Planlægnings- og installationsvejledning
V E N T I L AT I O N S S Y S T E M
04 I 201031701
Indhold
Uponor PP plast ventilationskanaler og -komponenter ...................................................................4
Materialedata ......................................................................................................................................4
Tekniske data for kanaler .....................................................................................................................4
Tekniske data for kanalisolering ...........................................................................................................5
Kvalitet ................................................................................................................................................5
Mål og tolerancer.................................................................................................................................5
Kanalernes tæthed ...............................................................................................................................5
Emballage ............................................................................................................................................5
Opbevaring ..........................................................................................................................................5
Ventilationskanaler og -komponenter ................................................................................................6
Ventilationskanaler ....................................................................................................................................6
Ventilationskomponenter .....................................................................................................................6
Præ-isolerede ventilationskanaler ........................................................................................................8
Præ-isolerede ventilationskomponenter ..............................................................................................8
Armaturer og ventiler ........................................................................................................................10
Konstruktion af ventilationssystem .............................................................................................12
Defi nitioner .......................................................................................................................................12
Anvendelser for Uponor ventilationskanaler ......................................................................................12
Køkken emhætte/ventilator kanaler ..................................................................................................12
Placering af kanaler ...........................................................................................................................12
Offentlige regler ................................................................................................................................12
Isolering af kanalerne ........................................................................................................................12
Ventilation af saunarum .....................................................................................................................12
Dimensionering af kanaler og lyddæmpere .................................................................................15
Lyddæmpernes lyddæmpning pr oktav, ISO 7235:2003 .....................................................................19
Lyddæmpernes tryktab, ISO 7235:2003 ............................................................................................19
Lyddæmpernes tryktab, ISO 7235:2003
USI-125-300, USI-125-650 og USI-125-1000 .............................................................................20
USI-160-650 og USI-160-1000 ...................................................................................................20
2 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0
Installation ............................................................................................................................................21
Oversigt .............................................................................................................................................21
Kanalføring ........................................................................................................................................21
Kanalføring gennem dampspærrer .....................................................................................................22
Kanalføring af præ-isolerede kanaler gennem dampspærrer ..............................................................22
Understøtninger ................................................................................................................................23
Understøtning af præ-isolerede kanaler ............................................................................................23
Isolering ........................................................................................................................................24
Installation og indstilling af luftarmaturer ...............................................................................................26
Oversigt .............................................................................................................................................26
Tilslutning af luftarmaturer til kanalerne ............................................................................................26
Friskluftrist ........................................................................................................................................27
Friskluftsarmatur til vægmontage ......................................................................................................27
Friskluftsarmatur til ventilationshul ...................................................................................................27
Spalteventil ........................................................................................................................................28
Friskluftsarmatur ...............................................................................................................................28
Justering af armaturer .......................................................................................................................28
Tabeller over armatur fabriksindstillinger, trykdifferens 20 Pa ..................................................29
Luftstrøm, trykdifferens og støjniveau .......................................................................................30
Luftstrøm og trykdifferens ..........................................................................................................32
U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 3
Uponor PP plast ventilationskanaler og -komponenter
• Alle kanaler og komponenter
er rene og beskyttede fra pro-
duktion til installation.
• Vores produktudvalg indehol-
der fabriksfærdige, præ-iso-
lerede kanaler og kanalsek-
tioner.
• Opsamler ikke støv eller snavs:
Antistatisk PP materiale mod-
står enhver forurening.
• Hurtig og nem installation.
• Let bearbejdelige materialer.
• Kanalerne kan installeres uden
separat forsegling og låsning.
Materialespecifi kationer
Råmaterialer: polypropylen;
lugtfri og ugiftig
Farve: blå
Massefylde: ≈ 900 kg/m3
Brudstyrke: 30 MPa
Varmeudvidelse: 0,06 mm/m °C
Tekniske data for kanaler
Den indvendige overfl ade på kana-
ler er ren og fri for ujævnheder.
Modstandsdygtighed mod slag:
Opfylder kraven angivet i
SFS-EN 1411.
Korrosionsbestandighed:
Kemisk modstandsdygtighed som
beskrevet i standarden ISO/TR
10358
Antistatiske egenskaber:
Antistatiske produkter. De antista-
tiske egenskaber af kanalernes og
komponenternes indre overfl ader
måles under produktionen i over-
ensstemmelse med testproceduren i
ANSI/EOS/ESD-S11.11.
Varmebestandighed:
Kontinuerlig –50°C...+85°C,
kortvarigt +100 °C.
Kuldebestandighed:
Den lavest anbefalede temperatur
er -15°C. Kuldebestandigheden ve-
rifi ceres gennem konstant kvalitets-
kontrol i fl g. testmetoderne i SFS/
EN 1411.
Renhedsklassifi kation:
Renhedsklasse M1. Udviklet i sam-
arbejde med det fi nske Astma- og
Allergiforbund.
Tekniske data for kanalisolering
Råmaterialer: polyætylen skum
Farve: Blå
Massefylde: 30 kg/m3, isolering
tykkelse 15 mm
U-værdi 0,037 W/ m x K
Brandsikkerhed: Ingen brandklas-
sifi cering.
VTT studier:
- En fabriksisoleret ventilationska-
nal til 1 – 2 familiehuse eller ræk-
kehuse
Laboratorietest for overfl ade
temperatur
Dato 6. november 2006
En computerberegning af den
nødvendige isolerings tyk-
kelse for at hindre kondens og
begrænse produktets varmetab
udviklings- og laboratoriums- af-
prøvning
Dato 10. maj 2006
Instruktionerne i denne manual er
udarbejdet til brug for implemente-
ring af lejligheds-adskilte ventilati-
onssystemer i fritliggende huse, ter-
rassehuse eller rækkehuse. I terras-
sehuse og rækkehuse skal der være
fuldstændig strukturel brandadskil-
lelse af boligenes loftsrum.
Uponors produktsortiment er blevet
opdateret, og vi introducerer nu
præ-isolerede ventilationskanaler
og -kanalsektioner på markedet. Et
isoleret kanalsystem tillader en sik-
rere køling af indsugningsluften, og
der mistes ikke energi i strukturen.
På den anden side er fabriksisolere-
de kanaler i den øverste tagisolering
"sikre", og det gør det lettere at
undgå kondens og risici pga. instal-
lationsfejl.
������������ ������ ���������� �� �������� � � �����������������������������
���� �!� "�#� $ � �� %�& ����'
� %!�'��'( �#
� %!�'��'()#'�##*�& #
" ' �+,%�' ��-)+,#'),�
Kanalmærkning
• Teknisk excellent struktur for
luftgennemstrømning
• Ingen korrosionsproblemer
• Ingen lugtproblemer
• Garanteret ren indeluft i hele
hjemmet
• Patenterede struktur- og sam-
lingsløsninger
4 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0
Lyddæmpere
Lyddæmperne er udført i PE plast.
Lyddæmperne er testet af
VTT Technical Research Centre of
Finland, Certifi kat
Nr. VTT-S-03839-07
Dato 24.04.2007
- Firkantede lyddæmpere med
runde kanaltilslutninger
- Lille vægt og lette at håndtere
- Fremragende lyddæmpende
egenskaber
- Modstandsdygtige mod slag og
korrosion
- Sort farve
- Det indvendige lyddæmpende
materiale er Dacron
- Ingen løse fi bre eller fugtabsorp-
tion
- Ingen irritation af hud eller ån-
dedræt
- Ingen lugt eller støbeproblemer
Kanalernes tæthed
Kanalerne opfylder lufttæthedsklas-
se D. Kanalerne skal tilsluttes i over-
ensstemmelse med instruktionerne i
denne manual.
Forbindelserne kan ikke limes sam-
men, fordi opløsningsmidlerne ikke
virker på polypropylen.
Emballage
Kanalerne leveres lukkede i begge
ender for at holde dem rene. Kanal-
komponenterne leveres i plastposer
og papkasser.
Opbevaring
Modstår udendørs oplagring i cen-
traleuropæisk klima. Kanalerne er
UV-beskyttede. Højst 2 lag oven på
hinanden.
Kvalitet
Uponors plast ventilationssystem
kanaler er blevet tildelt et VTT pro-
duktcertifi kat.
Mål og tolerancer
Kanalstørrelserne er ø 100 (+0.5)
mm, ø 125 (+0.5) mm, ø 160 (+0.6)
mm
og ø 200 (+0.7) mm.
Tolerancerne opfylder kanalstandar-
den SFS 3282.
Tolerancerne for de sprøjtestøbte
komponenter er bedre end standar-
den kræver.
Uponors ventilationskanaler og
-komponenter er kompatible med
kanalkomponenter, der opfylder
standarden SFS 3282.
U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 5
Ventilationskanaler og -komponenter
Ventilationskanaler Materiale: Polypropylen. Farve: blå.
Ventilationskanal Leveres i længder på 3 meter.
di x l Uponor nr. VVS nr. s
100 x 3000 1046152 35.3500.100 2,1
125 x 3000 1046153 35.3500.125 2,1
160 x 3000 1046154 35.3500.160 2,5
200 x 3000 1046155 35.3500.200 3,0
Ventilationskomponenter Materiale: Polypropylen. Farve: Blå.
