4-way blow ceiling-suspended type - daikin comfort
TRANSCRIPT
![Page 1: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/1.jpg)
4-Way Blow Ceiling-Suspended TypeFXUQ-PVJU
EDUS391437A-F15202010
Engineering Data
60 Hz
![Page 2: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/2.jpg)
![Page 3: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/3.jpg)
1
FXUQ-PVJU EDUS391437A-F15
Table of Contents
1. FeaturesandBenefits ................................................................................22. Specifications .............................................................................................33. Dimensions .................................................................................................54. CenterofGravity ........................................................................................65. Piping Diagrams .........................................................................................76. Wiring Diagrams .........................................................................................87. Electric Characteristics .............................................................................108. SafetyDevicesSetting ............................................................................. 119. CapacityTables ........................................................................................12
9.1 CoolingCapacityatTe:43°F(6°C) .................................................129.2 HeatingCapacity .............................................................................129.3 CorrectionFactorforCoolingCapacityatTe:48°F(9°C) ...............12
10.AirVelocityandTemperatureDistributions(ReferenceData) ..................1310.1CoolingOperation ...........................................................................1310.2HeatingOperation ...........................................................................17
11.SoundLevels(ReferenceData) ...............................................................2112.Accessories ..............................................................................................23
12.1OptionalAccessories(forUnit) .......................................................23
![Page 4: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/4.jpg)
2
FXUQ-PVJU EDUS391437A-F15
1. Features and Benefits
Theunique4-wayceiling-suspendedcassetteisanidealsolutionforroomswithoutafalseceiling,orminimalspaceaboveafalseceiling,whereadaptivecomfortcontrolispreferred.
TheoptionalSensorKit(occupancyandsurfacetemperature)togetherwithairtemperaturesensorandadvancedcontrolfunctionsenablestheunittoprovideanexceptionalcomfortlevel,energyefficiency,andflexibility.
� Verylowunitheightofunder8”makesitanidealsolutionforschool,shops,restaurantsandofficeswithnoorlowfalseceilings
� OptionalSensorKitenablesinputfromthreeroomsensorstoprovideoptimizedoccupantcomfortandefficiency
� Stylishunitblendseasilywithanyinterior,astheairlouverscloseentirelywhennotinoperation � Lowenergyconsumptionthankstoaspeciallydevelopedsmalltubeheatexchanger,DCfanmotoranddrainpump
� Individualairlouvercontrol-oneormorelouvercanbeeasilyclosedviatheremotecontrollerwhenrequired
� Idealforbothnewandexistingbuildings � Canalsobemountedpartiallyrecessedinafalseceiling � Sameappearanceandsizeforallcapacitymodels
![Page 5: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/5.jpg)
3
FXUQ-PVJU EDUS391437A-F15
2. Specifications
4-way blow ceiling-suspended type
Model FXUQ18PVJU FXUQ24PVJUPowersupply 1phase,60Hz,208/230V 1phase,60Hz,208/230V
1,3Coolingcapacity Btu/h(kW) 18,000(5.3) 24,000(7.0)
2,3Heatingcapacity Btu/h(kW) 20,000(5.9) 27,000(7.9)
Casing/Color Resin/Freshwhite Resin/FreshwhiteDimensions:(H×W×D) in.(mm) 7-13/16×37-3/8×37-3/8(198×950×950) 7-13/16×37-3/8×37-3/8(198×950×950)Coil(crossfincoil)
Rows×Stages×FPI 3×10×21 3×10×21Face area ft²(m²) 3.55(0.330) 3.55(0.330)
Fan
Model QTS48D11M QTS48D11MType Turbofan TurbofanMotoroutput W 46 46
Airflowrate(H/M/L) cfm (m³/min) 795/689/565(22.5/19.5/16.0) 795/689/565(22.5/19.5/16.0)
Drive Directdrive Directdrive
Temperaturecontrol Microprocessorthermostatforcoolingandheating
Microprocessorthermostatforcoolingandheating
