BA 062D/06/en/11.0150098514
Valid as of software version:V 1.02.XX (amplifier)V 1.02.XX (communication)
PROline promass 40Coriolis Mass Flow Measuring System
Description of Device Functions
Device Functions PROline Promass 40
2 Endress+Hauser
Device Functions PROline Promass 40 Table of contents
Endress+Hauser 3
Table of contents
1 HART Function matrix PROline Promass 40 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1 The HART function matrix: layout and use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51.2 Operation with the HART protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51.3 Graphical illustration of the HART function matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2 Group ASSIGN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3 Group MEASURING VALUES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4 Group SYSTEM UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5 Group OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6 Group USER INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
7 Group TOTALIZER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
8 Group CURRENT OUTPUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
9 Group PULSE/FREQUENCY OUTPUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
10 Group STATUS OUTPUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
10.1 Information on the response of the status output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2710.2 Switching action of the status output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
11 Group STATUS INPUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
12 Group COMMUNICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
13 Group PROCESS PARAMETER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
14 Group SYSTEM PARAMETER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
15 Group SENSOR DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
16 Group SUPERVISION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
17 Group SIMULATION SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
18 Group SENSOR VERSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
19 Group AMPLIFIER VERSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
20 Index of key words . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Device Functions PROline Promass 40
4 Endress+Hauser
Registered trademarksHART�Registered trademark of HART Communication Foundation, Austin, USA
S-DAT™, FieldTool™Registered trademark of Endress+Hauser Flowtec AG, Reinach, CH
Device Functions PROline Promass 40 1 HART Function matrix PROline Promass 40
Endress+Hauser 5
1 HART Function matrix PROline Promass 40
1.1 The HART function matrix: layout and use
The HART function matrix is a two-level construct: the groups form one level, the functions the other.
The groups are the highest-level grouping of the control options for the measuring device. Each group comprises a number of functions. You select a group in order to access the individual functions for controlling or parameterizing the measuring device.
You will find an overview of the groups in the table of contents on Page 3 and in the graphical representation of the HART Function matrix on Page 6.
You will also find an overview of the functions on Page 6, complete with the page references of the detailed function descriptions.
The descriptions of the individual functions start on Page 7.
1.2 Operation with the HART protocol
The flowmeter can be parameterized and measured values called up by using the HART protocol. You have the following possibilities for the operation:
• The “HART Communicator DXR 275” universal handheld terminal.
• A personal computer using the configuration software “FieldTool” and the “Commubox FXA 191” modem.
For a detailed description of the operation with the HART protocol, please refer to BA061D/06/en “Promass 40 Operating Instructions”.
1 HART Function matrix PROline Promass 40 Device Functions PROline Promass 40
6 Endress+Hauser
1.3 Graphical illustration of the HART function matrix
VA
LUE
SIM
. FR
EQ
. (p
.22
)
DE
NS
ITY
AD
JUS
T
(p.3
5)
MA
X. T
EM
P. M
EA
S.
(p.3
9)
SIM
ULA
TIO
N F
RE
Q.
(p.2
2)
ME
AS
UR
E F
LUID
(p
.34)
MIN
. T
EM
P. M
EA
S.
(p.3
9)
RE
ST.
DAT
A F
AIL
UR
E
(p.4
1)
AC
TU
AL
FR
EQ
.(p
.22)
DE
NS
ITY
SE
T V
ALU
E(p
.34)
DE
NS
ITY
CO
EF
F. C
3(p
.39)
SY
ST
EM
RE
SE
T(p
.41)
VA
LUE
SIM
. CU
RR
. (p
.18)
FAIL
SA
FE
VA
LUE
(p
.21)
VA
L. S
IM. S
WIT
. PN
T
(p.2
6)
ZE
RO
PO
INT
(p
.34)
DE
NS
ITY
CO
EF
F. C
2(p
.39)
ALA
RM
DE
LAY
(p.4
1)
TE
ST
DIS
PLA
Y(p
.14)
SIM
ULA
TIO
N C
UR
R.
(p.1
8)
FAIL
SA
FE
MO
DE
(p.2
1)
SIM
. SW
ITC
H P
OIN
T
(p.2
6)
DE
VIC
E I
D
(p.3
1)
ZE
RO
PO
INT
AD
J.
(p.3
4)
DE
NS
ITY
CO
EF
F. C
1(p
.39)
ER
RO
R C
ATE
GO
RY
(p.4
1)
UN
IT L
EN
GT
H
(p.1
1)
CO
NT
RA
ST
LC
D(p
.14
)
AC
TU
AL
CU
RR
EN
T
(p.1
7)
TIM
E C
ON
STA
NT
(p.2
1)
AC
TU
AL
STA
TU
S(p
.26
)
VA
L. S
IM. S
TAT.
IN
(p.3
0)
MA
NU
FAC
TU
RE
R ID
(p.3
1)
EP
D R
ES
PO
NS
ET
IME
(p
.33
)
DE
NS
ITY
CO
EF
F. C
0(p
.39
)
AS
SIG
N P
RO
C. E
RR
. (p
.40
)
UN
IT V
OLU
ME
(p.1
0)
DIS
PLA
Y D
AM
PIN
G(p
.14)
FAIL
SA
FE
MO
DE
(p.1
5)
FAIL
SA
FE
MO
DE
(p.1
7)
OU
TP
UT
SIG
NA
L (p
.20)
FAIL
SA
FE
MO
DE
(p.2
4)
TIM
E C
ON
STA
NT
(p.2
6)
SIM
. STA
TU
S IN
(p.2
9)
WR
ITE
PR
OT
EC
TIO
N
(p.3
1)
EP
D V
ALU
E L
OW
(p.3
3)
FLO
W D
AM
PIN
G(p
.38)
TE
MP.
CO
EF
F. K
M(p
.39)
ER
RO
R C
ATE
GO
RY
(p
.40)
UN
IT V
OLU
ME
FLO
W(p
.10)
STA
TU
S A
CC
ES
S(p
.12)
DIS
PLA
Y F
OR
MAT
(p
.13)
RE
SE
T T
OTA
L.(p
.15)
TIM
E C
ON
STA
NT
(p.1
7)
VA
LUE
F H
IGH
(p
.20)
OU
TP
UT
SIG
NA
L (p
.24)
OF
F-V
ALU
E
(p.2
5)
MIN
. P
ULS
E W
IDT
H
(p.2
9)
BU
S A
DD
RE
SS
E
(p.3
1)
EM
PT
Y P
IPE
DE
T.(p
.33)
PO
S. Z
ER
O R
ET
UR
N
(p.3
8)
NO
MIN
AL
DIA
ME
TE
R
(p.3
9)
AS
SIG
N S
YS
. ER
RO
R
(p.4
0)
VALU
E S
IM. M
EA
S.
(p.4
2)
SW
-RE
V. S
-DAT
(p.4
3)
SW
-RE
V. I/
O(p
.43)
VO
LUM
E F
LOW
(p.8
)
UN
IT M
AS
S(p
.9)
AC
CE
SS
CO
DE
(p.1
2)
100%
VA
LUE
LIN
E 2
(p.1
3)
OV
ER
FLO
W(p
.15
)
VA
LUE
20
mA
(p.1
6)
EN
D V
ALU
E F
RE
Q.
(p.1
9)
PU
LSE
WID
TH
(p.2
3)
ON
-VA
LUE
(p
.25
)
AC
TIV
E L
EV
EL
(p.2
9)
TAG
DE
SC
RIP
TIO
N(p
.31
)
OF
F-V
AL.
LF
-CU
TOF
F(p
.32
)
ME
AS
UR
ING
MO
DE
(p
.36
)
ZE
RO
PO
INT
(p.3
9)
PR
EV.
SY
S. C
ON
D
(p.4
0)
SIM
. M
EA
SU
RA
ND
(p
.42
)
SE
NS
OR
TY
PE
(p.4
3)
I/O
TY
PE
(p.4
3)
MA
SS
/VO
LUM
E(p
.7)
MA
SS
FLO
W(p
.8)
UN
IT M
AS
S F
LOW
(p.9
)
LAN
GU
AG
E(p
.12)
AS
SIG
N L
INE
2(p
.13)
SU
M(p
.15)
CU
RR
EN
T S
PAN
(p.1
6)
OP
ER
ATIO
N M
OD
E
(p.1
9)
PU
LSE
VA
LUE
(p.2
3)
AS
SIG
N S
TAT
US
(p
.25)
AS
SIG
N S
TAT
US
IN
(p.2
9)
TAG
NA
ME
(p.3
1)
ON
-VA
L. L
F-C
UTO
FF
(p.3
2)
RE
STO
RE
OR
IGIN
AL
(p.3
5)
INS
TL.
DIR
. SE
NS
OR
(p
.36)
K-F
AC
TOR
(p.3
9)
AC
TU
AL
SY
S. C
ON
D.
(p.4
0)
SIM
. FA
ILS
AF
E M
OD
E
(p.4
2)
SE
RIA
L N
UM
BE
R
(p.4
3)
SW
-RE
V. A
MP.