Bøjning 45°
do x α Uponor nr. VVS nr l1 l2
100 x 45° 1046172 35.3502.100 46 40
125 x 45° 1046173 35.3502.125 36 50
160 x 45° 1046174 35.3502.160 45 50
200 x 45° 1046171 35.3502.200 54 50
Bøjning 90°
do x α Uponor nr. VVS nr. l1 l2
100 x 90° 1046168 35.3501.100 81 40
125 x 90° 1046169 35.3501.125 84 50
160 x 90° 1046170 35.3501.160 160 50
200 x 90° 1046167 35.3501.200 130 50
T-stykker
do1/do2 Uponor nr. VVS nr. l1 l2 l3
100/100 1046175 35.3503.100 142 40 71
125/100 1046179 35.3503.124 144 50 81
125/125 1046176 35.3503.125 168 50 81
160/100 1046180 35.3503.158 144 50 98
160/125 1046177 35.3503.159 168 50 101
160/160 1046178 35.3503.160 196 50 100
200/160 1046181 35.3503.199 202 50 118
%
�.
'
α
%� %�
�
% �% �
%�
% �
�
�
%�%� %�
��
% �
α
% �
% �
% ��
% �
6 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0
Ventilationskomponenter Materiale: Polypropylen. Farve: Blå.
%�
%�%�
�
%�
�
�
%�
�
�
%�
Samlenippel
do Uponor nr. VVS nr. l1 l2
100 1046164 35.3508.100 83 40
125 1046165 35.3508.125 103 50
160 1046166 35.3508.160 103 50
200 1046163 35.3508.200 103 50
Prop
do1/do2 Uponor nr. VVS nr. do3 l1 l2
100 1046182 35.3506.100 120 43 40
125 1046183 35.3506.125 145 33 30
125/160 1046184 35.3506.159 180 53 50
Reduktionsstykke
do1/do2 Uponor nr. VVS nr. l2 l3 l4
100/125 1046185 35.3504.124 50 20 40
125/160 1046186 35.3504.159 51 30 50
160/200 1046187 35.3504.199 51 40 50
% �% �
��
��
% �% �
��
��
��
% �% �
��
��100
125
125/160
U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 7
Præ-isolerede ventilationskanaler Kanalmateriale: Polypropen. Farve: Blå.
Isoleringsmateriale: Polyætylen skum Farve: Blå
Isoleringstykkelse: 15 mm
VentilationskanalLeveres i længder på 3 meter.
di x l Uponor nr. VVS nr.
100 x 3000 1046156 35.3510.100
125 x 3000 1046157 35.3510.125
160 x 3000 1046158 35.3510.160
200 x 3000 1046159 35.3510.200
Præ-isolerede ventilationskomponenter Kanalmateriale: Polypropen. Farve: Blå.
Isoleringsmateriale: Polyætylen skum Farve: Blå
Isoleringstykkelse: 15 mm
Bøjning 45°
do x α Uponor nr. VVS nr.
100 x 45° 1046197 35.3512.100
125 x 45° 1046198 35.3512.125
160 x 45° 1046199 35.3512.160
200 x 45° 1046196 35.3512.200
Bøjning 90°
do x α Uponor nr. VVS nr.
100 x 90° 1046193 35.3511.100
125 x 90° 1046194 35.3511.125
160 x 90° 1046195 35.3511.160
200 x 90° 1046192 35.3511.200
T-stykker
do1/do2 Uponor nr. VVS nr.
100/100 1046200 35.3513.100
125/100 1046204 35.3513.124
125/125 1046201 35.3513.125
160/100 1046205 35.3513.158
160/125 1046202 35.3513.159
160/160 1046206 35.3513.160
200/160 1046203 35.3513.199
l
di
s
l
di
s
8 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0
Samlenippel
do Uponor nr. VVS nr.
100 1046189 35.3518.100
125 1046190 35.3518.125
160 1046191 35.3518.160
200 1046188 35.3518.200
Prop
do1/do2 Uponor nr. VVS nr.
100 1046207 35.3516.100
125 1046208 35.3516.125
125/160 1046209 35.3516.159
Reduktionsstykke
do1/do2 Uponor nr. VVS nr.
100/125 1046210 35.3514.124
125/160 1046211 35.3514.159
160/200 1046212 35.3514.199
Aluminiumsspændbånd
Produkt Uponor nr. VVS nr.
Aluminiumsspændbånd 5 stk. / pose 1046258 35.3529.800
�
��
��
��
��100
125
125/160
Kanalføring gennem dampspærre
Selvklæbende PE-plast.
Mål d1 Uponor nr. VVS nr. l1 l2 tykkelse
100 1046252 35.3529.010 240 240 10
125 1046251 35.3529.012 240 240 10
Lyddæmper Firkantet, indvendigt lyddæmpene materiale er Dacron
Tilslutningsdiameter og model Uponor nr. VVS nr. l1 l2 l3
USI - 125 - 300 1046253 35.3529.123 300 190 270
USI - 125 - 650 1046254 35.3529.126 650 190 270
USI - 125 - 1000 1046255 35.3529.120 1000 190 270
USI - 160 - 650 1046256 35.3529.166 650 225 300
USI - 160 - 1000 1046257 35.3529.160 1000 225 300
%�
�
% �
U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 9
Armaturer og ventiler Standardfarve: Hvid.
Indblæsningsarmaturer (mekanisk ventilation)
Lofts-monterede armaturer Tilslutningsdiameter og model Uponor nr. VVS nr. D D1 H
UTK-100 1046266 35.3520.110 140 98 60
UTK-C-100, krom 1046267 35.3520.114 140 98 60
UTK-B-100, messing 1046268 35.3520.116 140 98 60
* UTK-S-100, sauna 1046269 35.3520.210 140 98 60
* UTK-S-B-100, sauna messing 1046270 35.3520.216 140 98 60
UTK-125 1046271 35.3520.120 175 115 67Vægmonterede armaturer
UTK-C-125, krom 1046272 35.3520.124 175 115 67
UTK-B-125, messing 1046273 35.3520.126 175 115 67
* UTK-S-125, sauna 1046274 35.3520.220 175 115 67
* UTK-S-B-125, sauna messing 1046275 35.3520.226 175 115 67
UKK-125, armaturkrave 1046227 35.3520.820 166 135 55
Armaturkrave UTS-100 1046226 35.3520.410 Mål i billedet
UTS-125 1046218 35.3520.420 Mål i billedet
* Varmebestandigt op til 200°C. Ved brug af saunaarmaturet, brug altid kraven i emballagen.
Udsugningsarmaturer (mekanisk ventilation)
Loftsmonterede armaturer Tilslutningsdiameter og model Uponor nr. VVS nr. D D1 H
UPK-100 1046214 35.3521.110 138 72 50
UPK-C-100, krom 1046228 35.3521.114 138 72 50
UPK-M-100, messing 1046229 35.3521.116 138 72 50
UPK-125 1046213 35.3521.120 168 90 60
UPK-C-125, krom 1046230 35.3521.124 168 90 60
UPK-M-125, messing 1046231 35.3521.126 168 90 60
* UPK-S-100 med træknop 1046232 35.3521.210 138 72 50
* UPK-S-125, med træknop 1046233 35.3521.220 168 90 60
* UPK-S-M-100, messing, med træknop 1046234 35.3521.216 138 72 50
* UPK-S-M-125, messing, med træknop 1046235 35.3521.226 168 90 60
* Varmebestandigt op til 200°C. Ved brug af saunaarmaturet, brug altid kraven i emballagen.
Tallerkenventiler (naturlig ventilation)
Tilslutningsdiameter og model Uponor nr. VVS nr. D D1 H
ULV-100 1046236 35.35211.10 138 72 58
ULV-125 1046237 35.3522.120 168 90 66
/
0 0�
/
0 0�
/
0 0�
/
0 0�
10 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0
Armaturer og ventiler Standardfarve: Hvid.
Friskluftsriste
Tilslutningsdiameter og model Uponor nr. VVS nr. A D H
USS-100 med insektnet 1046238 35.3525.110 143 123 57
USS-125 med insektnet 1046239 35.3525.120 143 123 57
USS-160 med aftagelig netkassette 1046240 35.3525.160 235 160 74
USS-200 med aftagelig netkassette 1046241 35.3525.200 235 200 74
160/200 Netkassette til friskluftrist 1046242 35.3525.620
Friskluftsarmatur
Tilslutningsdiameter og model Uponor nr. VVS nr.
URS-100 1046243 35.3523.100
Friskluftsarmatur til ventilationshul
Tilslutningsdiameter og model Uponor nr. VVS nr.
UKS-100, vægmonteret 1046244 35.3523.200
UKTL-100, ventilationshul 1046245 35.3523.300
Spalteventil
Tilslutningsdiameter og model Uponor nr. VVS nr.
URV-18, 18 x 245 x 340 1046246 35.3523.618
1��
�
��
���
1��
2
1��
�
1��
�1��
�
�2���
1��
�
���
�3
���
��
��
��3 ��4�
U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 11
Konstruktion af ventilationssystem
Defi nitioner
- Friskluftkanalen tilfører frisk
udeluft til ventilatoren.
- Indblæsningskanalerne fordeler
den friske luft fra ventilationsenhe-
den til rummene.
- Udsugningskanalerne fører
indeluften til ventilationsenheden,
som overfører varmen fra udblæs-
ningsluften til at opvarme den ind-
kommende friske luft, om nødven-
digt.
