ADDENDA #01
PROJECT: Mount Allison University Gairdner Renovations Project PROJECT No: CFEI-16-01 TP02 DATE: 2017.03.24
This Addendum shall be considered part of the specifications for the construction of this work and shall be read in conjunction with such specifications. All work mentioned herein shall be in addition to and shall supersede the specifications and shall be included in the contractor’s tender. This Addendum shall be read in conjunction with drawings and Specifications Issued for RFP on March 15, 2017. This Addendum has a total of Eighteen (18) pages including attachments.
1. SPECIFICATIONS
1.1. Reference Cover Page
a. Revise date to read March 15, 2017. b. Revise title ‘SPECIFICATION ISSUED FOR TENDER’ to read ‘SPECIFICATIONS:
REQUEST FOR PROPOSALS’
1.2. Reference Section 00 11 16 Request for Proposals a. Revise first sentence to read as follows:
‘Proposals will be received from Qualified General Contractors at the office of the Mount Allison University department of Financial Services, Room 310, Centennial Hall, 65 York Street, Sackville New Brunswick E4L 1E4, until 4:00:00PM, Tuesday April 11, 2017 for the following project:’
1.3. Reference Section 00 21 13 Instructions to Proponents a. Reference page 2. Modify Closing Date to Tuesday, April 11, 2017.
1.4. Reference Specification Section 02 82 00.09 Asbestos Abatement Minimum
Precautions a. Change Specification Section number from 02 82 00.09 to 02 82 00.01
1.5. Reference Specification Section 02 85 14 Miscellaneous Hazardous Materials
Abatement- Gairdner Fine Arts Building, Mount Allison University a. Delete Section 02 85 14, in its entirety.
Page 2 of 6
1.6. Reference Specification 09 91 10 Painting item 2.1 Manufacturers
a. Modify item 2.1.1 to read as follows: Sherwin Williams b. Modify item 2.1.2 to read as follows:
‘Other acceptable manufacturers offering functionally and aesthetically equivalent products .1 CIL .2 PPG’
1.7. Reference Specification Section 22 15 00 a. Item 2.2.1: Compressed Air Piping shall not be copper tubing. Compressed air
piping shall be an approved plastic tubing with ASTM E84 compliant 25/50 smoke/flame development.
1.8. Reference Specification Section 25 05 01 a. Clarification: All Controls work shall be supplied and installed under separate
contract by Siemens (Owner’s controls contractor), except as noted herein: b. Item 1.1.2: Controls shall include all control hardware, software, graphics,
programming, relays, conduit, wiring, devices, sensors, control valves, actuators, laboratory control system, lab air control devices (air valves/terminals and associated silencers), and integration to all facility equipment (i.e air handlers, chillers, etc) with integral on-board controllers.
c. Disregard item 1.1.5: Not in contract. Disregard section requesting separate pricing of air valves and control system. Air valves/terminals, laboratory silencers shall be installed by HVAC contractor under supervision of certified device supplier. Setup, configuration, Ashrae 110 testing, etc shall be by controls contractor supplying air terminal/valves and associated laboratory controls.
d. All systems Control Valves and Actuators to be supplied by Siemens and installed by General Contractor. General Contract shall provide all required sensor wells.
1.9. Reference Specification Section 25 30 01
a. Disregard Specification Section 25 30 01 Laboratory Controllers/Devices: Not in contract.
1.10. Reference Specification Section 25 50 00
a. Disregard Specification Section 25 50 00 BACnet Device Interfacing: Not in contract.
1.11. Reference Specification Section 25 50 05.01
a. Disregard Spec section 25 50 05.01 BACnet Integration – Variable Frequency Drives: Not in contract.
Page 3 of 6
1.12. Reference Specification Section 25 50 82.22 a. Clarification: VRF System Interfacing- Provided for reference of VRF system
device supply (By General Contract) for compatibility/reference only. Install by Siemens for to Building Automation Interface. VRF controls/devices to be supplied by VRF supplier/manufacturer thru the General contractor. VRF controls to be installed by controls contractor (Siemens). Wiring & conduit by Siemens. General Contractor shall coordinate with Siemens and have VRF supplier (Daikin) provide commissioning of VRF systems.
2. DRAWINGS
2.1. Reference Drawing Coversheet a. Replace Drawing Coversheet Issued for RFP 2017.03.14 with attached Drawing
Cover Issued for RFP 2017.03.15.
2.2. Reference Drawing F1.02 a. Delete stair modifications per sketches SSK.02 and SSK.03, attached.
2.3. Reference Drawing S1.01
a. Added design loads to canopy as per sketch SSK.04, attached.
2.4. Reference Drawing S1.04 a. Delete two hangers and short beam folding partition and support & revise
partition support beam W8x24 as per sketch SSK.05 attached. b. At air make up unit relocate piping relocate piping openings to left side of the
unit per sketch SSK.05, attached. c. Revise note 6 to C4x5.4 and maximum span on deck to 5’-0 per sketch SSK.05,
attached.
2.5. Reference Drawing S1.05 a. Delete detail indicated on sketch SSK.06, attached.
2.6. Reference Drawing S1.06
a. Add two roof anchors per sketch SSK.07
2.7. Reference Drawing S1.08 a. Relocated canopy support HSS5x5x2.5 per sketches SSK.08 and SSK.09,
attached.
2.8. Reference Drawings S1.09 to S1.12 a. Revise stair riser detail per sketch SSK.10, attached.
Page 4 of 6
2.9. Reference Drawings A6.03 and A6.04 Finish Schedule and Finish Floor Plans a. Reference ROOM FINISH SCHEDULE and Revise Ceiling Finishes for the following
rooms as follows: 101 Phytoplankton Ecophysiology Lab GWB2
101C Transfer Hood Alcove GWB2 107 Phytoplankton Ecology & Modelling Lab GWB2 107B Transfer Hood Alcove GWB2
b. Reference ROOM FINISH SCHEDULE and Revise Comments for the following rooms 101, 101C, 107 and 107B to ADD the following: ‘GWB2 ceilings are furred to underside of existing concrete slab. Mechanical and Electrical services are exposed. Both GWB ceiling and exposed Mechanical and Electrical services/ hangers to receive a paint finish.’
c. Reference ROOM FINISH SCHEDULE: Add GENERAL NOTE: All exposed ductwork, Mechanical and Electrical Hangers, Underside of Structure, underside of slab or GWB to receive paint finish.
