2 equivalent circuits of power transformers
TRANSCRIPT
GRIDTechnical Institute
This document is the exclusive property of Alstom Grid and shall not be transmitted by any means, copied, reproduced or modified without the prior written consent of Alstom Grid Technical Institute. All rights reserved.
Equivalent Circuits of Power Transformers
> Equivalent Circuits of Power Transformers2
Three Phase Transformers
1. Three single phase units
2. limb core type 4. Shell type
3. 5-limb core type
> Equivalent Circuits of Power Transformers3
Winding Polarity
> Equivalent Circuits of Power Transformers4
Transformer Equivalent Circuit
> Equivalent Circuits of Power Transformers5
> Equivalent Circuits of Power Transformers6
Simplified Equivalent Circuit
> Equivalent Circuits of Power Transformers7
Two Winding Transformer
(a)
(b)
(c)
> Equivalent Circuits of Power Transformers8
Three Phase Transformers
Under balanced conditions all phases behave in a similar manner and can be considered independently.
Thus equivalent (single phase) circuit for both positive and negative sequence quantities is a single series impedance representing the primary and secondary leakage reactance.
(Resistance can usually be ignored.)
i.e. Same as single phase transformer
NB! Actual circuit:
> Equivalent Circuits of Power Transformers9
Dy 1
> Equivalent Circuits of Power Transformers10
Positive Sequence Current
Consider Dy 1 transformer
Voltage ratio 1 : 1
Turns ratio : 1
3
> Equivalent Circuits of Power Transformers11
150I
3
1aI
3
I
3
aII
90I3
aaI
3
aI
3
IaI
30I3
a1I
3
Ia
3
II
1111
C
1
2
111
2
B
1
2
11
21
A
90II 1B
150II 1C
30II 1A 1IIa
1aIIc 12IaIb
> Equivalent Circuits of Power Transformers12
Negative Sequence Current
Consider Dy 1 transformer
Voltage ratio 1 : 1
Turns ratio : 1
3
> Equivalent Circuits of Power Transformers13
150I
3
1aI
3
I
3
IaI
90I3
aaI
3
Ia
3
aII
30I3
a1I
3
aI
3
II
2
2
222
2
C
2
2
22
22
B
1222
A
150II 2C
30II 2A
90II 2B
2IIa
2aIIb 22IaIc
> Equivalent Circuits of Power Transformers14
Example
210530530II
30530II
2)R(2
1)R(1
> Equivalent Circuits of Power Transformers15
Example continued …
pu9066.824051205
IaaII
pu9066.812052405
aIIaI
0III
:FAt
pu90104505905
2105.2401305.1201
IaaII
pu90533052105
2105.1201305.2401
aIIaI
pu9052105305
III
:RAt
22
1C
212
B
21A
)R(22
)R(1C
)R(2)R(12
B
)R(2)R(1A
> Equivalent Circuits of Power Transformers16
Example continued …
AMPS 875 5.87 x 10I
AMPS 5.437 5.87 x 5I
AMPS 5.437 5.87 x 5I
:RAt
AMPS90931050 x 66.8I
AMPS90931050 x 66.8I
0I
:FAt
AMPS87.5 kV) (132Current Base
AMPS1050 (11kV)Current Base
C
B
A
C
B
A
> Equivalent Circuits of Power Transformers17
Zero Sequence
The transformer response to zero sequence quantities depends upon:
a) The existence (or otherwise) of a neutral connection
b) The interconnection of the phase windings
c) Type of core (3-Limb, Shell etc)
The 3 or 4 terminal single phase equivalent circuit can be retained but
the above factors require consideration in order to determine the
connection of the circuit to the network.
> Equivalent Circuits of Power Transformers18
> Equivalent Circuits of Power Transformers19
Transformer Zero Sequence Impedance
> Equivalent Circuits of Power Transformers20
‘b’ links closed for a delta winding as this forms a trap for I0 in
earthed star which induces current in delta.
I0s in phase
∴ I0 circulatesd round the delta and no I0 passes into the line.
> Equivalent Circuits of Power Transformers21
‘a’ link closed
←path for zero sequence current
Link closed if I0 can flow from line into transformer winding
‘a’ link open
No I0 in neutral∴ none in line as I0 in each phaseis in phase
unearthed
I0 not possible in line asconsistent current distribution in delta not possible
> Equivalent Circuits of Power Transformers22
General zero sequence equivalent circuit for two winding transformer
Primary Secondaryterminal terminal
On appropriate side of transformer:
Earthed star winding - Close link ‘a’Open link ‘b’
Delta winding - Open link ‘a’Close link ‘b’
> Equivalent Circuits of Power Transformers23
Delta-star transformer Zero sequence equivalent circuit
There is a transfer of zero-sequence current between windings – the impedance presented being the zero sequence leakage inpedance.
