ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016 - THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICAL MANUAL. - SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g. COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS. - ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THE CONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS. 10 35 ALPINE STONE VENEER CLADDING ALPINE STONE ADHESIVE/ MORTAR BGC STONESHEET OR SUMNER BOARD LINTEL FRAMING SPECIFIED CAVITY BATTENS FRAME PROTECTION SYSTEM OR RIGID AIR BARRIER TAPE HEAD FLASHING BACK TO WALL UNDERLAY WITH SPECIFIED TAPE SLOPE BASE OF STONES 5° TO FORM DRIP EDGE REDWAY CAVITY CLOSER 15mm MIN. ABOVE BASE OF FIBRE CEMENT SHEET FIBRE CEMENT SHEET FIXINGS AS PER ALPINE STONE TECHNICAL MANUAL HEAD FLASHING AS SPECIFIED BY WINDOW JOINERY MANUFACTURER LOW FOAMING POLYURETHANE FOAM FOLLOWED BY CONTINUOUS AIR SEAL 5-10mm CONTINUOUS DRAINAGE GAP SPECIFIED FOAM TAPE BETWEEN HEAD FLASHING & JOINERY MIN. 10mm COVER OF HEAD FLASHING TO JOINERY WALL UNDERLAY DRESSED INTO OPENING SPECIFIED FLEXIBLE FLASHING TAPE INSTALLED TO CORNERS AT HEAD & LAP 50mm OVER UNDERLAY FOR RIGID AIR BARRIERS FOLLOW MANUFACTURER'S SPECIFICATIONS REFER TO COLOURED 3D DETAILS FOR FURTHER INFORMATION & CLARIFICATION WINDOW JOINERY DWG - 01 WINDOW HEAD DETAIL SCALE - 1:2

Upload: trinhthuan

Post on 18-Mar-2018

222 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016

- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.

10

35

ALPINE STONE VENEER CLADDING

ALPINE STONE ADHESIVE/ MORTAR

BGC STONESHEET OR SUMNER BOARD LINTEL FRAMING

SPECIFIED CAVITY BATTENS

FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER

TAPE HEAD FLASHING BACK TO WALLUNDERLAY WITH SPECIFIED TAPE

SLOPE BASE OF STONES 5° TO FORMDRIP EDGE

REDWAY CAVITY CLOSER 15mm MIN.ABOVE BASE OF FIBRE CEMENT SHEET

FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL

HEAD FLASHING AS SPECIFIED BYWINDOW JOINERY MANUFACTURER

LOW FOAMING POLYURETHANE FOAMFOLLOWED BY CONTINUOUS AIR SEAL

5-10mm CONTINUOUS DRAINAGE GAP

SPECIFIED FOAM TAPE BETWEEN HEADFLASHING & JOINERY

MIN. 10mm COVER OF HEAD FLASHINGTO JOINERY

WALL UNDERLAY DRESSED INTOOPENING

SPECIFIED FLEXIBLE FLASHING TAPEINSTALLED TO CORNERS AT HEAD & LAP50mm OVER UNDERLAY

FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS

REFER TO COLOURED 3D DETAILSFOR FURTHER INFORMATION &

CLARIFICATION

WINDOW JOINERY

DWG - 01 WINDOW HEAD DETAIL SCALE - 1:2

Page 2: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016

- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.

