Page 1: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings

Verification Manual

Page 2: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 2

Page 3: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

1Timber Tech srl

TABLE OF CONTENTS

TABLE OF CONTENTS .................................................................................................................... 1

INTRODUCTION .............................................................................................................................. 3

EXAMPLE 1: CALCULATION OF THE FLOOR SELF WEIGHT G1 ................................................. 5

E XAMPLE 2: CALCULATION OF THE BEAM SELF WEIGHT G1 ................................................. 7

EXAMPLE 3: CALCULATION OF THE SNOW LOAD ...................................................................... 9

EXAMPLE 4: CALCULATION OF THE WIND LOAD ..................................................................... 11

EXAMPLE 5: BEAM’S INERTIA PROPERTIES ............................................................................. 15

EXAMPLE 6: PILLAR’S INERTIA PROPERTIES ........................................................................... 17

EXAMPLE 7: FLOOR LOAD ........................................................................................................... 19

EXAMPLE 8: CALCULATION OF FLOOR FORCES ..................................................................... 21

EXAMPLE 9: FLOOR RESISTANCE CHECKS .............................................................................. 24

EXAMPLE 10: BEAM LOAD ........................................................................................................... 27

EXAMPLE 11: CALCULATION OF BEAM FORCES ...................................................................... 29

EXAMPLE 12: RESISTANCE CHECKS OF THE TIMBER BEAM ................................................. 33

EXAMPLE 13: RESISTANCE CHECKS OF THE STEEL BEAM ................................................... 37

EXAMPLE 14: DEFLECTION CHECK OF TIMBER BEAM ............................................................ 40

EXAMPLE 15: AXIAL FORCE IN THE PILLAR .............................................................................. 44

EXAMPLE 16: STABILITY CHECK IN A TIMBER PILLAR ............................................................ 46

EXAMPLE 17: STABILITY CHECK IN A STEEL PILLAR ............................................................... 50

EXAMPLE 18: VERTICAL LOAD ON THE WALL .......................................................................... 54

EXAMPLE 19: WIND LOAD ON THE WALL .................................................................................. 57

EXAMPLE 20: STABILITY CHECK OF THE WALL ....................................................................... 59

EXAMPLE 21: ORTHOGONAL COMPRESSION CHECK ............................................................. 63

EXAMPLE 22: CONNECTOR STRENGTH FRAME-PANEL.......................................................... 66

EXAMPLE 23: CONNECTOR STRENGTH IN A CLT JOINTED WALL ......................................... 71

EXAMPLE 24: MODAL ANALYSIS ................................................................................................. 76

Page 4: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 2

Page 5: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

3Timber Tech srl

INTRODUCTION

This verification manual provides solved and commented test cases with reference to the input file

necessary to reproduce the elaboration.

Page 6: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 4

Page 7: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

5Timber Tech srl

EXAMPLE 1: CALCULATION OF THE FLOOR SELF WEIGHT G1

File name: EsempioValidazione.bldg

DESCRIPTION OF THE PROBLEM

The self weight per unit area of the joists floor is the weight of the joists included in a unit area.

The comparison between the value provided by the software and that obtained with a hand

calculating is conducted assuming:

Joist cross section: 160 200mm

Volumetric weight : 6kN/m

Spacing : 500mm

INDEPENDENT VERIFICATION

Calculation of the joist cross section area:

∙ 160 200 32000mm 32 10 m

Calculation of the linear weight per unit length for the joist:

∙ 32 10 6 0,192KN/m

Calculation of the weight per unit area:

∙ 0,1920,5

0,38KN/m

Page 8: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 6

RESULTS PROVIDED BY THE SOFTWARE

Self-weight of the floor : 0,38kN/m

RESULTS COMPARISON

Comparison between the value provided by the software and the hand-calculating value:

Validated parameter

Independent verification

Software Percentage error

, 0,38KN/m 0,38 KN/m 0%

CONCLUSIONS

The comparison shows the coincidence between the value provided by the software and that hand-

calculated.

Page 9: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

7Timber Tech srl

E XAMPLE 2: CALCULATION OF THE BEAM SELF WEIGHT G1

File name: EsempioValidazione.bldg

DESCRIPTION OF THE PROBLEM

The comparison between the value of the beam self weight provided by the software and that

obtained independently is conducted assuming:

Cross section of the beam: 160 240mm

Volumetric weight : 6kN/m

INDEPENDENT VERIFICATION

Calculation of the beam cross section area:

∙ 160 240 38400mm 38,4 10 m

Calculation of the beam linear weight:

∙ 38,4 10 6 0,23KN/m

RESULTS PROVIDED BY THE SOFTWARE

Self-weight of the beam : 0,23kN/m

Page 10: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 8

RESULTS COMPARISON

Comparison between the value provided by the software and the hand-calculating value:

Validated parameter

Independent verification

Software Percentage error

, 0,23KN/m 0,23 KN/m 0%

CONCLUSIONS

The comparison shows the coincidence between the value provided by the software and that hand-

calculated.

Page 11: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

9Timber Tech srl

EXAMPLE 3: CALCULATION OF THE SNOW LOAD

File name: EsempioValidazione.bldg

DESCRIPTION OF THE PROBLEM

The calculation of the snow load on the roof is been made with reference to the dispositions

provided by the Italian Standard D.M.14-01-2008, assuming:

Building position: Trento

Altitude m.a.s.l.: 193 m

Snow load zone: Zona I – Alpina

Topographic class: Normale

Exposure factor: 1

Thermal coefficient: 1

INDEPENDENT VERIFICATION

The load caused by snow on roof is assessed by the equation:

⋅ ⋅ ⋅

where:

is the shape coefficient of the roof equal to 0,8 in the case of flat roof

is the characteristic value of the reference snow load on the ground

Page 12: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 10

For locations belonging to Zone I – Alpina and for heigth above sea level less than 200m,

takes the value of 1,5.

Load assumes the value:

⋅ ⋅ ⋅ 0,8 1,5 1 1 1,2kN/m

RESULTS PROVIDED BY THE SOFTWARE

1,2kN/m

RESULTS COMPARISON

Comparison between the value provided by the software and the value calculated in an

independent manner:

Validated parameter

Independent verification

Software Percentage error

1,2 kN 1,2 kN 0%

CONCLUSIONS

The comparison shows the coincidence between the value provided by the software and that hand-

calculated.

