HYDROCIAT LW R134a Water cooled chillers 1 AIR CONDITIONING - HEATING- REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.588 B USE HYDROCIAT LW The HYDROCIAT LW water chillers with water cooled condensors and screw compressors are designed for indoor installation and offer an optimal solution for any refrigeration application in the air conditioning or industrial process. The use of HFC R134a refrigerant fluid means that the units respond to the most stringent specifications for environmental protection, high efficiency and low electrical consumption The units conform to regulations EN 60.204 EN 378-2 and to directives : - Machine (98 / 37 CEE) modified - CEM (89 / 336 CEE) modified 92/31 CEE - 93/68 CEE - Low voltage (73/23 CEE) modified 92/31 CEE - 93/68 CEE - DESP 97 / 23 CEE LW - LWP group 3 sizes 1800BX (HPS) to 2800BX (HPS) group 4 sizes 3200BX (HPS) to 4200BX (HPS) HYDROCIAT LW-LWP 2 compressors - 2 refrigerant circuits 8 models : LW - LWP -1800BX - 1800BX HPS - 2150BX - 2150BX HPS - 2500BX - 2500BX HPS - 2800BX - 2800BX HPS. 3 compressors - 3 refrigerant circuits 8 models : LW - LWP 3200BX - 3200BX HPS - 3400BX - 3400BX HPS - 3750BBX - 3750BX HPS - 4200BX - 4200BX HPS. HYDROCIAT LWP The design of the water/water heat pumps range HYDROCIAT LWP is identical to that of HYDROCIAT LW. These machines produce hot water for heating applications. They can also be used in the cooling operation by reversing cycle on the hydraulic circuits. RANGE Cooling capacity : 420 to 1030 kW Heating capacity : 520 to 1270 kW Screw compressors CIAT direct expansion shell and tubes evaporator HPS equipment (High Power System) Heat recovery Cooling or heating HFC R134a E N V I R O N M E N T A L L Y F R I E N D L Y P R O T E C T I O N D E L'E N V IR O N N E M E N T

Upload: others

Post on 20-Oct-2020

21 views

Category:

Documents


0 download

TRANSCRIPT

  • HYD

    RO

    CIA

    T LW

    R13

    4aWater cooled chillers

    1AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.588 B

    USE

    HYDROCIAT LWThe HYDROCIAT LW water chillers with water cooledcondensors and screw compressors are designed for indoorinstallation and offer an optimal solution for any refrigerationapplication in the air conditioning or industrial process.

    The use of HFC R134a refrigerant fluid means that the unitsrespond to the most stringent specifications forenvironmental protection, high efficiency and low electricalconsumption

    The units conform to regulations EN 60.204 EN 378-2 and todirectives :- Machine (98 / 37 CEE) modified- CEM (89 / 336 CEE) modified 92/31 CEE - 93/68 CEE- Low voltage (73/23 CEE) modified 92/31 CEE - 93/68 CEE- DESP 97 / 23 CEE

    ➝ LW - LWPgroup 3 sizes 1800BX (HPS) to 2800BX (HPS)group 4 sizes 3200BX (HPS) to 4200BX (HPS)

    HYDROCIAT LW-LWP2 compressors - 2 refrigerant circuits

    8 models : LW - LWP -1800BX - 1800BX HPS - 2150BX - 2150BX HPS - 2500BX - 2500BX HPS - 2800BX - 2800BX HPS.

    3 compressors - 3 refrigerant circuits

    8 models : LW - LWP 3200BX - 3200BX HPS - 3400BX -3400BX HPS - 3750BBX - 3750BX HPS - 4200BX - 4200BX HPS.

    HYDROCIAT LWPThe design of the water/water heat pumps range HYDROCIAT LWP is identical to that of HYDROCIAT LW.

    These machines produce hot water for heating applications.

    They can also be used in the cooling operation by reversingcycle on the hydraulic circuits.

    RANGE

    Cooling capacity : 420 to 1030 kWHeating capacity : 520 to 1270 kW

    Screw compressorsCIAT direct expansion shell and tubes evaporator

    HPS equipment(High Power System)

    Heat recovery

    Cooling or heating

    HFC R134a

    ENV

    IRONME

    NTALLY FRIENDLY

    PR

    OTECTION DE L'ENVIRONN

    EM

    ENT

  • AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.588 B

    HYDROCIAT LW R134a

    2

    Water cooled chillers

    HYDROCIAT LW - LW¨P

    ■ Compressors

    ■ Accessible hermetic twin screw type

    ■ Optimized profile of rotors ensuring a high efficiency

    ■ Electrical motor incorporated with part winding start

    ■ Integral electronic protection fo motor

    ■ Control of the phases balance and rotation direction

    ■ Integrated overpressure valve

    ■ Discharge temperature control

    ■ Lubrication under controlled pressure

    ■ 3-stage integrated oil separator

    ■ Crankcase heater

    ■ Thin filter at suction

    ■ Discharge valve

    ■ Slide for modulating continued output capacity control

    ■ Assembly on antivibration mounts

    ■ Integrated oil separator

    ■ Installed at the compressor discharge

    ■ The large amount of oil injected during the compression cyclenecessitates the use of an oil separator.

    ■ Oil, after separation from the refrigerant, is filtered beforebeing injected into the compressor.

    Note :

    The refrigerant oil has several important roles to ensure thesmooth running of the compressor. It :

    ■ Lubricates bearings and moving parts and eradicates anydirect contact between parts.

    ■ Ensures a secure tightness between the different mechanicalparts, thereby guaranteeing good volumetric output.

    ■ Cools the compressor by direct oil injection into the gasvolume being compressed.

    If required, the cooling of oil allows gas discharge temperature to be limited.

    ■ Evaporator

    ■ High performance copper tubes bundle

    ■ Steel tubular plates

    ■ Steel shell

    ■ Corrosion resistant baffles

    ■ Thermal insulation with polyurethane foam

    ■ Water cooled condenser

    ■ High performance copper tubes bundle

    ■ Carbon steel shell

    ■ Carbon steel tubular plates

    ■ Removable cast iron headers

    ■ Safety valves on the refrigerant circuits

    ■ HPS (High Power System)

    on models LW/LWP...HPS

    ■ The HPS system allows a significant increase in the coolingcapacity, improving the performance coefficients (EER) of yourinstallation, particulary in part load, and therefore ensuring anoptimal operation of the unit all year round.

    ■ Refrigerant accessories

    ■ Filter dryers with rechargeable cartridges

    ■ Liquid sight glasses

    ■ Solenoid valves on HPS liquid refrigerant lines

    ■ Thermostatic expansion valves

    ■ Electrical panel

    ■ IP 21

    ■ Electrical supply 400 V - 3 ph. - 50 Hz + earth (-5% / +4%)

    ■ Main fused isolator with outside handle

    ■ Transformer for control circuit

    ■ Compressor motors contactors

    ■ Compressor motors protection by fused circuit breakers(depending on sizes of compressors).

    ■ General earth connection

    ■ Phase controller (reversal, loss, over and under voltage)

    ■ Electronic module with microprocessorXTRA CONNECT

    with the following main functions :

    - 2 remote switchable set points

    - chilled water temperature control

    - Possibility of water temperature variation according to theoutside temperature (water law)

    - Low temperature ice storage control

    - Compressors discharge temperature control

    - Compressors anti-short cycle control

    - Control and optimisation of operating parameters

    - Counting and balancing of compressors operating time

    - Automaticity control

    ■ LCD display panel, 2 lines of 20 characters allowing :

    - parametering of the unit

    - direct reading of all information: settings, water inlet/outlettemperatures, outside temperature, HP/LP pressures, unitoperating status...

    - Faults control with memorization of the last 9 faults and operating reading of when those faults occured

    - Weekly management of the unit

    - Unit general fault display on terminals

    - Automaticity control on terminals

    - RS 485 output for bus connection with centralized BuildingManagement System.

    DESCRIPTION

  • HYD

    RO

    CIA

    T LW

    R13

    4aWater cooled chillers

    3AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.588 B

    ■ Safety and regulation devices

    ■ HP/LP pressure sensors

    ■ Low and high pressure safety valves

    ■ Chilled water control sensor (inlet or outlet)

    ■ External temperature sensor

    ■ Evaporator antifreeze sensor

    ■ Compressors discharge sensor

    ■ Evaporator water flow switch

    ■ Capacity control

    ■ Modulating capacity control :

    - fom 25 to 100 % (Sizes 1800BX (HPS) to 2800BX (HPS)).

    - from 17 to 100 % (Sizes 3200BX (HPS) to 4200BX (HPS)).

    HYDROCIAT LWPThe HYDROCIAT LWP water-water heat pump range has thesame design as the HYDROCIAT LW.

    The calories are taken from the natural water network (groundwater, ...) or from a water loop and are sent to the heatingnetwork through the thermodynamic circuit, instead of beingdischarged by a cooling tower or a drycooler as is the casewith the water chiller.

    These water-water heat pumps can be used for cooling byreversing the cycle on the water circuits (modification of thehydraulic circuits to be made on site).

