01 equivalent circuits
TRANSCRIPT
-
7/31/2019 01 Equivalent Circuits
1/12
Equivalent Circuit of Power System ComponentsGenerator
Equivalent Circuit of an AC Generator
Eg generated emf at no load due to the field excitation
Xar: reactance due to the armature reaction known as
fictitious reactance.Xl: reactance due to the leakage flux known as leakage
reactance orpotier reactance.
Xs: summation of Xar and Xl known as synchronous
reactance.
Ra: resistance die to armature winding known as armature
resistance.
Er: voltage behind the armature reaction effect.
Vt: terminal voltage.
If the resistance Ra is very small as compared to Xs, the equivalent circuit of an ac generator can be
simplified as shown in the following figure (a). Similarly, the simplified equivalent circuit of an ac
motor can be given as shown in figure (b).
Transformer (XF)The transformer is a device for transferring electrical energy from one circuit to another circuit without
a change in frequency.
Features of a Transformer
1. Transfer electrical energy from one circuit to another circuit by changing voltage and current2. Frequency cannot be changed3. Energy transformation is accomplished by electromagnetic induction4. Electrical circuits are magnetically coupled no direct electric connection5. Efficiency is high and mantainence is simpler since there has no rotating parts
Main Components of a Transformer
1. The magnetic core2. Primary and secondary windings3. Insulation of windings4. Lead and tapping for coils with their supports, terminals and terminal insulator5. Tank, oil, cooling arrangement etc.
Application of Transformer
1. Stepping-up of voltage
-
7/31/2019 01 Equivalent Circuits
2/12
2. Stepping-down of voltage3. Electrical Isolation4. Impedance matching5. Link between AC and DC systems6. Instrument extension
Classification of Transformer
Transformer can be classified according to the following ways:1. Based on number of phases
(a)Single-phase transformer(b)Three phase transformer
2. Based on relative position (construction) of winding and core(a)Core type transformer(b)Shell type transformer
3. Based on number of winding per phase(a)One winding per phase(b)Two winding per phase(c)Three winding per phase
4. Based on volt-ampere and voltage ratings(a)Low voltage transformer [VHV < 1.1 kV](b)Medium voltage transformer [1.1 kV VHV < 11 kV](c)High voltage transformer [VHV 11 kV]
5. Based on service conditions(a)Power transformer(b)Distribution transformer(c) Instrument Transformer
i. Current transformerii. Potential transformer
6. Based on method of cooling(a)Air Natural(b)Air Blast(c)Oil Natural(d)Oil Blast(e)Forced Oil Cooling(f) Oil and Water Cooled(g)Forced Oil and Water Cooled
Current (or Series) Transformer (CT)Used with low-range ammeters to measure current in high-current ac circuit
Step up the voltage
Step down the current
Has a primary coil with one or more turns of thick wire connected in series with the line whose current
is to be measuredHas a secondary coil with a large number of turns of fine wire and connected across the ammeter
terminals
-
7/31/2019 01 Equivalent Circuits
3/12
If the current transformer has primary to secondary current ratio (I1/I2) of 100:5, then it steps up the
voltage 20 times whereas it steps down the current to (1/20) th of its actual value.
One of the most commonly used current transformer is the one knownclamp-type orclip-on type.
Since the ammeter resistance is very low, the current transformer normally works short circuited.
The secondary of a current transformershould never be left open under any circumstances. If this not
done, then due top the absence of counter amp-turns of the secondary, the unopposed primary mmf
will set up an abnormally high flux in the core which will produce excessive core loss with subsequent
heating and a high voltage across the secondary terminals.
Potential Transformer (PT)Used with low-range voltmeter to measure high
voltage in high-voltage ac circuit
Step down the voltage
Step up the current
For safety, the secondary should be completely
insulated from the high-voltage primary andshould be, in addition, grounded for affording
protection to the operator.
Equivalent Circuit of a Practical Transformer
R1, X1, I1, V1, E1: primary side resistance, leakage reactance, current, voltage, and counter (or self
induced) emf, respectively.
-
7/31/2019 01 Equivalent Circuits
4/12
R2, X2, I2, V2, E2: secondary side resistance, leakage reactance, current, voltage, and counter (or self
induced) emf, respectively.
R0 (orRc orRm),X0 (orXm): core loss resistance, mutual inductance, respectively.
I0,I (orIc) Iw: no-load current, magnetizing current, and working or core loss current, respectively.