Soundabsorbingthermalinsulationmaterial Polyethylenefoam Polyethylenefoam4Soundpressurelevel(referencedata)(H/M/L) dBA 40/38/36 40/38/36
4Soundpowerlevel(referencedata)(H/M/L) dB 58/56/54 58/56/54
Weight lbs(kg) 58(26) 58(26)
Piping connections
Liquidpipes in.(mm) f1/4(f6.4)(flareconnection) f3/8(f9.5)(flareconnection)Gaspipes in.(mm) f1/2(f12.7)(flareconnection) f5/8(f15.9)(flareconnection)
Drain pipe in.(mm) VP20(externaldia.1(26),internaldia.13/16(20))
VP20(externaldia.1(26),internaldia.13/16(20))
Safetydevices Fuse FuseRefrigerantcontrol Electronicexpansionvalve ElectronicexpansionvalveConnectableoutdoorunit R410AVRV series R410AVRV series
StandardaccessoriesOperationmanual,Installationmanual,Paper
patternforinstallation,Drainhose,Sealingpads,Clamps,Washers,Screws,Insulationforfitting,
Clampmetal,Conduitmountingplate
Operationmanual,Installationmanual,Paperpatternforinstallation,Drainhose,Sealingpads,Clamps,Washers,Screws,Insulationforfitting,
Clampmetal,Conduitmountingplate
Note:1. Nominalcoolingcapacitiesarebasedonthefollowingconditions:
Returnairtemperature:80°FDB(26.7°CDB),67°FWB(19.4°CWB) Outdoortemperature:95°FDB(35.0°CDB) Equivalentrefrigerantpipinglength:25ft(7.6m)(horizontal)
2. Nominalheatingcapacitiesarebasedonthefollowingconditions: Returnairtemperature:70°FDB(21.1°CDB). Outdoortemperature:47°FDB(8.3°CDB),43°FWB(6.1°CWB) Equivalentrefrigerantpipinglength:25ft(7.6m)(horizontal)
3. Capacitiesarenet,includingadeductionforcooling(anadditionforheating)forindoorfanmotorheat.4. Anechoicchamberconversionvalue,measuredunderJISconditions.Duringactualoperation,
thesevaluesmaybehigherasaresultofinstallationconditions.
C:3D090219A
![Page 6: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/6.jpg)
4
FXUQ-PVJU EDUS391437A-F15
4-way blow ceiling-suspended type
Model FXUQ30PVJU FXUQ36PVJUPowersupply 1phase,60Hz,208/230V 1phase,60Hz,208/230V
1,3Coolingcapacity Btu/h(kW) 30,000(8.8) 36,000(10.6)
2,3Heatingcapacity Btu/h(kW) 34,000(10.0) 40,000(11.7)
Casing/Color Resin/Freshwhite Resin/FreshwhiteDimensions:(H×W×D) in.(mm) 7-13/16×37-3/8×37-3/8(198×950×950) 7-13/16×37-3/8×37-3/8(198×950×950)Coil(crossfincoil)
Rows×Stages×FPI 3×10×21 3×10×21Face area ft²(m²) 3.55(0.330) 3.55(0.330)
Fan
Model QTS48D11M QTS48D11MType Turbofan TurbofanMotoroutput W 106 106
Airflowrate(H/M/L) cfm (m³/min) 1,095/918/742(31.0/26.0/21.0) 1,095/918/742(31.0/26.0/21.0)
Drive Directdrive Directdrive
Temperaturecontrol Microprocessorthermostatforcoolingandheating
Microprocessorthermostatforcoolingandheating
Soundabsorbingthermalinsulationmaterial Polyethylenefoam Polyethylenefoam4Soundpressurelevel(referencedata)(H/M/L) dBA 47/44/40 47/44/40
4Soundpowerlevel(referencedata)(H/M/L) dB 65/62/58 65/62/58
Weight lbs(kg) 60(27) 60(27)
Piping connections
Liquidpipes in.(mm) f3/8(f9.5)(flareconnection) f3/8(f9.5)(flareconnection)Gaspipes in.(mm) f5/8(f15.9)(flareconnection) f5/8(f15.9)(flareconnection)
Drain pipe in.(mm) VP20(externaldia.1(26),internaldia.13/16(20))
VP20(externaldia.1(26),internaldia.13/16(20))
Safetydevices Fuse FuseRefrigerantcontrol Electronicexpansionvalve ElectronicexpansionvalveConnectableoutdoorunit R410AVRV series R410AVRV series
StandardaccessoriesOperationmanual,Installationmanual,Paper
patternforinstallation,Drainhose,Sealingpads,Clamps,Washers,Screws,Insulationforfitting,
Clampmetal,Conduitmountingplate
Operationmanual,Installationmanual,Paperpatternforinstallation,Drainhose,Sealingpads,Clamps,Washers,Screws,Insulationforfitting,
Clampmetal,Conduitmountingplate
Note:1. Nominalcoolingcapacitiesarebasedonthefollowingconditions:
Returnairtemperature:80°FDB(26.7°CDB),67°FWB(19.4°CWB) Outdoortemperature:95°FDB(35.0°CDB) Equivalentrefrigerantpipinglength:25ft(7.6m)(horizontal)
2. Nominalheatingcapacitiesarebasedonthefollowingconditions: Returnairtemperature:70°FDB(21.1°CDB). Outdoortemperature:47°FDB(8.3°CDB),43°FWB(6.1°CWB) Equivalentrefrigerantpipinglength:25ft(7.6m)(horizontal)
3. Capacitiesarenet,includingadeductionforcooling(anadditionforheating)forindoorfanmotorheat.4. Anechoicchamberconversionvalue,measuredunderJISconditions.Duringactualoperation,
thesevaluesmaybehigherasaresultofinstallationconditions.