    ■ Accessories

    ■ Identical to those of the HYDROCIAT LW

    OPTIONS

    HYDROCIAT LW - LWP■ LOW NOISE version: acoustically lined housingcompressors

    ■ Antivibration equipment :

    - antivibration mounts

    - evaporator flexible sleeves

    - condenser flexible sleeves

    ■ Compressor isolating suction valves

    ■ Condenser water headers

    ■ Low temperature glycol water

    ■ Electronic expansion valve

    ■ Heat recovery with brazed plates desuperheaters (1 foreach refrigerant circuit)

    ■ Progressive soft start

    ■ Reduced height version

    ■ Remote control unit

    ■ Voltage-free contact relay board

    ■ Management of several units - MULTICONNECT

    ■ LonWorks gateway

    ■ Shackles

  • AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.588 B

    HYDROCIAT LW R134a

    4

    Water cooled chillers

    ● Standard supply ▲ Option - Not available

    HYDROCIAT 1800BX1800BX

    HPS2150BX

    2150BXHPS

    2500BX 2500BX HPS 2800BX2800BX

    HPS

    Standard

    R134a refrigerant ● ● ● ● ● ● ● ●2 refrigerant circuits ● ● ● ● ● ● ● ● Main safety switch ● ● ● ● ● ● ● ● Control circuit transformer ● ● ● ● ● ● ● ● RS 485 communication interface ● ● ● ● ● ● ● ● Electrical panel wires numbering ● ● ● ● ● ● ● ● Compressors Part Winding starting ● ● ● ● ● ● ● ● Phase controller (reversal, loss, over and under voltage) ● ● ● ● ● ● ● ●

    Options

    Low Noise version (Compressor acoustic housing) ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲

    Compressors isolating suction valves ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲Condenser water headers with hydraulic flexible connections ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲

    Antivibration mounts ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲Evaporator and Condensor hydraulic flexible connections ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲

    Remote control box (remote console) ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲Dry-contact relay board ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲Low temperature glycol water from 0°C to -8°C ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲

    Desuperheaters ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲Soft start ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲Reduced height version ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲Electronic expansion valve ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲Management of several units -MULTICONNECT ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲

    LonWorks gateway ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲Shackles ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲

    HYDROCIAT 3200BX3200BX

    HPS3400BX

    3400BXHPS

    3750BX3750BX

    HPS4200BX

    4200BXHPS

    Standard

    R134a refrigerant ● ● ● ● ● ● ● ●3 refrigerant circuits ● ● ● ● ● ● ● ● Main safety switch ● ● ● ● ● ● ● ● Control circuit transformer ● ● ● ● ● ● ● ● RS 485 communication interface ● ● ● ● ● ● ● ● Electrical panel wires numbering ● ● ● ● ● ● ● ● Compressors Part Winding starting ● ● ● ● ● ● ● ● Phase controller (reversal, loss, over and under voltage) ● ● ● ● ● ● ● ●

    Options

    Low Noise version (Compressor acoustic housing) ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲

    Compressors isolating suction valves ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲Condenser water headers with hydraulic flexible connections ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲

    Antivibration mounts ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲Evaporator and Condensor hydraulic flexible connections ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲

    Remote control box (remote console) ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲Dry-contact relay board ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲Low temperature glycol water from 0°C to -8°C ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲

    Desuperheaters ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲Soft start ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲Reduced height version ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲Electronic expansion valve ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲Management of several units -MULTICONNECT ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲

    LonWorks gateway ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲Shackles ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲Manilles de manutention ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲

    STANDARD EQUIPMENT / AVAILABLE OPTIONS

  • HYD

    RO

    CIA

    T LW

    R13

    4aWater cooled chillers

    5AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.588 B

    (1) Cooling capacity for 12 / 7°C evaporator chilled water and 30 / 35 °C condenser hot water(2) Compressors absorbed power(3) Lw : Global sound power level - Lp : Global sound pressure level at 10 meters, in free field, following ISO 3744 regulation

    HYDROCIAT LW - LWP 1800BX 1800BX HPS 2150BX 2150BX HPS 2500BX 2500BX HPS 2800BX 2800BX HPS

    LW - LWP versionsCooling capacity (1) kW 418 433 492 533 588 625 661 692Absorbed power (2) kW 93 96 110 115 126 134 140 145EER/ESEER 4.50/5.32 4.51/5.45 4.47/5.24 4.63/5.52 4.67/5.36 4.66/5.56 4.72/5.58 4.77/5.73

    Compressor

    Type Hermetic twin screwNumber 2Rotation speed rpm 2900

    R134a refrigerant charge kgcirc.1 34 39 50 53 53 52 59 52circ.2 35 40 42 44 53 52 59 52

    Capacity controlModulating from 25 to 100%

    (50 to 100% on each compressor)Type of oil for R134a BITZER BSE 170Oil charge for compressor liters 2 x 15 22 + 15 2 x 22

    Evaporator

    Type Direct expansion shell and tubesNumber 1Water content liters 171 219Hydraulic connections VICTAULIC typeMaximum pressure on waterside

    bar 10

    Mini / maxi water flow m3/h 50 / 150

    Water cooledcondenser

    Type Shell and tubesNumber 2Water content litres 2 x 28 36 + 28 2 x 36Hydraulic connections VICTAULIC typeMaximum pressure on waterside

    bar 10

    Maximum water flow m3/h 140 166 192Standard version Lw / Lp (3) dB(A) 90 / 58 91 / 59 93 / 61 96 / 64

    Low Noise version Lw / Lp dB(A) (3) dB(A) 86 / 54 88 / 56 90 / 58 93 / 61

    HYDROCIAT LW - LWP 3200BX 3200BX HPS 3400BX 3400BX HPS 3750BX 3750BX HPS 4200BX 4200BX HPS

    LW - LWP versionsCooling capacity (1) kW 730 762 780 808 850 883 977 1026Absorbed power (2) kW 164 167 175 180 193 198 209 216EER/ESEER 4.45/5.42 4.56/5.57 4.46/5.2 4.49/5.39 4.40/5.16 4.46/5.43 4.67/5.56 4.75/5.79

    Compressor

    Type Hermetic twin screwNumber 3Rotation speed rpm 2900

    R134a refrigerant charge kgcirc.1 59 60 53 53 53 54 59 57circ.2 37 38 53 46 53 55 59 58circ.3 37 38 37 56 53 60 59 62

    Capacity controlModulating from 17 to 100%

    (50 to 100% on each compressor) Type of oil for R134a BITZER BSE 170 Oil charge for compressor liters 22 + 2 x 15 2 x 22 + 15 3 x 22

    Evaporator

    Type Direct expansion shell and tubesNumber 1Water content liters 352 407 414Hydraulic connections VICTAULIC typeMaximum pressure on waterside

    bar 10

    Mini / maxi water flow m3/h 70 / 216 70 / 220

    Water cooledcondenser

    Type Shell and tubesNumber 3Water content litres 36 + 2 x 28 2 x 36 + 28 3 x 36Hydraulic connections VICTAULIC typeMaximum pressure on waterside

    bar 10

    Maximum water flow m3/h 236 262 288Standard version Lw / Lp (3) dB(A) 94 / 62 95 / 63 98 / 66

    Low Noise version Lw / Lp dB(A) (3) dB(A) 93 / 61 92 / 60 93 / 61 96 / 64

    TECHNICAL CHARACTERISTICS

  • AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.588 B

    HYDROCIAT LW R134a

    6

    Water cooled chillers

    (1) Current for 400V / 3Ph / 50Hz voltage(2) Current for 230V / 1Ph / 50Hz voltage(3) Starting current of the biggest compressor + maximum current of others compressors in full loadNominal current for cables selection = add the maximum nominal currents indicated in the above tables

    HYDROCIAT LW - LWP 1800BX 1800BX HPS 2150BX 2150BX HPS 2500BX 2500BX HPS

    COMPRESSORS (1)

    Maximum nominal current A324

    (2 x 162)358

    (196 + 162)392

    (2 x 196)

    Part winding starting current (3) A 585 774 808

    Starting current with Soft start option (3)

    A 437 560 614

    REMOTE-CONTROLLED AUXILIARY CIRCUIT (2)Maximum nominal current A 4Transformer power VA 630

    Electrical panel for LW 1800BX (HPS) to 2800BX (HPS)

    ELECTRICAL CHARACTERISTICS

    HYDROCIAT LW - LWP 3200BX 3200BX HPS 3400BX 3400BX HPS 3750BX 3750BX HPS 4200BX 4200BX HPS

    COMPRESSORS (1)

    Maximum nominal current A538

    (214 + 2 x 162)554

    (2 x 196 + 162)588

    (3 x 196)642

    (3 x 214)

    Part winding starting current (3) A 989 970 1004 1093

    Starting current with Soft start option (3)

    A 776 830 924

    REMOTE-CONTROLLED AUXILIARY CIRCUIT (2)Maximum nominal current A 4Transformer power VA 1000

  • HYD

    RO

    CIA

    T LW

    R13

    4aWater cooled chillers

    7AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.588 B

    PERFORMANCESHYDROCIAT LW - LWP

    Pf : Cooling capacity valid a ΔT according to operating limits Glycol water utilisation zone compulsoryPa : Compressor absorbed power Low temperature option necessaryPc : Heating capacity valid a ΔT according to operating limits EUROVENT ConditionsOperation without HPS for condenser water outlet at 60°C

    R1

    34

    a

    LWLWP

    CONDENSER WATER OUTLET TEMPERATURE °C

    Evaporator water outlet °C

    35 40 45 50 55 60Pf Pa Pc Pf Pa Pc Pf Pa Pc Pf Pa Pc Pf Pa Pc Pf Pa Pc

    kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW

    1800BX

    Glycolwater

    -8 220 81 301 206 90 296 190 98 288 174 109 283-6 242 83 325 230 91 321 210 99 309 193 110 303-4 275 84 359 258 92 350 239 101 340 219 111 330 200 124 324 176 141 317-2 298 86 384 280 93 373 261 102 363 240 112 352 219 126 345 194 142 3360 323 87 410 304 95 399 284 104 388 262 114 376 239 127 366 216 143 3592 349 89 438 329 96 425 308 105 413 285 116 401 261 129 390 236 144 380

    Pure water

    5 397 92 489 375 99 474 349 108 457 323 119 442 296 131 427 269 146 4157 418 93 511 404 101 505 378 110 488 349 121 470 321 133 454 291 148 43910 476 96 572 451 105 556 424 114 538 393 124 517 362 137 499 329 151 48012 512 99 611 484 107 591 456 116 572 424 127 551 387 139 526 356 154 51015 567 102 669 537 110 647 506 120 626 474 130 604 435 143 578 400 157 557

    1800BX

    Glycolwater

    -8 256 88 344 244 97 341 231 109 340 216 122 338-6 276 89 365 265 98 363 252 109 361 238 123 361-4 298 89 387 286 99 385 273 110 383 258 124 382 243 141 384-2 320 90 410 308 100 408 294 111 405 279 125 404 262 142 4040 345 91 436 331 101 432 317 112 429 300 126 426 283 143 4262 370 92 462 356 102 458 341 114 455 323 127 450 305 144 449

    Pure water

    5 415 95 510 399 104 503 381 116 497 363 129 492 343 146 4897 433 96 529 427 106 533 409 117 526 389 131 520 367 147 51410 489 99 588 471 108 579 452 120 572 430 133 563 406 149 55512 521 100 621 503 110 613 482 122 604 459 135 594 435 151 58615 570 103 673 553 113 666 529 124 653 505 138 643 478 154 632