(p
.43)
� � � � � � � � � � � � � � � � � �
AS
SIG
N
(p.7
)
ME
AS
UR
ING
VA
LUE
S
(p.8
)
SY
ST
EM
UN
ITS
(p.9
)
OP
ER
ATIO
N(p
.12
)
US
ER
INT
ER
FAC
E(p
.13
)
TOTA
LIZ
ER
(p.1
5)
CU
RR
EN
T O
UT
PU
T(p
.16
)
PU
LSE
/FR
EQ
. OU
T.
(p.1
9)
STA
TU
S O
UT
PU
T
(p.2
5)
STA
TU
S IN
PU
T(p
.29
)
CO
MM
UN
ICAT
ION
(p
.31
)
PR
OC
ES
S P
AR
AM
. (p
.32
)
SY
ST
EM
PA
RA
M.
(p.3
6)
SE
NS
OR
DAT
A(p
.39
)
SU
PE
RV
ISIO
N(p
.40
)
SIM
ULA
T. S
YS
TE
M
(p.4
2)
SE
NS
OR
VE
RS
ION
(p
.43
)
AM
P. V
ER
SIO
N(p
.43
)
Device Functions PROline Promass 40 2 Group ASSIGN
Endress+Hauser 7
2 Group ASSIGN
Function description ASSIGN
MASS/VOLUME Promass 40 can be configured as mass flowmeter or as volume flowmeter.The measuring mode selection is done in this function.
Options:MASS = the instrument works as mass flowmeterVOLUME = the instrument works as volume flowmeter
Factory setting:MASS
" Caution!The selection in this function has influence on:• the available functions e.g. assignmet of system units (UNIT MASS FLOW or
UNIT VOLUME FLOW)• the available selections within single functions e.g. assignment of status
output (LIMIT MASS or LIMIT VOLUME)
In case the measuring mode is changed, the following functions must be checked and adjust if necessary:
1. In case of changing measuring mode from MASS to VOLUME:• UNIT VOLUME FLOW• UNIT VOLUME• 100% VALUE LINE 2• VALUE 20 mA• VALUE f-max• PULSE VALUE• ASSIGN STATUS• ON-VALUE• OFF-VALUE• ON VALUE LOW FLOW CUT OFF• OFF VALUE LOW FLOW CUT OFF
2. In case of changing measuring mode from VOLUME to MASS:• UNIT MASS FLOW• UNIT MASS• 100% VALUE LINE 2• VALUE 20 mA• VALUE f-max• PULSE VALUE• ASSIGN STATUS• ON-VALUE• OFF-VALUE• ON VALUE LOW FLOW CUT OFF• OFF VALUE LOW FLOW CUT OFF
3 Group MEASURING VALUES Device Functions PROline Promass 40
8 Endress+Hauser
3 Group MEASURING VALUES
Function description MEASURING VALUES
! Note!• The engineering unit of the measured variable shown here can be set in the “SYSTEM UNITS” group.• If the fluid in the pipe flows backwards, a negative sign prefixes the flow reading on the display.
MASS FLOW! Note!This function is not available unless MASS was selected in the MASS/VOLUME function (see Page 7).
Display of the currently measured mass flow.
Display shows:5-digits with floating decimal point, including unit and sign (e.g. 462.87 kg/h; –731.63 lb/min; etc.)
VOLUME FLOW! Note!This function is not available unless VOLUME was selected in the MASS/VOL-UME function (see Page 7).
Display of the currently measured volumetric flow.
Display shows:5-digits with floating decimal point, including unit and sign (e.g. 5.5445 dm3/min; 1.4359 m3/h; –731.63 gal/d; etc.)
Device Functions PROline Promass 40 4 Group SYSTEM UNITS
Endress+Hauser 9
4 Group SYSTEM UNITS
Function description SYSTEM UNITS
You can select the unit for the measured variable in this function group.
UNIT MASS FLOW! Note!This function is not available unless MASS was selected in the MASS/VOLUME function (see Page 7).
Use this function to select the unit for displaying the mass flow (mass/time).
The unit you select here is also valid for:• Current output• Frequency output• Status output (limit value for mass flow, flow direction)• Low flow cut off
Options:Metric:gram → g/s; g/min; g/h; g/daykilogram → kg/s; kg/min; kg/h; kg/dayMetric ton → t/s; t/min; t/h; t/day
US:ounce → oz/s; oz/min; oz/h; oz/daypound → lb/s; lb/min; lb/h; lb/dayton → ton/s; ton/min; ton/h; ton/day
Factory setting:kg/h
UNIT MASS! Note!This function is not available unless MASS was selected in the MASS/VOLUME function (see Page 7).
Use this function to select the unit for displaying the mass.
The unit you select here is also valid for:• Pulse weighting (e.g. kg/p)• Totalizer
Options:Metric → g; kg; t
US → oz; lb; ton
Factory setting:kg
4 Group SYSTEM UNITS Device Functions PROline Promass 40
10 Endress+Hauser
UNIT VOLUME FLOW! Note!This function is not available unless VOLUME was selected in the MASS/VOL-UME function (see Page 7).
Use this function to select the unit for displaying the volume flow.
The unit you select here is also valid for:• Current output• Frequency output• Status output (limit value for volume flow, flow direction)• Low flow cut off
Options:Metric:Cubic centimeter → cm3/s; cm3/min; cm3/h; cm3/dayCubic decimeter → dm3/s; dm3/min; dm3/h; dm3/dayCubic meter → m3/s; m3/min; m3/h; m3/dayMilliliter → ml/s; ml/min; ml/h; ml/dayLiter → l/s; l/min; l/h; l/dayHectoliter → hl/s; hl/min; hl/h; hl/dayMegaliter → Ml/s; Ml/min; Ml/h; Ml/day
US:Cubic centimeter → cc/s; cc/min; cc/h; cc/dayAcre foot → af/s; af/min; af/h; af/dayCubic foot → ft3/s; ft3/min; ft3/h; ft3/dayFluid ounce → oz f/s; oz f/min; oz f/h; oz f/dayGallon → gal/s; gal/min; gal/h; gal/dayMillion gallon → Mgal/s; Mgal/min; Mgal/h; Mgal/dayBarrel (normal fluids: 31.5 gal/bbl) → bbl/s; bbl/min; bbl/h; bbl/dayBarrel (beer: 31.0 gal/bbl) → bbl/s; bbl/min; bbl/h; bbl/dayBarrel (petrochemicals: 42.0 gal/bbl) → bbl/s; bbl/min; bbl/h; bbl/dayBarrel (filling tanks: 55.0 gal/bbl) → bbl/s; bbl/min; bbl/h; bbl/day
Imperial:Gallon → gal/s; gal/min; gal/h; gal/dayMega gallon → Mgal/s; Mgal/min; Mgal/h; Mgal/dayBarrel (beer: 36.0 gal/bbl) → bbl/s; bbl/min; bbl/h; bbl/dayBarrel (petrochemicals: 42.0 gal/bbl) → bbl/s; bbl/min; bbl/h; bbl/day
Factory setting:m3/h
UNIT VOLUME! Note!This function is not available unless VOLUME was selected in the MASS/VOL-UME function (see Page 7).
Use this function to select the unit for displaying the volume.
The unit you select here is also valid for:• Pulse value (e.g. m3/p)• Totalizer
Options:Metric → cm3; dm3; m3; ml; l; hl; Ml
US → cc; af; ft3; oz f; gal; Mgal; bbl (normal fluids); bbl (beer); bbl (petro-chemicals); bbl (filling tanks)
Imperial → gal; Mgal; bbl (beer); bbl (petrochemicals)
Factory setting:m3
Function description SYSTEM UNITS
Device Functions PROline Promass 40 4 Group SYSTEM UNITS
Endress+Hauser 11
UNIT LENGTH Use this function to select the unit for displaying the length unit for the nominal diameter.
The unit you select here is also valid for:• nominal diameter of the sensor (see the NOMINAL DIAMETER function on
Page 7)
Options:MILLIMETERINCH
Factory setting:MILLIMETER
Function description SYSTEM UNITS
5 Group OPERATION Device Functions PROline Promass 40
12 Endress+Hauser
5 Group OPERATION
Function description OPERATION
LANGUAGE Use this function to select the language for all parameters and messages shown on the local display.
Options:ENGLISHDEUTSCHFRANCAISESPANOLTALIANOJAPANESE (syllabary)
ACCESS CODE Certain functions are accessible only for service purposes when a special service code is entered. This code is entered in this function by the Endress+Hauser service technician.
STATUS ACCESS Use this function to check the access status for the function matrix.
Display shows:ACCESS USER
Device Functions PROline Promass 40 6 Group USER INTERFACE
Endress+Hauser 13
6 Group USER INTERFACE
Function description USER INTERFACE
ASSIGN LINE 2 Use this function to define the display value assigned to the additional line (the bottom line of the local display) for display during normal measuring operation.
Options (if the instrument works as mass flowmeter):OFFMASS FLOW IN %TOTALIZERTAG NAMESYSTEM CONDITIONFLOW DIRECTIONMASS FLOW BARGRAPH IN %
Options (if the instrument works as volume flowmeter):OFFVOLUME FLOW IN %TOTALIZERTAG NAMESYSTEM CONDITIONFLOW DIRECTIONVOLUME FLOW BARGRAPH IN %
Factory setting:TOTALIZER
! Note!The first line is always assigned to the flow value selected in the function MASS/VOLUME (see Page 7).
