Page 1: a Nexans company INTERFACE A CONNE… ·  · 2008-07-092 EUROMOLD COMPANY PRESENTATION While every care is taken to ensure that the information contained in this publication is correct,

a Nexans company

Catalogue 2008

Page 2: a Nexans company INTERFACE A CONNE… ·  · 2008-07-092 EUROMOLD COMPANY PRESENTATION While every care is taken to ensure that the information contained in this publication is correct,

2

EUROMOLDCOMPANY PRESENTATION

While every care is taken to ensure that the information contained in this publication is correct, no legal responsibility can be accepted for any inaccuracy. Nexans Network Solutions N.V. - Div. Euromold reserves the right to alter or modify the characteristics of its products

described in this catalogue as standards and technology evolve.

EUROMOLDEuromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories for medium voltage energy distribution. Euromold provides a complete range of acces-sories for underground cables: pre-moulded EPDM or silicone rubber connectors, terminationsand joints for cables and epoxy bushings for transformers and switch gear, as well as a large range of cold-shrinkable terminations and joints from 12 to 42 kV.Euromold is also the manufac-turer of electrical components for the high voltage accessories of the Nexans group.

ISO 9001 CertificateSince 1992, Euromold’s commitment to quality is demonstrated by its ISO 9001 certification.

Laboratory accreditationSince June 2000, Euromold’s independent ELAB laboratory obtained the BELTEST accredi-tation no.192-T-ISO 17025 conform with the European standards for laboratories ISO 17025 for electrical testing of medium voltage cable acces-sories according to the Inter-national standards IEC 61442 and HD 629.

International standardsAll our products meet the International standards like CENELEC HD 629.1, CENELEC EN 50180, IEC 60137, IEEE 386 & 404… or country speci-fications. Official certificates, CESI, KEMA, ATEX… prove the conformity of our products. Long duration tests of existing or new products are con-tinuously performed in our test fields.

Page 3: a Nexans company INTERFACE A CONNE… ·  · 2008-07-092 EUROMOLD COMPANY PRESENTATION While every care is taken to ensure that the information contained in this publication is correct,

3

03/2

008

SEPARABLE CONNECTORSAND BUSHINGS

INTERFACE A

Interface ADimensions according to European CENELEC EN 50180 and 50181 (in mm).

48

9 min.

Dia. 32.5± 0.2

Dia. 44.5± 0.2

0 - 0.2

Dia. 48.5 ± 0.2

Dia. forpin 7.9 +0.02

- 0.05

Dia. 31 +0.1 - 0.3

Table of contents158LR - elbow connector152SR - straight connector151SP - straight plug156SA - surge arresterPITO-E - plug-in termination 180AR-1 /-2 /-3 and 180AR-1-G /-3-G - equipment bushing180A-24P-O - in-air bushingFixings for equipment bushingsAccessoriesBail restraints

Page 4: a Nexans company INTERFACE A CONNE… ·  · 2008-07-092 EUROMOLD COMPANY PRESENTATION While every care is taken to ensure that the information contained in this publication is correct,

4

Connecting possibilities

PITO-EPlug-in termination

(K)150DRDead-end receptacle

(K)150DRDead-end receptacle

(K)151SPStraight plug

BUSHINGS / ACCESSORIES /CONNECTOR

CONNECTION CONNECTORS /ACCESSORIES

(K)400RTPAReducing tap plug

(K)151SOPStand-off plug

(K)150DPDead-end plug

cable isolation

in-line junction + 2 tap-offs

tap-off630/250 A

disconnectable joint

in-line junction+ 2 tap-offs

in-line junction+ tap-off

cableinsulation

tap-off630/250 A

250GPEarthing plug

180A-24P-OIn-air bushing

(K)180AR-1(-G),-2 & -3(-G)Equipment bushing

Equipment interface

cableearthing

(K)200TTee connector

(K)200XCross connector

(K)200TTee connector

one cable toequipment

(K)200XCross connector

(K)200TTee connector

(K)200XCross connector

in-line junction + tap-off

dead-ending of equipment

two cables to equipment

one line to equipment

three cables to equipment

(K)676RTPAReducing tap plug

(K)152SR(/G)Straight connector

(K)158LR(/G)Elbow connector

(K)158LR(/G)Elbow connector

(K)152SR(/G)Straight connector

Page 5: a Nexans company INTERFACE A CONNE… ·  · 2008-07-092 EUROMOLD COMPANY PRESENTATION While every care is taken to ensure that the information contained in this publication is correct,

5

03/2

008

Specifications and standardsThe separable connector 158LR meets the requirements of CENELEC HD 629.1.

