ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016
- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.
10
35
ALPINE STONE VENEER CLADDING
ALPINE STONE ADHESIVE/ MORTAR
BGC STONESHEET OR SUMNER BOARD LINTEL FRAMING
SPECIFIED CAVITY BATTENS
FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER
TAPE HEAD FLASHING BACK TO WALLUNDERLAY WITH SPECIFIED TAPE
SLOPE BASE OF STONES 5° TO FORMDRIP EDGE
REDWAY CAVITY CLOSER 15mm MIN.ABOVE BASE OF FIBRE CEMENT SHEET
FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL
HEAD FLASHING AS SPECIFIED BYWINDOW JOINERY MANUFACTURER
LOW FOAMING POLYURETHANE FOAMFOLLOWED BY CONTINUOUS AIR SEAL
5-10mm CONTINUOUS DRAINAGE GAP
SPECIFIED FOAM TAPE BETWEEN HEADFLASHING & JOINERY
MIN. 10mm COVER OF HEAD FLASHINGTO JOINERY
WALL UNDERLAY DRESSED INTOOPENING
SPECIFIED FLEXIBLE FLASHING TAPEINSTALLED TO CORNERS AT HEAD & LAP50mm OVER UNDERLAY
FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS
REFER TO COLOURED 3D DETAILSFOR FURTHER INFORMATION &
CLARIFICATION
WINDOW JOINERY
DWG - 01 WINDOW HEAD DETAIL SCALE - 1:2
ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016
- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.
15
8
ALPINE STONE VENEER CLADDING
ALPINE STONE ADHESIVE/ MORTAR
BGC STONESHEET OR SUMNER BOARD
SPECIFIED CAVITY BATTENS
FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER
5mm GAP BEHIND & 6mm DRAINAGEGAP UNDER WINDOW FLANGE
FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL
CONTINUOUS AIRSEAL INSTALLED TOEDGE OF SILL TRAY
MIN. 8mm COVER OF JOINERY TO FIBRECEMENT SHEET
WANZ WINDOW SUPPORT BARLOCATED UNDER LIP OF SILL TRAY
SPECIFIED FLEXIBLE FLASHING TAPETO CORNERS & LAP ONTO FACE OFWALL UNDERLAY 50mm
WALL UNDERLAY DRESSED INTOOPENING
SPECIFIED SILL TRAY WITH SUPPORTBLOCKS ADHERED AT FIXING POINTS
SPECIFIED SILL TRAY END CAPSADHERED TO ENDS OF SILL TRAY
PROPRIETARY SUPPORT BLOCKS BYJOINERY MANUFACTURER
FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS
REFER TO COLOURED 3D DETAILSFOR FURTHER INFORMATION &
CLARIFICATION
TAPE SILL TRAY END CAPS BACK TOWALL UNDERLAY WITH SPECIFIED TAPE
STONE SILL WITH 15° MIN. SLOPE
FLEXIBLE FLASHING TAPE MAY BEINSTALLED TO ENTIRE SILL,
HOWEVER THIS IS NOT REQUIREDUNDER THE SPECIFIED SILL TRAY
WINDOW JOINERY
DWG - 02 WINDOW SILL DETAIL SCALE - 1:2
ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016
- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.
105
ALPINE STONE VENEER CLADDING
ALPINE STONE ADHESIVE/ MORTAR
BGC STONESHEET OR SUMNER BOARD
TIMBER FRAMING
SPECIFIED CAVITY BATTENS
FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER
HEAD FLASHING TO CONTINUE 20mmPAST JAMB SEALANT
FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL
LOW FOAMING POLYURETHANE FOAMFOLLOWED BY CONTINUOUS AIR SEAL
MIN. 10mm COVER OF JOINERY TOFIBRE CEMENT SHEET
WALL UNDERLAY DRESSED INTOOPENING
SPECIFIED FLEXIBLE FLASHING TAPEINSTALLED TO CORNERS AT HEAD & LAP50mm OVER UNDERLAY
CUT SLOT IN FIBRE CEMENT SHEET TOACCOMODATE HEAD FLASHING
FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS
LINE OF SILL TRAY BELOW
REFER TO COLOURED 3D DETAILSFOR FURTHER INFORMATION &
CLARIFICATION
5mm GAP FROM STONE TO JOINERYFILLED WITH MS SEALANT
5mm THICK SPECIFIED FOAM TAPEBETWEEN JOINERY AND FIBRE CEMENT
SHEET
WINDOW JOINERY
DWG - 03 WINDOW JAMB DETAIL SCALE - 1:2
ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016
- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.
FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS
5mm GAP BETWEEN SHEETS, JOINTSEALED WITH RENDER TAPE
SPECIFIED CAVITY BATTENS
FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL
WALL UNDERLAY CONTINUOUS AROUNDCORNER
ALPINE STONE VENEER CLADDING
ALPINE STONE ADHESIVE/ MORTAR
BGC STONESHEET OR SUMNER BOARD
TIMBER FRAMING
FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER
'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS
DWG - 04 PLAN VIEW OF EXTERNAL CORNER DETAIL SCALE - 1:2
ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016
- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.
FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS
ALPINE STONE VENEER CLADDING
ALPINE STONE ADHESIVE/ MORTAR
BGC STONESHEET OR SUMNER BOARD
FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER
SOLID BLOCKING AS REQUIRED FORTHE FIXING OF FIBRE CEMENT SHEET
FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL
SPECIFIED CAVITY BATTENS
WALL UNDERLAY CONTINUOUS AROUNDCORNER
TIMBER FRAMING
5mm GAP BETWEEN SHEETS, JOINTSEALED WITH RENDER TAPE
'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS
DWG - 05 PLAN VIEW OF INTERNAL CORNER DETAIL SCALE - 1:2
ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016
- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.
50
GR
OU
ND
CLE
ARAN
CE
20 M
IN.
150mm MIN. (PAVED)225mm MIN. (UNPAVED)
BGC STONESHEET OR SUMNER BOARD
SPECIFIED CAVITY BATTENS
ALPINE STONE VENEER CLADDING
ALPINE STONE ADHESIVE/ MORTAR
FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER
FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL
TIMBER BOTTOM PLATE WITH FIXINGS
DAMP PROOF COURSE (DPC) BETWEENTIMBER AND CONCRETE
REDWAY CAVITY CLOSER 20mm MIN.ABOVE BASE OF STONE SHEET
FIBRE CEMENT SHEET TO OVERLAPTHE CONCRETE SLAB BY 50mm
BASE OF STONE SLOPED 5° TO FORM ADRIP EDGE
FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS
PAVED GROUND SLOPING AWAY FROMTHE BUILDING MAY BROUGHT UP TO
WITHIN 50mm OF FLOOR LEVEL ATGARAGE DOOR OPENINGS
TAPE BOTTOM EDGE OF WALLUNDERLAY TO SLAB WITH SPECIFIED
TAPE
'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS
DWG - 06 SLAB EDGE DETAIL SCALE - 1:2
ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016
- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.
50
30
GR
OU
ND
CLE
ARAN
CE
100mm MIN. (PAVED)150mm MIN. (UNPAVED)
BGC STONESHEET OR SUMNER BOARD
SPECIFIED CAVITY BATTENS
VERMIN-PROOFING SHALL PROVIDE AMIN. 1000mm² VENTILATION PER
LINEAL METRE OF WALL
ALPINE STONE VENEER CLADDING
ALPINE STONE ADHESIVE/ MORTAR
FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER
FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL
TIMBER BOTTOM PLATE WITH FIXINGS
LIQUID APPLIED DAMP PROOF COURSE(DPC) BETWEEN TIMBER ANDCONCRETE TO CONTINUE ALONGREBATE (e.g. JAYDEX EASYGUM)
CAVITY BATTENS TO STOP 30mm CLEARFROM SLAB REBATE
FIBRE CEMENT SHEET TO ALIGN FLUSHWITH SLAB EDGE
PROPRIETARY VERMIN-PROOF VENT OR3-5mm DRAINAGE/ VENT HOLES OR
SLOTS THROUGH STONE AND FIBRECEMENT SHEET
STONE ADHERED DIRECTLY TO SLABEDGEPAVED GROUND SLOPING AWAY FROM
THE BUILDING MAY BROUGHT UP TOWITHIN 50mm OF FLOOR LEVEL AT
GARAGE DOOR OPENINGS
FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS
TAPE BOTTOM EDGE OF WALLUNDERLAY TO DPC WITH SPECIFIED
TAPE
'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS
DWG - 07 REBATED SLAB EDGE DETAIL SCALE - 1:2
ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016
- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.