Page 13: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

11Timber Tech srl

EXAMPLE 4: CALCULATION OF THE WIND LOAD

File name: EsempioValidazione.bldg

DESCRIPTION OF THE PROBLEM

The calculation of the snow load on the roof is been made with reference to the dispositions

provided by the Italian standard D.M.14-01-2008, assuming:

Province: Trento

Altitude m.a.s.l.: 193 m

Wind load zone: Zone 1

Roughness class: Class A

Distance from the coast: Hinterland

Exposure category: V

Airtight construction

INDEPENDENT VERIFICATION

The wind is considered to act in the horizontal direction and exerts actions on structures that vary

in time and space, usually causing dynamic effects. For the usual constructions, actions are

conventionally traced to the equivalent static actions. The wind pressure is given by the

expression:

⋅ ⋅ ⋅

where:

Page 14: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 12

is the kinetics reference pressure

is the exposure factor

is the shape factor

is the dynamic factor

KINETICS PRESSURE

The kinetics reference pressure (in N/m²) is given by:

12⋅ ⋅

where:

is the density of the air assumed equal to 1,25 kg/m3

is the reference velocity (in m/s)

In the absence of specific and appropriate statistics investigations is given by:

, for as ≤ a0

, ⋅ for a0 < as ≤ 1500 m

in which , , , are parameters provided and depending on the building’s region:

is the altitude a.s.l. (in m)

, 25m/s

1000m

0,0101/s

Since as ≤ a0, the reference velocity is equal to 25,00m/s. The kinetics reference pressure

assumes the value:

12⋅ ⋅

12

1,25 25 390,63N/m

EXPOSURE FACTOR

The exposure factor depends on the heigth z on the ground of the considered point, on the

topography of the land, and on the exposure category of the construction’s site. In absence of

specific analyzes that take into account the wind direction, the effective roughness and the

topography of the land surrounding the building for heigths on ground not greater than z 200m,

the exposure factor is given by the equation:

⋅ ⋅ ln ⋅ 7 ⋅ ln for z ≥ zmin

per z<zmin

Page 15: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

13Timber Tech srl

in which

is the topography factor.

The heigth on ground for the category exposure V is 12m, and, being the heigth of the

building equal to 2,8m, the exposure factor is:

12 0,23 ⋅ 1 ⋅ ln12,00,7

⋅ 7 1 ⋅ ln12,00,7

1,479

SHAPE FACTOR

The shape factor (or aerodynamic coefficient) is a function of the typology and the geometry of the

building and depends on its orientation respect to the wind direction. The value of the external

shape factor can be assessed by the diagram shown in the following figure:

The internal exposure factor is zero value if the construction is airtight while it takes the values

± 0.2 if it is open. Based on the assumptions made, the exposure factor assumes zero value.

Element

Windward wall 90 0,8

Leeward wall 90 0,4

Leeward pitched roof - 0,4

Windward pitched roof 0° 0 0,4

Page 16: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 14

WIND PRESSURE

The wind pressure, calculated with reference to the two values of reported in the table above,

takes the following values:

⋅ ⋅ ⋅ 390,63 1,479 0,8 1 0,46kN/m

⋅ ⋅ ⋅ 390,63 1,479 0,4 1 0,23kN/m

RESULTS PROVIDED BY THE SOFTWARE

0,46kN/m

0,23kN/m

RESULTS COMPARISON

Comparison between the value provided by the software and the value calculated in an

independent manner:

Validated parameter

Independent verification

Software Percentage error

0,46kN/m 0,46 kN/m 0%

0,23 kN/m 0,23 kN/m 0%

CONCLUSIONS

The comparison shows the coincidence between the value provided by the software and that hand-

calculated.

Page 17: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

15Timber Tech srl

EXAMPLE 5: BEAM’S INERTIA PROPERTIES

File name: EsempioValidazione.bldg

DESCRIPTION OF THE PROBLEM

Inertia properties of the beam cross-section are the following:

Cross section area ;

Moment of inertia refers to axis y-y

Moment of inertia refers to axis z-z

The comparison between the values provided by the software and those obtained independently is

conducted assuming:

Cross section of the beam: 160 240mm

INDEPENDENT VERIFICATION

Calculation of the beam cross section area:

∙ 160 240 38400mm 38,4 10 m

Calculation of the inertia moment :

∙12

160 24012

1,84 10 mm

Calculation of the inertia moment :

Page 18: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 16

∙12

160 24012

8,19 10 mm

RESULTS PROVIDED BY THE SOFTWARE

Area A: 38400mm

Moment of inertia Jy-y: 1,84 10 mm

Moment of inertia Jz-z: 8,19 10 mm

RESULTS COMPARISON

Comparison between the value provided by the software and the value calculated in an

independent manner:

Validated parameter

Independent verification

Software Percentage error

A 38,4 10 mm 38,4 10 mm 0%

Jy-y 1,84 10 mm 1,84 10 mm 0%

Jz-z 8,19 10 mm 8,19 10 mm 0%

CONCLUSIONS

The comparison shows the coincidence between the value provided by the software and that hand-

calculated.

Page 19: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

17Timber Tech srl

EXAMPLE 6: PILLAR’S INERTIA PROPERTIES

File name: EsempioValidazione.bldg

DESCRIPTION OF THE PROBLEM

Inertia properties of the pillar cross-section are the following:

Cross section area ;

Moment of inertia refers to axis y-y

Moment of inertia refers to axis z-z

The comparison between the values provided by the software and those obtained independently is

conducted assuming:

Cross section of the beam: 200 200mm

INDEPENDENT VERIFICATION

Calculation of the pillar cross section area:

200 40000 40 10 m

Calculation of the inertia moment Jy-y:

1220012

1,33 10 mm

RESULTS PROVIDED BY THE SOFTWARE

Area : 40000mm

Page 20: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 18

Moment of inertia : 1,33 10 mm

Moment of inertia : 1,33 10 mm

RESULTS COMPARISON

Comparison between the value provided by the software and the value calculated in an

independent manner:

Validated parameter

Independent verification

Software Percentage error

A 40 10 mm 40 10 mm 0%

Jy-y 1,33 10 mm 1,33 10 mm 0%

Jz-z 1,33 10 mm 1,33 10 mm 0%

CONCLUSIONS

The comparison shows the coincidence between the value provided by the software and that hand-

calculated.

Page 21: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

19Timber Tech srl

EXAMPLE 7: FLOOR LOAD

File name: EsempioValidazione.bldg

DESCRIPTION OF THE PROBLEM

The calculation of the distributed load on the generic joist floor qSLU is conducted with reference to

the following ultimate limit load combination:

Load G1 G2 Live load

cat. H Snow Wind

Partial factors 1,3 1,5 1,5 0 0

Assuming:

Floor self weight : 0,38kN/m

Permanent load : 2,00kN/m

Live load cat. H : 0,50kN/m

Spacing between joists : 500mm

INDEPENDENT VERIFICATION

The distribuited load per unit length results:

1,3 ∙ 1,5 ∙ 1,5 ∙ ∙ 1,3 0,38 1,5 2,00 1,5 0,5 0,5 2,12kN/m

RESULTS PROVIDED BY THE SOFTWARE

: 2,12kN/m

Page 22: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 20

RESULTS COMPARISON

Comparison between the value provided by the software and the value calculated in an

independent manner:

Validated parameter

Independent verification

Software Percentage error

2,12kN/m 2,12 kN/m 0%

CONCLUSIONS

The comparison shows the coincidence between the value provided by the software and that hand-

calculated.