Up to 24 kV - 250 A

DesignSeparable connector comprising:1. Conductive EPDM insert.2. Conductive EPDM jacket.3. Insulating EPDM layer moulded between the insert and the jacket.4. Type A - 250 A interface as described by CENELEC EN 50180 and 50181.5. Conductor connector.6. Earthing lead (-/G version only).

158LRINTERFACE A

ELBOW CONNECTOR

ApplicationSeparable elbow connector designed to connect polymeric insulated cable to equipment (transformers, switch gear, motors...).Also connects cable to cable, using the appropriate mating part.

6/10 (12) kV6.35/11 (12) kV

8.7/15 (17.5) kV12/20 (24) kV

12.7/22 (24) kV

Technical characteristics •ThethickconductiveEPDM

jacket provides a total safe to touch screen which ensures safety for personnel.•Eachseparableconnectoris

tested for AC withstand and partial discharge prior to leaving the factory.

1

3

221 mm

160 mm

2

4

5

6

Separable connector

type

VoltageUm(kV)

CurrentIr

(A)

Conductor sizes (mm2)

min. max.158LR/G

158LR

K158LR/G

K158LR

12

12

24

24

250

250

250

250

16

70

16

25

70

95

25

95

Page 6: a Nexans company INTERFACE A CONNE… ·  · 2008-07-092 EUROMOLD COMPANY PRESENTATION While every care is taken to ensure that the information contained in this publication is correct,

6

Kit contentsThe complete (K)158LR or (K)158LR/G elbow connector kit comprises the following components:

The kit also comprises lubricant, wipers,

installation instructions and crimp chart.

Ordering instructionsSelect the part number which gives the best centring to the cable core insulation diameter and substitute X using table X, according to the conductor size and type.Add a 'K' for use up to 24 kV.

Orderingpart number

Dia. over core insulation (mm)

min. max.

158LR/G-11-X158LR/G-13-X

158LR-FB-X+11TL

158LR-FG-X+11TL

158LR-GA-X+11TL

158LR-GAB-X+11TL

158LR-GH-X+11TL

12.6

14.6

17.5

18.4

19.7

21.0

23.2

16.1

18.7

20.2

21.2

22.5

23.8

26.4

Example:The copper wire screened cable is 24 kV, 50 mm2 stranded aluminium with a diameter over core insulation of 20.4 mm.Order a K158LR-FG-50(K)M-12-2+11TL elbow connector kit.

Conductorsizes

(mm²)

Aluminium Copper

DIN hexagonal Deep indent DIN hexagonal

16

25

35

50

70

95

-

25(K)M-12-2

35(K)M-12-2

50(K)M-12-2

70(K)M-12-2

95(K)M-12-2

-

25KM-12-1

35KM-12-1

50(K)M-12-1

70(K)M-12-1

95(K)M-12-1

16(K)M-11-2

25(K)M-11-2

35(K)M-11-2

50(K)M-11-2

70(K)M-11-2

95(K)M-11-2

Table X

+ + +

Conductor

contact

164LRC-X

Pin contact

+ hex key

154LRF

Bail

restraint

150BA-B1Connector housing

(K)158BLR-W

+ (K)158LR-W-X+11TL

connector kit for

larger sizes

=

Cable adaptor

11TL

Connector housing

(K)158BLR/G-WCable reducer

211CA

= (K)158LR/G-W-Xconnector kit for

smaller sizes

+

Table W

For adaptedbail restraints:

see 'Bail restraints and typical applications'.

For outdoorapplications.

Order: +MWS.

Components can be ordered individually.

For use withcopper tape

screened cables. Order: Kit MT.

