    Shear LoadConnectorsfor the Construction Industry

    CI/SfB (29) Et6

    February 2008

  • 8/11/2019 Ancon Shear Load Connector

    2/30

    2

  • 8/11/2019 Ancon Shear Load Connector

    3/30

    3

    Ancon designs and manufactures high integrity steel products for

    the construction industry. Through continuous programmes of new

    product development, inward investment and employee

    advancement, the company is committed to maintaining the

    highest level of customer service within a dynamic and challenging

    industry.

    Reinforced concrete is an important

    construction material. It offers strength,

    durability and can be formed into a variety of

    shapes. Concrete structures are designed with

    expansion and contraction joints at appropriate

    places to allow movement to take place. The

    design of the joint is important for the overall

    design to function correctly.

    Ancon shear load connectors offer significant

    advantages over plain dowels.

    Dowelled & Keyed Joints 4

    Ancon Solutions to Joints 5

    Ancon Shear Connector Range 6-7

    Installation Procedure 8

    Design Capacities 9

    DSD and DSDQ Connectors 10-14

    ESD, ESDQ, ED

    and Acoustic Connectors 15-18

    Applications 19

    Other Ancon Products 19

    Masonry Support Systems

    Masonry Reinforcement

    Windposts and Lintels

    Wall Ties and Restraint Fixings

    Channel and Bolt Fixings

    Tension Systems

    Stainless Steel Fabrications

    Flooring and Formed Sections

    Shear Load Connectors

    Reinforcing Bar Couplers

    Reinforcement Continuity Systems

    Punching Shear Reinforcement

    Insulated Balcony Connectors

    Refractory Fixings

    BS EN ISO 9001: 2000

    FM12226

    ISO 14001: 2004

    EMS 505377

  • 8/11/2019 Ancon Shear Load Connector

    4/30

    Misaligned dowels can result in cracking away from the expansion joint

    Shear Load Connectors

    4

    Dowel bar

    Debonding

    sleeve

    End cap to allow

    dowel movement

    Compressible

    joint filler

    DOWELLED JOINTS

    Dowels are used to transfer shear across

    construction and movement joints in concrete.

    They are often either cast or drilled into the

    concrete. A single row of short thick dowels

    provides reasonable shear transfer but suffersfrom deformation. This can lead to stress

    concentrations, resulting in subsequent spalling

    of the concrete.

    Where dowels are used across expansion and

    contraction joints, half the length of the bar is

    debonded to allow movement to take place.

    KEYED JOINTS

    Keyed joints require complicated formwork to

    create the tongue and groove. If the joint is not

    formed correctly, differential movement can

    take place. Load is transferred through the

    locally reduced section of the joint which can attimes result in cracking.

    Dowelled joints either require formwork to be

    drilled for the dowels to pass through, or

    concrete to be drilled for dowels to be resin

    fixed in one side.

    At movement joints, dowels will need to be

    accurately aligned in both directions to ensure

    movement can actually take place, otherwise

    cracking is likely to occur.

    Plain dowels are not very effective when used

    across joints wider than 10mm.

  • 8/11/2019 Ancon Shear Load Connector

    5/30

    ANCON SOLUTIONS TO JOINTS

    In most cases dowelled or keyed joints can be

    replaced by joints incorporating Ancon shear

    load connectors. These connectors are more

    effective at transferring load and allowing

    movement to take place, easier to fix on site

    and can prove a more cost-effective solution.

    Ancon connectors can be used for movement

    joints in floor slabs, suspended slabs, and for

    replacing double columns and beams at

    structural movement joints. Applications in civil

    engineering include joints in bridge parapets,

    bridge abutments and diaphragm wall

    construction.

    Dowel Bar Ancon DSD

    Keyed Joint Ancon DSD

    Double Columns

    The two-part assembly ofAncon connectors ensures

    dowel alignment

    Ancon DSD

    Wall

    Structural Movement Joint

    Ancon DSD sleeve

    Ancon DSD

    dowel component

    Conventional Joints

    Floor Slab

    Ancon Solutions

    Floor to Wall Connection

    Corbel Support Ancon DSD

    5

    Tel: +44 (0) 114 275 5224 Web: www.ancon.co.uk

    6 Dowel Bars 32mm Diameter

    Design Capacity 197.5kN

    1 Ancon DSD 130

    Design Capacity 202.5kN

    Comparison of Performance with

    Plain Dowels

    400mmThick Slab Six 32mmwith Joint One Ancon Dia DowelWidth of 20mm DSD130 Bars

    DowelDiameters mm

    2 x 35 6 x 32

    Area ofDowels mm2

    1924 4825

    DesignCapacity kN

    202.5 197.5

  • 8/11/2019 Ancon Shear Load Connector

    6/30

    Ancon DSDQShear Connectors

    Slab movement willbe in oppositedirections in this area

    Ancon DSDQ Shear Connectors allowingrotation

    Ancon DSDQ Shear Connectors allowingmovement in two directions

    Plan

    Longitudinalmovement

    Sleeve withinrectangular boxsection

    Lateral movementor rotation

    ANCON S HEA R LOAD CONNECTORS

    The DSD range of connectors offers significant

    advantages over plain dowels. Each connector

    is a two-part assembly comprising a sleeve

    and a dowel component. Installation is a fast

    and accurate process, drilling of either

    formwork or concrete is not required. The

    sleeve is simply nailed to the formwork

    ensuring subsequent alignment with the dowel,

    essential for effective movement.

    They are manufactured from stainless steel to

    ensure a high degree of corrosion resistance

    with no requirement for additional protection.

    Free software is available from Ancon that

    simplifies the design of movement joints in

    reinforced concrete. For a given application,

    Ancons design program will calculate the size

    and quantity of shear load connectors required,

    the edge distance and spacings at which they

    should be installed, and details of the local

    reinforcement.

    Ancon DSD

    The Ancon DSD is the original two-part, double

    dowel, shear load connector. The two dowelsare Duplex stainless steel bar. The dowel

    component can move longitudinally within the

    sleeve to accommodate movement. The

    connector is available in ten standard sizes and

    has design capacities from around 20kN to

    over 950kN. The larger connectors can be

    used in joints up to 60mm wide. Larger joints

    can be accommodated using special dowels.

    Please contact Ancons Technical Department

    for further information.

    Ancon DSDQ

    The Ancon DSDQ shear load connectoruses the same dowel component as the Ancon

    DSD, but the cylindrical sleeve is contained

    within a rectangular box section to allow lateral

    movement in addition to the longitudinal

    movement. There are nine standard sizes

    which have design capacities from around

    30kN to over 950kN.

    DSDQ

    Longitudinalmovement

    Dowel bar

    Web plate

    DSD

    Cross dowels

    End cap

    Guide tube

    End plate withnail holes

    6

    Shear Load Connectors

  • 8/11/2019 Ancon Shear Load Connector

    7/30

    7

    A range of stainless steel single dowel shear

    connectors is also available.

    Ancon ESD

    The Ancon ESD shear load connector is used

    where loads are small, but where alignment is

    critical. It is available in four sizes with each size

    available in two lengths. The dowel component

    is Duplex stainless steel bar.

    Ancon ESDQ

    The Ancon ESDQ shear load connector uses

    the same dowel as the ESD, but the cylindrical

    sleeve is contained within a rectangular boxsection to allow lateral movement or rotation in

    addition to longitudinal movement.

    Ancon ED

    The Ancon ED is a low cost dowel connector

    for use in floor slabs where alignment is

    important but loads are small. The single dowel

    shear connector is available in four sizes with

    each size available in two lengths. The sleeve

    component is made from a durable plastic and

    features an integral nail plate. The dowel

    component is Duplex stainless steel.

    Ancon Staisil

    The Ancon Staisil acoustic connector is

    designed to transfer shear loads and limit

    sound transmission across joints in concrete.

    The sleeve has Elastomer sound absorbing

    material between two stainless steel tubes and

    a nail plate for fixing to formwork. The sound

    transmission properties are generally

    unaffected by either joint width or service load.