    2150BX

    Glycolwater

    -8 283 97 380 264 106 370 244 116 360 220 127 347-6 308 98 406 289 107 396 268 117 385 246 129 375-4 335 100 435 314 109 423 293 119 412 270 131 401 244 145 389 218 161 379-2 363 101 464 341 110 451 319 121 440 295 133 428 269 147 416 241 163 4040 394 103 497 370 112 482 347 123 470 322 135 457 295 150 445 265 166 4312 425 105 530 401 114 515 376 125 501 349 138 487 321 152 473 289 168 457

    Pure water

    5 483 108 591 456 118 574 428 129 557 398 141 539 364 156 520 331 172 5037 492 110 602 482 120 602 462 131 593 431 144 575 397 158 555 360 175 53510 578 114 692 549 124 673 517 135 652 483 148 631 447 162 609 408 179 58712 621 117 738 588 127 715 556 138 694 520 151 671 482 166 648 440 182 62215 687 122 809 653 131 784 617 142 759 579 155 734 539 170 709 492 186 678

    2150BX

    Glycolwater

    -8 316 107 423 303 119 422 289 132 421 268 150 418-6 341 107 448 327 120 447 313 134 447 295 151 446-4 368 108 476 353 121 474 337 135 472 319 152 471 299 172 471-2 396 110 506 381 122 503 364 137 501 344 154 498 324 174 4980 425 111 536 409 123 532 391 138 529 372 155 527 349 176 5252 455 112 567 439 125 564 420 140 560 400 157 557 374 178 552

    Pure water

    5 511 114 625 493 127 620 472 142 614 450 160 610 425 181 6067 533 115 648 527 129 656 506 144 650 482 162 644 455 183 63810 601 119 720 582 132 714 558 147 705 533 165 698 505 186 69112 640 121 761 620 134 754 596 149 745 569 167 736 539 188 72715 702 125 827 681 137 818 655 152 807 625 169 794 593 191 784

  • AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.588 B

    HYDROCIAT LW R134a

    8

    Water cooled chillers

    Pf : Cooling capacity valid a ΔT according to operating limits Glycol water utilisation zone compulsoryPa : Compressor absorbed power Low temperature option necessaryPc : Heating capacity valid a ΔT according to operating limits EUROVENT ConditionsOperation without HPS for condenser water outlet at 60°C

    PERFORMANCESHYDROCIAT LW - LWP

    R1

    34

    a

    LWLWP

    CONDENSER WATER OUTLET TEMPERATURE °C

    Evaporator water outlet °C

    35 40 45 50 55 60Pf Pa Pc Pf Pa Pc Pf Pa Pc Pf Pa Pc Pf Pa Pc Pf Pa Pc

    kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW

    2500BX

    Glycolwater

    -8 320 112 432 303 121 424 278 134 412 255 145 400-6 350 113 463 330 123 453 304 135 439 278 147 425-4 389 115 504 364 125 489 337 137 474 306 150 456 278 165 443 249 182 431-2 422 116 538 396 127 523 369 139 508 333 153 486 306 168 474 273 184 4570 456 118 574 429 129 558 401 142 543 369 156 525 336 171 507 301 188 4892 493 120 613 465 131 596 435 144 579 402 158 560 366 174 540 328 191 519

    Pure water

    5 560 124 684 529 136 665 493 148 641 455 163 618 415 178 593 378 196 5747 588 126 714 571 138 709 535 151 686 494 166 660 453 182 635 412 199 61110 670 132 802 636 143 779 600 156 756 556 170 726 509 186 695 468 205 67312 719 135 854 682 146 828 645 159 804 601 173 774 544 189 733 506 208 71415 795 141 936 758 152 910 716 164 880 673 178 851 622 195 817 568 214 782

    2500BX

    Glycolwater

    -8 370 123 493 350 140 490 332 157 489 317 176 493-6 395 125 520 380 141 521 361 159 520 342 178 520-4 432 127 559 415 142 557 396 160 556 375 180 555 346 202 548-2 465 128 593 447 143 590 427 161 588 405 182 587 380 205 5850 498 129 627 480 145 625 459 163 622 437 184 621 411 209 6202 534 131 665 515 146 661 494 165 659 470 186 656 443 211 654

    Pure water

    5 599 133 732 578 149 727 555 168 723 530 190 720 500 215 7157 625 134 759 619 151 770 594 170 764 567 192 759 537 218 75510 705 139 844 682 154 836 656 173 829 627 195 822 595 221 81612 751 142 893 728 157 885 700 175 875 670 197 867 636 224 86015 824 146 970 798 161 959 770 178 948 737 200 937 701 227 928

    2800BX

    Glycolwater

    -8 366 125 491 340 136 476 313 151 464 289 168 457-6 399 127 526 371 138 509 344 153 497 316 170 486-4 434 128 562 405 140 545 375 155 530 345 172 517 315 192 507 286 215 501-2 470 130 600 442 143 585 408 157 565 375 174 549 344 194 538 313 217 5300 509 132 641 480 145 625 443 159 602 411 177 588 377 197 574 342 220 5622 551 134 685 520 147 667 484 162 646 446 179 625 407 200 607 372 223 595

    Pure water

    5 627 138 765 585 150 735 545 165 710 495 185 680 447 202 649 404 226 6307 661 140 801 627 153 780 582 167 749 553 188 741 490 206 696 452 230 68210 752 144 896 710 157 867 660 173 833 609 190 799 564 212 776 517 236 75312 806 147 953 764 160 924 710 175 885 650 192 842 605 215 820 556 240 79615 892 151 1043 847 164 1011 794 180 974 730 198 928 678 221 899 626 245 871

    2800BX

    Glycolwater

    -8 414 135 549 400 151 551 384 170 554 362 192 554-6 445 137 582 431 153 584 413 172 585 396 194 590-4 479 138 617 463 154 617 445 173 618 425 196 621 395 215 610-2 515 139 654 498 155 653 479 174 653 457 197 654 425 217 6420 552 140 692 534 157 691 514 176 690 491 199 690 458 219 6772 592 141 733 572 158 730 551 178 729 527 201 728 501 221 722

    Pure water

    5 663 144 807 642 161 803 617 181 798 591 204 795 566 224 7907 692 145 838 684 162 846 659 182 841 630 206 836 612 226 83810 779 148 927 754 165 919 725 185 910 695 209 904 665 228 89312 829 150 979 802 167 969 773 187 960 740 211 951 698 230 92815 908 153 1061 879 170 1049 847 190 1037 811 214 1025 780 234 1014

  • HYD

    RO

    CIA

    T LW

    R13

    4aWater cooled chillers

    9AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.588 B

    R1

    34

    a

    LWLWP

    CONDENSER WATER OUTLET TEMPERATURE °C

    Evaporator water outlet °C

    35 40 45 50 55 60Pf Pa Pc Pf Pa Pc Pf Pa Pc Pf Pa Pc Pf Pa Pc Pf Pa Pc

    kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW

    3200BX

    Glycolwater

    -8 409 149 558 381 163 544 352 179 531 322 199 521-6 448 151 599 418 165 583 388 181 569 356 201 557-4 487 153 640 456 167 623 424 184 608 390 203 593 354 226 580 317 253 570-2 531 155 686 497 169 666 463 186 649 427 206 633 390 229 619 350 256 6060 575 157 732 540 172 712 504 189 693 466 209 675 428 232 660 386 258 6442 624 159 783 587 174 761 549 191 740 508 211 719 467 234 701 423 261 684

    Pure water

    5 675 162 837 635 177 812 594 194 788 549 214 763 504 237 741 456 264 7207 730 164 894 689 180 869 644 197 841 596 217 813 548 241 789 499 267 76610 812 167 979 770 184 954 719 200 919 671 220 891 614 244 858 565 270 83512 867 169 1036 824 187 1011 769 202 971 721 223 944 658 247 905 608 273 88115 952 173 1125 908 192 1100 849 206 1055 796 228 1024 727 252 979 674 278 952

    3200BX

    Glycolwater

    -8 450 155 605 434 172 606 413 193 606 391 217 608-6 472 156 628 458 173 631 437 194 631 416 218 634-4 525 157 682 504 175 679 483 195 678 462 220 682 426 250 676-2 562 159 721 538 176 714 520 197 717 497 222 719 461 252 7130 607 160 767 583 178 761 557 198 755 534 224 758 496 254 7502 654 162 816 628 180 808 601 201 802 570 226 796 537 256 793

    5 729 165 894 698 183 881 667 205 872 633 229 862 591 259 8507 762 167 930 750 185 935 720 207 927 681 232 913 639 261 90010 860 171 1031 825 189 1014 788 210 998 752 236 988 707 265 97212 913 174 1087 886 192 1078 837 212 1049 802 238 1040 759 268 102715 988 177 1165 954 197 1151 913 217 1130 876 242 1118 827 273 1100

    3400BX

    Glycolwater

    -8 445 156 601 414 170 584 380 187 566 344 204 548-6 486 159 645 454 173 628 418 189 607 380 208 588-4 528 161 689 496 175 672 459 192 650 419 211 630 378 233 610 335 257 592-2 574 163 737 539 177 716 500 194 694 458 213 671 416 236 652 369 260 6290 620 165 785 583 180 763 543 196 739 499 215 714 456 239 694 407 262 6692 670 167 837 632 182 814 590 198 788 543 217 760 496 241 737 445 265 710

    Pure water

    5 734 171 906 691 187 877 643 205 848 594 225 819 543 248 791 489 272 7617 780 175 970 749 191 940 700 209 909 648 230 877 595 252 847 537 276 81310 891 181 1072 839 196 1035 787 214 1001 732 236 968 673 258 931 613 284 89612 959 185 1144 906 200 1106 851 218 1069 791 240 1031 731 263 994 667 289 95515 1060 191 1251 1006 206 1212 945 224 1170 881 246 1127 821 269 1090 749 296 1045

    3400BX

    Glycolwater

    -8 485 167 652 463 186 649 444 208 652 410 232 642-6 526 169 695 503 188 691 478 209 687 444 235 679-4 556 169 701 532 189 700 501 213 708 486 237 723 453 277 730-2 610 172 782 592 190 782 559 216 775 532 242 774 497 281 7780 658 173 831 633 193 826 602 220 822 570 244 814 536 283 8192 708 175 883 680 195 875 648 224 872 615 247 862 579 287 866