Page 23: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

21Timber Tech srl

EXAMPLE 8: CALCULATION OF FLOOR FORCES

File name: EsempioValidazione.bldg

DESCRIPTION OF THE PROBLEM

The calculation of the forces on the generic joist floor is conducted with reference to a span equal

to 5 , assuming:

2,12kN/m

VERIFICATION

Assuming that the joist can be considered simply supported at the ends, the reactions at the ends

of the joist are:

∙2

2,12 ∙ 52

5,3kN

The shear force at the ends of the joist is equal to restraint reactions:

5,3kN

5,3kN

The bending moment at the midpoint of the joist is:

∙8

2,12 ∙ 58

6,62kNm

Page 24: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 22

RESULTS PROVIDED BY THE SOFTWARE

Restraint reactions: 5,29kN

Shear force A: 5,29kN

Shear force B: -5,28kN

Maximum bending moment: 6,64kNm

RESULTS COMPARISON

Validated parameter

Independent verification

Software Percentage error

, 5,30 kN 5,29 kN 0,2%

5,30 kN 5,29 kN 0,2%

5,30 kN 5,28 kN 0,4%

6,62 kNm 6,64 kNm 0,3%

Page 25: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

23Timber Tech srl

CONCLUSIONS

The comparison shows how results provided by the software are comparable to results obtained

with an independent verification. Errors are caused by different approximation between the manual

verification and the software.

Page 26: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 24

EXAMPLE 9: FLOOR RESISTANCE CHECKS

File name: EsempioValidazione.bldg

DESCRIPTION OF THE PROBLEM

The resistance checks (bending and shear) are conducted with reference to the dispositions

provided by UNI EN 1995-1-1:2009 al § 6.3.3, assuming:

Joist cross section : 160 200mm

Material: solid timber C24

Bending moment: 6,64kNm

Shear force 5,29kNm

INDEPENDENT VERIFICATION

The area A and the modulus of resistance W are equal to:

∙ 160 200 32000mm

∙6

160 2006

1,067 10 mm

BENDING CHECK

The checks are conducted according to § 6.3.2 of EN 1995-1-1. The following expression shall be satisfied:

,

⋅ ,1

Page 27: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

25Timber Tech srl

where:

, is the design bending stress

, is the design bending strength

is a factor which takes into account the reduced bending strength due to lateral

buckling

kcrit is assumed equal to 1.0 for beams in which the lateral displacement of the compressed edge is

prevented over the entire length and the torsional rotation is prevented at the supports.

The design bending stress assumes the value:

,6,64 101,067 10

6,22MPa

The solid timber C24 presents a characteristic value of the bending strength , equal to:

, 24MPa

Assuming that the bending moment is calculated with a load combination in which the snow is

the load of short duration, the factor assumes the value equal to 0.9, and the design bending

strenght is equal to:

,⋅ , 0,8 ⋅ 24

1,512,80MPa

The bending check is satisfied, obtaining:

,

,

6,2212,80

48,59%

SHEAR CHECK

The checks are conducted according to § 6.1.7 of EN 1995-1-1. The following expression shall be satisfied:

,1

where:

is the design shear stress

, is the design shear strength for the actual condition

For the verification of shear resistance of members in bending, the influence of cracks should be

taken into account using an effective width of the member given as:

For solid timber kcrit is equal to 0,67.

Page 28: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 26

The maximum design shear stress in a rectangular cross section can be evaluated using the following expression:

32⋅

⋅32

5,29 100,67 32 10

0,37MPa

The solid timber C24 presents a characteristic value of shear strenght , equal to:

, 4MPa

The design shear strength is:

,⋅ , 0,8 4

1,52,13MPa

The shear check is satisfied, obtaining:

,

0,372,13

17,37%

RESULTS PROVIDED BY THE SOFTWARE

Bending check: 48,67%

Shear check: 17,36%

RESULTS COMPARISON

Comparison between the value provided by the software and the value calculated in an

independent manner:

Validated parameter

Independent verification

Software

Bending check 48,59% 49%

Shear check 17,37% 17%

CONCLUSIONS

The comparison shows how results provided by the software are comparable to results obtained

with an independent verification. Errors are caused by different approximation between the manual

verification and the software.

Page 29: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

27Timber Tech srl

EXAMPLE 10: BEAM LOAD

File name: EsempioValidazione.bldg

DESCRIPTION OF THE PROBLEM

The calculation of the distributed load on the two spans beam qSLU is conducted with reference to

the following ultimate limit load combination:

Load G1 G2 Live load

cat. H Snow Wind

Partial factors 1,3 1,5 1,5 0 0

Assuming:

Floor self weight : 0,38kN/m

Permanent load : 2,00kN/m

Live load cat. H : 0,50kN/m

Spacing joists : 500mm

Floor span : 5m

Beam self weight , : 0,23kN/m

INDEPENDENT VERIFICATION

The restraint reaction of the generic joist results:

1,3 ∙ 1,5 ∙ 1,5 ∙ ∙ ∙2

1,3 0,38 1,5 2,00 1,5 0,5 0,5 2,5 5,30kN

Page 30: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 28

The distributed load per meter acting on the beam is calculated by adding to the reaction of

the joist, redistributed along the spacing of the joists, the weight per meter of the beam multiplied

by the appropriate partial factor :

1,3 ∙ ,5,300,50

1,3 0,23 10,91kN

RESULTS PROVIDED BY THE SOFTWARE

: 10,92 /

RESULTS COMPARISON

Comparison between the value provided by the software and the value calculated in an

independent manner:

Validated parameter

Independent verification

Software Percentage error

10,91 kN/m 10,92 kN/m 0,01%

CONCLUSIONS

The comparison shows the coincidence between the value provided by the software and that hand-

calculated.

Page 31: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

29Timber Tech srl

EXAMPLE 11: CALCULATION OF BEAM FORCES

File name: EsempioValidazione.bldg

DESCRIPTION OF THE PROBLEM

In the example we consider a beam consisting of two equal spans (each one has a length of 2 m).

The maximum values of the forces in the beam are determined considering various configurations

with alternated loads. In this example we consider the following load combinations.

Load G1 G2 Live load

cat. H Snow Wind

1,3 1,5 1,5 0 0

1 0 0 0 0

The distributed loads e assume the values:

10,96kN/m

1,18kN/m

INDEPENDENT VERIFICATION

Configuration 1/2 (maximum moment in span)

Page 32: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 30

Given the symmetry of the beam, it is sufficient to solve the beam with reference to one of the two

load configurations.

