a novel thÉvenin-based oltage droop control ... raghami...a novel thévenin-based voltage droop...

135
A NOVEL THÉVENIN-BASED VOLTAGE DROOP CONTROL IMPROVING REACTIVE POWER SHARING WITH STRUCTURES TO IDENTIFY THÉVENIN PARAMETERS Alireza Raghami BS.c. and MS.c. in Electrical Engineering A Thesis Submitted in fulfilment of the requirements for the degree of Doctor of Philosophy Science and Engineering Faculty School of Electrical Engineering and Computer Science Queensland University of Technology Queensland, Australia 2019

Upload: others

Post on 02-Feb-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

  • A NOVEL THÉVENIN-BASED VOLTAGE

    DROOP CONTROL IMPROVING REACTIVE

    POWER SHARING WITH STRUCTURES TO

    IDENTIFY THÉVENIN PARAMETERS

    Alireza Raghami

    BS.c. and MS.c. in Electrical Engineering

    A Thesis Submitted in fulfilment of the requirements for the degree of

    Doctor of Philosophy

    Science and Engineering Faculty

    School of Electrical Engineering and Computer Science

    Queensland University of Technology

    Queensland, Australia

    2019

  • A Novel Thévenin-Based Voltage Droop Control Improving Reactive Power Sharing with Structures to Identify

    Thévenin Parameters i

    Keywords

    Correlation

    Customers’ inverters

    Distribution system’s identification

    Identification through power lines

    Reactive power sharing

    Real-time identification

    Residential load

    Thévenin parameters identification

    Voltage droop control

  • A Novel Thévenin-Based Voltage Droop Control Improving Reactive Power Sharing with Structures to Identify

    Thévenin Parameters ii

    Abstract

    The prevalent radial configuration of distribution systems and changes in

    customer load have made serious voltage magnitude issues concerning the operation

    of these systems. The voltage issues relating to urban low voltage systems with a

    relatively reactive impedance can be handled by reactive power compensation.

    Handling these voltage issues is an increasingly challenging problem. Insufficient

    reactive power sources, lack of flexibility in the existing sources and their control are

    some of the major problems.

    However, a growing number of photovoltaic/battery inverter systems with

    reactive power capability creates an opportunity to accurately meet the reactive power

    compensation needs. On the one hand, some utilities are providing local compensation

    at inverters installation points and many researchers are investigating distributed droop

    based voltage control strategies. On the other hand, the cost-effectiveness of the local

    compensation may concern individual customers about getting involved for reactive

    power support. One of the major concerns is the relative amount of support provided

    by each customer.

    In fact, when inverters are coordinated using the conventional droop control

    strategies, their reactive power contributions could be adversely affected by their

    positions. This positioning is the relative distance of each inverter from the power

    transformer connecting the feeder to the higher voltage system. This drawback is

    investigated in this thesis. Critical elements that can impede an even provision of

    reactive power support are diagnosed. Elements of the Thévenin equivalent circuit

    model are used to systematically develop a novel droop control strategy improving the

    reactive power sharing. Identification of Thévenin equivalent circuit parameters is then

    required.

    However, the real-time Thévenin parameters identification through power lines

    is not a straightforward task. Challenges are detailed regarding the status of loads and

    inverters and some innovative solutions are provided. Different scenarios are studied

    from the uncompensated conventional systems with ideally unchanged loads to the

    voltage compensated systems with continual demand variations. Some statistical and

  • A Novel Thévenin-Based Voltage Droop Control Improving Reactive Power Sharing with Structures to Identify

    Thévenin Parameters iii

    non-statistical approaches are proposed to enable inverters for this challenging

    identification task.

    Results show that voltage magnitude is regulated through an even distribution of

    reactive power compensation among customers’ inverters using the proposed

    Thévenin based droop control. Each droop controller is regularly adjusted via the real-

    time Thévenin identification in a fundamentally local process. The statistical and the

    non-statistical-based identification approaches are assessed based on locally

    measurable metrics of performance.

  • A Novel Thévenin-Based Voltage Droop Control Improving Reactive Power Sharing with Structures to Identify

    Thévenin Parameters iv

    Table of Contents

    Keywords .................................................................................................................................. i

    Abstract .................................................................................................................................... ii

    Table of Contents .................................................................................................................... iv

    List of Figures ........................................................................................................................ vii

    List of Tables ............................................................................................................................ x

    Statement of Original Authorship ........................................................................................... xi

    Acknowledgements ................................................................................................................ xii

    Publications Arising from the Thesis .................................................................................... xiii

    Chapter 1: Introduction ...................................................................................... 1

    1.1 Background .................................................................................................................... 1

    1.2 Aims and Objectives of the Thesis ................................................................................. 2

    1.3 Significance of the Research .......................................................................................... 2

    1.4 Key Contributions of this Research ............................................................................... 3

    1.5 Thesis Outline ................................................................................................................ 4

    Chapter 2: Literature Review ............................................................................. 7

    2.1 Phasor Analysis and Thévenin Equivalent Circuit ......................................................... 7

    2.2 Norton Equivalent Circuit ............................................................................................ 11

    2.3 Significance of Thévenin Equivalent Circuit in Power System Studies ...................... 12

    2.4 Typical Power Elements Connected to an Inverter ...................................................... 13

    2.5 A Typical Hierarchical Control for an Inverter ............................................................ 13 2.5.1 Tertiary Control ................................................................................................. 14 2.5.2 Secondary Control ............................................................................................. 15 2.5.3 Synchronisation of Inverters .............................................................................. 16 2.5.4 Primary Control and Basics of Droop Control .................................................. 17

    2.6 Advantages, Limitations and Variations of the Conventional Droop .......................... 21

    2.7 Adaptiveness of Droop ................................................................................................. 22

    2.8 Summary and Implications .......................................................................................... 24

    Chapter 3: Signal Processing Concepts Relevant to Local Identification Problems .......................................................................................................... 27

    3.1 Overview ...................................................................................................................... 27

    3.2 Signal Processing Basics Required for Understanding of a Local Identification ........ 27 3.2.1 Continuous and Discrete Random Process ........................................................ 27 3.2.2 Deterministic and Nondeterministic Random Process....................................... 29 3.2.3 Expected Value and Stationarity ........................................................................ 29 3.2.4 Time Average and Ergodicity ............................................................................ 30 3.2.5 Statistical Concepts for Discrete-Time Processes .............................................. 31 3.2.6 Orthogonality ..................................................................................................... 32 3.2.7 Signal to Noise Ratio ......................................................................................... 33

  • A Novel Thévenin-Based Voltage Droop Control Improving Reactive Power Sharing with Structures to Identify

    Thévenin Parameters v

    3.2.8 Crest Factor ........................................................................................................33 3.2.9 Continuous Uniform and Normal Distributions .................................................34 3.2.10 White Noise ........................................................................................................35 3.2.11 Random Walk .....................................................................................................36

    3.3 Mathematical Framework and Possible Solutions to a Multiple Access Problem .......36 3.3.1 Ordinary Least Squares Estimation and Pseudo-Inverse Estimator ...................37 3.3.2 Properly Posed and Well-Conditioned Problems ...............................................38 3.3.3 FDMA ................................................................................................................40 3.3.4 TDMA ................................................................................................................40 3.3.5 CDMA ................................................................................................................41

    3.4 Orthogonal Functions and Their Properties ..................................................................42 3.4.1 Walsh Functions .................................................................................................43 3.4.2 Application of Walsh Functions .........................................................................46 3.4.3 An Example of Walsh Based CDMA Multiple Access Problem .......................48

    3.5 Nature of Variation of Loads in Distribution Systems .................................................49

    3.6 Applications of the Signal Processing Concepts for Identification Problems in Power Engineering .............................................................................................................................52

    3.7 Summary and Implications ...........................................................................................55

    Chapter 4: A Novel Thévenin-Based Voltage Droop Control Improving Reactive Power Sharing with Structures to Learn Thévenin Parameters.......... 57

    4.1 Overview ......................................................................................................................57

    4.2 Proposed Adaptive Droop Control Strategy .................................................................58

    4.3 Proposed Load-Based Thévenin Identification Strategies ............................................61 4.3.1 Thévenin Parameters Identification in Ideally No Noise Condition ..................64 4.3.2 Thévenin Parameters Identification in Conventional Distribution Systems .......65

    4.4 Proposed Inverter-Based Thévenin Identification Strategies .......................................70 4.4.1 Walsh-Based Identification Strategies in a Highly Reactive System .................70 4.4.2 Practicality Challenges of Simultaneous Walsh-Based Identification ...............74 4.4.3 Identification Strategies in an Uncompensated Distribution System .................75 4.4.4 Identification Strategies in Droop Compensated Systems .................................77

    4.5 Synopsis of the Proposals .............................................................................................80

    Chapter 5: Results and Discussion ................................................................... 82

    5.1 Voltage Control via the Conventional Droop Strategy .................................................82

    5.2 Correlation ....................................................................................................................84

    5.3 SNR ..............................................................................................................................87