    Tests in the frequency range of 100 - 3150 Hz

    have shown a reduction in sound transmission

    of 20dB. When the standard solid dowel was

    replaced by an antivibration dowel a reductionof 25dB was recorded.

    ESD

    ED

    Tel: +44 (0) 114 275 5224 Web: www.ancon.co.uk

    ESDQ

    Sound absorbing

    material

    Staisil

  • 8/11/2019 Ancon Shear Load Connector

    8/30

    2

    Fix the local reinforcement in position around the sleeve component together with any other

    reinforcement that is required, ensuring that the correct cover to the reinforcement is maintained.

    Pour the concrete to complete the installation of the sleeve component.

    3

    When the concrete has achieved sufficient

    strength, strike the shuttering. Peel off or

    puncture the label to reveal the holes for the

    dowels. Where Q versions are being used, the

    label should only be punctured enough to allow

    the dowel into the cylindrical sleeve to prevent

    debris entering the box section.

    1

    Nail the sleeve component to the shuttering

    ensuring that the sleeve is correctly orientated

    for the direction of the load. Check that the

    minimum spacing and edge distances are notexceeded. The label prevents debris from

    entering into the sleeve aperture and should

    not be removed at this stage.

    4

    Position compressible joint filler of the

    appropriate width, for applications where

    movement is expected between the two

    sections of concrete.

    5

    Push the dowel component through the joint

    filler (if applicable) until it is fully located in the

    sleeve component. It may be necessary to tap

    the dowel component to overcome the dimple

    which pinch holds the dowel in the sleeve and

    prevents dislocation when the concrete is

    vibrated.

    6

    Fix the local reinforcement in position around

    the dowel component together with any other

    reinforcement that is required, ensuring that the

    correct cover to the reinforcement is

    maintained. Pour the concrete to complete the

    installation of the shear connector.

    Notes:

    (i) Although installation is shown for Ancon DSD, the procedure is the same for all Ancon shear connectors.

    (ii) Where deep concrete pours are proposed, the installation will require further consideration. More robust fixing ofthe sleeve and dowel components will be necessary to avoid displacement during placing of the concrete.

    INSTALLATION PROCEDURE

    The two-part assembly of all Ancon shear connectors removes the need for drilling formwork on

    site, supporting dowel bars and fitting debonding sleeves and end caps. The installation is a fast

    and accurate process.

    Directionof load

    Shear Load Connectors

    8

  • 8/11/2019 Ancon Shear Load Connector

    9/30

    Tel: +44 (0) 114 275 5224 Web: www.ancon.co.uk

    10 mm 20 mm 30 mm 40 mm 50 mm 60 mm

    Joint Widths (mm)

    900

    1000

    800

    400

    500

    600

    700

    300

    200

    100

    0

    FRd

    (kN)

    9

    10 mm 20 mm 30 mm 40 mm

    60

    70

    80

    50

    40

    30

    20

    10

    0

    FRd

    (kN)

    Joint Widths (mm)

    Ancon ESD FRd

    Design Capacities (kN) for Various Joint Widths (mm) at the Maximum Slab Thickness (mm) in C30/37 Concrete

    Ancon DSD FRd Design Capacities (kN) for Various Joint Widths (mm) at the Maximum Slab Thickness (mm) in C30/37 Concrete

    DSD 450

    DSD 400

    DSD 150DSD 130

    DSD 100

    DSD 75

    DSD 65

    DSD 50

    DSD 30

    DSD 25

    ESD 25ESD 20

    ESD 15

    ESD 10

    DESIGN CAPACITIES

    Note: For more detailed information please see page 17.

    Note: For more detailed information please see page 11.

  • 8/11/2019 Ancon Shear Load Connector

    10/30

    FRd Design Capacities (kN) for Various Joint Widths (mm) and Slab Thickness (mm) using C25/30 Concrete