2.10. Reference Drawing M3.07 a. Detail 3/M3.07 Temporary Relocation of Owen’s Gallery Chiller to be
disregarded; not in contract. Work shall be coordinated directly by Facilities Management. Final relocation IS included in contract.
2.11. Reference Drawing Series M3.XX (Heating)
a. General reference: Steam/Condensate piping extending from loading dock into existing Gairdner building basement, to be isolated, capped and removed.
2.12. Reference Drawing M3.09
a. Tunnel Services Plan: All Existing service tunnel services including water, steam and condensate to be removed and replaced with new services as indicated.
2.13. Reference Drawing M2.09
a. Detail 5/M2.09: Gravity Intake Hoods (GIH) shall be equipped with Low leakage insulated control dampers. Actuators/controls by Siemens. Delete gravity backdraft dampers.
2.14. Reference Drawing M1.00
a. Note 1: Acid Neutralizer tank shall be supplied c/w ‘PHIX’ media, not limestone.
2.15. Reference Drawing M1.05 a. Aqualab sink P-4 shall be supplied with a Salt Water Fill Tap. Provide ½” fill line
to P-4, extended from local main.
2.16. Reference Drawings E0.00 a. Add Fire Alarm System symbol ‘FR’ with description: Fire Alarm Relay.
2.17. Reference Drawings E0.01
a. Add Note #7 to Site Notes as follows: Underground conduits feeding new type AA Luminaires to follow new concrete footpaths to minimize damage existing tree roots. Extend length of conduit accordingly.
Page 5 of 6
2.18. Reference Drawings E1.01
a. Add Specific Note #2 to Detail #1 as follows: Lighting override switches, refer to detail #2 on drawing E3.01 for lighting control for fixtures G & H.
b. Refer to Basement Floor RCP – Lighting, at Gridlines D-6 Add two (2) Override Lighting switches with reference to new Specific Note #2.
c. Refer to Basement Floor RCP – Lighting, add ceiling mounted type L lighting fixture in tunnel entrance from Mechanical/Electrical Room B18 and connect to existing tunnel circuit. Add new 3-way lighting switch on wall inside of tunnel entrance to control tunnel lighting.
d. Refer to Basement Floor RCP – Lighting, add wall mounted type L lighting fixture in beside light switch in elevator pit and circuit to B1-11, controlled by lighting switch shown in elevator pit.
e. Refer to Basement Floor RCP – Lighting, add ceiling mounted occupancy sensors to the following rooms:
1. Loading B16: Quantity 1 2. Fish Biochem & Nano Particle Lab B13: Quantity 3 3. CHN Analyzer B11 : Quantity 1 4. Faculty Office B15 : Quantity 1
f. Refer to First Floor RCP – Lighting, add ceiling mounted occupancy sensors to the following rooms:
1. Phytoplancton & Eco. Lab 107: Quantity: 3 2. Transfer Hood Alcove 107B: Quantity 1 3. Phytoplancton & Eco. Lab 101: Quantity: 3 4. Transfer Hood Alcove 101C: Quantity 1
g. Refer to Second Floor RCP – Lighting, add ceiling mounted occupancy sensors to the following rooms:
1. North Stair 2 ST1-2-2: Quantity: 1 2. Meeting Room/Kitchenette 213: Quantity 1 3. Flex Innovation Lab 211: Quantity: 2 4. Eco. And Paleo Freshwater Lab 209: Quantity: 3 5. Molecular & Bio Lab 203-2: Quantity 3 6. Molecular & Bio Lab 203-1: Quantity 3
2.19. Reference Drawings E3.03
a. Replace Drawing E3.03 Revision 0 with Drawing E3.03 Revision 1, attached.
