Triconex CorporationTriconex Corporation
SystemSystemGroundingGrounding
TRICON HardwareTRICON Hardware
-
7/21/2019 Triconex Training
2/38
Electrical systems must be connected to groundin order to:
Protect personnel from electric shock.Protect personnel from electric shock.
Protect equipment from damage.Protect equipment from damage.
Protect the site from lightning damage.Protect the site from lightning damage. Ensure the reliability and electrical integrity of theEnsure the reliability and electrical integrity of the
system.system.
To have interference free operationTo have interference free operation
-
7/21/2019 Triconex Training
3/38
What is Ground?What is Ground? It is a connection to the earth, or to something usedIt is a connection to the earth, or to something used
in place of the earth.in place of the earth.
Why do we require a ground?Why do we require a ground? The ground is required as it is used to establish andThe ground is required as it is used to establish and
maintain the potential of the earth.maintain the potential of the earth.
-
7/21/2019 Triconex Training
4/38
TRICON System typically utilizes three (3)separate ground references:
AC safety or chassis ground (protective earthground) - TRICON Chassis Ground
Signal or Instrument (or Master Reference) ground- TRICON Signal Ground (TSG)
Field loop shield ground
-
7/21/2019 Triconex Training
5/38
AC Safety ground is applied to each chassis
Signal or Instrument (or Master Reference)ground is the field loop power supply return
Field loop shield ground is for referencinginstrument loop wiring shields typically toinstrument or Master Reference ground
-
7/21/2019 Triconex Training
6/38
TRICONTRICONMainMain
ChassisChassis
AC Safety Ground Bar
TRICONTRICONExpansionExpansionChassisChassis
Each chassisEach chassis MUST BEMUST BEconnected to AC Safetyconnected to AC Safetyground to ensure personnelground to ensure personnelsafety!safety!
TRICONTRICONExpansionExpansionChassisChassis
-
7/21/2019 Triconex Training
7/38
TRICONTRICON
ChassisChassis
AC Safety Ground BarAC Safety Ground Bar
Each V5Each V5 -- V8 Digital I/OV8 Digital I/OTerm PanelTerm Panel MUST BEMUST BEconnected to AC Safetyconnected to AC Safetyground to ensure personnelground to ensure personnelsafety!safety!
Digital Input TermDigital Input Term
-
7/21/2019 Triconex Training
8/38
AC Safety Ground MUST be applied to eachchassis (Main, Expansion & RXM) regardless offloating or non-floating systems.
AC Safety Ground MUST be applied to each V5 -
V8 DI/DO Term Panel. (floating/non-floating) asthe V5 - V8 I/O ELCO cables do not have aconnecting wire to chassis. Connection to AC
Safety Ground for V9 Terms are not required.
AC Safety Ground MUST NOTbe applied to
AI/AO Term Panels and #3504E.
-
7/21/2019 Triconex Training
9/38
-
7/21/2019 Triconex Training
10/38
AC Safety Ground Analog SystemAC Safety Ground Analog System
AC SafetyAC Safety
TRICONTRICON
ChassisChassis
Isolated +24Isolated +24Power SupplyPower Supply
V+V+ VV--
Analog Input TermAnalog Input Term
Once VOnce V-- is connected to ais connected to aAI/AO Term Panel, it isAI/AO Term Panel, it isconnected to the internalconnected to the internalTRICON Signal GroundTRICON Signal Ground(TSG).(TSG).
If the TRICON RC Clip isIf the TRICON RC Clip isinstalledinstalled, TSG is connected, TSG is connectedto AC Safety Ground via ato AC Safety Ground via a
parallel resistor/capacitorparallel resistor/capacitorcircuit.circuit.
TSG VTSG V-- is referenced to ACis referenced to ACSafety withinSafety within millivoltsmillivolts
range.range.
-
7/21/2019 Triconex Training
11/38
Dedicated Ground Analog SystemDedicated Ground Analog System
If the TRICON RC Clip isIf the TRICON RC Clip isremoved, TSG isremoved, TSG isdisconnected from ACdisconnected from ACSafety Ground.Safety Ground.
TSGTSG MUST BEMUST BE connectedconnectedto a dedicated ground.to a dedicated ground.