    Slab Thickness Product Joint Widths (mm)(mm) Reference 10 20 30 40 50 60

    180 39.5 39.5 29.9 23.2 - -

    200 45.7 41.8 29.9 23.2 - -

    220 52.3 41.8 29.9 23.2 - -

    240 59.3 41.8 29.9 23.2 - -

    260 66.7 41.8 29.9 23.2 - -

    280 69.6 41.8 29.9 23.2 - -

    180 42.7 42.7 42.7 34.7 - -

    200 49.2 49.2 44.6 34.7 - -

    220 56.1 56.1 44.6 34.7 - -

    240 63.4 62.4 44.6 34.7 - -

    260 71.1 62.4 44.6 34.7 - -

    280 79.1 62.4 44.6 34.7 - -

    180 43.8 43.8 43.8 43.8 40.4 -

    200 50.3 50.3 50.3 49.4 40.4 -

    220 57.3 57.3 57.3 49.4 40.4 -

    240 64.6 64.6 63.5 49.4 40.4 -

    260 72.3 72.3 63.5 49.4 40.4 -

    280 80.4 80.4 63.5 49.4 40.4 -

    180 54.6 54.6 54.6 54.6 54.6 -200 62.2 62.2 62.2 62.2 55.4 -

    220 64.3 64.3 64.3 64.3 55.4 -

    240 68.6 68.6 68.6 67.7 55.4 -

    260 76.4 76.4 76.4 67.7 55.4 -

    280 84.6 84.6 84.6 67.7 55.4 -

    240 86.1 86.1 86.1 86.1 73.8 -

    260 89.1 89.1 89.1 89.1 73.8 -

    280 94.8 94.8 94.8 90.1 73.8 -

    300 104.0 104.0 104.0 90.1 73.8 -

    320 113.6 113.6 113.6 90.1 73.8 -

    340 123.4 123.4 115.9 90.1 73.8 -

    320 161.5 157.6 154.0 150.5 133.6 114.0

    340 166.5 162.6 158.8 155.2 133.6 114.0

    360 170.8 166.7 162.8 159.1 133.6 114.0

    380 183.2 178.9 174.7 161.4 133.6 114.0

    400 196.0 191.4 186.9 161.4 133.6 114.0

    420 209.1 204.2 199.4 161.4 133.6 114.0360 185.0 181.3 177.7 174.3 171.0 167.9

    380 193.4 189.5 185.8 182.2 178.8 175.5

    400 206.6 202.5 198.5 194.7 191.0 176.1

    420 220.2 215.8 211.5 207.5 203.6 176.1

    440 234.0 229.3 224.8 220.5 206.5 176.1

    460 248.2 243.2 238.4 233.8 206.5 176.1

    450 280.8 276.0 271.3 266.8 262.4 253.6

    500 308.2 302.8 297.7 292.8 288.0 253.6

    550 339.7 333.8 328.2 322.7 297.4 253.6

    600 380.5 373.9 367.6 359.3 297.4 253.6

    700 465.4 457.3 449.6 359.3 297.4 253.6

    800 485.6 477.2 451.2 359.3 297.4 253.6

    600 441.1 434.6 428.3 422.2 369.3 315.0

    650 485.1 478.0 471.0 441.8 369.3 315.0

    700 529.9 522.1 514.5 441.8 369.3 315.0

    800 620.9 611.8 554.1 441.8 369.3 315.0

    900 712.7 666.4 554.1 441.8 369.3 315.0

    1000 745.3 666.4 554.1 441.8 369.3 315.0

    600 485.1 485.1 485.1 485.1 485.1 485.1

    650 515.5 515.5 515.5 515.5 515.5 515.5

    700 561.4 561.4 561.4 561.4 561.4 561.4

    800 654.4 654.4 654.4 654.4 654.4 586.9

    900 747.9 747.9 747.9 747.9 684.7 586.9

    1000 840.1 840.1 840.1 811.4 684.7 586.9

    10

    Shear Load Connectors

    DSD 25

    DSD/DSDQ 30

    DSD/DSDQ 50

    DSD/DSDQ 65

    DSD/DSDQ 75

    DSD/DSDQ 100

    DSD/DSDQ 130

    DSD/DSDQ 150

    DSD/DSDQ 400

    DSD/DSDQ 450

    DSD AND DSDQ SHEAR CONNECTORS

  • 8/11/2019 Ancon Shear Load Connector

    11/30

    11

    Tel: +44 (0) 114 275 5224 Web: www.ancon.co.uk

    Slab Thickness Product Joint Widths (mm)(mm) Reference 10 20 30 40 50 60

    180 44.7 41.8 29.9 23.2 - -

    200 51.8 41.8 29.9 23.2 - -

    220 59.3 41.8 29.9 23.2 - -

    240 67.3 41.8 29.9 23.2 - -

    260 69.6 41.8 29.9 23.2 - -

    280 69.6 41.8 29.9 23.2 - -

    180 48.3 48.3 44.6 34.7 - -

    200 55.7 55.7 44.6 34.7 - -

    220 63.6 62.4 44.6 34.7 - -

    240 71.8 62.4 44.6 34.7 - -

    260 80.5 62.4 44.6 34.7 - -

    280 89.7 62.4 44.6 34.7 - -

    180 49.6 49.6 49.6 49.4 40.4 -

    200 57.0 57.0 57.0 49.4 40.4 -

    220 64.9 64.9 63.5 49.4 40.4 -

    240 73.2 73.2 63.5 49.4 40.4 -

    260 82.0 82.0 63.5 49.4 40.4 -

    280 91.1 88.9 63.5 49.4 40.4 -

    180 61.8 61.8 61.8 61.8 55.4 -200 70.5 70.5 70.5 67.7 55.4 -

    220 72.8 72.8 72.8 67.7 55.4 -

    240 77.8 77.8 77.8 67.7 55.4 -

    260 86.6 86.6 86.6 67.7 55.4 -

    280 95.8 95.8 87.1 67.7 55.4 -

    240 97.6 97.6 97.6 90.1 73.8 -

    260 101.0 101.0 101.0 90.1 73.8 -

    280 107.4 107.4 107.4 90.1 73.8 -

    300 117.9 117.9 115.9 90.1 73.8 -

    320 128.7 128.7 115.9 90.1 73.8 -

    340 139.9 139.9 115.9 90.1 73.8 -

    320 183.0 178.7 174.5 161.4 133.6 114.0

    340 188.7 184.3 180.0 161.4 133.6 114.0

    360 193.5 188.9 184.5 161.4 133.6 114.0

    380 207.7 202.7 198.0 161.4 133.6 114.0

    400 222.2 216.9 203.9 161.4 133.6 114.0

    420 237.0 231.4 203.9 161.4 133.6 114.0360 209.7 205.5 201.4 197.6 193.8 176.1

    380 219.2 214.8 210.6 206.5 202.7 176.1

    400 234.2 229.5 225.0 220.7 206.5 176.1

    420 249.5 244.5 239.8 235.1 206.5 176.1

    440 265.2 259.9 254.8 249.5 206.5 176.1

    460 281.2 275.6 270.2 249.5 206.5 176.1

    450 318.2 312.8 307.5 302.3 297.4 253.6

    500 349.2 343.2 337.4 331.8 297.4 253.6

    550 385.0 378.3 371.9 359.3 297.4 253.6

    600 431.2 423.8 416.6 359.3 297.4 253.6

    700 527.4 518.3 451.2 359.3 297.4 253.6

    800 582.7 553.0 451.2 359.3 297.4 253.6

    600 499.9 492.5 485.4 441.8 369.3 315.0

    650 549.8 541.7 533.8 441.8 369.3 315.0

    700 600.5 591.7 554.1 441.8 369.3 315.0

    800 703.7 666.4 554.1 441.8 369.3 315.0

    900 778.7 666.4 554.1 441.8 369.3 315.0

    1000 778.7 666.4 554.1 441.8 369.3 315.0

    600 549.8 549.8 549.8 549.8 549.8 549.8

    650 584.2 584.2 584.2 584.2 584.2 584.2

    700 636.2 636.2 636.2 636.2 636.2 586.9

    800 741.7 741.7 741.7 741.7 684.7 586.9

    900 847.6 847.6 847.6 811.4 684.7 586.9

    1000 952.1 952.1 941.1 811.4 684.7 586.9

    FRd Design Capacities (kN) for Various Joint Widths (mm) and Slab Thickness (mm) using C30/37 Concrete

    DSD 25

    DSD/DSDQ 30

    DSD/DSDQ 50

    DSD/DSDQ 65

    DSD/DSDQ 75

    DSD/DSDQ 100

    DSD/DSDQ 130

    DSD/DSDQ 150

    DSD/DSDQ 400

    DSD/DSDQ 450

    DSD Design Example

    Slab thickness = 400mmJoint width = 30mmConcrete strength = C30/37Characteristic dead load = 100kN/m G = 1.35*Character istic imposed load = 120kN/m Q = 1.5*Design load = (100 x 1.35) + (120 x 1.5) = 315kN/m

    FRd (Design capacity) Maximum centresDSD100 = 203.9kN = 203.9 / 315 = 0.647m use 600mmDSD130 = 225.0kN = 225.0 / 315 = 0.714m use 700mm

    *The partial safety factors of 1.35 (G) and 1.5 (Q) are those recommended in EN 1990 Eurocode: Basis for structural design.For designs to Eurocode 2, please refer to the national annex for the factors to be used in the country concerned. For designersto BS8110, G = 1.4 andQ = 1.6. Other national standards may require different safety factors.

    Either connector would be acceptable, althoughusing DSD130s at 700mm centres would minimisethe number of connectors to be installed.

  • 8/11/2019 Ancon Shear Load Connector

    12/30

    Shear Load Connectors

    12

    Reinforcement Details

    Local reinforcement is required around each

    connector to guarantee that the forces are

    transferred between the connectors and the

    concrete. Correct detailing in accordance with

    appropriate design codes and therecommendations provided here will ensure

    Ancon DSD and DSDQ connectors attain their

    full capacity.

    The tables show proposals for the type and

    spacing of the main reinforcement, together

    with details of reinforcement above and below

    the connectors.Main reinforcement each

    side of connector

    Longitudinalreinforcement

    above connectors

    Longitudinalreinforcement

    below connectors

    Longitudinalreinforcement

    above connectors

    Longitudinalreinforcement

    below connectors

    * DSD only

    Mainreinforcement

    each side of connector

    DSD/DSDQ Options for Main Reinforcement (No. of U-bars each side)

    Reference H8 H10 H12 H14 H16 H20

    25* 3 2 - - - -

    30 - 3 2 - - -

    50 - 3 3 - - -

    65 - 4 3 - - -

    75 - 5 4 3 - -

    100 - - 5 4 3 -

    130 - - - 5 4 3

    150 - - - - 6 4

    400 - - - - 7 5

    450 - - - - 9 7

    DSD/DSDQ Options for Main Reinforcement (No. of U-bars each side)Reference H8 H10 H12 H14 H16 H20

    25* 3 2 - - - -

    30 - 3 2 - - -

    50 - 4 3 - - -

    65 - 4 3 - - -

    75 - 5 4 3 - -

    100 - - 6 5 4 -

    130 - - - 5 4 3

    150 - - - - 6 5

    400 - - - - 6 5

    450 - - - - 9 7

    DSD/DSDQ Options for Longitudinal Reinforcement (No. of bars top and bottom)

    Reference H8 H10 H12 H14 H16 H20

    25* 2 2 - - - -

    30 2 2 - - - -

    50 - 2 2 - - -

    65 - 2 2 - - -75 - 3 2 - - -

    100 - - 3 3 2 -

    130 - - 4 3 2 -

    150 - - - - 4 3

    400 - - - - 5 3

    450 - - - - 7 5

    DSD/DSDQ Options for Longitudinal Reinforcement (No. of bars top and bottom)Reference H8 H10 H12 H14 H16 H20

    25* 2 2 - - - -

    30 2 2 - - - -

    50 - 2 2 - - -

    65 - 2 2 - - -

    75 - 3 2 - - -

    100 - - 3 2 2 -

    130 - - 3 3 2 -

    150 - - - - 4 3

    400 - - - - 5 3

    450 - - - - 6 4

    Based on C25/30 concrete, maximum slab depth (see table on page 10) and 20mm joint

    Based on C30/37 concrete, maximum slab depth (see table on page 11) and 20mm joint

  • 8/11/2019 Ancon Shear Load Connector

    13/30

    13

    Tel: +44 (0) 114 275 5224 Web: www.ancon.co.uk

    RefDSD Max CoverDSDQ to Face (mm)

    25* 30

    30 30

    50 30

    65 40

    75 50

    100 50

    130 50

    150 50

    400 60

    450 60

    50mm min.