100% VALUE LINE 2! Note!This function is not available unless MASS FLOW IN % or MASS FLOW BAR-GRAPH IN % resp. VOLUME FLOW IN % or VOLUME FLOW BARGRAPH IN % was selected in the ASSIGN LINE 2 function.
Use this function to define the flow value to be shown on the display as the 100% value of the variable assigned to line 2.
User input:5-digit floating-point number
Factory setting:• 10 kg/s (if the instrument works as mass flowmeter)• 10 l/s (if the instrument works as volume flowmeter)
DISPLAY FORMAT Use this function to define the maximum number of digits after the decimal point displayed for the reading in the main line.
Options:XXXXX. - XXXX.X - XXX.XX - XX.XXX -X.XXXX
Factory setting: X.XXXX
! Note!• Note that this setting only affects the reading as it appears on the display, it
has no influence on the accuracy of the system's calculations.• The places after the decimal point as computed by the measuring device
cannot always be displayed, depending on this setting and the engineering unit. In these instances an arrow appears on the display between the meas-ured value and the engineering unit (e.g. 1.2 → kg/h), indicating that the measuring system is computing with more decimal places than can be shown on the display.
6 Group USER INTERFACE Device Functions PROline Promass 40
14 Endress+Hauser
DISPLAY DAMPING Use this function to enter a time constant defining how the display reacts to severely fluctuating flow variables, either very quickly (enter a low time con-stant) or with damping (enter a high time constant).
User input:0...100 s
Factory setting:1 s
! Note!Setting the time constant to 0 seconds switches off damping.
CONTRAST LCD Use this function to optimize display contrast to suit local operating conditions (ambient temperature).
User input:10...100%
Factory setting:50%
TEST DISPLAY Use this function to test the operability of the local display and its pixels.
Options:OFFON
Factory setting:OFF
Test sequence:1. Start the test by selecting ON.
2. All pixels of the main line and additional line are darkened for minimum 0.75 second.
3. Main line and additional line show an “8” in each field for minimum 0.75 second.
4. Main line and additional line show a “0” in each field for minimum 0.75 second.
5. Main line and additional line show nothing (blank display) for minimum 0.75 second.
6. When the test completes the local display returns to its initial state and the setting changes to OFF.
Function description USER INTERFACE
Device Functions PROline Promass 40 7 Group TOTALIZER
Endress+Hauser 15
7 Group TOTALIZER
Function description TOTALIZER
SUM Use this function to view the total for the totalizer measured variable aggre-gated since measuring commenced. The value can be positive or negative.
Display shows:max. 7-digit floating-point number, including sign and unit (e.g. 15467.04 kg)
! Note!• The totalizer response to faults is defined in the FAILSAFE MODE function
(see Page 15).• The unit of the Totalizer depends on the selections in the the MASS/VOLUME
function and in the SYSTEM UNITS group.
OVERFLOW Use this function to view the overflow for the totalizer aggregated since meas-uring commenced.
Total flow quantity is represented by a floating decimal point number consist-ing of max. 7 digits. You can use this function to view higher numerical values (>9,999,999) as overflows. The effective quantity is thus the total of OVER-FLOW plus the value returned by the SUM function.
Example:Reading for 2 overflows: 2 E7 kg (= 20,000,000 kg)The value returned by the SUM function = 196,845.7 kgEffective total quantity = 20,196,845.7 kg
Display shows: Integer with exponent, including sign and unit, e.g. 2 E7 kg
RESET TOTALIZER Use this function to reset the sum and the overflow of the totalizer to zero.
Options:NOYES
Factory setting:NO
! Note!If the device has a status input and is appropriately configured, a reset for the totalizer can also be triggered by a pulse.
FAILSAFE MODE Use this function to define the totalizer response to fault.
Options:STOPThe totalizer is paused until the fault is rectified. The totalizer stops at the last value prior to the occurrence of the error.
ACTUAL VALUEThe totalizer continues to count on the basis of the current measured flow value. The fault is ignored.
HOLD VALUEThe totalizer continues to count the flow on the basis of the last valid flow value (before the fault occurred).
Factory setting:STOP
8 Group CURRENT OUTPUT Device Functions PROline Promass 40
16 Endress+Hauser
8 Group CURRENT OUTPUT
Function description CURRENT OUTPUT
The current output is automatically assigned to mass or volume measurement, depending on the selection in the function MASS/VOLUME (see Page 7).
CURRENT SPAN Use this function to define the current range. You can configure the current output either in accordance with the NAMUR recommendation (max. 20.5 mA) or for a maximum drive of 25 mA.
Auswahl:NAMUR-compliant:4-20 mA HART
not NAMUR-compliant:4-20 mA (25 mA) HART
Factory setting:4-20 mA HART
Scaled limit value Flow
VALUE 20 mA Use this function to assign a flow value to the 20 mA current. In the SYMME-TRY measuring mode (see Page 36), the value assigned in this way applies to both flow directions; in the STANDARD measuring mode it applies only to positive flow (forward flow).
User input:5-digit floating-point number
Factory setting:depends on diameter
! Note!The appropriate unit is taken from the corresponding UNIT function in the group SYSTEM UNITS (see Page 9).
F-x
0xxx
xx-0
5-xx
-xx-
xx-0
04
Device Functions PROline Promass 40 8 Group CURRENT OUTPUT
Endress+Hauser 17
TIME CONSTANT Use this function to enter a time constant defining how the current output signal reacts to severely fluctuating measured variables, either very quickly (enter a low time constant) or with damping (enter a high time constant).
User input:Fixed-point number: 0.01...100.00 s
Factory setting:1.00 s
FAILSAFE MODE For reasons of safety it is advisable to ensure that the current output assumes a predefined state in the event of a fault. The setting you select here affects only the current output. It has no effect on other outputs and the display (e.g. totalizer).
Options:MINIMUM CURRENTIf the Current range is:4-20 mA (25 mA) HART → Output current = 2 mA4-20 mA HART (NAMUR) → Output current = 2 mA
MAXIMUM CURRENTDepending on the setting selected in the CURRENT SPAN function.If the Current range is:4-20 mA (25 mA) HART → Output current = 25 mA4-20 mA HART (NAMUR) → Output current = 22 mA
HOLD VALUEMeasured value output on the basis of the last measured value saved before the fault occurred.
ACTUAL VALUEMeasured value output on the basis of the current flow measurement. The fault is ignored.
Factory setting:MINIMUM CURRENT
ACTUAL CURRENT Use this function to view the computed value of the output current.
Display shows:0.00...25.00 mA
Function description CURRENT OUTPUT
8 Group CURRENT OUTPUT Device Functions PROline Promass 40
18 Endress+Hauser
SIMULATION CURRENT Use this function to activate simulation of the current output.
Options:ONOFF
Factory setting:OFF
! Note!The “SIMULATION CURRENT OUTPUT” message indicates that simulation is active. The measuring device continues to measure while simulation is in progress, i.e. the actual measured values are output correctly via the other outputs.
" Caution!The setting is not saved if the power supply fails.
VALUE SIMULATION CURRENT ! Note!
This function is not available unless the SIMULATION CURRENT function is active (= ON).
Use this function to define a selectable value (e.g. 12 mA) to be output at the current output. This value is used to test downstream devices and the flow-meter itself.
User input:Floating-point number: 0.00...25.00 mA
Factory setting:0.00 mA
" Caution!The setting is not saved if the power supply fails.
Function description CURRENT OUTPUT
Device Functions PROline Promass 40 9 Group PULSE/FREQUENCY OUTPUT
Endress+Hauser 19
9 Group PULSE/FREQUENCY OUTPUT
Function description PULSE/FREQUENCY OUTPUT
The pulse/frequency output is automatically assigned to mass or volume measurement, depending on the selection in the function MASS/VOLUME (see Page 7).
OPERATION MODE Use this function to configure the output as a pulse or frequency output.The functions available in this function group vary, depending on which option you select here.
Options:PULSEFREQUENCY
Factory setting:PULSE
END VALUE FREQUENCY ! Note!
This function is not available unless the FREQUENCY setting was selected in the OPERATION MODE function.
Use this function to define a full scale frequency for the frequency output.You define the associated measured value of the measuring range in the VALUE F HIGH function described on Page 20.
User input:5-digit fixed-point number: 2...1000 Hz
Factory setting:1000 Hz
Example:• VALUE F HIGH = 1000 kg/h, full scale frequency = 1000 Hz: i.e. a frequency
of 1000 Hz is output at a flow of 1000 kg/h.• VALUE F HIGH = 3600 kg/h, full scale frequency = 1000 Hz: i.e. a frequency
of 1000 Hz is output at a flow of 3600 kg/h.
! Note!In the FREQUENCY operating mode the output signal is symmetrical (on/off ratio = 1:1). At low frequencies the pulse duration is limited to a maximum of 10 seconds, i.e. the on/off ratio is no longer symmetrical.
9 Group PULSE/FREQUENCY OUTPUT Device Functions PROline Promass 40
20 Endress+Hauser
VALUE F HIGH! Note!This function is not available unless the FREQUENCY setting was selected in the OPERATION MODE function.
