wendy’s – borger, tx · wendy's company bid review notes june 17, 2020 wendy’s - #12817...
TRANSCRIPT
Addendum #1 Page 1 of 1 2810 Duniven Circle Amarillo, Texas 806/358-7069
Wendy’s – Borger, TX
ADDENDUM #1
DATE: June 19, 2020 FROM: Lavin Associates Architects TO: All plan holders of record PROJECT: Wendy’s – Borger, TX This addendum forms a part of the Contract Documents and modifies the original bidding documents dated May 29, 2020. Work not specifically deleted, modified, changed, or altered by this addendum should remain in effect as part of the Contract Documents. Acknowledge receipt of this Addendum on your Bid Form. Failure to do so may subject Bidder to disqualification. 1.01 See attached documents from Wendy’s:
A. Bid Review Notes (3 Pages), B. Construction Exhibit “B” (5 Pages) C. CaptiveAire 2018 Functional Checklist (5 Pages) D. Trane 2017 RTU Installation Certification (2 Pages) E. CaptiveAire 2018 Hood System - Functional Checklist (2 Pages) F. Geotech report (24 Pages) G. CPI 2019 Fan Control Panel Functional Test Checklist Smart Building (4 Pages) H. CPI 2019 Fan Control Panel Functional Test Procedures Smart Building (9 pages) I. CPI 2019 Fan Control Lighting Control Troubleshooting Smart Design (5 Pages), and J. Trane 2018 BAYSENS924 Thermostat Programming - Quick Reference (8 Pages).
ON THE DRAWINGS:
CIVIL
1.02 SHEETS C1.0, C2.0, C2.1, C3.0, C3.1, C3.2, C4.0, C7.2: Replace with the attached revised sheets.
ARCHITECTURAL
1.03 SHEET A6.3: Replace with the attached Sheet A6.3, which shows revisions to the vision panels for doors C and E that are required by the TAS plan review.
1.04 SHEET EQ1.1: Replace with the attached Sheet EQ1.1, which shows revisions to the community table required by the TAS plan review.
ELECTRICAL
1.05 SHEETS E1.0 and E3.1: Replace with the attached revised sheets.
END OF ADDENDUM #1
Wendy's Company
BID REVIEW NOTES June 17, 2020
WENDY’S - #12817 1419 Wilson Borger, TX
GC TO INCLUDE BUILDERS RISK INSURANCE WENDY’S MANAGING PROJECT ON BEHALF OF TOOT N TOTUM. CONTACT IS: MAT KNUPP BUILDING DESIGN IS WENDY’S PROTOTYPE SMART 55 SQE. BUILDING PERMIT APPLICATION HAS BEEN MADE BY THE ARCHITECT. DO NOT INCLUDE
COST OF PERMIT IN THE GC PROPOSAL. GC TO PICK UP AND PAY FOR THE PERMIT AND SUBMIT SEPARATE INVOICE FOR PERMIT COST.
SIGN PERMITS BY WENDY’S. ALL OTHER PERMITS ARE BY GC AND/OR SUBCONTRACTORS. ANY COSTS TO BE
INCLUDED IN PROPOSAL PROVIDE SCHEDULE AND PROJECT DURATION IN CALENDAR DAYS WITH THE PROPOSAL TURNOVER TO OPERATIONS PROJECT EXPECTATIONS
o PROJECT 100% COMPLETE EXCEPT FOR MINOR PUNCHLIST ITEMS o SITE PROFESSIONALLY CLEANED o ALL CONSTRUCTION MATERIALS, EQUIPEMENT, WASTE, ETC. HAS BEEN
REMOVED o ALL INSPECTIONS COMPLETE AND SIGNED OFF o RECEIPT OF CERTIFICATE OF OCCUPANCY
GAS & ELECTRIC APPLICATIONS HAVE BEEN MADE. GC TO ASSIST WITH APPLICATION AND IS RESPSONSIBLE TO SCHEDULE/COORDINATE INSTALLATION
TEMPORARY POWER IS BY GC GC REQUIRE TO MAKE APPLICATION/PAY TAP FEES FOR WATER SERVICE, SEWER
SERVICE, ETC. PREPARE AND SUBMIT WITH YOUR PROPOSAL EXHIBIT ‘A’ (DRAWING/EXHIBIT LIST)
STATING ALL DOCUMENTS INCLUDED IN YOUR PROPOSAL. EXHIBIT A WILL BECOME A PART OF THE GC CONTRACT.
o ARCHITECTURAL & CIVIL DRAWINGS o GEOTECH REPORT o EXHIBIT B o OTHER
Wendy's Company
EXHIBIT ‘B’ o GC TO THOROUGHLY REVIEW EXHIBIT B o EXHIBIT SPECIFIES WENDY’s VENDORS AND GC RESPONSIBILITIES o NOT SPECIFICALLY CALLED OUT IN EXHIBIT ‘B’
GC RESPONSIBLE TO COMPLETE CONDENSATE LINE IN ICS WALK IN BOX
ICS WALK IN BOX INTERNAL RAMP, SS BASE AND FLASHING INSTALLED BY GC
SITE IS AS IS. GC TO INCLUDE DEMO OF ANY/ALL EXISTING CONDITIONS: GEOTECH REPORT
o GC TO INCLUDE ALL REQUIRED SOILS WORK AS OUTLINED IN THE GEOTECH REPORT; INCLUDING BUT NOT LIMITED TO:
BUILDING AREA EXCAVATION/FILL PAVEMENT AREA STABILIZATION ALL REQUIRED SOIL TESTING/COMPACTION BY GC
GC TO PROVIDE UNIT PRICING FOR REMOVAL OF ADDITIONAL UNSTABLE SOIL AND UNIT PRICE TO IMPORT & PLACE COMPACTED FILL ($/CY)
GC TO INCLUDE 1 YEAR LABOR WARRANTY FOR RTU’S SUPPLIED BY WENDY’S RTU BASIS OF DESIGN IS TRANE, MAKE SURE SWITCHGEAR BID REFLECTS TRANE. CPI
IS THE ONLY APPROVED VENDOR FOR THE ELECTRICAL SWITHGEAR GC TO INCLUDE TRANSFORMER PAD, SECONDARY CONDUIT & WIRE; ASSUME 50 LF GC TO PROVIDE 2- 2” SLEEVES FOR IT/PHONE (100 LF EACH) STOOL SEATING CORED AND INSTALLED BY GC; SEE CODED NOTE 1 SHEET EQ1.1 WASHROOM SINKS FURNISHED AND INSTALLED BY GC ALL CORIAN WINDOWSILLS, WALL CAPS, ETC. ARE FURNISHED/INSTALLED BY GC. THE
CORIAN COUNTERTOPS ON THE FRONT COUNTER AND BEVERAGE BAR ARE FURNISHED AND INSTALLED BY WENDY’S VENDORS
LANDSCAPING/IRRIGATION WILL BE BY WENDY’S. GC TO INCLUDED: WATER TAP/CONNECTION, INCLUDING BACKFLOW FOR IRRIGATION SYSTEM. INCUDE OUTLET FOR IRRIGATION TIME CLOCK
ADA SURVEY WILL BE COMPLETED AT THE END OF THE PROJECT BY TEXAS TDR INSPECTOR
PAINT ALL SUBSTRATE BEHIND WT-2, BLACK PRIOR TO INSTALL OF WT-2 ALL SITE MENUBOARD FOOTINGS, DIRECTIONAL FOOTINGS, PRE-SELL BOARD
FOOTINGS, CLEARANCE BAR, ORDER CANOPY BY GC. WENDY’S SIGN VENDOR WILL PROVDE ANCHOR BOLTS AND TEMPLATES
INCLUDE IN PROPOSAL GC SUPT, ELECTRICIAN, PLUMBER & HVAC TRADESMAN TO BE AT STORE ON OPENING DAY TO RESOLVE ANY ISSUES THAT COME UP
GC IS NOT REQUIRED TO UTILZE HJC FOR MATERIAL PURCHASES. AN HJC QUOTE WILL BE PROVIDED FOR GC TO USE AT THEIR DISCRETION. GC RESPONSIBLE FOR VERIFYING ANY/ALL QUANTITIES
STAINLESS STEEL TRIM AROUND PUW’S FURNISHED AND INSTALLED BY GC HVAC “DUMP BOXES” SHOWN ON 3/M2.0 ARE TO BE FIELD FABRICATED BY GC/HVAC
SUB. EGGER NO LONGER MANUFACTURES.
Wendy's Company
ALL HVAC DIFFUSERS, REGISTERS, GRILLS, ETC FURNISHED/INSTALLED BY GC/HVAC
SUB CURB CUT/APPROACH ON WILSON IS BY OTHERS. PUBLIC SIDEWALKS ON WILSON ARE A PART OF THIS PROJECT AND TO BE INCLUDED IN
PROPOSL. ANY TXDOT PERMITS REQUIRED ARE BY GC PATIO FURNITURE IS SUPPLIED BY WENDY’S, INSTYALLED BY GC. CORING NOT
REQUIRED FOR INSTALLATION PATIO RAILING IS SUPPLIED AND INSTALLED BY GC (HJC CAN QUOTE MATERIAL) DUMPSTER ENCLOSURE MATERIAL TO BE COMPOSITE MATERIAL: AZEK, TRX, ETC.
CONSTRUCTION EXHIBIT “B” (#12817) 1419 W. Wilson
Borger, TX 1. Toot N Totum (Wendy’s) will provide and install the equipment or items listed below.
All work in this group is to be scheduled and supervised by the GC in order to maintain a schedule that will satisfy the projected completion date of the project. The GC is to monitor the quality of workmanship and act as Wendy’s agent in supervision of the installation of each item. A. Kitchen equipment and seating including installation per schedule shown on sheet EQ1.1 &
EQ1.2 of the architectural drawings. All kitchen equipment is delivered and installed by Wendy’s kitchen equipment consolidator or by specialty contractors for certain items. Prior to delivery the following must be completed: Floor tile installed & grouted Acoustical ceiling grid and panels HVAC systems Dining room paneling, and tile installed Wall coverings and/or finishes All final plumbing and electrical connections are the responsibility of the General Contractor and Subcontractors.