15

8

ALPINE STONE VENEER CLADDING

ALPINE STONE ADHESIVE/ MORTAR

BGC STONESHEET OR SUMNER BOARD

SPECIFIED CAVITY BATTENS

FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER

5mm GAP BEHIND & 6mm DRAINAGEGAP UNDER WINDOW FLANGE

FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL

CONTINUOUS AIRSEAL INSTALLED TOEDGE OF SILL TRAY

MIN. 8mm COVER OF JOINERY TO FIBRECEMENT SHEET

WANZ WINDOW SUPPORT BARLOCATED UNDER LIP OF SILL TRAY

SPECIFIED FLEXIBLE FLASHING TAPETO CORNERS & LAP ONTO FACE OFWALL UNDERLAY 50mm

WALL UNDERLAY DRESSED INTOOPENING

SPECIFIED SILL TRAY WITH SUPPORTBLOCKS ADHERED AT FIXING POINTS

SPECIFIED SILL TRAY END CAPSADHERED TO ENDS OF SILL TRAY

PROPRIETARY SUPPORT BLOCKS BYJOINERY MANUFACTURER

FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS

REFER TO COLOURED 3D DETAILSFOR FURTHER INFORMATION &

CLARIFICATION

TAPE SILL TRAY END CAPS BACK TOWALL UNDERLAY WITH SPECIFIED TAPE

STONE SILL WITH 15° MIN. SLOPE

FLEXIBLE FLASHING TAPE MAY BEINSTALLED TO ENTIRE SILL,

HOWEVER THIS IS NOT REQUIREDUNDER THE SPECIFIED SILL TRAY

WINDOW JOINERY

DWG - 02 WINDOW SILL DETAIL SCALE - 1:2

Page 3: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016

- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.

105

ALPINE STONE VENEER CLADDING

ALPINE STONE ADHESIVE/ MORTAR

BGC STONESHEET OR SUMNER BOARD

TIMBER FRAMING

SPECIFIED CAVITY BATTENS

FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER

HEAD FLASHING TO CONTINUE 20mmPAST JAMB SEALANT

FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL

LOW FOAMING POLYURETHANE FOAMFOLLOWED BY CONTINUOUS AIR SEAL

MIN. 10mm COVER OF JOINERY TOFIBRE CEMENT SHEET

WALL UNDERLAY DRESSED INTOOPENING

SPECIFIED FLEXIBLE FLASHING TAPEINSTALLED TO CORNERS AT HEAD & LAP50mm OVER UNDERLAY

CUT SLOT IN FIBRE CEMENT SHEET TOACCOMODATE HEAD FLASHING

FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS

LINE OF SILL TRAY BELOW

REFER TO COLOURED 3D DETAILSFOR FURTHER INFORMATION &

CLARIFICATION

5mm GAP FROM STONE TO JOINERYFILLED WITH MS SEALANT

5mm THICK SPECIFIED FOAM TAPEBETWEEN JOINERY AND FIBRE CEMENT

SHEET

WINDOW JOINERY

DWG - 03 WINDOW JAMB DETAIL SCALE - 1:2

Page 4: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016

- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.

FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS

5mm GAP BETWEEN SHEETS, JOINTSEALED WITH RENDER TAPE

SPECIFIED CAVITY BATTENS

FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL

WALL UNDERLAY CONTINUOUS AROUNDCORNER

ALPINE STONE VENEER CLADDING

ALPINE STONE ADHESIVE/ MORTAR

BGC STONESHEET OR SUMNER BOARD

TIMBER FRAMING

FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER

'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS

DWG - 04 PLAN VIEW OF EXTERNAL CORNER DETAIL SCALE - 1:2

Page 5: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016

- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.

FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS

ALPINE STONE VENEER CLADDING

ALPINE STONE ADHESIVE/ MORTAR

BGC STONESHEET OR SUMNER BOARD

FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER

SOLID BLOCKING AS REQUIRED FORTHE FIXING OF FIBRE CEMENT SHEET

FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL

SPECIFIED CAVITY BATTENS

WALL UNDERLAY CONTINUOUS AROUNDCORNER

TIMBER FRAMING

5mm GAP BETWEEN SHEETS, JOINTSEALED WITH RENDER TAPE

'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS

DWG - 05 PLAN VIEW OF INTERNAL CORNER DETAIL SCALE - 1:2

Page 6: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016

- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.

50

GR

OU

ND

CLE

ARAN

CE

20 M

IN.

150mm MIN. (PAVED)225mm MIN. (UNPAVED)

BGC STONESHEET OR SUMNER BOARD

SPECIFIED CAVITY BATTENS

ALPINE STONE VENEER CLADDING

ALPINE STONE ADHESIVE/ MORTAR

FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER

FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL

TIMBER BOTTOM PLATE WITH FIXINGS

DAMP PROOF COURSE (DPC) BETWEENTIMBER AND CONCRETE

REDWAY CAVITY CLOSER 20mm MIN.ABOVE BASE OF STONE SHEET

FIBRE CEMENT SHEET TO OVERLAPTHE CONCRETE SLAB BY 50mm

BASE OF STONE SLOPED 5° TO FORM ADRIP EDGE

FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS

PAVED GROUND SLOPING AWAY FROMTHE BUILDING MAY BROUGHT UP TO

WITHIN 50mm OF FLOOR LEVEL ATGARAGE DOOR OPENINGS

TAPE BOTTOM EDGE OF WALLUNDERLAY TO SLAB WITH SPECIFIED

TAPE

'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS

DWG - 06 SLAB EDGE DETAIL SCALE - 1:2

Page 7: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016

- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.