Use this function to assign a flow value to the full scale frequency. Positive and negative values are permissible. You define a measuring range by defining the VALUE F HIGH.
User input:5-digit floating-point number
Factory setting:depends on nominal diameter
Measuring range Flow (forward/backward)� = VALUE F HIGH
! Note!The appropriate unit is taken from the corresponding UNIT function in the group SYSTEM UNITS (see Page 9).
OUTPUT SIGNAL! Note!This function is not available unless the FREQUENCY setting was selected in the OPERATION MODE function.
Use this function to select the polarity of the frequency signal.
Options:PASSIVE - POSITIVEPASSIVE - NEGATIVE
Factory setting:PASSIVE - POSITIVE
PASSIVE:
! Note!For continuous currents up to 25 mA (Imax = 250 mA / 20 ms)
Function description PULSE/FREQUENCY OUTPUT
F-x
0xxx
xx-0
5-xx
-xx-
xx-0
02F
-xxx
xxxx
-04-
xx-x
x-en
-000
PASSIVE-NEGATIVE
conducting conducting
nonconducting
nonconducting
t t
transistor transistor
PASSIVE-POSITIVE
F-x
xxxx
xx-0
5-xx
-xx-
en-0
02
Device Functions PROline Promass 40 9 Group PULSE/FREQUENCY OUTPUT
Endress+Hauser 21
TIME CONSTANT! Note!This function is not available unless the FREQUENCY setting was selected in the OPERATION MODE function.
Use this function to enter a time constant defining how the frequency output signal reacts to severely fluctuating measured variables, either very quickly (enter a low time constant) or with damping (enter a high time constant).
User input:Floating-point number 0.00...100.00 s
Factory setting:0.00 s
FAILSAFE MODE! Note!This function is not available unless the FREQUENCY setting was selected in the OPERATION MODE function.
For safety reasons it is advisable to ensure that the frequency output assumes a predefined state in the event of a fault. Use this function to define this state. The setting you select here affects only the frequency output. It has no effect on other outputs and the display (e.g. totalizer).
Options:FALLBACK VALUEOutput is 0 Hz.
ERROR LEVELOutput is the frequency specified in the FAILSAFE VALUE function.
HOLD VALUEMeasured value output on the basis of the last measured value saved before the fault occurred.
ACTUAL VALUEMeasured value output on the basis of the current flow measurement. The fault is ignored.
Factory setting:FALLBACK VALUE
FAILSAFE VALUE! Note!This function is not available unless FREQUENCY was selected in the OPERA-TION MODE function and ERROR LEVEL was selected in the FAILSAFE MODE function.
Use this function to define frequency that the measuring device outputs in the event of an fault.
User input:max. 4-digit number: 0...1250 Hz
Factory setting:1250 Hz
Function description PULSE/FREQUENCY OUTPUT
9 Group PULSE/FREQUENCY OUTPUT Device Functions PROline Promass 40
22 Endress+Hauser
ACTUAL FREQUENCY! Note!This function is not available unless the FREQUENCY setting was selected in the OPERATION MODE function.
Use this function to view the computed value of the output frequency.
Display shows:0...1250 Hz
SIMULATION FREQUENCY ! Note!
This function is not available unless the FREQUENCY setting was selected in the OPERATION MODE function.
Use this function to activate simulation of the frequency output.
Options:OFFON
Factory setting:OFF
! Note!• The “SIMULATION FREQUENCY OUTPUT” message indicates that
simulation is active.• The measuring device continues to measure while simulation is in progress,
i.e. the currently measured values are output correctly via the other outputs.
" Caution!The setting is not saved if the power supply fails.
VALUE SIMULATION FREQUENCY ! Note!
This function is not available unless FREQUENCY was selected in the OPERA-TION MODE function and the VALUE SIMULATION FREQUENCY function is active (= ON).
Use this function to define a selectable frequency value (e.g. 500 Hz) to be output at the frequency output. This value is used to test downstream devices and the flowmeter itself.
User input:0...1250 Hz
Factory setting:0 Hz
" Caution!The setting is not saved if the power supply fails.
Function description PULSE/FREQUENCY OUTPUT
Device Functions PROline Promass 40 9 Group PULSE/FREQUENCY OUTPUT
Endress+Hauser 23
PULSE VALUE! Note!This function is not available unless the PULSE setting was selected in the OPERATION MODE function.
Use this function to define the flow at which a pulse is triggered. These pulses can be totaled by an external totalizer, and the total flow quantity since meas-uring started can be registered in this way.
User input:5-digit floating-point number
Factory setting:depends on nominal diameter
! Note!The appropriate unit is taken from the corresponding UNIT function in the group SYSTEM UNITS (see Page 9).
PULSE WIDTH! Note!This function is not available unless the PULSE setting was selected in the OPERATION MODE function.
Use this function to enter the pulse width of the output pulses.
User input:0.5...2000 ms
Factory setting:100 ms
Pulse output is always with the pulse width (B) entered in this function. The intervals (P) between the individual pulses are automatically configured. How-ever, they must at least correspond to the pulse width (B = P).
B = Pulse width entered (the illustration applies to positive pulses)P= Intervals between the individual pulses
! Note!When entering the pulse width, select a value that can still be processed by an external totalizer (e.g. mechanical totalizer, PLC, etc.).
" Caution!If the pulse number or frequency resulting from the pulse value entered, (see function PULSE VALUE on Page 23), and from the current flowis too large to maintain the pulse width selected (interval P is smaller than the pulse width B entered), a system error message (pulse memory) is generated after buffering/balancing time.
Function description PULSE/FREQUENCY OUTPUT
B=P
B
PP
B
B< P
F06-xxxxxxxx-05-xx-xx-xx-012
9 Group PULSE/FREQUENCY OUTPUT Device Functions PROline Promass 40
24 Endress+Hauser
OUTPUT SIGNAL! Note!This function is not available unless the PULSE setting was selected in the OPERATION MODE function.
Use this function to configure the output in such a way that it matches an external totalizer, for example. The direction of the pulses can be selected here, if this feature is supported by the application.
Options:PASSIVE - POSITIVEPASSIVE - NEGATIVE
Factory setting:PASSIVE - POSITIVE
PASSIVE:
! Note!For continuous currents up to 25 mA (Imax = 250 mA / 20 ms)
FAILSAFE MODE! Note!This function is not available unless the PULSE setting was selected in the OPERATION MODE function.
For safety reasons it is advisable to ensure that the pulse output assumes a predefined state in the event of a fault. Use this function to define this state. The setting you select here affects only the pulse output. It has no effect on other outputs and the display (e.g. totalizer).
Options:FALLBACK VALUEOutput is 0 pulse.
HOLD VALUEMeasured value output on the basis of the last measured value saved before the fault occurred.
ACTUAL VALUEMeasured value output on the basis of the current flow measurement. The fault is ignored.
Factory setting:FALLBACK VALUE
Function description PULSE/FREQUENCY OUTPUT
F-x
xxxx
xx-0
4-xx
-xx-
en-
000
B B
PASSIVE-NEGATIVEpulses
conducting conducting
nonconducting
nonconducting
t t
transistor transistor
PASSIVE-POSITIVEpulses
B = Pulse width
F-x
xxxx
xx-0
5-xx
-xx-
en-0
01
Device Functions PROline Promass 40 10 Group STATUS OUTPUT
Endress+Hauser 25
10 Group STATUS OUTPUT
Function description STATUS OUTPUT
This group is not available unless the measuring device is fitted with a status output.
ASSIGN STATUS Use this function to assign a switching function to the status output.
Options:OFFON (operation)FAULT MESSAGENOTICE MESSAGEFAULT MESSAGE or NOTICE MESSAGEEMPTY PIPE DETECTION (only if function is active)FLOW DIRECTIONLIMIT MASS FLOW (if the instrument works as mass flowmeter)LIMIT VOLUME FLOW (if the instrument works as volume flowmeter)
Factory setting:FAULT MESSAGE
! Note!• The behaviour of the status output is of the quiescent-current type, in other
words the output is closed (transistor conductive) when normal, error-free measuring is in progress.
• Please read and comply with the information on the switching characteristics of the status output (see Page 27, 28).
• If you select OFF, the only function shown in this function group is this func-tion, in other words ASSIGN STATUS.
ON-VALUE! Note!This function is not available unless LIMIT MASS FLOW, LIMIT VOLUME FLOW or FLOW DIRECTION was selected in the ASSIGN STATUS function.
Use this function to assign a value to the switch-on point (status output conductive). The value can be greater or less than the switch-off point.Positive and negative values are permissible.
User input:5-digit floating-point number
Factory setting:0 [kg/h] or 0 [m3/h]
OFF-VALUE! Note!This function is not available unless LIMIT MASS FLOW or LIMIT VOLUME FLOW was selected in the ASSIGN STATUS function.
Use this function to assign a value to the switch-off point (status output not conductive). The value can be greater or less than the switch-on point.Positive and negative values are permissible.