ALPINE STONE VENEER CLADDING
ALPINE STONE ADHESIVE/ MORTAR
BGC STONESHEET OR SUMNER BOARD
FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER
SPECIFIED CAVITY BATTENS
FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL
FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS
NOG TO SUPPORT WALL UNDERLAY ATLINE OF SOFFIT TO BLOCK AIRFLOWFROM CAVITY
CONTINUOUS TIMBER TO BLOCKAIRFLOW FROM CAVITY
TIMBER FRAMING
SOFFIT LINING
'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS
5mm GAP BETWEEN SOFFIT & FIBRECEMENT SHEET, JOINT SEALED WITH
RENDER TAPE
DWG - 08 SOFFIT DETAIL SCALE - 1:2
ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016
- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.
50
35FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER
TIMBER FRAMING
ALPINE STONE VENEER CLADDING
ALPINE STONE ADHESIVE/ MORTAR
BGC STONESHEET OR SUMNER BOARD SPECIFIED CAVITY BATTENS
CONTINUOUS H3.1 TIMBER BLOCKINGTO BLOCK AIRFLOW FROM CAVITY INTOROOF SPACE
FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL
SLOPING SOFFIT FLASHING - IFALUMINIUM IS USED KEEP FROMCONTACT WITH CEMENT GROUT
ANGLE OF SOFFIT91°-115°
FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS
'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS
DWG - 09 SLOPING SOFFIT DETAIL SCALE - 1:2
ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016
- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.
3575
130 **
ALPINE STONE VENEER CLADDING
ALPINE STONE ADHESIVE/ MORTAR
BGC STONESHEET OR SUMNER BOARD
NOGGING TO SUPPORT FLASHING
SPECIFIED CAVITY BATTENS FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER
TAPE APRON FLASHING BACK TO WALLUNDERLAY WITH SPECIFIED TAPE
SLOPE BASE OF STONES 5° TO FORMDRIP EDGE
REDWAY CAVITY CLOSER 15mm MIN.ABOVE BASE OF FIBRE CEMENT SHEET
FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL
TROUGH TURNED UP TO CREATESTOPEND FOR PROFILED ROOFINGAPRON FLASHING TURNED
DOWN TO SUIT ROOFINGPROFILE
ROOFING UNDERLAY CONTINUED UPWALL BEHIND FLASHING
APRON TO HAVE 75mm UPSTANDBEHIND CLADDING INCREASE TO 90mmFOR EH WIND ZONES
APRON TO HAVE 35mm CLEARANCEFROM BASE OF CLADDING
FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS
** APRON FLASHING COVERTO BE 200mm IN VH OR
ABOVE WIND ZONE OR ROOFPITCHES <11°
APRON FLASHING FIXED WITHCOMPATIBLE FIXINGS BY OTHERS
TIMBER FRAMING
DWG - 10 TRANSVERSE APRON DETAIL SCALE - 1:2
ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016
- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.