Bending moment: the moment on the support and the maximum span moment assume

the values:

0

∙ ∙8 ⋅

10,96 2 1,18 28 ⋅ 2 2

3,04kNm

,∙

8 2⋅

⋅1

10,96 28

3,042

3,0410,96 ⋅ 2

1 4,07kNm

Reaction forces: the reaction forces assume the values:

⋅2

10,96 22

3,042

9,44kN

∙2

∙2

⋅1 1

10,96 22

1,19 22

3,0412

12

12,91kN

⋅2

1,19 22

3,042

0,33kN

Shear: the shear localised at the end supports is equal to reaction forces while the left and

right shear of the central support assumes the values:

, ∙ 9,44 10,96 2 12,48

, ∙ 0,33 1,19 2 2,05

Configuration 3 (maximum moment on the central support)

Reaction forces: the reaction forces assume the values:

0,375 ∙ ∙ 0,375 10,96 2 8,22kN/m

1,25 ∙ ∙ 1,25 10,96 2 27,40kN/m

Shear: the shear localised at the end supports is equal to reaction forces while the left and

right shear of the central support assumes the values:

, 0,625 ∙ ∙ 0,625 10,96 2 13,70kN

, 0,625 ∙ ∙ 0,625 10,96 2 13,70kN

Page 33: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

31Timber Tech srl

Bending moment: the moment on the support and the maximum span moment assume

the values:

0

18∙ ∙

18

10,96 2 5,48kNm

,1

14,3∙ ∙

114,3

10,96 2 3,07kNm

RESULTS PROVIDED BY THE SOFTWARE

Maximum positive shear on A support: 9,29kN

Maximum negative shear on A support: 0,34kN

Maximum positive shear on B support: 13,53kN

Maximum negative shear on B support: 13,53kN

Maximum span moment: 4,05kNm

Maximum moment on B support: 5,46kNm

Page 34: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 32

RESULTS COMPARISON

Comparison between the values provided by the software and the values calculated in an

independent manner:

Validated parameter

Independent verification

Software Percentage error

, 9,44 kN 9,29 kN 1,6%

, 0,33 kN 0,34 kN -3%

, 13,70 kN 13,53 kN -1,2%

, 13,70 kN 13,53 kN 1,2%

, 4,07 kNm 4,05 kNm 0,5%

, 5,48 kNm 5,46 kNm 0,4%

CONCLUSIONS

The comparison shows how results provided by the software are comparable to results obtained

with an independent verification. Errors are caused by different approximation between the manual

verification and the software.

Page 35: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

33Timber Tech srl

EXAMPLE 12: RESISTANCE CHECKS OF THE TIMBER BEAM

File name: EsempioValidazione.bldg

DESCRIPTION OF THE PROBLEM

The resistance checks (bending and shear) are conducted with reference to the dispositions

provided by UNI EN 1995-1-1:2009 al § 6.3.3, assuming:

Beam cross section : 160 240mm

Material: homogenous glulam timber GL28h

Bending moment: 5,48kNm

INDEPENDENT VERIFICATION

The area A and the modulus of resistance W are equal to:

∙ 160 240 38400mm

∙6

160 2406

1,536 10 mm

BENDING CHECK

The checks are conducted according to § 6.3.2 of EN 1995-1-1. The following expression shall be satisfied:

,

⋅ ,1

where:

, is the design bending stress

, is the design bending strength

Page 36: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 34

is a factor which takes into account the reduced bending strength due to lateral

buckling

kcrit is assumed equal to 1.0 for beams in which the lateral displacement of the compressed edge is

prevented over the entire length and the torsional rotation is prevented at the supports.

The design bending stress assumes the value:

,5,46 101,536 10

3,55MPa

The glulam timber GL28h presents a characteristic value of the bending strength , equal to:

, 28MPa

Assuming that the bending moment is calculated with a load combination in which the snow is

the load of short duration, the factor assumes the value equal to 0.9, and the design bending

strenght is equal to:

,⋅ , 0,8 28

1,4515,45MPa

The bending check is satisfied, obtaining:

,

,

3,5515,45

22,98%

SHEAR CHECK

The checks are conducted according to § 6.1.7 of EN 1995-1-1. The following expression shall be satisfied:

,1

where:

is the design shear stress

, is the design shear strength for the actual condition

For the verification of shear resistance of members in bending, the influence of cracks should be

taken into account using an effective width of the member given as:

For glulam timber kcrit is equal to 0,67.

The maximum design shear stress in a rectangular cross section can be evaluated using the

following expression:

32⋅

⋅32

13,59 100,67 38,4 10

0,79MPa

Page 37: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

35Timber Tech srl

The solid timber GL28h presents a characteristic value of shear strenght , equal to:

, 3,5MPa

The design shear strength is:

,⋅ , 0,8 ⋅ 3,5

1,451,77MPa

The shear check is satisfied, obtaining:

,

0,791,93

40,93%

RESULTS PROVIDED BY THE SOFTWARE

Bending check: 23%

Shear check: 41%

RESULTS COMPARISON

Comparison between the values provided by the software and the values calculated in an

independent manner:

Validated parameter

Independent verification

Software

Bending check 22,98% 23%

Shear check 40,93% 41%

CONCLUSIONS

Page 38: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 36

The comparison shows how results provided by the software are comparable to results obtained

with an independent verification. Errors are caused by different approximation between the manual

verification and the software.

Page 39: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

37Timber Tech srl

EXAMPLE 13: RESISTANCE CHECKS OF THE STEEL BEAM

File name: EsempioValidazioneAcciaio.bldg

DESCRIPTION OF THE PROBLEM

The resistance checks (bending and shear) are conducted with reference to the dispositions

provided by UNI EN 1993-1-1:2009 al § 6.2., assuming:

Beam profile IPE 100, Class 1

Material: steel S235 EN 10025 -2

Maximum bending moment: 6,67kNm

Maximum shear: 16,55kN

INDEPENDENT VERIFICATION

In this example we do the bending and shear checks for element “Beam 6”.

When the shear force is less than half the plastic shear resistance , its effect on the

moment resistance may be neglected.

0.5 ,

Otherwise the reduced moment resistance should be taken as the design resistance of the cross-

section, calculated using a reduced yield strength for the shear area :

1

where:

2

,1

Page 40: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 38

The reduced design plastic resistance moment allowing for the shear force may alternatively be

obtained for I-cross-sections (class 1 or 2) with equal flanges and bending about the major axis as

follows:

, ,

,∙4

,

In this case the design plastic resistance shear is equal to:

,⋅

√3 ∙65,64

is the shear area equal to 5,08 mm² for a profile IPE100;

is the charateristic yield strenght equal to 235 MPa;

is the partial safety factor for the resistance of cross-section equal to 1,05.

In this example the design shear force is lower than 0,5 , and therefore the design moment

resistance is:

,, 8,82

where:

, is the plastic section modulus

The bending check results:

,

6,678,82

75,62%

The shear check results:

,

16,5565,64

25,21%

RESULTS PROVIDED BY THE SOFTWARE

Bending check 76 %

Shear check: 25%

Page 41: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

39Timber Tech srl

RESULTS COMPARISON

Comparison between the value provided by the software and the value calculated in an

independent manner:

Validated parameter

Independent verification

Software

Bending check 75,62 % 76 %

Shear check 25,21% 25%

CONCLUSIONS

The comparison shows how results provided by the software are comparable to results obtained

with an independent verification.

Page 42: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 40

EXAMPLE 14: DEFLECTION CHECK OF TIMBER BEAM

File name: EsempioValidazione.bldg

DESCRIPTION OF THE PROBLEM

The deflection checks are conducted with reference to the dispositions provided by UNI EN 1995-

1-1:2009 al § 2.2.3, considering a symmetrical beam with 2 spans, assuming:

Cross section of the beam : 160 240mm

Spans length: 2

Material: homogenous glulam timber GL28h

Load q under the combination SLE rare (1): 6,43kN/m

The code orders that we have to do a check for the instantaneous deflection and another one for

the final deflection (considering the creep deflection).

