440tb nexans euromold 1250a 11kv bolted tee connectors 240-800sqmm - nexans euromold separable...
TRANSCRIPT
8
Up to 41.5 kV - 630 A
400TBINTERFACE C
TEE CONNECTOR
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
18/30 (36) kV19/33 (36) kV
20.8/36 (41.5) kV
Technical characteristics• The thick conductive EPDM
jacket provides a total safe totouch screen which ensuressafety for personnel.
• Each separable connector istested for AC withstand andpartial discharge prior toleaving the factory.
Separableconnector
type
VoltageUm(kV)
CurrentIr
(A)
Conductor size (mm2)
min. max.
400TB/GK400TB/GM400TB/GP400TB/G
122436
41.5
630630630630
35353535
300300240240
ApplicationSeparable tee shapeconnector (bolted type)designed to connect polymericinsulated cable to equipment(transformers, switch gear,motors, ...).Also connects cable to cablewhen using the appropriatemating parts.
DesignSeparable connectorcomprising:
1. Conductive EPDM insert.2. Conductive EPDM jacket.3. Insulating EPDM layer.4. Type C - 630 A interface
as described by CENELECEN 50180 and 50181.
5. Conductor connector.6. Basic insulating plug (with
VD point).7. Cable reducer.8. Conductive rubber cap.9. Clamping screw.
10. Earthing lead.
The screen break designenables cable outer sheathtesting without removing ordismantling the connector.
Specifications andstandardsThe separable connector 400TBmeets the requirements ofCENELEC HD 629.1 S1.
255 mm220 mm
390 mm
3
2
1
4
56
7
8
10
9
9
For use withother cable types.
Please contact ourrepresentative.
For outdoorapplications.
Order: +MWS.
Components can beordered individually.
For use withcopper tape
screened cables.Order: Kit MT.
For use with Alupe orC 33-226 cables.
Please contact ourrepresentative.
For use in potentiallyexplosive atmospheres
(for 12 kV max.).Order: -/ATEX.
Kit contentsThe complete (K)(M)(P)400TB/Gtee connector kit comprises thefollowing components:
The kit also comprises lubricant, wipers,installation instructions and crimp chart.
Ordering instructionsTo order the tee connector,select the ordering part numberwhich gives you the bestcentring of your core insula-tion diameter and substitute Xusing table X, according to yourconductor size and type.Add a 'K' for use up to 24 kV,an 'M' for use up to 36 kV oradd a 'P' for use up to41.5 kV.
Orderingpart number
Dia. over core insulation (mm)
min. max.
400TB/G-11-X400TB/G-15-X400TB/G-19-X400TB/G-22-X400TB/G-25-X400TB/G-27-X
12.016.020.023.526.528.5
17.522.026.531.032.537.5
Example:The copper wire screened cableis 36 kV, 150 mm2 strandedcopper with a diameter overcore insulation of 32.5 mm.Order a M400TB/G-27-150(K)M-11-2 tee connector kit.
Connector housing(K)(M)(P)400BT/G
Clampingscrew
400TCS
ConductorcontactTBC-X
Basic insulatingplug +
rubber cap(K)(M)(P)400BIPA
Cable reducer411CA-W
(K)(M)(P)400TB/G-W-Xconnector kit
Table W
Table X
Conductor size(mm2)
Aluminium conductor Copper conductor
DINhexagonal
Deepindent
DINhexagonal
35507095120150185240300
35(K)M-12-250(K)M-12-270(K)M-12-295(K)M-12-2
120(K)M-12-2150(K)M-12-2185(K)M-12-2240(K)M-12-2300(K)M-12-2
35KM-12-150KM-12-170KM-12-195KM-12-1120KM-12-1150KM-12-1185KM-12-1240KM-12-1300KM-12-1
35(K)M-11-250(K)M-11-270(K)M-11-295(K)M-11-2
120(K)M-11-2150(K)M-11-2185(K)M-11-2240(K)M-11-2300(K)M-11-2
+ + + + =