For use with Alupe orC 33-226 cables.

Please contact our representative.

For use withother cable types.

Please contact our representative.

Page 7: a Nexans company INTERFACE A CONNE… ·  · 2008-07-092 EUROMOLD COMPANY PRESENTATION While every care is taken to ensure that the information contained in this publication is correct,

7

03/2

008

Specifications and standardsThe separable connector 152SRmeets the requirements of CENELEC HD 629.1.

Up to 24 kV - 250 A

152SRINTERFACE A

STRAIGHT CONNECTOR

6/10 (12) kV6.35/11 (12) kV

8.7/15 (17.5) kV12/20 (24) kV

12.7/22 (24) kV

ApplicationSeparable straight connector designed to connect polymeric insulated cable to equipment (transformers, switch gear, motors...).Also connects cable to cable, using the appropriate mating part.

DesignSeparable connector comprising:1. Conductive EPDM insert.2. Conductive EPDM jacket.3. Insulating EPDM layer moulded between the insert and the jacket.4. Type A - 250 A interface as described by CENELEC EN 50180 and 50181.5. Conductor connector.6. Earthing lead (-/G version only).

Technical characteristics •ThethickconductiveEPDM

jacket provides a total safe to touch screen which ensures safety for personnel.•Eachseparableconnectoris

tested for AC withstand and partial discharge prior to leaving the factory.

Separable connector

type

VoltageUm(kV)

CurrentIr

(A)

Conductor sizes (mm2)

min. max.152SR/G

152SR

K152SR/G

K152SR

12

12

24

24

250

250

250

250

16

70

16

25

70

95

25

95

255 mm

1

3

2

4

5

100 mm

6

Page 8: a Nexans company INTERFACE A CONNE… ·  · 2008-07-092 EUROMOLD COMPANY PRESENTATION While every care is taken to ensure that the information contained in this publication is correct,

8

Kit contentsThe complete (K)152SR or (K)152SR/G straight connector kit comprises the following components:

The kit also comprises lubricant, wipers,

installation instructions and crimp chart.

Ordering instructionsSelect the part number which gives the best centring to the cable core insulation diameter and substitute X using table X, according to the conductor size and type.Add a 'K' for use up to 24 kV.

Example:The copper wire screened cable is 24 kV, 50 mm2 stranded aluminium with a diameter over core insulation of 20.4 mm.Order a K152SR-FG-50(K)M-12-2+11TL straight connector kit.

+ +

Bail restraint

151BA

Conductor

contact

151SRC-X

Connector housing

(K)152SRH-W

+ (K)152SR-W-X+11TL

connector kit for

larger sizes

=

Cable adaptor

11TL

Connector housing

(K)152SRH/G-W

Cable reducer

211CA

= (K)152SR/G-W-X

connector kit for

smaller sizes

+

For adaptedbail restraints:

see 'Bail restraints and typical applications'.

For outdoorapplications.

Order: +MWS.

Components can be ordered individually.

For use withcopper tape

screened cables. Order: Kit MT.

For use with Alupe orC 33-226 cables.

Please contact our representative.

For use withother cable types.

Please contact our representative.

Orderingpart number

Dia. over core insulation (mm)

min. max.

152SR/G-11-X152SR/G-13-X

152SR-FG-X+11TL

152SR-GA-X+11TL

152SR-GAB-X+11TL

152SR-GH-X+11TL

12.6

14.6

18.4

19.7

21.0

23.2

16.1

18.7

21.2

22.5

23.8

26.4

Conductorsizes

(mm²)

Aluminium Copper

DIN hexagonal Deep indent DIN hexagonal

16

25

35

50

70

95

-

25(K)M-12-2

35(K)M-12-2

50(K)M-12-2

70(K)M-12-2

95(K)M-12-2

-

25KM-12-1

35KM-12-1

50(K)M-12-1

70(K)M-12-1

95(K)M-12-1

16(K)M-11-2

25(K)M-11-2

35(K)M-11-2

50(K)M-11-2

70(K)M-11-2

95(K)M-11-2

Table X

Table W

Page 9: a Nexans company INTERFACE A CONNE… ·  · 2008-07-092 EUROMOLD COMPANY PRESENTATION While every care is taken to ensure that the information contained in this publication is correct,

9

03/2

008

ApplicationSeparable straight plug designed to connect polymeric insulated cable to cable.Mates with the elbow, straight and branch joint connectors.