3575
Y
10
FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER
FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL
NOGGING TO SUPPORT FLASHING
APRON TO HAVE 75mm UPSTANDBEHIND CLADDING INCREASE TO 90mmFOR EH WIND ZONES
APRON TO HAVE 35mm CLEARANCEFROM BASE OF CLADDING
ROOFING UNDERLAY CONTINUED UPWALL BEHIND FLASHING
FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS
ALPINE STONE VENEER CLADDING
ALPINE STONE ADHESIVE/ MORTAR
BGC STONESHEET OR SUMNER BOARD
REDWAY CAVITY CLOSER 15mm MIN.ABOVE BASE OF FIBRE CEMENT SHEET
SLOPE BASE OF STONES 5° TO FORMDRIP EDGE
FIXING THROUGH CREST OF PROFILE
FLASHING TO HAVE 5mmMIN. ANTI CAPPILARY GAP
TAPE APRON FLASHING BACK TO WALLUNDERLAY WITH SPECIFIED TAPE
SPECIFIED CAVITY BATTENS
Y = MIN. 2 CRESTS OF ROOFINGPROFILE & FINISH IN NEXT TROUGH
APRON FLASHING FIXED WITHCOMPATIBLE FIXINGS
TIMBER FRAMING
DWG - 11 PARALLEL APRON DETAIL SCALE - 1:2
ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016
- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.
70
70
ALPINE STONE VENEER CLADDING
ALPINE STONE ADHESIVE/ MORTAR
BGC STONESHEET OR SUMNER BOARD
SPECIFIED CAVITY BATTENS
FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER
INSTALL SPECIFIED FLASHING TAPE TOENTIRE CAP PRIOR TO FLASHING
FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL
METAL CAPPING SIDE FIXED ONLY
FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS
WALL UNDERLAY CONTINUOUS OVERFACE OF STRUCTURE
CAPPING DETAIL MAY BE USED FORCHIMNEY CAPPING. REFER TO FLUEMANUFACTURER FOR CAPPINGDETAILS AND USE NON-COMBUSTIBLEMATERIALS WHERE REQUIRED.
FOR CAPPING JOINTS ANDREQUIREMENTS REFER TO E2/AS1
FIGURE 9 AND SECTION 6.4
5° MIN.SLOPE
9mm MIN. H3.1 PLY PACKED TO SLOPEOR SLOPED POLYSTYRENE BLOCK
BIRD'S BEAK EDGE WHERE USED ASBALUSTRADE CAPPING
70mm MIN. OVERLAP TO CLADDING90mm MIN. IN EH WIND ZONES
H3.1 PACKER FOR FIXING CAPPINGFIXED TO FRAMING AS REQUIRED
NZBC E2 COMPLIANTCLADDING SYSTEM ON ACAVITY
'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS
TIMBER FRAMING
DWG - 12 PARAPET/ BALUSTRADE DETAIL SCALE - 1:2
ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016
- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.
10
ALPINE STONE VENEER CLADDING
ALPINE STONE ADHESIVE/ MORTAR
BGC STONESHEET OR SUMNER BOARD
SPECIFIED CAVITY BATTENS
NO SHEET FIXINGS TO INTER-FLOORBOUNDARY JOIST
FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER
10mm GAP SLOPE STONES 5° TO AIDDRAINAGE
BOTTOM COURSE OF STONEOVERLAPS LOWER SHEET 10mm
WITHOUT ADHESIVE/ MORTAR
FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL
OVER 2 STOREYS OR 7m USE AFLASHING TO BRIDGE THE CAVITY AS
PER E2/AS1 FIGURE 70
FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL
STONE, FIBRE CEMENT SHEET ANDCAVITY BATTENS ARE
DISCONTINUOUS AT FLOOR LEVELSTO ALLOW FOR INTER-STOREY
MOVEMENT
10mm MIN. GAP BETWEEN CAVITYBATTENS & FIBRE CEMENT SHEETS
FLOORING TO FINISH 10mm BACK FROMOUTSIDE FACE OF FRAMING
HORIZONTAL CONTROL JOINT AT ALLFLOOR JOISTS AND ALL WALLSEXCEEDING 5600mm IN HEIGHT 'RENDER TAPE' TO BE APPLIED OVER
ALL SHEET JOINTS
TIMBER FRAMING
'RENDER TAPE' APPLIED OVER GAPBETWEEN FIBRE CEMENT SHEETS
STONE AT JOINT TO BE FIXED ON ONESIDE OF JOINT ONLY
DWG - 13 HORIZONTAL CONTROL JOINT SCALE - 1:2
ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016
- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.