50

30

GR

OU

ND

CLE

ARAN

CE

100mm MIN. (PAVED)150mm MIN. (UNPAVED)

BGC STONESHEET OR SUMNER BOARD

SPECIFIED CAVITY BATTENS

VERMIN-PROOFING SHALL PROVIDE AMIN. 1000mm² VENTILATION PER

LINEAL METRE OF WALL

ALPINE STONE VENEER CLADDING

ALPINE STONE ADHESIVE/ MORTAR

FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER

FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL

TIMBER BOTTOM PLATE WITH FIXINGS

LIQUID APPLIED DAMP PROOF COURSE(DPC) BETWEEN TIMBER ANDCONCRETE TO CONTINUE ALONGREBATE (e.g. JAYDEX EASYGUM)

CAVITY BATTENS TO STOP 30mm CLEARFROM SLAB REBATE

FIBRE CEMENT SHEET TO ALIGN FLUSHWITH SLAB EDGE

PROPRIETARY VERMIN-PROOF VENT OR3-5mm DRAINAGE/ VENT HOLES OR

SLOTS THROUGH STONE AND FIBRECEMENT SHEET

STONE ADHERED DIRECTLY TO SLABEDGEPAVED GROUND SLOPING AWAY FROM

THE BUILDING MAY BROUGHT UP TOWITHIN 50mm OF FLOOR LEVEL AT

GARAGE DOOR OPENINGS

FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS

TAPE BOTTOM EDGE OF WALLUNDERLAY TO DPC WITH SPECIFIED

TAPE

'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS

DWG - 07 REBATED SLAB EDGE DETAIL SCALE - 1:2

Page 8: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016

- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.

ALPINE STONE VENEER CLADDING

ALPINE STONE ADHESIVE/ MORTAR

BGC STONESHEET OR SUMNER BOARD

FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER

SPECIFIED CAVITY BATTENS

FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL

FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS

NOG TO SUPPORT WALL UNDERLAY ATLINE OF SOFFIT TO BLOCK AIRFLOWFROM CAVITY

CONTINUOUS TIMBER TO BLOCKAIRFLOW FROM CAVITY

TIMBER FRAMING

SOFFIT LINING

'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS

5mm GAP BETWEEN SOFFIT & FIBRECEMENT SHEET, JOINT SEALED WITH

RENDER TAPE

DWG - 08 SOFFIT DETAIL SCALE - 1:2

Page 9: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016

- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.

50

35FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER

TIMBER FRAMING

ALPINE STONE VENEER CLADDING

ALPINE STONE ADHESIVE/ MORTAR

BGC STONESHEET OR SUMNER BOARD SPECIFIED CAVITY BATTENS

CONTINUOUS H3.1 TIMBER BLOCKINGTO BLOCK AIRFLOW FROM CAVITY INTOROOF SPACE

FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL

SLOPING SOFFIT FLASHING - IFALUMINIUM IS USED KEEP FROMCONTACT WITH CEMENT GROUT

ANGLE OF SOFFIT91°-115°

FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS

'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS

DWG - 09 SLOPING SOFFIT DETAIL SCALE - 1:2

Page 10: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016

- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.