    Pure water

    5 786 178 964 757 199 956 737 230 967 690 256 946 651 294 9457 808 180 988 818 201 1019 794 232 1026 747 262 1009 703 297 100010 916 186 1102 897 208 1105 870 235 1105 825 266 1091 777 302 107912 1003 192 1195 972 212 1184 934 238 1172 889 269 1158 841 305 114615 1110 196 1306 1071 217 1288 1031 243 1274 982 273 1255 925 309 1234

    PERFORMANCESHYDROCIAT LW - LWP

    Pf : Cooling capacity valid a ΔT according to operating limits Glycol water utilisation zone compulsoryPa : Compressor absorbed power Low temperature option necessaryPc : Heating capacity valid a ΔT according to operating limits EUROVENT ConditionsOperation without HPS for condenser water outlet at 60°C

  • AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.588 B

    HYDROCIAT LW R134a

    10

    Water cooled chillers

    Pf : Cooling capacity valid a ΔT according to operating limits Glycol water utilisation zone compulsoryPa : Compressor absorbed power Low temperature option necessaryPc : Heating capacity valid a ΔT according to operating limits EUROVENT ConditionsOperation without HPS for condenser water outlet at 60°C

    PERFORMANCESHYDROCIAT LW - LWP

    R1

    34

    a

    LWLWP

    CONDENSER WATER OUTLET TEMPERATURE °C

    Evaporator water outlet °C

    35 40 45 50 55 60Pf Pa Pc Pf Pa Pc Pf Pa Pc Pf Pa Pc Pf Pa Pc Pf Pa Pc

    kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW

    3750BX

    Glycolwater

    -8 467 165 632 436 180 616 402 197 599 364 215 579-6 509 167 676 476 183 659 441 200 641 402 219 621-4 554 170 724 519 186 705 483 203 686 443 223 666 399 245 644 361 265 626-2 600 172 772 562 189 751 525 206 731 485 227 712 439 249 688 401 269 6700 645 174 819 607 192 799 568 209 777 527 230 757 479 253 732 441 273 7142 690 176 866 652 195 847 612 212 824 571 234 805 519 257 776 480 277 757

    Pure water

    5 802 186 988 752 206 958 700 227 927 648 250 898 595 274 869 540 302 8427 850 193 1043 812 209 1021 756 230 986 701 253 954 647 277 924 592 307 89910 955 195 1150 902 214 1116 840 235 1075 780 259 1039 725 283 1008 670 312 98212 1015 197 1212 962 217 1179 896 238 1134 832 262 1094 777 286 1063 722 317 103915 1105 202 1307 1052 222 1274 980 243 1223 912 267 1179 858 291 1149 803 325 1128

    3750BX

    Glycolwater

    -8 525 184 709 503 205 708 471 228 699 445 255 700-6 567 186 753 544 207 751 518 232 750 486 259 745-4 612 187 799 584 210 794 558 235 793 520 264 784 491 299 790-2 657 189 846 630 211 841 599 237 836 561 265 826 524 302 8260 708 191 899 679 214 893 649 239 888 616 271 887 560 305 8652 761 193 954 730 216 946 697 242 939 662 273 935 617 309 926

    Pure water

    5 841 196 1037 808 219 1027 769 246 1015 734 278 1012 682 315 9977 883 198 1081 860 222 1082 827 249 1076 784 281 1065 726 318 104410 977 201 1178 944 225 1169 916 253 1169 864 285 1149 825 324 114912 1063 205 1268 1023 228 1251 966 255 1221 927 289 1216 878 327 120515 1170 211 1381 1122 236 1358 1080 260 1340 1031 294 1325 981 334 1315

    4200BX

    Glycolwater

    -8 540 186 726 506 204 710 470 225 695 433 251 684-6 588 189 777 552 207 759 514 229 743 475 254 729-4 640 191 831 601 210 811 561 232 793 519 257 776 476 287 763 431 322 753-2 695 194 889 654 213 867 611 235 846 567 260 827 521 291 812 474 326 8000 755 197 952 711 216 927 665 238 903 618 264 882 568 294 862 518 330 8482 816 200 1016 768 219 987 721 242 963 670 268 938 618 298 916 567 334 901

    Pure water

    5 926 205 1131 874 225 1099 819 248 1067 762 275 1037 705 305 1010 647 341 9887 977 209 1186 943 229 1172 884 252 1136 823 279 1102 763 310 1073 702 346 104810 1110 214 1324 1052 234 1286 988 256 1244 923 285 1208 857 315 1172 790 351 114112 1185 218 1403 1125 238 1363 1058 260 1318 989 289 1278 920 320 1240 850 356 120615 1297 224 1521 1234 224 1458 1163 266 1429 1090 295 1385 1014 328 1342 940 364 1304

    4200BX

    Glycolwater

    -8 619 202 821 596 226 822 562 253 815 504 284 788-6 667 204 871 642 227 869 616 255 871 571 288 859-4 718 205 923 692 229 921 654 255 909 633 291 924 578 330 908-2 762 206 968 737 231 968 706 259 965 679 293 972 641 333 9740 830 209 1039 798 233 1031 751 261 1012 731 296 1027 693 336 10292 889 211 1100 849 235 1084 821 264 1085 782 298 1080 737 337 1074

    Pure water

    5 960 213 1173 932 240 1172 907 268 1175 863 302 1165 790 341 11317 1026 216 1242 1007 243 1250 968 271 1239 925 305 1230 858 345 120310 1138 221 1359 1096 248 1344 1071 275 1346 1010 309 1319 957 351 130812 1221 227 1448 1190 252 1442 1148 277 1425 1088 313 1401 1027 354 138115 1346 235 1581 1305 257 1562 1254 282 1536 1194 318 1512 1129 360 1489

  • HYD

    RO

    CIA

    T LW

    R13

    4aWater cooled chillers

    11AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.588 B

    DESUPERHEATER EXCHANGER LW - LWPThe system consists in a hot water supplying by an heat recovery system on the compressors discharge gas, on an auxiliarydesuperheater exchanger mounted in the unit.This optional equipment is only available on request, and factory mounted.

    ■ Recovery example on desuperheaterHYDROCIAT Cooling capacity Compressor absorbed Recovery Water flow Pressure drop

    LW - LWP Pf (kW) Pa (kW) Pr (kW) qv (m3/h) dP (mCE)1800BX 418 93 21 3.6 30

    1800BX HPS 433 96 22 3.8 332150BX 492 110 25 4.3 40

    2150BX HPS 533 115 27 4.6 452500BX 588 126 29 5.0 50

    2500BX HPS 625 134 31 5.3 602800BX 661 140 33 5.7 65

    2800BX HPS 692 145 35 6.0 703200BX 730 164 37 6.3 40

    3200BX HPS 762 167 38 6.5 433400BX 780 175 39 6.7 46

    3400BX HPS 808 180 40 7.0 493750BX 850 193 43 7.3 50

    3750BX HPS 883 198 44 7.6 554200BX 997 209 49 8.4 70

    4200BX HPS 1026 216 51 8.8 77

    Note : heat recovery performances for :➨ machine running in full load, chilled water = +12/+7°C and condenser hot water = 30°C / 35°C°C➨ hot water temperature on recovery = +55/+60°C

    ■ Diagram of therefrigerant circuitThe following refrigeration diagramdescribes an example of a CIAT unit,with desuperheater (on eachrefrigerant circuit).The heat recovery is possible only ifthe machine is running.For the same cooling or heatingcapacity, the desuperheater systemallows a free heating of hot water witha reduction of the total input power ofthe machine.

    Circuit 2 and 3 same conception than circuit 1- - - HPS equipment

    OPTION 1 : 3 ways valve fittingOPTION 2 : Compressor valveOPTION 3 : 3 ways valve fitting

    External sensor

    EVAPORATOR

    CONDENSER

    Standardfitting

    WATER

    WATER

    Only without HPS equipment

    WATER

    DESUPERHEATERSOPTION

    WATER

    ■ Principle and precautions of hydraulicconnection

    To start and to run the machine under good conditions, the waterloop must be as short as possible, and the water flow of thedesuperheater must start slowly with a water flow equal to 10%of its nominal value, and must be calculated for a hot water inlettemperature of +50°C.

    Thus, it is recommended to have a hydraulic diagram making itpossible to obtain hot water very quickly at the inlet of thedesuperheater (3-way valve + controller + temperature sensoron the exchanger water inlet)

    The controller set point must be adjusted to +50°C minimum.

    Note: particular attention must be given when selecting the expansion tank because the recovery water circuit can reach a

    as

    me

    dsv3v

    50˚C

    Optional desuperheater

    Min. 50°C

    Domestic hotwater circuit

  • AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.588 B

    HYDROCIAT LW R134a

    12

    Water cooled chillersR

    13

    4a

    LWLWP

    Desu

    perh

    eate

    rwa

    ter in

    let a

    ndou

    tlet te

    mpe

    ratu

    rein

    °CEv

    apor

    ator

    wat

    erou

    tlet t

    emp.

    °C CONDENSER WATER OUTLET TEMPERATURE °C

    35 40 45 50 55Pf Pa Pde Qde Pf Pa Pde Qde Pf Pa Pde Qde Pf Pa Pde Qde Pf Pa Pde Qde

    kW kW kW m3/h kW kW kW m3/h kW kW kW m3/h kW kW kW m3/h kW kW kW m3/h

    1800 BX

    50 °C / 55 °C

    5 397 92 32 5,5 375 99 45 7,7 349 108 56 9,6 323 119 65 11,1 296 131 77 13,2

    7 418 93 33 5,8 404 101 48 8,3 378 110 60 10,4 349 121 70 12,0 321 133 83 14,4

    10 476 96 38 6,5 451 105 54 9,3 424 114 68 11,7 393 124 79 13,5 362 137 94 16,2

    12 512 99 41 7,0 484 107 58 10,0 456 116 73 12,5 424 127 85 14,6 387 139 101 17,3

    15 567 102 45 7,8 537 110 64 11,1 506 120 81 13,9 474 130 95 16,3 435 143 113 19,5