6-8
ALPINE STONE VENEER CLADDING
ALPINE STONE ADHESIVE/ MORTAR
BGC STONESHEET OR SUMNER BOARD
SPECIFIED CAVITY BATTENS
FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER
6-8mm GAP BETWEEN FC SHEETSCOVERED WITH 'RENDER TAPE'
POLYETHYLENE BOND BREAKER TAPEMIN. 12mm EACH SIDE OF JOINT
FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL
VERTICAL CONTROL JOINTS AT5400mm CENTERS MAX. 6000mm
WHEN WALL FINISHES AT ANEXTERNAL CORNER
DOUBLE STUD AT CONTROL JOINT
FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS
'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS
TIMBER FRAMING
DWG - 14 PLAN VIEW OF VERTICAL CONTROL JOINT DETAIL SCALE - 1:2
ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016
- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.
10
ALUMINIUM IF USED SHOULD BE KEPTFROM CONTACT WITH CEMENT GROUT
MS SEALANT CAN BE USED AS ASUBSTITUTE
FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL
SPECIFIED FLEXIBLE FLASHING TAPETO CORNERS AT HEAD TO ENTIRE SILLAND 100mm UP JAMBS LAP 50mm OVERWALL UNDERLAY
TIMBER FRAMING
ALPINE STONE ADHESIVE/ MORTAR
FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER
BGC STONESHEET OR SUMNER BOARD
METERBOXES SHOULD BE LOCATEDIN SHELTERED AREAS
FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS
ALPINE STONE VENEER CLADDING
5-10mm GAP BETWEEN FIBRE CEMENTSHEET AND METERBOX FILLED WITH MS
SEALANT
TAPE METERBOX FIXING ANGLE BACKTO WALL UNDERLAY FIRST AT SILLFOLLOWED BY JAMBS THEN HEADOVERLAPPING AT CORNERS WITH
SPECIFIED TAPE
SPECIFIED CAVITY BATTENS
WALL UNDERLAY DRESSED INTOOPENING
LOW FOAMING POLYURETHANE FOAMFOLLOWED BY CONTINUOUS AIR SEAL
CONTINUOUS FLANGE CREATED FROM40 x 40mm MIN. ANGLE MITRED ATCORNERS FIXED TO METERBOX WITHRIVETS ON SEALANT BED
METERBOX FLANGE SHOULD HAVEJOINTS SEALED WITH SEALANT
A PROPRIETARY METERBOX WITHINTEGRAL FLANGE MAY BE USED
'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS
DWG - 15 METERBOX DETAIL SCALE - 1:2
ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016
- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.
75m
m M
IN.
ALUMINIUM IF USED SHOULD BE KEPTFROM CONTACT WITH CEMENT GROUT.
MS SEALANT CAN BE USED AS ASUBSTITUTE
SOLID BLOCKING AROUNDPENETRATION WITH MIN. 75mmOVERLAP TO UNDERLAY
ALPINE STONE ADHESIVE/ MORTAR
FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER
BGC STONESHEET OR SUMNER BOARD
PIPE AND SIMILAR PENETRATIONSSHOULD BE LOCATED IN SHELTERED
AREASFOR RIGID AIR BARRIERS FOLLOW
MANUFACTURER'S SPECIFICATIONS
ALPINE STONE VENEER CLADDING
5-10mm GAP BETWEEN FIBRE CEMENTSHEET AND PIPE
PROPRIETARY BOOT FLASHINGSEALING PIPE TO BUILDING UNDERLAY
SPECIFIED CAVITY BATTENS
RENDER TAPE TO BE APPLIED OVERFIBRE CEMENT SHEET AROUND PIPE
TIMBER FRAMING
'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS
DWG - 16 PENETRATION DETAIL SCALE - 1:2
ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016
- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.