The net deflection below a straight line between the supports, wnet,fin, is taken as:

,

where:

, is the net final deflection

is the instantaneous deflection

is the creep deflection

is the precamber (if applied)

Page 43: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

41Timber Tech srl

is the final deflection

INDEPENDENT VERIFICATION

CALCULATION OF THE INSTANTANEOUS AND THE FINAL DEFLECTION

The inertia moment Jy-y of the cross section is:

∙12

160 24012

1,84 10 mm

The deflection of a single span can be evaluated considering the fact that, in the present case,

there is a symmetry of geometry, load and constraints. Therefore, the single span can be

assimilated to a beam simply supported on one end and fixed on the other end.

So the maximum deflection is given by:

,2384

⋅⋅

, ⋅2384

6,43 10 21,26 10 1,8432 10

0,23mm

For structures consisting of members, components and connections with the same creep

behaviour and under the assumption of a linear relationship between the actions and the

corresponding deformations the final deformation, wfin, may be taken as:

, , ,

where:

, , ⋅ 1 for a permanent action, G

, , , , ⋅ 1 Ψ , ⋅ for the leading variable action, Q1

, , , , ⋅ Ψ , Ψ , ⋅ for accompanying variable actions, Qi (i>1)

In this case we have:

, 023 ⋅ 1 0,6 0,37mm

Page 44: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 42

The limiting values for deflections are assumed as shown in the following table.

winst wnet,fin

Beam on two supports

l/300 l/250

Cantilevering beams

l/150 l/125

CHECK OF INSTANTANEOUS DEFLECTION

The maximum value for the instantaneous deflection results:

, 3002000300

6,67mm

The check is satisfied:

,

0,236,67

3,45%

CHECK OF FINAL DEFLECTION

The maximum value for the final deflection results:

, 2502000250

8,00mm

The check is satisfied:

,

0,378,00

4,62%

RESULTS PROVIDED BY THE SOFTWARE

Instantaneous deflection: 0,23mm

Final deflection: 0,37mm

Check of instantaneous deflection: 3%

Check of final deflection: 5%

Page 45: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

43Timber Tech srl

RESULTS COMPARISON

Comparison between the values provided by the software and the values calculated in an

independent manner:

Validated parameter

Independent verification

Software Percentage error

0,23 mm 0,23 mm 0%

0,37 mm 0,37 mm 0%

Check 3,45% 3%

Check 4,62% 5%

CONCLUSIONS

The comparison shows how results provided by the software are comparable to results obtained

with an independent verification.

Page 46: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 44

EXAMPLE 15: AXIAL FORCE IN THE PILLAR

File name: EsempioValidazione.bldg

DESCRIPTION OF THE PROBLEM

The calculation of the axial force NSLU in the pillar is conducted with reference to the following

ultimate limit load combination:

Load G1 G2 Live load

cat. H Snow Wind

Partial factors 1,3 1,5 1,5 0 0

Assuming:

Pillar’s cross section l : 200 200mm

Pillar’s heigth: 2,8m

Material: Homogenous glulam timber GL24h

Reaction on the pillar: 27,19kN

INDEPENDENT VERIFICATION

The axial force NSLU is calculated adding to the reaction of the beam, applied on the top of the

element, the weight of the pillar multiplied by the appropriate partial γg:

∙ ∙ 27,19 6 2,8 0,2 28,05kN

Page 47: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

45Timber Tech srl

RESULTS PROVIDED BY THE SOFTWARE

28,16kN

RESULTS COMPARISON

Comparison between the value provided by the software and the value calculated in an

independent manner:

Validated parameter

Independent verification

Software Percentage error

28,05 kN 28,16 kN 0,4%

CONCLUSIONS

The comparison shows how results provided by the software are comparable to results obtained

with an independent verification. Errors are caused by different approximation between the manual

verification and the software.

Page 48: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 46

EXAMPLE 16: STABILITY CHECK IN A TIMBER PILLAR

File name: EsempioValidazione.bldg

DESCRIPTION OF THE PROBLEM

The stability checks are conducted with reference to the dispositions provided by UNI EN 1995-1-

1:2009 al § 6.3.2, assuming:

Pillar’s cross section l : 200 200mm

Pillar’s heigth: 2,8m

Material: Homogenous glulam timber GL24h

Reaction on the pillar: 28,30kN

INDEPENDENT VERIFICATION

Given the symmetry of the cross section of the pillar, the inertial radius of gyration has the same

value in the two main directions:

√12

200

√1257,74mm

The buckling length is:

2800mm

The slenderness is, for both main directions, equal to:

280057,74

48,49

Page 49: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

47Timber Tech srl

The relative slenderness ratios should be taken as:

, ⋅ , ,

,

, ⋅ , ,

,

where:

Charateristic compression resistance , , is equal to 24kN

Young modulus parallel to grain , is equal to 9600MPa

The relative slenderness ratios is:

48,49⋅

249600

0,77

The stresses should satisfy the expressions:

, ,

, ⋅ , ,

, ,

, ,⋅ , ,

, ,1

, ,

, ⋅ , ,⋅ , ,

, ,

, ,

, ,1

where the symbols are defined as follows:

,1

,

,1

,

0,5 ⋅ 1 ⋅ , 0,3 ,

0,5 ⋅ 1 ⋅ , 0,3 ,

is a factor for members within the straightness limits defined in Section 10 of EN 1995-1-1 and

assumes the following values:

0,2 for solid timber

0,1 for glued laminated timber and LVL

The factors , , , result:

0,5 1 0,1 0,77 0,3 0,77 0,82

Page 50: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 48

, ,1

0,82 0,82 0,770,955

The design compressive stress along the grain is:

, ,283000,2

10 0,71MPa

The design compressive strenght along the grain is,

, ,⋅ , , 0,8 ⋅ 24

1,4513,24MPa

The check is satisfied, obtaining:

0,710,955 ⋅ 13,24

5,61%

RESULTS PROVIDED BY THE SOFTWARE

Axial force : 28,16kN

Stability check: 6%

RESULTS COMPARISON

Comparison between the value provided by the software and the value calculated in an

independent manner:

Validated parameter

Independent verification

Software

Stability check 5,61% 6%

Page 51: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

49Timber Tech srl

CONCLUSIONS

The comparison shows how results provided by the software are comparable to results obtained

with an independent verification. Errors are caused by different approximation between the manual

verification and the software.