    55 °C / 60 °C

    5 397 92 20 3,4 375 99 34 5,8 349 108 42 7,2 323 119 45 7,8 296 131 47 8,1

    7 418 93 21 3,6 404 101 36 6,3 378 110 45 7,8 349 121 49 8,4 321 133 51 8,8

    10 476 96 24 4,1 451 105 41 7,0 424 114 51 8,8 393 124 55 9,5 362 137 58 10,0

    12 512 99 26 4,4 484 107 44 7,5 456 116 55 9,4 424 127 59 10,2 387 139 62 10,7

    15 567 102 28 4,9 537 110 48 8,3 506 120 61 10,4 474 130 66 11,4 435 143 70 12,0

    1800 BX

    HPS

    50 °C / 55 °C

    5 415 95 33 5,7 399 104 48 8,2 381 116 61 10,5 363 129 73 12,5 343 146 89 15,3

    7 433 96 35 6,0 427 106 51 8,8 409 117 65 11,3 389 131 78 13,4 367 147 95 16,4

    10 489 99 39 6,7 471 108 57 9,7 452 120 72 12,4 430 133 86 14,8 406 149 106 18,2

    12 521 100 42 7,2 503 110 60 10,4 482 122 77 13,3 459 135 92 15,8 435 151 113 19,5

    15 570 103 46 7,8 553 113 66 11,4 529 124 85 14,6 505 138 101 17,4 478 154 124 21,4

    55 °C / 60 °C

    5 415 95 21 3,6 399 104 36 6,2 381 116 46 7,9 363 129 51 8,7 343 146 55 9,4

    7 433 96 22 3,7 427 106 38 6,6 409 117 49 8,4 389 131 54 9,4 367 147 59 10,1

    10 489 99 24 4,2 471 108 42 7,3 452 120 54 9,3 430 133 60 10,4 406 149 65 11,2

    12 521 100 26 4,5 503 110 45 7,8 482 122 58 9,9 459 135 64 11,1 435 151 70 12,0

    15 570 103 29 4,9 553 113 50 8,6 529 124 63 10,9 505 138 71 12,2 478 154 76 13,2

    2150 BX

    50 °C / 55 °C

    5 483 108 39 6,6 456 118 55 9,4 428 129 68 11,8 398 141 80 13,7 364 156 95 16,3

    7 492 111 39 6,8 492 120 59 10,2 462 131 74 12,7 431 144 86 14,8 397 158 103 17,8

    10 578 114 46 8,0 549 124 66 11,3 517 135 83 14,2 483 148 97 16,6 447 162 116 20,0

    12 621 117 50 8,5 588 127 71 12,1 556 138 89 15,3 520 151 104 17,9 482 166 125 21,6

    15 687 122 55 9,5 653 131 78 13,5 617 142 99 17,0 579 155 116 19,9 539 170 140 24,1

    55 °C / 60 °C

    5 483 108 24 4,2 456 118 41 7,1 428 129 51 8,8 398 141 56 9,6 364 156 58 10,0

    7 492 111 25 4,2 492 120 44 7,6 462 131 55 9,5 431 144 60 10,4 397 158 64 10,9

    10 578 114 29 5,0 549 124 49 8,5 517 135 62 10,7 483 148 68 11,6 447 162 72 12,3

    12 621 117 31 5,3 588 127 53 9,1 556 138 67 11,5 520 151 73 12,5 482 166 77 13,3

    15 687 122 34 5,9 653 131 59 10,1 617 142 74 12,7 579 155 81 13,9 539 170 86 14,8

    2150 BX

    HPS

    50 °C / 55 °C

    5 511 114 41 7,0 493 127 59 10,2 472 142 76 13,0 450 160 90 15,5 425 181 111 19,0

    7 533 116 43 7,3 527 129 63 10,9 506 144 81 13,9 482 162 96 16,6 455 183 118 20,3

    10 601 119 48 8,3 582 132 70 12,0 558 147 89 15,4 533 165 107 18,3 505 186 131 22,6

    12 640 121 51 8,8 620 134 74 12,8 596 149 95 16,4 569 167 114 19,6 539 188 140 24,1

    15 702 125 56 9,7 681 137 82 14,1 655 152 105 18,0 625 169 125 21,5 593 191 154 26,5

    55 °C / 60 °C

    5 511 114 26 4,4 493 127 44 7,6 472 142 57 9,7 450 160 63 10,8 425 181 68 11,7

    7 533 116 27 4,6 527 129 47 8,2 506 144 61 10,4 482 162 67 11,6 455 183 73 12,5

    10 601 119 30 5,2 582 132 52 9,0 558 147 67 11,5 533 165 75 12,8 505 186 81 13,9

    12 640 121 32 5,5 620 134 56 9,6 596 149 72 12,3 569 167 80 13,7 539 188 86 14,8

    15 702 125 35 6,0 681 137 61 10,5 655 152 79 13,5 625 169 88 15,1 593 191 95 16,3

    PARTIAL HEAT RECOVERY CAPACITY

    Pf : Cooling capacity valid a DT according to operating limitstPa : Compressors + fans absorbed power

    Pde: Desuperheater heating capacity recoveredQde : Desuperheater water flow

  • HYD

    RO

    CIA

    T LW

    R13

    4aWater cooled chillers

    13AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.588 B

    R1

    34

    a

    LWLWP

    Desu

    perh

    eate

    rwa

    ter in

    let a

    ndou

    tlet te

    mpe

    ratu

    rein

    °CEv

    apor

    ator

    wat

    erou

    tlet t

    emp.

    °C CONDENSER WATER OUTLET TEMPERATURE °C

    35 40 45 50 55Pf Pa Pde Qde Pf Pa Pde Qde Pf Pa Pde Qde Pf Pa Pde Qde Pf Pa Pde Qde

    kW kW kW m3/h kW kW kW m3/h kW kW kW m3/h kW kW kW m3/h kW kW kW m3/h

    2500 BX

    50 °C / 55 °C

    5 560 124 45 7,7 529 136 63 10,9 493 148 79 13,6 455 163 91 15,7 415 178 108 18,6

    7 588 127 47 8,1 571 138 69 11,8 535 151 86 14,7 494 166 99 17,0 453 182 118 20,3

    10 670 132 54 9,2 636 143 76 13,1 600 156 96 16,5 556 170 111 19,1 509 186 132 22,8

    12 719 135 58 9,9 682 146 82 14,1 645 159 103 17,8 601 173 120 20,7 544 189 141 24,3

    15 795 141 64 10,9 758 152 91 15,6 716 164 115 19,7 673 178 135 23,2 622 195 162 27,8

    55 °C / 60 °C

    5 560 124 28 4,8 529 136 48 8,2 493 148 59 10,2 455 163 64 11,0 415 178 66 11,4

    7 588 127 29 5,1 571 138 51 8,8 535 151 64 11,0 494 166 69 11,9 453 182 72 12,5

    10 670 132 34 5,8 636 143 57 9,8 600 156 72 12,4 556 170 78 13,4 509 186 81 14,0

    12 719 135 36 6,2 682 146 61 10,6 645 159 77 13,3 601 173 84 14,5 544 189 87 15,0

    15 795 141 40 6,8 758 152 68 11,7 716 164 86 14,8 673 178 94 16,2 622 195 100 17,1

    2500 BX

    HPS

    50 °C / 55 °C

    5 599 133 48 8,2 578 149 69 11,9 555 168 89 15,3 530 190 106 18,2 500 215 130 22,4

    7 625 135 50 8,6 619 151 74 12,8 594 170 95 16,3 567 192 113 19,5 537 218 140 24,0

    10 705 139 56 9,7 682 154 82 14,1 656 173 105 18,1 627 195 125 21,6 595 221 155 26,6

    12 751 142 60 10,3 728 157 87 15,0 700 175 112 19,3 670 197 134 23,0 636 224 165 28,4

    15 824 146 66 11,3 798 161 96 16,5 770 178 123 21,2 737 200 147 25,4 701 227 182 31,3

    55 °C / 60 °C

    5 599 133 30 5,2 578 149 52 8,9 555 168 67 11,5 530 190 74 12,8 500 215 80 13,8

    7 625 135 31 5,4 619 151 56 9,6 594 170 71 12,3 567 192 79 13,7 537 218 86 14,8

    10 705 139 35 6,1 682 154 61 10,6 656 173 79 13,5 627 195 88 15,1 595 221 95 16,4

    12 751 142 38 6,5 728 157 66 11,3 700 175 84 14,4 670 197 94 16,1 636 224 102 17,5

    15 824 146 41 7,1 798 161 72 12,4 770 178 92 15,9 737 200 103 17,7 701 227 112 19,3

    2800 BX

    50 °C / 55 °C

    5 627 138 50 4,3 585 150 70 6,0 545 165 87 7,5 495 185 99 8,5 447 202 116 10,0

    7 661 140 53 4,5 627 153 75 6,5 582 167 93 8,0 553 188 111 9,5 490 206 127 11,0

    10 752 144 60 5,2 710 157 85 7,3 660 173 106 9,1 609 190 122 10,5 564 212 147 12,6

    12 806 147 64 5,5 764 160 92 7,9 710 175 114 9,8 650 192 130 11,2 605 215 157 13,5

    15 892 151 71 6,1 847 164 102 8,7 794 180 127 10,9 730 198 146 12,6 678 221 176 15,2

    55 °C / 60 °C

    5 627 138 31 2,7 585 150 53 4,5 545 165 65 5,6 495 185 69 6,0 447 202 72 6,2

    7 661 140 33 2,8 627 153 56 4,9 582 167 70 6,0 553 188 77 6,7 490 206 78 6,7

    10 752 144 38 3,2 710 157 64 5,5 660 173 79 6,8 609 190 85 7,3 564 212 90 7,8

    12 806 147 40 3,5 764 160 69 5,9 710 175 85 7,3 650 192 91 7,8 605 215 97 8,3

    15 892 151 45 3,8 847 164 76 6,6 794 180 95 8,2 730 198 102 8,8 678 221 108 9,3

    2800 BX

    HPS

    50 °C / 55 °C

    5 663 144 53 4,6 642 161 77 6,6 617 181 99 8,5 591 204 118 10,2 566 224 147 12,7

    7 692 146 55 4,8 684 162 82 7,1 659 182 105 9,1 630 206 126 10,8 612 226 159 13,7

    10 779 148 62 5,4 754 165 90 7,8 725 185 116 10,0 695 209 139 12,0 665 228 173 14,9

    12 829 150 66 5,7 802 167 96 8,3 773 187 124 10,6 740 211 148 12,7 698 230 181 15,6

    15 908 153 73 6,2 879 170 105 9,1 847 190 136 11,7 811 214 162 13,9 780 234 203 17,4

    55 °C / 60 °C

    5 663 144 33 2,9 642 161 58 5,0 617 181 74 6,4 591 204 83 7,1 566 224 91 7,8

    7 692 146 35 3,0 684 162 62 5,3 659 182 79 6,8 630 206 88 7,6 612 226 98 8,4

    10 779 148 39 3,3 754 165 68 5,8 725 185 87 7,5 695 209 97 8,4 665 228 106 9,2

    12 829 150 41 3,6 802 167 72 6,2 773 187 93 8,0 740 211 104 8,9 698 230 112 9,6

    15 908 153 45 3,9 879 170 79 6,8 847 190 102 8,7 811 214 114 9,8 780 234 125 10,7

    PARTIAL HEAT RECOVERY CAPACITY

    Pf : Cooling capacity valid a DT according to operating limitstPa : Compressors + fans absorbed power

    Pde: Desuperheater heating capacity recoveredQde : Desuperheater water flow

  • AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.588 B

    HYDROCIAT LW R134a

    14

    Water cooled chillersR

    13

    4a

    LWLWP

    Desu

    perh

    eate

    rwa

    ter in

    let a

    ndou

    tlet te

    mpe

    ratu

    rein

    °CEv

    apor

    ator

    wat

    erou

    tlet t

    emp.

