7/29/2019 Voltage and frequency protection relay Argus8.pdf http://slidepdf.com/reader/full/voltage-and-frequency-protection-relay-argus8pdf 1/4 Numerical Voltage & Frequency Protection Relay -Argus 8 Numerical  Voltage & Frequency Protection Relay The Argus 8 range of numerical voltage and frequency relays have the power and flexibility of microprocessor technology, giving a wide range of settings which are supplemented by advanced features such as metering, data storage and Fibre-Optic communications. Supervisory and self-monitoring features give added confidence to the user as well as reduced maintenance and down time. A menu-based interface gives user- friendly access to relay settings, meters and operational data.  Applications Capacitor Bank Ungrounded/High impedance earthed system • AC Generators • Transmission Lines • Distribution Feeders Features Protection Over voltage (59) Under voltage (27) Neutral voltage displacement Negative sequence overvoltage (47) Over Frequency (810) Under Frequency (81U) Control • The basic 2 pole Argus 8 relay contains 7 programmable output relays, 1 of which have 1 CO contact, 1 NC contact and 5 have 1 NO contact • The basic 3 pole Argus 8 relay contains 7 programmable output relays, 3 of which have 1 CO contact and 4 have 1 NO contact. Expanded variants provides 4 extra output relays, each having 1 NO contact • The basic 2 pole Argus 8 relay contains 4 programmable digital (status) input • The basic 3 pole Argus 8 relay contains 1 programmable digital (status) input, with an additional 4 or 8, provided in expanded variants Description  ARGUS 8

Upload: ajitkalel

Post on 14-Apr-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Voltage and frequency protection relay Argus8.pdf

7/29/2019 Voltage and frequency protection relay Argus8.pdf

http://slidepdf.com/reader/full/voltage-and-frequency-protection-relay-argus8pdf 1/4

Numerical Voltage & Frequency Protection Relay -Argus 8

Numerical Voltage & Frequency Protection Relay 

The Argus 8 range of numerical voltage and frequency relays

have the power and flexibility of microprocessor technology,

giving a wide range of settings which are supplemented by

advanced features such as metering, data storage and

Fibre-Optic communications. Supervisory and self-monitoring

features give added confidence to the user as well as reduced

maintenance and down time. A menu-based interface gives user-

friendly access to relay settings, meters and operational data.

 Applications

• Capacitor Bank• Ungrounded/High impedance earthed system

• AC Generators

• Transmission Lines

• Distribution Feeders

Features

Protection• Over voltage (59)

• Under voltage (27)

• Neutral voltage displacement

• Negative sequence overvoltage (47)• Over Frequency (810)

• Under Frequency (81U)

Control• The basic 2 pole Argus 8 relay contains 7 programmable

output relays, 1 of which have 1 CO contact, 1 NC contact

and 5 have 1 NO contact

• The basic 3 pole Argus 8 relay contains 7 programmable

output relays, 3 of which have 1 CO contact and 4 have 1

NO contact. Expanded variants provides 4 extra output relays,

each having 1 NO contact

• The basic 2 pole Argus 8 relay contains 4 programmable

digital (status) input

• The basic 3 pole Argus 8 relay contains 1 programmable

digital (status) input, with an additional 4 or 8, provided in

expanded variants

Description

 ARGUS 8

Page 2: Voltage and frequency protection relay Argus8.pdf

7/29/2019 Voltage and frequency protection relay Argus8.pdf

http://slidepdf.com/reader/full/voltage-and-frequency-protection-relay-argus8pdf 2/4

Monitoring

• Trip circuit supervision (95)• Storage of 500 time-tagged event records

• Storage of 5 multiple waveforms and status records

• Records upto 10 faults

Metering• Primary RMS voltages

• Secondary RMS voltages

• Secondary RMS sequence voltages

• System frequency

User Interface

• User-friendly settings and indications

• Backlit liquid crystal alpha-numeric display with16-characters,2 lines

• LEDs for protection healthy, trip and starting

• Push buttons for programming and resetting

Communication

• Fibre-Optic or RS485 communication port at rear 

• Data communication using IEC 60870-5-103 or MODBUS

RTU protocol

Wiring Diagram

Notes

1) Diagram shows 2ph-ph connections. See below for 

alternative connection.

2) Diagram shows ph-E+ 3Vo connections.

3) Diagram shows ph-ph+3Vo connection.

4) For the Phase-Phase of Phase-Earth connections, any

phasing may be used.

Page 3: Voltage and frequency protection relay Argus8.pdf

7/29/2019 Voltage and frequency protection relay Argus8.pdf

http://slidepdf.com/reader/full/voltage-and-frequency-protection-relay-argus8pdf 3/4

Technical Information

Input Rating AC Voltage 63.5 / 110V AC, 50 / 60Hz

Settings Voltage 1,2,3,4 5V to 200V ∆ 0.5V Definite time delay 0sec to 20s ∆ 0.01sec

20sec to 100s ∆ 0.5sec100sec to 600s ∆ 1.0sec

Output phases Any 1 or all phasesNegative sequence 1V to 100V ∆ 0.5V overvoltage 1, 2Definite time delay 0sec to 20sec ∆ 0.01sec

0sec to 100sec ∆ 0.5sec100sec to 600sec ∆ 1.0sec

Neutral voltage 1V to 100V  ∆ 0.5V displacement 1,2Definite time delay 0sec to 20sec ∆ 0.01sec

20sec to 100sec ∆ 0.5sec100sec to 600sec ∆ 1.0sec

Frequency 1,2,3,4 47Hz to 62Hz. 0.01HzDefinite time delay 0sec to 20sec ∆ 0.01sec