B. Building permits. Permits will be applied for by the Architect and/or Wendy’s Construction Manager. GC is responsible to complete any contractor information and obtain and pay for the Building Permit. The GC will send a separate invoice to Wendy’s for the cost of the Building Permit without any mark up. Do not include the cost of the permit in your proposal. Any/all other permits, licenses or bonds required of General or Subcontractors will be the responsibility of the appropriate contractor and should be included in your proposal.
C. Cash register system, monitors, menu board & order confirmation board, Digital menu boards, vertical display boards. These items will be installed by a Wendy’s supplier during the last week of construction but will be scheduled and supervised by the General Contractor. GC to provide electric outlets and data conduit and boxes.
D. Communication system. The Drive Thru communication system will be installed by a Wendy’s supplier during the last week of construction after the items in C above are complete. The Drive Thru detector loops will be provided to the General contractor for installation at the time the concrete drive thru lane is poured. Integrity of the loop and wiring will be the responsibility of the General Contractor.
E. Ansul system.
The exhaust hood fire suppression system and installation are included in the Wendy’s supplied hood package. The hoods are installed by the HVAC contractor and pull station rough-in is completed by the electrical contractor. The automatic gas valve shut off is supplied by Wendy’s and installed by the plumbing or gas piping contractor. The fire suppression system is completed by a Wendy’s subcontractor. All work is to be scheduled by the General Contractor.
F. Security system. The security alarm system is supplied by Toot N Totum and installed by a Toot N Totum contractor. Electric conduits and receptacles are installed by the electrical contractor.
G. Walk-in cooler/ freezer. The walk-in cooler/freezer is delivered and installed by a Wendy’s supplier under a separate contract with Wendy’s. Final electrical connection is by the GC/Electrical sub-contractor.
H. Building signage including final connections.
General Contractor to provide electrical feed for all building and site signs.
I. Site signage including final connections and concrete bases.
Sign installation contractor and all sign materials are provided by Wendy’s. General Contractor, through the electrical contractor, is responsible for conduit and wire to each sign location as shown on the plans. All concrete bases are installed by the GC. All final electrical connections are completed by the sign contractor if the electrical contractor has completed all conduit and wiring. If circuits are not complete the electrical contractor will assume responsibility for the final connections. Scheduling and supervision are the responsibility of the General Contractor.
J. Music system.
Sound system is furnished by Wendy’s and installed by a Wendy’s approved installer. Ceiling Grid must be in place for installation to proceed. General Contractor is responsible for scheduling.
K. Fire alarm system. (NOT APPLICABLE)
Fire alarm system is furnished by Wendy’s and installed by a Wendy’s approved installer. General Contractor is responsible for installation scheduling and coordination of required inspections and confirmation of all requirements for electrical rough-in, audio/visual and manual pull station locations.
L. Telephone wiring. Telephone wiring and jack installation is to be completed by the Phone Company. Installation scheduling of telephone service and interface box, or terminal strip is the responsibility of the General Contractor. Installation of Fire Alarm telephone circuit is the exclusive responsibility of the Fire Alarm Contractor, a Wendy’s subcontractor; however, scheduling is the responsibility of the General Contractor. General Contractor is responsible for site sleeve, rough in as shown on the plans, and plywood mounting pad for interface cabinet above office ceiling.
M. Free-Style soda system including CO2 tank.
The dining room and drive-thru window Free-style soda system is furnished and installed by Coke. In addition, Coke is responsible for the installation of the potable water filtering system which is to be connected to the water shut-off valve installed by GC. The CO2 tank, along with the recessed exterior wall fill box is furnished by Wendy’s. Installation scheduling is coordinated by the General Contractor during the last week of construction. Kitchen equipment installation must be completed prior to soda system installation. Soda lines are usually installed prior to the kitchen equipment installation.
N. Office desk, cabinets and shelving.
All office equipment and furnishings are furnished and installed by the kitchen equipment consolidator at the time of kitchen equipment installation.
O. Stainless steel wall panels at fryer wall.
Stainless steel wall panels and rear door kick panels are furnished and installed by the kitchen equipment consolidator at the time of kitchen equipment installation.
P. Safes
Safes (2) are furnished by Wendy’s and installed by Safe supplier during the last week of construction. Scheduling is coordinated by the General Contractor. All office cabinet installation must be completed prior to installation.
Q. Refrigeration.
The refrigeration lines are installed by the ice machine installer. Water supply, drain lines, roof penetrations and electric connections are the responsibility of the General Contractor and must be complete at the time of refrigeration installation since start-up and testing is required. The cook-center refrigeration is completed by the kitchen equipment consolidator.
R. TV Monitor & Wi-Fi service Dining room TV monitor supplied and installed by Wendy’s. General Contractor to provide ceiling outlets and roof penetrations for dish. Wi-Fi service and all necessary devices are to be provided and installed by Wendy’s.
S. Order station canopy and clearance height bar
GC to install foundation for order station canopy. Wendy’s vendor to install order station canopy along with clearance height bar & concrete base.
T. PUW Awnings. Wendy’s vendor to manufacture and install pick-up window awning. GC to provide Wendy’s vendor with rough framing dimensions. GC to include electrical circuit for heat tape and final connection
U. Exterior building pin letters Supplied by Wendy’s and installed by Wendy’s sign contractor.
V. Grease tank Wendy’s vendor to supply and install grease tank and flexible grease line run from kitchen grill/ fry area to tank. General Contractor to install solid piping to above ceiling at grill/ fry area.
W. Final Clean-up GC to provide a professional cleaning company to completely clean interior and exterior prior to turnover.
2. Toot N Totum will PROVIDE ONLY the equipment or items listed below: The General Contractor is responsible for receiving, storing, installing or coordinating the installation of the equipment listed. A. Kitchen equipment per schedule shown on sheet EQ1.1 & EQ1.2 of the architectural drawings.
All kitchen equipment as shown is furnished, delivered and installed by the kitchen equipment consolidator. The General Contractor is responsible to have all finishes completed prior to installation. The General Contractor and subcontractors are responsible for all final plumbing and electrical connections.
B. Exhaust hoods. The HVAC contractor is responsible for hood installation, black iron grease duct fabrication and installation and furnishing and installing duct wrap and clean out access doors.
C. Exhaust fans and curbs.
Wendy’s supplies the exhaust fans and curbs as a part of the hood package. GC/HVAC sub-contractor is responsible for the installation, wiring, hook up, & start up.
D. HVAC units, curbs.
Wendy’s supplies the HVAC (RTU’s) units and curbs. The HVAC contractor is responsible for, receiving, crane to remove from truck, setting in place, installation and start up. All plenums and ductwork between the curbs and diffusers or grilles are furnished and installed by the HVAC contractor. Crane rental for equipment hoisting is also the responsibility of the HVAC contractor. Hoisting of the ICS, ice machine and cook center condensers is also required, but only if the condensers are at the job site at the time the HVAC equipment is hoisted. The electrical contractor is responsible for electrical connections to the exhaust fans and HVAC units and verification off the direction of rotation of all 3 phase fans. The General Contractor is responsible for scheduling and supervising the installation of all HVAC equipment. All ductwork, diffusers, dump boxes, etc. is by supplied & installed by the GC/HVAC sub-contractor
E. Kitchen hand sinks. The plumbing contractor is responsible for installing handsink(s) and furnishing water supply and waste plumbing and trims. The plumbing contractor is responsible for final adjustment of handsink and lavatory hot water temperature not to exceed 110F.
F. Stainless steel kitchen corners. The General Contractor is responsible for plumb and square installation of all stainless steel kitchen corners and end caps.
G. Restroom paper towel dispensers, lavatories and baby changing tables. Touch-free battery operated lavatory faucets supplied by GC.
H. Ware Wash, Power soak sink and prep sink. The plumbing contractor is responsible for installation of the prep sink(s) including furnishing and installation of all supply and waste piping. Water supply lines for sinks are to include hot and cold check valves located outside of the wall. Lever wastes and faucets are furnished by the kitchen equipment consolidator. Detergent and Sanitizing Blend Center will be installed by the kitchen equipment installer with the exception of the plastic tubing and components that can only be installed at the time of power soak sink installation by the plumbing contractor. The plumbing contractor is responsible to install all water lines, etc. as detailed, and plumbing lines and hook up of ware wash. Electrical contractor to install power, disconnect and hookup as shown.
I. Dining room vinyl wall covering. Vinyl wall covering is installed by the General Contractor.
J. Fire extinguishers and cabinets.
Fire extinguisher cabinets and portable extinguishers will be furnished and installed by the General Contractor; not Wendy’s. The General Contractor is responsible for communication with the local fire department to verify extinguisher types and locations.
K. Kitchen paper towel dispensers and toilet paper dispensers. Towel dispensers and toilet paper dispensers will be furnished by Wendy’s and installed by the General Contractor. The General Contractor is responsible to verify the correct ADA location for the toilet paper dispensers.
L. Miscellaneous interior signs. Miscellaneous interior signs (Art Pack) are to be installed by the General Contractor in locations shown on the plans or as specified by the Wendy’s Construction Manager
P. Recessed stainless steel mop sink Wendy’s equipment supplier to provide.
Q. Outdoor Seating Area Seating elements and trash units delivered to site by Wendy’s and installed by GC. Security fence for outdoor seating to be provided and installed by GC.
R. Lot Lights Wendy’s vendor will provide the lot light anchor bolts, poles and heads. GC responsible to furnish and install conduit, wire, concrete bases; and install poles & heads. All final connections by GC. The GC is responsible to coordinate delivery of anchor bolts, poles and heads.
3. Communication with Wendy’s suppliers.
The general contractor is responsible to verify delivery dates for all equipment ordered by Wendy’s. Requested delivery dates will be provided on a purchase order log that lists the item, supplier, contact name, phone and fax numbers. The general contractor is responsible for notifying Wendy’s construction manager of any delays in delivery of equipment. The general contractor is not to change any scheduled delivery dates without a prior discussion with Wendy’s construction manager.