3575

130 **

ALPINE STONE VENEER CLADDING

ALPINE STONE ADHESIVE/ MORTAR

BGC STONESHEET OR SUMNER BOARD

NOGGING TO SUPPORT FLASHING

SPECIFIED CAVITY BATTENS FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER

TAPE APRON FLASHING BACK TO WALLUNDERLAY WITH SPECIFIED TAPE

SLOPE BASE OF STONES 5° TO FORMDRIP EDGE

REDWAY CAVITY CLOSER 15mm MIN.ABOVE BASE OF FIBRE CEMENT SHEET

FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL

TROUGH TURNED UP TO CREATESTOPEND FOR PROFILED ROOFINGAPRON FLASHING TURNED

DOWN TO SUIT ROOFINGPROFILE

ROOFING UNDERLAY CONTINUED UPWALL BEHIND FLASHING

APRON TO HAVE 75mm UPSTANDBEHIND CLADDING INCREASE TO 90mmFOR EH WIND ZONES

APRON TO HAVE 35mm CLEARANCEFROM BASE OF CLADDING

FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS

** APRON FLASHING COVERTO BE 200mm IN VH OR

ABOVE WIND ZONE OR ROOFPITCHES <11°

APRON FLASHING FIXED WITHCOMPATIBLE FIXINGS BY OTHERS

TIMBER FRAMING

DWG - 10 TRANSVERSE APRON DETAIL SCALE - 1:2

Page 11: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016

- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.

3575

Y

10

FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER

FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL

NOGGING TO SUPPORT FLASHING

APRON TO HAVE 75mm UPSTANDBEHIND CLADDING INCREASE TO 90mmFOR EH WIND ZONES

APRON TO HAVE 35mm CLEARANCEFROM BASE OF CLADDING

ROOFING UNDERLAY CONTINUED UPWALL BEHIND FLASHING

FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS

ALPINE STONE VENEER CLADDING

ALPINE STONE ADHESIVE/ MORTAR

BGC STONESHEET OR SUMNER BOARD

REDWAY CAVITY CLOSER 15mm MIN.ABOVE BASE OF FIBRE CEMENT SHEET

SLOPE BASE OF STONES 5° TO FORMDRIP EDGE

FIXING THROUGH CREST OF PROFILE

FLASHING TO HAVE 5mmMIN. ANTI CAPPILARY GAP

TAPE APRON FLASHING BACK TO WALLUNDERLAY WITH SPECIFIED TAPE

SPECIFIED CAVITY BATTENS

Y = MIN. 2 CRESTS OF ROOFINGPROFILE & FINISH IN NEXT TROUGH

APRON FLASHING FIXED WITHCOMPATIBLE FIXINGS

TIMBER FRAMING

DWG - 11 PARALLEL APRON DETAIL SCALE - 1:2

Page 12: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016

- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.

70

70

ALPINE STONE VENEER CLADDING

ALPINE STONE ADHESIVE/ MORTAR

BGC STONESHEET OR SUMNER BOARD

SPECIFIED CAVITY BATTENS

FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER

INSTALL SPECIFIED FLASHING TAPE TOENTIRE CAP PRIOR TO FLASHING

FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL

METAL CAPPING SIDE FIXED ONLY

FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS

WALL UNDERLAY CONTINUOUS OVERFACE OF STRUCTURE

CAPPING DETAIL MAY BE USED FORCHIMNEY CAPPING. REFER TO FLUEMANUFACTURER FOR CAPPINGDETAILS AND USE NON-COMBUSTIBLEMATERIALS WHERE REQUIRED.

FOR CAPPING JOINTS ANDREQUIREMENTS REFER TO E2/AS1

FIGURE 9 AND SECTION 6.4

5° MIN.SLOPE

9mm MIN. H3.1 PLY PACKED TO SLOPEOR SLOPED POLYSTYRENE BLOCK

BIRD'S BEAK EDGE WHERE USED ASBALUSTRADE CAPPING

70mm MIN. OVERLAP TO CLADDING90mm MIN. IN EH WIND ZONES

H3.1 PACKER FOR FIXING CAPPINGFIXED TO FRAMING AS REQUIRED

NZBC E2 COMPLIANTCLADDING SYSTEM ON ACAVITY

'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS

TIMBER FRAMING

DWG - 12 PARAPET/ BALUSTRADE DETAIL SCALE - 1:2

Page 13: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016

- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.