Up to 24 kV - 200 A

151SPINTERFACE A

STRAIGHT PLUG

6/10 (12) kV6.35/11 (12) kV

8.7/15 (17.5) kV12/20 (24) kV

12.7/22 (24) kV

Technical characteristics •ThethickconductiveEPDM

jacket provides a total safe to touch screen which ensures safety for personnel.•Eachstraightplugistested

for AC withstand and partial discharge prior to leaving the factory.

Separable plugtype

VoltageUm(kV)

CurrentIr

(A)

Conductor sizes (mm2)

min. max.

151SP

K151SP

12

24

200

200

16

16

95

95

223 mm

Dia. 54 mm

5

4

1

3

2

DesignSeparable connector comprising:1. Conductive EPDM insert.2. Conductive EPDM jacket.3. Insulating EPDM layer moulded between the insert and the jacket.4. Type A interface as described by CENELEC EN 50180 and 50181.5. Conductor connector.

Page 10: a Nexans company INTERFACE A CONNE… ·  · 2008-07-092 EUROMOLD COMPANY PRESENTATION While every care is taken to ensure that the information contained in this publication is correct,

10

Kit contentsThe complete (K)151SP straight plug kit comprises the following components:

The kit also comprises lubricant, wipers,

installation instructions and crimp chart.

Straight plug housing

(K)151SPH-W

Conductor

contact

151SPC-X

Cable

adaptor

11TL

+ + (K)151SP-W-X+11TL

straight plug kit=

Ordering instructionsSelect the part numberwhich gives the best centring to the cable core insulation diameter and substitute X using table X, according to the conductor size and type.Add a 'K' for use up to 24 kV.

Example:The copper wire screened cable is 12 kV, 50 mm2 stranded aluminium with a diameter over core insulation of 16.9 mm.Order a 151SP-A-50(K)M-12-2+11TL-FA/FAB straight plug kit.

Table X

Table W

For adaptedbail restraints:

see 'Bail restraints and typical applications'.

For outdoorapplications.

Order: +MWS.

Components can be ordered individually.

For use withcopper tape

screened cables. Order: Kit MT.

For use with Alupe orC 33-226 cables.

Please contact our representative.

For use withother cable types.

Please contact our representative.

Conductorsizes

(mm²)

Aluminium Copper

DIN hexagonal Deep indent DIN hexagonal

16

25

35

50

70

95

-

25(K)M-12-2

35(K)M-12-2

50(K)M-12-2

70(K)M-12-2

95(K)M-12-2

-

25KM-12-1

35KM-12-1

50(K)M-12-1

70(K)M-12-1

95(K)M-12-1

16(K)M-11-2

25(K)M-11-2

35(K)M-11-2

50(K)M-11-2

70(K)M-11-2

95(K)M-11-2

Orderingpart number

Dia. over core insulation (mm)

min. max.

151SP-A-X+11TL-FA/FAB

151SP-B-X+11TL-FB/FG

151SP-B-X+11TL-GA/GAB

151SP-C-X+11TL-GB/GH

14.6

17.2

19.7

22.2

18.7

21.2

23.0

26.4

Page 11: a Nexans company INTERFACE A CONNE… ·  · 2008-07-092 EUROMOLD COMPANY PRESENTATION While every care is taken to ensure that the information contained in this publication is correct,

11

03/2

008

ApplicationSurge arrester designed to protect 12 and 24 kV class components, including transformers, equipment, cable and accessories from high voltage surges resulting from lightning or switching.

Up to 24 kV

156SAINTERFACE A

SURGE ARRESTER

Technical characteristics •Thissurgearresterisametal

oxide varistor surge arrester in an elbow configuration.•Eacharresteristestedfor

AC withstand and partial discharge prior to leaving the factory.