- Afkastluftkanalen overfører
udblæsningsluften fra ventilations-
enheden til udblæsningsrøret på
taget.
- Mineraluld refererer til både
glasuld og stenuld (fx Rockwool).
Mineraluld kan hverken brænde el-
ler rådne.
Ved design af luftkanalerne og di-
mensionering af kanalerne anbefa-
les det som udgangspunkt at bruge
en relativt lav lufthastighed (under
3 m/s) i kanalerne.
Anvendelser for Uponor
ventilationskanaler
Uponor ventilationskanaler bruges i
overensstemmelse med kapitel 6.3.1
i det danske bygningsreglement til
individuel ventilation af beboelses-
bygninger og andre bygninger end
beboelsesbygninger..
Køkken emhætte / emfang med
ekstern ventilator
Udsugningskanalerne fra køkken-
ventilatorer og emhætter tilslut-
tes ikke til ventilationssystem, men
føres ud til taget separat og har sin
egen udsugningsventilator.
Placering af kanaler
Indblæsnings- og udsugnings-kana-
lerne installeres normalt
- Nede i loftsisoleringen over loftet
- I loftsrummene
- Inde i gulv/loftsadskillelser
- Over et forsænket loft, eller
- Under loftet i huset.
Indblæsningsarmaturerne installeres
især i opholdsrum og soverum for at
tilføre frisk udeluft. Fordi udsug-
ningsarmaturerne er konstrueret til
affugtning og fjernelse af dårlige
lugt i tillæg til luftcirkulation, an-
bringes de i baderum, saunaer,
og nytterum (fyrrum, hobbyrum,
bryggers), skabsrum, køkkener og
toiletter. Den brugte luft fl yder
gennem døråbninger fra rummene
med indblæsning til rummene med
udsugning.
Myndighedernes bestemmelser
I designet af luftkanalerne og deres
installation skal regler og instruk-
tionerne, der står i det danske
bygningsreglement kapitel 6 over-
holdes. Ventilationskanalerne skal
beskyttes af et nedhængt loft eller
konstruktion mod opholdsrum..
Isolering af kanalerne
Forholdene vedr. opvarmning, kon-
dens og brandisolering af kanalerne
er specifi ceret i ventilationsplanen.
Isolering kan vises på tegningerne
fx med følgende markeringer:
- HI1: Varmeisolering, mineraluld
50 mm uden overfl adeafslutning.
- HI2: Varmeisolering, mineraluld
50 + 50 mm uden overfl ade-
afslutning.
- HI2: Varmeisolering, mineraluld
50 mm uden overfl adeafslutning
+ indblæst løs isolering eller til-
svarende mindst 100 mm oven på
den isolerede kanal.
- HI4: I opvarmede områder iso-
lering mod varme og kondens
med ekspanderet polystyren 15
mm. Inde i den øverste loftspla-
des isolering: Mindst 100 mm
løst indblæst mineraluld oven på
kanalerne, der er isoleret med 15
mm ekspanderet polystyren.
- HI5: Isolering mod varme og kon-
dens med ekspanderet polystyren
15 mm + mineraluld 50 mm uden
overfl adeafslutning.
Uanset ovenstående forslag skal
ventilationsrør som minimum iso-
leres mod energitab jf. DS 452,
klasse 1.
Brugen af præ-isolerede
indendørs luftprodukter letter
isoleringsarbejdet, især på
vanskeligt tilgængelige steder.
Ventilation af saunarum
Ved design af kanaler til saunaer skal
temperaturbegrænsningerne over-
holdes. Kanalerne skal enten indsæt-
tes i saunaens isolering eller installe-
ret over isoleringen. I andre tilfælde,
fx hvor den skal anbringes direkte
bag panelerne, skal rørene isoleres
termisk. Kanalerne og rammerne til
de loftsmonterede armaturer skal
fastgøres til loftsstrukturerne på for-
svarlig vis med skruer.
Bemærk venligst: Brug kun anbefale-
de varmebestandige saunaarmaturer
ved loftet i saunaer. Indblæsnings-
armaturerne er markeret med en rød
etiket, og udsugningsarmaturerne
har en træknop. Saunaarmaturer skal
altid installeres i en armaturkrave.
Armaturkraven skal fastgøres til sau-
naloftets træ med skruer, hvorefter
saunaarmaturet indsættes. Undgå at
installere saunaarmaturet lige over
saunaens ovn.
Tuloilma
katosta kiukaan
l heisyydest
Poisto-
ilma
lattian
l helt
0,5—1,0 m/s
Ventilation af saunarum
Tilluft fra taget i nærheden
af ventilationsaggregatet
Fraluft
ved
gulv
12 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0
RE
GU
LA
TO
R F
OR
PE
ISA
VT
RE
KK
SAUNA
FUGTSENSOR
VÆRELSE
VÆRELSE
VÆRELSE
UDHUS
TERRASSE
STUE
KØKKEN
EMHÆTTE
LYD-
DÆMPER
LYD-
DÆMPER
KLÆDESKAB
BRYGGERS
VENTILATIONSREGULATOR
(UDEN INSEKTNET)
FR
ALU
FT
VE
NT
IL
MO
NT
ER
ES 4
00
MM
OV
ER
GU
LV,
RE
KTA
NG
ULÆ
R K
AN
AL
I V
ÆG
GE
N 4
0 X
14
0
Ø1
60
TIL
TA
GE
T
+A
FK
AST
HÆ
TT
E
UN
DE
RTA
GSN
IVE
AU
Eksempel på ventilationssystem design for et fritliggende hus. Materialelisten fi ndes på næste side.
U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 13
Materialeliste for ventilations-plan for et een-familiehus som det vist på forrige side
Uponor Størrelse Produkt Producent stk m nr /kode
1046158 Ø 160 Kanal, præ-isoleret Uponor 13 36
1046157 Ø 125 Kanal, præ-isoleret Uponor 18 48
1046195 Ø 160 Bøjning 90°, præ-isoleret Uponor 3
1046194 Ø 125 Bøjning 90°, præ-isoleret Uponor 12
1046202 Ø 160/125 T-stykke, præ-isoleret Uponor 11
1046201 Ø 125/125 T-stykke, præ-isoleret Uponor 12
1046206 Ø 160/160 T-stykke, præ-isoleret Uponor 1
1046191 Ø 160 Samlenippel, præ-isoleret Uponor 8
1046190 Ø 125 Samlenippel, præ-isoleret Uponor 9
1046209 Ø 125/160 Prop, præ-isoleret Uponor 1
1046208 Ø 125 Prop, præ-isoleret Uponor 8
1046211 Ø 125/160 Reduktion, præ-isoleret Uponor 2
1046251 Ø 125 Dampspærre gennemføring Uponor 21
1046271 UTK-125 Indblæsningsarmatur Uponor 8
1046213 UPK-125 Udsugningsarmatur Uponor 9
1046237 ULV-125 Tallerkenventil Uponor 4
1046241 USS-200 Friskluftrist m/aftagelig netkassette Uponor 2
1046239 USS-125 Friskluftrist m/insektnet Uponor 4
1046253 USI-125-300 Lyddæmper Uponor 3
1046255 USI-125-1000 Lyddæmper Uponor 2
Tillægsliste over produkter, der ikke fi ndes i Uponors produkt-sortiment
Størrelse Produkt Producent stk m2 /kode
Mineraluld isolering 50 mm 7
40x140 Rektangulær kanalpakke for badstue 1
Ø 160 Taggennemføring med hætte og inddækning for afkastluft 2
Ø 160 Tallerkenventil 1
Ø 200 Tallerkenventil 1
Bemærk at der ikke indgår produkter til emhætte/emfang i ovenstående materialeliste.