C:3D090219A
![Page 7: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/7.jpg)
5
FXUQ-PVJU EDUS391437A-F15
3. Dimensions
FXUQ18-36PVJU
3D09
0217
A
![Page 8: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/8.jpg)
6
FXUQ-PVJU EDUS391437A-F15
4. Center of Gravity
FXUQ18-36PVJU
4D090212
Unit: in. (mm)
![Page 9: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/9.jpg)
7
FXUQ-PVJU EDUS391437A-F15
5. Piping Diagrams
FXUQ18-36PVJU
Unit:in.(mm)Model Gas Liquid
FXUQ18PVJU f1/2(f12.7)
f1/4(f6.4)
FXUQ24PVJUFXUQ30PVJUFXUQ36PVJU
f5/8(f15.9)
f3/8(f9.5)
C: 4D034245R
![Page 10: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/10.jpg)
8
FXUQ-PVJU EDUS391437A-F15
6. Wiring Diagrams
FXUQ18-36PVJU
C: 3
D09
0218
NO
TES
1.
: T
ERM
INAL
BLO
CK
:
CO
NN
ECTO
R
:
FIEL
D W
IRIN
G2.
IN C
ASE
USI
NG
CEN
TRAL
REM
OTE
CO
NTR
OLL
ER, C
ON
NEC
T IT
TO
TH
E U
NIT
IN A
CC
OR
DAN
CE
WIT
H T
HE
ATTA
CH
ED IN
STAL
LATI
ON
MAN
UAL
.3.
IN C
ASE
OF
MAI
N/S
UB
CH
ANG
EOVE
R, S
EE T
HE
INST
ALLA
TIO
N M
ANU
AL A
TTAC
HED
TO
REM
OTE
CO
NTR
OLL
ER.
4. S
YMBO
LS S
HO
W A
S FO
LLO
WS:
BLK
: BLA
CK
RED
: RED
BLU
: BLU
E W
HT:
WH
ITE
YLW
: YEL
LOW
GR
N: G
REE
N O
RG
: OR
ANG
E B
RN
: BR
OW
N P
NK:
PIN
K.5.
WH
EN C
ON
NEC
TIN
G T
HE
INPU
T W
IRIN
G F
RO
M O
UTS
IDE,
FO
RC
ED O
FF O
R O
N/O
FF C
ON
TRO
L O
PER
ATIO
N C
AN B
E SE
LEC
TED
BY
THE
REM
OTE
C
ON
TRO
LLER
. SEE
INST
ALLA
TIO
N M
ANU
AL F
OR
MO
RE
DET
AILS
.6.