4. Receiving of equipment, materials and supplies ordered by Wendy’s.
The general contractor is responsible for receiving all items ordered by Wendy’s and verifying the condition of the items received. Visual inspection of all equipment and cartons must be made prior to signing for delivery. Damaged cartons must be noted on the shipper’s delivery ticket or bill of lading. The shipper or supplier and Wendy’s construction manager must be notified of any damaged equipment or damaged packaging within 24 hours. Failure to receive and properly store materials including but not limited to Coke supplies may result in backcharges.
5. On site storage of equipment, materials or supplies ordered by Wendy’s.
Wendy’s Construction Manager and Capital Control Coordinator will make every attempt to request ‘just in time delivery’ of equipment and materials to minimize the storage time required. The construction schedule is how the delivery dates are established. The General Contractor is responsible for providing clean, secure on-site storage for materials direct shipped to the job site for later installation. The General Contractor may opt to have certain materials or equipment to their own offsite facility for staging or to a subcontractor’s facility. Charges for this cannot exceed what would normally be associated with an on-site temporary storage trailer. Example of this is light poles delivered to an electrical contractor’s facility. These would be rare conditions and are dependent on the facilities and available equipment of the subcontractor. This is to be discouraged and due diligence in maintaining the construction schedule and receiving ‘just in time delivery’ is preferred. The ICS refrigerator/freezer is not to be used for temporary storage of any kind to avoid damage to the unit and to allow room for shelving and small wares at the time of kitchen equipment delivery. The estimated size of temporary storage required is one 20’ trailer or container dedicated exclusively to Wendy’s material and equipment storage. Contractor storage of tools and equipment are to be stored elsewhere. Open storage on site of certain materials is acceptable if minimum storage time is necessary, however, these materials must be protected from traffic, weather and theft with suitable covering and or protection from traffic or ground splash.
6. Storage of plans, specifications or other construction documents and receiving or shipping tickets.
The general contractor is required to provide secure space for storage and review of site and building plans and related documents. Dated and signed delivery tickets and bills of lading must be scanned and submitted to Wendy’s Construction Manager using Wentrack and have available at any time. Permit copies of the site and building plans are consigned to the General Contractor. These are to be maintained in good condition and are to be used for review at the time of any building or site inspection. They are not to be used by subcontractors for daily work. A job set of prints with field notes, as built information or changes to the scope of work through change orders or addenda needs to be maintained by the General Contractor. Copies of Wendy’s project inspection reports and receipts or sign off cards or pass/fail notices from site and building inspectors needs to be maintained and available at all times. Daily logs are to be maintained and should contain weather, manpower for general and subcontractors, deliveries, the day’s activities, unusual conditions encountered and communications from suppliers, municipal or utility agents, landlords, or adjacent property owners and uploaded weekly to Wentrack.
RQC-2017-061 Version-1 2/13/181 of 5Page
Supplies Necessary:
Test H4 and H5 Procedures:
1.
CaptiveAire2018 Functional Checklist Procedures
TestH4
Test Set-upEF-1 Grill Exhaust Fans -
Speed Set
HoodSwitch
RestaurantOpenSwitch
ON OFF
Fan RPM Readings Hood CFM Reading
Exhaust FanRPM Speed
Fan SpeedAfter Adjustment
Preliminary HoodCFM Reading
Final Hood CFMReading After
Adjustment
RPM/CFM Settings
TestH5
Test Set-upEF-2 Fryer Exhaust Fans -
Speed Set
HoodSwitch
RestaurantOpenSwitch
ON OFF
Fan RPM Readings Hood CFM Reading
Exhaust FanRPM Speed
Fan SpeedAfter Adjustment
Preliminary HoodCFM Reading
Final Hood CFMReading After
Adjustment
RPM/CFM Settings
Table #1 - Exhaust Fan - Speed
Kitchen Design Hood Type Fan Type Ventilation Rate RPM
Single Line NGK 3 VAT Fryer Hood DU85HFA 1176 CFM 1189
Double Line NGK 4 VAT Fryer Hood DU85HFA 1470 CFM 1266
Grill Hood Grill Hood DU85HFA 1150 CFM 1182
Restroom Exhaust Exhaust Fan DR10HFA 300 CFM 1456
RQC-2017-061 Version-1 2/13/182 of 5Page
2.
3.
4.
4.
5.
CaptiveAire2018 Functional Checklist Procedures
Measured Filter Velocity at each Hood Filter
Kitchen Design
Hood Type
Grease Filters
Filter #1
Filter #2
Filter #3
Filter #4
Filter #5
Filter #6
Filter #7
AverageVelocity ofAll Filters
80% ofAverageVelocity
Total Area of Hood Filters
Actual CFM (Average Velocity*
0.8* Area of Filters)
StandardVentilation
CFM(1)
SingleLine NGK
3 VAT Fryer Hood
6 8.16 1176
Double Line NGK
4 VAT Fryer Hood
7 9.52 1470
Grill Hood
Grill Hood 5 6.8 1150
Table #2 - Hood Ventilation Rate Calculation Table
RQC-2017-061 Version-1 2/13/183 of 5Page
6.
7.
8.
9.
Notes:
CaptiveAire2018 Functional Checklist Procedures
RQC-2017-061 Version-1 2/13/184 of 5Page
T-Stat Field Adjustment
1.
2.
2.1
2.2
2.3
2.4
2.5
CaptiveAire2018 Functional Checklist Procedures
Adjustment
RQC-2017-061 Version-1 2/13/185 of 5Page
CaptiveAire2018 Functional Checklist Procedures
RQC-2017-022 Version-1 1/2/181 of 2Page
RTU #:#2
RTU #:#1
Instructions: Complete review and certify that the RTU Installation is done according the Trane and Wendy’s
Gas Lines
O Gas Lines installed, pressure testedand air bled from system
O Gas Piping is painted Safety Yellow
O Gas Lines do not interfere or prevent the opening of every RTU Service Panel
O Gas Valve is left in the Open Position
Economizer
O Economizer Blankoff Plate (ships in return)is installed
O Economizer operates freely - linkages are notdamaged
O Economizer is not physical obstructed or mechanically shut or screwed closed
O Economizer is operational
Condensate Line
O Condensate Line is installed and operational
O Condensate Line is sloped (1/2” per 10’)
O P Trap is in place
O Cleanout is in place
O The Drain Line is sloped without sags.No double traps exist
RTU Power/RTU Control Wiring
O RTU Power - is connected and operational
O Control Wiring between Panel System is complete
O Control Wiring for Thermostats and Remote Sensors is complete
RTU Power/RTU Control Wiring
O RTU Power - is connected and operational
O Control Wiring between Panel System is complete
O Control Wiring for Thermostats and Remote Sensors is complete
Condensate Line
O Condensate Line is installed and operational
O Condensate Line is sloped (1/2” per 10’)
O P Trap is in place
O Cleanout is in place
O The Drain Line is sloped without sags.No double traps exist
Economizer
O Economizer Blankoff Plate (ships in return)is installed
O Economizer operates freely - linkages are notdamaged
O Economizer is not physical obstructed or mechanically shut or screwed closed
O Economizer is operational
Gas Lines
O Gas Lines installed, pressure testedand air bled from system
O Gas Piping is painted Safety Yellow
O Gas Lines do not interfere or prevent the opening of every RTU Service Panel
O Gas Valve is left in the Open Position
Completed by:______________________________________________________________Company Name: ___________________________________________________________Date of Inspection:_______________________________________________________________
Restaurant #:______________________________________________________________Address:___________________________________________________________________City:_________________________________________________________________________State:_______________________________________________________________________Zip:__________________________________________________________________________
Trane2017 RTU Installation Certification
RTU Serving (Kitchen/Dining Room)_______________________
O RTU is labeled (RTU #1 - Dining Room, RTU #2 - Kitchen)
O Model # matches construction drawings
O RTU is not damaged or dented
O RTU is level
O RTU Curb has 3 - 4” visible(RTU is not sitting on the Roof Deck)
O No non-factory penetrations of the Base Pan
O Construction Filters changed out with clean Filters
RTU Serving (Kitchen/Dining Room)_______________________
O RTU is labeled (RTU #1 - Dining Room, RTU #2 - Kitchen)
O Model # matches construction drawings
O RTU is not damaged or dented
O RTU is level
O RTU Curb has 3 - 4” visible(RTU is not sitting on the Roof Deck)
O No non-factory penetrations of the Base Pan
O Construction Filters changed out with clean Filters
RQC-2017-022 Version-1 1/2/182 of 2Page
RTU #:#1
Voyager Unit
ODischarge Temperature Limit Potentionmeter (DA COOL) must set to 9 O’Clock.This corresponds to 55oF
O “Human Interface” on RTU must be in Read Only mode for the Thermostat to function
Space Temperature:____________________
O Cooling System is operational
O Heating System is operational
Space Temperature:____________________
O Cooling System is operational
O Heating System is operational
O Trane Start-Up Process and Procedures were followed
Thermostats and Remote Sensors Thermostats and Remote Sensors
O Contractor obtained hours of operation and times from the owner for thermostat settings
O Remote Sensor installed on wall in the Dining Room and on Kitchen wall
O Remote Sensor is operational
O Thermostat programmed following theTrane BAYSENS924 Guide
O Thermostat is in Occupied Mode during restaurant open hours
O Thermostat is locked with Maintenance Code and Operator Code
O Operator can raise or lower the temperature by no more than 3 degrees
O Operator does not have access to theschedule when locked
O Maintenance Code and User Code provided to the Operator
O Maintenance Code:_________________________________________
O User Code:______________________________________________________
O Contractor obtained hours of operation and times from the owner for thermostat settings
O Remote Sensor installed on wall in the Dining Room and on Kitchen wall
O Remote Sensor is operational
O Thermostat programmed following theTrane BAYSENS924 Guide
O Thermostat is in Occupied Mode during restaurant open hours
O Thermostat is locked with Maintenance Code and Operator Code
O Operator can raise or lower the temperature by no more than 3 degrees
O Operator does not have access to theschedule when locked
O Maintenance Code and User Code provided to the Operator
O Maintenance Code:_________________________________________
O User Code:______________________________________________________
Voyager Unit
ODischarge Temperature Limit Potentionmeter (DA COOL) must set to 9 O’Clock.This corresponds to 55oF
O “Human Interface” on RTU must be in Read Only mode for the Thermostat to function
cont.