10

ALPINE STONE VENEER CLADDING

ALPINE STONE ADHESIVE/ MORTAR

BGC STONESHEET OR SUMNER BOARD

SPECIFIED CAVITY BATTENS

NO SHEET FIXINGS TO INTER-FLOORBOUNDARY JOIST

FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER

10mm GAP SLOPE STONES 5° TO AIDDRAINAGE

BOTTOM COURSE OF STONEOVERLAPS LOWER SHEET 10mm

WITHOUT ADHESIVE/ MORTAR

FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL

OVER 2 STOREYS OR 7m USE AFLASHING TO BRIDGE THE CAVITY AS

PER E2/AS1 FIGURE 70

FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL

STONE, FIBRE CEMENT SHEET ANDCAVITY BATTENS ARE

DISCONTINUOUS AT FLOOR LEVELSTO ALLOW FOR INTER-STOREY

MOVEMENT

10mm MIN. GAP BETWEEN CAVITYBATTENS & FIBRE CEMENT SHEETS

FLOORING TO FINISH 10mm BACK FROMOUTSIDE FACE OF FRAMING

HORIZONTAL CONTROL JOINT AT ALLFLOOR JOISTS AND ALL WALLSEXCEEDING 5600mm IN HEIGHT 'RENDER TAPE' TO BE APPLIED OVER

ALL SHEET JOINTS

TIMBER FRAMING

'RENDER TAPE' APPLIED OVER GAPBETWEEN FIBRE CEMENT SHEETS

STONE AT JOINT TO BE FIXED ON ONESIDE OF JOINT ONLY

DWG - 13 HORIZONTAL CONTROL JOINT SCALE - 1:2

Page 14: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016

- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.

6-8

ALPINE STONE VENEER CLADDING

ALPINE STONE ADHESIVE/ MORTAR

BGC STONESHEET OR SUMNER BOARD

SPECIFIED CAVITY BATTENS

FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER

6-8mm GAP BETWEEN FC SHEETSCOVERED WITH 'RENDER TAPE'

POLYETHYLENE BOND BREAKER TAPEMIN. 12mm EACH SIDE OF JOINT

FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL

VERTICAL CONTROL JOINTS AT5400mm CENTERS MAX. 6000mm

WHEN WALL FINISHES AT ANEXTERNAL CORNER

DOUBLE STUD AT CONTROL JOINT

FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS

'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS

TIMBER FRAMING

DWG - 14 PLAN VIEW OF VERTICAL CONTROL JOINT DETAIL SCALE - 1:2

Page 15: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016

- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.

10

ALUMINIUM IF USED SHOULD BE KEPTFROM CONTACT WITH CEMENT GROUT

MS SEALANT CAN BE USED AS ASUBSTITUTE

FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL

SPECIFIED FLEXIBLE FLASHING TAPETO CORNERS AT HEAD TO ENTIRE SILLAND 100mm UP JAMBS LAP 50mm OVERWALL UNDERLAY

TIMBER FRAMING

ALPINE STONE ADHESIVE/ MORTAR

FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER

BGC STONESHEET OR SUMNER BOARD

METERBOXES SHOULD BE LOCATEDIN SHELTERED AREAS

FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS

ALPINE STONE VENEER CLADDING

5-10mm GAP BETWEEN FIBRE CEMENTSHEET AND METERBOX FILLED WITH MS

SEALANT

TAPE METERBOX FIXING ANGLE BACKTO WALL UNDERLAY FIRST AT SILLFOLLOWED BY JAMBS THEN HEADOVERLAPPING AT CORNERS WITH

SPECIFIED TAPE

SPECIFIED CAVITY BATTENS

WALL UNDERLAY DRESSED INTOOPENING

LOW FOAMING POLYURETHANE FOAMFOLLOWED BY CONTINUOUS AIR SEAL

CONTINUOUS FLANGE CREATED FROM40 x 40mm MIN. ANGLE MITRED ATCORNERS FIXED TO METERBOX WITHRIVETS ON SEALANT BED

METERBOX FLANGE SHOULD HAVEJOINTS SEALED WITH SEALANT

A PROPRIETARY METERBOX WITHINTEGRAL FLANGE MAY BE USED

'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS

DWG - 15 METERBOX DETAIL SCALE - 1:2

Page 16: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016

- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.

75m

m M

IN.

ALUMINIUM IF USED SHOULD BE KEPTFROM CONTACT WITH CEMENT GROUT.

