vr-300 multi function voltage protection relay im en 6 2012

28
IL02602004E For more information visit: www.Eaton.com VR-300 Multi Function Voltage Protection Relay Instructional Literature New Information Description Page 1. General Information . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2. Electrostatic Discharge Awareness . . . . . . . . . . . . . . . 3 3. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 4. Functional Description . . . . . . . . . . . . . . . . . . . . . . . . 8 5. Display and Operating Elements . . . . . . . . . . . . . . . . . 9 6. Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 7. Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Appendix A. Dimensions . . . . . . . . . . . . . . . . . . . . . . 22 Appendix B. Technical Data . . . . . . . . . . . . . . . . . . . . 23 Appendix C. Measured Quantities . . . . . . . . . . . . . . . . 24 Appendix D. List of Parameters . . . . . . . . . . . . . . . . . . 25 VR-300 Display Clear Operating Alarm Select Digit Cursor Reversible Display Menu Converting, Controlling, Monitoring Hz L 1 / L12 L 2 / L23 L 3 / L31 []

Upload: rodruren01

Post on 26-Sep-2015

219 views

Category:

Documents


0 download

DESCRIPTION

VR-300 Multi Function Voltage Protection Relay IM en 6 2012

TRANSCRIPT

  • IL02602

    VR-300

    Reversible Display

    Monitoring

    Hz

    3 L3 / L31 [ ]Display

    Operating Alarm

    Selec004E For more information visitClear

    t Digit Cursor

    MenuVR-300 Multi Function Voltage Protection RelayInstructional Literature

    New Information

    Description Page

    1. General Information . . . . . . . . . . . . . . . . . . . . . . . . . . 32. Electrostatic Discharge Awareness . . . . . . . . . . . . . . . 33. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44. Functional Description . . . . . . . . . . . . . . . . . . . . . . . . 85. Display and Operating Elements . . . . . . . . . . . . . . . . . 96. Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117. Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

    Appendix A. Dimensions . . . . . . . . . . . . . . . . . . . . . . 22Appendix B. Technical Data . . . . . . . . . . . . . . . . . . . . 23Appendix C. Measured Quantities . . . . . . . . . . . . . . . . 24Appendix D. List of Parameters. . . . . . . . . . . . . . . . . . 25

    Converting, Controlling,

    L 1 / L12 L2 / L2: www.Eaton.com

  • Instructional LiteraturePage 2 Effective: July 2007 VR-300 Multi Function Voltage Protection Relay

    Important Definitions

    Note: Provides other helpful information that does not fall under the warn-ing or caution categories.

    Eaton reserves the right to update any portion of this publication

    and reliable. However, Eaton assumes no responsibility unlessotherwise expressly undertaken.

    Eaton Corporation

    All Rights Reserved.

    Revision History

    WARNINGINDICATES A POTENTIALLY HAZARDOUS SITUATION THAT, IF NOTAVOIDED, COULD RESULT IN DEATH OR SERIOUS INJURY.

    CAUTIONINDICATES A POTENTIALLY HAZARDOUS SITUATION THAT, IF NOTAVOIDED, COULD RESULT IN DAMAGE TO EQUIPMENT.

    REV. DATE EDITOR CHANGES

    06-08-11 TPNEW Release based on 3735107-07-18 TPA New relay assignment function

    starting with SW version 3.1450; cutout section added

    at any time. Information provided by Eaton is believed to be correct

    WARNING

    CAUTION

    OUT-OF-DATE PUBLICATION

    READ THIS ENTIRE MANUAL AND ALL OTHER PUBLICATIONS PERTAINING TO THE WORK TO BE PERFORMED BEFORE INSTALL-ING, OPERATING, OR SERVICING THIS EQUIPMENT. PRACTICE ALL PLANT AND SAFETY INSTRUCTIONS AND PRECAUTIONS. FAILURE TO FOLLOW INSTRUCTIONS CAN CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.

    THE ENGINE, TURBINE, OR OTHER TYPE OF PRIME MOVER SHOULD BE EQUIPPED WITH AN OVER SPEED (OVER TEMPERA-TURE, OR OVERPRESSURE, WHERE APPLICABLE) SHUTDOWN DEVICE(S), THAT OPERATES TOTALLY INDEPENDENTLY FO THE PRIME MOVER CONTROL DEVICE(S) TO PROTECT AGAINST RUNAWAY OR DAMAGE TO THE ENGINE, TURBINE, OR OTHER TYPE OF PRIME MOVER WITH POSSIBLE PERSONAL INJURY OR LOSS OF LIFE SHOULD THE MECHANICAL-HYDRAULIC GOVERNOR(S) OR ELECTRIC CONTROL(S), THE ACTUATOR(S), FUEL CONTROL(S), THE DRIVING MECHANISM(S), THE LINKAGE(S), OR THE CONTROLLED DEVICE(S) FAIL.