3. CLARIFICATIONS
3.1. Reference all Structural Drawings a. Revise revision title block per sketch SSK.01, attached.
Page 6 of 6
4. ATTACHMENTS
4.1. Drawing Coversheet, dated March 15, 2017
4.2. Structural Sketches SSK.01-SSK.10, dated March 24, 2017
4.3. Electrcial Drawing E3.03, Issued for Addendum 1, dated March 23, 2017.
END OF ADDENDA #01
2010 NATIONAL BUILDING CODE DATA MATRIX PART 3
PROJECT DESCRIPTION: CHANGE OF USE NEW BUILDING ADDITION RENOVATION PART 3 PART 9
MAJOR OCCUPANCY:
BUILDING AREA:
GROSS AREA:
NUMBER OF STOREYS:
HEIGHT OF BUILDING:
GROUP F - DIVISION 3 : LOW- HAZARD INDUSTRIAL
EXISTING: 455 SQ. M NEW: 61 SQ. M TOTAL: 516 SQ. M
EXISTING: 1314 SQ. M NEW: 116 SQ. M TOTAL: 1430 SQ. M
2 STOREYS ABOVE GRADE: 2 BELOW GRADE: 1
10.1 m
NUMBER OF STREETS: 2 STREETS
BUILDING CLASSIFICATION: GROUP F, DIVISION 3, UP TO 2 STORYS, SPRINKLERED
SPRINKLER SYSTEM PROPOSED: ENTIRE BUILDING
STANDPIPE REQUIRED: NO
FIRE ALARM REQUIRED: YES
WATER SERVICE/ SUPPLY: SUPPLY IS ADEQUATE
HIGH BUILDING: NO
PERMITTED CONSTRUCTION: COMBUSTIBLE OR NON-COMBUSTIBLE
OCCUPANT LOAD: BASED ON DESIGN OF BUILDINGBASEMENT FLOOR LOAD: 33 PEOPLEFIRST FLOOR LOAD: 33 PEOPLESECOND FLOOR LOAD: 33 PEOPLEMECHANICAL MEZZANINE LOAD: 0 PEOPLE
BARRIER-FREE DESIGN: YES- FULL COMPLIANCE
HAZARDOUS SUBSTANCES: NO
REQUIRED FIRERESISTANCE RATINGS:
FLOORSROOFMEZZANINESFRR OF SUPPORTING MEMBERSSTAIRSELEVATOR SHAFT/ CONTROL RMJANITOR RMCUSTODIAL STORAGECOMMSLABSMECHANICAL ROOMSSEPARATION AT LINK/ LOADING
0 HR FIRE SEPARATION (NON-COMBUSTIBLE)NONEN/ANONE (NON-COMBUSTIBLE)1 HR FIRE SEPARATION1 HR FIRE SEPARATION0 HR FIRE SEPARATION0 HR FIRE SEPARATION1 HR FIRE SEPARATION0 HR FIRE SEPARATION1 HR FIRE SEPARATION2 HR FIREWALL (NOTE 3)
SPATIAL SEPARATION-CONSTRUCTION OFEXTERIOR WALLS:
WALL PERMITTED %OFUNPROTECTEDOPENINGS
AREA OFEXPOSINGBUILDINGFACE
LIMITINGDISTANCE (m)
FRR(HOURS)
TYPE OFCONSTRUCTIONREQUIRED
TYPE OF CLADDINGREQUIRED
COMB. NON-COMB. COMB. NON-COMB.NORTHSOUTHEASTWEST
PLUMBING FIXTUREREQUIREMENTS:
MALEFEMALE
% OCCUPANCY W/CREQUIRED
OCCUPANTLOAD
W/C TOTALPROVIDED
W/CPROVIDED
50%50%
5050
33
33
6 SINGLE STALL W/C,INCL. 3 BARRIER FREE
3.1.2.1 (1)
1.4.1.2 (A)
1.4.1.2 (A), 3.2.1.1 (NOTE 1)
3.2.2.5
3.2.2.10
3.2.2.84
3.2.5.8
3.2.4.1
3.2.5.7
3.2.6
3.1.17 (NOTE 2)
3.8
3.3.1.2
3.2.3.1 D
3.7.2.2 C
1.4.1.2 (A)
3.2.2.84
3.2.2.84
3.2.2.84
NOTE 1: EXCEPTIONS TO BUILDING HEIGHT REFER TO NBCC 2010 REFERNCE 3.2.1.1 (1) AND 3.2.1.1 (8) AND CLAUSES:3.2.5.14 BUILDING IS SPRINKLERED3.3.1.24 ILLUMINATED SIGNS INDICATING DIRECTION OF EGRESS PROVIDED3.2.4.19 (10) AUDIBLE SIGNAL DEVICES CONNECTED TO FIRE ALARM PROVIDED3.2.7.3 (2) EMERGENCY LIGHTING PROVIDED3.3.1.3 (7) ONLY ONE POINT OF EGRESS REQUIRED, AREA OF MECHANICAL ROOM 70 SQ. M.3.4.2.4 (3) TRAVEL DISTANCE IS NO MORE THAN 50M3.4.4.4 (9) VESTIBULE PROVIDED
NOTE 2: LAB OCCUPANCY LOADS ARE DICTATED BY UNIVERSITY PROCEDURES AND MAXIMUM OCCUPANCY AT PEAK RESEARCH TIMES. A GROSS-UP FACTOR OF 1.3 IS APPLIED TOTHE HIGHEST PREDICTED OCCUPANCY AS A PRECAUTION FOR FUTURE USE.
NOTE 3: 3.1.10.2 (2) PROVIDE 2HR FIREWALL TO SEPARATE GROUP F3 OCCUPANCY FROM GROUP A.
NBCC 2010 REFERENCE
340340215.5215.5
N/AN/A20m10m
100%NONENONENONE
NONE X XX X
X XX
X XXX
XX X
100%100%100%
X X
GAIRDNER RENOVATIONSPROJECT
PROJECT NO. CFEI-16-01 TP02
ISSUED FOR RFP 2017.03.15
MOUNT ALLISON UNIVERSITY
DSRA Architecture Inc.5495 Spring Garden Road, 4th Floor,Halifax, NS, B3J 1G2TEL. (902) 420-9990
ARCHITECT
DRAWING LIST
CIVILC1.01C1.02
CIVIL SERVICESDETAILS
J. M. Giffin Engineering21042 Lower LaPlanche Street (Highway #2),Amherst, NS, B4H 3Y5TEL. (902) 667-3300
STRUCTURAL CONSULTANT
MCW Consultants Ltd.77 Vaughan Harvey Blvd., Suite 200,Moncton, NB, E1C 0K2TEL. (506) 857-8880