RTU #:#2cont.
I certify that the Trane RTU System was installed in accordance with manufacturers guidelines and instructions and is fully operational.
Provide a copy of this document with the final closeout paperwork.
All rights reserved. (c) 2017 Wendy’s Quality Is Our Recipe, LLC
Name________________________________________________________________________________________________________________________
Company:_________________________________________________________________________________________________________________
Title__________________________________________________________________________________________________________________________
Signature__________________________________________________________________________ Date________________________________
Trane2017 RTU Installation Certification
RQC-2017-060 Version-1 2/8/181 of 2Page
TestH4
Test Set-upEF-1 Grill Exhaust Fans -
Speed Set
HoodSwitch
RestaurantOpenSwitch
ON OFF
Fan RPM Readings Hood CFM Reading
Exhaust FanRPM Speed
Fan SpeedAfter Adjustment
Preliminary HoodCFM Reading
Final Hood CFMReading After
Adjustment
RPM/CFM Settings
TestH5
Test Set-upEF-2 Fryer Exhaust Fans -
Speed Set
HoodSwitch
RestaurantOpenSwitch
ON OFF
Fan RPM Readings Hood CFM Reading
Exhaust FanRPM Speed
Fan SpeedAfter Adjustment
Preliminary HoodCFM Reading
Final Hood CFMReading After
Adjustment
RPM/CFM Settings
Pass
Y/N
Note Any Corrections Made to System:
Pass
Y/N
Note Any Corrections Made to System:
Instructions: Contractor to complete Hood and Exhaust Fan Tests after building is weather tight, RTU Units are optional, all diffusers are installed, and ceiling tiles are installed. This checklist is for CaptiveAire Hoods Single Line or Double Line NGK. Follow Test Procedures and consult Installation, Operation and Maintenance Guide. Follow manufacturer instructions and all federal, state and local safety regulations
Test Conducted by:_______________________________________________________Date:__________________________________________________________________________________
Restaurant #:______________________________________________________________Address:___________________________________________________________________City:_________________________________________________________________________State:_______________________________________________________________________Zip:__________________________________________________________________________
CaptiveAire2018 Hood System - Functional Checklist
Measurements - Grill HoodRefer to H Drawings
Measurements - Fry HoodRefer to H Drawings
Notes:
Notes:
Hood Height -Floor to Bottom of Hood Skirt
(78” - U.S. 83” - Canada)
Filter Bank at the Frontof the Hood?
Yes / No
LED Light Installed (No CFL)?Yes / No
Hood Height -Floor to Bottom of Hood Skirt
(78” - U.S. 83” - Canada)
Filter Bank at the Frontof the Hood?
Yes / No
LED Light Installed (No CFL)?Yes / No
RQC-2017-060 Version-1 2/8/182 of 2Page
CaptiveAire2018 Hood System - Functional Checklist
Refer to Construction Drawings and the CaptiveAire Installation and Operational Manual.
1. Record actual condition during test. GC to adjust speeds and settings. 2. Contractor to initial “Pass” only after all elements are adjusted and validated. 3. Heat rated LED lamp at 3500K temperature is required. Substitution of CFL or incadescent lamp is not authorized.4. Contractor to be present and assist during test & balance process.
I hereby verify and certify that the Hood Tests were completed and the system is fully functional.
Provide this completed start up form with the construction contract close out form.
Name________________________________________________________________________________________________________________________
Title__________________________________________________________________________________________________________________________
Signature__________________________________________________________________________ Date________________________________
All rights reserved. ©2017 Wendy’s Quality Is Our Recipe, LLC
RQC-2019-043 Version-2 04/05/191 of 4Page
FC Test1A
FC Test1B
FC Test2A
FC Test2B
FC Test3
Test Set-up
Test Set-up
Test Set-up
Test Set-up
Test Set-up
Pass
Pass
Pass
Pass
Pass
Y/N
Y/N
Y/N
Y/N
Y/N
Expected StateCheck Circle if Actual State Matches
BuildingSigns
MenuBoard
Parking LotLights
Fry LineReceptacles/Hood Lights
ExhaustFans
Hood CaptureJet Fans
OFF O OFF O OFF O ON O ON O ON O
Expected StateCheck Circle if Actual State Matches
BuildingSigns
MenuBoard
Parking LotLights
Fry LineReceptacles/Hood Lights
ExhaustFans
Hood CaptureJet Fans
OFF O OFF O OFF O ON O ON O ON O
Expected StateCheck Circle if Actual State Matches
BuildingSigns
MenuBoard
Parking LotLights
Fry LineReceptacles/Hood Lights
ExhaustFans
Hood CaptureJet Fans
OFF O OFF O OFF O ON O ON O ON O
Expected StateCheck Circle if Actual State Matches
BuildingSigns
MenuBoard
Parking LotLights
Fry LineReceptacles/Hood Lights
ExhaustFans
Hood CaptureJet Fans
ON O ON O ON O ON O ON O ON O
Expected StateCheck Circle if Actual State Matches
BuildingSigns
MenuBoard
Parking LotLights
Fry LineReceptacles/Hood Lights
ExhaustFans
Hood CaptureJet Fans
OFF O OFF O OFF O ON O ON O ON O
Note Any Corrections Made to System:
Note Any Corrections Made to System:
Note Any Corrections Made to System:
Note Any Corrections Made to System:
Note Any Corrections Made to System:
Test Conducted by:_______________________________________________________Date:__________________________________________________________________________________
Restaurant #:______________________________________________________________Address:___________________________________________________________________City:_________________________________________________________________________State:_______________________________________________________________________Zip:__________________________________________________________________________
Instructions: Follow CPI’s instructions and warnings for the CPI switchboards. Follow all federal, state and local safety guidelines when working around energized panel systems. These test procedures are designed to verify and document the operation of the Fan Control Panel. Only qualified persons should makeadjustments or changes inside the CPI Panel.
CPI2019 Fan Control Panel Functional Test ChecklistSmart Building
Cooking Equipment On -Night
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
OverridePhotocell
ON OFF OFF OFF COVERED
Cooking Equipment Off -Day
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
OverridePhotocell
ON OFF OFF OFF UNCOVERED
Restaurant Open - Bldg Lights/Signs -Day
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
OverridePhotocell
ON ON OFF OFF UNCOVERED
Restaurant Open - Bldg Signs -Night
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
OverridePhotocell
ON ON OFF OFF COVERED
Restaurant Closed -Clean Up
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
OverridePhotocell
ON OFF OFF OFF COVERED
Test Results
Test Results
Test Results
Test Results
Test Results
RQC-2019-043 Version-2 04/05/192 of 4Page
FC Test4
FC Test5A
FC Test5B
FC Test6
FC Test7
FC Test8
Test Set-up
Test Set-up
Test Set-up
Test Set-up
Test Set-up
Test Set-up
Pass
Pass
Pass
Pass
Pass
Pass
Y/N
Y/N
Y/N
Y/N
Y/N
Y/N
Expected StateCheck Circle if Actual State Matches
BuildingSigns
MenuBoard
Parking LotLights
Fry LineReceptacles/Hood Lights
ExhaustFans
Hood CaptureJet Fans
OFF O OFF O OFF O OFF O OFF O OFF O
Expected StateCheck Circle if Actual State Matches
BuildingSigns
MenuBoard
Parking LotLights
Fry LineReceptacles/Hood Lights
ExhaustFans
Hood CaptureJet Fans
OFF O OFF O OFF O OFF O ON O ON O
Expected StateCheck Circle if Actual State Matches
BuildingSigns
MenuBoard
Parking LotLights
Fry LineReceptacles/Hood Lights
ExhaustFans
Hood CaptureJet Fans
OFF O OFF O OFF O OFF O ON O ON O
Expected StateCheck Circle if Actual State Matches
BuildingSigns
MenuBoard
Parking LotLights
Fry LineReceptacles/Hood Lights
ExhaustFans
Hood CaptureJet Fans
OFF O OFF O OFF O OFF O ON O ON O
Expected StateCheck Circle if Actual State Matches
BuildingSigns
MenuBoard
Parking LotLights
Fry LineReceptacles/Hood Lights
ExhaustFans
Hood CaptureJet Fans
OFF O OFF O ON O OFF O OFF O OFF O
Expected StateCheck Circle if Actual State Matches
BuildingSigns
MenuBoard
Parking LotLights
Fry LineReceptacles/Hood Lights
ExhaustFans
Hood CaptureJet Fans
OFF O OFF O ON O OFF O OFF O OFF O
Note Any Corrections Made to System:
Note Any Corrections Made to System:
Note Any Corrections Made to System:
Note Any Corrections Made to System:
Note Any Corrections Made to System:
Note Any Corrections Made to System:
Cooking Equipment Shutdown -Night
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
OverridePhotocell
OFF OFF OFF OFF COVERED
Hood Heat Sensor -Grill
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
OverridePhotocell
OFF OFF OFF OFF UNCOVERED
Hood Heat Sensor -Fryer
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
OverridePhotocell
OFF OFF OFF OFF UNCOVERED
Ansul System Test
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
OverridePhotocell
OFF OFF OFF OFF UNCOVERED
Lot Light Override - 1 HR -Day
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
OverridePhotocell
OFF OFF ON OFF UNCOVERED
Lot Light Override - 1 HR -Night
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
OverridePhotocell