Viewed from the star side, the Δ winding appears as a short circuit to zero sequence current.
Viewed from the delta side, the transformer appears as an open circuit (no zero sequence current in line connections).
Single phase equivalent circuit
> Equivalent Circuits of Power Transformers24
> Equivalent Circuits of Power Transformers25
Example
> Equivalent Circuits of Power Transformers26
Example continued …
0 IaIaI
AMPS473pu18041.5 aIIaI
)A5.87I(
AMPS473 pu041.5 III
:R At
30II30II
AMPS9843
A1050I pu375.9IIII
pu125.332.0
0.1III
)R(22
)R(1C
)R(2)R(12
B
b
)R(2)R(1A
2)R(21)R(1
b021F
021
132 kV / 11 kV
Current Distribution
> Equivalent Circuits of Power Transformers27
Transformer Sequence Impedances
For or transformers
ZM1 >> ZP1 or ZS1
ZM0 >> ZP0 or ZS0
Thus ZM1 and ZM0 are usually ignored.
Positive sequence
Equivalent cct
Zero sequence
Equivalent cct
Also Z1 = Z2 = Z0
> Equivalent Circuits of Power Transformers28
For transformers
Similar to above but:
Z0 ≈ 0.85 Z1 for 3-limb core type
Z0 = Z1 for 5-limb core type
shell type
3 x 1 phase units
> Equivalent Circuits of Power Transformers29
Zero Sequence Equivalent Circuits
> Equivalent Circuits of Power Transformers30
Two Winding Transformer Zero Sequence Network
> Equivalent Circuits of Power Transformers31
NOTE!
“Source” earthing arrangements can affect transformer zero sequence diagram.
Eg:
> Equivalent Circuits of Power Transformers32
Measurement of Transformer Impedance(Two Winding Transformer)
Require two tests:(a) Open circuit test(b) Short circuit test
Consider equivalent circuit:
Open Circuit Test Short Circuit Test
Tests are repeated from secondary side.
To give Zo/c’ = Zs + ZM
Zs/c’ = Zs + ZPZM
ZP + ZM
In pu Zo/c ≈ Zo/c’ and Zs/c ≈ Zs/c’
> Equivalent Circuits of Power Transformers33
Star/Delta Transformer
Zero sequence impedance
Open circuit test:
Short circuit test:
> Equivalent Circuits of Power Transformers34
ZM can be ignored for positive and negative sequence network.
ZM0 cannot be ignored for zero sequence network
Eg:
Zero Sequence Network
Typically:
Z0 = (ZS0 + ZM0) = 50 – 100% for 3-limb core type
= 100 – 500% for 5-limb core type
(400%) shell type
3 x 1 phase units
Non-Earthed Star Winding
> Equivalent Circuits of Power Transformers35
Interconnected Star (Zig-Zag) Windings
Positive sequence current distribution
Zig-zag / Star transformer
> Equivalent Circuits of Power Transformers36
Consider ampere-turns on ‘A’ Phase zig-zag winding
For ampere-turn balance
Zig-zag / star transformer has 30° phase shift for positive sequence quantities
30IT3033
IT
)a1(3
IT3
TxIa
3
TxI.T.A
2
2
30 I (a) I Thus
T (a) I 30 IT
A.T.Star A.T.zag-Zig
> Equivalent Circuits of Power Transformers37
Zy 11
Zy 1
Zd 0
> Equivalent Circuits of Power Transformers38
As with / connections the / connection introduces opposite
phase shifts for positive and negative sequence components.
Positive (and negative) sequence impedance:
Determined in usual manner by:
a) Open circuit test
b) Short circuit test
From both sides of transformer.
Again magnetising impedance can usually be ignored.
Thus equivalent single phase circuit:
Zig-Zag Transformers
> Equivalent Circuits of Power Transformers39
Zig-Zag TransformersZero Sequence Current Distribution
Net ampere turns on each phase = 0
∴ current in secondary winding = 0
Zero sequence current can flow in zig-zag winding without regard to any other winding.
Leakage flux is very small, therefore inductive reactance to zero sequence current is small.