CLA
SS 2
WIR
E
![Page 11: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/11.jpg)
9
FXUQ-PVJU EDUS391437A-F15
FXUQ18-36PVJUINDOORUNITA1P PRINTEDCIRCUITBOARDC105 CAPACITOR(M1F)F1U FUSEHAP FLASHINGLAMP(SERVICEMONITORGREEN)M1F MOTOR(INDOORFAN)M1P MOTOR(DRAINPUMP)M1S·M2SM3S·M4S MOTOR(SWINGBLADE)
R1T THERMISTOR(AIR)R2T·R3T THERMISTOR(COIL)S1L FLOATSWITCHV1R DIODEBRIDGEX1M TERMINALBLOCKX2M TERMINALBLOCKY1E ELECTRONICEXPANSIONVALVEZ1F NOISEFILTERZ1C FERRITECOREPS POWERSUPPLYCIRCUITSENSORKITA3P PRINTEDCIRCUITBOARDA4P PRINTEDCIRCUITBOARDCONNECTORFOROPTIONALPARTSX35A CONNECTOR(POWERSUPPLYFORADAPTOR)X81A CONNECTOR(SENSORKIT)
C:3D090218
![Page 12: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/12.jpg)
10
FXUQ-PVJU EDUS391437A-F15
7. Electric Characteristics
FXUQ18-36PVJU
ModelPowersupply IFM Input(W)
Hz Volts Voltagerange MCA MOP kW FLA Cooling HeatingFXUQ18PVJU
60 208/230V Max.253V Min. 187 V
0.6 15 0.046 0.5 90 73FXUQ24PVJU 0.6 15 0.046 0.5 90 73FXUQ30PVJU 1.4 15 0.106 1.1 200 179FXUQ36PVJU 1.4 15 0.106 1.1 200 179
Symbol:MCA:Min.CircuitAmps(A)MOP:Max.OvercurrentProtectiveDevice(A)kW: FanMotorRatedOutput(kW)FLA: FullLoadAmps(A)IFM: IndoorFanMotor
Note:1.Voltagerange Unitsaredesignedtooperateonlyattheratedvoltageprovidedinthetableabove.
2.Maximumallowablevoltageunbalancebetweenphaseis2%.3.MCA/MOP MCA=1.25×FLA MOP≤4×FLA (Nextlowerstandardfuseraring.Min.15A)
4.SelectwiringsizebasedontheMCA.
C:4D090214A
![Page 13: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/13.jpg)
11
FXUQ-PVJU EDUS391437A-F15
8. Safety Devices Setting
Model FXUQ18PVJU FXUQ24PVJU FXUQ30PVJU FXUQ36PVJUPrintedcircuitboardfuse 250V,3.15A 250V,3.15A 250V,3.15A 250V,3.15ADrainpumpthermalfuse °F(°C) – – – –Fanmotorthermalprotector °F(°C) – – – –Fanmotorthermalfuse °F(°C) – – – –
C:3D090213
![Page 14: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/14.jpg)
12
FXUQ-PVJU EDUS391437A-F15
9. Capacity Tables9.1 Cooling Capacity at Te: 43°F (6°C)
Model
Indoorairtemp.°FWB(°CWB)(Te:43°F(6°C))61(16.1) 64(17.8) 67(19.4) 70(21.1) 72(22.2) 75(23.9)
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHCMBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH
FXUQ18PVJU 14.2 11.8 16.1 12.9 18.0 13.7 18.4 13.6 18.6 13.0 18.9 12.8 FXUQ24PVJU 19.0 15.4 21.5 16.9 24.0 18.0 24.5 17.8 24.8 17.0 25.3 16.6 FXUQ30PVJU 23.7 18.8 26.8 20.7 30.0 22.1 30.6 21.8 31.0 20.9 31.6 20.2 FXUQ36PVJU 28.4 22.1 32.2 24.2 36.0 26.0 36.7 25.7 37.2 24.7 37.9 23.6
TC: Totalcapacity:MBHSHC:Sensibleheatcapacity:MBH
Note:1.ThesecapacitytablescanbeusedwhenselectingaVRVindoorunit.TheactualcapacityoftheVRVsystemdependsonfactorssuchastheselectedmodelofoutdoorunits,outdoorairtemperatureandpipinglength.PleaseconfirmthatthecorrectedcapacityoftheVRVsystemsatisfiestherequiredheatload.
2. showsratedcondition.
9.2 Heating Capacity
Model
Indoorairtemp.°FDB(°CDB)(Tc:115°F(46°C))62(16.7) 65(18.3) 68(20.0) 70(21.1) 72(22.2) 75(23.9)
TC TC TC TC TC TCMBH MBH MBH MBH MBH MBH
FXUQ18PVJU 23.3 21.9 20.7 20.0 19.3 18.1 FXUQ24PVJU 31.5 29.5 28.0 27.0 26.0 24.5 FXUQ30PVJU 39.7 37.1 35.3 34.0 32.7 30.9 FXUQ36PVJU 46.7 43.7 41.5 40.0 38.5 36.3
TC:Totalcapacity:MBH
Note:1.ThesecapacitytablescanbeusedwhenselectingaVRVindoorunit.TheactualcapacityoftheVRVsystemdependsonfactorssuchastheselectedmodelofoutdoorunits,outdoorairtemperatureandpipinglength.PleaseconfirmthatthecorrectedcapacityoftheVRVsystemsatisfiestherequiredheatload.