OFF OFF ON OFF COVERED
Test Results
Test Results
Test Results
Test Results
Test Results
Test Results
CPI2019 Fan Control Panel Functional Test Checklist
RQC-2019-043 Version-2 04/05/193 of 4Page
CPI2019 Fan Control Panel Functional Test Checklist
FC Test9
FC Test10
FC Test11
FC Test12
FC Test13
Y/N
Y/N
Y/N
Y/N
Y/N
Note Any Corrections Made to System:
Note Any Corrections Made to System:
Note Any Corrections Made to System:
Note Any Corrections Made to System:
Note Any Corrections Made to System:
Automatic Off -Dining Room Lights - 2 HR
Dining RoomGeneralLights
Dining RoomDecorative
Lights
KitchenLights
PatioHeaters
PatioLights
ON ON OFF OFF OFF
Test Set-up - RestaurantLight Switches
Automatic Off -Kitchen Lights - 2 HR
Dining RoomGeneralLights
Dining RoomDecorative
Lights
KitchenLights
PatioHeaters
PatioLights
OFF OFF ON OFF OFF
Test Set-up - RestaurantLight Switches
Automatic Off -Patio Heater - ON
Dining RoomGeneralLights
Dining RoomDecorative
Lights
KitchenLights
PatioHeaters
PatioLights
OFF OFF OFF ON OFF
Test Set-up - RestaurantLight Switches
Automatic Off -Patio Lights - ON
Dining RoomGeneralLights
Dining RoomDecorative
Lights
KitchenLights
PatioHeaters
PatioLights
OFF OFF OFF OFF ON
Test Set-up - RestaurantLight Switches
Restaurant OperationsOverride - 1 HR
Dining RoomGeneralLights
Dining RoomDecorative
Lights
KitchenLights
PatioHeaters
PatioLights
ON ON ON OFF OFF
Test Set-up - RestaurantLight Switches
Expected StateCheck Circle if Actual State Matches
Dining RoomGeneralLights
Dining RoomDecorative
Lights
KitchenLights
PatioHeaters
PatioLights
OFF O OFF O OFF O OFF O OFF O
Test Results
Expected StateCheck Circle if Actual State Matches
Dining RoomGeneralLights
Dining RoomDecorative
Lights
KitchenLights
PatioHeaters
PatioLights
OFF O OFF O OFF O OFF O OFF O
Test Results
Expected StateCheck Circle if Actual State Matches
Dining RoomGeneralLights
Dining RoomDecorative
Lights
KitchenLights
PatioHeaters
PatioLights
OFF O OFF O OFF O OFF O OFF O
Test Results
Expected StateCheck Circle if Actual State Matches
Dining RoomGeneralLights
Dining RoomDecorative
Lights
KitchenLights
PatioHeaters
PatioLights
OFF O OFF O OFF O OFF O OFF O
Test Results
Expected StateCheck Circle if Actual State Matches
Dining RoomGeneralLights
Dining RoomDecorative
Lights
KitchenLights
PatioHeaters
PatioLights
ON O ON O ON O OFF O OFF O
Test Results
Pass
Pass
Pass
Pass
Pass
Automatic Off -Dining Room Lights - 2 HR
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
Override
OFF OFF OFF OFF
Test Set-up - Fan Control
Automatic Off -Kitchen Lights - 2 HR
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
Override
OFF OFF OFF OFF
Test Set-up - Fan Control
Automatic Off -Patio Heater - ON
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
Override
OFF OFF OFF OFF
Test Set-up - Fan Control
Automatic Off -Patio Lights - ON
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
Override
OFF OFF OFF OFF
Test Set-up - Fan Control
Restaurant OperationsOverride - 1 HR
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
Override
OFF OFF OFF ON
Test Set-up - Fan Control
RQC-2019-043 Version-2 04/05/194 of 4Page
CPI2019 Fan Control Panel Functional Test Checklist
Follow CPI Fan Control Panel Test Procedure Instructions. Reference CPI FCLC Troubleshooting document should a test initially fail.
1. Mark actual condition during the tests.2. GC to Initial “Pass” only after all elements are verified. I hereby verify and certify that the Fan Control Panel Tests were completed and the system is fully functional.
Name________________________________________________________________________________________________________________________
Title__________________________________________________________________________________________________________________________
Signature__________________________________________________________________________ Date________________________________
All rights reserved. ©2019 Wendy’s Quality Is Our Recipe, LLC
Notes:_________________________________________________________________________________________________________________________________________________________________________
___________________________________________________________________________________________________________________________________________________________________________________
___________________________________________________________________________________________________________________________________________________________________________________
___________________________________________________________________________________________________________________________________________________________________________________
___________________________________________________________________________________________________________________________________________________________________________________
___________________________________________________________________________________________________________________________________________________________________________________
(1) The Hood CaptureJet is specific to Halton Hoods. CaptiveAire hoods do not have CaptureJet fans. Ignore this element suring testing on CaptiveAire locations.All other elements on the individual tests are common between hood types.
RQC-2019-044 Version-2 4/05/191 of 11Page
A-41 is ONA-5 ON
Photocell
Test #1A: Cooking Equipment On (Night)
Hoods ON/OFF Hoods
Hoods ONthe Photocell
Test Set-upCooking Equipment On -
Night
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
OverridePhotocell
ON OFF OFF OFF COVERED
Expected State After Action
BuildingSigns
MenuBoard
Parking LotLights
Fry LineReceptacles/Hood Lights
ExhaustFans
Hood CaptureJet Fans
OFF OFF OFF ON ON ON
Test ResultsFC Test
1A
CPI2019 Fan Control PanelFunctional Test ProceduresSmart Building
FC Test1B
Test Set-upCooking Equipment Off -
Day
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
OverridePhotocell
ON OFF OFF OFF UNCOVERED
Expected State After Action
BuildingSigns
MenuBoard
Parking LotLights
Fry LineReceptacles/Hood Lights
ExhaustFans
Hood CaptureJet Fans
OFF OFF OFF ON ON ON
Test Results
RQC-2019-044 Version-2 4/05/192 of 11Page
Hoods ONON
Hoods ONON
Photocell
Hoods ONOFF
Test Set-upRestaurant Open - Bldg Lights/Signs -
Day
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
OverridePhotocell
ON ON OFF OFF UNCOVERED
Expected State After Action
BuildingSigns
MenuBoard
Parking LotLights
Fry LineReceptacles/Hood Lights
ExhaustFans
Hood CaptureJet Fans
OFF OFF OFF ON ON ON
Test ResultsFC Test
2A
FC Test2B
Test Set-upRestaurant Open - Bldg Signs -
Night
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
OverridePhotocell
ON ON OFF OFF COVERED
Expected State After Action
BuildingSigns
MenuBoard
Parking LotLights
Fry LineReceptacles/Hood Lights
ExhaustFans
Hood CaptureJet Fans
ON ON ON ON ON ON
Test Results
FC Test3
Test Set-upRestaurant Closed -
Night
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
OverridePhotocell
ON OFF OFF OFF COVERED
Expected State After Action
BuildingSigns
MenuBoard
Parking LotLights
Fry LineReceptacles/Hood Lights
ExhaustFans
Hood CaptureJet Fans
OFF OFF OFF ON ON ON
Test Results
CPI2019 Fan Control Lighting Control - Test Procedures
RQC-2019-044 Version-2 4/05/193 of 11Page
Hoods ON/OFF OFFOFF
in the and the
for
using the
in the and the
for
using the
FC Test4
Test Set-upCooking Equipment Shutdown -
Night
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
OverridePhotocell
OFF OFF OFF OFF COVERED
Expected State After Action
BuildingSigns
MenuBoard
Parking LotLights
Fry LineReceptacles/Hood Lights
ExhaustFans
Hood CaptureJet Fans
OFF OFF OFF OFF OFF OFF
Test Results
FC Test5A
Test Set-upHood Heat Sensor -
Grill
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
OverridePhotocell
OFF OFF OFF OFF UNCOVERED
Expected State After Action
BuildingSigns
MenuBoard
Parking LotLights
Fry LineReceptacles/Hood Lights
ExhaustFans
Hood CaptureJet Fans
OFF OFF OFF OFF ON ON
Test Results
FC Test5B
Test Set-upHood Heat Sensor -
Fryer
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
OverridePhotocell
OFF OFF OFF OFF UNCOVERED
Expected State After Action
BuildingSigns
MenuBoard
Parking LotLights
Fry LineReceptacles/Hood Lights
ExhaustFans
Hood CaptureJet Fans
OFF OFF OFF OFF ON ON
Test Results
CPI2019 Fan Control Lighting Control - Test Procedures
RQC-2019-044 Version-2 4/05/194 of 11Page
Do not trip the Ansul System with the system charged.
The
Note:
FC Test6
Test Set-up
Ansul System Test
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
OverridePhotocell
OFF OFF OFF OFF UNCOVERED
Expected State After Action
BuildingSigns
MenuBoard
Parking LotLights
Fry LineReceptacles/Hood Lights
ExhaustFans
Hood CaptureJet Fans
OFF OFF OFF OFF ON ON
Test Results
Test Set-upLot Light Override - 1 HR -
Day
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
OverridePhotocell
OFF OFF ON OFF UNCOVERED
Expected State After Action
BuildingSigns
MenuBoard
Parking LotLights
Fry LineReceptacles/Hood Lights
ExhaustFans
Hood CaptureJet Fans
OFF OFF ON OFF OFF OFF
Test ResultsFC Test
7
CPI2019 Fan Control Lighting Control - Test Procedures
RQC-2019-044 Version-2 4/05/195 of 11Page
OFF and the OFF
Note:
Hoods ON/OFF HoodsOFF
ONON
Hoods ON/OFF HoodsON OPEN
ON
Test Set-upLot Light Override - 1 HR -
Night
Hoods On
Button
RestaurantOpenSwitch
Lot LightsOverride
RestaurantOper.