Surgearrester

type

Nominal discharge

current In (kA)

Rated voltage

Ur(kV)

Max. continuousoperatingvoltageUc (kV)

Steep currentresidual

voltage @ 5 kA[1/20 µs] (kV)

Lightning currentresidual

voltage @ 5 kA[8/20 µs] (kV)

High currentimpulse

withstand(kA)

156SA-12

156SA-15

156SA-18

156SA-21

156SA-24

5

5

5

5

5

15

19

22

26

30

12.5

15.5

18.0

21.0

24.5

62.5

77.0

87.0

101.5

116.5

54.5

69.0

79.0

93.5

108.5

40

40

40

40

40

6/10 (12) kV6.35/11 (12) kV

8.7/15 (17.5) kV12/20 (24) kV

12.7/22 (24) kV

DesignSurge arrester comprising: 1. Bail restraint. 2. Conductive EPDM insert. 3. Type A - 250 A interface as described by CENELEC EN 50180 and 50181. 4. Pin contact. 5. Contact disc. 6. Copper shunt. 7. Metal oxide valve elements. 8. Aluminium spacer. 9. Steel cap. 10. Earth connection. 11. Insulating EPDM layer moulded between the insert and the jacket. 12. Conductive EPDM jacket.

12

11

9

10

5

2

6

3

4

5

8

6

1

7

Page 12: a Nexans company INTERFACE A CONNE… ·  · 2008-07-092 EUROMOLD COMPANY PRESENTATION While every care is taken to ensure that the information contained in this publication is correct,

12

Typical application anddimensions

Ordering instructionsTo order the surge arrester, specify the surge arrester type, as described on previous page.

Example:For a maximum continuous operating voltage (rms) of 21 kV.Order a 156SA-21 surge arrester.

330

K400TE/G orK400TB/Gconnector

K400RTPAreducing tap plug

220 195

156

131

415

Surge arrester156SA-24

Page 13: a Nexans company INTERFACE A CONNE… ·  · 2008-07-092 EUROMOLD COMPANY PRESENTATION While every care is taken to ensure that the information contained in this publication is correct,

13

03/2

008

Ordering instructionsTo order the plug-in termination for 12 or 24 kV, specify PITO-E.The kit includes the bail restraint and 2 brass nuts.

Up to 24 kV - 250 A

Plug-intermination

type

VoltageUr

(kV)

CurrentIr

(A)

Creepage distanceA-B

(mm)

PITO-E

PITO-E

12

24

250

250

510

510

DesignThe plug-in termination is a moulded epoxy insulated part. It meets the type A - 250 Ainterface as described in CENELEC EN 50180 and 50181.

PITO-EPLUG-IN

TERMINATION

Application•Separabletermination

designed to connect overhead lines or bus bars to equipment.•Issuitableforindoorand

outdoor use for medium polluted atmosphere. 6/10 (12) kV

6.35/11 (12) kV8.7/15 (17.5) kV

12/20 (24) kV12.7/22 (24) kV

Technical characteristics Each plug-in termination is testedfor AC withstand prior to leavingthe factory.

Specifications and standardsThe separable termination PITO-E meets the requirements of IEC 60137.

30

235

267

90

35

Dia. 110

M12

10

A

Dia. 70

Dia. 8.2

Dia. 80

Dia. 20

B

In mm.

Page 14: a Nexans company INTERFACE A CONNE… ·  · 2008-07-092 EUROMOLD COMPANY PRESENTATION While every care is taken to ensure that the information contained in this publication is correct,

14

03/2

008

Up to 24 kV - 250 A

Equipmentbushing

type

VoltageUr

(kV)

CurrentIr

(A)

Dimensions (mm)

A B

180AR-1(-G)

K180AR-1(-G)

180AR-2

K180AR-2

180AR-3(-G)

K180AR-3(-G)

12

24

12

24

12

24

250

250

250

250

250

250

222

222

284

284

171

171

106

106

168

168

55

55

180AR-1 /-2 /-3 and 180AR-1-G /-3-GINTERFACE A

EQUIPMENT BUSHING

ApplicationFor use in equipment insulated with oil fluid, typically for transformers, switch gear, capacitors...