    Where a sleeve component is cast into a wall

    the thickness of the wall should be at least

    50mm more than the length of the sleeve.

    Cover

    Minimum cover to local reinforcement is to the

    recommendations of BS 8110 Part 1: 1997.

    Maximum cover is as shown below:-

    Wall Reinforcement

    Reinforcement in walls is designed in the

    conventional way as though the slab was

    integral with the wall. The additional local

    reinforcement is in the form of a square mesh

    or loose bar equivalent to the details as shown

    below.

    Ref Bar Maximum MinimumDSD Diameter Centres Width/DepthDSDQ (mm) (mm) (mm)

    25* 8 100 300

    30 8 100 300

    50 8 100 300

    65 10 100 400

    75 12 150 450

    100 12 150 450

    130 12 150 600

    150 12 175 700

    450mmmin.

    Minimum Widthand Depth

    450mm min.

    DSD75Sleevecomponent

    H12 at 150mm

    max. centres

    Reinforcement for DSD 75s in a Wall

    Wall Reinforcement

    Local Reinforcementto Connector

    * DSD only

    * DSD only

    Cover

  • 8/11/2019 Ancon Shear Load Connector

    14/30

    Shear Load Connectors

    14

    Dowel Component DSD Sleeve DSDQ Sleeve

    Ref Dowel Component DSD Sleeve DSDQ Sleeve

    DSD Overall Dowel Dowel Dowel Anchor Bar Anchor Bar Overall Anchor Bar Anchor Bar Overall Anchor Bar Anchor Bar LateralDSDQ Length Dia Centres Projection Position Lengths Length Position Lengths Length Position Length Movnt

    25* 250 14 40 120 31 50/110 120 28 50/110 - - - -

    30 260 16 48 120 31 50/110 120 28 50/110 140 33 70 26

    50 280 18 50 130 31 50/130 135 28 50/130 160 33 70 25

    65 300 20 65 150 31 50/130 155 29 50/130 175 33 70 21

    75 340 22 75 150 33 50/150 155 31 50/150 175 33 120 20

    100 400 30 100 210 34 80/170 210 36 80/170 235 54 170 41

    130 470 35 105 260 34 80/170 265 36 80/170 275 59 170 36

    150 550 42 120 270 54 80/210 275 41 80/210 305 54 170 21

    400 660 52 160 330 70 130/300 335 70 130/300 350 64 300 27

    450 690 65 180 360 80 130/300 370 80 130/300 400 89 300 54

    Dowel bardiameter

    Anchor barposition

    Anchor barposition

    Projection

    Sleeve length

    Anchor barposition

    Sleeve lengthDowel length

    Anchor barlengths

    Anchor barlengths

    Anchor barlengths

    Maximumlateralmovement

    Centres

    Notes: *DSD only. All dimensions are in millimetres (mm).

    Edge Distance and SpacingThe minimum edge distance and spacing of all

    Ancon shear load connectors is determined by

    the depth of slab and is illustrated in the

    adjacent drawing.

    min. 0.75 H

    H

    min. 1.50 H

    Dimensions

  • 8/11/2019 Ancon Shear Load Connector

    15/30

    Edge Distance and Spacing

    The minimum edge distance and spacing of all

    Ancon shear load connectors is determined by

    the depth of slab and is illustrated in the

    adjacent drawing.

    min. 0.75 H

    H

    min. 1.50 H

    15

    Tel: +44 (0) 114 275 5224 Web: www.ancon.co.uk

    RefDowel Component ESD Sleeve ESDQ Sleeve

    ESD Dowel Dowel Internal Sleeve Internal Sleeve Max. LateralESDQ Diameter Length Diameter Length Diameter Length Movement

    10 300 20 300 21 175 21 175 20

    10 400 20 400 21 225 21 225 20

    15 300 22 300 23 175 23 175 20

    15 400 22 400 23 225 23 225 20

    20 300 30 300 31 175 31 175 41

    20 400 30 400 31 225 31 225 41

    25 350 35 350 36 200 36 200 36

    25 470 35 470 36 260 36 260 36

    Note: Example Ref ESD10 300

    Dowel length Sleeve length Sleeve length

    Internal diameter Internal diameterMaximum

    lateralmovementDowel

    diameter

    ESD10/15 76

    ESD20/25 100

    ESDQ10/15 76

    ESDQ20/25 110Dimensions

    ANCON ESD AND ESDQ SHEAR CONNECTORS

    Dowel Dowel Sleeve SleeveRef Length Diameter Length Diameter

    Staisil 400 35 127 64

    Dowel length Sleeve length80

    Doweldiameter

    Doweldiameter

    Sleeve

    diameter

    ANCON ED SHEAR CONNECTORS

    ANCON STAISIL ACOUST IC CONNECTORS

    100 Sleeve lengthDowel length

    Dimensions

    Dimensions

    Ref Dowel Dowel SleeveED Length Diameter Length

    10 300 300 20 170

    10 400 400 20 220

    15 300 300 22 170

    15 400 400 22 220

    20 300 300 30 170

    20 400 400 30 220

    25 350 350 35 195

    25 470 470 35 260

    Dowel Component ESD Sleeve ESDQ Sleeve

    Dowel Component ED Sleeve

    Dowel Component Staisil Sleeve

  • 8/11/2019 Ancon Shear Load Connector

    16/30

    Slab Thickness Product Joint Widths (mm)(mm) Reference 10 20 30 40

    180 25.6 25.6 22.4 19.7

    200 26.7 25.7 22.4 19.7

    220 26.7 25.7 22.4 19.7

    240 26.7 25.7 22.4 19.7260 26.7 25.7 22.4 19.7

    280 26.7 25.7 22.4 19.7

    180 28.7 28.7 28.1 24.9

    200 32.3 31.9 28.1 24.9

    220 32.3 31.9 28.1 24.9

    240 32.3 31.9 28.1 24.9

    260 32.3 31.9 28.1 24.9

    280 32.3 31.9 28.1 24.9

    220 47.3 47.3 47.3 47.3

    240 54.9 54.9 54.9 52.7

    260 60.0 60.0 57.8 52.7

    280 60.0 60.0 57.8 52.7

    300 60.0 60.0 57.8 52.7

    350 60.0 60.0 57.8 52.7

    240 56.8 56.8 56.8 55.7

    260 65.0 65.0 61.5 55.7

    280 73.7 68.0 61.5 55.7

    300 75.4 68.0 61.5 55.7

    350 75.4 68.0 61.5 55.7

    400 75.4 68.0 61.5 55.7

    16

    Shear Load Connectors

    FRd Design Capacities (kN) for Various Joint Widths (mm) and Slab Thickness (mm) using C25/30 Concrete

    ESD/ESDQ 10

    ESD/ESDQ 15

    ESD/ESDQ 20

    ESD/ESDQ 25

    Slab Thickness Product Joint Widths (mm)(mm) Reference 10 20 30 40

    180 25.6 25.6 22.4 19.7

    200 26.7 25.7 22.4 19.7

    220 26.7 25.7 22.4 19.7

    240 26.7 25.7 22.4 19.7

    260 26.7 25.7 22.4 19.7

    280 26.7 25.7 22.4 19.7

    180 28.7 28.7 28.1 24.9

    200 32.3 31.9 28.1 24.9

    220 32.3 31.9 28.1 24.9

    240 32.3 31.9 28.1 24.9

    260 32.3 31.9 28.1 24.9

    280 32.3 31.9 28.1 24.9

    220 47.3 47.3 47.3 47.3

    240 54.9 54.9 54.9 52.7

    260 60.0 60.0 57.8 52.7

    280 60.0 60.0 57.8 52.7

    300 60.0 60.0 57.8 52.7

    350 60.0 60.0 57.8 52.7

    240 56.8 56.8 56.8 55.7

    260 65.0 65.0 61.5 55.7

    280 73.7 68.0 61.5 55.7

    300 75.4 68.0 61.5 55.7

    350 75.4 68.0 61.5 55.7

    400 75.4 68.0 61.5 55.7

    Slab Thickness Product Joint Widths (mm)