If all secondary parameters are referred to the primary side then the equivalent circuit becomes:
R2= R2/K
2;X2
= X2/K
2;E2
=E2/K=E1; V2
=V1/K.
-
7/31/2019 01 Equivalent Circuits
5/12
Parameters of Transmission (TM) LineThe basic transmission-line parameters are:
1. Series resistance: Series resistance accounts for copper (or ohmic or I2R) losses.The resistance of a conductor at a specified temperature is
A
l=
dcR
Resistance of a conductor depends of the following factors:
(a)Spiraling(b)Temperature(c)Frequency (due o skin effect)(d)Current magnitude magnetic conductor
2. Series inductance (or inductive reactance): Series inductive reactance gives rise to series voltagedrops along the line.
The inductance of a magnetic circuit that has a constant permeability can be obtained by
determining the following:
(a)Magnetic field intensityHfrom Amperes Law(b)Magnetic flux densityB (B=H)
(c)Flux linkage (d)Inductance from flux linkage per ampere (L=/I)
3. Shunt capacitance (or capacitive reactance): Shunt capacitive reactance gives rise to line-charging current.
The capacitance between conductors in a medium with constant permittivity canobtained by
determining the following:
(a)Electric field strengthE, from Gausss Law(b)Voltage between conductors(c)Capacitance from charge per unit volt (C=q/V)
4. Shunt conductance (or admittance): Shunt conductance accounts for real power (V2G) linelosses due to leakage currents between conductors or between conductors and ground. Shunt
conductance of overhead line is usually neglected since this loss is very small compared to copper
loss..
This power loss is due to leakage currents at insulators and to corona.
Corona occurs when a high value of electric field strength at a conductor surface causes the air to
become electrically ionized and to conduct. The real power loss due to corona, calledcorona loss,
depends on meteorological conditions, particularly rain, and on conductor surface irregularities.
Series impedance is including the series resistance and series inductive reactance
Representation of Transmission LineLet,
R is series resistance per unit length (/m) and per phaseG is shunt conductance per unit length (S/m) and per phase
L is series inductance per unit length (H/m) and per phase
Cis shunt capacitance per unit length (F/m) and per phase
z =R +jL is series impedance per unit length (/m) and per phase
y = G +jCis shunt admittance per unit length (S/m) and per phase
l is line length (m) and per phase
-
7/31/2019 01 Equivalent Circuits
6/12
Z=zl is total impedance () and per phase
Y=yl is total impedance (S) and per phase
Short-Transmission Line (less than 80 km): For a short-transmission line, shunt capacitance is so
small that it can be omitted entirely with little loss of accuracy, and we need to consider only the series
resistance and the series inductance for the total length of the line.
Medium Transmission Line (from 80 to 250 km): A medium-length line can be represented
sufficiently well by series resistance, series inductance as lump parameters with half the capacitance to
neutral of the line lumped at each end of the equivalent circuit.
-
7/31/2019 01 Equivalent Circuits
7/12
Fig. 5.6 Nominal- circuit of a medium-length transmission line
Fig. Nominal-T circuit of a medium-length transmission line
VS, VR are sending end and receiving end voltages.
IS,IR are sending end and receiving end currents.
Long Transmission Line (more than 250 km): The exact solution of any transmission line and the
one required for a high degree of accuracy more than approximately 150 mile long must consider the
fact that the parameters are not lumped but are distributed uniformly through out the length of the line.
xeZIVxeZIVV cRRcRR +=22
; xeIZVxeIZVI RcRRcR +=2
/2
/
yzZc /= ischaracteristic impedance of the line
jzy +== ispropagation constant
isattenuation constant
isphase constant
-
7/31/2019 01 Equivalent Circuits
8/12
Fig. 5.8 Equivalent- circuit of a long transmission line
The One Line or Single Line Diagram [1, 6.11, p. 155]In power engineering, a one-line or single-line diagram is a simplified notation for representing athree-phase power system.
A simplified diagram of an electrical system is called one-line or single-line diagram. The purpose of
the one-line diagram is to supply in concise form the significant information about the power system.
The one-line diagram has its largest application in power flow studies. Electrical elements such as
circuit breakers, transformers, capacitors, bus bars, and conductors are shown by standardized
schematic symbols as shown in the following Table 1.
Instead of representing each of three phases with a separate line or terminal, only one conductor is
represented. It is a form of block diagram graphically depicting the paths for power flow between
entities of the system.