OverridePhotocell
OFF OFF ON OFF COVERED
Expected State After Action
BuildingSigns
MenuBoard
Parking LotLights
Fry LineReceptacles/Hood Lights
ExhaustFans
Hood CaptureJet Fans
OFF OFF ON OFF OFF OFF
Test ResultsFC Test
8
CPI2019 Fan Control Lighting Control - Test Procedures
FC Test9
Automatic Off -Dining Room Lights - 2 HR
Dining RoomGeneralLights
Dining RoomDecorative
Lights
KitchenLights
PatioHeaters
PatioLights
ON ON OFF OFF OFF
Expected State
Dining RoomGeneralLights
Dining RoomDecorative
Lights
KitchenLights
PatioHeaters
PatioLights
OFF OFF OFF OFF OFF
Automatic Off -Dining Room Lights - 2 HR
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
Override
OFF OFF OFF OFF
Test Set-up - RestaurantLight Switches Test ResultsTest Set-up - Fan Control
RQC-2019-044 Version-2 4/05/196 of 11Page
CPI2019 Fan Control Lighting Control - Test Procedures
Hoods ON/OFF OFFOFF
OFF
• • • The correct process is to press the Hoods ON/OFF
ON
Hoods ON/OFF ONOFF
ON
Hoods ON/OFF ONON OPEN
ON
Hoods ON/OFF OFFOFF
OFF
Automatic Off -Kitchen Lights - 2 HR
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
Override
OFF OFF OFF OFF
Test Set-up - Fan ControlFC Test10
Expected State
Dining RoomGeneralLights
Dining RoomDecorative
Lights
KitchenLights
PatioHeaters
PatioLights
OFF OFF OFF OFF OFF
Automatic Off -Kitchen Lights - 2 HR
Dining RoomGeneralLights
Dining RoomDecorative
Lights
KitchenLights
PatioHeaters
PatioLights
OFF OFF ON OFF OFF
Test Set-up - RestaurantLight Switches Test Results
RQC-2019-044 Version-2 4/05/197 of 11Page
• • The correct process is to press the Hoods ON/OFF
ON
Hoods ON/OFF ONOFF
ON
Hoods ON/OFF ONON OPEN
OFF ON
Hoods ON/OFF OFFOFF
OFF
• Hoods ON/OFF ON
CPI2019 Fan Control Lighting Control - Test Procedures
FC Test11
Expected State
Dining RoomGeneralLights
Dining RoomDecorative
Lights
KitchenLights
PatioHeaters
PatioLights
OFF OFF OFF OFF OFF
Automatic Off -Patio Heater - ON
Dining RoomGeneralLights
Dining RoomDecorative
Lights
KitchenLights
PatioHeaters
PatioLights
OFF OFF OFF ON OFF
Test Set-up - RestaurantLight Switches Test Results
Automatic Off -Patio Heater - ON
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
Override
OFF OFF OFF OFF
Test Set-up - Fan Control
RQC-2019-044 Version-2 4/05/198 of 11Page
Hoods ON/OFF ONOFF
ON
Hoods ON/OFF ONON OPEN
ON
Hoods ON/OFF OFFOFF
OFF
• ON/OFF ON
CPI2019 Fan Control Lighting Control - Test Procedures
FC Test12
Expected State
Dining RoomGeneralLights
Dining RoomDecorative
Lights
KitchenLights
PatioHeaters
PatioLights
OFF OFF OFF OFF OFF
Automatic Off -Patio Lights - ON
Dining RoomGeneralLights
Dining RoomDecorative
Lights
KitchenLights
PatioHeaters
PatioLights
OFF OFF OFF OFF ON
Test Set-up - RestaurantLight Switches Test Results
Automatic Off -Patio Lights - ON
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
Override
OFF OFF OFF OFF
Test Set-up - Fan Control
FC Test13
Expected StateCheck Circle if Actual State Matches
Dining RoomGeneralLights
Dining RoomDecorative
Lights
KitchenLights
PatioHeaters
PatioLights
ON O ON O ON O OFF O OFF O
Restaurant OperationsOverride - 1 HR
Dining RoomGeneralLights
Dining RoomDecorative
Lights
KitchenLights
PatioHeaters
PatioLights
ON ON ON OFF OFF
Test Set-up - RestaurantLight Switches Test Results
Restaurant OperationsOverride - 1 HR
Hoods On
Button
RestaurantOpen
Button
Lot LightsOverride
RestaurantOper.
Override
OFF OFF OFF ON
Test Set-up - Fan Control
RQC-2019-044 Version-2 4/05/199 of 11Page
CPI2019 Fan Control Lighting Control - Test Procedures
Hoods ON/OFF OFFOFF
ONON
ON
Hoods ON/OFF ONON OPEN
Hoods ON/OFF OFFOFF
OFFOFF
• Hoods ON/OFF ON
Hoods ON/OFF OFF OFF
CPI at
RQC-2019-045 Version-2 4/5/191 of 5Page
CPI2019 Fan Control Lighting Control TroubleshootingSmart Design
Building and Sign Lighting
• Verify Panel A Circuit #41 is ON
• Verify Restaurant OPEN/CLOSE Button light is ON
• Verify that the CPI 400/800 is NOT in the Automatic Off time period. Check time of day vs. programming in the system.
• Verify Photocell is ACTIVE
o Cover Photocell
o Disconnect Photocell Wire
• Verify Panel A Circuit #41 is ON
• Verify Restaurant OPEN/CLOSE Button light is OFF
• Verify Photocell is NOT Active
o Shine light in Photocell
o Verify Photocell Wire connection
Issue: Building & Sign Lights Won’t Turn ON
Issue: Building & Sign Lights Won’t Turn OFF
RQC-2019-045 Version-2 4/5/192 of 5Page
Menu Board
• Verify Panel A Circuit #41 is ON
• Verify Restaurant OPEN/CLOSE Button light is ON
• Verify that the CPI 400/800 is NOT in the Automatic Off time period. Check time of day vs. programming in the system.
• Verify Photocell is ACTIVE
o Cover Photocell
o Disconnect Photocell Wire
Issue: Menu Boards Won’t Turn ON
CPI2019 Fan Control Lighting Control Troubleshooting - Smart Design
• Verify Panel A Circuit #41 is ON
• Verify Restaurant OPEN/CLOSE Button light is OFF
• Verify Photocell is NOT Active
o Shine light in Photocell
o Verify Photocell Wire connection
Parking Lot Lighting
• Verify Panel A Circuit #41 is ON
• Verify Restaurant OPEN/CLOSE Button light is ON
• Verify that the CPI 400/800 is NOT in the Automatic Off time period. Check time of day vs. programming in the system.
• Verify Photocell is ACTIVE
o Cover Photocell
o Disconnect Photocell Wire
Issue: Parking Lot Lights Won’t Turn ON
Issue: Menu Boards Won’t Turn OFF
RQC-2019-045 Version-2 4/5/193 of 5Page
CPI2019 Fan Control Lighting Control Troubleshooting - Smart Design
Hoods
• Verify Panel A Circuit #41 is ON
• Verify the Hoods ON/OFF Button light is ON
o The Heat Sensors are ACTIVE (Heat Sensors contact is CLOSED)
o The Grill Interlock is ACTIVE (Interlock Contact is CLOSED)
Issue: Hoods Won’t Turn ON
• Verify Panel A Circuit #41 is ON
• Verify Restaurant OPEN/CLOSE Button light is OFF
• Verify Photocell is NOT Active
o Shine light in Photocell
o Verify Photocell Wire connection
Issue: Parking Lot Lights Won’t Turn OFF
Fry Line Receptacles / Hood Lights
• Verify Panel A Circuit #41 is ON
• Verify the Hoods ON/OFF Button light is ON
Issue: Fry Line / Hood Lights Won’t Turn ON
• Verify Panel A Circuit #41 is ON
• Verify the Hoods ON/OFF Button light is OFF
Issue: Fry Line / Hood Lights Won’t Turn OFF
RQC-2019-045 Version-2 4/5/194 of 5Page
• Verify Panel A Circuit #41 is ON
• Verify the Hoods ON/OFF Button light is OFF
o The Heat Sensors are NOT Active (Heat Sensors contact is OPEN, or no wires
connected to Terminal Strip TB, Terminals 1 and 2)
o The Grill Interlock is NOT Active (Interlock Contact is OPEN, or no wires
connected to Terminal Strip TB, Terminals 3 and 4)
Issue: Hoods Won’t Turn OFF
CPI2019 Fan Control Lighting Control Troubleshooting - Smart Design
Dining Room Lights / Kitchen Lights
• Verify that the Dining Room interior light switch is NOT turned OFF.
• Verify that the dining room circuit breakers are NOT Tripped.
• Verify that the CPI 400/800 is NOT in the Automatic Off time period. Check time of day vs. programming in the system.
• Verify that the circuit breakers are NOT Tripped.
• Verify time of day programmed into the CPI 400/800 against current time. Time period may be off resulting in the unit going into code-required automatic off time period. Adjust time of day vs. programming in the system.
• Verify that the Dining Room interior light switch is NOT turned OFF. • Verify the circuit breakers are NOT tripped.
• Verify that the CPI 400/800 is NOT in the Automatic Off time period. Check time of day vs. programming in the system.
Issue: Dining Room Lights / Kitchen Lights Won’t Turn ON
Issue: Dining Room Lights / Kitchen Lights Turn Off in the Middle of the Day
Issue: Dining Room Lights / Kitchen Lights Won’t Turn ON
RQC-2019-045 Version-2 4/5/195 of 5Page
Patio Heaters
• Verify that the Remote Control used with the Heat Controller has good batteries
• Verify the circuit breakers are NOT tripped.
• Verify that the CPI 400/800 is NOT in the Automatic Off time period. Check time of day vs. programming in the system.
• Verify that the CPI 400/800 is NOT in the Automatic Off time period. Check time of day vs. programming in the system.
• Verify that the Patio Heaters are on the correct control zone - Control Zone 7.
Issue: Patio Heaters Won’t Turn ON
Issue: Patio Heaters Won’t Turn OFF
CPI2019 Fan Control Lighting Control Troubleshooting - Smart Design
Programming the CPI 400/800
RQC-2017-021 Version-1 1/9/181 of 8Page
1. 2. 3. 4.
1.
2. 3. 4.