Page 52: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 50

EXAMPLE 17: STABILITY CHECK IN A STEEL PILLAR

File name: EsempioValidazioneAcciaio.bldg

DESCRIPTION OF THE PROBLEM

The stability checks are conducted with reference to the dispositions provided by UNI EN 1993-1-1

al § 6.3.1, assuming:

Steel profile HEA 100, in class 1 (Compression section class)

Pillar’s heigth: 2,8m

Material S235 – EN 10025 - 2

Vertical load: 34,11kN

INDEPENDENT VERIFICATION

The inertial properties of the section are deducted from the profile table; the radius of gyration of

inertia, in the two main directions have the following values:

40,6

25,1

The buckling length, in both direction, is:

2800mm

Page 53: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

51Timber Tech srl

The non-dimensional slenderness is given by:

∙ 1 Class1, 2e3

∙ Class4

where:

is the buckling length in the buckling plane considered;

is the radius of gyration about the relevant axis, determined using the properties of

the gross cross-section;

is the slenderness of proportionality.

The non-dimensional slenderness, for the two main directions, assume the values of:

0,735

1,187

A compression member should be verified against buckling as:

,1

where , , is the design buckling resistance of the compression member:

,

forclass1,2e3

,

forclass4

where is the partial factor for resistance of members to instability equal to 1.05, and are

the gross area and the effective area of the cross section (the effective area is calculated in

accordance to § 4.4 of UNI EN 1993-1-5) and is the reduction factor for the relevant buckling

mode, given by:

1

Φ Φ

1

In this case, for two main directions, result:

Φ 0.5 1 0,2 0,861 0,764

Page 54: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 52

Φ 0.5 1 0,2 1,446 0,440

The design buckling resistance is:

, , 362,4

, , 208,8

The check is satisfied, obtaining:

, min , , , , ,

34,11kN208,8

16%

RESULTS PROVIDED BY THE SOFTWARE

Axial force : 34,07kN

Stability check: 16%

RESULTS COMPARISON

Comparison between the value provided by the software and the value calculated in an

independent manner:

Validated parameter

Independent verification

Software

Stability check 16% 16%

Page 55: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

53Timber Tech srl

CONCLUSIONS

The comparison shows the coincidence between the value provided by the software and that hand-

calculated.

Page 56: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 54

EXAMPLE 18: VERTICAL LOAD ON THE WALL

File name: EsempioValidazione.bldg

DESCRIPTION OF THE PROBLEM

The calculation of the vertical load is conducted assuming:

Cross section stud: : 100 160mm

Stud spacing: 625mm

Material: Solid timber C24

Heigth of the wall: 2,8m

Length of the wall: 3m

Wall self weight : 0,46kN/m

Permanent load : 0,6kN/m

Distributed load on the top of the wall : 10,61kN/m

Beam reaction on the external stud : 8,22kN (“Configuration 3”)

Page 57: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

55Timber Tech srl

INDEPENDENT VERIFICATION

The distributed load caused by the self-weight and the permanent load is:

1,3 0,46 1,5 0,6 2,8m 4,19kN/m

The external stud takes the beam reaction and the distributed load for a length equal to:

26252

313mm

The load per meter length acting at the base of the wall in the external stud influence zone is:

Page 58: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 56

, 4,19 10,618,220,313

41,06kN/m

The load per meter length acting at the base of the wall out from the external stud influence zone

is:

, 4,19 10,61 14,80kN/m

The weighted average of the load n is:

, ∙ , ∙ 41,06 0,313 14,80 2,6873

17,54kN/m

The total load of the wall is:

, ∙ , ∙ 44,60 0,313 14,81 2,687 52,61kN

RESULTS PROVIDED BY THE SOFTWARE

: 17,52kN/m

: 52,57kN

RESULTS COMPARISON

Comparison between the value provided by the software and the value calculated in an

independent manner:

Validated parameter

Independent verification

Software Percentage error

n 17,54 kN/m 17,52 kN/m 0,1%

N 53,61 kN 52,57 kN 0,08%

CONCLUSIONS

The comparison shows how results provided by the software are comparable to results obtained

with an independent verification. Errors are caused by different approximation between the manual

verification and the software.

Page 59: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

57Timber Tech srl

EXAMPLE 19: WIND LOAD ON THE WALL

File name: EsempioValidazione.bldg

DESCRIPTION OF THE PROBLEM

The calculation of the wind load is conducted assuming:

Wall height: : 2,8m

Wall length: : 3m

Wind secondary load: 0,6;

Wind load p (Windward): 0,46KN/m

INDEPENDENT VERIFICATION

The shear force out of plane per meter length at the wall base is:

∙ ⋅ ⋅2

0,46 1,5 0,62,82

0,58kN/m

The total shear force out of plane is:

⋅ 0,58 3 1,74kN

The bending moment per meter length results:

∙ ⋅ ⋅8

0,46 1,5 0,6 2,88

0,41kNm/m

The total bending moment per meter length results:

⋅ 0,41 3 1,23kNm

Page 60: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 58

RESULTS PROVIDED BY THE SOFTWARE

v3: 0,58kN/m

V3: 1,75kN

m22: 0,41kNm/m

M22: 1,22kNm

RESULTS COMPARISON

Comparison between the value provided by the software and the value calculated in an

independent manner:

Validated parameter

Independent verification

Software Percentage error

0,58kN/m 0,58 kN/m 0%

1,75 kN 1,75 kN 0%

0,41kNm/m 0,41 kNm/m 0%

1,22 kNm 1,22 kNm 0%

CONCLUSIONS

The comparison shows the coincidence between the value provided by the software and that hand-

calculated.

Page 61: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

59Timber Tech srl

EXAMPLE 20: STABILITY CHECK OF THE WALL

File name: EsempioValidazione.bldg

DESCRIPTION OF THE PROBLEM

The stability of the studs subjected to compression is verified in accordance with § 6.3.2 of EN

1995-1-1. Specifically, the checked elements are the internal and the external studs which are the

most loaded. These elements (stud or column in a sheathed wall) are braced against buckling in

the in-plane direction therefore checks are performed only in the orthogonal direction. In this

example we consider the internal stud and the load combination below (SLU 33 istantaneous):

Load G1 G2 Live load

cat. H Snow

Orthogonal wind

Partial factors 1,3 1,5 1,5 0 0,9

Assuming:

Internal stud cross section of wall 21: : 100 160mm

Stud spacing: 625mm

Material: Solid timber C24

Heigth of the wall: 2,8m

Length of the wall: 3m

Distributed load on the top of the wall : 10,61kN/m

Distributed load , : 14,80 /

Page 62: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 60

VALIDAZIONE

The stresses should satisfy the expressions:

, ,

⋅ , ,

, ,

, ,1

where:

, , is the design compressive stress along the grain;

, , is the design bending stress about the principal axis;

, , is the design compressive strength along the grain;

, , is the design bending strength about the principal axis;

is a factor calculated as:

1

In wich k is:

0,5 ⋅ 1 ⋅ 0,3

The total vertical load acting at the base of the internal stud is:

, ∙ 14,80 0,625 9,25

The bending moment acting at the wall midpoint is:

⋅ ∙ ⋅ ⋅ ⋅8

0,46 1,5 0,6 0,625 ⋅2,88

0,25

The cross section area of the internal stud is:

∙ 0,10 0,16 0,016

The inertia moment in the buckling direction is equal to:

⋅12

0,1 0,1612

3,4133 10

The section modulus is equal to:

/24,2666 10

The gyration radius of inertia i is equal to:

46,19

Page 63: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

61Timber Tech srl

The buckling length results:

2800

The slenderness of the stud is:

280046,19

60,62

The relative slenderness is:

⋅ , ,

,⋅

217400

1,028

In this case we obtain:

0,5 ⋅ 1 0,2 ⋅ 1,028 0,3 1,028 1,1

1

1,1 1,1 1,0280,67

The design stresses are equal to:

, ,9,250,016

10 0,58MPa

,0,25

4,2666 100,59MPa

The design strengths are:

, ,∙ , , 1 21

1,514MPa

, ,∙ , , 1 24

1,516MPa

Where the factor is equal to 1 because we consider an instantaneous combination. The

stability check is satisfied, obtaining:

, ,

⋅ , ,

, ,

, ,

0,580,67 14

0,5916

9,9%

RESULTS PROVIDED BY THE SOFTWARE

Internal stud stability check: 10%

RESULTS COMPARISON

Page 64: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 62

Comparison between the value provided by the software and the value calculated in an

independent manner:

Validated parameter

Independent verification

Software

Internal stud stability check

9,9% 10%

CONCLUSIONS

The comparison shows the coincidence between the value provided by the software and that hand-

calculated.

Page 65: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

63Timber Tech srl

EXAMPLE 21: ORTHOGONAL COMPRESSION CHECK

File name: EsempioValidazione.bldg

DESCRIPTION OF THE PROBLEM

The studs are supported at the base by the bottom plate which is stressed by compression forces

perpendicular to the grain. The orthogonal compression check is verified in accordance with §

6.1.5 of EN 1995-1-1, assuming:

Internal stud cross section of wall 21: : 100 160mm

Stud spacing: 625mm

Material: Solid timber C24

Distributed load on the top of the wall : 10,61kN/m

Distributed load , : 14,80 /

INDEPENDENT VERIFICATION

The following expression shall be satisfied:

, , , , ⋅ , ,

with

, ,, ,

where:

Page 66: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 64

, , is the design compressive stress in the effective contact area perpendicular to the grain

, , is the design compressive load perpendicular to the grain

is the effective contact area in compression perpendicular to the grain

, , is the design compressive strength perpendicular to the grain

, , is a factor taking into account the load configuration, the possibility of splitting and the degree of compressive deformation.

The effective contact area perpendicular to the grain, , should be determined taking into

account an effective contact length parallel to the grain, where the actual contact length, l, at each

side is increased by 30 mm, but not more than , , / :

The value of kc,90 should be taken as 1,0 unless the conditions in the following paragraphs apply.

For members on continuous supports, provided that 2 , the value of kc,90 should be taken as:

, 1,25 for solid softwood timber;

, 1,5 for glued laminated softwood timber;

The total vertical load on the internal stud is:

∙ 14,80 0,625 9,25kN

The effective contact area is:

∙ 30 2 25600mm

The stress , , result:

, ,, , 9,25 10

256000,36MPa

The design compressive strength perpendicular to the grain , , is:

Page 67: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

65Timber Tech srl

, ,⋅ , , 1 2,5

1,51,67MPa

The orthogonal compression check is satisfied:

, ,

, , ⋅ , ,

0,361,25 ⋅ 1,67

⋅ 100 17,3%

RESULTS PROVIDED BY THE SOFTWARE

Orthogonal compression internal stud 17%

RESULTS COMPARISON

Comparison between the value provided by the software and the value calculated in an

independent manner:

Validated parameter

Independent verification

Software

Orthogonal compression internal stud

17,3% 17%

CONCLUSIONS

The comparison shows how results provided by the software are comparable to results obtained

with an independent verification. Errors are caused by different approximation between the manual

verification and the software.

Page 68: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 66

EXAMPLE 22: CONNECTOR STRENGTH FRAME-PANEL

File name: EsempioValidazione.bldg

DESCRIPTION OF THE PROBLEM

The resistance of each connector is estimated according to the theory of Johansen presented in

8.2.2 EN 1995-1-1 for panel-to-timber connections (Single shear), assuming:

Connector: Nail with improved adherence RING HH6 2,8/3,1 x 65;

Panel: OSB/2 with a thickness of 12,5mm;

Frame thickness t=160 mm.

INDEPENDENT VERIFICATION

CONNECTOR STRENGTH

The characteristic load-carrying capacity for nails, staples, bolts, dowels and screws per shear

plane per fastener, should be taken as the minimum value found from the following expressions:

a) , , , , ⋅ ⋅

b) , , , , ⋅ ⋅

c) , , , , ⋅ ⋅⋅ 2 1 1 ,

4

d) , , 1,05 ⋅ , , ⋅ ⋅⋅ 2 1 ,

, , ⋅ ⋅,

4

Page 69: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

67Timber Tech srl

e) , , 1,05 ⋅ , , ⋅ ⋅⋅ 2 1 ,

, , ⋅ ⋅,

4

f) , , 1,15 ⋅ 2 ⋅ , ⋅ , , ⋅,

4

with:

, ,

, ,

where:

ti is the timber or board thickness or penetration depth;

, , is the characteristic embedment strength in timber member i;

is the fastener diameter;

, is the characteristic fastener yield moment;

, is the contribution from the rope effect. The contribution to the load-carrying capacity

due to the rope effect should be limited to 50% of the Johansen part for nail with improved

adherence.

In the following table are reported the values used in the calculation of the failure modes.

fh,timber

[MPa] ttimber

[mm] tpen

[mm] fh,panel

[MPa] tpannello

[mm] d

[mm] My,k

[Nmm]

21,07 160 52,5 40,70 12,5 2,8 2710

In the figure below there are the failure modes for timber and panel connections.

Page 70: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 68

Characteristic withdrawal capacity

The characteristic withdrawal capacity of nails with improved adherence, , for nailing perpendicular to the grain, should be taken as the smaller of the values found from the following expressions:

,, ,

,

where:

fax,k is the characteristic pointside withdrawal strength;

fhead,k is the characteristic headside pull-through strength;

d is the nail diameter;

dh is the nail head diameter;

tpen,frame is the minimum value between the pointside penetration length and the length of the threaded part in the pointside member.

For threaded nails, the pointside penetration should be at least 6d. For nails with a pointside

penetration smaller than 8d the withdrawal capacity should be multiplied by 3.

In the following table are reported the calculations for the characteristic pointside withdrawal

strength (Fax,k,point) and for the characteristic headside pull-through strength (Fax,k,head).