    (mm) Reference 10 20 30 40160 22.3 22.3 22.3 22.3

    180 27.8 27.4 24.9 22.7

    200 30.3 27.4 24.9 22.7

    220 30.3 27.4 24.9 22.7

    240 30.3 27.4 24.9 22.7

    260 30.3 27.4 24.9 22.7

    Staisil

    ED 10

    ED 15

    ED 20

    ED 25

  • 8/11/2019 Ancon Shear Load Connector

    17/30

    17

    Tel: +44 (0) 114 275 5224 Web: www.ancon.co.uk

    Slab Thickness Product Joint Widths (mm)(mm) Reference 10 20 30 40

    180 29.1 25.7 22.4 19.7

    200 29.6 25.7 22.4 19.7

    220 29.6 25.7 22.4 19.7

    240 29.6 25.7 22.4 19.7260 29.6 25.7 22.4 19.7

    280 29.6 25.7 22.4 19.7

    180 32.6 31.9 28.1 24.9

    200 36.3 31.9 28.1 24.9

    220 36.3 31.9 28.1 24.9

    240 36.3 31.9 28.1 24.9

    260 36.3 31.9 28.1 24.9

    280 36.3 31.9 28.1 24.9

    220 53.6 53.6 53.6 52.7

    240 62.2 62.2 57.8 52.7

    260 69.9 63.5 57.8 52.7

    280 69.9 63.5 57.8 52.7

    300 69.9 63.5 57.8 52.7

    350 69.9 63.5 57.8 52.7

    240 64.4 64.4 61.5 55.7

    260 73.7 68.0 61.5 55.7

    280 75.4 68.0 61.5 55.7

    300 75.4 68.0 61.5 55.7

    350 75.4 68.0 61.5 55.7

    400 75.4 68.0 61.5 55.7

    FRd Design Capacities (kN) for Various Joint Widths (mm) and Slab Thickness (mm) using C30/37 Concrete

    ESD/ESDQ 10

    ESD/ESDQ 15

    ESD/ESDQ 20

    ESD/ESDQ 25

    Slab Thickness Product Joint Widths (mm)(mm) Reference 10 20 30 40

    180 29.1 25.7 22.4 19.7

    200 29.6 25.7 22.4 19.7

    220 29.6 25.7 22.4 19.7

    240 29.6 25.7 22.4 19.7

    260 29.6 25.7 22.4 19.7

    280 29.6 25.7 22.4 19.7

    180 32.6 31.9 28.1 24.9

    200 36.3 31.9 28.1 24.9

    220 36.3 31.9 28.1 24.9

    240 36.3 31.9 28.1 24.9

    260 36.3 31.9 28.1 24.9

    280 36.3 31.9 28.1 24.9

    220 53.6 53.6 53.6 52.7

    240 62.2 62.2 57.8 52.7

    260 69.9 63.5 57.8 52.7

    280 69.9 63.5 57.8 52.7

    300 69.9 63.5 57.8 52.7

    350 69.9 63.5 57.8 52.7

    240 64.4 64.4 61.5 55.7

    260 73.7 68.0 61.5 55.7

    280 75.4 68.0 61.5 55.7

    300 75.4 68.0 61.5 55.7

    350 75.4 68.0 61.5 55.7

    400 75.4 68.0 61.5 55.7

    ED 10

    ED 15

    ED 20

    ED 25

    Slab Thickness Product Joint Widths (mm)

    (mm) Reference 10 20 30 40160 25.3 25.3 24.9 22.7

    180 30.3 27.4 24.9 22.7

    200 30.3 27.4 24.9 22.7

    220 30.3 27.4 24.9 22.7

    240 30.3 27.4 24.9 22.7

    260 30.3 27.4 24.9 22.7

    Staisil

    ESD Design Example

    Slab thickness = 220mmJoint width = 30mmConcrete strength = C30/37Characteristic dead load = 20kN/m G = 1.35*Character istic imposed load = 26kN/m Q = 1.5*Design load = (20 x 1.35) + (26 x 1.5) = 66kN/m

    FRd (Design capacity) Maximum centres

    ESD10 = 22.4kN = 22.4 / 66 = 0.339m use 330mmESD15 = 28.1kN = 28.1 / 66 = 0.426m use 400mmESD20 = 53.6kN = 53.6 / 66 = 0.812m use 800mm

    *The partial safety factors of 1.35 (G) and 1.5 (Q) are those recommended in EN 1990 Eurocode: Basis for structural design.For designs to Eurocode 2, please refer to the national annex for the factors to be used in the country concerned. For designersto BS8110, G = 1.4 and Q = 1.6. Other national standards may require different safety factors.

    Any of the three connectors would be acceptable,although using ESD20s at 800mm centres wouldminimise the number of connectors to be installed.

  • 8/11/2019 Ancon Shear Load Connector

    18/30

    18

    Shear Load Connectors

    ED/ESD/ESDQ/Staisil Options for Main Reinforcement (No. of U-bars each side)Reference H8 H10 H12 H14

    10 2 2 - -15 2 2 - -20 3 3 2 -25 - 3 3 2Staisil 2 2 - -

    ED/ESD/ESDQ/Staisil Options for Longitudinal Reinforcement (No. of bars top and bottom)Reference H8 H10 H12 H14

    10 2 2 - -15 2 2 - -20 2 2 2 -25 3 2 2 -

    Staisil 2 2 - -

    ED/ESD/ESDQ/Staisil Options for Main Reinforcement (No. of U-bars each side)

    Reference H8 H10 H12 H14

    10 2 1 - -

    15 2 2 - -

    20 3 2 2 -

    25 - 3 3 2

    Staisil 2 2 - -

    ED/ESD/ESDQ/Staisil Options for Longitudinal Reinforcement (No. of bars top and bottom)Reference H8 H10 H12 H14

    10 2 2 - -

    15 2 2 - -

    20 2 2 2 -

    25 3 2 2 -Staisil 2 2 - -

    Based on C30/37 concrete, maximum slab depth (see table on page 17) and 20mm joint

    Based on C25/30 concrete, maximum slab depth (see table on page 16) and 20mm joint

    Reinforcement Details

    Local reinforcement is required around each

    connector to guarantee that the forces are

    transferred between the connectors and the

    concrete. Correct detailing in accordance with

    appropriate design codes and therecommendations provided here will ensure

    Ancon ESD, ESDQ, ED and Staisil connectors

    attain their full capacity.

    The tables show proposals for the type and

    spacing of the main reinforcement, together

    with details of reinforcement above and below

    the connectors. Main reinforcement eachside of connector

    Longitudinalreinforcement

    above connectors

    Longitudinal

    reinforcementbelow connectors

    Longitudinalreinforcement

    above connectors

    Longitudinalreinforcement

    below connectors

    Mainreinforcement

    each side of connector

  • 8/11/2019 Ancon Shear Load Connector

    19/30

    19

    Tel: +44 (0) 114 275 5224 Web: www.ancon.co.uk

    OTHER ANCON PRODUCTS

    Reinforcement Continuity Systems

    Reinforcement Continuity Systems are an

    increasingly popular means of maintaining

    continuity of reinforcement at construction

    joints in concrete. Ancon Eazistrip is approvedby UK CARES and consists of pre-bent bars

    housed within a galvanised steel casing. Once

    installed, the protective cover is removed and

    the bars are straightened. Ancon Starter Bars

    are supplied fixed to an Ancon coupler. Once

    cast in concrete, the couplers end cap is

    removed and a threaded continuation bar is

    installed with a calibrated torque wrench to

    complete the connection.