User input:5-digit floating-point number
Factory setting:0 [kg/h] or 0 [m3/h]
10 Group STATUS OUTPUT Device Functions PROline Promass 40
26 Endress+Hauser
TIME CONSTANT Use this function to enter a time constant defining how the status output reacts to severely fluctuating measured variables, either very quickly (enter a low time constant) or with damping (enter a high time constant). The purpose of damping, therefore, is to prevent the status output changing state continuously in response to fluctuations in flow.
User input:5-digit floating-point number: 0.00...100.00 s
Factory setting:0.00 s
ACTUAL STATUS Use this function to check the current status of the status output.
Display shows:NOT CONDUCTIVECONDUCTIVE
SIMULATIONSWITCH POINT
Use this function to activate simulation of the status output.
Options:OFFON
Factory setting:OFF
! Note!• The “SIMULATION STATUS OUTPUT” message indicates that simulation is
active.• The measuring device continues to measure while simulation is in progress,
i.e. the current measured values are output correctly via the other outputs.
" Caution!The setting is not saved if the power supply fails.
VALUE SIMULATION SWITCH POINT ! Note!
This function is not available unless the SIMULATION SWITCH POINT function is active (= ON).
Use this function to define the switching response of the status output during the simulation. This value is used to test downstream devices and the flow-meter itself.
User input:NOT CONDUCTIVECONDUCTIVE
Factory setting:NOT CONDUCTIVE
" Caution!The setting is not saved if the power supply fails.
Function description STATUS OUTPUT
Device Functions PROline Promass 40 10 Group STATUS OUTPUT
Endress+Hauser 27
10.1 Information on the response of the status output
GeneralIf you have configured the status output for “LIMIT” or “FLOW DIRECTION”, you can define the requisite switching points in the ON-VALUE and OFF-VALUE functions. When the measured variable in question reaches one of these predefined values, the status output signal switches as shown in the illustrations below.
Status output configured for direction of flowThe value you entered in the ON-VALUE function defines the switching points for the positive and negative directions of flow. If, for example, the switching point you define is = 1 kg/h, the status output is not conductive at –1 kg/h and is conductive at +1 kg/h. Set the switching point to 0 if your process calls for direct switchover (no switching hysteresis).If low flow cut off is used, it is advisable to set hysteresis to a value greater than or equal to the low flow cut off rate.
Switch-off / switch-on point
a = Status output conductiveb = Status output not conductive
Status output configured for limit valueThe status output signal switches as soon as the measured variable falls below or exceeds a defined switching point. Application: Monitoring flow or process-related boundary conditions.
Measured variable
� = ON ≤ OFF-VALUE (maximum safety)� = ON > OFF-VALUE (minimum safety)� = Status output off (not conductive)
F-x
xxxx
xx-0
5-xx
-xx-
xx-0
04F
-xxx
xxxx
-05-
xx-x
x-xx
-00
5
10 Group STATUS OUTPUT Device Functions PROline Promass 40
28 Endress+Hauser
10.2 Switching action of the status output
Function State Open Collector (Transistor)
ON (operation) System in measuring mode
conductive
System not in measuring mode (power supply failure) not
conductive
Fault message System OK
conductive
(System or process error)Fault � Error response of outputs, inputs and totalizer
not conductive
Notice message System OK
conductive
(System or process error)Fault � Continuation of measuring
not conductive
Fault messageorNotice message
System OK
conductive
(System or process error)Fault � Response to error or Info � Continuation of measuring
not conductive
Empty pipe detection (EPD)
Fluid density above response level, e.g. full measuring tube
conductive
Fluid density below response level, e.g. empty measuring tube
not conductive
Flow direction forward
conductive
reversenot
conductive
Limit value• mass flow• volume flow
Limit value not overshot or undershot
conductive
Limit value overshot or undershot not
conductive
Device Functions PROline Promass 40 11 Group STATUS INPUT
Endress+Hauser 29
11 Group STATUS INPUT
Function description STATUS INPUT
This group is not available unless the measuring device is fitted with a status input I/O module.
ASSIGN STATUS INPUT Use this function to assign a switching function to the status input.
Options:OFFRESET TOTALIZERPOSITIVE ZERO RETURNZEROPOINT ADJUSTMENT
Factory setting:OFF
! Note!Positive zero return is active as long as the active level is available at the status input (continuous signal). All other assignments react to a change in level (pulse) at the status input.
ACTIVE LEVEL Use this function to define whether the assigned function (see ASSIGN STATUS INPUT function) is released when the signal level is present (HIGH) or not present (LOW).
Options:HIGHLOW
Factory setting:HIGH
MINIMUM PULSE WIDTH
Use this function to define a minimum width which the input pulse must achieve in order to trigger the defined switching function.
User input:20...100 ms
Factory setting:50 ms
SIMULATION STATUS INPUT
Use this function to activate simulation of the status input, in other words to trigger the function assigned to the status input (see the ASSIGN STATUS INPUT function on Page 29).
Options: OFFON
Factory setting:OFF
! Note!The “SIMULATION STATUS INPUT” message indicates that simulation is active.
" Caution!The setting is not saved if the power supply fails.
11 Group STATUS INPUT Device Functions PROline Promass 40
30 Endress+Hauser
VALUE SIMULATION STATUS INPUT ! Note!
This function is not available unless the SIMULATION STATUS INPUT function is active (= ON).
Use this function to select the level to be assumed at the status input during the simulation.
Options:HIGHLOW
Factory setting:LOW
" Caution!The setting is not saved if the power supply fails.
Function description STATUS INPUT
Device Functions PROline Promass 40 12 Group COMMUNICATION
Endress+Hauser 31
12 Group COMMUNICATION
Function description COMMUNICATION
TAG NAME Use this function to enter a tag name for the measuring device.
User input:max. 8-character text, permissible: A-Z, 0-9, +,–, punctuation marks
Factory setting:“_ _ _ _ _ _ _ _” (without text)
TAG DESCRIPTION Use this function to enter a tag description for the measuring device.
User input:max. 16-character text, permissible: A-Z, 0-9, +,–, punctuation marks
Factory setting:“_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _” (without text)
BUS ADDRESSE Use this function to define the address for the exchange of data with the HART protocol.
User input:0...15
Factory setting:0
! Note!Addresses 1...15: a constant 4 mA current is applied.
WRITE PROTECTION Use this function to check whether the measuring device can be write accessed.
Display shows:OFF = Data exchange is possible
ON = Data exchange disabled (an activation of the write protection is at present not available)
Factory setting:OFF
MANUFACTURER ID Use this function to view the manufacturer ID in decimal numerical format.
Display shows:17 (≅ 11 hex) for Endress+Hauser
DEVICE ID Use this function to view the device ID in hexadecimal numerical format.
Display shows:53 (≅ 83 dez) for Promass 40
13 Group PROCESS PARAMETER Device Functions PROline Promass 40
32 Endress+Hauser
13 Group PROCESS PARAMETER
Function description PROCESS PARAMETER
ON VALUE LOW FLOW CUT OFF
Use this function to assign the on value for the low flow cut off.Low flow cut off is active if the setting is a value not equal to 0. The sign of the flow value is highlighted on the display to indicate that low flow cut off is active.
User input:5-digit floating-point number
Factory setting:depends on nominal diameter
! Note!The appropriate unit is taken from the corresponding UNIT function in the group SYSTEM UNITS (see Page 9).
OFF VALUE LOW FLOW CUT OFF
Use this function to enter the switch-off point for low flow cut off.Enter the switch-off point as a positive hysteresis value from the switch-on point.
User input:Integer 0...100%
Factory setting:50%
Example:
Q = Flow [volume/time]t = TimeH = Hysteresisa = ON VALUE LOW FLOW CUT OFF = 200 g/hb = OFF VALUE LOW FLOW CUT OFF = 10%c = Low flow cut off active1 = Low flow cut off is switched on at 200 g/h2 = Low flow cut off is switched off at 220 g/h
1
c c
Q
t
1
2b
a
2
H
F06
-80x
xxxx
x-05
-xx-
xx-x
x-00
7
Device Functions PROline Promass 40 13 Group PROCESS PARAMETER
Endress+Hauser 33
EMPTY PIPE DETECTION (EPD)
Use this function to activate the empty pipe detection (EPD). With empty measuring tubes the density of the fluid falls below a specified value (see EPD VALUE LOW function).
Options: OFFON
Factory setting:OFF
" Caution!• Select a correspondingly low EPD responce value so that the difference to
the effective density of the fluid is sufficiently large enough.This ensures that totally empty measuring tubes and not partially filled ones are detected.
• For gas measurement we strongly recommend to switch off empty pipe detection.
EPD VALUE LOW! Note!This function is not available unless the ON selection was selected in the EMPTY PIPE DETECTION function.
Use this function to set a lower threshold for the fluid density value, in order to detect possible problems in the process indicated by too low density.
User input:5-digit floating-point number
Factory setting:0.2000 g/cc
EPD RESPONSE TIME Use this function to enter the time span for which the criteria for an empty pipe have to be satisfied without interruption before a notice message or fault message is generated.
User input:Fixed-point number: 1.0...60.0 s
Factory setting:1.0 s
Function description PROCESS PARAMETER
13 Group PROCESS PARAMETER Device Functions PROline Promass 40
34 Endress+Hauser
ZERO POINT ADJUST This function enables a zero point adjustment to be automatically carried out. The new zero point determined by the measuring system is adopted by the function ZERO POINT (see Page 39).