MS SEALANT CAN BE USED AS ASUBSTITUTE

SOLID BLOCKING AROUNDPENETRATION WITH MIN. 75mmOVERLAP TO UNDERLAY

ALPINE STONE ADHESIVE/ MORTAR

FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER

BGC STONESHEET OR SUMNER BOARD

PIPE AND SIMILAR PENETRATIONSSHOULD BE LOCATED IN SHELTERED

AREASFOR RIGID AIR BARRIERS FOLLOW

MANUFACTURER'S SPECIFICATIONS

ALPINE STONE VENEER CLADDING

5-10mm GAP BETWEEN FIBRE CEMENTSHEET AND PIPE

PROPRIETARY BOOT FLASHINGSEALING PIPE TO BUILDING UNDERLAY

SPECIFIED CAVITY BATTENS

RENDER TAPE TO BE APPLIED OVERFIBRE CEMENT SHEET AROUND PIPE

TIMBER FRAMING

'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS

DWG - 16 PENETRATION DETAIL SCALE - 1:2

Page 17: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016

- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.

40

15 5

NZBC E2 COMPLIANT CLADDINGSYSTEM ON A CAVITY

FLASHING WITH MIN 40mm (65mm EHWIND ZONES) TOTAL UPSTAND

5mm MIN. CLEARANCE AT BASE OFCLADDING

FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL

FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS

REDWAY CAVITY CLOSER 15mm MIN.ABOVE BASE OF FIBRE CEMENT SHEET

ALPINE STONE VENEER CLADDING

ALPINE STONE ADHESIVE/ MORTAR

BGC STONESHEET OR SUMNER BOARD

STONE SILL WITH 15° MIN. SLOPE KEEPMIN. 5mm CLEAR OF WALL UNDERLAY

SPECIFIED CAVITY BATTENS

NOGGING TO SUPPORT FLASHING

FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER

TIMBER FRAMING

'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS

TAPE FLASHING BACK TO WALLUNDERLAY WITH SPECIFIED TAPE

ALPINE STONE ADHESIVE/ MORTAR

DWG - 17 HORIZONTAL JOINT WITH ALTERNATIVE CLADDING SCALE - 1:2

Page 18: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016

- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.

6-8

ALPINE STONE VENEER CLADDING

ALPINE STONE ADHESIVE/ MORTAR

BGC STONESHEET OR SUMNER BOARD

SPECIFIED CAVITY BATTENS

FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER

100mm WIDE PVC BACK FLASHING

LOW FOAMING POLYURETHANE FOAMFOLLOWED BY CONTINUOUS AIR SEAL

FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL

DOUBLE STUD

FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS

NZBC E2 COMPLIANT CLADDINGSYSTEM ON A CAVITY

SCRIBER SEALED TO STONE FORWEATHERBOARD CLADDING

TIMBER FRAMING

'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS

DWG - 18 PLAN VIEW OF VERTICAL JOINT WITH ALTERNATIVE CLADDING SCALE - 1:2

Page 19: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016

- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.

50

50

6-8

FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS

WALL UNDERLAY CONTINUOUS AROUNDCORNER

ALPINE STONE VENEER CLADDING

ALPINE STONE ADHESIVE/ MORTAR

BGC STONESHEET OR SUMNER BOARD

TIMBER FRAMING

FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER

FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL

50mm X 50mm WIDE PVC BACKFLASHING

LOW FOAMING POLYURETHANE FOAMFOLLOWED BY CONTINUOUS AIR SEAL

NZBC E2 COMPLIANT CLADDINGSYSTEM ON A CAVITY

H3.2 SCRIBER SEALED TO STONE FORWEATHERBOARD CLADDING

SPECIFIED CAVITY BATTENS

'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS

DWG - 19 PLAN VIEW OF EXTERNAL CORNER JOINT WITH ALTERNATIVE CLADDING SCALE - 1:2

Page 20: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016

- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.

