TRANSCRIPT

Size

Bio/CR-7 (On Gyp) Clean Room Cove Base Detail w/ Tapered Cove BaseCage Code Drawing Number Rev

SheetScale

Life Science Products, Inc.124 Speer Road - Chestertown, MD 21620

www.lspinc .com

800-638-9874

(410) 778-6474

Fax (410) 778-4076

GLWBCR- 104Date

4"

1/4"

CONCRETE FLOOR

3/4" or 1" COVE RADIUS

EPOXY COVE BASE

METAL STUDS

BIO/CR-7COMPOSITE WALL PANEL

TOP OF EPOXY COVE BASEAT 4 OR 6 INCHES ABOVE CONCRETE(TO BE DETERMINED BY ARCH OR DESIGNER)AND TAPERED TO 1/16".

5/8” GYP BD

ADHESIVE

NTS

10.17

Size

Bio/CR-7 (On Gyp) Standard Cove Base Details - End ViewCage Code Drawing Number Rev

SheetScale

Life Science Products, Inc.124 Speer Road - Chestertown, MD 21620

www.lspinc.com

800-638-9874

(410) 778-6474

Fax (410) 778-4076

GLWBCR91

METAL STUD

CONCRETE1" COVE RADIUS

RESINOUS FLOOR

COVE BASE

CAULK

ZINC COVE STRIP

5/8" GYP BD

BIO/CR-7COMPOSITE WALL PANEL

6" = 1'-0"

11.15

ADHESIVE

Size

Bio/CR-7 DOOR FRAME SEALING DETAIL, TYPICAL JAMB (HEAD SIMILAR)Cage Code Drawing Number Rev

SheetScale

Life Science Products, Inc.124 Speer Road - Chestertown, MD 21620

www.lspinc.com

800-638-9874

(410) 778-6474

Fax (410) 778-4076

GLWBCR50

1"

1 1/4"

DRYWALL SCREW ALONG DOOR ROUGH OPENING:1.25" (31.76mm) @ 12" (30cm) o.c. (TYP)

DRYWALL

BIO/CR­7 COMPOSITE WALL PANEL

DOOR FRAME, STAINLESS STEEL, FIBERGLASS,PAINTED METAL, ATTACHED TO STUDS AS REQUIRED

DOUBLE METAL STUDS

DOUBLEMETALSTUDS

SEALANT

SEALANT

DOOR FRAME, STAINLESS STEEL,FIBERGLASS, PAINTED METAL,ATTACHED TO STUDS AS REQUIRED

DRYWALL

BIO/CR­7COMPOSITEWALL PANEL

25 .4mm

31 .8mm

6" = 1'-0"

11.15

Size

Bio/CR-7 Inside Corner Joint Detail - Top ViewCage Code Drawing Number Rev

SheetScale

Life Science Products, Inc.124 Speer Road - Chestertown, MD 21620

www.lspinc .com

800-638-9874

(410) 778-6474

Fax (410) 778-4076

GLWBCR49

FASTENERS, TYP

MOUNTING STUDS

BIO/CR-7COMPOSITE WALL PANEL

BIO/CR-7COMPOSITE WALL PANEL

SEALANT

5/8" GYP BD

5/8" GYP BDSEALANT OR TAPE

11.15

Size

Bio/CR-7 Outside Corner DetailCage Code Drawing Number Rev

SheetScale

Life Science Products, Inc.124 Speer Road - Chestertown, MD 21620

www.lspinc.com

800-638-9874

(410) 778-6474

Fax (410) 778-4076

GLWBCR48

5/8" GYP BD

5/8" GYP BD

METAL STUDS

BIO/CR­7COMPOSITE WALL PANEL

ALL JOINTS SEALEDWITH SEALANT, TYP

BIO/CR­7COMPOSITE WALL PANEL

STAINLESSCORNER GUARD

FILLED WITH SEALANT

FASTENERS, TYP

11.15

Size

Bio/CR-7 Clean Room Joint Detail (Top View)Cage Code Drawing Number Rev

SheetScale

Life Science Products, Inc.124 Speer Road - Chestertown, MD 21620

www.lspinc.com

800-638-9874

(410) 778-6474

Fax (410) 778-4076

GLWBCR47

5/8"GYP BD

BIO/CR­7COMPOSITEWALL PANEL

1/8" SEALED JOINT:100% SOLIDURETHANESEALANTMETAL

STUD

5/8"GYP BD

BIO/CR­7COMPOSITEWALL PANEL

METALSTUD

PANEL BUTT JOINT

ADHESIVE

Finished View Exploded View

11.15

Size

Bio/CR-7 Clean Room Cove Base Detail on GypCage Code Drawing Number Rev

SheetScale

Life Science Products, Inc.124 Speer Road - Chestertown, MD 21620

www.lspinc.com

800-638-9874

(410) 778-6474

Fax (410) 778-4076

GLWBCR39

4"CONCRETE FLOOR

3/4" or 1" COVE RADIUS

EPOXY COVE BASE

METAL STUDS

5/8" GYP BD

BIO/CR­7COMPOSITE WALL PANEL

PANEL FACE ROUTEDTO 4 OR 6 INCHESABOVE CONCRETE(TO BE DETERMINED BY ARCH OR DESIGNER).

ADHESIVE

11.15

Size

Bio/CR Panel Through Wall Penetration - PipeCage Code Drawing Number Rev

SheetScale

Life Science Products, Inc.124 Speer Road - Chestertown, MD 21620

www.lspinc.com

800-638-9874

(410) 778-6474

Fax (410) 778-4076

GLWBCR62Date

ESCUTCHEON PLATEBY OTHERS

BIO/CR URETHANE SEALANT

4.17

TAPE/BACKER ROD BIO/CR COMPOSITE WALL PANEL

BIO.CR URETHANESEALANT

PIPE PENETRATION

top related