    5.4 The Proposed Voltage Droop Control with the Identification Structures .....................89 5.4.1 Significance of Lower Correlation .....................................................................92 5.4.2 Significance of Higher SNR ...............................................................................95 5.4.3 Significance of Lower Numerical Sensitivity ....................................................96 5.4.4 Significance of More Controlled Droop Dynamics ............................................97

    5.5 Crest Factor .................................................................................................................101

    5.6 Summary .....................................................................................................................106

    Chapter 6: Conclusions and Recommendation ............................................. 109

    6.1 Conclusions ................................................................................................................109

    6.2 Recommendations for Future Research ......................................................................113

  • A Novel Thévenin-Based Voltage Droop Control Improving Reactive Power Sharing with Structures to Identify

    Thévenin Parameters vi

    Bibliography ........................................................................................................... 114

  • A Novel Thévenin-Based Voltage Droop Control Improving Reactive Power Sharing with Structures to Identify

    Thévenin Parameters vii

    List of Figures

    Figure 2.1. Circuits’ energy storing elements with the graphical voltage-current

    relationship in the complex phasor and the time domain planes ................... 8

    Figure 2.2. Schematic of the first method of Thévenin impedance derivation .......... 10

    Figure 2.3. Norton equivalent circuit of the Thévenin equivalent in Figure 2.2 ....... 11

    Figure 2.4. n-bus radial feeder connected to the voltage robust main grid ............... 11

    Figure 2.5. One configuration of power elements connected to a PV module .......... 13

    Figure 2.6. A typical hierarchical control strategy implemented to coordinate

    the inverters of a microgrid (a) tertiary control and secondary control

    (b) secondary control and primary control................................................... 14

    Figure 2.7. A current source grid supporting inverter controlled by the primary

    level .............................................................................................................. 18

    Figure 2.8. (a) Schematic of a voltage droop controlled current source grid

    supporting inverter (b) simplified presentation of the schematic ................ 19

    Figure 2.9. (a) Configuration of a typical n bus modern radial feeder with

    customers having loads and PV/battery inverter systems (b) Circuit

    model of the ith droop-controlled inverter connected to the system’s

    Thévenin equivalent ..................................................................................... 19

    Figure 2.10. Voltage reactive current droop characteristic........................................ 20

    Figure 2.11. (a) Norton descriptor and (b) Thévenin descriptor of an inverter

    managed by the droop control characterised in (2.13) ................................. 21

    Figure 3.1. A continuous random process ................................................................. 28

    Figure 3.2. A discrete-time random process (or a continuous random sequence)

    formed by sampling the waveforms of Figure 3.1 ....................................... 29

    Figure 3.3. PDFs of zero-mean normal distribution (the bell-shape solid curve)

    versus zero-mean uniform distribution of the same variance (the

    dotted rectangle)........................................................................................... 35

    Figure 3.4. Auto-correlation of a white noise process ............................................... 36

    Figure 3.5. Dimensions of two widely applied multiple access techniques .............. 41

    Figure 3.6. CDMA dimensions .................................................................................. 41

    Figure 3.7. Walsh function ensemble of length eight ................................................ 44

    Figure 3.8. Superimposition of a Walsh ensemble and sine-cosine function ............ 46

    Figure 3.9. Extraction of Walsh codes employed by two CDMA terminals ............. 48

    Figure 3.10. The sent messages with the reconstructed messages ............................ 49

    Figure 4.1. (a) Vector diagram of the circuit in Figure 2.9 (b) in a common

    reference frame (b) Magnified components of the voltage change ............. 59

  • A Novel Thévenin-Based Voltage Droop Control Improving Reactive Power Sharing with Structures to Identify

    Thévenin Parameters viii

    Figure 4.2. Effective equivalent circuit model of the system connected to a

    droop controlled inverter .............................................................................. 59

    Figure 4.3. Newmarket pilot smart grid geographical map ....................................... 61

    Figure 4.4. Cross-correlation of demand changes of the neighbours’ loads (a)

    Five randomly selected customers (b) Twenty five randomly selected

    customers ..................................................................................................... 63

    Figure 4.5. Circuit model of the network as seen from ith customer viewpoint

    connected to an unchanged system .............................................................. 64

    Figure 4.6. Circuit model of the network as seen from ith customer viewpoint

    in a conventional distribution system ........................................................... 65

    Figure 4.7. Circuit model of the network as seen from the viewpoint of ith

    customer’s passive inverter .......................................................................... 70

    Figure 4.8. Flowchart of the proposed Walsh-based Thévenin parameters

    identification structure from the viewpoint of ith passive inverter .............. 73

    Figure 4.9. Interference limitation in CDMA exemplified for Walsh-based

    identification of inverters of different probing power ................................. 74

    Figure 4.10. (a) Thévenin equivalent of the network from the perspective of ith

    active inverter, (b) Thévenin equivalent of the network obtainable by

    probing of ith inverter .................................................................................. 78

    Figure 4.11. The control strategy flowchart from the perspective of ith inverter ...... 80

    Figure 5.1. Single-line diagram of IEEE 33-bus system ........................................... 82

    Figure 5.2. Contoured reactive power contribution (p.u.×100) of the inverters

    coordinated by the conventional voltage droop strategy ............................. 84

    Figure 5.3. Magnitude change correlation between the inverter at bus 28 and

    some of the neighbour inverters: (a) droop, (b) Walsh-based probing

    (c) normal distribution-based probing (d) uniform distribution-based

    probing ......................................................................................................... 86

    Figure 5.4. Voltage compensation via the novel droop with Walsh based-

    identification (a) Inverters’ total current (b) Bus voltage (c) Identified

    Thévenin source magnitude (d) Identified system’s Thévenin

    reactance ....................................................................................................... 91

    Figure 5.5. Length-32 Walsh-based probing (a) Identified Thévenin source

    magnitude (b) Identified system’s Thévenin reactance ............................... 93

    Figure 5.6. Neglecting a part of Walsh codes in Walsh-based probing (a)

    Identified Thévenin source magnitude (b) Identified system’s

    Thévenin reactance ...................................................................................... 94

    Figure 5.7. Neglecting the processing gain and synthesising single

    measurement for each observation (a) Identified Thévenin source

    magnitude (b) Identified system’s Thévenin reactance ............................... 95

    Figure 5.8. Neglecting the numerical properties in this low-level probing

    identification problem (a) Identified Thévenin source magnitude (b)

    Identified system’s Thévenin reactance ....................................................... 97

  • A Novel Thévenin-Based Voltage Droop Control Improving Reactive Power Sharing with Structures to Identify

    Thévenin Parameters ix

    Figure 5.9. System operated using the novel Thévenin droop without LPF (a)

    Inverters’ total current (b) Bus voltage ........................................................ 98

    Figure 5.10. Voltage compensation via the novel droop with normal

    distribution based-identification (a) Inverters’ total current (b) Bus

    voltage (c) Identified Thévenin source magnitude (d) Identified

    system’s Thévenin reactance ....................................................................... 99

    Figure 5.11. Voltage compensation via the novel droop with uniform

    distribution based-identification (a) Inverters’ total current (b) Bus

    voltage (c) Identified Thévenin source magnitude (d) Identified

    system’s Thévenin reactance ..................................................................... 100

    Figure 5.12. Voltage perturbation crest factor from sequential probing to

    simultaneous probing ................................................................................. 104

    Figure 5.13. Zoomed voltage perturbation at buses 15, 31 and 33 (a) Walsh

    probing (b) Normal probing (c) Uniform probing ..................................... 105

  • A Novel Thévenin-Based Voltage Droop Control Improving Reactive Power Sharing with Structures to Identify

    Thévenin Parameters x

    List of Tables

    Table 2.1 Summary of some of the shortcomings of droop-based control

    strategies and the solutions .......................................................................... 22

    Table 4.1 Different Thévenin parameters identification scenarios based on the

    status of customers’ equipment and identification principle ....................... 64

    Table 5.1 Electrical parameters of the adopted 12.66 kV cable ................................. 83

    Table 5.2 Walsh sequency allocation ......................................................................... 85

    Table 5.3 Parameters of zero-mean probing with the same energy density ............... 87

    Table 5.4 SNRs of single measurement-single observation ....................................... 88

    Table 5.5 SNRs of five samples-single observation .................................................. 89

    Table 5.6 Settings of the novel control strategy ......................................................... 90

    Table 5.7 Voltage perturbation crest factor in sequential probing ........................... 102

    Table 5.8 Voltage perturbation crest factor from sequential probing to

    simultaneous probing ................................................................................. 103

    Table 5.9 Current crest factor ................................................................................... 106

  • A Novel Thévenin-Based Voltage Droop Control Improving Reactive Power Sharing with Structures to Identify

    Thévenin Parameters xi

    Statement of Original Authorship

    The work contained in this thesis has not been previously submitted to meet

    requirements for an award at this or any other higher education institution. To the best

    of my knowledge and belief, the thesis contains no material previously published or

    written by another person except where due reference is made.