User input:CANCELSTART
Factory setting:CANCEL
" Caution!Before carrying out the calibration, please refer to BA061D/06/en “Promass 40 Operating Instructions” where a detailed description of the zero point adjust-ment is given.
! Note!• Programming is locked during zero point adjustment and the display shows:
“ZERO ADJUST RUNNING”.• If the zero point adjustment is not possible, e.g. with a flow velocity
> 0.1 m/s, or has been cancelled, then the alarm message “ZERO ADJUST NOT POSSIBLE” is shown on the display.
• If the Promass 40 measuring electronics are fitted with a status input, then the zero point can also be activated by using this input.
ZERO POINT This function shows the actual zero point.
DENSITY SET VALUE In this function, enter the density set value of the particular fluid for which you want to carry out a field density adjustment.
User input:5-digit number with floating decimal point, incl. units(corresponding to 0.1...5.9999 kg/l)
! Note!• The preset density entered here should not vary from the actual fluid density
by more than ±10%.• The appropriate unit is always g/cc ≅ kg/l.
MEASURE FLUID In this function the actual density of the fluid is determined for the density adjustment.
Options:CANCELSTART
Function description PROCESS PARAMETER
Device Functions PROline Promass 40 13 Group PROCESS PARAMETER
Endress+Hauser 35
DENSITY ADJUST With this function a density adjustment can be carried out on site.The density set value will thus be recalculated and stored. This ensures that the values dependent on density calculations (e.g. volume flow) are as accurate as possible.
" Caution!Before carrying out a density adjustment, please refer to BA061D/06/en “Promass 40 Operating Instructions” where a detailed description of the density adjustment is given.
! Note!The density adjustment is only required if the characteristics of the fluid are outside the reference conditions under which the flowmeter has been calibrated at the factory.
User input:CANCELDENSITY ADJUST
Factory setting:CANCEL
RESTORE ORIGINAL With this function the original density coefficient determined at the factory are restored.
Options:NOYES
Factory setting:NO
Function description PROCESS PARAMETER
14 Group SYSTEM PARAMETER Device Functions PROline Promass 40
36 Endress+Hauser
14 Group SYSTEM PARAMETER
Function description SYSTEM PARAMETER
INSTALLATION DIRECTION SENSOR
Use this function to reverse the sign of the measured variable, if necessary.
Options:NORMAL (flow as indicated by the arrow)INVERSE (flow opposite to direction indicated by the arrow)
Factory setting:NORMAL
! Note!Ascertain the actual direction of fluid flow with reference to the direction indicated by the arrow on the sensor (nameplate).
MEASURING MODE Use this function to define the measuring mode for all outputs and the internal totalizer.
Options:STANDARDSYMMETRY
Factory setting:STANDARD
The responses of the individual outputs and the internal totalizer in each of the measuring modes are described in detail below:
Current and frequency outputSTANDARDThe output signals of the current and frequency output are proportional to the measured variable.The flow components outside the scaled measuring range (between Q = 0 � and the VALUE 20 mA or VALUE F HIGH �) are not taken into account for sig-nal output, but a message “CURRENT OUTPUT AT FULL SCALE VALUE” or “FREQUENCY OUTPUT AT FULL SCALE VALUE” is issued.
Example for current output:
SYMMETRYThe output signals of the current and frequency output are independent of the direction of flow (absolute amount of the measured variable).The “VALUE 20 mA” or “VALUE F HIGH” � (e.g. backflow) corresponds to the mirrored VALUE 20 mA or VALUE F HIGH � (e.g. flow).
Example for current output:
Q
20
4
0➀ ➁
mAF
-xxx
xxxx
-05-
xx-x
x-xx
-003
Q
20
0➀ ➁➂
mA
4 F-x
xxxx
xx-0
5-xx
-xx-
xx-0
07
Device Functions PROline Promass 40 14 Group SYSTEM PARAMETER
Endress+Hauser 37
MEASURING MODE(Continuation)
Pulse outputSTANDARDOnly positive flow components are totaled. Negative components are not taken into account.
SYMMETRYPositive and negative flow components are taken into account.
! Note!The direction of flow can be output via the configurable status output.
Status output
! Note!Only if in the ASSIGN STATUS function the LIMIT option is selected.
STANDARDThe status output signal switches at the defined switching points.
SYMMETRYThe status output signal switches at the defined switching points, irrespective of the sign. In other words, if you define a switching point with a positive sign the status output signal switches as soon as the value is reached in the nega-tive direction (negative sign) (see illustration).
Example for the SYMMETRY measuring mode:Switch-on point Q = 4Switch-off point Q = 10
� = Status output switched on (conductive)� = Status output switched off (non-conductive)
TotalizerSTANDARDOnly positive flow components are registered.
SYMMETRYThe positive and negative flow components are balanced. In other words, net flow in the flow direction is registered.
Function description SYSTEM PARAMETER
0
- 4
- 10
4
10
Q
t
➀ ➀ ➀➁ ➁F
-xxx
xxxx
-05-
xx-x
x-xx
-005
14 Group SYSTEM PARAMETER Device Functions PROline Promass 40
38 Endress+Hauser
POSITIVE ZERO RETURN
Use this function to interrupt evaluation of measured variables.This is necessary when a piping system is being cleaned, for example.The setting acts on all functions and outputs of the measuring device.
Options:OFFON (signal output is set to zero flow value)
Factory setting:OFF
FLOW DAMPING! Note!System damping acts on all functions and outputs of the measuring device.
Using the interference blanking (= time constant for exponential filter) the sensitivity of the flow measurement signal can be reduced with respect to transient flows and interference peaks; e.g. with fluid containing solids or gas bubbles.
User input:0.00...100 seconds (in 10 ms steps)
0.00 seconds = OFF100 seconds = extremly high damping
Factory setting:0.00 seconds
Function description SYSTEM PARAMETER
Device Functions PROline Promass 40 15 Group SENSOR DATA
Endress+Hauser 39
15 Group SENSOR DATA
Function description SENSOR DATA
All sensor data, including nominal diameter, calibration factor, and zero point, are set at the factory. All the sensor's parameter settings are saved on the S-DAT memory chip.
K-FACTOR This function shows the current calibration factor for the sensor.
Factory setting:depends on nominal diameter and calibration
ZERO POINT This function shows the current zero-point correction value for the sensor.
Factory setting:depends on calibration
NOMINAL DIAMETER This function shows the nominal diameter for the sensor.
Factory setting:depends on the size of the sensor
TEMPERATURE COEFFICIENT KM
This function shows the temperature coefficient KM.
DENSITY COEFFICIENT C 0
This function shows the actual density coefficient C 0.
" Caution!A density adjustment can alter the calibration value of this coefficient.
DENSITY COEFFICIENT C 1
This function shows the actual density coefficient C 1.
" Caution!A density adjustment can alter the calibration value of this coefficient.
DENSITY COEFFICIENT C 2
This function shows the actual density coefficient C 2.
" Caution!A density adjustment can alter the calibration value of this coefficient.
DENSITY COEFFICIENT C 3
This function shows the actual density coefficient C 3.
" Caution!A density adjustment can alter the calibration value of this coefficient.
MINIMAL TEMPERATURE MEASURED
This function shows the lowest fluid temperature measured.
MAXIMUM TEMPERATURE MEASURED
This function shows the highest fluid temperature measured.
16 Group SUPERVISION Device Functions PROline Promass 40
40 Endress+Hauser
16 Group SUPERVISION
Function description SUPERVISION
ACTUAL SYSTEM CONDITION
Use this function to check the current system status.
Display shows:“SYSTEM OK” or the fault / notice message with the highest priority.
PREVIOUS SYSTEM CONDITION
Use this function to view the fifteen most recent fault and notice messages since measuring last started.
Display shows:The 15 most recent fault or notice messages.
ASSIGN SYSTEM ERROR
Use this function to view all system messages and the associated error categories (fault message or notice message). If you select a single system fault you can change its error category.
Display shows:List of system errors
! Note!• Press “ENTER” twice to call the ERROR CATEGORY function.• Use “ESC” or select CANCEL in the system error list to exit the function.
ERROR CATEGORY Use this function to define whether a system error triggers a notice message or a fault message. If you select “FAULT MESSAGES”, all outputs respond to a fault in accordance with their defined error-response patterns.
Options:NOTICE MESSAGES (display only)FAULT MESSAGES (outputs and display)
! Note!• Press “ENTER” twice to call the ASSIGN SYSTEM ERROR function.• Use “ESC” to exit the function.
ASSIGN PROCESS ERROR
Use this function to view all process errors and the associated error categories (fault message or notice message). If you select a single process error you can change its error category.
Display shows:List of process errors
! Note!• Press “ENTER” twice to call the ERROR CATEGORY function.• Use “ESC” or select CANCEL in the process error list to exit the function.
Device Functions PROline Promass 40 16 Group SUPERVISION
Endress+Hauser 41
ERROR CATEGORY Use this function to define whether a process error triggers a notice message or a fault message. If you select “FAULT MESSAGES”, all outputs respond to a fault in accordance with their defined error-response patterns.