Elements on the diagram do not represent the physical size or location of the electrical equipment, but
it is a common convention to organize the diagram with the same left-to-right, top-to-bottom sequence
as the switchgear or other apparatus represented.
Why one line diagram?
1. Power systems are extremely complicated2. Geographically spread system3. Three phase (3) System
Need a simple way to express the network
Characteristic
1. Concise form of basic arrangement of PS2. Not show the exact electrical connection3. Expressed in block diagram4. Diagram varies for different purposes
Fig. 6.26 is the one-line diagram of a very simple power system. Two generators, one grounded
through a reactor and one through a resistor, are connected to a bus and through a step-up transformer
to a transmission line. Another generator, grounded through a reactor, is connected to a bus and
through a transformer to the opposite end of the transmission lie. A load is connected to each bus. On
the diagram information about the loads, the rating of the generator and transformers, and reactances
of the different components of the circuit is often given.
-
7/31/2019 01 Equivalent Circuits
9/12
Machine or
(basic)
Two wtransformer
Three
transformer
Fuse
Current tra
Potential tr
Ammeter
hy Grou Pro
Gro
indu
rotating ar
inding
inding
sformer (C
nsformer (
ding?ect against t
unded can
ctor doesnt
ature
ower
ower
)
T)
he faulty C
be solid or
have any ef
Table 1 A
ndition
through re
fect on the
pparatus Sy
Po
(O
Air
Thr
con
Thr
ung
Thr
gro
rThr
gro
or r
Vol
sistor or re
teady-state
mbols
er circuit
B) or other
circuit brea
e-phase thr
ection
e-phase
rounded
e-phase
nded
e-phase
nded throu
sistor
meter
actor/induct
operation
breaker, o
liquid
er
ee wire delt
ye, neutr
ye, neutr
ye, neutr
gh a react
or. This ad
il
a
l
l
l
r
ditional res
or
or
istor or
-
7/31/2019 01 Equivalent Circuits
10/12
Fig. 6.26 One-line diagram of an electrical system.
Impedance and Reactance Diagram [1, 6.12, p.157]A single-phase circuit diagram is drawn from the one-line diagram to calculate the performance of a
system under load conditions or upon the occurrence of a fault.
Fig. 6.27 combines the equivalent circuits of the various components shown in Fig. 6.26 to form the
impedance diagram of the system.
The shunt admittance in an equivalent circuit of a transformer is usually omitted, since the magnetizing
current is usually insignificant compared with the full-load current.
Shunt conductance of overhead line is usually neglected since this loss is very small compared tocopper loss.
In transmission line, transformer and synchronous machine the resistance is very small as compared to
the reactance, so resistance is often omitted from the circuit when making fault calculation.
Fig. 6.27.1 is the simplified impedance diagram of Fig. 6.27.
Fig. 6.27 Impedance diagram corresponding to the one-line diagram of 6.26.
If a fault is occurred in the transmission line then loads are disconnected. If the impedance diagram is
simplified by omitting all static loads, all resistances, the magnetizing current of each transformer, all
the capacitance of the transmission line, the impedance diagram reduces to the reactance diagram of
Fig. 6.28. These simplification apply to fault calculations only and not to load-flow studies.
-
7/31/2019 01 Equivalent Circuits
11/12
Fig. 6.27.1 Simplified impedance diagram of Fig. 6.27.
Fig. 6.28 Reactance impedance diagram of Fig. 6.27.
References
[1] Willaim D. Stevenson, Elements of Power System Analysis, Fouth Edition, McGraw-HillInternational Editions, Civil Engineering Series, McGraw-Hill Inc.
[2] John J. Grainger, William D. Steevnson, Jr., Power System Analysis, McGraw-Hill Series in
Electrical and Conputer Engineering, McGraw-Hill Inc.
[3] J. Duncan Glover, Mulukutla S. Sharma, Thomas J. Overbye, Power System Analysis and Design,
Fouth Edition (India Edition), Course Technology Cengage Learning
[4] V. K. Mehta, Rohit Mehta, Principles of Power System, Multicolor Illustrative Edition, S. Chand
and Company Limited
-
7/31/2019 01 Equivalent Circuits
12/12
Home Work 01Draw the (i) simplified impedance diagram, and (ii) reactance diagram for the following figures.
Fig. (a) For example
Fig. (b) For example
Fig. (c) For example