One connection is requiredOne connection is requiredand is completed at theand is completed at the
Main Chassis locationMain Chassis location & any& anyremote RXM locations.remote RXM locations.
The dedicated ground isThe dedicated ground istypically considered a quiettypically considered a quietearth ground or DCSearth ground or DCS
Master Reference Ground.Master Reference Ground.
Isolated +24Isolated +24Power SupplyPower Supply
V+V+ VV--
TRICONTRICON
ChassisChassis
Analog Input TermsAnalog Input Terms
Dedicated GroundDedicated Ground
AC SafetyAC Safety
-
7/21/2019 Triconex Training
12/38
Dedicated Ground Analog SystemDedicated Ground Analog System
AC SafetyAC Safety
Dedicated GroundDedicated Ground
Field loop wiring shieldsField loop wiring shieldsare typically connected toare typically connected toTRICON Term Panels.TRICON Term Panels.
The TRICON Term PanelThe TRICON Term Panelshield ground screwsshield ground screwsshould be tied toshould be tied toinstrument ground or theinstrument ground or thededicated ground.dedicated ground.
TRICONTRICON
ChassisChassis
Isolated +24Isolated +24Power SupplyPower Supply
V+V+ VV--
Analog Input TermsAnalog Input Terms
-
7/21/2019 Triconex Training
13/38
TRIOCN RC networkTRIOCN RC network
V5V5 -- V8 SystemV8 System
#8300/#8301/#8305/#8306 TRICON Power#8300/#8301/#8305/#8306 TRICON PowerModules are equipped with a simple RC networkModules are equipped with a simple RC networkconnected between the signal and chassis groundconnected between the signal and chassis ground
#8300A/#8301A/#8305A/#8306A TRICON Power#8300A/#8301A/#8305A/#8306A TRICON PowerModules allows one to disconnect the internal RCModules allows one to disconnect the internal RC
network and directly access the TRICON signalnetwork and directly access the TRICON signalground.ground.
-
7/21/2019 Triconex Training
14/38
TRIOCN RC networkTRIOCN RC network
V9 SystemV9 System
The RC network is external to the TRICON PowerThe RC network is external to the TRICON PowerModules.Modules.
-
7/21/2019 Triconex Training
15/38
TRIOCN RC networkTRIOCN RC network
StandStand--Alone DigitalAlone Digital--Only SystemOnly System
Connecting the RC jumper will be sufficient
StandStand--Alone AnalogAlone Analog--Only or MixedOnly or Mixed
Analog/Digital SystemAnalog/Digital SystemConnecting the RC jumper will be sufficient
-
7/21/2019 Triconex Training
16/38
TRIOCN RC networkTRIOCN RC network
Integration with DCSIntegration with DCS
If TRICON is a stand-alone digital-only system, connection of theRC jumper (at the power module for V5 to V8) is sufficient
If TRICON is a stand-alone analog-only or mixed analog/digital
system, a single connection must be made between TRICON signalground and the common tie point of the DCS signal ground
A TriStation Link with model #410x ICM/EICM may cause a
problem if the TriStation PC does not share the safety groundconnection as the TRICON.
Exercise caution especially if the TRICON and the DCS are
physically separated or reside in separate buildings. The sameproblem could also occur with any RS232 connection including anyMODBUS connections.
-
7/21/2019 Triconex Training
17/38
Connecting two pieces of equipment located inConnecting two pieces of equipment located indifferent buildingsdifferent buildings
TRICON I/O bus RSTRICON I/O bus RS--485 connection485 connectionextended beyond the control room.extended beyond the control room.
Current flow via the Shield ground which isCurrent flow via the Shield ground which isnot held at a constant, nonnot held at a constant, non--varying voltage.varying voltage.
Implementing a floating ground system.Implementing a floating ground system.
In most industrial control systems, the return sideIn most industrial control systems, the return sideof the field power supply is directly connected toof the field power supply is directly connected toearth.earth.
-
7/21/2019 Triconex Training
18/38
Emergency Shutdown (ESD) and Fire & GasEmergency Shutdown (ESD) and Fire & Gasdetection applications very often require thedetection applications very often require the
I/O system to be "floating".I/O system to be "floating".
In a floating ground system, the field powerIn a floating ground system, the field powersupply is not directly connected to earthsupply is not directly connected to earthground , but is connected to an artificialground , but is connected to an artificial
ground which can be created with a highground which can be created with a high--impedance resistor voltage divider.impedance resistor voltage divider.