MECHANICAL CONSULTANT ELECTRICAL CONSULTANT
53 YORK STREET. SACKVILLE. N.B.
MCW Consultants Ltd.77 Vaughan Harvey Blvd., Suite 200,Moncton, NB, E1C 0K2TEL. (506) 857-8880
DSRA JOB NO. 16135
BUILDING RENOVATIONS
MECHANICALM0.00M1.00M1.01M1.02M1.03M1.04M1.05M1.06M1.07M1.08M1.09M1.10M2.00M2.01M2.02M2.03M2.04M2.05M2.06M2.07M2.08M2.09M3.00M3.01M3.02M3.03M3.04M3.05M3.06M3.07M3.08M3.09M3.10M3.11M4.00M4.01M4.02M4.03M4.04M4.05M5.00M5.01M5.02M5.03
MECHANICAL SYMBOL, LEGEND, DRAWING LIST AND GENERAL NOTESUNDERGROUND FLOOR PLAN - SANITARYBASEMENT FLOOR PLAN - SANITARYFIRST FLOOR PLAN- SANITARYSECOND FLOOR PLAN- SANITARYMEZZANINE AND MECH RM B18 FLOOR PLANS- PLUMBINGBASEMENT FLOOR PLAN - WATER & GASFIRST FLOOR PLAN - WATERSECOND FLOOR PLAN - WATERDETAILS - PLUMBINGDETAILS AND SCHEDULES - PLUMBINGDETAILS - PLUMBINGBASEMENT FLOOR PLAN - VENTILATIONFIRST FLOOR PLAN - VENTILATIONSECOND FLOOR PLAN - VENTILATIONMEZZANINE FLOOR PLAN - VENTILATIONROOF PLAN - MECHANICALDETAILS - VENTILATIONDETAILS & SCHEMATICS - VENTILATIONSCHEMATIC - VENTILATIONSCHEDULES- VENTILATIONSCHEDULES- VENTILATIONBASEMENT FLOOR PLAN - HEATINGFIRST FLOOR PLAN - HEATINGSECOND FLOOR PLAN - HEATINGMEZZANINE & MECHANICAL ROOM B18 FLOOR PLANS - HEATINGDETAILS - HEATINGDETAILS AND SCHEMATICS - HEATINGSCHEMATICS - HEATINGSCHEMATICS - HEATINGSCHEDULES - HEATINGTUNNEL SERVICE PLANSCHEMATIC AND DETAILS - STEAM PIPINGTUNNEL PIPING SUPPORTBASEMENT FLOOR PLAN - FIRE PROTECTIONFIRST FLOOR PLAN - FIRE PROTECTIONSECOND FLOOR PLAN - FIRE PROTECTIONMEZZANINE AND MECH. RM B18 FLOOR PLANS- FIRE PROTECTIONDETAILS - FIRE PROTECTIONSTAIRWELL SECTIONS - FIRE PROTECTIONBUILDING SECTIONS - MECHANICAL SERVICESBUILDING SECTIONS - MECHANICAL SERVICESBUILDING SECTIONS - MECHANICAL SERVICESMECHANICAL ROOM/ MEZZANINE SECTIONS - MECHANICAL SERVICES
ARCHITECTURALA0.11A0.12A0.13A1.01A1.02A1.03A1.11A1.12A1.13A1.21A1.22A2.01A3.01A3.02A4.01A4.02A5.51A5.52A5.53A5.54A5.61A5.65A6.01A6.02A6.03A6.04A7.01A7.02A7.03A8.01A8.02A8.03A8.04A8.05
BASEMENT AND FIRST FLOOR DEMOLITION PLANSSECOND FLOOR AND MEZZANINE DEMOLITION PLANSROOF DEMOLITION PLANBASEMENT AND FIRST FLOOR PLANSSECOND FLOOR AND MEZZANINE PLANSROOF PLANBASEMENT FLOOR EQUIPMENT PLANFIRST FLOOR EQUIPMENT PLANSECOND FLOOR EQUIPMENT PLANBASEMENT AND FIRST FLOOR REFLECTED CEILING PLANSSECOND FLOOR AND MEZZANINE REFLECTED CEILING PLANSEXTERIOR BUILDING ELEVATIONSBUILDING SECTIONSBUILDING SECTIONSWALL SECTIONSWALL SECTIONSEXTERIOR SECTION DETAILSEXTERIOR SECTION DETAILSEXTERIOR SECTION DETAILSEXTERIOR SECTION DETAILSEXTERIOR PLAN DETAILSINTERIOR PLAN DETAILSWINDOW SCHEDULEDOOR AND SCREEN SCHEDULEFINISH SCHEDULE AND FINISH FLOOR PATTERNFINISH SCHEDULE AND FINISH FLOOR PATTERNSOUTH STAIR PLANS AND SECTIONSNORTH STAIR PLANS AND SECTIONSSTAIR AND CANOPY DETAILSENLARGED PLANS AND INTERIOR ELEVATIONSENLARGED PLANS AND INTERIOR ELEVATIONSENLARGED PLANS AND INTERIOR ELEVATIONSENLARGED PLANS AND INTERIOR ELEVATIONSMILLWORK SECTIONS AND DETAILS
ELECTRICALE0.00E0.01E0.02E1.01E2.01E2.02E3.01E3.02E3.03E4.01E5.01E5.02E5.03
ELECTRICAL SYMBOL LEGED, DRAWING LIST AND GENERAL NOTESSITE PLAN - ELECTRICALCAMPUS PLAN - ELECTRICALLIGHTING FLOOR PLANSPOWER AND SYSTEMS FLOOR PLANSPOWER AND SYSTEMS FLOOR PLANSLUMINAIRE AND EQUIPMENT SCHEDULESOWNER'S EQUIPMENT SCHEDULEMECHANICAL EQUIPMENT SCHEDULESINGLE LINE DIAGRAMPANEL LEGENDSPANEL LEGENDSPANEL LEGENDS
STRUCTURALF1.01F1.02F1.03F1.04S1.01S1.02S1.03S1.04S1.05S1.06S1.07S1.08S1.09S1.10S1.11S1.12S1.13
FOUNDATION PLANFOUNDATION PLAN AT LOADING DOCKSECTIONS AND DETAILSSECTIONS AND DETAILSFIRST FLOOR FRAMING PLANSECOND FLOOR FRAMING PLANMEZZANINE FLOOR & NEW ROOF FRAMING PLANROOF FRAMING PLANSECTIONS AND ELEVATIONSSECTIONS AND DETAILSSECTIONSROOF FRAMING PLAN AND SECTIONSTAIR SECTIONSTAIR SECTIONSTAIR SECTIONSTAIR SECTIONSECTION
Harbourside Engineering219 Waverley Road, Suite 200Dartmouth, NS B2X 2C3TEL. (902) 405-4696
CIVIL CONSULTANT
LANDSCAPE
L1.01L1.02L1.03L1.04L1.05L1.06L1.07L1.08L1.09L1.10
EXISTING CONDITIONS AND REMOVALSSITEWORK LAYOUT PLANSITEWORK GRADING PLANSITEWORK PLANTING PLANSITEWORK DETAILS 1SITEWORK DETAILS 2SITEWORK DETAILS 3SITEWORK DETAILS 4SITEWORK DETAILS 5SITEWORK DETAILS 6
PHASINGP0.00 PROJECT PHASING PLAN
Vollick McKee Petersmann & Associates2030 Gottingen StreetHalifax, NS, B3K 3A9TEL. (902) 422-6514
LANDSCAPE ARCHITECTURE CONSULTANT
SSK. 01
NO. REVISION DATEISSUED FOR RFP0 MAR 15 2017
EXISTING STAIR
PLAN
(DWG.F1.02)
SSK. 02
DELETE
SECTION
(DWG.F1.02)
SSK. 03
DELETE
CANOPY
DESIGN LOADS
(DWG.S1.01)
SSK. 04
ROOF FRAMING
PLAN
(DWG.S1.04)
SSK.05
SECTION
AT CANOPY
(DWG.S1.05)
SSK.06
DELETE DETAIL
FROM VIEWPORT
ROOF FRAMING
PLAN
(DWG.S1.06)
SSK.07
SECTION
AT CANOPY
(DWG.S1.08)
SSK. 08
END PLATE
DETAILS
(DWG.S1.08)
SSK.09
SSK. 10
SCALE:
DRAWN BY:
CHECKED BY:
MCW JOB NO.:
STAMP
KEY PLAN N
GENERAL NOTES:
1. ALL DRAWINGS, SPECIFICATIONS, AND RELATED DOCUMENTSARE THE COPYRIGHT PROPERTY OF THE ARCHITECT AND MUSTBE RETURNED UPON REQUEST. REPRODUCTION OF DRAWINGS,SPECIFICATIONS, AND RELATED DOCUMENTS IN PART OR WHOLEIS FORBIDDEN WITHOUT THE ARCHITECT'S WRITTEN PERMISSION.
