VOLTAGE DROP SPREADSHEET SINGLE OR THREE PHASEPROJECT: DATE 3/29/94UNION CREEK CAMPGROUND VOLTAGE DROP

ENTER DATA HERE CALCULATEDLOAD KVA PHASE Voltage Power Factor Length WIRE SIZE R X CURRENT VOLTS

1 OR 3 L-L KV 0.5-1.0 KFT AWG OHM/KFT OHM/KFT AMPS DROP

5.52 1 0.23 0.90 0.15 #10 1.200 0.050 24.00 7.93

5.52 1 0.23 0.90 0.15 #8 0.780 0.052 24.00 5.22

5.52 1 0.23 0.90 0.15 #6 0.490 0.051 24.00 3.34 0.00 3 0.48 0.90 0.10 #8 0.000 0.000 0.00 0.00 0.00 3 0.48 0.90 0.10 #8 0.000 0.000 0.00 0.00

Generator to RV based on 24A load @120VAC

Generator to RV based on 24A load @120VACGenerator to RV based on 24A load @120VAC

Page 2: [XLS] · Web viewA PROJECT: UNION CREEK CAMPGROUND VOLTAGE DROP DATE 3/29/94 LOAD KVA PHASE WIRE SIZE #6 #8 1/0 #4 CU 3 SINGLE CONDUCTORS ALUM 3 SINGLE CONDUCTORS ALUM 3 SINGLE CONDUCTORS

CALCULATED%

VDROP

3.45%

2.27%

1.45%0.00%0.00%