40
15 5
NZBC E2 COMPLIANT CLADDINGSYSTEM ON A CAVITY
FLASHING WITH MIN 40mm (65mm EHWIND ZONES) TOTAL UPSTAND
5mm MIN. CLEARANCE AT BASE OFCLADDING
FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL
FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS
REDWAY CAVITY CLOSER 15mm MIN.ABOVE BASE OF FIBRE CEMENT SHEET
ALPINE STONE VENEER CLADDING
ALPINE STONE ADHESIVE/ MORTAR
BGC STONESHEET OR SUMNER BOARD
STONE SILL WITH 15° MIN. SLOPE KEEPMIN. 5mm CLEAR OF WALL UNDERLAY
SPECIFIED CAVITY BATTENS
NOGGING TO SUPPORT FLASHING
FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER
TIMBER FRAMING
'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS
TAPE FLASHING BACK TO WALLUNDERLAY WITH SPECIFIED TAPE
ALPINE STONE ADHESIVE/ MORTAR
DWG - 17 HORIZONTAL JOINT WITH ALTERNATIVE CLADDING SCALE - 1:2
ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016
- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.
6-8
ALPINE STONE VENEER CLADDING
ALPINE STONE ADHESIVE/ MORTAR
BGC STONESHEET OR SUMNER BOARD
SPECIFIED CAVITY BATTENS
FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER
100mm WIDE PVC BACK FLASHING
LOW FOAMING POLYURETHANE FOAMFOLLOWED BY CONTINUOUS AIR SEAL
FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL
DOUBLE STUD
FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS
NZBC E2 COMPLIANT CLADDINGSYSTEM ON A CAVITY
SCRIBER SEALED TO STONE FORWEATHERBOARD CLADDING
TIMBER FRAMING
'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS
DWG - 18 PLAN VIEW OF VERTICAL JOINT WITH ALTERNATIVE CLADDING SCALE - 1:2
ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016
- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.
50
50
6-8
FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONS
WALL UNDERLAY CONTINUOUS AROUNDCORNER
ALPINE STONE VENEER CLADDING
ALPINE STONE ADHESIVE/ MORTAR
BGC STONESHEET OR SUMNER BOARD
TIMBER FRAMING
FRAME PROTECTION SYSTEM OR RIGIDAIR BARRIER
FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL
50mm X 50mm WIDE PVC BACKFLASHING
LOW FOAMING POLYURETHANE FOAMFOLLOWED BY CONTINUOUS AIR SEAL
NZBC E2 COMPLIANT CLADDINGSYSTEM ON A CAVITY
H3.2 SCRIBER SEALED TO STONE FORWEATHERBOARD CLADDING
SPECIFIED CAVITY BATTENS
'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS
DWG - 19 PLAN VIEW OF EXTERNAL CORNER JOINT WITH ALTERNATIVE CLADDING SCALE - 1:2
ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016
- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.
6-850
LOW FOAMING POLYURETHANE FOAMFOLLOWED BY CONTINUOUS AIR SEAL
H3.2 SCRIBER SEALED TO STONE FORWEATHERBOARD CLADDING
FOR RIGID AIR BARRIERS FOLLOWMANUFACTURER'S SPECIFICATIONSALPINE STONE VENEER CLADDING
ALPINE STONE ADHESIVE/ MORTAR
BGC STONESHEET OR SUMNER BOARD
SOLID BLOCKING AS REQUIRED FORTHE FIXING OF FIBRE CEMENT SHEET
FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL
SPECIFIED CAVITY BATTENS
WALL UNDERLAY CONTINUOUS AROUNDCORNER
TIMBER FRAMING
BACK FLASHING WITH MIN. 50mmOVERLAP TO JOINT & STONESHEET
NZBC E2 COMPLIANT CLADDINGSYSTEM ON A CAVITY
BACK FLASHING TO BE OF A SUITABLYCOMPATIBLE MATERIAL
'RENDER TAPE' TO BE APPLIED OVERALL SHEET JOINTS
50
DWG - 20 PLAN VIEW OF INTERNAL CORNER JOINT WITH ALTERNATE CLADDING SCALE - 1:2
ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016
- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.