6/10 (12) kV6.35/11 (12) kV

8.7/15 (17.5) kV12/20 (24) kV

12.7/22 (24) kV

Design•Theequipmentbushingisa

moulded epoxy insulated part in accordance with CENELEC EN 50180.

The 180AR-2 bushing has a length B outside this standard.•Thestandardbushings,

(K)180AR-1 /-2 /-3, are equipped with 6 tabs for the bail restraint.•The(K)180AR-1-Gand (K)180AR-3-G are equipped

with 4 tabs and 2 threaded inserts M6x1 (-G version).

Technical characteristics Each bushing is tested forAC withstand and partialdischarge prior to leaving thefactory.

Ordering instructionsTo order the equipment bushing, specify the type.The bushings are supplied with an earth lead (/J) or an earth plate (/GS). This earth connection must be specified when ordering.

Specifications and standardsThe plug-in type equipment bushings 180AR-X meet the requirements of CENELEC EN 50180 and IEC 60137.

In mm.

M6x1

11

B

A

28

8

19

Dia. 110

Dia. 75

M10

Minimum oil level: - 12 kV: 40 mm - 24 kV: 50 mm

180AR-1-G /-3-G 180AR-1 /-2 /-3

Page 15: a Nexans company INTERFACE A CONNE… ·  · 2008-07-092 EUROMOLD COMPANY PRESENTATION While every care is taken to ensure that the information contained in this publication is correct,

15

03/2

008

180A-24P-OINTERFACE A

IN-AIR BUSHING

Up to 24 kV - 250 AApplicationFor use in equipment insulated with air, typically for transformers, motors, switch gear, capacitors...

Technical characteristics Each bushing is tested forAC withstand and partialdischarge prior to leaving thefactory.

DesignThe equipment bushing is amoulded epoxy insulated part inaccordance with CENELEC EN50181.

Specifications and standardsThe plug-in type equipment bushings 180A-24P-O meet the requirements of CENELEC EN 50181 and IEC 60137.

6/10 (12) kV6.35/11 (12) kV

8.7/15 (17.5) kV12/20 (24) kV

12.7/22 (24) kV

Equipmentbushing

type

VoltageUr

(kV)

CurrentIr

(A)

Creepage distanceA-B

(mm)

180A-24P-O

180A-24P-O

12

24

250

250

630

630

Ordering instructionsTo order the equipment bushing, specify the type.The bushings are supplied with an earth lead.To include the ring clamp, add:•/B,ifperBritishstandards.•/D,ifperGermanstandards.•/F,ifperFrenchstandards.E.g. 180A-24P-O/D.

In mm.

59

Dia. 80 M10

20

351

250

20

B

Dia. 70

Dia. 110 A

Page 16: a Nexans company INTERFACE A CONNE… ·  · 2008-07-092 EUROMOLD COMPANY PRESENTATION While every care is taken to ensure that the information contained in this publication is correct,

16

03/2

008

FIXINGS FOR EQUIPMENT BUSHINGS

INTERFACE A

180AR-1/J, 180AR-1-G/J, 180AR-2/J, 180AR-3/J and 180AR-3-G/J bushingsDIN 42 538German standards.

180AR-1/GS, 180AR-1-G/GS, 180AR-2/GS, 180AR-3/GS and 180AR-3-G/GS bushingsNFC 52-053French standards.

E DIN 42 538clamp

earth jumper

A DIN 42 538fixing flange

bushing interface

equipment

sealing gasket

NF C 52-053clamp

equipmentconnection

earth plate

tabs for bail restraint

fixing studs

55

M10

Dia. 78

Dia. 123

25

4 fixingstuds

52

M8 orM10

Dia. 78

Dia. 126

27

3 fixingstuds

In mm.

