® If you have a problem, question, or request, call your local dealer, or Steelcase Line 1 at 888.STEELCASE (888.783.3522) for immediate action by people who want to help you. (Outside the U.S.A., Canada, Mexico, Puerto Rico, and the U.S. Virgin Islands, call: 1.616.247.2500) Or visit our website: www.steelcase.com © 2001 Steelcase Inc. Grand Rapids, MI 49501 U.S.A. Printed in U.S.A. Page 1 of 12 939504304 Rev H Series 9000 ® Enhanced & ap40 Power Pole

Upload: vuongtu

Post on 13-Jul-2019

213 views

Category:

Documents


0 download

TRANSCRIPT

®

If you have a problem, question, or request, callyour local dealer, or Steelcase Line 1 at888.STEELCASE (888.783.3522)for immediate action by people who want to help you.

(Outside the U.S.A., Canada, Mexico, Puerto Rico, and the U.S. Virgin Islands, call: 1.616.247.2500)Or visit our website: www.steelcase.com© 2001 Steelcase Inc. Grand Rapids, MI 49501 U.S.A.

Printed in U.S.A.

RAYBO

Page 1 of 12939504304 Rev H

Series 9000® Enhanced & ap40™ Power Pole

Page 2 of 12939504304 Rev H

WARNING:ALL ELECTRICAL INSTALLATIONS SHOULD BE

PERFORMED BY A QUALIFIED PERSON IN ACCORDANCEWITH CODES AND REGULATIONS APPLICABLE AT THEINSTALLATION SITE. CIRCUITS SHOULD BE CHECKED

FOR PROPER VOLTAGES

System Flag Color

-3-Circuit, Shared Neutral and System Ground (SHN) Black

-4-Circuit, 3 with Shared Neutral and System Ground

and 1- Isolated Circuit and Ground (3+D) Black

Optional Wiring Schematics: System Flag Color

-2-General Circuits with Shared Neutral & System Ground

and 2-Isolated circuits with Shared Neutral and Isolated Ground (2+2) Grey

-3-Separate Circuits - 2 with own Neutral and Isolated Ground,

1 with own Neutral and System Ground (SPN) White

-4-Circuit - 3 with Shared Neutral and Isolated Ground,

1-Circuit with System Ground) (3I+1) Tan

Wiring

Page 3 of 12939504304 Rev H

Wiring Schematic

GROUND

P-1 P-2 P-3

NEUTRAL

LINE 1

LINE 1

LINE 3

LINE 2

SHARED NEUTRAL

SYSTEM GROUND

ISOLATED GROUND

LINE 2 LINE 3

LINE 4

SHARED NEUTRAL

NOTE:L-1, L-2, & L-3 are connected to P-1, P-2 & P-3 respectively. L-4 is connected to P-1 or P-2 only and not to the samephase as L-3.

NOTE:L-1, and L-2 must be connected to different phases. L-3 and L-4 must be connected to different phases.

NEUTRAL A

NEUTRAL

GROUND

GROUND

GROUND

NEUTRAL BNEUTRAL C

ISOLATED GROUND

P-1 P-2 P-3

NEUTRAL

LINE 1

LINE 1Red

Black

Red

Blue

Red

BluePink

White/Red LettersGray

White/Black LettersGreen/YellowGreen

Black

Red

PinkBlue

Blue

Pink

LINE 2

SHARED NEUTRA LWhite/ Black Letters

White/Red Letters

Gray

Green/Yellow

Green

Whi

te/R

ed L

ette

rs

Whit

e/Blac

k Let

ters

Whit

e/Red

Let

ters

Green

Green

/Yell

ow

Gre

en/Y

ello

w

Whi

te/B

lack

Let

ters

Gre

en

SYSTEM GROUNDLINE 3

LINE 4

SHARED NEUTRAL

ISOLATED GROUND

LINE 2

P-1 P-2 P-3

NEUTRAL

LINE 3 LINE 4

SYSTEM GROUND

P-1 P-2 P-3LINE A

LINE A

LINE C

LINE B

LINE B LINE C

2+2 - Powered by Separate Panels

GROUND

GROUND

P-1 P-2 P-3

NEUTRAL

NEUTRAL

LINE A

LINE A

LINE B

NEUTRAL ANEUTRAL B

ISOLATED GROUND LINE C

NEUTRAL C

SYSTEM GROUND

LINE B

P-1 P-2 P-3LINE C

3 Circuit, Separate Neutrals Powered by Separate Panels 3 Circuit, Separate Neutrals Powered by Single Panels

WARNING:

Risk of Fire or Electric Shock: This office furnishing systemmay be connected to more than one source of supply. All

sources must be disconnected prior to any servicing.No single circuit may be powered by more than one source.

2+2 - Powered by Single Panels

ELECTRICAL DATA:125 V 60 HZ 20 Amp USA/CANADA

208Y/120 VAC 3-Phase Service250/125 VAC 1-Phase Service

Wiring schematics must be followedto prevent overloading of the neutrals.

