vr-300 multi function voltage protection relay im en 6 2012
DESCRIPTION
VR-300 Multi Function Voltage Protection Relay IM en 6 2012TRANSCRIPT
-
IL02602
VR-300
Reversible Display
Monitoring
Hz
3 L3 / L31 [ ]Display
Operating Alarm
Selec004E For more information visitClear
t Digit Cursor
MenuVR-300 Multi Function Voltage Protection RelayInstructional Literature
New Information
Description Page
1. General Information . . . . . . . . . . . . . . . . . . . . . . . . . . 32. Electrostatic Discharge Awareness . . . . . . . . . . . . . . . 33. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44. Functional Description . . . . . . . . . . . . . . . . . . . . . . . . 85. Display and Operating Elements . . . . . . . . . . . . . . . . . 96. Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117. Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Appendix A. Dimensions . . . . . . . . . . . . . . . . . . . . . . 22Appendix B. Technical Data . . . . . . . . . . . . . . . . . . . . 23Appendix C. Measured Quantities . . . . . . . . . . . . . . . . 24Appendix D. List of Parameters. . . . . . . . . . . . . . . . . . 25
Converting, Controlling,
L 1 / L12 L2 / L2: www.Eaton.com
-
Instructional LiteraturePage 2 Effective: July 2007 VR-300 Multi Function Voltage Protection Relay
Important Definitions
Note: Provides other helpful information that does not fall under the warn-ing or caution categories.
Eaton reserves the right to update any portion of this publication
and reliable. However, Eaton assumes no responsibility unlessotherwise expressly undertaken.
Eaton Corporation
All Rights Reserved.
Revision History
WARNINGINDICATES A POTENTIALLY HAZARDOUS SITUATION THAT, IF NOTAVOIDED, COULD RESULT IN DEATH OR SERIOUS INJURY.
CAUTIONINDICATES A POTENTIALLY HAZARDOUS SITUATION THAT, IF NOTAVOIDED, COULD RESULT IN DAMAGE TO EQUIPMENT.
REV. DATE EDITOR CHANGES
06-08-11 TPNEW Release based on 3735107-07-18 TPA New relay assignment function
starting with SW version 3.1450; cutout section added
at any time. Information provided by Eaton is believed to be correct
WARNING
CAUTION
OUT-OF-DATE PUBLICATION
READ THIS ENTIRE MANUAL AND ALL OTHER PUBLICATIONS PERTAINING TO THE WORK TO BE PERFORMED BEFORE INSTALL-ING, OPERATING, OR SERVICING THIS EQUIPMENT. PRACTICE ALL PLANT AND SAFETY INSTRUCTIONS AND PRECAUTIONS. FAILURE TO FOLLOW INSTRUCTIONS CAN CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
THE ENGINE, TURBINE, OR OTHER TYPE OF PRIME MOVER SHOULD BE EQUIPPED WITH AN OVER SPEED (OVER TEMPERA-TURE, OR OVERPRESSURE, WHERE APPLICABLE) SHUTDOWN DEVICE(S), THAT OPERATES TOTALLY INDEPENDENTLY FO THE PRIME MOVER CONTROL DEVICE(S) TO PROTECT AGAINST RUNAWAY OR DAMAGE TO THE ENGINE, TURBINE, OR OTHER TYPE OF PRIME MOVER WITH POSSIBLE PERSONAL INJURY OR LOSS OF LIFE SHOULD THE MECHANICAL-HYDRAULIC GOVERNOR(S) OR ELECTRIC CONTROL(S), THE ACTUATOR(S), FUEL CONTROL(S), THE DRIVING MECHANISM(S), THE LINKAGE(S), OR THE CONTROLLED DEVICE(S) FAIL.
