sub-suppliers for the raw materials, list of standards according to which the raw materials are tested, list of tests, normally carried out on raw materials in presence of Bidder‘s representative, copies of test certificates.

(ii) Information and copies of test certificates as in (I) above in respect of bought-out items.

(iii) List of manufacturing facilities available.

(iv) Level of automation, achieved and list of areas where manual processing exists.

(v) List of areas in manufacturing process where stage inspections are normally carried out for quality control and details of such tests and inspections.

(vi) Special features provided in the equipment to make it maintenance free.

(vii) List of testing equipments, meters available with Bidder for final testing of equipment, specified and test plant limitation, if any, vis-à-vis the type, acceptance and routine tests, specified in the relevant standards and this specification. These limitations shall be very clearly

Page 52: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

52 | P a g e

brought out in the offer.

(viii) All the testing equipments, meters etc. should have been calibrated in a Government approved laboratory. The Bidder must submit the list of testing equipments and meters test-wise as per Annexure-C of this Technical Specification.

14.16.2 The suppliers, within 30 days of placement of order submit the following information to the purchaser.

(i) List of raw materials as well as bought out accessories and the names of the materials as well as bought-out accessories and the names of sub-suppliers, selected from those, furnished along with the offer.

(ii) Type test certificates of the raw material and bought out accessories.

(iii) Quality Assurance Plan (QAP) with hold points for the purchaser‘s inspection. The QAP and hold points shall be discussed between the purchaser and the supplier before the QAP is finalized.

14.16.3 The supplier shall submit the routine test certificates of bought out item and raw martial at the time of acceptance testing of the fully assembled equipment.

14.17 DOCUMENTATION:

14.17.1 All drawings shall conform to relevant Indian Standard as per relevant IS. All drawings shall be in ink and suitable for microfilming. All dimensions and data shall be in S.I. Units.

14.17.2 The supplier shall furnish four sets of following drawings / documents along with his offer. (i) General out line drawings of the complete Arrester with technical parameters.

(ii) Drawings showing clearance from grounded and other line objects and between adjacent poles of Surge Arresters, required at various heights of Surge Arresters.

(iii) Drawings showing details of pressure relief devices.

(iv) Detailed drawing of discharge counters along with the wiring and schematic drawing of discharge counter and meter.

(v) Outline drawing of insulating base.

(vi) Details of grading rings, if used.

(vii) Mounting details of Surge Arresters.

(viii) Details of line terminal and ground terminals.

(ix) Volt-time characteristics of Surge Arresters.

(x) Details of galvanization being provided on different ferrous parts.

(xi) The detailed dimensional drawing of porcelain Housing such as ID, OD, thickness and insulator details such as height, profile of petticoats, angle of inclination and gap between successive petticoats, total creepage distance etc.

(xii) Cross-sectional view of the Surge Arrester Units showing all components.

Page 53: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

53 | P a g e

14.18 TEST REPORTS:

(i) Four copies of type test reports shall be furnished to the purchaser with the tender specification.

Copies of acceptance test reports and routine test reports shall be furnished to the purchaser. One copy will be returned duly certified by the purchaser and only thereafter shall the materials be dispatched.

(ii) All records of routine test reports shall be maintained by the supplier at his works for periodic inspection by the purchaser.

(iii) All test reports of tests, conducted during manufacture shall be maintained by the supplier.

These shall be produced for verification as and when requested for by the purchaser.

14.19 PACKING AND FORWARDING:

14.19.1 The equipment shall be packed in suitable crates so as to withstand handling during transport and outdoor storage during transit. The supplier shall be responsible for any damage to the equipment during transit, due to improper and inadequate packing. The easily damageable material shall be carefully packed and marked with the appropriate caution symbols. Wherever necessary, proper arrangement of lifting such as lifting hooks etc. shall be provided. Any material found short inside the packing cases shall be supplied by the supplier without any extra cost.

14.19.2 Each consignment shall be accompanied by a detailed packing list containing the following information:

(a) Name of the consignee :

(b) Details of consignment :

(c) Destination :

(d) Total weight of consignment :

(e) Sign showing upper/lower side of the crate :

(f) Handling and unpacking instructions :

(g) Bill of materials indicating contents of each package :

The supplier shall ensure that the bill of materials is approved by the purchaser before dispatch.

14.20 QUANTITY AND DELIVERY REQUIREMENT:

The scope of supply shall include a supply of 2.5% extra quantity of bolts, nuts, washers, split pins, cotter pins and such other small loose items free of cost.

Page 54: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

54 | P a g e

GUARANTED TECHNICAL PARTICULARS OF 33KV L.A (To be Submitted along with offer)

Sl no. Description Specified Bidder’s offer

Name of the Manufacturer & Address To be specified by bidder

1 Nominal system voltage (phase to phase) (KV rms).

33

2

Highest system voltage (phase to phase) (KV rms).

36

3 System Frequency (HZ). 50 ±5%

4 System Neutral earthing. Effectively earthed

5 Installation. Outdoor

6 Class. Station class, 10 KA, heavy duty type

7

Type of construction for 10 KA rated arrester. Single column, single phase

8 No. of phases. Three 9 Maximum duration of earth fault

(Sec.) 3

10

Maximum prospective symmetrical fault current at arrester location (KA rms.)

40

11 Rated arrester voltage (KV rms) 30 12

Nominal discharge current (KAP) Discharge current at which insulation co-ordination will be done

10 KA of 8/20 µsec Wave

13 Minimum energy discharge capability (KJ/KV)

As per relevant ISS/IEC

14 Maximum continuous operating voltage at 50º C (KV rms)

25

15 Maximum switching surge residual voltage (KVP)

72 at 500A

16 Maximum residual voltage at 8/20 micro second(KVP)

(i) 5 KA. 85 (ii) 10 KA Nominal discharge current. 90

(iii) 20 KA. 100

17 Long duration discharge class

2

18

High current short duration test value (KAP) (4/10 Micro-second wave).

100

Page 55: “GROUP – A”nescoodisha.com/Tech_l_Specification_of_Gr_A_19.pdfFor each of the Post Insulators / Insulator sets Bolts, Nuts, Set Screws & Washers shall be supplied as follows

55 | P a g e

19

Current for pressure relief test (KA-rms)

40

20 Minimum total creepage distance (mm).

900

21 One minute dry and wet power frequency withstand voltage of Arrester housing (KV-rms).

70

22 (a) b)

Impulse withstand voltage of arrester housing with 1.2/ 50 micro-second wave (KVP). Switching Impulse Voltage (Wet) (KVP)

110.5 -

23 Pressure relief class. A

24 Corona extinction voltage (KV- rms).

-

25 RIV at 92 KV rms.

Less than 500 micro volts

26

Partial discharge at 1.05 times continuous over-voltage.

Nor more than 50 PC

27 Seismic acceleration. 0.3g horizontal 0.15g vertical

28 Reference ambient temperature. 50ºC

29 (a) IR at MCOV. Less than 400 micro amperes

(b) IC at MCOV. Less than 1200 micro amperes

30 a) Reference Current (mA) 1 to 5 mA

b) Reference voltage at reference current. Greater than rated voltage 31

Maximum steep current Impulse RDV (KVP). at KAP

100

32

Maximum cantilever strength of the arresters (KGM).

325

33 TOV(KVP).

(i) 0.1 sec. 53

(ii) 1.0 sec. 51

(iii) 10.0 sec. 49

(iv) 100.0 sec.

47

Name & Signature of Bidder with seal