-
7/21/2019 Triconex Training
19/38
24VDC POWER
SUPPLY UNIT
+
-
24VDC POWER
SUPPLY UNIT
+
-
EARTH GROUND
TO ETP POWER
24VDC
0VDC
R1
R2
-
7/21/2019 Triconex Training
20/38
The main use of a floating ground system with aThe main use of a floating ground system with asuitable Ground Fault Detector allows for thesuitable Ground Fault Detector allows for the
implementation of a "noimplementation of a "no--fail system".fail system".
A noA no--fail system is faultfail system is fault--tolerant of anytolerant of any singlesinglefieldfield--wiring fault to earth ground.wiring fault to earth ground.
These ground faults should be detectable byThese ground faults should be detectable bythe GFD, and if repaired in a timely manner, athe GFD, and if repaired in a timely manner, ashutdown or disturbance to the applicationshutdown or disturbance to the applicationshould be avoided.should be avoided.
-
7/21/2019 Triconex Training
21/38
The main purpose of a GFD is to detect theThe main purpose of a GFD is to detect thepresence of an unintentional connection topresence of an unintentional connection to
earth ground, other than that of the fixedearth ground, other than that of the fixedhighhigh--impedance connection.impedance connection.
A GFD should provide some means of alarmingA GFD should provide some means of alarmingupon detecting an ground fault.upon detecting an ground fault.
-
7/21/2019 Triconex Training
22/38
The HOLEC GFD has a sensitivity of 20mAThe HOLEC GFD has a sensitivity of 20mAminimum (between +minimum (between +veve andand --veve), when used with), when used with
an external 1.2kan external 1.2k resistor divider in 24VDCresistor divider in 24VDCapplications.applications.
24VDC POWER
SUPPLY UNIT
+
-
24VDC POWER
SUPPLY UNIT
+-
EARTH GROUND
HOLEC
+
-R1
R2
-
7/21/2019 Triconex Training
23/38
It is common to install multipleIt is common to install multiple GFDsGFDs in ain asystem, either one per Marshallingsystem, either one per MarshallingCabinet or one per termination panel.Cabinet or one per termination panel.After a ground fault has been detected,After a ground fault has been detected,
only the field wiring of the pointsonly the field wiring of the pointsattached to the alarmed GFD needs to beattached to the alarmed GFD needs to besearched for the earth short.searched for the earth short.
-
7/21/2019 Triconex Training
24/38
Ground Fault Detection with D.I. ModuleGround Fault Detection with D.I. Module
EARTH GROUND
R1
R2
HOLEC
24VDC
0VDC
PS+
PS-
+
-
DI ETP
DI MODULE
-
7/21/2019 Triconex Training
25/38
Ground Fault Detection with D.I. ModuleGround Fault Detection with D.I. Module
The following limitations apply to the useThe following limitations apply to the useofof GFDsGFDs with digital inputswith digital inputs::
A GFD always detects ground faults onA GFD always detects ground faults on
the positive side of the contact.the positive side of the contact. A GFD always detects ground faults onA GFD always detects ground faults on
the negative side of the contact when thethe negative side of the contact when the
contact is closed. When the contact iscontact is closed. When the contact isopen, the GFD might not detect the fault.open, the GFD might not detect the fault.
-
7/21/2019 Triconex Training
26/38
Ground Fault Detection with D.I. ModuleGround Fault Detection with D.I. Module
When the contact is open, the impedanceWhen the contact is open, the impedanceof the input circuitry is in series with theof the input circuitry is in series with thefault impedance.fault impedance.
If the sum of the impedances exceedsIf the sum of the impedances exceedsthe sensitivity of the GFD, then the GFDthe sensitivity of the GFD, then the GFDmight not detect the fault.might not detect the fault.