Connector frame-panel fax,k

[MPa] d

[mm] tpen,frame

[mm] Fax,k,point

[N] fhead,k

[MPa] dh

[mm] Fax,k,head

[N]

RING HH6 2,8/3,1 X 65 6,13 2,8 45 772 12,32 4,3 228

Lateral load-carrying capacity

In the table below there are the characteristic load-carryng capacity per shear plane per fastener

for each failure mode:

Failure modes a b c d e f

, , 1424 3098 1134 606 1248 747

Ropeeffectlimit(N)

- - 515 301 570 367

, / - - 57 57 57 57

, 1424 3098 1191 663 1305 804

Page 71: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

69Timber Tech srl

The characteristic load-carryng capacity per shear plane per fastener is:

, , , 663N

SLIP MODULUS KSER

The slip modulus per shear plane per fastener for nail with improved adherence is:

, ∙ ,

30

is the mean density

is the fastener diameter

If the mean densities of the two jointed wood-based members are different then in the above

expressions should be taken as:

Panel: , 650kg/m

Frame: , 420kg/m

, , √660 420 526kg/m

The slip modulus per shear plane per fastener for nail with improved adherence is:

, ∙ ,

30522,5 , 2,8 ,

30918kN/m

RESULTS PROVIDED BY THE SOFTWARE

, 663N

918

Page 72: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 70

RESULTS COMPARISON

Comparison between the value provided by the software and the value calculated in an

independent manner:

Validated parameter

Independent verification

Software Percentage error

, 663 N 663 N 0%

918Nmm

918Nmm

0%

CONCLUSIONS

The comparison shows the coincidence between the value provided by the software and that hand-

calculated.

Page 73: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

71Timber Tech srl

EXAMPLE 23: CONNECTOR STRENGTH IN A CLT JOINTED WALL

File name: EsempioValidazione.bldg

DESCRIPTION OF THE PROBLEM

The resistance of each connector is estimated according to the theory of Johansen presented in

8.2.2 EN 1995-1-1 for panel-to-timber connections, assuming:

CLT panels with a thickness of 120 mm;

Joint typology:

o Central board in LVL KertoQ with a thickness of 27 mm

o Nail with an improved adherence RING HH3 3,8/4,2 x 120;

INDEPENDENT VERIFICATION

CONNECTOR STRENGTH

The characteristic load-carrying capacity for nails, staples, bolts, dowels and screws per shear

plane per fastener in double shear, should be taken as the minimum value found from the following

expressions:

g) , , , , ⋅ ⋅

h) , , 0.5 ⋅ , , ⋅ ⋅

j) , , 1,05 ⋅ , , ⋅ ⋅⋅ 2 1 ,

, , ⋅ ⋅,

Page 74: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 72

k) , , 1,15 ⋅ 2 ⋅ , ⋅ , , ⋅,

with:

, ,

, ,

where:

ti is the timber or board thickness or penetration depth;

, , is the characteristic embedment strength in timber member i;

is the fastener diameter;

, is the characteristic fastener yield moment;

, is the contribution from the rope effect. The contribution to the load-carrying capacity

due to the rope effect should be limited to 50% of the Johansen part for nail with improved

adherence.

In the following table are reported the values used in the calculation of the failure modes.

fh,CLT

[MPa] tCLT

[mm] tpen,CLT

[mm] fh,board

[MPa] tboard

[mm] d

[mm] My,k

[Nmm]

19,23 46,5 46,5 26,37 27 3,8 5790

In the figure below there are the failure modes for timber and panel connections.

Characteristic withdrawal capacity

The characteristic withdrawal capacity of nails with improved adherence, , for nailing perpendicular to the grain, should be taken as the smaller of the values found from the following expressions:

Page 75: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

73Timber Tech srl

,, ,

,

where:

fax,k is the characteristic pointside withdrawal strength;

fhead,k is the characteristic headside pull-through strength;

d is the nail diameter;

dh is the nail head diameter;

tpen,frame is the minimum value between the pointside penetration length and the length of the threaded part in the pointside member.

For threaded nails, the pointside penetration should be at least 6d. For nails with a pointside

penetration smaller than 8d the withdrawal capacity should be multiplied by 3.

In the following table are reported the calculations for the characteristic pointside withdrawal

strength (Fax,k,point) and for the characteristic headside pull-through strength (Fax,k,head).

Connector frame-panel fax,k

[MPa] d

[mm] tpen,punta

[mm] Fax,k,punta

[N] fhead,k

[MPa] dh

[mm] Fax,k,testa

[N]

RING HH6 2,8/3,1 X 65 6,13 3,8 46,5 1083 8,58 5,3 241

Lateral load-carrying capacity

In the table below there are the characteristic load-carryng capacity per shear plane per fastener

for each failure mode:

Failure modes g h j k

, , 3398 1353 1385 1138

Ropeeffectlimit(N)

- - 693 569

, / - - 60 60

, 3398 1353 1445 1198

The characteristic load-carryng capacity per double shear plane per fastener is:

, 2 ∙ , , 2396N

SLIP MODULUS KSER

The slip modulus per double shear plane per fastener for nail with improved adherence is:

Page 76: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 74

2 ∙, ∙ ,

30

is the mean density

is the fastener diameter

If the mean densities of the two jointed wood-based members are different then in the above

expressions should be taken as:

CLT: , 420kg/m

Board: , 510kg/m

, , √510 420 463kg/m

The slip modulus per double shear plane per fastener for nail with improved adherence is:

2 ∙, ∙ ,

302 ∙

463 , 3,8 ,

301931kN/m

RESULTS PROVIDED BY THE SOFTWARE

, 2396N

1931

Page 77: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

75Timber Tech srl

RESULTS COMPARISON

Comparison between the value provided by the software and the value calculated in an

independent manner:

Validated parameter

Independent verification

Software Percentage error

, 2396 N 2396 N 0%

1931Nmm

1931Nmm

0%

CONCLUSIONS

The comparison shows the coincidence between the value provided by the software and that hand-

calculated.

Page 78: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

Timber Tech srl 76

EXAMPLE 24: MODAL ANALYSIS

File name: EsempioModale.bldg

DESCRIPTION OF THE PROBLEM

The modal analysis involves the solution of the generalized eigenvalue problem:

0

where:

is the stiffness matrix;

the mass matrix;

e are the eigenvalues and the eigenvectors.

For the calculation we consider an irregular building with two levels (figure above).

Page 79: Verification Manual EN - Albena Design · KINETICS PRESSURE The kinetics reference pressure M ... l 12,0 0,7 p h L1,479 SHAPE FACTOR The shape factor (or aerodynamic coefficient)

TimberTech Buildings Verification Manual

77Timber Tech srl

VERIFICATION WITH SAP2000

In order to validate the solution obtained with the TimberTech Buildings software a modeling in

SAP2000 was performed.

It shows a comparison between the periods of the structure and the participating masses along the

two main directions "X " and "Y "

TimberTech Buildings SAP2000

Modes

Periods

[s]

Participating mass X

[%]

Participating mass Y

[%]

Periods

[s]

Participating mass X

[%]

Participating mass Y

[%]

1  0,18  2,67  72,35  0,18  2,67  72,35 

2  0,18  70,23  2,81  0,18  70,23  2,81 

3  0,11  0,01  0,72  0,11  0,01  0,71 

4  0,08  0,00  24,06  0,08  0,00  24,06 

5  0,08  26,81  0,00  0,08  26,81  0,00 

6  0,06  0,28  0,06  0,06  0,28  0,06 

CONCLUSIONS

The comparison shows how results provided by the software are comparable to results obtained

with a verification with SAP2000.