Options: NOTICE MESSAGES (display only)FAULT MESSAGES (outputs and display)
! Note!• Press “ENTER” twice to call the ASSIGN PROCESS ERROR function.• Use “ESC” to exit the function.
ALARM DELAY Use this function to define a time span for which the criteria for an error have to be satisfied without interruption before an error or notice message is generated.
Depending on the setting and the type of fault, this suppression acts on:• Display• Current output• Frequency output• Status output
User input:0...100 s (in steps of one second)
Factory setting:0 s
" Caution!If this function is activated fault and notice messages are delayed by the time corresponding to the setting before being forwarded to the higher-order con-troller (process controller, etc.). It is therefore imperative to check in advance in order to make sure whether a delay of this nature could affect the safety requirements of the process. If fault and notice messages cannot be sup-pressed, a value of 0 seconds must be entered here.
SYSTEM RESET Use this function to perform a reset of the measuring system.
Options:NORESTART SYSTEM (restart without interrupting line supply)
Factory setting:NO
RESTORE DATA FAIL-URE
Use this function to rectify errors in the EEPROM (Error message AMP SW-EEPROM, # 012). The EEPROM is divided into a number of blocks. Only blocks which an error has occurred are shown. Select the block in question and press “ENTER” to clear the error.
! Note!When you clear an error in a block, the parameters of the block you select are reset to their factory settings.
Function description SUPERVISION
17 Group SIMULATION SYSTEM Device Functions PROline Promass 40
42 Endress+Hauser
17 Group SIMULATION SYSTEM
Function description SIMULATION SYSTEM
SIMULATION FAILSAFE MODE
Use this function to set all inputs, outputs and totalizer to their defined fault response modes, in order to check whether they respond correctly. During this time, the words “SIMULATION FAILSAFE MODE” appear on the display.
Options:OFFON
Factory setting:OFF
" Caution!• The measuring device cannot be used for measuring while this simulation is
in progress.• The setting is not saved if the power supply fails.
SIMULATION MEASURAND
Use this function to set all inputs, outputs and totalizer to their defined flow-response modes, in order to check whether they respond correctly. During this time, the words “SIMULATION MEASURAND” appear on the display.
Options:OFFMASS (if the instrument works as mass flowmeter)VOLUME (if the instrument works as volume flowmeter)
Factory setting:OFF
" Caution!• The measuring device cannot be used for measuring while this simulation is
in progress.• The setting is not saved if the power supply fails.
VALUE SIMULATION MEASURAND ! Note!
This function is not available unless the SIMULATION MEASURAND function is active.
Use this function to define a selectable value (e.g. 12 kg/s). This value is used to test downstream devices and the flowmeter itself.
User input:5-digit floating-point number
Factory setting:0
" Caution!The setting is not saved if the power supply fails.
Device Functions PROline Promass 40 18 Group SENSOR VERSION
Endress+Hauser 43
18 Group SENSOR VERSION
19 Group AMPLIFIER VERSION
Function description SENSOR VERSION
SERIAL NUMBER Use this function to view the serial number of the sensor.
SENSOR TYPE Use this function to view the sensor type.
SOFTWARE REVISION NUMBER S-DAT
Use this function to view the software revision number of the S-DAT.
Function description AMPLIFIER VERSION
SOFTWARE REVISION NUMBER AMPLIFIER
Use this function to view the software revision number of the amplifier.
I/O TYPE Use this function to view the I/O type (input/output type).
SOFTWAREREVISION NUMBER I/O
Use this function to view the software revision number of the I/O module.
19 Group AMPLIFIER VERSION Device Functions PROline Promass 40
44 Endress+Hauser
Device Functions PROline Promass 40 20 Index of key words
Endress+Hauser 45
20 Index of key words
AAccess code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Active Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Actual
Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Status output . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26System condition . . . . . . . . . . . . . . . . . . . . . . . . 40
Alarm delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41Assign
Display line 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Mass/Volume . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Process error . . . . . . . . . . . . . . . . . . . . . . . . . . . 40Status input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Status output . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25System error . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
CContrast LDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Current
Span . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Current Output
Actual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Failsafe mode . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Span . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Time constant . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Value Simulation . . . . . . . . . . . . . . . . . . . . . . . . . 18Value 20 mA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
DDensity
Adjust . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35Coefficient
C 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39C 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39C 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39C 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Set value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34Device ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Display
Damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
EEmpty pipe detection
EPD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33Low value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33Response time . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
End value frequency . . . . . . . . . . . . . . . . . . . . . . . . . 19Error category
Process error . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41System error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
FFailsafe mode
Current output . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Pulse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Simulation system . . . . . . . . . . . . . . . . . . . . . . . . 42Totalizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Failsafe valueFrequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Flow Damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38Frequency
Actual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22End value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Failsafe mode . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Failsafe value . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Time constant . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Value f high . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Value Simulation . . . . . . . . . . . . . . . . . . . . . . . . . 22
GGroup
Amplifier Version . . . . . . . . . . . . . . . . . . . . . . . . . 43Assign Mass/Volume . . . . . . . . . . . . . . . . . . . . . . . 7Communication . . . . . . . . . . . . . . . . . . . . . . . . . . 31Current output . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Measuring values . . . . . . . . . . . . . . . . . . . . . . . . . . 8Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Process parameter . . . . . . . . . . . . . . . . . . . . . . . 32Pulse/Frequency output . . . . . . . . . . . . . . . . . . . . 19Sensor data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39Sensor Version . . . . . . . . . . . . . . . . . . . . . . . . . . . 43Simulation system . . . . . . . . . . . . . . . . . . . . . . . . 42Status input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Status output . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Supervision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40System parameter . . . . . . . . . . . . . . . . . . . . . . . . 36System units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Totalizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15User interface . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
20 Index of key words Device Functions PROline Promass 40
46 Endress+Hauser
HHART Funktion matrix
Graphical illustration . . . . . . . . . . . . . . . . . . . . . . . 6Layout and use . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
HART protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
IInstallation direction sensor . . . . . . . . . . . . . . . . . . . 36
KK-Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
LLanguage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12LCD Contrast . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Low flow cut off
Off-value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32On-value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
MManufacturer ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Mass flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Maximal temperature measured . . . . . . . . . . . . . . . 39Measured fluid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34Measuring mode . . . . . . . . . . . . . . . . . . . . . . . . . . . 36Minimal temperature measured . . . . . . . . . . . . . . . . 39Minimum pulse width . . . . . . . . . . . . . . . . . . . . . . . . 29
NNominal Diameter . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
OOff-value
Low flow cut off . . . . . . . . . . . . . . . . . . . . . . . . . . 32Status output . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
On-valueLow flow cut off . . . . . . . . . . . . . . . . . . . . . . . . . . 32Status output . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
OperationMode Pulse-/Freq.-output . . . . . . . . . . . . . . . . . . 19
Output signalFrequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Pulse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
OverflowTotalizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
PPositive zero return . . . . . . . . . . . . . . . . . . . . . . . . . 38Previous system condition . . . . . . . . . . . . . . . . . . . 40Process Error
Assign . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40Error category . . . . . . . . . . . . . . . . . . . . . . . . . . 41