14 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0
�
�
�
�
�3
2
��
��
��
��
��
3�
�� �� �� �� �� 3� 2� ��� ��� ��� ����%! ���% +��'+��� �5!��'6
� �
-,+
�*4��
������7
����8�7
",)�,��������7�& �����8�7��
�
�
�
�
�3
2
��
��
��
��
��
3�
�� �� �� �� �� 3� 2� ��� ��� ��� ����%! ���% +��'+��� �5!��'6
� �
-,+
�*4��
��9�'��'�����3�
: & �'�3�����
$����%����;���9�'��'������3��& �% & �'��3�����
���%! ���- )'��4���#<�!�
����%! ���% +��'+��� �5!��'6
���������2�3������������4�
�4�
�4�
�4��4��43
�42�
�
�
��32
��
��
� �
-,+
�*4��
5� �
!6
1��� 1�3�3�!�'
��!�'
��!�'
��!�'
" + ��1����4�1����4�1��3��& �1����
1���
��!�'
��!�'
1���
�
�
�
�
�3�2
��
��
��
��
��3���
�� �� �� �� �� 3� 2� ��� ��� ��� ���
�%! ���% +��'+��� �5!��'6
� �
-
,+�*
4��
��9�'��'�3�����
: & �'�����3�
$����%����;���9�'��#' ���������4��3�����4& �% & �#' ����������& ������3�
: & �'���������9�'��'
�������
2�8�
���
Tryk
tab
, P
a
Luftstrøm (l/s)
Reduktionsstykke: Reduktionsstykker 125/100,
160/125, 100/125 og 125/160
Reduktion
Reduktion
Ekspansion
Ekspansion
10
20
30
40
50
60
70
0 20 30 40 50 60 80 100Ilman tilavuusvirta haarakanavassa q
3 [dm3/s]
Kok
onai
spai
ne-e
ro Δ
p 1-3
[Pa]
2
T-kappale 100/100Poisto sivulta. Kokonaispaine-ero Δp1-3
80
90100
0
-10
-20
-30
-40
-50
-6010 70 90 110 120 130
4
6
8
10
V1 m/s
1
3
2
Tota
l tr
ykd
iffe
ren
s Δp
1-3
, (P
a)
Luftstrøm i kanalgrenen q3 (l/s)
T-stykke 100/100
Side udsugning Total trykdifferens Δp1-3
3�28
��
3�
� �� �� �� �� 3� 2� ���
�%! ���% +��'+��� �- � # + '' �N��5!��'6
"�#
� �
'9 �
(
���O
9 �(��
5� 6
�
�(# 99 % ����������%��'�+�%% Q�"�#� �'9 � ( ���O9�(�
��2�8�
�� �� 8� ��� ��� ���
�
3
2
��
�
�
�
�
�
��
��
�
�
�
��
��
���!�'
Tota
l tr
ykd
iffe
ren
s Δp
1-3
, (P
a)
Luftstrøm i kanalgrenen q3 (l/s)
T-stykke 100/100
Side udsugning Total trykdifferens Δp1-3
6789
10
20
0 20 30 40 50 60 80 100
Ilman tilavuusvirta haarakanavassa q2 [dm3/s]
Kok
onai
spai
ne-e
ro Δ
p 1-2
[Pa]
2
T-kappale 100/100Poisto sivulta. Kokonaispaine-ero Δp1-2
30
40
50
0,90,80,70,60,50,4
10 70 90 110 120 130
4
6
8
10
V1 m/s
140 150
54
3
2
1
0,3
0,2
0,1
1
3
2
Luftstrøm i kanalgrenen q2 (l/s)
T-stykke 100/100
Side udsugning Total trykdifferens Δp1-2
Tota
l tr
ykd
iffe
ren
s Δp
1-2
, (P
a)
Dimensionering af kanaler og
lyddæmpere
Hoved indblæsnings- og udsug-
nings-kanalerne skal så vidt muligt
være store (ø 160) for at mindske
tryktabet i kanalerne mest muligt.
Indblæsningsarmaturerne skal til-
sluttes til hovedkanalen med for-
greninger.
Luftstrøm (l/s)
Tryk
tab
, P
a
Kanaler ø 100, ø 125, ø 160 og ø 200
Luftstrøm (l/s)
Tryk
tab
, P
a
Reduktionsstykke: Reduktionsstykker 200/160,
160/200
Reduktion
Ekspansion
Luftstrøm (l/s)
Tryk
tab
, P
a
Bøjning 200/45° og 200/90°Luft massefylde 1,20 kg/m³
Tryk
tab
, P
a
Luftstrøm l/s
Bøjninger 100/45°, 100/90°, 125/45°, 2x125/45°,
125/90°, 160/45° og 160/90°
og
U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 15
Ilman tilavuusvirta haarakanavassa q3 [dm3/s]0 10 20 30 40 50 60 70 80 90 100 110 120130
10
8
6
4
21
3
2
v1 [m/s]
5060
80
1
2
3
456
20
30
40
100
810
Tota
l tr
ykd
iffe
ren
s Δp
1-3
, (P
a)
Luftstrøm i kanalgrenen q3 (l/s)
T-stykke 125/125
Side indsugning Total trykdifferens Δp1-3
�%! ���% +��'+��� ���#�# + '' �N��5!��'6
"�
#�
�'9
�
( �
��O
9�S
��5�
6
S��
�
�
��
��
��
��
��
� �� �� �� �� �� 3� �� 2� 8� ��� ��� ������
��2
3��
�
�
�
+��5!�'6
S�
�(# 99 % ����������%��'�+�%% Q�"�#� �'9 � ( ���O9�S�
��
��
��
��
��
3�
��
� �� �� �� �� 3� 2� ����%! ���% +��'+��� �- � # + '' �N
��5!��'6
"�#�
�'
9 �
( �
��O9
�(��
5� 6
�
�(# 99 % �����������'���'�+�%� Q�"�#� �'9 � ( ���O9�(�
2�
8����
�
(��
(��
(��
(��
(��
(3��� �� 8� ��� ��� ���
�32
��
���!�'
�
�
�
3
2��
��
� �� �� �� �� 3� 2� ���
�%! ���% +��'+��� �- � # + '' �N��5!��'6
"�#�
�'
9 �
( �
��O
9 �(��
5� 6
�
�(# 99 % �����������'���'�+�%� Q�"�#� �'9 � ( ���O9�(�
��
����
�42�43�4��4�
�� �� 8� ��� ��� ���
�
3
2
��
���!�'
��� ���
��
�
�
�
�4�
�4�
�4�
�
�
�
�%! ���% +��'+��� �- � # + '' �N��5!��'6
"�
#�
�'9
�
( �
��O
9�S
��5�
6
� �� �� �� �� �� 3� �� 2� 8� ��� ��� ������
��
2
3
�
�
�
�
�
+��5!�'6
��3�
2�
�
�
�
��3
��
��
��
���
2��
�(# 99 % ����������%��'�+�%% Q�"�#� �'9 � ( ���O9�S�
��
��
� �� �� �� �� 3� 2� ���
�%! ���% +��'+��� �- � # + '' �N��5!��'6
"�#�
�'
9 �
( �
��O
9 �(��
5� 6
�
�(# 99 % ����������%��'�+�%% Q�"�#� �'9 � ( ���O9�(�
��
��
�� �� 8� ��� ��� ���
�3
2
�����!�'
��� ���
��
�
�
(�
(��
�
�
�
��
��
� �� �� �� �� 3� 2� ���
�%! ���% +��'+��� �- � # + '' �N��5!��'6
"�#
� �
'9 �
(
���O
9 �(��
5� 6
�
�(# 99 % ����������%��'�+�%% Q�"�#� �'9 � ( ���O9�(�
��
��
�� �� 8� ��� ��� ���
�3
2
��
���!�'
��� ���
��
�
�
(�
(��
�
�
�
Tota
l tr
ykd
iffe
ren
s Δp
1-2
, (P
a)
Luftstrøm i kanalgrenen q2 (l/s)
T-stykke 100/100
Side udsugning Total trykdifferens Δp1-3
-60
-50
-40
-30
-20
-10
0
10
20
30
40
50
60
70
80
90
100
0 10 20 30 40 50 60 70 80 90 100 110120 130
Ko
kon
aisp
ain
e-er
o Δ
p1–
3 [P
a]
10
8
6
42 v1 [m/s]
1
3
2
T-kappale 125/125Poisto sivulta. Kokonaispaine-ero Δp1–3
Luftstrøm i kanalgrenen q3 (l/s)
T-stykke 125/125
Side udsugning Total trykdifferens Δp1-3
Tota
l tr
ykd
iffe
ren
s Δp
1-3
, (P
a)
Ilman tilavuusvirta runkokanavassa q2 [dm3/s]
Ko
kon
aisp
ain
e-er
o Δ
p1–
2 [P
a]
0,1
0,2
0,30,40,50,60,8
1
2
34568
10
20
304050
0 10 20 30 40 50 60 70 80 90 100 120 140150
10
8
6
4
2
v1 [m/s]
1
3
2
T-kappale 125/125Poisto sivulta. Kokonaispaine-ero Δp1–2
Tota
l tr
ykd
iffe
ren
s Δp
1-2
, (P
a)
Luftstrøm i kanalgrenen q2 (l/s)
T-stykke 125/125
Side udsugning Total trykdifferens Δp1-2
Luftstrøm i kanalgrenen q2 (l/s)
T-stykke 125/125
Side indblæsning Total trykdifferens Δp1-2
Tota
l tr
ykd
iffe
ren
s Δp
1-2
, (P
a)
Luftstrøm i kanalgrenen q3 (l/s)
T-stykke 125/100
Side udsugning Total trykdifferens Δp1-3
Tota
l tr
ykd
iffe
ren
s Δp
1-3
, (P
a)
Luftstrøm i kanalgrenen q3 (l/s)
T-stykke 125/100
Side udsugning Total trykdifferens Δp1-2
Tota
l tr
ykd
iffe
ren
s Δp
1-2
, (P
a)
Luftstrøm i kanalgrenen q3 (l/s)
T-stykke 125/100
Side indblæsning Total trykdifferens Δp1-3
Tota
l tr
ykd
iffe
ren
s Δp
1-3
, (P
a)
Luftstrøm i kanalgrenen q2 (l/s)
T-stykke 125/100
Side udsugning Total trykdifferens Δp1-3
Tota
l tr
ykd
iffe
ren
s Δp
1-3
, (P
a)
16 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0
��23��
� �� �� 3� 2� ��� ��� ��� �3� �2� ��� ���
+��5!�'6
99
��
8�
S��
��
��
��
��
��
2�
���
���
��
���
3�
�
�
�
�
99
��
56
� �� �� �� �� �� 3� �� 2� 8� ��� ��� ������
��2
3
�
�
�
�
�
+��5!�'6
��3�
2�
�
�
�
��3
��
��
��
���
2��
��
2
3
��
"�
#�
�'9
�
( �
��O
��(
��5�
6
�3��8�7+��5!�'6
� �� �� 3� 2� ��� ��� ��� �3� �2� ��� ���S3�
S��
S��
S��
S��
S��
�
��
��
��
��
��
3�
��
2�
8�
���
�
�
�
�%! ���% +��'+��� �- � # + '' �N��5!��'6
��
2
3
�
�
S��
S��
S��
S��
S��
�
��
��
��
��
��
3�
��
2�
8�
���
� �� �� �� �� �� 3� �� 2� 8� ��� ��� ������
�
�
�
+��5!�'6
��
2
3
�
�
��3�
2�
�
�
�
��3
��
��
��
���
2��
� �� �� 3� 2� ��� ��� ��� �3� �2� ��� ���
�
�
�
+��5!�'6
(3�
(��
(��
(��
(��
(��
�
��
��
��
��
��
3�
��
2�
8�
���
� �� �� �� �� �� 3� �� 2� 8� ��� ������ ����%! ���% +��'+��� �- � # + '' �N��5!��'6
"�
#�
�'9
�
( �
��O
9�S
��5�
6
��
2
3
�
� +��5!�'6
�
�
�
�(# 99 % ��3��������'���'�+�%� Q�"�#� �'9 � ( ���O9�S�
3
2��
��
�� �� �� �� 3� 2� ���
�%! ���% +��'+��� �- � # + '' �N��5!��'6
"�#
� �
'9 �
(
���O
9 �(��
5� 6
�
�(# 99 % ��3��������'���'�+�%� Q�"�#� �'9 � ( ���O9�(�
��
����
�42
�43�4��4�
�� �� 8� ���������
�
3 2
��
���!�'
������
��
�
�
�
�4�
�4�
�4��3�����2��8�
�4�
�48
�
�
�
�%! ���% +��'+��� �- � # + '' �N��5!��'6
"�
#�
�'9
�
( �
��O
9�S
��5�
6
� �� �� �� �� �� 3� �� 2� 8� ��� ��� ������
��
2
3
�
�
�
�
�
+��5!�'6
��3�
2�
�
�
�
��3
��
��
��
���
2��
�(# 99 % ��3�������%��'�+�%% Q�"�#� �'9 � ( ���O9�S�
�%! ���% +��'+��� ���#�# + '' �N��5!��'6
"�
#�
�'9
�
( �
��O
9�S
��5�
6
S��
�
�
��
��
��
��
��
�� �� �� �� �� 3� �� 2� 8� ��� ��� ��� �2�
��
2
3��
�
�
�
+��5!�'6
S�
�(# 99 % ��3�������%��'�+�%% Q�"�#� �'9 � ( ���O9�S�
�3�
Tota
l tr
ykd
iffe
ren
s Δp
1-3
, (P
a)
Luftstrøm i kanalgrenen q3 (l/s)
T-stykke 160/125
Side udsugning Total trykdifferens Δp1-3
Tota
l tr
ykd
iffe
ren
s Δp
1-2
, (P
a)
Luftstrøm i kanalgrenen q2 (l/s)
T-stykke 160/125
Side udsugning Total trykdifferens Δp1-2
Luftstrøm i kanalgrenen q3 (l/s)
T-stykke 160/125
Side indblæsning Total trykdifferens Δp1-3
Tota
l tr
ykd
iffe
ren
s Δp
1-2
, (P
a)
Luftstrøm i kanalgrenen q2 (l/s)
T-stykke 160/125
Side indblæsning Total trykdifferens Δp1-2
Tota
l tr
ykd
iffe
ren
s Δp
1-3
, (P
a)
Luftstrøm i kanalgrenen q3 (l/s)
T-stykke 160/160
Side udsugning Total trykdifferens Δp1-3
Tota
l tr
ykd
iffe
ren
s Δp
1-3
, (P
a)
Luftstrøm i kanalgrenen q3 (l/s)
T-stykke 160/100
Side udsugning Total trykdifferens Δp1-3
Tota
l tr
ykd
iffe
ren
s Δp
1-3
, (P
a)
Luftstrøm i kanalgrenen q2 (l/s)
T-stykke 160/100
Side udsugning Total trykdifferens Δp1-2
Tota
l tr
ykd
iffe
ren
s Δp
1-2
, (P
a)
Luftstrøm i kanalgrenen q3 (l/s)
T-stykke 160/100
Side indblæsning Total trykdifferens Δp1-3
Tota
l tr
ykd
iffe
ren
s Δp
1-3
, (P
a)
Luftstrøm i kanalgrenen q2 (l/s)
T-stykke 160/100
Side indblæsning Total trykdifferens Δp1-2
Tota
l tr
ykd
iffe
ren
s Δp
1-2
, (P
a)
U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 17
��
2
3
�
�
� �� �� 3� 2� ��� ��� ��� �3� �2� ��� ����%! ���% +��'+��� �- � # + '' �N��5!��'6
"�
#�
�'9
�
( �
��O
��(
��5�
6
�
�
�
�
3
��
�
2
��
��
��
3�
���
��
2�
+��5!�'6
�(# 99 % ��3���3���%��'�+�%% Q�"�#� �'9 � ( ���O9�S�
�
�
�
��
2
3�
�
� �� �� 3� 2� ��� ��� ��� �3� �2� ��� ����%! ���% +��'+��� ���#�# + '' �N��5!��'6
"�
#�
�'9
�
( �
��O
��(
��5�
6
S��
�
��
�
��
��
��
S�
��
+��5!�'6
�(# 99 % ��3���3���%��'�+�%% Q�"�#� �'9 � ( ���O9�S�
�
�
�
��
2
3
�
�
� �� �� 3� 2� ��� ��� ��� �3� �2� ��� ����%! ���% +��'+��� ���#�# + '' �N��5!��'6
�4�
"�
#�
�'9
�
( �
��O
��(
��5�
6
�4�
�4��4�
�43
�
�4�
�42
�
��
3
��
�
2
��
������
�3��8�7+��5!�'6
�(# 99 % ��3���3����'���'�+�%� Q�"�#� �'9 � ( ���O9�S�
�
�
�
(3�
(��
(��
(��
(��
(��
�
��
��
��
��
��
3�
��
2�
8�
���
� �� �� �� �� �� 3� �� 2� 8� ��� ��� �3� ����%! ���% +��'+��� �- � # + '' �N��5!��'6
"�
#�
�'9
�
( �
��O
9�S
��5�
6
��
2
3
�
�+��5!�'6
�
�
�
�(# 99 % ������3����'���'�+�%� Q�"�#� �'9 � ( ���O9�S�
���
��
23
�
�
�� �� �� 3� 2� ��� ��� ��� �3� �2� ��� ����%! ���% +��'+��� ���#�# + '' �N��5!��'6
"�
#�
�'9
�
( �
��O
��(
��5�
6
�4�
�4��4�
�43
�
�4�
�42
�
��
3
��
�
2
��
������
�3��8�7+��5!�'6
�(# 99 % ������3����'���'�+�%� Q�"�#� �'9 � ( ���O9�S�
�
�
�
�4���� �3�
�%! ���% +��'+��� �- � # + '' �N��5!��'6
"�
#�
�'9
�
( �
��O
9�S
��5�
6
� �� �� �� �� �� 3� �� 2� 8� ��� ��� ������
��
2
3
�
�
�
�
�
+��5!�'6
��3�
2�
�
�
�
��3
��
��
��
���
2��
�(# 99 % ������3���%��'�+�%% Q�"�#� �'9 � ( ���O9�S�
��
23�
�
3� 2� ��� ��� ��� �3� �2� ��� ��� ��� �3� �2��%! ���% +��'+��� ���#�# + '' �N��5!��'6
"�
#�
�'9
�
( �
��O
��(
��5�
6
S��
�
��
�
��
��
��
S�
��
+��5!�'6
�(# 99 % ������3���%��'�+�%% Q�"�#� �'9 � ( ���O9�S�
�
�
�
Luftstrøm i kanalgrenen q2 (l/s)
T-stykke 160/160
Side udsugning Total trykdifferens Δp1-2
Tota
l tr
ykd
iffe
ren
s Δp
1-3
, (P
a)
Luftstrøm i kanalgrenen q3 (l/s)
T-stykke 160/160
Side indblæsning Total trykdifferens Δp1-3
Tota
l tr
ykd
iffe
ren
s Δp
1-2
, (P
a)
Luftstrøm i kanalgrenen q2 (l/s)
T-stykke 160/160
Side indblæsning Total trykdifferens Δp1-2
Tota
l tr
ykd
iffe
ren
s Δp
1-2
, (P
a)
Luftstrøm i kanalgrenen q3 (l/s)
T-stykke 200/160
Side udsugning Total trykdifferens Δp1-3
Tota
l tr
ykd
iffe
ren
s Δp
1-3
, (P
a)
Luftstrøm i kanalgrenen q2 (l/s)
T-stykke 200/160
Side udsugning Total trykdifferens Δp1-2
Tota
l tr
ykd
iffe
ren
s Δp
1-2
, (P
a)
Luftstrøm i kanalgrenen q3 (l/s)
T-stykke 200/160
Side indblæsning Total trykdifferens Δp1-3
Tota
l tr
ykd
iffe
ren
s Δp
1-3
, (P
a)
Luftstrøm i kanalgrenen q2 (l/s)
T-stykke 200/160
Side indblæsning Total trykdifferens Δp1-2
Tota
l tr
ykd
iffe
ren
s Δp
1-2
, (P
a)
18 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0
qVD = Luftstrøm, l/s
Val = Lufthastighed, m/s
PtD = Totalt tryktab for luft, Pa
ζτ = Total tryk træk koeffi cient, −
Lyddæmpernes lyddæmpning pr. oktav, ISO 7235:2003
STØJREDUKTION ΔL (dB)
Oktavbånd centerfrekvens (Hz)
Mål 63 125 250 500 1000 2000 4000 8000
125x300 2,0 6,5 9,5 15,5 11,0 7,5 8,0 6,0
125x650 5,0 14,5 15,5 23,5 33,0 24,5 22,0 15,5
125x1000 10,5 18,0 20,5 29,0 37,0 36,0 36,5 26,5
160x650 6,0 12,5 12,0 21,0 29,5 18,0 14,5 11,5
160x1000 10,5 17,0 16,0 25,0 30,5 27,5 23,0 16,5
Lyddæmperens tryktab, ISO 7235:2003
125x300 1 2 3 4 5
qVD / l/s 43,7 51,4 65,4 77,5 100,4
Val / m/s 3,6 4,2 5,3 6,3 8,2
PtD / Pa 2,5 3,5 5,6 7,9 13,2
ζτ / − 0,32 0,33 0,33 0,33 0,33
125x650 1 2 3 4 5
qVD / l/s 43,1 49,6 62,4 76,1 93,9
Val / m/s 3,5 4,0 5,1 6,2 7,7
PtD / Pa 5,2 6,9 10,3 15,0 22,3