    ANY UNAUTHORIZED MODIFICATIONS TO OR USE OF THE EQUIPMENT OUTSIDE ITS SPECIFIED MECHANICAL, ELECTRICAL, OR OTHER OPERATING LIMITS MAY CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE, INCLUDING DAMAGE TO THE EQUIPMENT. ANY SUCH UNAUTHORIZED MODIFICATIONS: (I) CONSTITUTE MISUSE AND/OR NEGLIGENCE WITHIN THE MEANING OF THE PRODUCT WARRANTY THEREBY EXCLUDING WARRANTY COVERAGE FOR ANY RESULTING DAMAGE, AND (II) INVALIDATE PRODUCT CERTIFICATIONS OR LISTING.

    TO PREVENT DAMAGE TO A CONTROL SYSTEM THAT USES AN ALTERNATOR OR BATTERY-CHARGING DEVICE, MAKE SURE THE CHARGING DEVICE IS TURNED OFF BEFORE DISCONNECTING THE BATTERY FROM THE SYSTEM

    ELECTRONIC CONTROLS CONTAIN STATIC-SENSITIVE PARTS. OBSERVE THE FOLLOWING PRECAUTIONS TO PREVENT DAMAGE TO THESE PARTS.

    DISCHARGE BODY STATIC BEFORE HANDLING THE CONTROL (WITH POWER TO THE CONTROL TURNED OFF, CONTACT A GROUNDED SURFACE AND MAINTAIN CONTACT WHILE HANDLING THE CONTROL).

    AVOID ALL PLASTIC VINYL, AND STYROFOAM (EXCEPT ANTISTATIC VERSIONS) AROUND PRINTED CIRCUIT BOARDS.

    DO NOT TOUCH THE COMPONENTS OR CONDUCTIONS ON A PRINTED CIRCUIT BOARD WITH YOUR HANDS OR WITH CONDUCTIVE DEVICES.

    THIS PUBLICATION MAY HAVE BEEN REVISED OR UPDATED SINCE THIS COPY WAS PRODUCED. TO VERIFY THAT YOU HAVE THE LATEST REVISION, BE SURE TO CHECK THE EATON WEBSITE:

    HTTP://WWW.EATON.COM

    THE REVISION LEVEL IS SHOWN ON THE FRONT COVER AFTER THE PUBLICATION NUMBER. THE LATEST VERSION OF MOST PUBLICATIONS IS AVAILABLE AT:

    HTTP://WWW.EATON.COM

    IF YOU PUBLICATION IS NOT THERE, PLEASE CONTACT YOUR CUSTOMER SERVICE REPRESENTATIVE TO GET THE LATEST COPY.IL02602004EFor more information visit: www.Eaton.com

  • Instructional LiteratureEffective: July 2007 Page 3VR-300 Multi Function Voltage Protection Relay

    Section 1: General InformationIntroductionThe VR-300 model is a multifunction protection unit packaged into one compact device. Typical applications are generators and switchgear equipment that require independent protection archi-tecture to implement transfer schemes.

    Measurement Value LoggingVoltageVoltage is displayed as three-phase R.M.S. measurement of the phase-neutral and/or phase-phase voltages. The unit utilizes sin-gle-phase R.M.S. measurement of the synchronizing voltage VL1-L2.This device can be ordered with the following measuring voltage input ranges (rated voltages). Please indicate the measuring volt-age input required when ordering (refer to Appendix B: Technical Data on page 23): 66 V/115 V...... [1]FrequencyFrequency measurement is extracted from the digitally filtered measuring voltages. The frequency is measured 3-phase if the measured voltage exceeds 15% of the nominal voltage. This ensures rapid and precise measurement of the frequency. How-ever the frequency is still measured correctly even if voltage is only applied to one phase.

    Functional DescriptionsThe unit is equipped with the following functions.General functions: One ready for operation relay output (normally open contact); One additional, freely configurable relay output (change-over

    contact); Discrete input for blocking of protective functions or remote

    acknowledgment; Password system; Wide-range power supply (90 to 250 Vac/dc); and Synch-check function

    Protective functions: 3-phase over-/undervoltage monitoring

    (2 limits) V>, V< Zero voltage monitoring: dead bus start

    (close CB to dead busbar) V 0 Voltage asymmetry monitoring VAS> 3-phase over-/underfrequency monitoring

    (2 limits) f>, f