2. THE ARCHITECT SHALL NOT TAKE RESPONSIBILITY FORCHANGES OCCURRING TO ELECTRONICALLY TRANSFERREDDRAWINGS, SPECIFICATIONS, AND RELATED DOCUMENTSDURING OR AFTER THEIR TRANSMISSION.
3. CONTRACTOR MUST CHECK AND VERIFY ALL DIMENSIONS ONTHE JOB SITE. ANY DISCREPANCY OR CONTRADICTORYINFORMATION WITHIN THIS SET OF DRAWINGS AND/OR OTHERCONSULTANTS' DRAWINGS MUST BE REPORTED TO THEARCHITECT BEFORE PROCEEDING WITH WORK.
4. NO VARIATIONS OR MODIFICATIONS TO WORK SHOWN SHALLBE IMPLEMENTED WITHOUT PRIOR APPROVAL OF THEARCHITECT.
5. ALL PREVIOUS VERSIONS OF THIS DRAWING ARESUPERSEDED.
6. THIS DRAWING SHALL NOT BE USED FOR CONSTRUCTIONPURPOSES UNLESS COUNTERSIGNED AND STAMPED BELOW.
MTA PROJECT #: CFEI-16-01
SHEET SIZE: 24"x36"
23
/03
/20
17 3
:12
:42
PM
D.H.
C.D.
53 YORK STREET, SACKVILLE NB
MECHANICAL EQUIPMENTSCHEDULE
E3.03
11-16-090
MOUNT ALLISON UNIVERSITY
GAIRDNER RENOVATIONS
77 Vaughan Harvey Blvd, Suite 200, Moncton, NB, E1C 0K2E-Mail: [email protected] www.mcw.comTel: 506-857-8880 Fax: 506-859-8393
Moncton Toronto Vancouver Winnipeg Ottawa HalifaxDauphin Kelowna Trail Truro Saint John
NO. REVISION DATE
0 ISSUED FOR RFP MAR 15 2017
1 ADDENDUM #1 MAR 23 2017
MECHANICAL EQUIPMENT SCHEDULE - ELECTRICAL REQUIREMENTS
REF. DESCRIPTION LOCATIONEQUIPMENT
LOAD MCA VOLTS Ø PANELPOWERSOURCE
BREAKERSIZE FEEDER CONNECTION STARTER
DISCONNECTAT UNIT REMARKS
AC-1 AIR COOLED SPLIT CONDENSER LOADING DOCK ROOF 31750 W 39.4 A 600 V 3 M NORMAL 50A-3P 3#8 RW90 + BOND, 1" EMT DIRECT CONNECT - 60A 3R
ACC-1 WALK-IN COOLER AIR COOLED CONDENSING UNIT LOADING DOCK ROOF 2130 W 5.9 A 208 V 3 B3 NORMAL 15A-3P 3#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A 3R
AHU-1 AQUALAB AIR HANDLING UNIT EXTERIOR 26100 W 31.4 A 600 V 3 EDP EM. 35A-3P 3#10 RW90 + BOND, 3/4" EMT DIRECT CONNECT - - VFD AND INTERGRAL DISCONNECT BY MECHANICAL
AIR-1A OIL FREE SCROLL AIR COMPRESSOR STORAGE - B01 8718 W 30.3 A 208 V 3 SB EM. 60A-3P 3#8 RW90 + BOND, 1" EMT DIRECT CONNECT - 60A
AIR-1B OIL FREE SCROLL AIR COMPRESSOR STORAGE - B01 8718 W 30.3 A 208 V 3 B3 NORMAL 60A-3P 3#8 RW90 + BOND, 1" EMT DIRECT CONNECT - 60A
BS-1 BRANCH SELECTOR UNIT CORRIDOR - B00 90 W 0.4 A 208 V 1 B1 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
BS-2 BRANCH SELECTOR UNIT CORRIDOR - B00 90 W 0.4 A 208 V 1 B1 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
BS-4 BRANCH SELECTOR UNIT CORRIDOR - 100 35 W 0.1 A 208 V 1 F2 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
BS-5 BRANCH SELECTOR UNIT CORRIDOR - 100 35 W 0.1 A 208 V 1 F2 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
BS-9 BRANCH SELECTOR UNIT CORRIDOR - 200 90 W 0.4 A 208 V 1 S2 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
BS-10 BRANCH SELECTOR UNIT CORRIDOR - 200 35 W 0.1 A 208 V 1 S2 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
BS-11 BRANCH SELECTOR UNIT CORRIDOR - 200 35 W 0.1 A 208 V 1 S2 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2" EMT DIRECT CONNECT - 30A
BS-12 BRANCH SELECTOR UNIT CORRIDOR - 100 35 W 0.1 A 208 V 1 F2 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
BS-13 BRANCH SELECTOR UNIT CORRIDOR - 100 90 W 0.4 A 208 V 1 F2 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
BS-14 BRANCH SELECTOR UNIT CORRIDOR - 100 35 W 0.1 A 208 V 1 F2 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
CH-1A AIR COOLED CHILLER LOADING DOCK ROOF 28260 W 34.0 A 600 V 3 EDP EM. 40A-3P 3#8 RW90 + BOND, 1" EMT DIRECT CONNECT - - VFD AND INTERGRAL DISCONNECT BY MECHANICAL
CH-1B AIR COOLED CHILLER (FUTURE) LOADING DOCK ROOF 28260 W 34.0 A 600 V 3
CT-1 COOLING TOWER EXTERIOR 9351 W 11.3 A 600 V 3 PA NORMAL 20A-3P 3#12 RW90 + BOND, 3/4 EMT DIRECT CONNECT - - VFD AND INTERGRAL DISCONNECT BY MECHANICAL