    Signature:

    Date: June 2019

    QUT Verified Signature

  • A Novel Thévenin-Based Voltage Droop Control Improving Reactive Power Sharing with Structures to Identify

    Thévenin Parameters xii

    Acknowledgements

    I wish to express my deepest gratitude to my principal supervisor, Professor

    Gerard Ledwich, for guiding me through this research and also teaching me valuable

    life lessons. I also extend my appreciation to my associate supervisor, Dr. Yateendra

    Mishra, for his support and advice during my PhD.

    I convey my special thanks to the QUT power engineering discipline leader

    Associate Professor Geoff Walker for his unwavering support. I also would like to

    thank the discipline coordinator, Dr. Adriana Bondarova, QUT EECS school librarian

    liaison, Mr. Graham Dawson, QUT Research Student Centre staff members, Ms.

    Janelle Fenner and Ms. Judy Liu, EECS staff members, Mrs. Joanne Kelly, Ms. Joanne

    Reaves and Ms. Ellainne Steele. I wish to thank all the academics and non-academic

    staff from our discipline and outside of the discipline at QUT who have assisted me in

    undertaking this research in different ways and creating a supportive environment

    during undertaking this PhD.

    I would like to sincerely thank QUT for providing scholarships to undertake this

    PhD. Also, I would gratefully acknowledge Energex, South East Queensland power

    distribution company for providing a set of data from their Newmarket pilot smart grid

    used in this research study.

    Last but not least, I cannot thank enough my sister, Farnaz, my mom, Parveen

    and my father, Yahya for their unconditional support and self-less love without them

    accomplishing this PhD study was impossible.

  • A Novel Thévenin-Based Voltage Droop Control Improving Reactive Power Sharing with Structures to Identify

    Thévenin Parameters xiii

    Publications Arising From the Thesis

    Journal papers

    1. A. Raghami, G. Ledwich and Y. Mishra "Improved reactive power sharing among customers’ inverters using online Thévenin estimates” Accepted for

    publication at IEEE Transactions on Power Systems, DOI:

    10.1109/TPWRS.2019.2918312 (Received great feedback from the reviewers,

    2017 Journal Impact Factor 5.255, H index 205, Review citation median 26)

    2. A. Raghami, et al. "Designing power-frequency probing for simultaneous identification of Thévenin parameters of residential distribution systems” (In

    preparation for submission to IEEE Transactions on Power Systems)

    Conference papers

    3. A. Raghami, G. Ledwich, and Y. Mishra, "Improved reactive power sharing among photovoltaic inverters using Tévenin's impedance based approach"

    presented at IEEE Power & Energy Society General Meeting, 2017, pp. 1-5

    (Awarded, power engineering flagship conference).

    4. A. Raghami, et al. " Simultaneous Demand-Based Identification of the Power

    System’s Thévenin Equivalent” (Ready for submission to IEEE Power &

    Energy Society General Meeting)

  • Chapter 1: Introduction 1

    Chapter 1: Introduction

    This chapter lays out the context of this research and its significance in relation

    to the analysis of the state-of-the-art electrical distribution systems. It brings the great

    potential of customer’s inverters for voltage compensation into the spotlight. Initially,

    a brief background to this research is given in which the research context is framed. It

    is followed by putting forward the research purposes. After that, the importance of the

    research is highlighted. The final section gives an outline of the remainder of the thesis.

    1.1 Background

    A regulated voltage magnitude has always been an important requirement in the

    power quality context [1]. Increasing on-site renewable generation and proliferation of

    sensitive loads are nascent driving forces that have heightened the concern over the

    voltage magnitude regulation [1]. On the one hand, renewable power intermittency on

    a daily cycle causes continual voltage magnitude fluctuation. On the other hand, more

    strict voltage regulation is required by a growing number of more sensitive loads (e.g.

    households’ air-conditioning systems and personal computers). These conflicting

    forces have recently caused momentary outages in some utilities [2].

    Voltage dip/sag typically happens in relatively long radial distribution branches

    during peak hours. The edge of the systems experiences the largest voltage variations.

    It has conventionally been the utilities’ responsibility to mitigate any violation of

    voltage standards otherwise malfunction of customers’ devices would be likely [3].

    Traditionally, systems have been reinforced in overhaul phases by replacing the

    existing cables with ones having a higher ampacity or by manual adjustment of the

    transformers’ taps [1]. Installation of switched capacitors has also been practised

    which could adequately meet the voltage regulation needs for slow variation of

    demand. However, the latter falls short handling today’s highly dynamic systems.

    Dynamic transformer tapping has alternatively been employed. Strategies have been

    investigated to set on-load tap changer according to instantaneous network

    information. However not only these strategies lead to hunting effect but also they are

    possibly too complex and communication intensive to be reliable for distribution

    systems’ application [4, 5]. DSTATCOMs have also been recently installed at some

  • Chapter 1: Introduction 2

    low and medium voltage distribution systems at a considerable overhead cost of

    installation. DSTATCOMs can address a range of power quality issues including

    voltage magnitude regulation. However not only are they expensive devices but also

    their controllers are highly complex [6, 7].

    A growing penetration of rooftop solar and battery inverter systems can be an

    asset to the system when controlled properly [8]. Fast response and high accuracy of

    these inverters are the key factors to differentiate between assets that help versus assets

    that hurt the system. Since switching losses of state-of-the-art inverters are limited,

    reactive power can be provided almost energy source free by the inverters. In addition

    to that, a slight increase in inverter size gives a substantial reactive power capability.

    All the preceding advantages have led to worldwide attention to the potential of

    reactive power support from customers’ inverter interfaced equipment [9-11].

    1.2 Aims and Objectives of the Thesis

    The following items are elaborated as the key objectives of this research:

    1. Development of a novel droop control strategy to compensate voltage while

    improving reactive power sharing among inverters

    2. Development of online strategies to robustly identify the elements of the

    system’s Thévenin equivalent from a customer’s inverter perspective using

    power lines at power frequency

    1.3 Significance of the Research

    Today’s electric power-hungry world is continually asking for higher power

    quality. Increasing number of customers’ inverters is not a power quality problem per

    se. When these inverters are managed appropriately, their advantages far outweigh the

    challenges they pose to the system. In other words, inverters can facilitate building

    grids with an improved power quality [2, 11, 12].

    Energy saving and the associated bill reduction benefits of photovoltaic/battery

    inverter systems have already been exploited widely [13]. Cutting the carbon emission

    and reducing the reliance on the main grid support also encourage some customers to

    adopt inverter-based renewable-centric local generations [14]. These inverters have

    been mostly operated according to a unity power factor strategy. This conservative

    strategy has worsened the voltage problems at some locations [9]. Although customers

  • Chapter 1: Introduction 3

    are satisfied in this fashion as long as they don’t see any malfunction in their home

    appliances, utilities have to deal with the pressing voltage regulation need to avoid the

    likely malfunction. On the one hand, operation at unity power factor is required by

    some utilities and on the other hand, the same utilities have to regulate the voltage

    magnitude at an overhead cost of grids’ upgrade in overhaul phases.

    Power system experts are unanimous about the advantages of local voltage

    compensation [15]. These broad advantages come under the umbrella of higher

    efficiency and improved performance of the system assets since the local solutions

    avert involvement of voltage compensators of the neighbouring distribution systems

    and upper grids [16]. Inspired by the preceding benefits and realised the potentials of

    the customers’ inverters, some utility companies have initialised voltage control at

    inverters installation points [9, 17].

    There are also strong arguments in favour of coordination of local assets by more

    distributed control strategies [18]. This includes droop based strategies that offer more

    straightforward cost-effective solutions by avoiding communication means [2].

    However when the inverters on a radial feeder are coordinated by a conventional

    droop strategy, a heavier burden of the voltage compensation is imposed on the

    inverters installed down the feeder. This drawback of the conventional droop control

    strategies is systematically investigated in this research using Thévenin theorem.

    1.4 Key Contributions of this Research

    Cost-effective straightforwardness of decentralised control strategies has been

    the prime factor driving their wide applications [2]. Despite the significant advantages,

    the conventional droop strategies are open to criticism because of lack of adaptiveness

    to the system in which they are employed.

    When the shunt inverters on a radial feeder are coordinated by the non-adaptive

    conventional droop strategies, the inverters are loaded unevenly. This uneven loading

    is an unsatisfactory compromise that has not been investigated yet according to our

    latest literature review.

    Adaptiveness needs a greater extent of knowledge. Thus, we have investigated

    methods to locally gain knowledge of the system from an inverter’s perspective. We

    draw on the circuit theory fundamentals to locally broaden the inverter’s perspective.

  • Chapter 1: Introduction 4

    Maintaining the straightforwardness of decentralised control strategies is our

    fundamental condition. The Thévenin theorem as the most significant circuit theorem

    is employed in this direction to provide as much knowledge of the system as possible.

    Then, Thévenin parameters identification at the terminals of any customer becomes

    the next challenge of this work. The big picture of this work can be dissected in two

    key contributions as follows.