6-850

LOW FOAMING POLYURETHANE FOAMFOLLOWED BY CONTINUOUS AIR SEAL

H3.2 SCRIBER SEALED TO STONE FORWEATHERBOARD CLADDING

FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONSALPINE STONE VENEER CLADDING

ALPINE STONE ADHESIVE/ MORTAR

BGC STONESHEET OR SUMNER BOARD

SOLID BLOCKING AS REQUIRED FORTHE FIXING OF FIBRE CEMENT SHEET

FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL

SPECIFIED CAVITY BATTENS

WALL UNDERLAY CONTINUOUS AROUNDCORNER

TIMBER FRAMING

BACK FLASHING WITH MIN. 50mmOVERLAP TO JOINT & STONESHEET

NZBC E2 COMPLIANT CLADDINGSYSTEM ON A CAVITY

BACK FLASHING TO BE OF A SUITABLYCOMPATIBLE MATERIAL

'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS

50

DWG - 20 PLAN VIEW OF INTERNAL CORNER JOINT WITH ALTERNATE CLADDING SCALE - 1:2

Page 21: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016

- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.

**H5 TREATED TIMBER POST OR STEELPOST TO SPECIFIC DESIGN

POST BRACKET AND FIXING TOSPECIFIC DESIGN

H3.2 TIMBER FRAMING

ALPINE STONE ADHESIVE/ MORTAR

BGC STONESHEET OR SUMNER BOARD

ALPINE STONE VENEERCLADDING

5mm GAP BETWEEN SHEETS, JOINTSEALED WITH RENDER TAPE

FIBRE CEMENT SHEET FIXINGS ASPER ALPINE STONE TECHNICAL

MANUAL

**POST MAY BE EMBEDED INCONCRETE AS AN ALTERNATIVE TO

BRACKET

DWG - 21 PLAN VIEW OF COLUMN DETAIL 1:5

Page 22: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016

- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.

20 M

IN

10

**H5 TREATED TIMBER POST ORSTEEL POST TO SPECIFICDESIGN

H3.2 TIMBER FRAMING FIXED TOPOST WITH ANGLE BRACKET

ALPINE STONE VENEERCLADDING

ALPINE STONE ADHESIVE/MORTAR

BGC STONESHEET OR SUMNERBOARD

CONCRETE PLINTH OPTION TO BEUSED IN FLOOD PRONE AREAS

POST BRACKET AND FIXING TOSPECIFIC DESIGN

PROVIDE 10mm MIN GAP BETWEENBOTTOM OF FIBRE CEMENT SHEET

AND GROUND.WHEN CONCRETE PLINTH OPTION IS

USED, PROVIDE VERMIN-PROOFVENT, MIN 1000mm² PER LINEAL

METRE OF STONE VENEER

**POST MAY BE EMBEDED INCONCRETE AS AN ALTERNATIVE TO

BRACKET

FIBRE CEMENT SHEET FIXINGS ASPER ALPINE STONE TECHNICAL

MANUAL

ALTERNATIVEGROUND LEVEL

DWG - 22 COLUMN BASE DETAIL 1:5

Page 23: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016

- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.

10mm MIN.

45

COPING STONE WITH 15° MIN. FALL

ALPINE STONE VENEER CLADDING

ALPINE STONE ADHESIVE/ MORTAR

BGC STONESHEET OR SUMNERBOARD

FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL

H3.2 TIMBER FRAMING FIXED TO POSTWITH ANGLE BRACKET

H5 TREATED TIMBER POST OR STEELPOST TO SPECIFIC DESIGN

ALPINE STONE ADHESIVE/ MORTAR

SPECIFIED RENDER TAPE ADHEREDTO POST AND TO COVER ALL JOINTS INFIBRE CEMENT BOARD

DWG - 23 HALF COLUMN DETAIL 1:5

Page 24: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016

- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.

10mm MIN.

45

COPING STONE WITH 15° MIN. FALL

ALPINE STONE VENEER CLADDING

ALPINE STONE ADHESIVE/ MORTAR

SPECIFIED RENDER TAPE ADHERED TOPOST AND TO COVER ALL JOINTS INFIBRE CEMENT BOARD. TAPE TO ADHEREMIN 45mm UP POST

H3.2 TIMBER FRAMING FIXED TO POSTWITH ANGLE BRACKET

**H5 TREATED TIMBER POST OR STEELPOST TO SPECIFIC DESIGN

FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL

BGC STONESHEET OR SUMNERBOARD

DWG - 24 HALF COLUMN CAPPING DETAIL 1:2

Page 25: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016

- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.