CU-1A CONDENSER UNIT MECH./ELEC. ROOM - B18 8400 W 22.4 A 208 V 3 DPA NORMAL 30A-3P 3#10 RW90 + BOND, 3/4" EMT DIRECT CONNECT - 30A
CU-1B CONDENSER UNIT MECH./ELEC. ROOM - B18 8400 W 22.4 A 208 V 3 DPA NORMAL 30A-3P 3#10 RW90 + BOND, 3/4" EMT DIRECT CONNECT - 30A
CU-2A CONDENSER UNIT MECH./ELEC. ROOM - B18 8400 W 22.4 A 208 V 3 DPA NORMAL 30A-3P 3#10 RW90 + BOND, 3/4" EMT DIRECT CONNECT - 30A
CU-2B CONDENSER UNIT MECH./ELEC. ROOM - B18 8400 W 22.4 A 208 V 3 DPA NORMAL 30A-3P 3#10 RW90 + BOND, 3/4" EMT DIRECT CONNECT - 30A
CU-3A CONDENSER UNIT MECH./ELEC. ROOM - B18 8400 W 22.4 A 208 V 3 DPA NORMAL 30A-3P 3#10 RW90 + BOND, 3/4" EMT DIRECT CONNECT - 30A
CU-3B CONDENSER UNIT MECH./ELEC. ROOM - B18 8400 W 22.4 A 208 V 3 DPA NORMAL 30A-3P 3#10 RW90 + BOND, 3/4" EMT DIRECT CONNECT - 30A
DHWR-1 DOMESTIC HOT WATER RECIRC. PUMP MECH./ELEC. ROOM - B18 120 W 1.0 A 120 V 1 B3 NORMAL 15A-1P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT MMS -
DHWT-1 DOMESTIC HOT WATER TANK MECH./ELEC. ROOM - B18 3800 W 22.8 A 208 V 1 B3 NORMAL 25A-2P 2#10 RW90 + BOND, 3/4" EMT DIRECT CONNECT - 30A
EF-1 EXHAUST FAN ROOF 665 W 4.0 A 208 V 1 S2 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A 3R
EF-2 EXHAUST FAN ROOF 665 W 4.0 A 208 V 1 S2 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A 3R
EF-3 EXHAUST FAN MECHANICAL ROOM EXHAUST 1580 W 7.6 A 208 V 1 B3 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A 3R
EF-4 EXHAUST FAN MECHANICAL ROOM EXHAUST 665 W 4.0 A 208 V 1 S2 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A 3R
EF-5A EXHAUST FAN EXPERIMENT RM3 - B03D 24 W 0.2 A 120 V 1 B2 NORMAL 15A-1P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT MMS -
EF-5B EXHAUST FAN EXPERIMENT RM 4 - B03C 24 W 0.2 A 120 V 1 B2 NORMAL 15A-1P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT MMS -
EF-5C EXHAUST FAN EXPERIMENT RM 1 - B03A 24 W 0.2 A 120 V 1 B2 NORMAL 15A-1P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT MMS -
EF-5D EXHAUST FAN EXPERIMENT RM 2 - B03B 24 W 0.2 A 120 V 1 B2 NORMAL 15A-1P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT MMS -
EF-6 CEILING EXHAUST FAN CHN ANALYZER ROOM B11 24 W 0.2 A 120 V 1 B3 NORMAL 15A-1P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT MMS -
ERV-1 ENERGY RECOVERY VENTILATOR STORAGE - B07 72 W 0.6 A 120 V 1 B3 NORMAL 15A-1P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT MS 30A
ESP-1 ELEVATOR SUMP PUMP BIOHAZARD ROOM - B08 1176 W 12.3 A 120 V 1 SB EM. 20A-1P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT MMS -
EV-1 WALK-IN COOLER EVAPORATOR WALK-IN COOLER - B09 300 W 2.3 A 120 V 1 B3 NORMAL 15A-1P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
FC-1 HORIZ. CLG. FAN COIL UNIT - SIZE 36 FACULTY OFFICE - 207 483 W 2.9 A 208 V 1 S1 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
FC-2 HORIZ. CLG. FAN COIL UNIT - SIZE 30 FLEX INOVATION LAB - 211 466 W 2.8 A 208 V 1 S1 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
FC-3 HORIZ. CLG. FAN COIL UNIT - SIZE 36 FACULTY OFFICE - 201 483 W 2.9 A 208 V 1 S2 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
FC-4 HORIZ. CLG. FAN COIL UNIT - SIZE 36 FACULTY OFFICE - 205 483 W 2.9 A 208 V 1 S2 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
FC-5 HORIZ. CLG. FAN COIL UNIT - SIZE 15 CORRIDOR - 200 250 W 1.5 A 208 V 1 S1 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
FC-6 HORIZ. CLG. FAN COIL UNIT - SIZE 15 CORRIDOR - 200 250 W 1.5 A 208 V 1 S2 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
FC-7 HORIZ. CLG. FAN COIL UNIT - SIZE 15 CORRIDOR - 200 250 W 1.5 A 208 V 1 S1 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