ζτ / − 0,70 0,71 0,667 0,651 0,634
125x1000 1 2 3 4 5
qVD / l/s 39,4 51,9 66,4 77,5 98,4
Val / m/s 3,2 4,2 5,4 6,3 8,0
PtD / Pa 7,2 12,4 19,3 26,2 40,8
ζτ / − 1,17 1,15 1,10 1,09 1,06
160x650 1 2 3 4 5
qVD / l/s 71,1 86,6 104 127 157
Val / m/s 3,5 4,3 5,2 6,3 7,8
PtD / Pa 5,2 7,9 11,1 16,4 25,2
ζτ / − 0,70 0,71 0,696 0,686 0,689
160x1000 1 2 3 4 5
qVD / l/s 74,1 95,2 116 144 180
Val / m/s 3,7 4,7 5,8 7,2 8,9
PtD / Pa 9,2 15,0 22,6 34,8 55,4
ζτ / − 1,13 1,11 1,13 1,13 1,15
U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 19
Lyddæmpernes tryktab, ISO 7235:2003
USI-125-300, USI-125-650 og USI-125-1000
USI-160-650 og USI-160-1000
Kanal lufthastighed, m/s
Tota
lt t
ryk, P
a
Luftstrøm, l/s
Luft massefylde 1,2 kg/m³
Kana lufthastighed, m/s
Tota
lt t
ryk,
Pa
Luftstrøm, l/s
Luft massefylde 1,2 kg/m³
20 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0
Installation
Oversigt
Uponors ventilationskanaler og
-komponenter er lavet af polypro-
pylen plast. De har derfor lille vægt
og er lette at håndtere.
Kanalinstallationen må ikke udsæt-
tes for temperaturer under -15°C.
Kanalerne må ikke kastes, trækkes,
bules eller på anden vis beskadiges.
Kanalerne leveres fra fabrikken med
begge ender tillukkede og pakket
i plastposer og papkasser for har
holde dem rene. Kanalerne og kom-
ponenterne skal beskyttes ved at
holde kanalenderne lukkede og ved
at opbevare komponenterne i deres
respektive emballager, når de op-
bevares på arbejdspladsen. De skal
beskyttes mod lang tids påvirkning
af direkte sollys.
Fjern først endelukningen og
de beskyttende poser, når de
installeres. Åbne ender af præ-
installerede kanaler skal be-
skyttes med endepropper, som
skal forblive på plads, indtil
armaturerne er installerede og
justerede.
Monter passende anbragte rense
lemme i kanalerne for at befordre
rensning.
Kanalmontage
Skæring og samling af kanaler
Uponor kanalerne skal afskæres
vinkelret med en fi ntandet (1-2
mm) sav . Fjern savsmuld fra både
de ydre og de indre overfl ader, og
affas de indre kanter af skærefl aden
for at lette indsættelsen af samle-
stykkerne.
Kanalsamlinger, retningsændrin-
ger og forgreninger må kun udføres
med kanalkomponenter. Kompo-
nenterne er forsynet med paknings-
false i komponentmaterialet. Kana-
lerne har ingen false.
Udfør samlingen ved at skubbe ka-
nalen ind på samlestykket, indtil det
når samlestykkets stopkant. Udfør
samlingerne manuelt; komponen-
terne kan smøres med rent vand
eller vand tilsat lidt opvaskemiddel.
Samlingerne udføres uden skruer
eller nitter.
Dog skal lodrette sektioner un-
derstøttes, så deres vægt ikke
hviler på samlestykket. Hvis
man ikke kan bruge vinkelbeslag,
kan samlingen sikres med 8-10 mm
popnitter, hvis det er nødvendigt.
Skæring og samling af præ-
isolerede kanaler og kanalsek-
tioner
Præisolerede kanaler skæres sam-
men med isoleringen og samles på
samme måde som ikke-isolerede
kanaler og kanalsektioner. I nogle
tilfælde kan det være nødvendigt at
fjerne noget af isoleringen.
Fx ved gennemføring gennem en
dampspærre, skal varmeisoleringen
fjernes på den varme side af fl angen
gennem dampspærren, hvis der ikke
er behov for kondensisolering.
Tip!
Lav et installationsmærke 5 cm fra
kanalens åbning. Det sikrer, at røret
er skubbet helt ind, og at samlingen
er tæt.
Præ-isoleret rørStopkant
Læbering
Aluminumsspændbånd
Stopkant Læbering
Samlekomponent
Aluminiumsspændbånd
Præ-isoleret samlekomponent
Ekstra isolering
Ekstra isolering
Præ-isoleret prop
Præ-isoleret rørPræ-isoleret komponent
Rør
Samlekomponent
U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 21
1 = Flangepakning
2 = Dampspærre
3 = Kanal
1 = Flangepakning
2 = Dampspærre
3 = Kanal
Kanalføring gennem
dampspærre
Når en kanal skal føres gennem en
struktur med en dampspærre (fx
et tag), skal gennemføringshul-
let forsegles med en dampspærre
fl angepakning. Den ene side af
dampspærre fl angepakningen er
selvklæbende.
Flangepakningen installeres normalt
over dampspærren, så der er tæt
mellem den termiske isolering og
dampspærren.
• Rens fugtspærren for støv m.m.
Fjern den beskyttende plast fra
fl angepakningen og tryk den
hårdt mod fugtspærren ovenfra/
udefra (A).
• Med en skarp kniv, lav en åbning
i dampspærren, der svarer til stør-
relsen af fl angepakningens hul
(B). Sørg for at fl angepakningen
er trykket ind mod dampspærren
på begge sider.
• Skub/træk forsigtigt kanalen
gennem fl angepakningens hul
mens kanalen roteres (C).
• Før kanalen ind på sin endelige
plads, og forbind den til de øvrige
kanaler (D).
Kanalføring af præ-isolerede
kanaler gennem dampspærre
Ved afskæring af præ-isolerede ka-
naler, bemærk at isoleringsmateria-
let skal skæres et andet sted en den
aktuelle kanal.
Varmeisoleringen skal slutte på den
kolde side af dampspærrens fl an-
gepakning. Kanalsektionen på den
varme side af dampspærren kan
efterlades uisoleret, med mindre ka-
nalerne kræver installation af kon-
densisolering.
På den varme side af dampspærren,
fx i et forsænket loft, skal indblæs-
ningskanalen være polystyren-iso-
leret, hvis indblæsningsluften er af-
kølet eller kold, eller hvis luften ikke
er forvarmet om vinteren. I dette
tilfælde afskær polystyren-isolerin-
gen ved fl angepakningen, og for-
segl den lufttæt til dampspærrens
fl angepakning.
22 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0
Understøttelse
Understøttelse skal udføres med
støtter, der er konstrueret til venti-
lationskanaler.
Den største afstand mellem støt-
ter på vandrette kanaler er 1.500
mm. Der skal (desuden) installeres
en støtte ved hver samling/kom-
ponent.
Lodrette sektioner skal understøt-
tes, så deres vægt ikke hviler på
samlestykket. Også skråtstillede ka-
naler skal understøttes for at hindre
bevægelser under installationen af
armaturer eller ved rengøringen af
kanaler/armaturer.
Støtterne kan fx monteres på støt-
tepælen under kanalen.
Kanalerne skal også fastgøres øverst
på loftsstrukturen for at hindre det i
at fl ytte sig under rengøring.
Understøttelse af præ-isolerede
kanaler
Præ-isolerede kanaler understøt-
tes på nøjagtig samme måde som
uisolerede kanaler. Bemærk dog,
at isoleringen ikke må skæres ved
støttepunktet. I stedet skal støtten
placeres udenpå isoleringen. I dette
tilfælde skal der benyttes støtter
med en større diameter.