Page 17: a Nexans company INTERFACE A CONNE… ·  · 2008-07-092 EUROMOLD COMPANY PRESENTATION While every care is taken to ensure that the information contained in this publication is correct,

17

180A-24P-O In-air bushing

In mm.

fixing flange BCA-B or BCA-D F

fixing flange BCA-F

earth jumper

bushing interface

gasket

fixing studs and nuts M10

equipment

equipment connection

tabs for bail restraint

BS 2562 stand.: 120 DIN 42 538 stand.: 123

Dia. 94.5

Dia. 111

10

Dia.12

Type BCA-B : BS 2562 British standards

Type BCA-D : DIN 42 538 German standards

4

Dia. 150

10

Dia. 150

126

F

120°

120°

Type BCA-F : NFC 52-053 French standards

4 Dia. 94.5

Dia. 111

Dia.12

52

Dia. 126

Dia. 82

27

M8 or M10

3 fixing studs

55

M10

Dia. 123

Dia. 82

25

4 fixing studs

Page 18: a Nexans company INTERFACE A CONNE… ·  · 2008-07-092 EUROMOLD COMPANY PRESENTATION While every care is taken to ensure that the information contained in this publication is correct,

18

03/2

008

ACCESSORIESINTERFACE A

Up to 24 kVApplicationFor use with connectors and bushings with an interface A as described by CENELEC EN 50180 and 50181.

Technical characteristics All these products, except theearthing plug, are tested forAC withstand and partialdischarge prior to leaving thefactory.

6/10 (12) kV6.35/11 (12) kV

8.7/15 (17.5) kV12/20 (24) kV

12.7/22 (24) kV

250GPEarthing plugIs designed to support and earth connectors with a type A interface when removed from equipment.

Ordering instructionsOrder 250GP for 12 kV or 24 kVapplications.

Ordering instructionsOrder 151SOP for 12 kV orK151SOP for 24 kVapplications.

151SOPStand-off plugIs designed to support and 'dead-end' connectors with a type A interface when removed from equipment.

150DPDead-end plugPlugs into connectors or receptacles to provide 'dead-end' facility.Renders the assembly watertight

Ordering instructionsOrder 150DP for 12 kV orK150DP for 24 kVapplications.

150DRDead-end receptacleFits over a bushing with a type A interface to provide 'dead-end' facility.Renders the assembly watertight.

Ordering instructionsOrder150DR for 12 kV orK150DR for 24 kVapplications.The dead-end receptacle canbe supplied with an earth lead.Order: -/G. E.g. K150DR/G.

Page 19: a Nexans company INTERFACE A CONNE… ·  · 2008-07-092 EUROMOLD COMPANY PRESENTATION While every care is taken to ensure that the information contained in this publication is correct,

19

Kit MTEarthing kit for copper tape screened cablesContains a tinned copper braid (25 mm² - L=500 mm), a tinned copper wire for cleating and water sealing mastic.

Ordering instructionsOrder Kit MT for 12 kV or 24 kVapplications.

200XSeparable cross connectorIs designed to connect four cables of the same or varying sizes or three cables to equipment.For an adapted bail, please refer to the catalogue or contact our representative.

Ordering instructionsOrder 200X for 12 kV orK200X for 24 kVapplications.

1501J3-U-8Three-way junctionProvides a flexible means of connecting two or three cables of the same or varying sizes. For an adapted bail, please refer to the catalogue or contact our representative.

Ordering instructionsOrder 1501J3-U-8 for 12 kV orK1501J3-U-8 for 24 kVapplications.

200TSeparable tee connectorIs designed to connect three cables of the same or varying sizes or two cables to equipment.For an adapted bail, please refer to the catalogue or contact our representative.

Ordering instructionsOrder 200T for 12 kV orK200T for 24 kVapplications.

Page 20: a Nexans company INTERFACE A CONNE… ·  · 2008-07-092 EUROMOLD COMPANY PRESENTATION While every care is taken to ensure that the information contained in this publication is correct,

20

03/2

008

BAIL RESTRAINTSINTERFACE A

ApplicationFor use with connectors, receptacles and bushings with an interface A as described by CENELEC EN 50180 and 50181.

Ordering instructions The type of bail restraint is defined by its intended use with different types of connector, receptacle and/or bushing.To order the bail restraint, specify the type needed.

149BAFor use with:1. (K)158LR elbow connector,2. (K)200T tee connector and3. (K)150DR dead-end receptacle.

148BAFor use with:1. (K)158LR elbow connector and2. (K)150DP dead-end plug.