FC-9 HORIZ. CLG. FAN COIL UNIT - SIZE 36 EQUIPMENT RM - 203B 483 W 2.9 A 208 V 1 S2 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
FC-11 HORIZ. CLG. FAN COIL UNIT - SIZE 09 TECH OFFICE - B05 100 W 0.6 A 208 V 1 F1 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
FC-12 HORIZ. CLG. FAN COIL UNIT - SIZE 09 FACULTY OFFICE - 105 100 W 0.6 A 208 V 1 F1 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
FC-13 HORIZ. CLG. FAN COIL UNIT - SIZE 48 INCUBATOR / FREEZER ROOM - 107C 566 W 3.4 A 208 V 1 F1 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
FC-14 HORIZ. CLG. FAN COIL UNIT - SIZE 24 PHYTO LAB - 107 300 W 1.8 A 208 V 1 F1 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
FC-15 HORIZ. CLG. FAN COIL UNIT - SIZE 09 FACULTY OFFICE - 109 100 W 0.6 A 208 V 1 F1 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
FC-16 HORIZ. CLG. FAN COIL UNIT - SIZE 12 NORTH STAIR - ST1-1 232 W 1.4 A 208 V 1 F2 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
FC-17 HORIZ. CLG. FAN COIL UNIT - SIZE 12 NORTH STAIR - ST1-1 232 W 1.4 A 208 V 1 F2 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
FC-18 HORIZ. CLG. FAN COIL UNIT - SIZE 24 PHYTO. ECO LAB - 101 300 W 1.8 A 208 V 1 F2 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
FC-19 HORIZ. CLG. FAN COIL UNIT - SIZE 48 INCUBATOR / FREEZER ROOM - 101B 566 W 3.4 A 208 V 1 F2 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
FC-20 HORIZ. CLG. FAN COIL UNIT - SIZE 09 FACULTY OFFICE - 103 100 W 0.6 A 208 V 1 F2 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
FC-21 HORIZ. CLG. FAN COIL UNIT - SIZE 09 CORRIDOR - 100 100 W 0.6 A 208 V 1 F2 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
FC-23 HORIZ. CLG. FAN COIL UNIT - SIZE 18 FISH LAB - B13 266 W 1.6 A 208 V 1 F1 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
FC-24 HORIZ. CLG. FAN COIL UNIT - SIZE 07 CORRIDOR - 100 100 W 0.6 A 208 V 1 F1 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
FC-25 CASSETTE FAN COIL UNIT - SIZE 09 NORTH STAIR - ST1-B 133 W 0.8 A 208 V 1 F1 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
FC-26 HORIZ. CLG. FAN COIL UNIT - SIZE 09 PHYTO LAB - 101 100 W 0.6 A 208 V 1 F2 NORMAL 15A-2P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
FE-1 LAB FAN EXHAUST c/w ECONOMIZER ROOF 22860 W 40.0 A 600 V 3 EDP EM. 40A-3P 3#8 RW90 + BOND, 1" EMT DIRECT CONNECT - - VFD AND INTERGRAL DISCONNECT BY MECHANICAL
FH-1 FUME HOOD - EQ27c FISH BIOCHEM. & NANO. LAB - B13 1200 W 10.0 A 120 V 1 B1 NORMAL 20A-1P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - - WIRE TO SINGLE POINT CONNECTION
FH-2 FUME HOOD - EQ27a PHYTO LAB - 107 1200 W 10.0 A 120 V 1 F1 NORMAL 20A-1P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - - WIRE TO SINGLE POINT CONNECTION
FH-3 FUME HOOD - EQ27d FLEX INOVATION LAB - 211 1200 W 10.0 A 120 V 1 S1 NORMAL 20A-1P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - - WIRE TO SINGLE POINT CONNECTION
FH-4 FUME HOOD - EQ27b PHYTO LAB - 101 1200 W 10.0 A 120 V 1 F2 NORMAL 20A-1P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - - WIRE TO SINGLE POINT CONNECTION
FH-5 FUME HOOD - EQ27e MOLEC. BIO LAB - 203-1 1200 W 10.0 A 120 V 1 S2 NORMAL 20A-1P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - - WIRE TO SINGLE POINT CONNECTION
GT-1 GLYCOL FILL TANK MECH./ELEC. ROOM - B18 60 W 0.5 A 120 V 1 B3 NORMAL 15A-1P 2#12 RW90 + BOND, 1/2 EMT 15/20A DUPLEX REC. - -
GT-3 GLYCOL FILL TANK MECHANICAL ROOM - 302 60 W 0.5 A 120 V 1 S1 NORMAL 15A-1P 2#12 RW90 + BOND, 1/2 EMT 15/20A DUPLEX REC. - -
GT-4 GLYCOL FILL TANK MECHANICAL ROOM - 302 60 W 0.5 A 120 V 1 S1 NORMAL 15A-1P 2#12 RW90 + BOND, 1/2 EMT 15/20A DUPLEX REC. - -