1 = Støtte ved nedre
tagafstivning
2 = Isoleret (50 mm) kanal
3 = T-stykke
4 = Støttepæl (hvis støtten
ikke er monteret på tag
afstivningen)
5 = Støtte
Eksempel på understøttelse af en loftsmonte-
ret kanal og et T-stykke.
1 = Kanal
2 = Støtte
3 = Nedre tagafstivning
4 = Nedsænket loft
Eksempel på understøttelse af en kanal over
et forsænket loft.
1 = Kanal + termisk isolering
LE5 (15+50)
2 = Støtte
3 = Støtte ved øvre tagafstiv-
ning
Eksempel på understøttelse af en isoleret kanal
på et loft. Mellemrum mellem støtter maks.
1.500 mm.
1 = Kanal + termisk isolering
2 = Støtte
3 = Nedre tagafstivning
4 = Nedsænket loft
Eksempel på understøttelse af en kanal over
et forsænket loft.
Næstestøttepunktmax. 1500 mm
U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 23
Isolering
Isoleringens tykkelse er specifi ceret
i ventilationsplanen. Normale isole-
ringstykkelser er som følger:
Varme rum (indenfor damp-
spærren):
• Indblæsnings og udsugnings
luftkanaler har ikke behov for
isolering undtagen kanaler inde i
saunalofter, som skal termisk iso-
leres med 50 mm mineraluld uden
overfl adeafslutning. Hvis indblæs-
ningsluften kan være afkølet, skal
indblæsningsluftkanalerne være
isoleret med ekspanderet PE plast.
Hvis indblæsningsluften ikke er for-
varmet om vinteren, skal kanalerne
være isoleret med ekspanderet PE-
plast.
• Udendørs og afkastluftkana-
ler skal installeres med ekspanderet
PE plast isolering, der fungerer som
kondensisolering.
Uopvarmede områder (udenfor
dampspærren)
• Indsugnings- og afkastluft-
kanaler samt friskluft- og ud-
sugningskanaler, som er anbragt
indenfor den yderste tagisolering,
hvor der er mindst 100 mm løst mi-
neraluldsfyld, skal kondens- og var-
meisoleres med 15 mm ekspande-
ret polystyren. Bemærk, at i dette
tilfælde skal indblæst mineraluld
være anbragt i den øverste del af
tagkonstruktionen.
• Alternativt skal der bruges 50 mm
mineraluld uden overfl adeafslutning
som kanalisolering af udsugnings-,
indsugnings- og afkast-kana-
ler, som er anbragt indenfor den
yderste tag-varmeisolering, hvor
der er mindst 100 mm indblæst løs
isolering.
• Indsugnings- og afkast-luftar-
maturer, der er placeret over den
yderste loftsisolering, skal varme-
isoleres med 15 mm ekspanderet
polystyren + 50 mm mineraluld
uden overfl adeafslutning eller 50 +
50 mm mineraluld uden overfl ade-
afslutning.
• Udsugnings-luftarmaturer, der er
placeret over den yderste loftsiso-
lering, kan varmeisoleres med 50
mm mineraluld uden overfl adeaf-
slutning.
• Friskluftsarmaturer, der er placeret
over den yderste loftsisolering, kan
varmeisoleres med 50 mm mineral-
uld uden overfl adeafslutning.
Når man isolerer kanaler på kolde
steder indenfor loftets termiske
isolering med ekspanderet PE plast,
skal loftets termiske isolering være
altid være baseret på mineraluld.
Men hvis den termiske isolering af
kanalerne er med mineraluld, må
loftet være isoleret med et vilkårligt
lovligt isoleringsmateriale på mar-
kedet.
Isoleringen er svøbt tæt rund om
kanalerne og fastgjort med ståltråd,
strips eller lignende.
Kondensisoleringen af kanalerne er
implementeret med 15 mm ekspan-
deret PE plast, som er ført ind over
kanalen.
Isoleringen kan også være åbnet
lodret, viklet rundt om kanalen og
samlet med limning. Luk de tværgå-
ende og lodrette samlinger tæt med
kontaktlim.
Isoleringen af præ-isolerede kanaler
er tæt, når enden af den præ-iso-
lerede kanal med intern samling
er forbundet meden anden intern
samling. Samlingens tæthed sikres
med to aluminiumsspændbånd.
Præisolerede samlinger, kanaler og
sektioner er installeret korrekt når
de præ-isolerede kanaler er skub-
bet ind, indtil det når stopkanten.
Samlingens tæthed sikres med et
aluminiumsspændbånd.
24 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0
Kanal isoleringsmuligheder
Kanaler i et varmt rum, i nedsænket
loft eller i en kasse
Lufttemperaturen i kanalen er over + 10 grader
• Udsugningskanal
• Luftforsyningskanal
Ingen isolering Dampspærre
Lufttemperaturen i kanalen er under + 10 grader
• Udeluftkanal til ventilationsenhed• Udsugningskanal fra ventilationsenhed• Luftforsyningskanal
Dampspærre
15 mm ekspanderet isolering LE4
Kanaler i kolde rum
(loft, forsænket loftisolering eller over den)
• Luftforsyningskanal
• Udsugningskanal
• Udeluft til ventilationsenhed
• Udsugningsluft fra
ventilationsenhed
Dampspærre Dampspærre
Dampspærre
Tagbjælke Tagbjælke
Kanaler i løs mineraluld eller tilsvarende Isoleringsmaterialet er PE ekspanderet polystyren LE 4 eller 50 mm mineraluld uden overfl adeafslutning LE3.
Dampspærre
I et koldt rum over lofts-isoleringen er kanalerne isoleret med 15 mm ekspanderet polystyren+ 50 mm mineraluld uden overfl adeafslutning LE5 eller 50 + 50 mm mineral-uld uden overfl adeafslutning LE2.
Dampspærre Dampspærre
U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 25
Installation og indstilling af luftarmaturer
Oversigt
Installer og indstil først armaturerne
efter den afsluttende rengøring af
arbejdspladsen.
Ventilationssystemet må først ta-
ges i brug, når bygningen er helt
færdig.
Tilslutning af luftarmaturer til kanalerne
1 = Kanal
2 = Dampspærre fl angepakning3 = Kanalsektion til afskæring
4 = Det endelige loft
5 = Armatur
6 = Monteringsskrue
A. Afskær kanalen til niveauet for
det endelige loft med en fi ntandet
sav eller end kanal skæretang. Fast-
gør kanalen indefra med to monte-
ringsskruer.
B. Indsæt armaturet i kanalen. Ar-
maturet låser selv til kanalen, og
montageproceduren er færdig. Be-
mærk venligst: Hvis det loftsmon-
terede armatur er monteret på en
komponent i stedet for en kanal,
skal kanalpakningen skæres tættere
på langs den punkterede linje med
en saks eller en skarp kniv.
C. Indblæsnings- og udsug-
ningsarmaturer er i saunaer for
loftsmontage er forsynet med mon-
teringsrammer, der skal fastgøres til
loftsstrukturen med skruer. Installer
armaturet i rammen ved at dreje
det. Loftsmonterede rammer, der
er installeret over saunaovnen, skal
altid være sikret med skruer.
D. Det loftsmonterede armaturs
(ø 125) krave er en ophøjet ring,
som fører den udgående luft gen-
nem loftet. Dette forhindrer støv i
indeluften i at komme op, og det
holder loftet rent. Den ophøjede
krave er velegnet til både nye byg-
ninger og renovering.
Installation af kraven
Afskær kanalen 50 mm under lof-
tets underside. Installer kraven på
ventilen. Skub ventilen op på kana-
len, så kraven tætter mellem venti-
len og loftet.
Hvis kanalen er afskåret til overfl a-
dens niveau, skal kanalen forlæn-
ges. Skær kanalpakningen tættere
på langs den punkterede linje, og
installer armaturet og kraven som
angivet i trin B.
Diameter 125
Produktkode 1046218
E. Installer det vægmonterede
armatur ved at skubbe det ind i
kanalen, som er afskåret i niveau
med væggens overfl ade. Armaturets
dæksel kan fjernes ved at vride det
af med en skruetrækker. Basispla-
den er forsynet med huller til mon-
teringsskruerne.
"����)'� �,�
Uponors ventilationssystemarma-
turer er klar til brug som indblæs-
nings- eller udsugningsarmaturer
med Uponor kanaler.
Udvidelse
Krave
Armatur
A. B. C.
� 3 �
�
�
� 3 �
�
�
� 3 �
�
�
Fastgørelseshuller
26 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0
Friskluftrist
Friskluftsristene er forsynet med
let udtagelig netkassette eller in-
sektnet.
Netkassetten skal renses regelmæs-
sigt, op til én gang om måneden på
de varme årstider (april-oktober).
Behovet for rensning kan variere
stærkt afhængig af bygningens
placering.
Det hvide ABS plastgitter kan males
med fx sprøjtemaling, og grunding
er normalt ikke nødvendig. Kon-
troller altid først, om malingen kan
bruges på ABS plast. Før malingen,
rens overfl aden med fx acetone.
Friskluftsventil til vægmontage
(udendørs luftarmatur med fi lter i
ventilation med mekanisk udblæs-
ning)
Armaturet installeres i et hul,
ø 106 mm, boret eller udsavet over
vinduet. Armaturet åbnes og lukkes
med træksnoren.