2. showsratedcondition.
9.3 Correction Factor for Cooling Capacity at Te: 48°F (9°C)
Refertothecorrectionfactortablebelowwhenamini-splitindoorunitisconnectedtoaVRVHeatPumpsystemusingaBranchPortbox.
ModelIndoorairtemp.°FWB(°CWB)(Te:48°F(9°C))
61(16.1) 64(17.8) 67(19.4) 70(21.1) 72(22.2) 75(23.9)TC SHF TC SHF TC SHF TC SHF TC SHF TC SHF
FXUQ18PVJU 0.706 1.162 0.765 1.108 0.786 1.090 0.806 1.073 0.841 1.045 0.865 1.028FXUQ24PVJU 0.706 1.162 0.765 1.108 0.786 1.090 0.806 1.073 0.841 1.045 0.865 1.028FXUQ30PVJU 0.707 1.161 0.773 1.103 0.795 1.087 0.811 1.077 0.842 1.053 0.865 1.035FXUQ36PVJU 0.707 1.161 0.773 1.103 0.795 1.087 0.811 1.077 0.842 1.053 0.865 1.035
TC: TotalcapacitySHF:Sensibleheatfactor
![Page 15: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/15.jpg)
13
FXUQ-PVJU EDUS391437A-F15
10. Air Velocity and Temperature Distributions (Reference Data)10.1 Cooling OperationFXUQ18PVJU
Note:Please understand that the analysis results may differ with actual installation conditions, or furniture arrangement.
5.6 ft/s (1.7 m/s)
4.9 ft/s (1.5 m/s)
4.3 ft/s (1.3 m/s)
3.6 ft/s (1.1 m/s)
3.0 ft/s (0.9 m/s)
2.3 ft/s (0.7 m/s)
1.6 ft/s (0.5 m/s)
1.0 ft/s (0.3 m/s)
80.6°F (27°C)
79°F (26°C)
77°F (25°C)
75.2°F (24°C)
73.4°F (23°C)
71.6°F (22°C)
69.8°F (21°C)
68°F (20°C)
8.9 ft(2.7 m)
0.0 ft(0.0 m)
0.0 ft(0.0 m)
26.2 ft(8.0 m)
8.9 ft(2.7 m)
0.0 ft(0.0 m)
0.0 ft(0.0 m)
26.2 ft(8.0 m)
Air velocity distribution of FXUQ18PVJU (Cooling operation)Air flow direction : Horizontal
Air temperature distribution of FXUQ18PVJU (Cooling operation)Air flow direction : Horizontal
![Page 16: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/16.jpg)
14
FXUQ-PVJU EDUS391437A-F15
FXUQ24PVJU
Note:Please understand that the analysis results may differ with actual installation conditions, or furniture arrangement.
5.6 ft/s (1.7 m/s)
4.9 ft/s (1.5 m/s)
4.3 ft/s (1.3 m/s)
3.6 ft/s (1.1 m/s)
3.0 ft/s (0.9 m/s)
2.3 ft/s (0.7 m/s)
1.6 ft/s (0.5 m/s)
1.0 ft/s (0.3 m/s)
80.6°F (27°C)
79°F (26°C)
77°F (25°C)
75.2°F (24°C)
73.4°F (23°C)
71.6°F (22°C)
69.8°F (21°C)
68°F (20°C)
8.9 ft(2.7 m)
0.0 ft(0.0 m)
0.0 ft(0.0 m)
26.2 ft(8.0 m)
8.9 ft(2.7 m)
0.0 ft(0.0 m)
0.0 ft(0.0 m)
26.2 ft(8.0 m)
Air velocity distribution of FXUQ24PVJU (Cooling operation)Air flow direction : Horizontal
Air temperature distribution of FXUQ24PVJU (Cooling operation)Air flow direction : Horizontal
![Page 17: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/17.jpg)
15
FXUQ-PVJU EDUS391437A-F15
FXUQ30PVJU
Note:Please understand that the analysis results may differ with actual installation conditions, or furniture arrangement.