    °C CONDENSER WATER OUTLET TEMPERATURE °C

    35 40 45 50 55Pf Pa Pde Qde Pf Pa Pde Qde Pf Pa Pde Qde Pf Pa Pde Qde Pf Pa Pde Qde

    kW kW kW m3/h kW kW kW m3/h kW kW kW m3/h kW kW kW m3/h kW kW kW m3/h

    3200 BX

    50 °C / 55 °C

    5 675 162 54 9,3 635 177 76 13,1 594 194 95 16,3 549 214 110 18,9 504 237 131 22,5

    7 730 164 58 10,0 689 180 83 14,2 644 197 103 17,7 596 217 119 20,5 548 241 142 24,5

    10 812 167 65 11,2 770 184 92 15,9 719 200 115 19,8 671 220 134 23,1 614 244 160 27,5

    12 867 169 69 11,9 824 187 99 17,0 769 202 123 21,2 721 223 144 24,8 658 247 171 29,4

    15 952 173 76 13,1 908 192 109 18,7 849 206 136 23,4 796 228 159 27,4 727 252 189 32,5

    55 °C / 60 °C

    5 675 162 34 5,8 635 177 57 9,8 594 194 71 12,3 549 214 77 13,2 504 237 81 13,9

    7 730 164 37 6,3 689 180 62 10,7 644 197 77 13,3 596 217 83 14,4 548 241 88 15,1

    10 812 167 41 7,0 770 184 69 11,9 719 200 86 14,8 671 220 94 16,2 614 244 98 16,9

    12 867 169 43 7,5 824 187 74 12,8 769 202 92 15,9 721 223 101 17,4 658 247 105 18,1

    15 952 173 48 8,2 908 192 82 14,1 849 206 102 17,5 796 228 111 19,2 727 252 116 20,0

    3200 BX

    HPS

    50 °C / 55 °C

    5 729 165 58 10,0 698 183 84 14,4 667 205 107 18,4 633 229 127 21,8 591 259 154 26,4

    7 762 168 61 10,5 750 185 90 15,5 720 207 115 19,8 681 232 136 23,4 639 261 166 28,6

    10 860 171 69 11,8 825 189 99 17,0 788 210 126 21,7 752 236 150 25,9 707 265 184 31,6

    12 913 174 73 12,6 886 192 106 18,3 837 212 134 23,0 802 238 160 27,6 759 268 197 33,9

    15 988 177 79 13,6 954 197 114 19,7 913 217 146 25,1 876 242 175 30,1 827 273 215 37,0

    55 °C / 60 °C

    5 729 165 36 6,3 698 183 63 10,8 667 205 80 13,8 633 229 89 15,2 591 259 95 16,3

    7 762 168 38 6,6 750 185 68 11,6 720 207 86 14,9 681 232 95 16,4 639 261 102 17,6

    10 860 171 43 7,4 825 189 74 12,8 788 210 95 16,3 752 236 105 18,1 707 265 113 19,5

    12 913 174 46 7,9 886 192 80 13,7 837 212 100 17,3 802 238 112 19,3 759 268 121 20,9

    15 988 177 49 8,5 954 197 86 14,8 913 217 110 18,8 876 242 123 21,1 827 273 132 22,8

    3400 BX

    50 °C / 55 °C

    5 734 171 59 10,1 691 187 83 14,3 643 205 103 17,7 594 225 119 20,4 543 248 141 24,3

    7 780 175 62 10,7 749 191 90 15,5 700 209 112 19,3 648 230 130 22,3 595 252 155 26,6

    10 891 181 71 12,3 839 196 101 17,3 787 214 126 21,7 732 236 146 25,2 673 258 175 30,1

    12 959 185 77 13,2 906 200 109 18,7 851 218 136 23,4 791 240 158 27,2 731 263 190 32,7

    15 1060 191 85 14,6 1006 206 121 20,8 945 224 151 26,0 881 246 176 30,3 821 269 213 36,7

    55 °C / 60 °C

    5 734 171 37 6,3 691 187 62 10,7 643 205 77 13,3 594 225 83 14,3 543 248 87 14,9

    7 780 175 39 6,7 749 191 67 11,6 700 209 84 14,4 648 230 91 15,6 595 252 95 16,4

    10 891 181 45 7,7 839 196 76 13,0 787 214 94 16,2 732 236 103 17,6 673 258 108 18,5

    12 959 185 48 8,2 906 200 82 14,0 851 218 102 17,6 791 240 111 19,1 731 263 117 20,1

    15 1060 191 53 9,1 1006 206 91 15,6 945 224 113 19,5 881 246 123 21,2 821 269 131 22,6

    3400 BX

    HPS

    50 °C / 55 °C

    5 786 178 63 10,8 757 199 91 15,6 737 230 118 20,3 690 256 138 23,7 651 294 169 29,1

    7 808 181 65 11,1 818 201 98 16,9 794 232 127 21,9 747 262 149 25,7 703 297 183 31,4

    10 916 186 73 12,6 897 208 108 18,5 870 235 139 23,9 825 266 165 28,4 777 302 202 34,7

    12 1003 192 80 13,8 972 212 117 20,1 934 238 149 25,7 889 269 178 30,6 841 305 219 37,6

    15 1110 196 89 15,3 1071 217 129 22,1 1031 243 165 28,4 982 273 196 33,8 925 309 241 41,4

    55 °C / 60 °C

    5 786 178 39 6,8 757 199 68 11,7 737 230 88 15,2 690 256 97 16,6 651 294 104 17,9

    7 808 181 40 6,9 818 201 74 12,7 794 232 95 16,4 747 262 105 18,0 703 297 112 19,3

    10 916 186 46 7,9 897 208 81 13,9 870 235 104 18,0 825 266 116 19,9 777 302 124 21,4

    12 1003 192 50 8,6 972 212 87 15,0 934 238 112 19,3 889 269 124 21,4 841 305 135 23,1

    15 1110 196 56 9,5 1071 217 96 16,6 1031 243 124 21,3 982 273 137 23,6 925 309 148 25,5

    PARTIAL HEAT RECOVERY CAPACITY

    Pf : Cooling capacity valid a DT according to operating limitstPa : Compressors + fans absorbed power

    Pde: Desuperheater heating capacity recoveredQde : Desuperheater water flow

  • HYD

    RO

    CIA

    T LW

    R13

    4aWater cooled chillers

    15AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.588 B

    R1

    34

    a

    LWLWP

    Desu

    perh

    eate

    rwa

    ter in

    let a

    ndou

    tlet te

    mpe

    ratu

    rein

    °CEv

    apor

    ator

    wat

    erou

    tlet t

    emp.

    °C CONDENSER WATER OUTLET TEMPERATURE °C

    35 40 45 50 55Pf Pa Pde Qde Pf Pa Pde Qde Pf Pa Pde Qde Pf Pa Pde Qde Pf Pa Pde Qde

    kW kW kW m3/h kW kW kW m3/h kW kW kW m3/h kW kW kW m3/h kW kW kW m3/h

    3750 BX

    50 °C / 55 °C

    5 802 186 64 11,0 752 206 90 15,5 700 227 112 19,3 648 250 130 22,3 595 274 155 26,6

    7 850 193 68 11,7 812 209 97 16,8 756 230 121 20,8 701 253 140 24,1 647 277 168 28,9

    10 955 195 76 13,1 902 214 108 18,6 840 235 134 23,1 780 259 156 26,8 725 283 189 32,4

    12 1015 197 81 14,0 962 217 115 19,9 896 238 143 24,7 832 262 166 28,6 777 286 202 34,7

    15 1105 202 88 15,2 1052 222 126 21,7 980 243 157 27,0 912 267 182 31,4 858 291 223 38,4

    55 °C / 60 °C

    5 802 186 40 6,9 752 206 68 11,6 700 227 84 14,4 648 250 91 15,6 595 274 95 16,4

    7 850 193 43 7,3 812 209 73 12,6 756 230 91 15,6 701 253 98 16,9 647 277 104 17,8

    10 955 195 48 8,2 902 214 81 14,0 840 235 101 17,3 780 259 109 18,8 725 283 116 20,0

    12 1015 197 51 8,7 962 217 87 14,9 896 238 108 18,5 832 262 116 20,0 777 286 124 21,4

    15 1105 202 55 9,5 1052 222 95 16,3 980 243 118 20,2 912 267 128 22,0 858 291 137 23,6

    3750 BX

    HPS

    50 °C / 55 °C

    5 841 196 67 11,6 808 219 97 16,7 769 246 123 21,2 734 278 147 25,2 682 315 177 30,5

    7 883 199 71 12,2 860 222 103 17,8 827 249 132 22,8 784 281 157 27,0 726 318 189 32,5

    10 977 201 78 13,4 944 225 113 19,5 916 253 147 25,2 864 285 173 29,7 825 324 215 36,9

    12 1063 205 85 14,6 1023 228 123 21,1 966 255 155 26,6 927 289 185 31,9 878 327 228 39,3

    15 1170 211 94 16,1 1122 236 135 23,2 1080 260 173 29,7 1031 294 206 35,5 981 334 255 43,9

    55 °C / 60 °C

    5 841 196 42 7,2 808 219 73 12,5 769 246 92 15,9 734 278 103 17,7 682 315 109 18,8