PulseFailsafe mode . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Width . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
RReset
System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41Totalizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
RestoreData Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41Original . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
SSensor type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43Serial number sensor . . . . . . . . . . . . . . . . . . . . . . . 43Simulation
Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Measurand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42Status input . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Switch point . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
SoftwareRevision number
Amplifier . . . . . . . . . . . . . . . . . . . . . . . . . . . 43I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43S-DAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
StatusInput
Active level . . . . . . . . . . . . . . . . . . . . . . . . . 29Assign . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Minimum pulse width . . . . . . . . . . . . . . . . . 29Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . 29Value Simulation . . . . . . . . . . . . . . . . . . . . . 30
OutputActual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Assign . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Off-Value . . . . . . . . . . . . . . . . . . . . . . . . . . 25On-Value . . . . . . . . . . . . . . . . . . . . . . . . . . 25Time constant . . . . . . . . . . . . . . . . . . . . . . . 26
Status Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Status output
Direction of flow . . . . . . . . . . . . . . . . . . . . . . . . . 27General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Limit value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Switching action . . . . . . . . . . . . . . . . . . . . . . . . . 28
SumTotalizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Device Functions PROline Promass 40 20 Index of key words
Endress+Hauser 47
S (continued)Switch point
Simulation Status output . . . . . . . . . . . . . . . . . . . 26Value Simulation Status output . . . . . . . . . . . . . . 26
SystemCondition
Actual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40Previous . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
ErrorAssign . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40Error category . . . . . . . . . . . . . . . . . . . . . . . 40
Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
TTag
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
TemperatureCoefficient KM . . . . . . . . . . . . . . . . . . . . . . . . . . 39Measured
Maximal . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39Minimal . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Test Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Time constant
Current output . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Status output . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
TotalizerFailsafe mode . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Overflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Sum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
UUnit
Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Mass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Mass flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Volume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Volume flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
VValue
Frequency high . . . . . . . . . . . . . . . . . . . . . . . . . . 20Pulse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Simulation
Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . 22Measurand . . . . . . . . . . . . . . . . . . . . . . . . . 42Status input . . . . . . . . . . . . . . . . . . . . . . . . . 30Switch point . . . . . . . . . . . . . . . . . . . . . . . . . 26
20 mA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
VersionAmplifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Volume flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
WWrite protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
ZZero point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34, 39Zero point adjust . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Numerics100% Value (Display) . . . . . . . . . . . . . . . . . . . . . . . . 13
Europe
Austria� Endress+Hauser Ges.m.b.H.WienTel. (01) 88056-0, Fax (01) 88056-35
Belarus� BelorgsintezMinskTel. (0172) 508473, Fax (0172) 508583
Belgium / Luxembourg� Endress+Hauser N.V.BrusselsTel. (02) 2480600, Fax (02) 2480553
BulgariaINTERTECH-AUTOMATIONSofiaTel. (02) 664869, Fax (02) 9631389
Croatia� Endress+Hauser GmbH+Co.ZagrebTel. (01) 6637785, Fax (01) 6637823
CyprusI+G Electrical Services Co. Ltd.NicosiaTel. (02) 484788, Fax (02) 484690
Czech Republic� Endress+Hauser GmbH+Co.PrahaTel. (026) 6784200, Fax (026) 6784179
Denmark� Endress+Hauser A/SSøborgTel. (70) 131132, Fax (70) 132133
EstoniaELVI-AquaTartuTel. (7) 441638, Fax (7) 441582
Finland� Endress+Hauser OyHelsinkiTel. (0204) 83160, Fax (0204) 83161
France� Endress+Hauser S.A.HuningueTel. (389) 696768, Fax (389) 694802
Germany� Endress+Hauser Messtechnik GmbH+Co.Weil am RheinTel. (07621) 975-01, Fax (07621) 975-555
Great Britain� Endress+Hauser Ltd.ManchesterTel. (0161) 2865000, Fax (0161) 9981841
GreeceI & G Building Services Automation S.A.AthensTel. (01) 9241500, Fax (01) 9221714
HungaryMile Ipari-ElektroBudapestTel. (01) 4319800, Fax (01) 4319817
IcelandBIL ehfReykjavikTel. (05) 619616, Fax (05) 619617
IrelandFlomeaco Company Ltd.KildareTel. (045) 868615, Fax (045) 868182
Italy� Endress+Hauser S.p.A.Cernusco s/N MilanoTel. (02) 921921, Fax (02) 92107153
LatviaRino TKRigaTel. (07) 315087, Fax (07) 315084
LithuaniaUAB "Agava"KaunasTel. (07) 202410, Fax (07) 207414
Netherland� Endress+Hauser B.V.NaardenTel. (035) 6958611, Fax (035) 6958825
Norway� Endress+Hauser A/STranbyTel. (032) 859850, Fax (032) 859851
Poland� Endress+Hauser Polska Sp. z o.o.WarszawyTel. (022) 7201090, Fax (022) 7201085
PortugalTecnisis, LdaCacémTel. (21) 4267290, Fax (21) 4267299
RomaniaRomconseng S.R.L.BucharestTel. (01) 4101634, Fax (01) 4112501
Russia� Endress+Hauser Moscow OfficeMoscowTel. (095) 1587564, Fax (095) 1589871
SlovakiaTranscom Technik s.r.o.BratislavaTel. (7) 44888684, Fax (7) 44887112
Slovenia� Endress+Hauser D.O.O.LjubljanaTel. (061) 5192217, Fax (061) 5192298
Spain� Endress+Hauser S.A.Sant Just DesvernTel. (93) 4803366, Fax (93) 4733839
Sweden� Endress+Hauser ABSollentunaTel. (08) 55511600, Fax (08) 55511655
Switzerland� Endress+Hauser Metso AGReinach/BL 1Tel. (061) 7157575, Fax (061) 7111650
TurkeyIntek Endüstriyel Ölcü ve Kontrol SistemleriIstanbulTel. (0212) 2751355, Fax (0212) 2662775
UkrainePhotonika GmbHKievTel. (44) 26881, Fax (44) 26908
Yugoslavia Rep.Meris d.o.o.BeogradTel. (11) 4441966, Fax (11) 4441966
Africa
EgyptAnasiaHeliopolis/CairoTel. (02) 4179007, Fax (02) 4179008
MoroccoOussama S.A.CasablancaTel. (02) 241338, Fax (02) 402657
South Africa� Endress+Hauser Pty. Ltd.SandtonTel. (011) 4441386, Fax (011) 4441977
TunisiaControle, Maintenance et RegulationTunisTel. (01) 793077, Fax (01) 788595
America
Argentina� Endress+Hauser Argentina S.A.Buenos AiresTel. (01) 145227970, Fax (01) 145227909
BoliviaTritec S.R.L.CochabambaTel. (042) 56993, Fax (042) 50981
Brazil� Samson Endress+Hauser Ltda.Sao PauloTel. (011) 50313455, Fax (011) 50313067
Canada� Endress+Hauser Ltd.Burlington, OntarioTel. (905) 6819292, Fax (905) 6819444
Chile� Endress+Hauser Chile Ltd.SantiagoTel. (02) 3213009, Fax (02) 3213025
ColombiaColsein Ltda.Bogota D.C.Tel. (01) 2367659, Fax (01) 6104186
Costa RicaEURO-TEC S.A.San JoseTel. (02) 961542, Fax (02) 961542
EcuadorInsetec Cia. Ltda.QuitoTel. (02) 269148, Fax (02) 461833
GuatemalaACISA Automatizacion Y ControlIndustrial S.A.Ciudad de Guatemala, C.A.Tel. (03) 345985, Fax (03) 327431
Mexico� Endress+Hauser S.A. de C.V.Mexico CityTel. (5) 5682405, Fax (5) 5687459
ParaguayIncoel S.R.L.AsuncionTel. (021) 213989, Fax (021) 226583
UruguayCircular S.A.MontevideoTel. (02) 925785, Fax (02) 929151
USA� Endress+Hauser Inc.Greenwood, IndianaTel. (317) 535-7138, Fax (317) 535-8498
VenezuelaControval C.A.CaracasTel. (02) 9440966, Fax (02) 9444554
Asia
China� Endress+Hauser Shanghai Instrumentation Co. Ltd.ShanghaiTel. (021) 54902300, Fax (021) 54902303
� Endress+Hauser Beijing OfficeBeijingTel. (010) 68344058, Fax (010) 68344068
Hong Kong� Endress+Hauser HK Ltd.Hong KongTel. 25283120, Fax 28654171
India� Endress+Hauser (India) Pvt Ltd.MumbaiTel. (022) 8521458, Fax (022) 8521927
IndonesiaPT Grama BazitaJakartaTel. (21) 7975083, Fax (21) 7975089
Japan� Sakura Endress Co. Ltd.TokyoTel. (0422) 540613, Fax (0422) 550275
Malaysia� Endress+Hauser (M) Sdn. Bhd.Petaling Jaya, Selangor Darul EhsanTel. (03) 7334848, Fax (03) 7338800
PakistanSpeedy AutomationKarachiTel. (021) 7722953, Fax (021) 7736884
Papua-NeuguineaSBS Electrical Pty LimitedPort MoresbyTel. 3251188, Fax 3259556
Philippines� Endress+Hauser Philippines Inc.Metro ManilaTel. (2) 3723601-05, Fax (2) 4121944
Singapore� Endress+Hauser (S.E.A.) Pte., Ltd.SingaporeTel. 5668222, Fax 5666848
South Korea� Endress+Hauser (Korea) Co., Ltd.SeoulTel. (02) 6587200, Fax (02) 6592838
TaiwanKingjarl CorporationTaipei R.O.C.Tel. (02) 27183938, Fax (02) 27134190
Thailand� Endress+Hauser Ltd.BangkokTel. (2) 9967811-20, Fax (2) 9967810
VietnamTan Viet Bao Co. Ltd.Ho Chi Minh CityTel. (08) 8335225, Fax (08) 8335227
IranPATSA Co.TehranTel. (021) 8754748, Fax (021) 8747761
IsraelInstrumetrics Industrial Control Ltd.NetanyaTel. (09) 8357090, Fax (09) 8350619
JordanA.P. Parpas Engineering S.A.AmmanTel. (06) 4643246, Fax (06) 4645707
Kingdom of Saudi ArabiaAnasia Ind. AgenciesJeddahTel. (02) 6710014, Fax (02) 6725929
LebanonNetwork EngineeringJbeilTel. (3) 944080, Fax (9) 548038
Sultanate of OmanMustafa Sultan Science & Industry Co. LLC.RuwiTel. 602009, Fax 607066
United Arab EmiratesDescon Trading EST.DubaiTel. (04) 2653651, Fax (04) 2653264
YemenYemen Company for Ghee and Soap IndustryTaizTel. (04) 230664, Fax (04) 212338
Australia + New Zealand
AustraliaALSTOM Australia LimitedMilperraTel. (02) 97747444, Fax (02) 97744667
New ZealandEMC Industrial Group LimitedAucklandTel. (09) 4155110, Fax (09) 4155115
All other countries
� Endress+Hauser GmbH+Co.Instruments InternationalD-Weil am RheinGermanyTel. (07621) 975-02, Fax (07621) 975345
� Members of the Endress+Hauser group
http://www.endress.com