Note: The thermostat accounts for the outside temperature and will adjust to hit the desired temperature at the
Energy Tip: Every temperature degree increases energy use by approximately 3% and impacts the electric and
Trane2018 BAYSENS924 Thermostat Programming - Quick Reference
Dining Room
Event Time
DR - Open_________________________AM
DR - Closed_________________________PM
DR - Clean up Complete___________________AM/PM
Kitchen
Event Time
Prep Start _________________________AM
Drive Thru Open _________________________PM
Drive Thru Closed ___________________AM/PM
Clean Up Complete ___________________AM/PM
Dining Room
Status RecommendedSet Point Set Point
Unoccupied Cooling 78oF _________________________
Occupied Cooling 72oF _________________________
Occupied Heating 72oF _________________________
Unoccupied Heating 60oF _________________________
Kitchen
Status RecommendedSet Point Set Point
Unoccupied Cooling 78oF _________________________
Occupied Cooling 72oF _________________________
Occupied Heating 72oF _________________________
Unoccupied Heating 60oF _________________________
RQC-2017-021 Version-1 1/9/182 of 8Page
OFF
Typical ScheduleDining Room (Non-Breakfast Restrauant)
Event Start End Heating Cooling Thermostat Status
DR - Drive T Open 12:01am 1:00am 60 78 Occupied (Fan ON)
DR - Closed 1:00am 7:00am 60 78 Unccupied (Fan Auto)
DR - Pre-Open 7:00am 10:30am 68 72 Occupied (Fan ON)
DR - Open 10:31am 10:00pm 68 72 Occupied (Fan ON)
DR - Drive T Open 10:01pm 11:59pm 68 72 Occupied (Fan ON)
Typical ScheduleKitchen (Non-Breakfast Restrauant)
Event Start End Heating Cooling Thermostat Status
KN - Open 12:01am 2:00am 68 72 Occupied (Fan ON)
KN - Closed 2:01am 7:00am 60 78 Unccupied (Fan Auto)
KN - Open 7:00am 11:59pm 68 72 Occupied (Fan ON)
Trane2018 BAYSENS924 Thermostat Programming - Quick Reference
RQC-2017-021 Version-1 1/9/183 of 8Page
• Press and hold down a finger where indicated.
1. Sensor Address: 002
2. Unit Address: 003
Note: Unit Address must match BCI board switches
BAYSENS924 Programming Quick ReferenceRefer to Interface Flowchart in the Installer Guide starting on Page 7
Access Programming Screens
1/2 - Network Settings Screen
Trane2018 BAYSENS924 Thermostat Programming - Quick Reference
RQC-2017-021 Version-1 1/9/184 of 8Page
1. Eco. Enable: ON
Opt. Strart/Stop ON
Shed Perm. OFF
Note: Critical to have schedule optimization so thatthe space will reach occupied space temperature
at start of occupied period
2/4 - Configuration Screen
3/4 - Configuration
Trane2018 BAYSENS924 Thermostat Programming - Quick Reference
Main Password: Set to desired 4 digit #Hold down button to advance numbers
User Password: Set to desired 4 digit #Hold down button to advance numbers
Schedule Menu: Disable
Cali. Temp: 0.0oF
Temp. occ time: 60 min
• Set temporary occupied time to 60 minutes to allow for a 1 hour override by the crew.
• Disable - Schedule is not accessible to crew. Clock is visible.
Main Password:___________________________________
User Password:___________________________________
1/4 - Configuration Screen
RQC-2017-021 Version-1 1/9/185 of 8Page
Trane2018 BAYSENS924 Thermostat Programming - Quick Reference
USER HMI: 1
Color: Blue
Units: F
1/2 - Display Screen
2/2 - Display
Unocc. Cool: 78oF
Occ. Cool: 72oF
Occ. Heat: 68oF
Unocc. Heat: 60oF Note: Adjust set points to desired operator temperatures
Min. Dead Band: 2oF
Max. Heating: 72oF
Min. Cooling: 68oF
Note: Adjust maximum set points based on operatordesires. It is critical to restrict maximum heating
and cooling points
1/2 - Set Point Screen
2/2 - Set Point Screen
RQC-2017-021 Version-1 1/9/186 of 8Page
Trane2018 BAYSENS924 Thermostat Programming - Quick Reference
Time Format: AM/PM .
Time: Current Time
Year: Current Year
Month: Current Month
Day: Current Day
Weekday: Current Weekday
Clock: Schedule Menu: From 1/2 - Set Up Menu
Clock
Occupancy CM: Loc. Occ.Where Occupancy is determined by the schedule
Schedule Type: 5 + 2 .
(Weekdays + Weekend)
Note: Adjust schedule type (7 day or 5+2) based onrestaurant schedule gathered earlier
Program the schedule for the Dining Roomand Kitchen thermostats
Note: Up to 3 occupied / unoccupied events are allowed
Options
Schedule
RQC-2017-021 Version-1 1/9/187 of 8Page
Trane2018 BAYSENS924 Thermostat Programming - Quick Reference
Kitchen - Weekdays
Event Schedule Time
Occupied 1 12:00 AM
Unoccupied 1 2:00 AM
Occupied 2 7:00 AM
Unoccupied 2 11:59 PM
Occupied 3 Not Used
Unoccupied 3 Not Used
Kitchen - Weekends
Event Schedule Time
Occupied 1 12:00 AM
Unoccupied 1 4:00 AM
Occupied 2 7:00 AM
Unoccupied 2 10:00 PM
Occupied 3 10:01 PM
Unoccupied 3 11:59 PM
Installer to adjust based on operator schedule
Dining Room - Weekdays
Event Schedule Time
Occupied 1 12:00 AM
Unoccupied 1 2:00 AM
Occupied 2 7:00 AM
Unoccupied 2 10:00 PM
Occupied 3 10:01 PM
Unoccupied 3 11:59 PM
Dining Room - Weekends
Event Schedule Time
Occupied 1 12:00 AM
Unoccupied 1 4:00 AM
Occupied 2 7:00 AM
Unoccupied 2 10:00 PM
Occupied 3 10:01 PM
Unoccupied 3 11:59 PM
RQC-2017-021 Version-1 1/9/188 of 8Page
•
Trane2018 BAYSENS924 Thermostat Programming - Quick Reference
DOOR SCHEDULEDOOR
REMARKS
DOORMARK
SIZE
ROOM WD HGT THK HDWGROUP TYPE MATL
FRAME
01 ENTRY #1 3'-0" 7'-0" 1 3/4" 1 A ALUM ALUM
03
ENTRY #2
3'-0" 7'-0" 1 3/4" A ALUM ALUM
04 REAR SERVICE DOOR 3'-6" 6'-8" 1 3/4" 3 D HM
05 MEN'S 3'-0" 6'-8" 1 3/4" 7 B PL
06 WOMEN'S 3'-0" 6'-8" 1 3/4" 7 B PL
HM
ALUM
ALUM
1, 2
1, 2
02 3'-0" 7'-0" 1 3/4"
2
A ALUM ALUM
DOOR ELEVATIONS
WINDOW ELEVATIONSDOOR HARDWARE SCHEDULE
VESTIBULE #1
1
WINDOW SCHEDULESIZES PROVIDED IN THE WINDOW SCHEDULE INDICATE ROUGH OPENING
DIMENSIONS U.N.O. *INDICATES SIZE IS ACTUAL FRAME DIMENSION
WINDOWMARK
SIZE
WD HGT THK TYPE
1A 8'-8 1/2" ALUM.
2A
4A
5'-3 1/4"
GLAZING
MATL
FRAME
5B
1"
1"
1"
1"
1"
G-1/G-5
G-1
G-1
G-1
G-1
G-31"
3A
4B
5A
7
REMARKS
9'-4"
1B
2B
1" G-1
1"
1" G-1
3B G-1
G-1
4'-6 1/2"
G-1
G-1
ALUM.
ALUM.
ALUM.
ALUM.
ALUM.
ALUM.
ALUM.
ALUM.
ALUM.
ALUM.
ALUM.
ALUM.
8'-8 1/2"
9'-2 1/2"
8'-8 1/2"
8'-8 1/2"
4'-6 1/2"
4'-6 1/2"
4'-6 1/2"
4'-6 1/2" 1"
1"
1"
1"
6'-10 1/2"
1
5'-3 1/4"
6'-10 1/2"
9'-2 1/4"*
0'-8"
1"
G-1
G-1
ALUM.
ALUM.
1"
TYPE MATL
01
FINISHDESCRIPTION
HINGES
1
CLOSER
1
EXIT DEVICE
1
1
1 FLOOR STOP
1
DOOR SWEEP1
THRESHOLD
QTY.
PULL (HOT CLIMATE)
PULL
EA.
EA.
EA.
EA.
EA.
EA.
EA.
MODEL MFG
SET 01 - EXTERIOR STOREFRONT ENTRANCE
BB1191 4 1/2" x 4 1/2" NRP HAGER
1792NL-HBOP
BF110
908.02.8
SC70-18
438
350
FALCON
ROCKWOOD
HAFELE
FALCON
ROCKWOOD
NGP
NGP
SET 02 - INTERIOR STOREFRONT ENTRANCEHINGES BB1279 4 1/2" x 4 1/2" HAGER
1 PUSH/PULLEA. 11047 ROCKWOOD
CLOSER1 EA. SC70-18 FALCON
1 FLOOR STOPEA. 438 ROCKWOOD
FINISHDESCRIPTIONQTY. MODEL MFG FINISHDESCRIPTIONQTY. MODEL MFG
SET 09 - EGRESS DOOR
PR.1 1/2
PR.1 1/2
GENERAL NOTES:1. G.C. TO PROVIDE AND INSTALL KICKPLATES ON INTERIOR DOORS.
FRAME ELEVS.
00
00
8.1
10
11
9'-2 1/2"
7'-2 "
9'-9 1/2"
4'-4 7/8"*
1 9'-4"
11'-4"
11'-4"
9
4'-6 1/2"*
NOT USED
PROVIDE STAINLESS STEEL EDGING CONT. AROUND DOOR SLAB. EDGING MATERIAL TO BE SUPPLIED BY SERTEK OR ALTERNATE VENDOR.