    Reinforcing Bar Couplers

    The use of reinforcing bar couplers can provide

    significant advantages over lapped joints.Design and construction of the concrete can

    be simplified and the amount of reinforcement

    required can be reduced. Because the strength

    of a mechanical splice is independent of the

    concrete in which it is located, the joint can

    also remain unaffected by any loss of cover.

    The range includes threaded and mechanically

    bolted couplers.

    Punching Shear Reinforcement

    Used within a slab to provide additional

    reinforcement around columns, Ancon Shearfix

    is the ideal solution to the design andconstruction problems associated with

    punching shear. The system consists of

    double-headed studs welded to flat rails,

    positioned around the column. The shear load

    from the slab is transferred through the studs

    into the column.

    Insulated Balcony Connections

    Ancon Isolan connectors join external concrete

    balconies to internal floor slabs. Used to

    minimise cold bridging, they provide continuity

    to the thermal insulation. Standard systems,

    comprising rigid CFC-free polystyrene insulation

    and duplex stainless steel shear reinforcement,

    suit most depths of cantilevered and simply

    supported balconies. Conventional reinforcing

    bars are used to provide the tension and

    compression reinforcement.

    Channels and Bolts for Fixing to Concrete

    Cast-in channels are used for fixing masonry

    support systems to the edges of concrete

    floors and beams. Channels are available in

    different sizes ranging from simple self

    anchoring channels for restraints, to large

    capacity channels with integral anchors.

    A selection of channels can also be supplied

    plain-backed for surface fixing. Stainless steel

    expansion bolts and resin anchors complete

    the range.

    APPLICATIONS

    Channel Tunnel Terminal, UK

    Forum Shopping Centre, Algarve

    Melbourne Cricket Ground, Australia

    Scottish Widows, Edinburgh, UK

    Olympic Stadium, Sydney, Australia

  • 8/11/2019 Ancon Shear Load Connector

    20/30

    The construction applications and details provided in this literatureare indicative only. In every case, project working details should be

    entrusted to appropriately qualified and experienced persons.

    Whilst every care has been exercised in the preparation of this

    document to ensure that any advice, recommendations or

    information is accurate, no liability or responsibility of any kind isaccepted in respect of Ancon Building Products.

    With a policy of continuous product development Ancon BuildingProducts reserves the right to modify product design and

    specification without due notice.

    These products are available from:

    Ancon Building ProductsPresident Way, President ParkSheffield S4 7UR

    United KingdomTel: +44 (0) 114 275 5224Fax: +44 (0) 114 276 8543Email: [email protected]: www.ancon.co.uk

    Ancon (Middle East) FZEPO Box 17225Jebel AliDubaiUnited Arab EmiratesTel: +971 (0) 4 883 4346Fax: +971 (0) 4 883 4347Email: [email protected]: www.ancon.ae

    Ancon Building Products114 Kurrajong AvenueMount DruittSydneyNSW 2770AustraliaTel: +61 (0) 2 8808 1111Fax: +61 (0) 2 9675 3390Email: [email protected]: www.anconbp.com.au

    Ancon (Schweiz) AGGewerbezone Widalmi 103216 Ried bei Kerzers

    SwitzerlandTel: +41 (0) 31 750 3030Fax: +41 (0) 31 750 3033Email: [email protected]: www.ancon.ch

    Ancon Building Products GesmbHGerspergasse 9/3 Top 1A-1210 ViennaAustriaTel: +43 (0) 1 259 58 62-0Fax: +43 (0) 1 259 58 62-40Email: [email protected]: www.ancon.at

    Ancon GmbHBartholomusstrasse 2690489 NurembergGermanyTel: +49 (0) 911 955 1234 0Fax: +49 (0) 911 955 1234 9Email: [email protected]: www.anconbp.de

    Ancon Building Products 2008

    ISO 9001: 2000

    FM 12226

    ISO 14001: 2004

    EMS 505377

  • 8/11/2019 Ancon Shear Load Connector

    21/30

    E-HLD

    Shear Load

    ConnectorsFor the connection of new slabs todiaphragm walls or secant pile walls inbasement construction

  • 8/11/2019 Ancon Shear Load Connector

    22/30

    Once the resin reaches full strength, the sleeve component is

    pushed over the exposed end of the dowel. The required local

    reinforcement is located around the sleeve, ensuring that the

    correct cover is maintained. The concrete is cast to complete the

    installation.

    *In applications where movement needs to be accommodated,

    please contact Ancon.

    Ancon E-HLD Shear Load Connector

    The Ancon E-HLD joins new concrete slabs to existing concrete

    walls. It is designed to transfer shear load where new slabs are

    connected to diaphragm walls or secant pile walls in basement

    construction*.

    The E-HLD comprises a stainless steel dowel and a high

    strength, stainless steel sleeve. It is available in seven standard

    sizes and can be used in a slab thickness from 160mm andjoints up to 60mm wide. Ancon two-part resin is required to

    install the dowel component. The quantity of resin cartridges

    required will depend on dowel diameter and number being fixed.

    Ancon Building Products

    President Way, President Park, Sheffield S4 7UR, United Kingdom,

    Tel: +44 (0) 114 275 5224, Fax: +44 (0) 114 276 8543

    Email: [email protected] Visit: www.ancon.co.uk

    Product Dowel Component Sleeve Component

    Reference Diameter Length Length Height Width

    E-HLD 18 18 270 155 75 70

    E-HLD 22 22 300 165 95 90

    E-HLD 24 24 330 175 110 100

    E-HLD 30 30 350 190 140 115

    E-HLD 35 35 400 215 160 132

    E-HLD 42 42 470 245 180 175

    E-HLD 52 52 570 295 220 210

    Dimensions

    Minimum FRd

    Design Capacities (kN) for VariousSlab (mm) Product Joint Widths (mm) using C25/30 ConcreteThickness B Reference 10 20 30 40 50 60

    160 E-HLD 18 41.8 36.8 30.1 25.0 21.4 18.7

    180 E-HLD 22 69.6 59.2 50.5 42.6 36.8 32.4200 E-HLD 24 83.1 71.7 62.2 53.6 46.5 41.1

    240 E-HLD 30 120.2 106.2 94.2 83.3 73.2 65.2

    300 E-HLD 35 165.7 148.6 133.8 120.4 107.3 96.3

    350 E-HLD 42 200.8 182.5 166.4 151.6 136.9 123.8

    400 E-HLD 52 302.3 280.0 260.1 242.2 225.9 210.8

    Performance

    Product Options for Main Reinforcement (No. of U-bars each side)Reference H8 H10 H12 H14 H16 H20

    E-HLD 18 3 2 2 - - -

    E-HLD 22 - 3 3 2 - -

    E-HLD 24 - - 3 2 2 -

    E-HLD 30 - - 4 3 3 -

    E-HLD 35 - - - 4 3 2

    E-HLD 42 - - - 4 4 3

    E-HLD 52 - - - - 5 3

    Product Options for Longitudinal Reinforcement (No. of bars top and bottom)Reference H8 H10 H12 H14 H16 H20

    E-HLD 18 2 2 - - - -

    E-HLD 22 3 2 2 - - -

    E-HLD 24 - 2 2 2 - -

    E-HLD 30 - - 3 2 2 -

    E-HLD 35 - - 3 2 2 -

    E-HLD 42 - - - 2 2 2

    E-HLD 52 - - - 3 2 2

    Note:The longitudinal reinforcement assumes that the E-HLDs are positioned at onemetre centres.

    Dowel Diameter (mm) 18 22 24 30 35 42 52

    Depth A (mm) 130 155 170 180 205 240 290

    Approx. No. Dowels per Cartridge 16 10 9 6 4 3 2

    Local Reinforcement - Second Phase

    Edge Distance and Spacing - Second Phase

    The minimum edge distance is determined by the depth of the

    adjoining slab.