**H5 TREATED TIMBER POST OR STEELPOST TO SPECIFIC DESIGN
POST BRACKET AND FIXING TOSPECIFIC DESIGN
H3.2 TIMBER FRAMING
ALPINE STONE ADHESIVE/ MORTAR
BGC STONESHEET OR SUMNER BOARD
ALPINE STONE VENEERCLADDING
5mm GAP BETWEEN SHEETS, JOINTSEALED WITH RENDER TAPE
FIBRE CEMENT SHEET FIXINGS ASPER ALPINE STONE TECHNICAL
MANUAL
**POST MAY BE EMBEDED INCONCRETE AS AN ALTERNATIVE TO
BRACKET
DWG - 21 PLAN VIEW OF COLUMN DETAIL 1:5
ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016
- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.
20 M
IN
10
**H5 TREATED TIMBER POST ORSTEEL POST TO SPECIFICDESIGN
H3.2 TIMBER FRAMING FIXED TOPOST WITH ANGLE BRACKET
ALPINE STONE VENEERCLADDING
ALPINE STONE ADHESIVE/MORTAR
BGC STONESHEET OR SUMNERBOARD
CONCRETE PLINTH OPTION TO BEUSED IN FLOOD PRONE AREAS
POST BRACKET AND FIXING TOSPECIFIC DESIGN
PROVIDE 10mm MIN GAP BETWEENBOTTOM OF FIBRE CEMENT SHEET
AND GROUND.WHEN CONCRETE PLINTH OPTION IS
USED, PROVIDE VERMIN-PROOFVENT, MIN 1000mm² PER LINEAL
METRE OF STONE VENEER
**POST MAY BE EMBEDED INCONCRETE AS AN ALTERNATIVE TO
BRACKET
FIBRE CEMENT SHEET FIXINGS ASPER ALPINE STONE TECHNICAL
MANUAL
ALTERNATIVEGROUND LEVEL
DWG - 22 COLUMN BASE DETAIL 1:5
ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016
- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.
10mm MIN.
45
COPING STONE WITH 15° MIN. FALL
ALPINE STONE VENEER CLADDING
ALPINE STONE ADHESIVE/ MORTAR
BGC STONESHEET OR SUMNERBOARD
FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL
H3.2 TIMBER FRAMING FIXED TO POSTWITH ANGLE BRACKET
H5 TREATED TIMBER POST OR STEELPOST TO SPECIFIC DESIGN
ALPINE STONE ADHESIVE/ MORTAR
SPECIFIED RENDER TAPE ADHEREDTO POST AND TO COVER ALL JOINTS INFIBRE CEMENT BOARD
DWG - 23 HALF COLUMN DETAIL 1:5
ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016
- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.
10mm MIN.
45
COPING STONE WITH 15° MIN. FALL
ALPINE STONE VENEER CLADDING
ALPINE STONE ADHESIVE/ MORTAR
SPECIFIED RENDER TAPE ADHERED TOPOST AND TO COVER ALL JOINTS INFIBRE CEMENT BOARD. TAPE TO ADHEREMIN 45mm UP POST
H3.2 TIMBER FRAMING FIXED TO POSTWITH ANGLE BRACKET
**H5 TREATED TIMBER POST OR STEELPOST TO SPECIFIC DESIGN
FIBRE CEMENT SHEET FIXINGS AS PERALPINE STONE TECHNICAL MANUAL
BGC STONESHEET OR SUMNERBOARD
DWG - 24 HALF COLUMN CAPPING DETAIL 1:2
ALPINE STONE VENEER CLADDING SYSTEM VERSION - 16/03/2016
- THESE DRAWINGS MUST BE READ IN CONJUNCTION WITH THE LIST OF SPECIFIED/ACCEPTED PRODUCTS SUPPLIED WITH THE ALPINE STONE TECHNICALMANUAL.- SUBSTRATE TO BE PREPPED READY TO APPLY ALPINE STONE VENEER TO. THIS MUST COMPLY WITH ALL RELEVANT STANDARDS AND REQUIREMENTS e.g.COUNCIL, NZBC, ALPINE STONE AND OTHER PRODUCTS DETAILS.- ANY SCRIBERS, PEF ROD, RENDERS, SEALERS etc (OTHER THAN THE SEALER SCRATCH COAT APPLIED BY ALPINE STONE) REQUIRED AS PART OF THECONSTRUCTION DETAIL BEFORE AND AFTER INSTALLATION WILL NOT BE DONE BY ALPINE STONE OR IT'S INSTALLERS.