5.6 ft/s (1.7 m/s)
4.9 ft/s (1.5 m/s)
4.3 ft/s (1.3 m/s)
3.6 ft/s (1.1 m/s)
3.0 ft/s (0.9 m/s)
2.3 ft/s (0.7 m/s)
1.6 ft/s (0.5 m/s)
1.0 ft/s (0.3 m/s)
10.5 ft(3.2 m)
0.0 ft(0.0 m)
0.0 ft(0.0 m)
26.2 ft(8.0 m)
80.6°F (27°C)
79°F (26°C)
77°F (25°C)
75.2°F (24°C)
73.4°F (23°C)
71.6°F (22°C)
69.8°F (21°C)
68°F (20°C)
10.5 ft(3.2 m)
0.0 ft(0.0 m)
0.0 ft(0.0 m)
26.2 ft(8.0 m)
Air velocity distribution of FXUQ30PVJU (Cooling operation)Air flow direction : Horizontal
Air temperature distribution of FXUQ30PVJU (Cooling operation)Air flow direction : Horizontal
![Page 18: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/18.jpg)
16
FXUQ-PVJU EDUS391437A-F15
FXUQ36PVJU
Note:Please understand that the analysis results may differ with actual installation conditions, or furniture arrangement.
5.6 ft/s (1.7 m/s)
4.9 ft/s (1.5 m/s)
4.3 ft/s (1.3 m/s)
3.6 ft/s (1.1 m/s)
3.0 ft/s (0.9 m/s)
2.3 ft/s (0.7 m/s)
1.6 ft/s (0.5 m/s)
1.0 ft/s (0.3 m/s)
10.5 ft(3.2 m)
0.0 ft(0.0 m)
0.0 ft(0.0 m)
26.2 ft(8.0 m)
80.6°F (27°C)
79°F (26°C)
77°F (25°C)
75.2°F (24°C)
73.4°F (23°C)
71.6°F (22°C)
69.8°F (21°C)
68°F (20°C)
10.5 ft(3.2 m)
0.0 ft(0.0 m)
0.0 ft(0.0 m)
26.2 ft(8.0 m)
Air velocity distribution of FXUQ36PVJU (Cooling operation)Air flow direction : Horizontal
Air temperature distribution of FXUQ36PVJU (Cooling operation)Air flow direction : Horizontal
![Page 19: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/19.jpg)
17
FXUQ-PVJU EDUS391437A-F15
10.2 Heating OperationFXUQ18PVJU
Note:Please understand that the analysis results may differ with actual installation conditions, or furniture arrangement.
5.6 ft/s (1.7 m/s)
4.9 ft/s (1.5 m/s)
4.3 ft/s (1.3 m/s)
3.6 ft/s (1.1 m/s)
3.0 ft/s (0.9 m/s)
2.3 ft/s (0.7 m/s)
1.6 ft/s (0.5 m/s)
1.0 ft/s (0.3 m/s)
8.9 ft(2.7 m)
0.0 ft(0.0 m)
0.0 ft(0.0 m)
26.2 ft(8.0 m)
80.6°F (27°C)
79°F (26°C)
77°F (25°C)
75.2°F (24°C)
73.4°F (23°C)
71.6°F (22°C)
69.8°F (21°C)
68°F (20°C)
8.9 ft(2.7 m)
0.0 ft(0.0 m)
0.0 ft(0.0 m)
26.2 ft(8.0 m)
Air velocity distribution of FXUQ18PVJU (Heating operation)Air flow direction : Down
Air temperature distribution of FXUQ18PVJU (Heating operation)Air flow direction : Down
![Page 20: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/20.jpg)
18
FXUQ-PVJU EDUS391437A-F15
FXUQ24PVJU
Note:Please understand that the analysis results may differ with actual installation conditions, or furniture arrangement.