    1. The novel adaptive droop control strategy

    Geometry of phasors is investigated to accurately determine the critical factors

    impeding an even distribution of the compensation effort in a droop controlled multi-

    inverter system. Elements of the Thévenin equivalent circuit model are incorporated

    in the development of a novel droop control strategy.

    2. On-line identification of the Thévenin elements at the supply frequency

    Following the arguments and the intuitions provided in the early chapters,

    Thévenin elements integrated into the novel droop strategy need to be identified.

    Structures for Thévenin parameters identification are proposed. There is a significant

    degree of difficulty when the local identification is undertaken in a real system with

    interference caused by loads and other inverters. To this end, challenges regarding the

    processing of the measured signals are discussed, and effective solutions are provided.

    The outcome of this research is a novel droop-based voltage compensation

    strategy improving power-sharing among customers’ inverters.

    1.5 Thesis Outline

    Following the research overview provided in the first chapter, the remainder of

    this thesis is organised as:

    A literature review is presented in Chapter 2. A preamble phasor analysis,

    methods for equivalent circuit parameters derivation and some applications of

    equivalent circuit knowledge in power system studies are briefly reviewed. Then a

    literature survey on control of modern inverter-based systems is reported. While

    advantages of the droop control strategies are highlighted, we shed light on the

    downsides of conventional droop strategies and the corresponding alternatives

    suggested to overcome the downsides. Inspired by many alternatives that focused on

  • Chapter 1: Introduction 5

    enhancing the adaptiveness of the droop strategies, we draw on Thévenin theorem to

    provide any customer with the greatest possible knowledge of the system.

    Thus the Thévenin parameters need to be identified. As conventional distribution

    systems have no means of inter-inverter communication, a local identification problem

    through power lines is desired. Relevant signal processing concepts relevant to this

    challenging identification are reviewed and appropriate metrics of performance are

    delineated in Chapter 3. This is along with a review of the previous research that have

    applied these concepts in similar context and the necessary implications are taken into

    account for Chapter 4.

    Our contributions are presented in Chapter 4. A Thévenin-based droop control

    strategy is proposed through detailed phasor analysis. Some reconciliation with our

    observations of a real modern residential distribution system is put forward.

    Identification of Thévenin parameters as a complex problem is progressively

    addressed in Chapter 4 based on the topics discussed in Chapter 3. Challenges of each

    step are theoretically elaborated. Dependency of the desired signals and the

    interference are determined through temporal analysis of the measurements.

    The methodologies designed in Chapter 4 are tested in Chapter 5. The tests’

    results are presented along with interpretations. Points of note drawn from this research

    as well as some directions for future work are given in Chapter 6.

  • Chapter 2: Literature Review 7

    Chapter 2: Literature Review

    This chapter can be partitioned into two parts. The importance of a phasor

    context is briefly reviewed for sinusoidal steady-state analysis of distribution systems.

    Derivation of equivalent circuit parameters is delineated in this context. It is followed

    by setting a synopsis of some of the previous applications of Thévenin theorem in

    power system studies.

    The second part of the chapter starts from section 2.4. The inverter’s position

    among the electrical apparatus of a typical customer’s PV/battery system is pinpointed.

    A typical hierarchical control structure is further described for the inverter. The

    primary level of this hierarchical control is deeply investigated. In particular, droop-

    based power control is delineated as the research focus. Some limitations of the

    conventional droop control are given with the corresponding solutions. Introducing

    adaptiveness to the conventional droop has been of paramount importance. Examples

    of adaptive droop-based control strategies are cited. Finally, a summary of the

    reviewed literature with regard to our research question and implications for the

    methodology chapter, i.e., Chapter 4 is highlighted in Section 2.8.

    2.1 Phasor Analysis and Thévenin Equivalent Circuit

    Linear operations (e.g. summation, subtraction, differentiation, and integration)

    on sinusoidal functions result in more sinusoidal functions [19]. Time-variant

    equations made of sinusoidal functions, i.e., excitations and the corresponding

    responses, can be represented as algebraic equations of complex quantities

    synthesising the phasor notation and the concept of impedance. Phasors in these

    algebraic equations are generally different in magnitude and angle. Steady-state power

    system studies rely on the analysis of these equations where integration in time is

    replaced by division by 𝑗𝜔, and differentiation in time is replaced by multiplication by

    𝑗𝜔 [19, 20].

    The purely dissipative nature of resistors causes their voltage and current phasors

    to be in the same phase angle. Whereas nondissipative nature of ideal energy storage

    elements causes their voltage to be perpendicular to their current phasors [19]. These

    energy storage elements, i.e., capacitors and inductors are presented as reactances as

  • Chapter 2: Literature Review 8

    shown in Figure 2.1. Voltage-current relationships of these reactances are presented as

    follows

    𝑣 = 𝐿𝑑𝑖

    𝑑𝑡�⃗� = 𝑗𝜔 ∙ 𝐿 ∙ 𝐼 �⃗� = 𝑗𝑋 ∙ 𝐼 𝐼 = 𝐼𝑚∠(𝜃) �⃗� = 𝑉𝑚∠(𝜃 +

    𝜋

    2) (2.1)

    𝑖 = 𝐶𝑑𝑣

    𝑑𝑡𝐼 = 𝑗𝜔 ∙ 𝐶 ∙ �⃗� 𝐼 = 𝑗𝑋 ∙ �⃗� �⃗� = 𝑉𝑚∠(𝜃) 𝐼 = 𝐼𝑚∠(𝜃 +

    𝜋

    2)(2.2)

    Figure 2.1. Circuits’ energy storing elements with the graphical voltage-current relationship in the

    complex phasor and the time domain planes

    Voltage and current phasors are aligned unless phase differences are induced by

    energy storage elements.

    This research is based on sinusoidal steady-state analysis. All circuit relations

    and theorems that apply to resistive circuits under DC conditions apply for sinusoidal

    steady-state analysis in the frequency domain to circuits consisting of resistance,

    inductance, and capacitance, with voltages and currents represented as phasors and

    impedances of circuit elements replacing resistance [19]. When power system analysis

    is conducted using a digital computer, writing nodal equations based on the current

    sources and admittances of the circuit is highly desirable [16]. Once, a reference bus

    is selected for the circuit and the circuit admittances and their bus connections are

    given as the computer input data, the admittance matrix can be formed. This matrix

    together with the input currents vector are employed to determine the bus voltage

    vector solving simultaneous linear equations using standard computer programs [16].

  • Chapter 2: Literature Review 9

    “Brute force” and mechanistic methods are undesirable in electrical circuit

    analysis, due to an important guiding principle expressing “always seek the simplest

    solution” thereby saving time and effort. Creativity and drawing on particular insights

    into circuit behaviour play a significant role in reducing a circuit to the simpler

    equivalence. In this direction, circuit theorems are the cornerstones to develop creative

    ways [19, 20].

    The Thévenin theorem is described as the circuit analysis most fundamental

    theorem [19]. According to this theorem, the voltage and current characteristic at any

    specified pair of terminals of a circuit can be expressed with a two-element circuit.

    These elements are an ideal voltage source, namely Thévenin voltage, in series with a

    source impedance, namely Thévenin impedance. Thévenin circuit is the simplest

    possible equivalent circuit as it consists of just an ideal source and an impedance [20].

    The Thévenin theorem applies to linear time-invariant circuits; thus the Thévenin

    impedance and the Thévenin voltage need updating following circuit changes over

    time.

    If a comprehensive knowledge of the circuit was available, nodal equations of

    the system could be summarized as

    𝑉 = 𝑍𝑏𝑢𝑠 ∙ 𝐼 (2.3)

    where 𝑉 and 𝐼 respectively denote the vector of the bus voltages and the vector of the

    current sources. 𝑍𝑏𝑢𝑠 is a symmetric matrix called the bus impedance matrix [21]. The

    diagonal elements of 𝑍𝑏𝑢𝑠, i.e., 𝑍11, 𝑍22, … , 𝑍𝑁𝑁 are the self-impedances. The ith nodal

    equation has a general form as indicated in (2.4)

    𝑉𝑖⃗⃗ = 𝑍𝑖𝑖⃗⃗ ⃗⃗ ∙ 𝐼𝑖⃗⃗ + 𝑓(𝐼1⃗⃗ , … , 𝐼�⃗⃗� , … , 𝐼𝑁⃗⃗ ⃗) (𝑓𝑜𝑟 𝑖 ≠ 𝑗) (2.4)

    Referring to the Thévenin impedance definition, 𝑍𝑖𝑖⃗⃗ ⃗⃗ denotes the Thévenin

    impedance seen from ith bus. Nonetheless, since the comprehensive knowledge of the

    system is mostly unavailable, Thévenin source and Thévenin impedance are generally

    determined as follows.