147BAFor use with:1. (K)152SR straight connector,2. (K)200T tee connector and3. (K)150DR dead-end receptacle.

150BA-B1For use with:1. (K)158LR elbow connector and2. an interface A equipment bushing (shown), 250GP earthing plug, (K)151SOP stand-off plug (shown) or (K)1501J3-U-8 three-way junction.

1

2

3 1

2

3

1

2

1

2

1

2

Page 21: a Nexans company INTERFACE A CONNE… ·  · 2008-07-092 EUROMOLD COMPANY PRESENTATION While every care is taken to ensure that the information contained in this publication is correct,

21

150TB-1For use with:1. (K)200T tee connector and2. an interface A equipment bushing (shown), 250GP earthing plug, (K)151SOP stand-off plug (shown) or (K)1501J3-U-8 three way junction.

151BAFor use with:1. (K)152SR straight connector and2. an interface A equipment bushing (shown), 250GP earthing plug, (K)151SOP stand-off plug (shown) or (K)1501J3-U-8 three-way junction.

153BAFor use with:1. (K)152SR straight connector and2. (K)150DP dead-end plug.

154BA-CS180For use with:1. (K)151SP straight plug and2. (K)150DR dead-end receptacle.

155BA-1For use with:1. 2 x (K)152SR straight connector and2. (K)200T tee connector.

155BA-2 - CS180For use with:1. (K)151SP straight plug and2. (K)158LR elbow connector or 3. (K)200T tee connector.

152BAFor use with:1. (K)150DR dead-end receptacle and2. an interface A equipment bushing (shown) or (K)1501J3-U-8 three-way junction.

1

2

1

2

1

2

1

2

3

11

2

1

2

1

2

1 2

2

1 1

Page 22: a Nexans company INTERFACE A CONNE… ·  · 2008-07-092 EUROMOLD COMPANY PRESENTATION While every care is taken to ensure that the information contained in this publication is correct,

22

201BAFor use with:1. (K)158LR elbow connector and2. (K)200X cross connector.

159BAFor use with:1. 2 x (K)158LR elbow connector and2. (K)200T tee connector

157BA - CS181For use with:1. (K)152SR straight connector and2. (K)151SP straight plug.

158BAFor use with:1. (K)152SR straight connector,2. (K)200T tee connector and3. (K)158LR elbow connector.

156BA-1For use with:1. (K)200T tee connector and2. (K)150DP dead-end plug.

200BAFor use with:1. (K)152SR straight connector and2. (K)200X cross connector.

1

2

1

2

1

2

1

2

1

2 1

2

3 1

Page 23: a Nexans company INTERFACE A CONNE… ·  · 2008-07-092 EUROMOLD COMPANY PRESENTATION While every care is taken to ensure that the information contained in this publication is correct,

23

202BAFor use with:1. (K)152SR straight connector,2. (K)200X cross connector and3. (K)150DR dead-end receptacle.

206BAFor use with:1. (K)152SR straight connector,2. (K)200X cross connector and 3. (K)158LR elbow connector.

207BAFor use with:1. 2 x (K)158LR elbow connector and2. (K)200X cross connector.

208BAFor use with:1. (K)200X cross connector and2. (K)150DR dead-end receptacle.

203BAFor use with:1. (K)158LR elbow connector,2. (K)200X cross connector and3. (K)150DR dead-end receptacle.

204BAFor use with:1. (K)200X cross connector and2. (K)151SP straight plug.

205BAFor use with:1. (K)200X cross connector and2. 2 x (K)152SR straight connector.

1

2 2

2

1 1

1

2

1 2

3 1

2

2

3 1 1

2

3

Page 24: a Nexans company INTERFACE A CONNE… ·  · 2008-07-092 EUROMOLD COMPANY PRESENTATION While every care is taken to ensure that the information contained in this publication is correct,

Additional catalogue information on power cable accessoriesis available by contacting us at the address below:

NexansNetworkSolutionsN.V.-Div.Euromold•ZuidIII,Industrielaan12,B-9320ErembodegemTel.:+32(0)53850211•Fax:+32(0)53831013•www.nexans.com•[email protected]

Catalogue also available on CD-ROM

Distributed by:

03/2