Pink

Page 4 of 12939504304 Rev H

Wiring Schematic

GROUND

GROUND

GROUND

GROUND

P-1 P-2 P-3

NEUTRAL

LINE 1

LINE 1Red

Pink

Black

Blu e LINE 3

LINE 2

SHARED NEUTRALWhite/Black Letters

Whi

te/R

ed L

ette

rs

Gre

en

Green/Yellow

SYSTEM GROUND

LINE 4

NEUTRAL

ISOLATED GROUND

LINE 3

SHARED NEUTRAL

SYSTEM GROUND

LINE 2

P-1 P-2 P-3

NEUTRAL

LINE 3

LINE 4

P-1 P-2 P-3

NEUTRAL

LINE 1

LINE 1Red

Black

Pink

Gray

Blue LINE 3

3+D - Powered by Separate Panels 3+D Powered by Single Panel

LINE 2

SHARED NEUTRALWhite

Green SYSTEM GROUNDLINE 4

NEUTRAL

ISOLATED GROUND

LINE 2

P-1 P-2 P-3

NEUTRAL

LINE 3

LINE 4

GROUND

P-1 P-2 P-3

NEUTRAL

LINE 1

LINE 1Red

BlackBluePink

Whit

e

Gray

Green

Green

/Yell

ow

LINE 3

LINE 2

NEUTRAL

SYSTEM GROUND

ISOLATED GROUND

LINE 2 LINE 3

LINE 4

SHARED NEUTRAL

GROUND

P-1 P-2 P-3

NEUTRAL

LINE 1

LINE 1Red

BlackBlue

White

Green

White

Green

LINE 2

LINE 2 LINE 3

3I+1 - Powered by Separate Panels

LINE 3

SHARED NEUTRAL

SYSTEM GROUNDGROUND

P-1 P-2

NEUTRAL

LINE 1

LINE 1Red

Black

BlueLINE 2

LINE 2

3I+1 - Powered by Single Panel

NOTE:L-4 may be connectedto P-1, P-2, or P-3

NOTE:L-4 may be connectedto P-1, P-2, or P-3

NOTE:L-3 must be omitted or connected to the load side of L-1 or L-2.

NOTE:L-4 should alternate between P-1, P-2, and P-3 to balance circuit loading.

GROUND

P-1 P-2 P-3

NEUTRAL

LINE 1

LINE 1Red

BlackBluePink

Whit

e/Blac

k Let

ters

Whit

e/Red

Let

ters

Green

Green

/Yell

ow

LINE 3

LINE 2

NEUTRAL

SYSTEM GROUND

ISOLATED GROUND

LINE 2 LINE 3

LINE 4

SHARED NEUTRAL

NOTE:L-4 should alternate between P-1, P-2, and P-3 to balance circuit loading.

WARNING:

Risk of Fire or Electric Shock: This office furnishing systemmay be connected to more than one source of supply. All

sources must be disconnected prior to any servicing.No single circuit may be powered by more than one source.

ELECTRICAL DATA:125 V 60 HZ 20 Amp USA/CANADA

208Y/120 VAC 3-Phase Service250/125 VAC 1-Phase Service

Wiring schematics must be followedto prevent overloading of the neutrals.

Gre

en/Y

ello

w

3 Circuit, Shared Neutral 3 Circuit, Shared Neutral Powered by Split Phase Panel

Page 5 of 12939504304 Rev H

“X” Configuration

End of Run

“L” Configuration

“T” Configuration

Pre-Installation Notes = Power Pole cannot be installed. = Power Pole can be installed. = Mount Power Pole to this panel.

Power Pole connection to the Powerway can only be made on the green end, brown side of Powerway.

X

.1

2

3

4

5

6

Page 6 of 12939504304 Rev H

- Powered by Separate Panels

7. Hinge and End Cover Arrangements

Note: An "L" panel installation is shown. X, T,and End of Run arrangements are similar.

8. Power Pole to PanelPower pole may be installed onto either panel.

Page 7 of 12939504304 Rev H

- Powered by Separate Panels

9. Ceiling obstruction lower than 131 inches will requirecutting of equal amounts off cover, retainer,and conduitto insure exact fit. NOTE: When cutting conduit usecaution to avoid damage to wires inside conduit.

1 Cut Cover to desired length2 Cut retainer to same length3 Re-drill retainer4 Remove elbow assembly5 Cut conduit to same length as cover

Use cut-off retainer section for drill template

Less than 131"

Retainer

Cover

Conduit

A

A

A

4

5

1

2 3

Page 8 of 12939504304 Rev H

- Powered by Separate Panels

10. Box and Upper Cover Retainer assembly

4

5

3

1

2

NOTE: Power may be connected to either panel.

Page 9 of 12939504304 Rev H

11. Installing Cable Door

2

1

2

3

5

6

4

Page 10 of 12939504304 Rev H

12. Lower Cover Retainer Assembly

1 Install Base filler 2 Install filler

NOTE: Line top of filler with top of upright (A)

13. Installation of Power Pole Cover 1 Install 2 Install filler

Top of Panel

Filler

A

1

21

23

4

Page 11 of 12939504304 Rev H

14

15

16

5 x 5127mm x 127mm

Page 12 of 12939504304 Rev H

17

NOTE: For access to cable area of power pole assembly you must remove all ceilingbrackets first, then reverse the installation procedures.