    The Thévenin source is simply the voltage at the specified terminals when these

    terminals are open circuited. There are four different methods to determine the

    Thévenin impedance [19]. The first method is conceptually shown in Figure 2.2 from

    the perspective of the ith bus in a sinusoidal steady-state, i.e., kth instant. The open

  • Chapter 2: Literature Review 10

    circuit voltage phasor is denoted by the argument and the angle of the Thévenin voltage

    estimate, i.e., |𝑉𝑖,𝐾𝑇ℎ𝑣⃗⃗ ⃗⃗ ⃗⃗ ⃗⃗ ̂⃗| ∠arg (𝑉𝑖,𝐾

    𝑇ℎ𝑣⃗⃗ ⃗⃗ ⃗⃗ ⃗⃗ ̂⃗). From the distribution system analysis perspective, it is

    worth noting that dynamically varying demand of the loads and supply of the inverters

    might need updating of the Thévenin equivalent model. Updates at subsequent time

    steps are indexed by the subscript K. Active and reactive components of the Thévenin

    impedance estimate are respectively denoted by 𝑅𝑖,𝐾𝑇ℎ�̂� and 𝑋𝑖,𝐾

    𝑇ℎ�̂�. According to the first

    Thévenin derivation method, the terminals of interest are short-circuited to measure

    the current, dividing the open circuit voltage by the short circuit current is calculated

    as the Thévenin impedance [20].

    Figure 2.2. Schematic of the first method of Thévenin impedance derivation

    In second method, independent sources are essentially set to zero. Thévenin

    impedance is then derived by applying circuit theorems (e.g. delta-star

    transformation).

    Alternatively, the Thévenin impedance is determined by applying a parametric

    test source (e.g. a voltage source) to the terminals of interest and the current is found

    as a function of the test source or vice versa. The Thévenin impedance is the

    proportional coefficient relating the voltage to the current, and the Thévenin voltage is

    seen as the constant offset term of the relationship [19].

    The fourth method is the most practical approach to determine the Thévenin

    impedance. While a test voltage or current is applied to the terminals of interest in this

    method, independent sources are considered effective at the stage of Thévenin

    impedance determination. Change of the voltage made by the test current is divided

    by the test current to calculate Thévenin impedance [19]. The fourth approach is also

    known as Tellegen’s Theorem method [22].

    It is noteworthy that elements of the Thévenin equivalent circuit are affected by

    the dependent sources. Their impact can be considered using superposition. Any

    dependent source is characterised by a law relating its current to the voltage. When

    this law can be translated straightforwardly to an equivalence of an independent source

  • Chapter 2: Literature Review 11

    and an impedance, the dependent source is replaced by the equivalence. Otherwise, it

    is treated as an independent source. An unknown can be assigned to the dependent

    source voltage and another unknown as its current. Following the analysis of the

    circuit, a new relationship is provided relating the two unknowns. The new relationship

    with the characteristic relationship are then used to calculate all the circuit parameters

    including the determination of Thévenin equivalent parameters seen from the terminals

    of interest [19].

    2.2 Norton Equivalent Circuit

    When a Thévenin voltage source, in conjunction with a Thévenin impedance, is

    transformed to an equivalent current source, a Norton equivalent circuit is obtained. It

    follows from the source transformation theorem [20]. The Norton equivalent of the

    circuit of Figure 2.2 is shown in Figure 2.3.

    Figure 2.3. Norton equivalent circuit of the Thévenin equivalent in Figure 2.2

    It may be noted that a circuit can have Thévenin equivalent but not a Norton

    equivalent and conversely [19]. The Thévenin equivalent circuit of an ideal voltage

    source is the source itself with zero Thévenin impedance. This makes the Norton

    current infinity, so the Norton equivalent circuit does not exist. The preceding case is

    exemplified for a typical n-bus radial distribution feeder connected to a robust main

    grid at Bus_1 with unity voltage shown in Figure 2.4. This modelling of the upper

    network is used in this thesis.

    Figure 2.4. n-bus radial feeder connected to the voltage robust main grid

  • Chapter 2: Literature Review 12

    2.3 Significance of Thévenin Equivalent Circuit in Power System Studies

    Today’s active distribution systems prompt a need for continual monitoring of

    the systems’ operation condition. Continual equivalent network derivation is in

    alignment with the need to the current broader observability of the system for decision-

    making processes [23, 24]. This is where attempts for online Thévenin learning fit in.

    Thévenin theorem has already been utilised to important wide-ranging topics of

    power system studies [9, 25]. Thévenin impedance extraction has been proved as a

    worthwhile knowledge for all phases of microgrid study [26, 27]. The significance of

    equivalent impedance application has been reflected for network upgrades. Ancillary

    services and power flow analysis have also been pointed out as two use cases of the

    equivalent network derivation [28]. The Thévenin equivalent circuit of a system has

    been derived for cyber security analysis [29]. Thévenin equivalent potential was first

    explored for voltage stability analysis in [30]. The preceding exploration was limited

    to the equivalent seen from the generator in a radial structure. Two Thévenin-based

    alternative approaches were provided for steady-state and transient voltage stability of

    a single transmission line connecting a generation side to a load centre side [31]. The

    difference in alternatives lays in the fact that to either model load side linearly or model

    a Thévenin equivalent for either side of the PMU [31]. The presented highly simplified

    models in [31] were appropriate for online stability analysis. Sequential load variation

    has been applied to work out the Thévenin based voltage stability margin following

    the system’s contingencies [32]. FACTS and HVDC impact on voltage stability was

    also studied using Thévenin equivalent [33]. Locally extracted Thévenin equivalent of

    the system was a significant milestone that was brought Thévenin-based voltage

    stability analysis to attention in [34]. The authors gave significant insights into possible

    undervoltage protection enhancement via Thévenin knowledge of the system, and

    concisely raised some practical challenges in this pathway [34]. An alternative simple

    and computationally efficient voltage stability index was given in [35] based on real-

    time Thévenin equivalent identification of the system. The Thévenin equivalent has

    been used to determine the voltage disturbance of an unbalanced 3-phase 3-wire and a

    3-phase 4-wire network [36]. A novel Thévenin-based distributed control strategy has

    been developed to coordinate battery systems of a multi-agent multi-zone distribution

    system [37]. Some challenges concerning synchronisation of inverters have been met

    by conducting a Thévenin based stability analysis for paralleled inverters [38]. Power

  • Chapter 2: Literature Review 13

    transfer capability of a PV plant for exchange with the main system has been improved

    by the development of an adaptive reactive power Thévenin based droop control [39].

    The permissible extent of wind penetration is evaluated undertaking a Thévenin based

    stability analysis [40]. Maximum voltage stability margin and maximum loadability

    have been increased utilising Thévenin knowledge. Unsymmetrical fault location has

    also been determined leveraging this knowledge [41]. Leveraging Thévenin

    impedance knowledge to locate unsymmetrical fault has been elaborated [42].

    2.4 Typical Power Elements Connected to an Inverter

    Increasing uptake of inverters by customers has led to the introduction of control

    strategies that actively organise clusters of inverters. These clusters are commonly

    known as microgrids and they are part of the distribution systems. Conceptually,

    microgrids can be operated in parallel or disconnected from the main grid as an isolated

    island.

    One configuration of a typical PV system is shown in Figure 2.5. While only

    power elements have been shown in Figure 2.5. The control system managing this

    interconnected system can be partitioned into input side and grid side. DC bus of the

    power converters is the boundary between the two sides [43].

    Figure 2.5. One configuration of power elements connected to a PV module

    There is a broad field of research on control aspects of any power element shown

    in Figure 2.5. The inverter’s control is highlighted in this research.

    2.5 A Typical Hierarchical Control for an Inverter

    Large synchronous generators of the conventional power systems have been

    operated using a hierarchical control structure which typically consists of three levels

    [44]. Analogously primary, secondary and tertiary control levels can be described for

    management of inverters [45]. A typical hierarchical control structure is shown in

    Figure 2.6 for a microgrid including two inverters.

  • Chapter 2: Literature Review 14

    Grid-feeding, grid-forming and grid-supporting are classes of inverters

    depending on their functions in an AC microgrid [46]. When real or reactive power

    delivery of PV/battery inverter systems are controlled to regulate the frequency and/or

    magnitude of the grid voltage, they are considered as grid-supporting inverters. Two

    different types of grid-supporting inverters are identified as noted in Figure 2.6 (b).

    When they can be independently operated in an islanded microgrid, they would be

    modelled as voltage source, i.e., the one at the bottom panel of Figure 2.6(b). Whereas

    grid-supporting inverters whose operation is limited to the voltage regulated systems

    are modelled as a current source, i.e., the one at the top panel of Figure 2.6(b) [46].