    End cap

    Longitudinalmovement

    Dowel

    component

    Sleevecomponent

    A hole should be drilled no more than 5mm wider than the

    dowel, to the depth shown in the table. Ancons two-part resin is

    injected into the hole and the dowel is inserted.

    min. 0.75 B

    B

    min. 1.50 B

    Installation

    Second phase - The sleeve component is installed.

    First phase - The dowel component is resin-fixed in the wall

    Doweldiameter

    Sleeve length Width 12

    A

    12Dowel length

    Height

  • 8/11/2019 Ancon Shear Load Connector

    23/30

    Lockable DowelsFor Temporary Movement Joints

    CI/SfB (29) Et6

    April 2009

  • 8/11/2019 Ancon Shear Load Connector

    24/30

    2

    The Lockable Dowel 2

    Slab-to-Slab Lockable Dowels 3

    Slab-to-Wall Lockable Dowel 3

    Performance Data 4

    Dimensions 5

    Edge Distance and Spacings 5

    Reinforcement Details 6

    Installation Procedure 7

    Ancon Lockable Dowels

    THE LOCKABLE DOWEL

    Ancon Lockable Dowels have been designed

    for use at temporary movement joints, most

    commonly found in post-tensioned concrete

    construction. The dowel allows initial shrinkage

    of the concrete to take place and is thenlocked in position with a mechanical plate and

    a controlled amount of epoxy resin. The locked

    dowel continues to transfer shear, but prevents

    further movement taking place.

    A Lockable Dowel provides many advantages

    over a site-assembled arrangement of carbon

    steel reinforcing bar, galvanised or plastic

    ducting, vent tubes and a non-specific grout.

    Use of a Lockable Dowel eliminates the need

    for complicated formwork and the additional

    materials used to construct a support corbel.

    The design capacities shown on page 4 are

    backed by independent test data and the

    unique void former allows inspection of the

    dowel before the joint is locked.

    Lockable Dowels can improve site access.

    When installed at slab joints they do not

    require to be propped from below and they

    replace pour strips, which are a potential trip

    hazard on site.

    Standard Ancon systems are available to suit

    slab joints and retaining / core walls.

    The performance of site-assembled components is unreliable and in mostapplications a support corbel is required.

    The Ancon Lockable Dowel has beenindependently tested and is easy

    to install.

    Slab-to-Slab

    Slab-to-Slab (Heavy Duty)

    Slab-to-Wall

  • 8/11/2019 Ancon Shear Load Connector

    25/30

    2 3

    SLAB-TO-SLAB LOCKABLE DOWELS

    ESDQ-L20*

    The dowel component is manufactured from

    30mm diameter Duplex stainless steel; one

    end is threaded with a fixed nut and washer,

    and the other features a series of grooves to

    accept the Locking Plate. The cylindrical

    sleeve which accepts the dowel component is

    contained within a box-section to allow lateral,

    longitudinal and some rotational movement.

    The epoxy resin is poured into the L-shaped

    void former. This product has a design

    capacity of almost 70kN. See pages 4-7 for

    full technical details.

    A Lockable Dowel allows initial shrinkage of the concrete to take place and then, after a pre-determined time period (generally 60-120 days), is locked in

    position with a mechanical plate and a controlled amount of epoxy resin. The range comprises three products; ESDQ-L20, HLDQ-L30 and ESDQ-L20W

    SLAB-TO-WALL LOCKABLE DOWEL

    ESDQ-L20W*

    The dowel component is manufactured from

    30mm diameter Duplex stainless steel, but is

    shorter than the ESDQ-L20 dowel. One end of

    the dowel is designed to fix into the stainless

    steel Ancon SKS24 Threaded Anchor cast into

    the face of the concrete and the other end

    features a series of grooves to accept the

    Locking Plate. The sleeve component is the

    same as used in the ESDQ-L20. See pages

    4-7 for full technical details.

    Slab-to-Wall Application

    Epoxy Resin

    Each dowel is locked after a pre-determined

    time period (generally 60-120 days) with a high

    quality, two-part epoxy resin. The resin is

    mixed and poured into the L-shaped void

    former. One 1.5 litre can is supplied per dowel.

    ESDQ-L20W

    for Slab-to-Wall

    SKS24 Threaded Anchorsupplied with a nailing plate

    * Patent pending

    Locking Plate

    Two-part Epoxy Resin

    Sleeve Componentsupplied with label onnailing plate

    Sleeve Componentsupplied with labelon nailing plate

    Two-part Epoxy Resin

    Two-part Epoxy Resin

    Sleeve Componentsupplied with label onnailing plate

    ESDQ-L20

    for Slab-to-Slab

    HLDQ-L30for Slab-to-Slab

    Dowel Component

    Dowel Component

    Dowel Component

    Locking Plate

    Locking Plate

    Tel: +44 (0) 114 275 5224 Web: www.ancon.co.uk

    HLDQ-L30*

    The HLDQ-L30 is a high load Lockable Dowel

    with a design capacity of up to 136kN. See

    pages 4-7 for full technical details.

  • 8/11/2019 Ancon Shear Load Connector

    26/30

    4

    Ancon Lockable Dowels

    PERFORMANCE DATA

    Design Resistance Along the Line of the DowelWhen used slab-to-slab, an Ancon Lockable Dowel provides a design resistance along the line of

    the dowel of 100kN. For the slab-to-wall version the design resistance is 80kN.

    Vertical Design Resistance

    ESDQ-L20 and ESDQ-L20W Lockable Dowels (Slab-to-Slab or Slab-to-Wall)

    Movement

    Vertical load transferbetween slabs

    LockedVertical load transferbetween slabs

    Load transferbetween slabs

    FRD (kN) for Various Design Joint Widths in C25/30 ConcreteSlabThickness 10mm 15mm 20mm 25mm 30mm 35mm 40mm

    220mm 47.3 47.3 47.3 47.3 47.3 47.3 47.3

    240mm 54.9 54.9 54.9 54.9 54.9 54.9 52.7

    260mm and above 60.0 60.0 60.0 60.0 57.8 55.2 52.7

    FRD (kN) for Various Design Joint Widths in C30/37 Concrete

    SlabThickness 10mm 15mm 20mm 25mm 30mm 35mm 40mm

    220mm 53.6 53.6 53.6 53.6 53.6 53.6 52.7

    240mm 62.2 62.2 62.2 60.6 57.8 55.2 52.7

    260mm and above 69.9 66.6 63.5 60.6 57.8 55.2 52.7

    Vertical Design Resistance

    HLDQ-L30 Lockable Dowel (Slab-to-Slab)

    FRD (kN) for Various Design Joint Widths in C25/30 and C30/37 ConcreteSlabThickness 10mm 15mm 20mm 25mm 30mm 35mm 40mm

    240mm and above 136.0 136.0 136.0 136.0 136.0 136.0 121.9

    ESDQ-L20 Example

    Slab thickness = 240mm

    Joint width = 20mm

    Concrete strength = C30/37

    Characteristic permanent action (dead load) = 40kN/m G = 1.35*

    Characteristic variable action (imposed load) = 50kN/m Q = 1.5*

    Design load = 1.35 x 40 + 1.5 x 50 = 129kN/m

    Vertical design resistance = 62.2kN (240mm slab 20mm joint)

    Therefore centres for vertical load = 62.2 / 129 = 0.482m use 450mm centres

    Each dowel will in addition provide a design resistance across the joint of 100kN (for slab to

    wall this is 80kN), therefore the total design resistance in the direction of the dowel = 100 /

    0.45 = 222kN (for slab to wall 80 / 0.45 = 177kN)

    If this is insufficient, the dowel centres can be reduced to a minimum of 1.5 x slab thickness

    to increase the design resistance across the joint, in this example it would increase to 100 /

    0.36 = 277kN (for slab to wall 80 / 0.36 = 222kN)

    *The partial safety factors of 1.35 (G) and 1.5 (Q) are those recommended in EN 1990 Eurocode: Basis forstructural design. For designs to Eurocode 2, please refer to the national annex for the factors to be used in thecountry concerned. For designers to BS8110, G = 1.4 and Q = 1.6. Other national standards may requiredifferent safety factors.