ANY UNAUTHORIZED MODIFICATIONS TO OR USE OF THE EQUIPMENT OUTSIDE ITS SPECIFIED MECHANICAL, ELECTRICAL, OR OTHER OPERATING LIMITS MAY CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE, INCLUDING DAMAGE TO THE EQUIPMENT. ANY SUCH UNAUTHORIZED MODIFICATIONS: (I) CONSTITUTE MISUSE AND/OR NEGLIGENCE WITHIN THE MEANING OF THE PRODUCT WARRANTY THEREBY EXCLUDING WARRANTY COVERAGE FOR ANY RESULTING DAMAGE, AND (II) INVALIDATE PRODUCT CERTIFICATIONS OR LISTING.
TO PREVENT DAMAGE TO A CONTROL SYSTEM THAT USES AN ALTERNATOR OR BATTERY-CHARGING DEVICE, MAKE SURE THE CHARGING DEVICE IS TURNED OFF BEFORE DISCONNECTING THE BATTERY FROM THE SYSTEM
ELECTRONIC CONTROLS CONTAIN STATIC-SENSITIVE PARTS. OBSERVE THE FOLLOWING PRECAUTIONS TO PREVENT DAMAGE TO THESE PARTS.
DISCHARGE BODY STATIC BEFORE HANDLING THE CONTROL (WITH POWER TO THE CONTROL TURNED OFF, CONTACT A GROUNDED SURFACE AND MAINTAIN CONTACT WHILE HANDLING THE CONTROL).
AVOID ALL PLASTIC VINYL, AND STYROFOAM (EXCEPT ANTISTATIC VERSIONS) AROUND PRINTED CIRCUIT BOARDS.
DO NOT TOUCH THE COMPONENTS OR CONDUCTIONS ON A PRINTED CIRCUIT BOARD WITH YOUR HANDS OR WITH CONDUCTIVE DEVICES.
THIS PUBLICATION MAY HAVE BEEN REVISED OR UPDATED SINCE THIS COPY WAS PRODUCED. TO VERIFY THAT YOU HAVE THE LATEST REVISION, BE SURE TO CHECK THE EATON WEBSITE:
HTTP://WWW.EATON.COM
THE REVISION LEVEL IS SHOWN ON THE FRONT COVER AFTER THE PUBLICATION NUMBER. THE LATEST VERSION OF MOST PUBLICATIONS IS AVAILABLE AT:
HTTP://WWW.EATON.COM
IF YOU PUBLICATION IS NOT THERE, PLEASE CONTACT YOUR CUSTOMER SERVICE REPRESENTATIVE TO GET THE LATEST COPY.IL02602004EFor more information visit: www.Eaton.com
-
Instructional LiteratureEffective: July 2007 Page 3VR-300 Multi Function Voltage Protection Relay
Section 1: General InformationIntroductionThe VR-300 model is a multifunction protection unit packaged into one compact device. Typical applications are generators and switchgear equipment that require independent protection archi-tecture to implement transfer schemes.
Measurement Value LoggingVoltageVoltage is displayed as three-phase R.M.S. measurement of the phase-neutral and/or phase-phase voltages. The unit utilizes sin-gle-phase R.M.S. measurement of the synchronizing voltage VL1-L2.This device can be ordered with the following measuring voltage input ranges (rated voltages). Please indicate the measuring volt-age input required when ordering (refer to Appendix B: Technical Data on page 23): 66 V/115 V...... [1]FrequencyFrequency measurement is extracted from the digitally filtered measuring voltages. The frequency is measured 3-phase if the measured voltage exceeds 15% of the nominal voltage. This ensures rapid and precise measurement of the frequency. How-ever the frequency is still measured correctly even if voltage is only applied to one phase.
Functional DescriptionsThe unit is equipped with the following functions.General functions: One ready for operation relay output (normally open contact); One additional, freely configurable relay output (change-over
contact); Discrete input for blocking of protective functions or remote
acknowledgment; Password system; Wide-range power supply (90 to 250 Vac/dc); and Synch-check function
Protective functions: 3-phase over-/undervoltage monitoring
(2 limits) V>, V< Zero voltage monitoring: dead bus start
(close CB to dead busbar) V 0 Voltage asymmetry monitoring VAS> 3-phase over-/underfrequency monitoring
(2 limits) f>, f