1

Industrial Systems

BUS2000 Busbar Differential Protection SystemDifferential overcurrent system with

percentage restraint protection

2

Industrial Systems

Typical Busbar Arrangements– Single Busbar– Double Busbar with Coupler– Breaker and a Half– Double Breaker– Double Busbar with Transfer Bar– Segregated Busbars with Coupler

3

Industrial Systems

Typical Single BusbarArrangement

4

Industrial Systems

Typical Double Busbarwith Coupler Arrangement

5

Industrial Systems

Typical Breaker and a Half Arrangement

6

Industrial Systems

Typical Double BreakerBusbar Arrangement

7

Industrial Systems

Typical Double Busbarwith Transfer Bar

8

Industrial Systems

Typical Segregated Busbarwith Coupler

9

Industrial Systems

Types of Protection Schemes

–Low Impedance–High Impedance

• Medium Values• High Values

10

Industrial Systems

Low Impedance Protection

11

Industrial Systems

Saturation of the AuxiliaryCTs

• A. Primary Fault Current• B. Secondary Current from the Source CTs• C. Secondary Current in the Faulty CT• D. Differential Current

12

Industrial Systems

Low Impedance Protection Current Detection + Second

Criteria–Time-delayed Overcurrent Relays–Directional Overcurrent Relays –Restraint Overcurrent relays–CT Saturation Detectors

13

Industrial Systems

High Impedance ProtectionScheme

14

Industrial Systems

High Impedance Protection

•• WHERE:• RL= CONNECTION WIRES RESISTANCE• IF = SECONDARY RMS CURRENT VALUE IN TI3

• VR = DIFFERENTIAL RELAY VOLTAGE• VS = CT MINIMUM SATURATION VOLTAGE• VOP = OPERATION VOLTAGE

• VR = IF x (2RL + RS)• VOP > VR Stability Criteria• VS > VOP Operation Criteria• TI3 Totally Saturated• RS CT Secondary Winding R Value

15

Industrial SystemsDifferential Overcurrent Relay with Percentage Restraint & Stabilizing

Resistor

16

Industrial Systems

BUS2000-External Fault

17

Industrial Systems

BUS2000-Internal Fault

18

Industrial Systems

BUS2000 - Differential Unit Block Diagram

19

Industrial Systems

BUS2000-Sensitivity Algorithm (1)

20

Industrial Systems

BUS2000-Sensitivity Algorithm (2)

21

Industrial Systems

BUS2000-Sensitivity Algorithm (3)

22

Industrial Systems

External Fault with CT Saturation

23

Industrial Systems

BUS2000-Stability Algorithm

24

Industrial Systems

BUS2000-Stability Limit

25

Industrial Systems

BUS2000-Operation Characteristic

26

Industrial Systems

BUS2000-Auxiliary CT. Magnetizing Curve of the Secondary Side

27

Industrial Systems

BUS2000-Alarm Unit Block Diagram

28

Industrial Systems

Breaker Failure Block Diagram

29

Industrial Systems

Numerical Monitoring Module– Differential and Restraint Currents Metering Information– Full Human-Machine Interface (Keypad + Graphic

Display)– IRIG-B Time Synchronization– Alarm Treatment– Differential Protection Outputs Status

30

Industrial Systems

Numerical Monitoring Module (cont)

– Oscillography Waveform Capture– Event Record– RS232 or fiber optics Communications– Configurable I/O– Undervoltage Supervision

31

Industrial Systems

BUS2000-Single Busbar(6 feeders) Differential Protection

32

Industrial Systems

BUS2000-Overcurrent and Breaker Failure (5 feeders) Protection

33

Industrial Systems

BUS2000-Test Rack

34

Industrial Systems

BUS2000-Numerical Monitoring Module

35

Industrial Systems

External Connections Diagram of Single Busbar BUS2000

System

36

Industrial Systems

BUS2000-Settings–K for Sensitivity–K and RE as low as possible–RE for CT requirements for

Overvoltage Conditions

37

Industrial Systems

Key Advantages

– Flexibility– Independent setttings for K and RE done in the field

without any additional changes– Wide Setting Range

– Suitable for all kinds of installations

– Measurement Units Supervision

– Current Circuits Supervision

38

Industrial Systems

Key Advantages (cont’d)

– Single-Three Phase Breaker Failure– Test Rack Independent from the protection– Easy Commisioning (accesible terminal blocks)– Suitable for updating of old Substations– Operating Principles well proven in the field– Numerical Monitoring Module