-
7/21/2019 Triconex Training
27/38
Ground Fault Detection with D.O. ModuleGround Fault Detection with D.O. Module
EARTH GROUND
R1
R2
HOLEC
24VDC
0VDC
PS+
PS-
+
-
DO ETP
FROM DO
MODULE
-
7/21/2019 Triconex Training
28/38
Ground Fault Detection with D.O. ModuleGround Fault Detection with D.O. Module
The following limitations apply to the useThe following limitations apply to the useofof GFDsGFDs with digital outputs:with digital outputs:
A GFD always detects ground faults onA GFD always detects ground faults on
the negative side of the load.the negative side of the load. A GFD always detects ground faults onA GFD always detects ground faults on
the positive side of the load when thethe positive side of the load when the
load is energized. When deload is energized. When de--energized, aenergized, aGFD might not detect the fault.GFD might not detect the fault.
-
7/21/2019 Triconex Training
29/38
Ground Fault Detection with D.O. ModuleGround Fault Detection with D.O. Module
When deWhen de--energized, the impedance of theenergized, the impedance of theload is in series with the fault impedance.load is in series with the fault impedance.
If the sum of the impedances exceedsIf the sum of the impedances exceeds
the sensitivity of the GFD, then the GFDthe sensitivity of the GFD, then the GFDmight not detect the fault.might not detect the fault.
-
7/21/2019 Triconex Training
30/38
Ground Fault Detection with A.I. ModuleGround Fault Detection with A.I. Module
EARTH GROUND
R1
R2
HOLEC
24VDC
0VDC
PS+
PS-
+
-
AI ETP
Tx
250
180
-
7/21/2019 Triconex Training
31/38
Ground Fault Detection with A.I. ModuleGround Fault Detection with A.I. Module
From test results and the electricalFrom test results and the electricalcircuit analysis, we confirmed that thecircuit analysis, we confirmed that theaccuracy degradation in the presence of aaccuracy degradation in the presence of a
ground fault is inherent in any 4ground fault is inherent in any 4--20mA20mAinstumentationinstumentation loops.loops.
-
7/21/2019 Triconex Training
32/38
TRICONEXTRICONEXYour supplier for allYour supplier for all
your Safety and Criticalyour Safety and CriticalControl NeedsControl Needs
DefectsDown TimeFalse Trips
-
7/21/2019 Triconex Training
33/38
BACKPLANE8-POINT ANALOG OUTPUT MODULE
PW RA (22A)
RTN (22E)
PWRB (24A)
CABLE
Selector
Logic
DAC
TERMINATION
PANEL
RTN (24E)
OUT1 (2A)
RTN1 (2E)
Selector
Logic
DAC
Selector
Logic
DAC
Loop powe r
Currentloopback
Currentloopback
Currentloopback
A
B
C
-
7/21/2019 Triconex Training
34/38
32-POINT ANALOG INPUT MODULESBACKPLANECABLE
tospare
TERMINATION PANEL
Isola tion/filte ring
ADCAmp1
32
Mux
Hi-Ref
Low-Ref
ADCAmp1
32
Mux
Hi-Ref
Low-Ref
ADCAmp1
32
Mux
Hi-Ref
Low-Ref
PS1
PS2
PS1
PS2
tootherpoints
180 ohms
Note 3
Types of Power T f E th C ti
-
7/21/2019 Triconex Training
35/38
Types of Power
Utility Power
Mains Power
UPS
Clean
Floating
AC / DC
Types of Earth Connection
Clean Earth
Dirty Earth
Utility Earth
Low noise
System
Computer
Basically on two types of
Ground :-
a) AC - dirty
b) DC - clean
System earth
Instrument earth
EMC
Electromagnetic Compatibility
-> Started by the military application 15 yrs ago
Use 3 core power cables for optimal line filtering
Power source is reference to earth
Floating power contains much more noise than earth reference
Floating power needs isolation transformer
Floating power may drift to any common mode potential
Line filtering requires earth connection
Impedance if 3 core power is 100 ohms
I/A designed by National Electrical Code
Normal and Common mode signals by :
-
7/21/2019 Triconex Training
36/38
Normal and Common mode signals by :
potential equalisation
Galvanic isolation
ShieldingEnclosures
Signal to noise ratio
-
7/21/2019 Triconex Training
37/38
GROUNDING th TRICONGROUNDING th TRICON
-
7/21/2019 Triconex Training
38/38
GROUNDING the TRICONGROUNDING the TRICON
Expansion Chassis
(Protective Earth)
AC
SAFETY
GROUND
1/4" Bolt on left sideof each chassis
Main Chassis
Expansion Chassis
AC Safety Ground
Bus Bar