Installation
Åbn det indvendige armatur med
træksnoren, og skru dækslet af. Ro-
ter friskluftristen lidt mod uret, og
træk det af. Afkort kanalforlængel-
sen, så den passer til murens tykkel-
se. Installer kanalen og selve arma-
turet, og fastgør dem med skruer.
Skru friskluftristen og dækslet på
igen, og juster armaturåbningen.
Fastgør friskluftristens holder med
skruer. Installer friskluftristen ved
at presse det ind på friskluftristens
holder.
Vedligeholdelse
Rens fi lteret to gange om året med
varmt vand.
Friskluftsventil til ventilationshul
(udendørs luftarmatur med fi lter i
ventilation med mekanisk udblæs-
ning)
Installer armaturet i et hul,
ø 106 mm, boret eller udsavet over
ventilhullet.
Installation
Åbn den indvendige ventil med
træksnoren, og skru dækslet af. Ro-
ter friskluftristen lidt mod uret, og
træk det af.
Installer selve armaturet og det løse
bunddæksel med skruer. Hvis muren
ved ventilhullet er over 90 mm tyk,
forlæng armaturet med den medle-
verede forhøjelsesring.
Skru friskluftristen og dækslet på
igen, og juster armaturåbningen ved
at dreje dækslet.
Luftføring
Luftføringen kan rettes opad, mod
venstre eller mod højre. Hvis der fx
er en radiator til venstre rettes luft-
føringen mod venstre.
Luftføringen kan trækkes ud for at
drejes ved først at åbne armatu-
ret ved træksnoren og derpå skrue
dækslet af.
Vedligeholdelse
Rens fi lteret to gange om året med
varmt vand.
U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 27
Spalteventil
(Friskluftventil med fi lter til luftind-
tag ved mekanisk ventilation med
afkast.)
Installer armaturet enten i en 19 x
250 mm spalte i toppen af vindues-
rammen eller mellem vinduesram-
men og muren. Hvis spalteventilen
er monteret over en radiator, skal
den indre kant vende opad og den
ydre kant vende nedad.
Vedligeholdelse
Rens fi lteret to gange om året med
varmt vand. Træk fi lteret i armatu-
rets rørsektion ud, efter at lukkela-
mellerne er fjernet ved at løsne de
to monteringsskruer.
Justering af armaturer
Juster armaturerne som vist i juste-
ringskurverne på side 24-25 ved at
rotere armaturskiven (loftsmonte-
rede armaturer) eller ved at åbne
nogle rækker huller (vægmonterede
armaturer). Trykdifferensen måles
på de punkter, der er vist på de til-
hørende tegninger. Efter justerin-
gen lås armaturernes position med
låseskruerne.
Et manometer kan også bruges til
at justere og kontrollere justerin-
gen af armaturerne. I dette tilfælde
er armaturets lukkede tilstand, dvs.
armaturets 0-niveau, følgende:
- Luftindblæsning, loft, ø 125:
+10 mm
- Luftindblæsning, loft, ø 100:
+10 mm
- Luftudsugning, loft, ø 125:
-3 mm
- Luftudsugning, loft, ø 100:
-1 mm
- Saunaarmatur, loft, ø 125:
+8 mm
Armaturerne præ-justeres før den
endelige justering og måling. De
præ-justerede værdier ved et tryk-
tab over armaturet på 20 Pa ses i
tabellerne på næste side.
Efter installationen af luftindblæs-
ningsarmaturerne, kan lukkelamel-
lerne fjernes fra rammen med en
skarp kniv.
- Mål trykdifferensen på punkterne
vist i tegningen.
- Juster ved at rotere ventilspind-
len, stigning 1 mm/omdrejning.
- 0-niveau = lukket armatur.
- Sidehuller åbne/lukkede.
- Åbn det nødvendige antal huller
med en saks eller kniv.
- Geninstaller lukkelamellerne ved
at trykke dem på plads.
� � !��� �'
� � !��� ��
��%#��' �
Friskluftsventil
(Friskluftventil med fi lter til luftind-
tag ved mekanisk ventilation med
afkast.)
Armaturet installeres i et hul,
ø 106 mm, boret eller udsavet midt
over vinduet.
Trykmåling
Lukkelameller
Manometer
28 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0
Tabeller over armatur fabriksindstillinger, trykdifferens 20 Pa
Luftindblæsningsarmaturer
Udsugningsarmaturer
Udsugningsluft
l/s
Udsugningsarma-
tur 125
Omdr. åben
Udsugningsarma-
tur 100
Omdr. åben
Udsugningsluft
l/s
Udsugningsarma-
tur 125
Omdr. åben
Udsugningsarma-
tur 100
Omdr. åben
3 3 4 11 14 20
4 4 6 12 15
5 6 8 13 16
6 7 10 14 18
7 8 12 15 20
8 10 14 16 22
9 11 16 17 23
10 13 18 18 24
Indblæsningsluft l/s
Loft-monteret/sauna armaturer 125
Omdrejninger åben
Loft-monteret/sauna armaturer 100
Omdrejninger åben
Vægmonterede armaturer100 & 125
Sidehuller åben
Rækker af åbne huller
Vægmonterede armaturer100 & 125
Sidehuller luk-kede.
Rækker af lukkede huller
6 3 4 2 3
7 4 4 3 3
8 4 5 3 4
9 5 6 4 5
10 5 6 4 5
11 6 5 6
12 6 6 6
13 7 7 7
14 8 8 8
15 9 9 9
16 10 9 10
17 11 10 10
U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 29
"� ���#'� �,,�* ' ���!!
���
���
���
��
��
��
��
���UW�X
$���
�'9
�
( �
���
�������������������������3��8������
���UW�X���UW�X
���UW�X
"Y�
48
"Y�
43
"Y�
4�"
Y�48
"Y�
4�"
Y�4�
"� ���#'� �,,�* ' ���!!
���
���
���
��
��
��
��
���UW�X
$���
�'9
�
( �
���
�������������������������3��8������
���UW�X���UW�X
���UW�X
"Y�
48
"Y�
43
"Y�
4�"
Y�48
"Y�
4�"
Y�4�
"� ���#'� �,,�* ' ���!!
���
���
���
��
��
��
��$���
�'9
�
( �
���
��������������������������3���8������
���UW�X
���UW�X
���UW�X
���UW�X
"Y�
48
"Y�
4�
"Y�
4�"
Y�43
"Y�
4�"
Y�4�
"� ���#'� �,,�* ' ���!!
���
���
���
��
��
��
��$���
�'9
�
( �
���
��������������������������3���8������
���UW�X
���UW�X
���UW�X
���UW�X
"Y�
48
"Y�
4�
"Y�
4�"
Y�43
"Y�
4�"
Y�4�
Luftstrøm, trykdifferens og støjniveau
Luftindblæsning loftsarmaturer Ø100
OmdrejningerJusteringsposition mm
Mål
t tr
ykd
iffe
ren
s P
a
Luftindblæsning loftsarmaturer Ø125
OmdrejningerJusteringsposition mm
Mål
t tr
ykd
iffe
ren
s P
a
Sauna luftindblæsningsarmaturer Ø100
OmdrejningerJusteringsposition mm
Mål
t tr
ykd
iffe
ren
s P
a
Sauna luftindblæsningsarmaturer Ø125
OmdrejningerJusteringsposition mm
Mål
t tr
ykd
iffe
ren
s P
a
Udsugningsarmaturer Ø100
OmdrejningerJusteringsposition mm
Mål
t tr
ykd
iffe
ren
s P
a
Udsugningsarmaturer Ø125
OmdrejningerJusteringsposition mm
Mål
t tr
ykd
iffe
ren
s P
a
30 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0
Luftindblæsning vægarmaturer Ø100 med lukkede
sidehuller
Justeringsposition, rækker med åbne huller
Mål
t tr
ykd
iffe
ren
s P
a
Luftindblæsning vægarmaturer Ø125 med lukkede
sidehuller
Justeringsposition, rækker med åbne huller
Mål
t tr
ykd
iffe
ren
s P
a
Luftindblæsning vægarmaturer Ø100 med åbne
sidehuller
Mål
t tr
ykd
iffe
ren
s P
a
Luftindblæsning vægarmaturer Ø125 med åbne
sidehuller
Mål
t tr
ykd
iffe
ren
s P
a
Justeringsposition, rækker med åbne huller
Justeringsposition, rækker med åbne huller
Luftstrøm, trykdifferens og støjniveau
U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 31
Luftstrøm og trykdifferens
Friskluftsarmatur ø100 Spalteventil 18x245x340
Tryk
fors
kel, P
a
Tryk
fors
kel, P
a
Uden fi lter
Med fi lter
Friskluftsriste
Mål
t tr
ykfo
rskel P
a
Mål
t tr
ykfo
rskel P
a
Mål
t tr
ykfo
rskel P
a
32 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0
Bemærkninger
U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 33
Bemærkninger
34 U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0
Bemærkninger
U P O N O R P L A N LÆ G N I N G S - O G I N S TA L L AT I O N S V E J L E D N I N G 2 0 1 0 35
Uponor A/S
Uponor VVS
Banemarksvej 2A
2600 Glostrup
T 4326 3400
F 4343 1011
W www.uponor.dk