*310
*310
*105 *100
**H3.2 TREATED TIMBER POST ORSTEEL POST TO SPECIFIC DESIGN
ALPINE STONE ADHESIVE/MORTAR
ALPINE STONE VENEERCLADDING
**H3.2 TREATED TIMBER POST IF USEDWITH POST BRACKET. USE H5 TREATEDTIMBER POST IF SEATED DIRECTLY INCONCRETE.
2 PIECE MOULDED POLYSTYRENESUBSTRATE. FIX EACH PIECE TO THE
OTHER AND TIMBER POST WITHPOLYSTYRENE COMPATIBLECONSTRUCTION ADHESIVE.
* POLY-COLUMN SUPPLIED TO SUITCOLUMN HEIGHT, WIDTH OF POST AND
SIZE AND SHAPE OF FINISHEDEXTERIOR.
SEE ALPINE STONE TECHNICALMANUAL FOR FULL INSTALLATION
INSTRUCTIONS.
DWG - 25 PLAN VIEW OF POLY-COLUMN DETAIL 1:5
HEAD : FINISHED WALLHEAD : FIBRE CEMENT SHEET
HEAD : FLASHINGHEAD : WRAP & TAPE
DWG - 26 WINDOW HEAD 3D SEQUENCE
1. TIMBER FRAMING INSTALLED2. WALL UNDERLAY RUN HORIZONTALLY & DRESSEDINTO WINDOW/ DOOR OPENING3. SPECIFIED FLEXIBLE FLASHING TAPE TO CORNERS ATHEAD AND JAMBS
4. HEAD FLASHING FIXED WITH PROPRIETARY STOPENDS INSTALLED5. TOP EDGE OF FLASHING TAPED BACK TO WALLUNDERLAY WITH SPECIFIED FLEXIBLE FLASHING TAPE6. CAVITY BATTENS INSTALLED
7. INSTALL CAVITY CLOSER THEN INSTALL FIBRECEMENT SHEET AROUND HEAD FLASHING8. INSTALL SPECIFIED FOAM TAPE ONTO FIBRE CEMENTSHEET AT JAMBS9. AIR SEAL SHOWN IS INSTALLED AFTER FIXING OFWINDOW
10. APPLY SPECIFIED FOAM TAPE TO HEAD OF JOINERYAND INSTALL JOINERY UNDER HEAD FLASHING AND FIXAS REQUIRED11. APPLY STONE TO FIBRE CEMENT SHEET WITHALPINE STONE ADHESIVE AND SEAL JAMB WITH MSSEALANT
SILL : WRAP & TAPE SILL : TRAY & WANZ BAR
SILL : FIBRE CEMENT SHEET SILL : FINISHED WALL
1. TIMBER FRAMING INSTALLED2. WALL UNDERLAY RUN HORIZONTALLY & DRESSED INTOWINDOW/ DOOR OPENING3. SPECIFIED FLEXIBLE FLASHING TAPE TO ENTIRE SILLAND 100mm UP AT JAMBS
4. REDWAY SILL TRAY ADHERED TO SILL TRAY ENDCAPSAND INSTALLED TO SILL TRIMMER WITH WANZ BAR5. TOP EDGE OF SILL END CAPS TAPED TO JAMB WITHSPECIFIED FLEXIBLE FLASHING TAPE6. CAVITY BATTENS INSTALLED
7. STONE SHEET FIXED8. 5mm THICK SPECIFIED FOAM TAPE INSTALLED ONTOSTONESHEET AT JAMBS9. AIR SEAL SHOWN IS INSTALLED AFTER FIXING OFWINDOW
10. WINDOW SUPPORT BLOCKS FITTED AND JOINERYINSTALLED AND FIXED AS REQUIRED12. STONE ADHERED TO STONE SHEET WITH ALPINESTONE ADHESIVE AND SEAL JAMB WITH MS SEALANT
DWG - 27 WINDOW SILL 3D SEQUENCE