  • 8/11/2019 Ancon Shear Load Connector

    27/30

    5

    DIMENSIONS

    ESDQ-L20 Components

    Dowel Component Sleeve Component

    HLDQ-L30 Components

    Dowel Component Sleeve Component

    ESDQ-L20W Components

    SKS24 Threaded Anchor Dowel Component

    170mm

    245mm

    110mm

    450mm

    31mm InternalDiameter30mm

    115mm 161mm12mm12mm

    140mm 140mm

    Max. 41mm

    lateralmovement

    Max. 41mmlateral

    movement

    30mm

    270mm

    490mm 280mm

    170mm

    170mm

    245mm

    31mm InternalDiameter

    31mm InternalDiameter

    103mm

    M30x3.5mm

    150mm

    40mm

    240mmmin.

    180 min. 360 min.

    h

    min. 0.75h min. 1.5h

    EDGE DISTANCE AND SPACINGS

    For connectors working at or near their

    maximum capacity, the minimum spacingshould be 1.5 times the slab thickness. Where

    the design load of the connector could be

    used in a thinner slab, a spacing of 1.5 times

    the thinner slab thickness can be used. The

    minimum end distance is always 0.5 times the

    spacing.

    ESDQ-L20 Example

    Slab thickness = 300mm

    Joint Width = 20mm

    Concrete strength = C30/37Design load per connector = 50kN

    Spacing for max. load 300 x 1.5

    = 450mm

    End distance for max. load 450 x 0.5

    = 225mm

    As an ESDQ-L20 can be used in a 220mm

    slab for a design load per connector of up

    to 53.6kN, the spacing can be based on a

    220mm slab. Therefore:

    Reduced spacing 220 x 1.5

    = 330mm

    Reduced end distance 330 x 0.5

    = 165mm

    Design resistance/metre 50 / 0.33

    = 151.5kN/m

    ESDQ-L20 Minimum Edge Distance and Spacings

    HLDQ-L30 Minimum Edge Distance and Spacings

    ESDQ-L20W Minimum Edge Distance and Spacings. h = depth of adjoining slab

    0.75h 1.5h

    100mm

    110mm

    Max. 41mmlateral

    movement100mm

    Sleeve Component

    30mm

    282mm

    Tel: +44 (0) 114 275 5224 Web: www.ancon.co.uk

  • 8/11/2019 Ancon Shear Load Connector

    28/30

    6

    Ancon Lockable Dowels

    REINFORCEMENT DETAILS

    Local reinforcement is required around each Ancon Lockable Dowel to guarantee that the forces are transferred between the connectors and the

    concrete. Correct detailing in accordance with appropriate design codes and the recommendations provided here will ensure the dowels attain their

    full capacity. The tables show the type and spacing of the main reinforcement, together with details of reinforcement above and below the

    connectors. Although only the sleeve components are illustrated, the same reinforcement is required around the dowel component.

    Threaded Anchor

    Reinforcement around the Ancon Threaded Anchor should be a minimum diameter of

    12mm, installed at maximum 200mm vertical and horizontal centres.

    Options for Main Reinforcement

    Lockable Dowel No. of U-bars each sideRef. H12 H14 H16

    ESDQ-L20 2 - -

    HLDQ-L30 4 3 3

    Options for Longitudinal Reinforcement

    Lockable Dowel No. of bars top and bottomRef. H12 H14 H16

    ESDQ-L20 2 - -

    HLDQ-L30 2 2 2Main

    reinforcementeach side of connector

    Longitudinalreinforcement

    above connectors

    Longitudinalreinforcement

    below connectors

    Longitudinalreinforcement

    above connectors

    Longitudinalreinforcement

    below connectors

    Longitudinalreinforcement

    above connectors

    Longitudinalreinforcement

    below connectors

    Mainreinforcement

    each side of connector

    Longitudinal

    reinforcementabove connectors

    Longitudinalreinforcement

    below connectors

    ESDQ-L20

    HLDQ-L30

    SKS24 Threaded Anchor, part of ESDQ-L20W

    HLDQ-L30

    ESDQ-L20

  • 8/11/2019 Ancon Shear Load Connector

    29/30

    7

    Tel: +44 (0) 114 275 5224 Web: www.ancon.co.uk

    INSTALLATION

    Slab-to-Slab

    Although installation is shown for the ESDQ-L20, the procedure is the same for the HLDQ-L30.

    Slab-to-Wall

    Notes: Where deep concrete pours are proposed, the installation will require further consideration. More robust fixing of the sleeve and dowel

    components will be necessary, to avoid displacement during casting of the concrete.

    Ensure joint has been filled before pouring resin.

    Nail the sleeve to the formwork either central in

    the slab or for slab depths over 300mm so the

    top of the grout box is level with the top of the

    slab. Do not remove the label over the nailing

    plate as this prevents ingress of concrete intothe sleeve. Fix the local reinforcement.

    1 2

    Pour the concrete, and when of sufficient

    strength, strike the formwork. Puncture the

    label to reveal the cylindrical sleeve only and

    insert the dowel until it is approximately 20mm

    from the back of the grout box.

    Mix the two-part epoxy resin and pour into the

    grout box, ensuring it flows along the stainless

    steel box section towards the joint.

    Joint must be filled before resin is installed.

    After a predetermined time period (generally

    60-120 days), when movement between the

    slabs has stabilised and the joint between the

    slabs has been filled, the dowel is ready to belocked. Fit the Locking Plate on a groove in

    the centre of the grout box. The fan-shaped

    Locking Plate allows the dowel to be locked in

    any position.

    5

    After 24 hours the grout box can be filled with

    cementitious material, level with the top of the

    slab, to complete the installation.

    The locked dowel continues to transfer vertical

    load between the slabs, but movement can no

    longer take place.

    64

    Fix the local reinforcement around the dowel

    component and pour the concrete.

    3

    Nail the threaded anchor to the formwork so

    the dowel will be central in the adjoining slab

    or within 150mm of the top of slabs over

    300mm. Fix the local reinforcement and cast

    the concrete.

    1 2

    When concrete reaches sufficient strength,

    strike the formwork and remove nailing plate.

    Screw the dowel into the anchor.

    Puncture the label of the sleeve to reveal the

    cylindrical sleeve only. Push the sleeve over the

    dowel, until the dowel is approximately 20mm

    from the back of the grout box. Tie sleeve to

    reinforcement and pour concrete.

    See Steps 4 to 6 above to complete

    installation.

    3

  • 8/11/2019 Ancon Shear Load Connector

    30/30

    Ancon Building Products 2009

    The construction applications and details provided in this literature

    are indicative only. In every case, project working details should be

    entrusted to appropriately qualified and experienced persons.

    Whilst every care has been exercised in the preparation of this

    document to ensure that any advice, recommendations orinformation is accurate, no liability or responsibility of any kind is

    accepted in respect of Ancon Building Products.

    With a policy of continuous product development Ancon Building

    Products reserves the right to modify product design andspecification without due notice.

    These products are available from:

    Ancon Building ProductsPresident Way, President ParkSheffield S4 7UR

    United KingdomTel: +44 (0) 114 275 5224Fax: +44 (0) 114 276 8543Email: [email protected]: www.ancon.co.uk

    Ancon (Middle East) FZEPO Box 17225Jebel AliDubaiUnited Arab EmiratesTel: +971 (0) 4 883 4346Fax: +971 (0) 4 883 4347Email: [email protected]: www.ancon.ae

    Ancon Building Products114 Kurrajong AvenueMount DruittSydneyNSW 2770AustraliaTel: +61 (0) 2 8808 1111Fax: +61 (0) 2 9675 3390Email: [email protected]: www.anconbp.com.au

    Ancon (Schweiz) AGGewerbezone Widalmi 103216 Ried bei Kerzers

    SwitzerlandTel: +41 (0) 31 750 3030Fax: +41 (0) 31 750 3033Email: [email protected]: www.ancon.ch