    7 883 199 44 7,6 860 222 77 13,3 827 249 99 17,1 784 281 110 18,9 726 318 116 20,0

    10 977 201 49 8,4 944 225 85 14,6 916 253 110 18,9 864 285 121 20,8 825 324 132 22,7

    12 1063 205 53 9,1 1023 228 92 15,8 966 255 116 19,9 927 289 130 22,3 878 327 140 24,2

    15 1170 211 59 10,1 1122 236 101 17,4 1080 260 130 22,3 1031 294 144 24,8 981 334 157 27,0

    4200 BX

    50 °C / 55 °C

    5 926 205 74 12,7 874 225 105 18,0 819 248 131 22,5 762 275 152 26,2 705 305 183 31,5

    7 977 209 78 13,4 943 229 113 19,5 884 252 141 24,3 823 279 165 28,3 763 310 198 34,1

    10 1110 214 89 15,3 1052 234 126 21,7 988 256 158 27,2 923 285 185 31,8 857 315 223 38,3

    12 1185 218 95 16,3 1125 238 135 23,2 1058 260 169 29,1 989 289 198 34,0 920 320 239 41,1

    15 1297 224 104 17,8 1234 224 148 25,5 1163 266 186 32,0 1090 295 218 37,5 1014 328 264 45,3

    55 °C / 60 °C

    5 926 205 46 8,0 874 225 79 13,5 819 248 98 16,9 762 275 107 18,3 705 305 113 19,4

    7 977 209 49 8,4 943 229 85 14,6 884 252 106 18,2 823 279 115 19,8 763 310 122 21,0

    10 1110 214 56 9,5 1052 234 95 16,3 988 256 119 20,4 923 285 129 22,2 857 315 137 23,6

    12 1185 218 59 10,2 1125 238 101 17,4 1058 260 127 21,8 989 289 138 23,8 920 320 147 25,3

    15 1297 224 65 11,2 1234 224 111 19,1 1163 266 140 24,0 1090 295 153 26,2 1014 328 162 27,9

    4200 BX

    HPS

    50 °C / 55 °C

    5 960 213 77 13,2 932 240 112 19,2 907 268 145 25,0 863 302 173 29,7 790 341 205 35,3

    7 1026 216 82 14,1 1007 243 121 20,8 968 271 155 26,6 925 305 185 31,8 858 345 223 38,4

    10 1138 221 91 15,7 1096 248 132 22,6 1071 275 171 29,5 1010 309 202 34,7 957 351 249 42,8

    12 1221 227 98 16,8 1190 252 143 24,6 1148 277 184 31,6 1088 313 218 37,4 1027 354 267 45,9

    15 1346 235 108 18,5 1305 257 157 26,9 1254 282 201 34,5 1194 318 239 41,1 1129 360 294 50,5

    55 °C / 60 °C

    5 960 213 48 8,3 932 240 84 14,4 907 268 109 18,7 863 302 121 20,8 790 341 126 21,7

    7 1026 216 51 8,8 1007 243 91 15,6 968 271 116 20,0 925 305 130 22,3 858 345 137 23,6

    10 1138 221 57 9,8 1096 248 99 17,0 1071 275 129 22,1 1010 309 141 24,3 957 351 153 26,3

    12 1221 227 61 10,5 1190 252 107 18,4 1148 277 138 23,7 1088 313 152 26,2 1027 354 164 28,3

    15 1346 235 67 11,6 1305 257 117 20,2 1254 282 150 25,9 1194 318 167 28,8 1129 360 181 31,1

    PARTIAL HEAT RECOVERY CAPACITY

    Pf : Cooling capacity valid a DT according to operating limitstPa : Compressors + fans absorbed power

    Pde: Desuperheater heating capacity recoveredQde : Desuperheater water flow

  • AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.588 B

    HYDROCIAT LW R134a

    16

    Water cooled chillers

    Difference of temperature for performances calculation tablesExample :For a water outlet : + 5 °C (ΔT for performances calculation 5 °C)ΔT minimum : 3,1 °C Water temp : 8,1 / 5 °CΔT maximum : 7,5 °C Water temp : 12,5 / 5 °C

    -8 -4 5 15

    C

    B A

    30

    50

    55

    60

    D

    Evaporator water outlet temperature ˚C

    Cond

    ense

    r wat

    er o

    utle

    t tem

    pera

    ture

    ˚C

    A - Full load operation with pure water

    B - Full load operation with glycol compulsory

    C - Operation without HPS

    D - Part load operation

    OPERATION RANGES

    EVAPORATOR LIMITSThe curve below represents the min. and max. admissible temperature differences on pure water or glycol water as a function of the fluid outlet temperature at the evaporator.

    Check also minimum and maximum temperature differencesaccording to minimum and maximum flow (see curves on"Hydraulic characteristics" page).

    CONDENSER LIMITSIMPORTANT : For the LW - LWP units to operate efficiently, particularly during start-up, itis necessary to fit a device which allows the condenser water inlet temperature to reach20°C very quickly (fitting of 3-way valves for example).

    Mass concentration %

    Multiplying coefficientCooling capacity

    Chilled water flow

    Chilled waterpressure drops

    10 0.99 1.05 1.0520 0.985 1.10 1.1030 0.98 1.15 1.1540 0.97 1.20 1.23

    CORRECTION FACTORS FOR ETHYLENE GLYCOL■ Evaporator ■ Condenser

    Mass concentration %

    Multiplying coefficientCooling capacity

    Hot water flow

    Hot water pressure drops

    10 1 1.05 1.0520 1 1.10 1.1030 0.99 1.15 1.1540 0.99 1.20 1.25

    ■ Glycol concentration necessaryMass concentration % 0 10 20 30 40

    Ethylene glycolFreezing point °C 0 -4 -9 -16 -23Minimum water outlet °C 4 2 0 -5 -11

    Propylene glycolFreezing point °C 0 -3 -7 -13 -22Minimum water outlet °C 4 3 -2 -4 -10

    ■ LW - LWP operation range

    HYDROCIAT LW LWPWater cooled condenserΔT mini °CΔT maxi °C

    YES48

    Evaporator water outlet temperature (˚C)

    ΔT b

    etw

    een

    evap

    orat

    or w

    ater

    inle

    t / o

    utle

    t ˚C

  • HYD

    RO

    CIA

    T LW

    R13

    4aWater cooled chillers

    17AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.588 B

    Do not extrapolate the values. Minimum and maximum water flow must be respected.

    40 50 60 80 100 150 200 2500.6

    0.81

    2

    3

    56

    810

    14

    4

    2150BX

    (HPS) -

    2500B

    X(HPS)

    - 2800

    BX(HP

    S)

    3750BX

    (HPS)

    3200BX

    (HPS) -

    3400B

    X (HPS)

    - 4200

    BX (HP

    S)

    1800BX

    (HPS)

    0.6

    1

    2

    3

    5

    4

    0.5

    0.4

    0.3

    0.2

    0.8

    30 50 60 80 100 150 200 30040 400

    1800

    BX(H

    PS) -

    2150

    BX(H

    PS)

    2500

    BX(H

    PS) -

    2800

    BX(H

    PS)

    3200

    BX (H

    PS) -

    3400

    BX (H

    PS)

    3750

    BX (H

    PS) -

    4200

    BX (H

    PS)

    -> W

    ater

    pre

    ssur

    e dr

    op in

    mW

    G

    -> Water flow in m3/h

    -> W

    ater

    pre

    ssur

    e dr

    op in

    mW

    G

    -> Water flow in m3/h

    HYDROCIAT LW - LWP■ Condenser

    WATER PRESSURE DROP

    HYDROCIAT LW - LWN - LWP■ Evaporator

  • AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.588 B

    HYDROCIAT LW R134a

    18

    Water cooled chillers

    MINIMUM CHILLED WATER VOLUMESHYDROCIAT LW - LWP

    A Xtra Connect microprocessor fitted on HYDROCIAT units allows a very flexible adjustment of the operation in relation to thedrift of parameters, especially for hydraulic installation with low water volume.

    The auto adaptive control of the units and modulating capacity control on each compressor means that the use of the anti-shortcycle function and the installation of buffer tank is not necessary.

    Minimum chilled water volumes calculation for the following conditions :

    - Evaporator chilled water temperature : 12°C / 7°C

    - Condenser hot water temperature : 30°C / 35°C

    Note : Installations with important thermal variation or some industrial process designed to supply very constant watertemperature, should be equipped with a buffer tank.

    Models LW- LWP

    1800BX1800BX

    HPS2150BX

    2150BXHPS

    2500BX2500BX

    HPS2800BX

    2800BXHPS

    3200BX3200BX

    HPS3400BX

    3400BXHPS

    3750BX3750BX

    HPS4200BX

    4200BXHPS

    Minimum volumeof installations

    (liters)1327 1381 1544 1691 1888 2021 2150 2261 1421 1499 1543 1611 1713 1745 2023 2086

    ■ Desuperheater water pressure drops

    0 50 100 1050

    2

    4

    6

    8

    10

    LW 32

    00BX (

    HPS)

    - 4200

    BX (H

    PS)

    LW 1

    800B

    X (H

    PS) -

    280

    0BX

    (HPS

    )

    -> W

    ater

    pre

    ssur

    e dr

    op in

    mW

    G

    -> Water flow in m3/h

  • HYD

    RO

    CIA

    T LW

    R13

    4aWater cooled chillers

    19AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.588 B

    LW - LWPSOUND PRESSURE LEVEL SPECTRUM (dB) Total pressure level

    dB (A)63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz

    1800BX (HPS) 42 44 50 58 54 45 29 582150BX (HPS) 43 48 60 57 53 51 36 592500BX (HPS) 45 42 58 59 56 53 38 612800BX (HPS) 48 46 61 62 59 56 41 643200BX (HPS) 45 42 59 61 57 53 38 623400BX (HPS) 46 45 58 61 57 53 38 623750BX (HPS) 47 44 60 61 58 55 40 634200BX (HPS) 49 47 62 64 61 58 42 66

    SOUND LEVELS

    Standard version (without acoustically lined housing compressors)

    ■ Sound pressure levels ref 2 x 10-5 Pa ± 3 dB (Lp)