5.6 ft/s (1.7 m/s)
4.9 ft/s (1.5 m/s)
4.3 ft/s (1.3 m/s)
3.6 ft/s (1.1 m/s)
3.0 ft/s (0.9 m/s)
2.3 ft/s (0.7 m/s)
1.6 ft/s (0.5 m/s)
1.0 ft/s (0.3 m/s)
8.9 ft(2.7 m)
0.0 ft(0.0 m)
0.0 ft(0.0 m)
26.2 ft(8.0 m)
80.6°F (27°C)
79°F (26°C)
77°F (25°C)
75.2°F (24°C)
73.4°F (23°C)
71.6°F (22°C)
69.8°F (21°C)
68°F (20°C)
8.9 ft(2.7 m)
0.0 ft(0.0 m)
0.0 ft(0.0 m)
26.2 ft(8.0 m)
Air velocity distribution of FXUQ24PVJU (Heating operation)Air flow direction : Down
Air temperature distribution of FXUQ24PVJU (Heating operation)Air flow direction : Down
![Page 21: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/21.jpg)
19
FXUQ-PVJU EDUS391437A-F15
FXUQ30PVJU
Note:Please understand that the analysis results may differ with actual installation conditions, or furniture arrangement.
5.6 ft/s (1.7 m/s)
4.9 ft/s (1.5 m/s)
4.3 ft/s (1.3 m/s)
3.6 ft/s (1.1 m/s)
3.0 ft/s (0.9 m/s)
2.3 ft/s (0.7 m/s)
1.6 ft/s (0.5 m/s)
1.0 ft/s (0.3 m/s)
10.5 ft(3.2 m)
0.0 ft(0.0 m)
0.0 ft(0.0 m)
26.2 ft(8.0 m)
80.6°F (27°C)
79°F (26°C)
77°F (25°C)
75.2°F (24°C)
73.4°F (23°C)
71.6°F (22°C)
69.8°F (21°C)
68°F (20°C)
10.5 ft(3.2 m)
0.0 ft(0.0 m)
0.0 ft(0.0 m)
26.2 ft(8.0 m)
Air velocity distribution of FXUQ30PVJU (Heating operation)Air flow direction : Down
Air temperature distribution of FXUQ30PVJU (Heating operation)Air flow direction : Down
![Page 22: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/22.jpg)
20
FXUQ-PVJU EDUS391437A-F15
FXUQ36PVJU
Note:Please understand that the analysis results may differ with actual installation conditions, or furniture arrangement.
5.6 ft/s (1.7 m/s)
4.9 ft/s (1.5 m/s)
4.3 ft/s (1.3 m/s)
3.6 ft/s (1.1 m/s)
3.0 ft/s (0.9 m/s)
2.3 ft/s (0.7 m/s)
1.6 ft/s (0.5 m/s)
1.0 ft/s (0.3 m/s)
10.5 ft(3.2 m)
0.0 ft(0.0 m)
0.0 ft(0.0 m)
26.2 ft(8.0 m)
80.6°F (27°C)
79°F (26°C)
77°F (25°C)
75.2°F (24°C)
73.4°F (23°C)
71.6°F (22°C)
69.8°F (21°C)
68°F (20°C)
10.5 ft(3.2 m)
0.0 ft(0.0 m)
0.0 ft(0.0 m)
26.2 ft(8.0 m)
Air velocity distribution of FXUQ36PVJU (Heating operation)Air flow direction : Down
Air temperature distribution of FXUQ36PVJU (Heating operation)Air flow direction : Down
![Page 23: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/23.jpg)
21
FXUQ-PVJU EDUS391437A-F15
11. Sound Levels (Reference Data)
FXUQ18-24PVJU
4D090216A
![Page 24: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/24.jpg)
22
FXUQ-PVJU EDUS391437A-F15
FXUQ30-36PVJU
4D090215A
![Page 25: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/25.jpg)
23
FXUQ-PVJU EDUS391437A-F15
12. Accessories12.1 Optional Accessories (for Unit)
Option Note FXUQ18PVJU FXUQ24PVJU FXUQ30PVJU FXUQ36PVJUBlockingmaterialkitfor2-waydischarge KDBHP49B140Airoutletblockingdecorationpanel KDBTP49B140Replacementlonglifefilter KAF5511D160
C:3D090253A
![Page 26: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/26.jpg)
![Page 27: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/27.jpg)
![Page 28: 4-Way Blow Ceiling-Suspended Type - Daikin Comfort](https://reader030.vdocuments.site/reader030/viewer/2022012711/61ab025cfdb03047883dc9bd/html5/thumbnails/28.jpg)
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.
Cautions on product corrosion
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.
Read the user’s manual carefully before using this product. The user’s manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any inquiries, please contact your local importer, distributor and/or retailer.
©All rights reserved 10/20 FS
●Specifications, designs and other content appearing in this brochure are current as of October 2020 but subject to change without notice.