> Equivalent Circuits of Power Transformers40
Zig-Zag Transformers
As there is no transfer of zero sequence current across the transformer, the zero sequence impedance viewed from the star side is high (effectively the zero sequence magnetising impedance)
Zero sequence equivalent circuit:
> Equivalent Circuits of Power Transformers41
Zig-Zag Earthing Transformers
Positive (and negative) sequence impedance is very high.
Equivalent circuit:
Zero sequence impedance is very low.
Equivalent circuit:
> Equivalent Circuits of Power Transformers42
Three Winding Transformer
Equivalent circuits can be found by performing open circuit and short circuit tests on each pair of windings in turn with the third winding open circuit.
Primary to Secondary Test
Primary to Tertiary Test
Secondary to Tertiary Test
etc
> Equivalent Circuits of Power Transformers43
Three Winding TransformerEquivalent Circuit
> Equivalent Circuits of Power Transformers44
Three Winding TransformerFor positive (negative) sequence tests
Thus, from the short circuit tests,
Primary to Secondary
Primary to Tertiary
Secondary to Tertiary
From these equations
> Equivalent Circuits of Power Transformers45
Three Winding TransformerZero Sequence Impedance
Each winding requires consideration in similar manner to two winding transformers.
Eg:
NB!
All impedances must be expressed to common base quantities
The star point of the above impedance network is a fictitious point and does not represent the system neutral
> Equivalent Circuits of Power Transformers46
Primary Tertiary Secondary
IPO induces current in secondary and tertiary current in delta ITO – proportion of IPO not converted into secondary zero sequence current.
ie. Proportion trapped in delta
‘b’ link closed for delta
‘a’ link closed for star
> Equivalent Circuits of Power Transformers47
Positive Sequence Network
Negative Sequence Network
Zg2 ZT2 ZP2 ZT2
ZS2
F2
N2
LOAD
Zg1 ZT1 ZP1 ZT1
ZS1
F1
N1
LOAD
> Equivalent Circuits of Power Transformers48
Zero Sequence Network
Zg0 a ZT0 a 3Zn1 3Zn2 a ZP0 ZT0 a
3Zn b b b
b
a
b
3Zn3 F0
N0
> Equivalent Circuits of Power Transformers49
Auto Transformers
Has a single winding per phase, part of which is common to bothprimary and secondary
A
B
C
series-commonwinding
serieswinding
commonwinding
HV
SIDE
LV
SIDE
> Equivalent Circuits of Power Transformers50
The positive (negative) sequence is obtained in similar way to two winding transformers.
For auto transformers with delta winding (ie. similar to 3 winding transformer):
Equivalent star impedances
> Equivalent Circuits of Power Transformers51
Auto TransformersZero Sequence Impedance
Similar to 2/3 winding transformers
Eg. For autotransformer with earthed neutral and delta winding
> Equivalent Circuits of Power Transformers52
> Equivalent Circuits of Power Transformers53
Auto Transformers
ZN is common to both HV and LV system
Zero sequence network:
Where n = HV voltage ratioLV
If PU → ZN referred to LV base quantities
If ZN in ohms → ZH, ZL & ZT must be referred to LV network
> Equivalent Circuits of Power Transformers54
Positive Sequence Network
Negative Sequence Network
Zg1 ZT1 ZL1 ZT1
ZH1
F1
N1
LOAD
E1
Zg2 ZT2 ZL2 ZT2
ZH2
F2
N2
LOAD
> Equivalent Circuits of Power Transformers55
Zero Sequence Network
Zg0 a ZT0 a 3Zn1 a
n
1n 3Zn2 ZL0 ZT0 n
Z3 2n
a
b
a
b
F0
N0
ZH0
3Zn b b b
2n
1n 3Zn2
> Equivalent Circuits of Power Transformers56
Typical Transformer Impedances
2 Winding Transformers
1 MVA 4.75 → 6%
5 MVA 6 → 7.5%
10 MVA 9 → 11%
15 MVA 10 → 15%
30, 45, 60 MVA 10 → 12.5%
90 MVA 15 → 22.5%
120 MVA 15 → 20%
210, 425 MVA 17%
600 MVA 14 → 17%
800 MVA 14 → 16%
Auto Transformers with Delta Tertiaries
ZH ZL ZT
120 MVA; 275/132 kV 17.5% -2.5% 20.5%
500 MVA; 400/132 kV 20% -8% 60%
1000 MVA; 400/275 kV 21% -5% 89%