    Figure 2.6. A typical hierarchical control strategy implemented to coordinate the inverters of a

    microgrid (a) tertiary control and secondary control (b) secondary control and primary control

    2.5.1 Tertiary Control

    The microgrid shown in Figure 2.6 is connected to the main grid through a tie-

    switch. The microgrid exchanged power with the main grid in parallel operation mode

    is usually controlled by tertiary control. This level is also known as grid level where

  • Chapter 2: Literature Review 15

    functions can be found implemented by distribution network operator (DNO) and

    market operator (MO) [47, 48]. This level of control also facilitates synchronisation of

    an islanded microgrid to smoothly reconnect with the main grid [45]. Magnitude and

    frequency of the voltage of the microgrid side of the tie-switch are controlled for this

    purpose. A typical proportional integral controller of the tertiary control can be

    expressed as

    𝜔𝑀𝐺∗ = 𝑘𝑝𝑃 ∙ (𝑃𝐺

    ∗ − 𝑃𝐺) + 𝑘𝑖𝑃 ∙ ∫(𝑃𝐺∗ − 𝑃𝐺)𝑑𝑡 (2.5)

    𝑉𝑀𝐺∗ = 𝑘𝑝𝑄 ∙ (𝑄𝐺

    ∗ − 𝑄𝐺) + 𝑘𝑖𝑄 ∙ ∫(𝑄𝐺∗ − 𝑄𝐺)𝑑𝑡 (2.6)

    2.5.2 Secondary Control

    When frequency and magnitude droop based control strategies are utilized as the

    primary controller in an islanded microgrid, frequency and magnitude of the voltage

    deviate following any change in demand or supply. Deviations within an allowable

    limit can be compensated using a secondary control level. These limits are dictated by

    grid code standards (e.g. ±6% for magnitude required by the Australian standards).

    Secondary control basically adjusts the reference points for the primary control of all

    inverters [45].

    In this direction, measured voltage frequency and magnitude, i.e., 𝜔𝑀𝐺 and 𝑉𝑀𝐺

    are compared with the references, i.e., 𝜔𝑀𝐺∗ and 𝑉𝑀𝐺

    ∗ ; all inverters are updated with the

    processed errors, i.e., 𝛿𝜔 and 𝛿𝑉 to restore frequency and magnitude to the rated

    values. Typical secondary control function for frequency and magnitude are presented

    as follow

    𝛿𝜔 = 𝑘𝑝𝜔 ∙ (𝜔𝑀𝐺∗ − 𝜔𝑀𝐺) + 𝑘𝑖𝜔 ∙ ∫(𝜔𝑀𝐺

    ∗ − 𝜔𝑀𝐺) ∙ 𝑑𝑡 (2.7)

    𝛿𝑉 = 𝑘𝑝𝑉 ∙ (𝑉𝑀𝐺∗ − 𝑉𝑀𝐺) + 𝑘𝑖𝑉 ∙ ∫(𝑉𝑀𝐺

    ∗ − 𝑉𝑀𝐺) ∙ 𝑑𝑡 (2.8)

    where 𝛿𝜔 and 𝛿𝑉 are frequency and magnitude of the voltage as the secondary

    controller’s outputs respectively, 𝑘𝑝𝜔 and 𝑘𝑝𝑉 are the corresponding proportional

    gains with 𝑘𝑖𝜔 and 𝑘𝑖𝑉 are the corresponding integral coefficients of the controller.

    In the reconnection process of an islanded microgrid to the main grid, the grid

    side frequency and magnitude of the voltage of the tie-switch are the references for the

    secondary controller. Any phase difference between the isolated microgrid and the

    main grid is corrected by a synchronisation control loop which can be a conventional

  • Chapter 2: Literature Review 16

    phase locked loop (PLL) [49]. In this process ∆𝜔𝑠 would be the correction term added

    to the (2.7) and sent out to all inverters as follow

    𝛿𝜔 = 𝑘𝑝𝜔 ∙ (𝜔𝑀𝐺∗ − 𝜔𝑀𝐺) + 𝑘𝑖𝜔 ∙ ∫(𝜔𝑀𝐺

    ∗ − 𝜔𝑀𝐺) ∙ 𝑑𝑡 + ∆𝜔𝑠 (2.9)

    Following the synchronisation, there would be zero exchanged power between

    the paralleled microgrid and the main grid.

    Secondary control level is also known as the management level where microgid

    central controller (MGCC) is the crucial element. MGCC is the DNO’s and MO‘s main

    interface with the microgrid. MGCC can handle considerations like market prices for

    electricity and even other commodities like gas. MGCC can also be taken responsible

    for optimisation of local production. When there are deferrable loads in the microgird,

    they are typically under the MGCC control.

    Implementation of tertiary and secondary control levels needs a central system

    using communication infrastructures [45].

    2.5.3 Synchronisation of Inverters

    Overall performance of the coordinated inverters is influenced by the precision

    of the estimation of the voltage parameters. Voltage magnitude, frequency, and phase

    angle need to be accurately estimated using a synchronisation algorithm to enable

    precise control of the active and the reactive power of each inverter module. Moreover,

    as it was mentioned in the previous section, any maneuver between the parallel and

    the isolated operation modes requires the grid condition monitoring [46].

    Synchronisation system of grid-forming and voltage source grid-supporting

    inverters should work in the parallel and the isolated operation modes of the microgrid.

    In the isolated mode, the synchronisation system oscillates at an unchanged frequency,

    i.e., 𝜔𝑓𝑓. In the transition of operation modes, phase angle and frequency of the

    isolated microgrid’s voltage are slowly varied to resynchronise with the main grid’s

    voltage. A stable and secure manoeuvre is required as all grid-feeding inverters are

    under the influence of the reconnection frequency and phase-angle transients [45].

    Synchronous reference frame phase-locked loop (SRF-PLL) has been

    extensively used in nearly balanced three-phase systems. It is shown as a constituent

    part of the primary control in Figure 2.7. Park transformation is employed to obtain

    signals in dq reference from the abc reference frame. The 𝑣𝑞 component is driven to

  • Chapter 2: Literature Review 17

    zero through a feedback control loop and the angular position of the dq reference frame

    is regulated. Phase estimation dynamics is normally improved by feed forwarding 𝜔𝑓𝑓

    [46].

    The considerations above should also be received under grids with unbalanced

    and distorted voltage conditions. Frequency-locked loop (FLL) can alternatively be

    used as the synchronisation system. Compared to PLL systems, FLL systems are

    generally less affected by likely phase-angle jumps during transient abnormal grid

    conditions [50, 51].

    2.5.4 Primary Control and Basics of Droop Control

    Active modern distribution grids host customers with loads and PV/battery

    inverters. Coordination of power-sharing among these inverters is the crucial role of

    primary control level [45]. In this context, proliferation of uninterruptable paralleled

    systems (UPS) has taken place before the advent of PV/battery inverters. UPS active

    and reactive power control strategies have already been examined for inverters’

    coordination. Centralized, master-slave, average-load sharing and circular-chain

    control architectures are some of the common UPS control categories [52]. However,

    UPS inverters have often been located close to each other equipped with

    communication channels. The need for technically complex and costly communication

    infrastructure impedes the application of the typical UPS control strategies to spatially

    dispersed customers’ inverters without any means of communication at first place [46].

    Privacy of individual customers might hinder the application of the UPS control

    strategies to PV/battery inverters’ coordination. Alternatively, these inverters can be

    controlled via decentralised strategies independent of communication means. Droop

    based strategies with an enduring legacy from the straightforward operation principles

    of large synchronous generators have been widely applied for decentralised

    coordination of the inverters. In fact, the microgrid concept of the Consortium for

    Electrical Reliability Technology Solutions (CERTS) strongly discourages

    communication-based control strategies for power-sharing purposes [53, 54]. Droop-

    based designs have particularly become a prominently robust control strategy since

    they are immune to likely disruptions to communication systems [55].

    The current regulation loop is considered as the inner part of the primary control.

    Droop control as the outer part of the primary control level provides references for the

  • Chapter 2: Literature Review 18

    current loop [56]. A typical control structure for a current-source-based grid-

    supporting inverter is delineated in Figure 2.7.

    Figure 2.7. A current source grid supporting inverter controlled by the primary level

    This control structure has been implemented in dq reference frame. There have

    been abc to dq transformations at different parts of the structure. The transformations’

    outcome has been DC signals rotating synchronously with the frequency of the grid

    voltage. These transformations have specifically required the voltage phase angle

    information. This information has been provided by a phase locked loop block as

    shown in the top part of Figure 2.7. Proportional-integral (PI) controllers used in the

    structure have had a typical transfer function given by

    𝐺𝑃𝐼(𝑠) = 𝐾𝑝 +𝐾𝑖

    𝑠 (2.10)

    where 𝐾𝑝 and 𝐾𝑖 respectively denote the integral gain and the proportional gain. From

    circuit perspective, a current-source-based grid-supporting inverter regulating its

    injection according to the bus voltage can be modelled as a voltage-controlled

    dependent current source. Droop control is further inspected as the focus of this

    research. In particular, voltage magnitude droop control is examined. The focus is

    highlighted in Figure 2.7 and Figure 2.8.

  • Chapter 2: Literature Review 19

    Figure 2.8. (a) Schematic of a voltage droop controlled current source grid supporting inverter (b)

    simplified presentation of the schematic

    A radial feeder consisting of n customers all having loads and PV/battery

    inverter systems is shown in Figure 2.9(a). The equivalent circuit model of the whole

    feeder from the ith inverter’s perspective is depicted in Figure 2.9(b). According to

    this model, a voltage controlled current source has been connected to the system’s

    Thévenin equivalent.