    LW - LWPSOUND POWER LEVEL SPECTRUM (dB) Total power

    level dB(A)63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz

    1800BX (HPS) 74 76 82 90 86 77 61 902150BX (HPS) 75 80 92 89 85 83 68 912500BX (HPS) 77 74 90 91 88 85 70 932800BX (HPS) 80 78 93 94 91 88 73 963200BX (HPS) 77 74 91 93 89 85 70 943400BX (HPS) 78 77 90 93 89 85 70 943750BX (HPS) 79 76 92 93 90 87 72 954200BX (HPS) 81 79 94 96 93 90 74 98

    ■ Sound power levels ref 10-12 W ± 3 dB (Lw)

    LW - LWPSOUND PRESSURE LEVEL SPECTRUM (dB) Total pressure level

    dB (A)63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz

    1800BX (HPS) 46 41 53 53 50 47 31 542150BX (HPS) 45 46 60 55 49 46 35 562500BX (HPS) 47 40 57 58 52 48 36 582800BX (HPS) 50 43 60 61 55 51 39 613200BX (HPS) 49 39 62 56 53 55 40 603400BX (HPS) 50 42 61 56 53 55 40 603750BX (HPS) 51 41 63 56 54 57 42 614200BX (HPS) 53 44 65 59 57 60 44 64

    LW - LWPSOUND POWER LEVEL SPECTRUM (dB) Total power

    level dB(A)63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz

    1800BX (HPS) 78 73 85 85 82 79 63 862150BX (HPS) 77 78 92 87 81 78 67 882500BX (HPS) 79 72 89 90 84 80 68 902800BX (HPS) 82 75 92 93 87 83 71 933200BX (HPS) 81 71 94 88 85 87 72 923400BX (HPS) 82 74 93 88 85 87 72 923750BX (HPS) 83 73 95 88 86 89 74 934200BX (HPS) 85 76 97 91 89 92 76 96

    Pressure levels are calculated following ISO 3744 regulation Lp = Lw - 10 log S, in free field and at 10 meters from theunit.We remind you that the sound pressure levels are given as an indication and only the sound power levels arecomparable and certified.

    Low noise version (with acoustically lined housing compressors)

    ■ Sound pressure levels ref 2 x 10-5 Pa ± 3 dB (Lp)

    ■ Sound power levels 10-12 W ± 3 dB (Lw)

  • AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.588 B

    HYDROCIAT LW R134a

    20

    Water cooled chillers

    DIMENSIONSHYDROCIAT LW - LWP

    ■ 2 compressors, 2 refrigerant circuits

    672

    810

    672

    2442

    889

    387

    270

    E F

    1320

    2450

    4230

    3800

    2680 690

    3200

    3945

    DN 200DN 16

    Option 4

    Option 1Option 2

    Option 5Option 3

    Option 3

    (1)

    NOTE : the electrical wiring is on the right of the panel through the bottomDimensions in mm

    (1) 1860 for reduced height version. Compressor suction valve mounted as standard and acoustically lined housing not availablefor this version.

    a : cooling water inlet

    b : cooling water outlet

    c : chilled water inlet

    d : chilled water outlet

    Option 1 : compressor suction valve

    Option 2 : acoustically lined housing

    Option 3 : condensers headers (flexible hydraulic sleeves andflange/Victaulic adapter included)

    Option 4 : hydraulic flexible connections (flange/Victaulicadapter included)

    Option 5 : 8 antivibration mounts 400 x 70 x 25

    with option

    without option

    without option

    with option

    LW - LWPA - B

    Victaulicc - d

    VictaulicD E F

    Weight in kgempty in operation

    1800BX (HPS) PN 16 DN 150 PN 16 DN 150 180 411 290 3130 3360

  • HYD

    RO

    CIA

    T LW

    R13

    4aWater cooled chillers

    21AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.588 B

    DIMENSIONSHYDROCIAT LW - LWP

    ■ 2 compressors, 2 refrigerant circuits

    672

    1060

    672

    2442

    889

    387

    190

    E F

    1320

    2450

    4455

    4010

    3180 690

    3200

    4005

    4700

    (1)DN 200

    DN 16

    with option

    without option

    with option

    without option

    a : cooling water inlet

    b : cooling water outlet

    c : chilled water inlet

    d : chilled water outlet

    Option 1 : compressor suction valve

    Option 2 : acoustically lined housing

    Option 3 : condensers headers (flexible hydraulic sleeves andflange/Victaulic adapter included)

    Option 4 : hydraulic flexible connections (flange/Victaulicadapter included)

    Option 5 : 8 antivibration mounts 400 x 70 x 25

    LW - LWPA - B

    Victaulicc - d

    VictaulicD E F

    Weight in kgempty in operation

    2150BX (HPS) PN 16 DN 150 PN 16 DN 150 180 383 346 3520 38002500BX (HPS) PN 16 DN 150 PN 16 DN 150 180 383 346 3830 41102800BX (HPS) PN 16 DN 150 PN 16 DN 150 180 383 346 3840 4120

    NOTE : the electrical connection is on the right of the panel through the bottomDimensions in mm

    (1) 1970 for reduced height version. Compressor suction valve mounted as standard and acoustically lined housing not availablefor this version.

  • AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.588 B

    HYDROCIAT LW R134a

    22

    Water cooled chillers

    LW - LWPA - B - CVictaulic

    c - dD E F

    Weight in kgVictaulic empty in operation

    3200BX (HPS) PN 16 DN 150 PN 16 DN 200 123 4475 3080 4930 53003400BX (HPS) PN 16 DN 150 PN 16 DN 200 123 4475 3080 5230 55103750BX (HPS) PN 16 DN 150 PN 16 DN 200 123 4725 3580 5660 60604200BX (HPS) PN 16 DN 150 PN 16 DN 200 98 4475 3080 5800 6210

    DIMENSIONSHYDROCIAT LW - LWP

    ■ 3 compressors, 3 refrigerant circuits

    780

    E

    F

    1730

    2325

    290

    29063200

    4065

    672 672

    (1)

    NOTE : the electrical connection is on the right of the panel through the bottomDimensions in mm

    (1) 2050 for reduced height version. Compressor suction valve mounted as standard and acoustically lined housingnot available for this version.

    a : cooling water inlet

    b : cooling water outlet

    c : chilled water inlet

    d : chilled water outlet

    Option 1 : compressor suction valve

    Option 2 : acoustically lined housing

    Option 3 : condensers headers (flexible hydraulic sleeves andflange/Victaulic adapter included)

    Option 4 : hydraulic flexible connections (flange/Victaulic adapter included)

    Option 5 : 12 antivibration mounts 400 x 70 x 25

  • HYD

    RO

    CIA

    T LW

    R13

    4aWater cooled chillers

    23AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.588 B

    RECOMMENDATIONS FOR ASSEMBLY

    HYDROCIAT LW - LWP

    ■ Installation

    HYDROCIAT LW - LWP are designed for indoor installation and must be protected from adverse weather andfrost.

    ■ A free space of 1 meter must be left all around the unit foraccess to the electrical panel and other components.

    ■ A free space on one side is also necessary (equal to thelength of the unit) in case one of heat exchangers needs to beremoved.

    ■ Sound level problems should be studied in detail. Beforeinstalling the unit, study and if necessary treat (with theassistance of a sound technicien) the various possible noisetransmissions in relation to the premises and its structure. Ifnecessary the machine should be equipped with anti-vibrationmounts and flexible connections (recommended and proposedas an option).

    ■ Electrical connections

    All the indications necessary for the electrical connections arementioned on the electrical diagram enclosed with the unit (tobe respected).

    ■ These connections will be made in accordance with accepted engineering practice and conform to the regulationsin force.

    ■ Leave the control circuit switched on to allow operation of thecrankcase heater.

    ■ The electrical mains supply must be fitted with fuse or circuitbreaker protection (to be supplied by the fitter).

    ■ Hydraulic connections■ Water connections must be made in accordance with goodengineering practice.

    ■ Provide the accessories necessary for hydraulic circuits :

    - Expansion vessel,

    - Drain cocks at low points,

    - Isolating valves,

    - Air vents at high points, etc ...,

    - Check that the water content in the installation is sufficient,

    - Provide, if required, a buffer tank.

    ■ Commissioning

    ■ In accordance with our installation and maintenance brochure.

    ■ Maintenance

    ■ See our operating and maintenance guide.

    ■ Subscribe a maintenance contract.

  • AIR CONDITIONING - HEATING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 08.588 B

    HYDROCIAT LW R134a

    24

    Water cooled chillers

    Non contractual document. With the thought of material improvement always in mind, CIAT reserves the right,without notice, to proceed with any technical modification.

    Head office & FactoriesAvenue Jean Falconnier - B.P. 1401350 - Culoz - FranceTel.: 33 4 79 42 42 42 - Fax: 33 4 79 42 42 10e-mail: [email protected] - http:\\www.ciat.com

    CCompagnie IIndustrielle d’AApplications TThermiques - S.A. with a registered capital of 26 000 000 € - R.C.S. Belley B 545 620 114

    CIAT ServiceTél. : 33 4 79 42 42 90 - Fax : 33 4 79 42 42 13

    XTRACONNECT CONTROL

    - LDC multilingual screen (2 lines of 20 characters)- Pressures and temperatures reading- Pump control- Communication

    Available free contacts inputs / outputs

    Inputs : - External ON/OFF contact- Chilled water pump external ON/OFF contact- Setpoint 1/2 selection- General fault- Emergency stop- Compressors load shedding- 0 - 20 mA remote control

    Output : - General fault of the unit- General fault per dircuit- Pump control

    MODBUS-JBUS open Protocol (standard)LONWORKS Protocol (option)

    RS 485 OUTPUT IN STANDARD

    FREE CONTACTS RELAY CARD (OPTION)

    REMOTE CONTROL BOX (OPTION)

    Operation and design same as display console

    Available outputs :- Water flow fault- Antifreeze fault- Pump fault- Fans fault- Emergency stop fault- Low and high pressure fault- Compressors safety fault- Compressors superheating fault- Compressors lubrication fault- Discharge temperature fault- Compressors running

    ERGONOMIC INTERFACE PANEL

    MULTICONNECT MULTI-UNIT MANAGEMENT (OPTION)Main functions available:

    - Management of up to 8 units on a single water loop

    - Management in cooling mode (water chiller) or heating mode (heat pump)

    - Management of chilled-water or hot-waterpumps

    - Centralised management of a backup unit- Unit load shedding- System time programming- Energy storage mode management- Fault management on each unit- Unit running time balancing- Integrated Modbus BMS link for obtaining

    information on unit operation and faults