GT-5 GLYCOL FILL TANK MECHANICAL ROOM - 302 60 W 0.5 A 120 V 1 S1 NORMAL 15A-1P 2#12 RW90 + BOND, 1/2 EMT 15/20A DUPLEX REC. - -
HUM-1 STEAM HUMIDIFIER MECHANICAL ROOM - 302 1200 W 10.0 A 120 V 1 S2 NORMAL 15A-1P 2#12 RW90 + BOND, 1/2 EMT DIRECT CONNECT - 30A
MUA-1 ROOFTOP PACKAGED MAKE-UP AIR UNIT ROOF 10390 W 10.0 A 600 V 3 EDP EM. 30A-3P 3#12 RW90 + BOND, 3/4 EMT DIRECT CONNECT - - VFD AND INTERGRAL DISCONNECT BY MECHANICAL
P-1A WSHP LOOP PUMP MECH./ELEC. ROOM - B18 6338 W 7.6 A 600 V 3 PA NORMAL 15A-3P 3#12 RW90 + BOND, 3/4" EMT DIRECT CONNECT HOA - VFD AND INTERGRAL DISCONNECT BY MECHANICAL
P-1B WSHP LOOP PUMP MECH./ELEC. ROOM - B18 6338 W 7.6 A 600 V 3 PA NORMAL 15A-3P 3#12 RW90 + BOND, 3/4" EMT DIRECT CONNECT HOA - VFD AND INTERGRAL DISCONNECT BY MECHANICAL
P-2A COOLING TOWER PUMP MECH./ELEC. ROOM - B18 6338 W 7.6 A 600 V 3 PA NORMAL 15A-3P 3#12 RW90 + BOND, 3/4" EMT DIRECT CONNECT HOA - VFD AND INTERGRAL DISCONNECT BY MECHANICAL
P-2B COOLING TOWER PUMP MECH./ELEC. ROOM - B18 6338 W 7.6 A 600 V 3 PA NORMAL 15A-3P 3#12 RW90 + BOND, 3/4" EMT DIRECT CONNECT HOA - VFD AND INTERGRAL DISCONNECT BY MECHANICAL
P-3A MUA-1 HEATING COIL PUMP MECHANICAL ROOM - 302 4052 W 4.9 A 600 V 3 EDP EM. 15A-3P 3#12 RW90 + BOND, 3/4" EMT DIRECT CONNECT HOA - VFD AND INTERGRAL DISCONNECT BY MECHANICAL
P-3B MUA-1 HEATING COIL PUMP MECHANICAL ROOM - 302 4052 W 4.9 A 600 V 3 EDP EM. 15A-3P 3#12 RW90 + BOND, 3/4" EMT DIRECT CONNECT HOA - VFD AND INTERGRAL DISCONNECT BY MECHANICAL
P-4A AQUALAB TANK HEATING PUMP MECHANICAL ROOM - 302 6338 W 7.6 A 600 V 3 EDP EM. 15A-3P 3#12 RW90 + BOND, 3/4" EMT DIRECT CONNECT HOA - VFD AND INTERGRAL DISCONNECT BY MECHANICAL
P-4B AQUALAB TANK HEATING PUMP MECHANICAL ROOM - 302 6338 W 7.6 A 600 V 3 EDP EM. 15A-3P 3#12 RW90 + BOND, 3/4" EMT DIRECT CONNECT HOA - VFD AND INTERGRAL DISCONNECT BY MECHANICAL
P-5A FE/MUA HEAT RECOVERY PUMP MECHANICAL ROOM - 302 2805 W 3.4 A 600 V 3 M NORMAL 15A-3P 3#12 RW90 + BOND, 3/4" EMT DIRECT CONNECT HOA - VFD AND INTERGRAL DISCONNECT BY MECHANICAL
P-5B FE/MUA HEAT RECOVERY PUMP MECHANICAL ROOM - 302 2805 W 3.4 A 600 V 3 M NORMAL 15A-3P 3#12 RW90 + BOND, 3/4" EMT DIRECT CONNECT HOA - VFD AND INTERGRAL DISCONNECT BY MECHANICAL
P-6A AQUALAB TANK CHILLER PUMP MECH./ELEC. ROOM - B18 6338 W 7.6 A 600 V 3 EDP EM. 15A-3P 3#12 RW90 + BOND, 3/4" EMT DIRECT CONNECT HOA - VFD AND INTERGRAL DISCONNECT BY MECHANICAL
P-6B AQUALAB TANK CHILLER PUMP MECH./ELEC. ROOM - B18 6338 W 7.6 A 600 V 3 EDP EM. 15A-3P 3#12 RW90 + BOND, 3/4" EMT DIRECT CONNECT HOA - VFD AND INTERGRAL DISCONNECT BY MECHANICAL
P-7A OWEN'S HEATING PUMP MECH./ELEC. ROOM - B18 2805 W 3.4 A 600 V 3 EDP EM. 15A-3P 3#12 RW90 + BOND, 3/4" EMT DIRECT CONNECT HOA - VFD AND INTERGRAL DISCONNECT BY MECHANICAL
P-7B OWEN'S HEATING PUMP MECH./ELEC. ROOM - B18 2805 W 3.4 A 600 V 3 EDP EM. 15A-3P 3#12 RW90 + BOND, 3/4" EMT DIRECT CONNECT HOA - VFD AND INTERGRAL DISCONNECT BY MECHANICAL
SWTP-1 SALT WATER TANK PUMP BIOHAZARD ROOM - B07 2880 W 17.3 A 208 V 1 B3 NORMAL 30A-2P 2#10 RW90 + BOND, 3/4" EMT DIRECT CONNECT HOA -
WP-1 SUBMERSIBLE WELL PUMP BIOHAZARD ROOM - B07 3816 W 13.3 A 208 V 3 DPA NORMAL 25A-3P 3#10 RW90 + BOND, 3/4" EMT DIRECT CONNECT HOA -
NOTES:
1.MS = MANUAL TYPE MOTOR STARTER
C/W OVERLOAD PROTECTIONMMS = MOTOR RATED SWITCHNCM = NON-COMBINATION MAGNETICFVNR = FULL VOLTAGE NON-REVERSINGRVNR = REDUCED VOLTAGE NON-REVERSING
HOA = COMBINATION MAGNETIC STARTER/NON-FUSEDDISCONNECT C/W HAND/OFF/AUTO SELECTOR SWITCH
CMB = COMBINATION MAGNETIC STARTER C/W FUSEDCONTROL TANSFORMER
VSD = VARIABLE SPEED DRIVE, BY DIV. 15/25NCHOA =NON-COMBINATION MAGNETIC STARTER C/W
HAND/OFF/AUTO SELECTOR SWITCH
STARTER LEGEND
Mar. 23, 2017