*310

*310

*105 *100

**H3.2 TREATED TIMBER POST ORSTEEL POST TO SPECIFIC DESIGN

ALPINE STONE ADHESIVE/MORTAR

ALPINE STONE VENEERCLADDING

**H3.2 TREATED TIMBER POST IF USEDWITH POST BRACKET. USE H5 TREATEDTIMBER POST IF SEATED DIRECTLY INCONCRETE.

2 PIECE MOULDED POLYSTYRENESUBSTRATE. FIX EACH PIECE TO THE

OTHER AND TIMBER POST WITHPOLYSTYRENE COMPATIBLECONSTRUCTION ADHESIVE.

* POLY-COLUMN SUPPLIED TO SUITCOLUMN HEIGHT, WIDTH OF POST AND

SIZE AND SHAPE OF FINISHEDEXTERIOR.

SEE ALPINE STONE TECHNICALMANUAL FOR FULL INSTALLATION

INSTRUCTIONS.

DWG - 25 PLAN VIEW OF POLY-COLUMN DETAIL 1:5

Page 26: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

HEAD : FINISHED WALLHEAD : FIBRE CEMENT SHEET

HEAD : FLASHINGHEAD : WRAP & TAPE

DWG - 26 WINDOW HEAD 3D SEQUENCE

1. TIMBER FRAMING INSTALLED2. WALL UNDERLAY RUN HORIZONTALLY & DRESSEDINTO WINDOW/ DOOR OPENING3. SPECIFIED FLEXIBLE FLASHING TAPE TO CORNERS ATHEAD AND JAMBS

4. HEAD FLASHING FIXED WITH PROPRIETARY STOPENDS INSTALLED5. TOP EDGE OF FLASHING TAPED BACK TO WALLUNDERLAY WITH SPECIFIED FLEXIBLE FLASHING TAPE6. CAVITY BATTENS INSTALLED

7. INSTALL CAVITY CLOSER THEN INSTALL FIBRECEMENT SHEET AROUND HEAD FLASHING8. INSTALL SPECIFIED FOAM TAPE ONTO FIBRE CEMENTSHEET AT JAMBS9. AIR SEAL SHOWN IS INSTALLED AFTER FIXING OFWINDOW

10. APPLY SPECIFIED FOAM TAPE TO HEAD OF JOINERYAND INSTALL JOINERY UNDER HEAD FLASHING AND FIXAS REQUIRED11. APPLY STONE TO FIBRE CEMENT SHEET WITHALPINE STONE ADHESIVE AND SEAL JAMB WITH MSSEALANT

Page 27: ALPINE STONE VENEER CLADDING · PDF filealpine stone veneer cladding system version - 16/03/2016 - these drawings must be read in conjunction with the list of specified/accepted products

SILL : WRAP & TAPE SILL : TRAY & WANZ BAR

SILL : FIBRE CEMENT SHEET SILL : FINISHED WALL

1. TIMBER FRAMING INSTALLED2. WALL UNDERLAY RUN HORIZONTALLY & DRESSED INTOWINDOW/ DOOR OPENING3. SPECIFIED FLEXIBLE FLASHING TAPE TO ENTIRE SILLAND 100mm UP AT JAMBS

4. REDWAY SILL TRAY ADHERED TO SILL TRAY ENDCAPSAND INSTALLED TO SILL TRIMMER WITH WANZ BAR5. TOP EDGE OF SILL END CAPS TAPED TO JAMB WITHSPECIFIED FLEXIBLE FLASHING TAPE6. CAVITY BATTENS INSTALLED

7. STONE SHEET FIXED8. 5mm THICK SPECIFIED FOAM TAPE INSTALLED ONTOSTONESHEET AT JAMBS9. AIR SEAL SHOWN IS INSTALLED AFTER FIXING OFWINDOW

10. WINDOW SUPPORT BLOCKS FITTED AND JOINERYINSTALLED AND FIXED AS REQUIRED12. STONE ADHERED TO STONE SHEET WITH ALPINESTONE ADHESIVE AND SEAL JAMB WITH MS SEALANT

DWG - 27 WINDOW SILL 3D SEQUENCE