    Figure 2.9. (a) Configuration of a typical n bus modern radial feeder with customers having loads and

    PV/battery inverter systems (b) Circuit model of the ith droop-controlled inverter connected to the

    system’s Thévenin equivalent

    Time steps in the inverter’s action have been indexed by k for any inverter

    compensating voltage magnitude. Taking the dynamic nature of the compensators and

    varying loads into account, parameters of the system’s Thévenin equivalent model are

    subject to change. However, there is a priori assumption that these parameters are

    unchanged for a short time span that they are being identified [57]. Updating the

    estimates of system’s Thévenin parameters has been indexed by K. Thévenin

    resistance, reactance and voltage have been denoted by 𝑅𝑖,𝐾𝑇ℎ�̂�, 𝑋𝑖,𝐾

    𝑇ℎ�̂�and 𝑉𝑖,𝐾𝑇ℎ𝑣⃗⃗ ⃗⃗ ⃗⃗ ⃗⃗ ̂⃗ in which

    subscript i shows the inverter bus number in a multi-inverter network. The preceding

  • Chapter 2: Literature Review 20

    notations have been consistently used in this thesis. The exchanged power of an

    inverter with the rest of the gird is presented as follow

    𝑃𝑖,𝑘 =|𝑉𝑖,𝑘⃗⃗ ⃗⃗ ⃗⃗ ⃗|

    𝑅𝑖,𝐾𝑇ℎ�̂�

    2+𝑋𝑖,𝐾

    𝑇ℎ�̂�2 ∙ [𝑅𝑖,𝐾

    𝑇ℎ�̂� ∙ (|𝑉𝑖,𝑘⃗⃗⃗⃗⃗⃗ | − |𝑉𝑖,𝐾𝑇ℎ𝑣⃗⃗ ⃗⃗ ⃗⃗ ⃗⃗ ̂⃗| ∙ cos (arg(𝑉𝑖,𝑘⃗⃗⃗⃗⃗⃗ ) − arg (𝑉𝑖,𝐾

    𝑇ℎ𝑣⃗⃗ ⃗⃗ ⃗⃗ ⃗⃗ ̂⃗))) + 𝑋𝑖,𝐾𝑇ℎ�̂� ∙ |𝑉𝑖,𝐾

    𝑇ℎ𝑣⃗⃗ ⃗⃗ ⃗⃗ ⃗⃗ ̂⃗| ∙

    sin (arg (𝑉𝑖,𝑘⃗⃗⃗⃗⃗⃗ ) − arg (𝑉𝑖,𝐾𝑇ℎ𝑣⃗⃗ ⃗⃗ ⃗⃗ ⃗⃗ ̂⃗))] (2.11)

    𝑄𝑖,𝑘 =|𝑉𝑖,𝑘⃗⃗ ⃗⃗ ⃗⃗ ⃗|

    𝑅𝑖,𝐾𝑇ℎ�̂�

    2+𝑋𝑖,𝐾

    𝑇ℎ�̂�2 ∙ [−𝑅𝑖,𝐾

    𝑇ℎ�̂� ∙ |𝑉𝑖,𝐾𝑇ℎ𝑣⃗⃗ ⃗⃗ ⃗⃗ ⃗⃗ ̂⃗| ∙ sin (arg(𝑉𝑖,𝑘⃗⃗⃗⃗⃗⃗ ) − arg (𝑉𝑖,𝐾

    𝑇ℎ𝑣⃗⃗ ⃗⃗ ⃗⃗ ⃗⃗ ̂⃗)) + 𝑋𝑖,𝐾𝑇ℎ�̂� ∙ (|𝑉𝑖,𝑘⃗⃗⃗⃗⃗⃗ | − |𝑉𝑖,𝐾

    𝑇ℎ𝑣⃗⃗ ⃗⃗ ⃗⃗ ⃗⃗ ̂⃗| ∙

    cos (arg(𝑉𝑖,𝑘⃗⃗⃗⃗⃗⃗ ) − arg (𝑉𝑖,𝐾𝑇ℎ𝑣⃗⃗ ⃗⃗ ⃗⃗ ⃗⃗ ̂⃗)))] (2.12)

    where active power and reactive power delivered by ith inverter to the grid have been

    respectively denoted by 𝑃𝑖,𝑘 and 𝑄𝑖,𝑘 [46]. The magnitude of the ith inverter’s terminal

    voltage has been denoted by |𝑉𝑖,𝑘⃗⃗ ⃗⃗⃗⃗ |. 𝑅𝑖,𝐾𝑇ℎ�̂�

    and 𝑋𝑖,𝐾𝑇ℎ�̂� respectively denote the active and

    the reactive component of the Thévenin equivalent impedance estimate of the rest of

    the system. 𝑉𝑖,𝐾𝑇ℎ𝑣⃗⃗ ⃗⃗ ⃗⃗ ⃗⃗ ̂⃗ shows the estimated phasor of the Thévenin voltage of the equivalent

    of the rest of the system. When the system’s impedance is relatively reactive,

    mathematical manipulation of (2.12) results in the conventional voltage reactive

    current droop control strategy as follows

    𝐼𝑖,𝑘𝐶⃗⃗⃗⃗ ⃗ = 𝑚 ∙ (1 − |𝑉𝑖,𝑘⃗⃗⃗⃗⃗⃗ |)∠(arg(𝑉𝑖,𝑘⃗⃗⃗⃗⃗⃗ ) − 𝜋 2⁄ ) (2.13)

    where phasor of the inverter’s compensating reactive current has been denoted by 𝐼𝑖,𝑘𝐶⃗⃗⃗⃗ ⃗

    [9]. 𝑚 shows the droop gain. The phase angle of the pure reactive compensation is

    ninety degree offset with regard to the terminal voltage phasor. This lagging offset has

    been due to the load convention adopted in this research. The conventional droop

    characteristic of an inverter is depicted in Figure 2.10. Inverters’ reactive current is

    reduced to zero at the rated voltage.

    Figure 2.10. Voltage reactive current droop characteristic

  • Chapter 2: Literature Review 21

    As synthesis of dependent sources in Thévenin circuit derivation was earlier

    described in section 2.1, the dependent source modelled by (2.13) can also be

    represented with an independent source connected to an impedance as depicted in

    Figure 2.11. This presentation is known as Thévenin descriptor [9]. The Norton

    descriptor is also deliverable using the voltage source transformation to current source.

    Figure 2.11. (a) Norton descriptor and (b) Thévenin descriptor of an inverter managed by the droop

    control characterised in (2.13)

    2.6 Advantages, Limitations and Variations of the Conventional Droop

    Droop-based strategies are closely tied with the concept of decentralisation in

    the control systems. Minimum dependency of these strategies on inter-module

    communications results in outstanding flexibility, excellent reliability and last but not

    least, economic benefits [54]. These all together have made droop-based strategies

    almost an obvious choice for the operation of large power systems over the decades

    and have created a huge interest for their applications in modern distribution systems.

    Despite the obvious advantages, droop control strategies have some limitations

    too [47]. Some of these limitations with the proposed alternate strategies are

    summarized in Table 2.1.

  • Chapter 2: Literature Review 22

    Table 2.1

    Summary of some of the shortcomings of droop-based control strategies and the solutions

    Limitation of the conventional droop Alternate strategy

    Trade-off between load sharing and

    voltage regulation

    Dynamic droop gain

    Restoration control

    High gain angle droop with supplementary loop

    Slow and oscillating dynamic response

    Adaptive derivative droop to damp transients

    Angle droop

    Droop based on coupling filter parameters

    Droop based on H infinite control theory

    Adverse influence of system impedance

    between inverters

    Voltage drooped as a function of mixed active and

    reactive powers output

    Additional loop with the grid Thévenin impedance

    and voltage estimation

    Interfacing a virtual inductor

    Poor harmonic sharing

    Virtual impedance

    Cooperative harmonic filtering strategy

    Additional loop reducing the bandwidth

    2.7 Adaptiveness of Droop

    System’s characteristics strongly impact the accuracy of droop-based reactive

    power sharing [55]. There has been a considerable effort to develop adaptive droop

    strategies. Adaptiveness has served different purposes.

    Oscillating dynamic response of power-sharing among paralleled inverters has

    been improved [58]. While a robust steady-state power-sharing has been ensured by

    the static droop gain, transient droop gains have been dynamically set to damp the

    oscillatory modes.

    Reactive power sharing has become less dependent on line impedances and

    active power control using a voltage droop as a non-linear function of inverters’ active

    and reactive power [59].

    There is an intrinsic trade-off between the accuracy of reactive power sharing

    and the voltage regulation in the conventional droop control. Reference of each module

    has been adaptively controlled to provide a proper current sharing in a single bus multi-

    inverter configuration. This adaptive reference modulation could also limit the

    variation of operating voltage [60].