20sec to 100sec ∆ 0.5sec100sec to 600sec ∆ 1.0sec

DC Auxiliary Supply Nominal Operating range

24, 30, 48 V 18-60 V  110, 220 V 85-280 V  

Output relays

• The basic 2 pole Argus 8 relay contains 7 programmable

output relays, 1 of which have 1 CO contact, 1 NC contact

and 5 have 1 NO contact

• The basic 3 pole Argus 8 relay contains 7 programmable

output relays, 3 of which have 1 CO contact and 4 have

1 NO contact. Expanded variants provides 4 extra output

relays, each having 1 NO contact

Contact ratings

Carry continuously 5A AC RMS or DCMake and carry 30A AC or DC for 0.2secBreak 75W DC resistive

1250VA AC resistive

DC Digital (status) inputs

• The basic 2 pole Argus 8 relay contains 4 programmabledigital (status) input

• The basic 3 pole Argus 8 relay contains 1 programmable

digital (status) input, with an additional 4 or 8, provided in

expanded variants

 Auxiliary voltage Operating range

30V DC 18-37.5V DC

48V DC 37.5- 60V DC

110/125V DC 87.5-137.5V DC

220/250V DC 175 - 280V DC

For relay with 110/125V DC or 220/225V DC auxiliaryvoltage, a 48 voltage input is supplied for use with externaldropper resistors: 110/125V resistor 2K7 ± 5% 2.5W220/250V resistor 8K2 ± 5% 6.0W

Indications

User-friendly settings and indications

LCD Alphanumeric display for settings,instruments and fault data

EnvironmentalTemperature IEC 68-2-1/2Operating range -10°C to +55°CStorage range -25°C to +70°CHumidity IEC 68-2-356 days at 40°C and 93% relative humidity

 Vibration IEC 255-21-1 class IShock and bump IEC 255-21-2 class ISeismic IEC 255-21-3 class IInsulation IEC 255-52KVrms for 1 minute between all terminals and earth.2KVrms for 1 minute between independent circuits.1KVrms for 1 minute across NO contacts.Transient overvoltage IEC 255-4 class III5KV 1.2/50µs between all terminals and earth withoutdamage or flashover High frequency disturbance IEC 255-22-1 class III2.5KV common mode < 3% deviation1.0KV series mode < 3% deviationElectrostatic discharge IEC 255-22-2 class III

8KV direct without maloperation or damageRadio frequency IEC 255-22-3disturbance20MHz to 1GHz at 10V/m < 5% deviationFast transient IEC 255-22-4 class IV  4KV 5/50ns < 3% deviation

Mechanical ClassificationDurability 106 operations

Page 4: Voltage and frequency protection relay Argus8.pdf

7/29/2019 Voltage and frequency protection relay Argus8.pdf

http://slidepdf.com/reader/full/voltage-and-frequency-protection-relay-argus8pdf 4/4

Cutout Details

• Two or three pole• Protection requirement (ie voltage or voltage and

frequency)• Auxiliary digital (status) input voltages• No. of output contact and digital (status) input on three pole

versions

ISO 9001 - 2000

Case Weight

 Argus 8 - E4

3.3 kg Argus 8 - E6 4.8 kg

Ordering Information

Qualification

SIZE 4 CASE SIZE 6 CASE

 A B C A B C

103 99. 5 5 2 155 1 51 1 03. 5

MODULAR CASES: SIZES 4-6

    F    A    C    T    /    A    R    G    U    S

    8    /    1    2  -

    0    5    /    R   e   v

    0

The policy of Easun Reyrolle is one of continuous improvement and development. The company therefore reserves the right to supply equipment, which

may differ slightly from that described and illustrated in this publication.

 AUTOMATION DIVISION

“Ashirwad”, #25, 29th Main,4th B Cross, BTM Layout 2nd Stage,Bangalore-560 076, India.Tel: +91 80 26685496/51311405Fax: +91 80 26685446Email: [email protected]

HOSUR WORKS#98, Sipcot Industrial Complex,Hosur 635 126, India.Tel: +91 4344 401600/01/02Fax: +91 4344 276397

SWITCHGEAR WORKS

Ernavur,Chennai-600 057, India.Tel: +91 44 25733715/358Fax: +91 44 25733468Email: [email protected]

BANGALORE WORKS#17/3 Arakere,Bannerghatta Road,Bangalore-560 076, India.Tel: +91 80 26581023 / 3268Fax: +91 80 26580642Email: [email protected]

EXPORTS DIVISION

#17/3 Arakere,Bannerghatta Road,Bangalore-560 076, India.Tel: +91 80 26581023 / 3268Fax: +91 80 26580642Email: [email protected]

Sales OfficesMumbaiTel: +91 22 22022270/22855415Fax: +91 22 22825703Email: [email protected]

BangaloreTel: +91 80 26685496/51311405Fax: +91 22 26685446Email: [email protected]

BhopalTelefax: +91 755 2684221Email: [email protected]

DelhiTel: +91 11 25747321/25747322Fax: +91 11 25747320Email: [email protected]

ChennaiTel: +91 44 24346425/24347608Fax: +91 44 24346435Email: [email protected]

SecunderabadTelefax: +91 40 27817847Email: [email protected]

KolkataTel: +91 33 22848320Fax: +91 33 22848326Email: [email protected]

Corporate Office

Easun Reyrolle Limited. 98 Sipcot Industrial Complex Hosur 635 126 India. Tel: +91 4344 401600/01/02Fax: +91 4344 276397

www.easunreyrolle.com