07 SERVING AREA 3'-4" 1 3/4" 8 E PL - 1, 3, 8-
G-3
G-1
GLAZ.TYPE
G-1
G-3
-
-
-
= TEMPERED GLASS
9'-6 3/4"
9'-6 3/4"
09 OFFICE 3'-0" 6'-8" 1 3/4" 4 C PL ALUM 100-
(DRAWN FROM EXTERIOR SIDE U.N.O.)
G-1 ALUM.1"8 3'-4"*
5'-6"
5'-6"
5'-6"
5'-6"
200NA
US26
US26D/626
US26/626
US26/626LIGHT
689
ALUMINUM
ANODIZED MILL
ALUMINUM
GRAY
US26/626
US26/626
689
US26D/626
WINDOW SCHEDULE GENERAL NOTES:
1. ALL EXTERIOR WINDOW FRAMES TO BE THERMALLY BROKEN.2. WINDOW CONTRACTOR SHALL FIELD VERIFY ROUGH OPENING DIMENSIONS FOR ALL
SCHEDULED WINDOWS PRIOR TO PREPARATION OF SHOP DRAWINGS.3. REFER TO FINISH SCHEDULE ON SHEET A6.1 FOR GLAZING AND FRAME TYPE
DESIGNATION DESCRIPTIONS.
G-1/G-5 5
5
SET 06 - RESTROOM DOOR (MULTIPLE USER)
SET 03 - ENHANCED REAR SERVICE DOOR (BY WIB SUPPLIER)
1 EA. CONTINUOUS HINGE
1 INTERIOR PANIC BAREA.
626
CLOSER1 EA. SC-70-18 AL
1 GASKETEA. 5050CL ---
1 SWEEPEA. 200NA DK BNZ NGP
1 SECURITY ASTRAGALEA. 1392SP 83" USP DRK BZ NGP
1 DOOR LITE (6" X 2")EA. L_VGLF-WD GPZ DRK BZ NGP
1 FLOOR STOP
1
DRIP CAP1
THRESHOLD
EA.
EA.
EA.
438
350
16
630 ROCKWOOD
AL NGP
--- NGP
ROCKWOOD
INTERCHANGEABLE CORE
FALCON
SELECT
626
FALCON
25EO
SL24HD
SET 03 - STANDARD REAR SERVICE DOOR (BY WIB SUPPLIER)
3 EA. HINGES - HEAVY
1 INTERIOR PANIC BAREA.
626
CLOSER1 EA. 6503 AL CALIBRE
1 KICKPLATEEA.
1 GASKETEA. 5050CL ---
1 SWEEPEA. 200NA AL NGP
1 SECURITY ASTRAGALEA. 1392SP 83" USP DRK BZ NGP
1 DOOR LITE (6" X 2")EA. L_VGLF-WD GPZ DRK BZ NGP
1 FLOOR STOP
1
DRIP CAP1
THRESHOLD
EA.
EA.
EA.
438
350
16
630 ROCKWOOD
AL NGP
--- NGP
ROCKWOOD
DUTY LEAF HINGE
KEYED ONLY EXTERIOR ENTRY W/ PULL HANDLE
NOT USED
SET 08 - SERVING AREA BARN DOOR96" TOP TRACK 9432 32D HAGER
1"x10" ROUND PULL1 EA. 14J
1 EA.
EA.1
32D HAGER
FLOOR GUIDE 1001 810 343 32D
1 EA.12"x12" VISION LITE
VSL 12"x12" B AIR LOUVERSBRONZE
1 EA.SURFACE MOUNT
BD1023 32D INOXDOOR LOCK
KIT WITH 1/4" TEMP.GLASS
SET 04 - OFFICE DOOR
SET 05 - CLOSET DOOR
HINGES ECBB1100 US26D HAGER
1 OFFICE LOCKSETEA. 3553 - GRADE 2 US26D HAGER
2 EA. 3984 CONTROL KEY HAGER
EA3
NOT USED
1 CONST. COREEA. 3982-C US26D HAGER
1 WALL STOPEA. 232W CONVEX US26D HAGER
SFIC CUT KEY
SET 07 - RESTROOM DOOR (SINGLE USER)
HINGES ECBB1100 US26D HAGER
CLOSER1 EA. 5200 SERIES-GRADE 2 ALM HAGER
1 WALL STOPEA. 236W CONCAVE HAGERUS26D
3 EA.
1 EA. HAGERPRIVACY LOCKSET US26D3540-GRADE 2-LESS SFIC
CONST. CORE1 EA. 3982 C US26D HAGER
SFIC CUT KEY2 EA. 3984 CONTROL KEY --- HAGER
6L G-1 ALUM.1" 6,2
6R G-1 ALUM.1" 6,3
4'-0 3/8"
3'-0 3/8"4'-0 3/8"
G-1 ALUM.1"6 3'-5 1/4"6'-0 1/4"
6L - ALT G-1 ALUM.1" 1,23'-5 1/4"4'-0 3/8"
6R - ALT G-1 ALUM.1" 1,33'-5 1/4"4'-0 3/8"
3'-0 3/8"
DOOR GENERAL NOTES:
A. USE 3-1/2" SCREWS ON ALL DOORHINGES.
B. COORD. LOCKSET COREREQUIREMENTS WITH OWNER.
C. DOOR SUPPLIER IS HAMILTONPARKER, REFER TO SUPPLIERSLIST FOR ORDERING INFO.
= TEMPERED GLASS
DOOR SCHEDULE REMARKS:
1. MARLITE AAA SERIES 500 DOOR ANDFRAME.
2. "MEN" OR "WOMEN" TOILET ROOM SIGN.
3. "EMPLOYEES ONLY" SIGN.
4. "EMERGENCY EXIT ONLY ALARM WILLSOUND" SIGN.
5. PROVIDE KICK PLATE BOTH SIDES.
6. "EXIT ONLY" APPLIED TO INTERIOR FACEAND LEGIBLE TO EXTERIOR.
7. DOOR BY WIB PROVIDER
8. REFER TO BARN DOOR DETAIL 1/A6.3
= DOOR IN STORE FRONT SYSTEM,REF: WINDOW ELEVATIONS
7'-0"
WINDOW SCHEDULE REMARKS:
1. QUIKSERV SS-4035E (AUTOMATIC). USE SS4035E-IP WHERE IMPACT RATED IS REQUIRED AND UPDATE DIMENSIONS.2. PROVIDE LEFT HANDED OPERATION AS INDICATED BY "L"3. PROVIDE RIGHT HANDED OPERATION AS INDICATED BY "R"4. PICK UP WINDOW 6'-0" OPTION: QUICKSERV BI-PARTING BP7252E OR BP-7241E-IP (IMPACT RESISTANT)5. REFER TO EXTERIOR ELEVATIONS FOR LOCATION OF PANES TO RECEIVE FROSTED GLAZING (G-5)6. QUIKSERV SC-4030 (MANUAL-SELF CLOSING). USE SS4035E-IP WHERE IMPACT RATED IS REQUIRED AND UPDATE DIMENSIONS.
01PLAN DETAILSCALE: 1/2" = 1'-0"
SEAL
DESCRIPTIONDATEREV.
ISSUE DATE: 05/29/2020
PROJECT NUMBER: 2020-05
DRAWN BY: WEN
CHECKED BY: DCN
SHEET NAME
SHEET NUMBER
6/19
/202
0, 1
1:32
AM
, P:\2
020-
05 W
endy
's B
orge
r\CAD
\Arc
h - S
truct
\30_
SMAR
T_55
-SQ
UAR
E_A6
_3_D
oor &
Win
dow
Sch
edul
e.dw
g, U
ser
SITE NUMBER:
BASE MDL:
OWNER:
BASE VERSION:
DRAWING RELEASE
PROJECT YEAR:
ASSET TYPE:
CLASSIFICATION:
UPGRADE CLASSIFICATION:
FURNITURE PACKAGE:
1419
W. W
ILSO
N S
T.BO
RG
ER, T
EXAS
, 790
07
PROJECT TYPE:
12817
SMART 55 - SQUARE 2020
FRANCHISEE
NEW
TOOT N TOTUM
SPRING 2019
NEW BUILD
2020
2016 V3
JANUARY 2020
NEWSMART 55 - SQUARE
AT
TS
XETE FO
SA
SHE
ILA A. SIMS
19 4 3 7
REG
IS
TERED ARCHITEC
T
05/29/20
20
BORGER
BORGER
BOR
GER
BOR
GER
A6.3DOOR & WINDOW SCHEDULE
ARTPACK & WAYFINDING LEGEND
GENERAL NOTES
CODED NOTES:
T
Q
Q,P
UU
EQ1.1FRZN BUN MARKET-PREF
EQUIPMENT PLAN
EQUIPMENT PLANSCALE: 1/4" = 1'-0"
SEAL
DESCRIPTIONDATEREV.
ISSUE DATE: 05/29/2020
PROJECT NUMBER: 2020-05
DRAWN BY: WEN
CHECKED BY: DCN
SHEET NAME
SHEET NUMBER
6/19
/202
0, 1
0:18
AM
, P:\2
020-
05 W
endy
's B
orge
r\CAD
\Arc
h - S
truct
\40_
SMAR
T_55
-SQ
UAR
E_EQ
1_1_
Equi
pmen
t Pla
n.dw
g, U
ser
SITE NUMBER:
BASE MDL:
OWNER:
BASE VERSION:
DRAWING RELEASE
PROJECT YEAR:
ASSET TYPE:
CLASSIFICATION:
UPGRADE CLASSIFICATION:
FURNITURE PACKAGE:
1419
W. W
ILSO
N S
T.BO
RG
ER, T
EXAS
, 790
07
PROJECT TYPE:
12817
SMART 55 - SQUARE 2020
FRANCHISEE
NEW
TOOT N TOTUM
SPRING 2019
NEW BUILD
2020
2016 V3
JANUARY 2020
NEWSMART 55 - SQUARE
AT
TS
XETE FO
SA
SHE
ILA A. SIMS
19 4 3 7
REG
IS
TERED ARCHITEC
T
05/29/20
20
BORGER
BORGER
BOR
GER
BOR
GER
01COMMUNITY TABLE ENLARGED PLANSCALE: 1/2"=1'-0"