    A combination of reactive power control and adaptive droop-based active power

    curtailment has been proposed for PV inverters with loss minimisation and voltage

    regulation as the objectives [61]. The objectives have been adaptively prioritised based

  • Chapter 2: Literature Review 23

    on the recommended range of operating point’s voltage. When the voltage has been in

    the operating range, loss minimisation has had priority however when the voltage has

    violated the rated operating range; the voltage regulation has been prioritised. When

    the reactive power supply has been exhausted in controlling over-voltages, the active

    power has been curtailed evenly according to a droop law with a gain adjusted

    according to the voltage sensitivity of the PV bus [61].

    Droop coefficients have been adaptively tuned to improve reactive power

    sharing using a communication system. Thus sharing could match the inverters’

    relative ratings despite differences in the output impedances. A floating term has been

    basically added to the conventionally fixed droop gain [62]. This floating term has

    been tuned according to the inverter’s active to reactive power ratio as well as the

    mismatch between the connecting impedance of different inverter modules to the

    common microgrid bus [62].

    Droop gain has been adaptively adjusted. A controller consisting of an estimator

    and an adaptive droop has been proposed with the objective of tight active and reactive

    power regulation decoupled from grid parameters. The estimated parameters have

    been equivalent impedance and voltage of the grid that the inverter has been connected

    to [63]. The proposed controller has been developed based on an offline static

    estimation where the sensitivity of the proposal has only been analysed to different

    system impedance in separate simulation scenarios. In other words, there has been no

    dynamical change in the impedance to really test the proposed estimation robustness

    [63]. The emphasis of this proposal has been on a single inverter case and has neglected

    the estimation challenges in a multi-inverter microgrid that in turn has led to significant

    limitation to the practicality of the proposal. A second order general integral frequency

    locked loop has been simplistically proposed as the solution to challenges of the

    Thévenin circuit’s parameters estimation with a justification revolving around the

    capability of integration of the voltage frequency [63]. Even when the connection and

    the disconnection of a single inverter to the grid is studied, one needs to discuss the

    variation in the grid side as well.

    Regulation of average voltage in a microgrid has been addressed, and reactive

    power has been shared proportionally using an adaptive consensus droop based control

    strategy [64]. This strategy has had two modules for each inverter to process the

    information gathered locally and also the data sent by the neighbours. Inverters have

  • Chapter 2: Literature Review 24

    reached to a consensus about overall voltage deviation, and they have consequently

    lowered/elevated their droop characteristic for voltage compensation. Proportional

    reactive power supply of each inverter has also been set according to the rating by

    droop gain adjustment.

    Voltage magnitude has been regulated using a combination of PV inverters’

    reactive power and battery inverters’ active power [4]. A variable droop gain based on

    the voltage sensitivity analysis has been applied for droop controlled battery inverters

    to realise even investment for battery storage capacity by all customers and has

    minimised the total capacity installation. However, this adaptiveness has been

    introduced as either set and forget process or communication dependent for regular

    update.

    A smooth operating mode transition has been realised for an inverter-based

    microgrid from the grid-connected operation mode to the isolated mode. In this

    direction, an adaptive droop-based control has been proposed to coordinate

    charge/discharge of the batteries with the generation of the other inverters to facilitate

    likely multi-transition. This droop characteristic’s reference has been shifted up and

    down accordingly to control the isolated microgrid’s frequency and to share the loads

    [65].

    2.8 Summary and Implications

    Since the infancy of large power systems, a higher observability of network

    operations has always been of the systems’ operators’ interest. The Thévenin theorem

    as the most significant electrical circuit theorem has been extensively employed in

    studies conducted at higher voltage levels to hone the adaptiveness of the system

    operation drawing on a higher observability.

    Penetration of distributed generations for the past two decades has made a

    significant transformation in the status of distribution systems from the formerly

    passive to the currently active. The proliferation of inverter-interfaced customers calls

    for coordination of these distributed generators. This coordination can be undertaken

    in a hierarchical scheme similar to what has been being applied to large generators of

    the conventional power systems. In this realm, we refine the research foci to the

    primary control of inverters. Then it should be noted that the power controller module

    of the primary control is investigated in particular. Power controllers can be

  • Chapter 2: Literature Review 25

    categorised based on the extent of their dependency on communication infrastructure.

    Considering the fact that inverters are being introduced to the existing conventional

    distribution systems that often do not have any means of inter-inverter communication,

    we focus on decentralised power sharing strategies. To this end, scalable and modular

    droop-based control strategies have already attracted the attention of the decision

    makers of the new distribution systems. Droop control applications in modern

    distribution systems are developed by imitating the self-regulation capability of

    synchronous generators.

    Despite the advantages, there are some drawbacks to droop-based control

    strategies that researchers have tried to address. In this direction, introducing

    adaptiveness to the conventional droop strategy has been widely applied for different

    objectives. Analogous to the high voltage systems, pursuit of adaptiveness is

    commonly tied up with an improved observability in distribution systems. A higher

    observability of the new age active distribution systems is advantageous not only to

    the actors at low voltage level but also to the higher voltage systems’ operators.

    However, most of the attempts at the introduction of adaptiveness have hinged

    on using communication means to some extent. The employment of the

    communication means is in contrast with the local nature of the droop-based control

    strategies as it incurs an increasing amount of cost and complexity.

    Saving cost and reducing complexity justifies leveraging circuit theorems for

    innovative methods in distribution systems’ analysis. Since Thévenin theorem gives

    the equivalent model of the whole system from any pair of terminals, the theorem’s

    potentials are exploited in this research to provide communication-free adaptiveness

    without compromising the local nature of droop-based control strategies.

    Previous attempt to acquire Thévenin parameters has been mostly limited to

    single point probing, single point measurement [36, 57, 66]. This kind of approach

    does not align with the coordination need of a multi-inverter system.

    In sum, a study of the literature has not revealed an in-depth investigation of

    Thévenin-based observability for local control of real distribution systems with

    dynamic loads and dynamic compensators. Thévenin parameters identification is a

    highly challenging task in this dynamic noisy system compared to the hypothetically

  • Chapter 2: Literature Review 26

    static noise-free system. The background signal processing concepts for a typical local

    identification through power lines is detailed in the next chapter.

  • Chapter 3: Signal Processing Concepts Relevant to Local Identification Problems 27

    Chapter 3: Signal Processing Concepts Relevant to Local Identification

    Problems

    3.1 Overview

    In this research, Thévenin parameters of the distribution system are identified

    locally through power lines at power frequency. The relevant background signal

    processing concepts and the mathematical topics relevant to this scene are discussed

    in this chapter.

    3.2 Signal Processing Basics Required for Understanding of a Local Identification

    Theoretical circuit principles of Thévenin parameters derivation were presented

    in section 2.1. Working with time waveforms is needed in many real-world science

    and engineering practices including local identification problems. Desired waveforms

    frequently appear as random time signals. In this direction, random waveforms need

    to be described in a probabilistic sense [67].

    3.2.1 Continuous and Discrete Random Process

    Enlarging the random variable concept across time gives rise to the concept of

    random process. Since the possible outcome of an experiment, i.e., s dictates the value

    of a random variable X, the random process becomes a function of both s and t. The

    random process can be denoted as X(s,t) representing a family or ensemble of time

    functions where s and t are variables. Each member of the ensemble as a specific

    waveform of a random process is called a sample function commonly represented as

    x(t) [67, 68].

    When t can have any value from a continuum and X is continuous too, X(s,t) is

    considered a continuous random process. A few sample functions of a continuous

    random process are illustrated in Figure 3.1.

  • Chapter 3: Signal Processing Concepts Relevant to Local Identification Problems 28

    Figure 3.1. A continuous random process

    When X is continuous, but t has only discrete values, the random process is

    considered as a continuous random sequence. A continuous random sequence is often

    referred to as a discrete-time (DT) random process as it is defined at only discrete

    (sample) times. Sample functions of a DT random process are frequently called DT

    random signal [67, 68]. A DT random process is technically a set of random variables

    denoted by {𝑥𝑖(𝑙 ∙ 𝑇𝑠) ∶ 𝑖 = 1,2, … , 𝑙 = 1,2, … } given for sample times with 𝑇𝑠 known

    as the sampling interval. 1 𝑇𝑠⁄ is called the sampling rate stated as samples per second.

    This type of random processes are frequently encountered in real-world local

    identification problems since data loggers have limited sampling rates. In practice, it

    is often sufficient to refer to a DT random process as 𝑋(𝑙 ∙ 𝑇𝑠). When the constant 𝑇𝑠

    is already known, 𝑋[𝑙] is adopted as a brief notation, where l is the time index. DT

    signal phasors are denoted by 𝑋𝑖,𝑙⃗⃗ ⃗⃗ ⃗ in this thesis [69]. A few members of an ensemble

    of a discrete-time random process formed by sampling the waveform of Figure 3.1 are

    depicted in Figure 3.2.

  • Chapter 3: Signal Processing Concepts Relevant to Local Identification Problems 29

    Figure 3.2. A discrete-time random process (or a continuous random sequence) formed by sampling

    the waveforms of Figure 3.1

    3.2.2 Deterministic