Substrate Viking SuperStrand or F11 Roofing ply Viking CertainTeed Underlay refer CT17 and CT18 for requirements Truss or Rafter Viking CertainTeed Shingles Nail fixed to Plywood or SuperStrand sarking Refer to Viking CertainTeed specification for fixing details in required wind-zone Step Flashing refer CT09 Barge detail refer CT06 Vented ridge refer CT02 Drip-edge refer CT01 Valley details refer CT07 and CT08 Pipe penetration refer CT15 Viking CertainTeed Shingles General Roof details Details 17/11/2016 DRAWING STATUS ISSUE Detail Ref: DATE DRAWN Not to Scale DRAWING TITLE NOTES: Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz INFORMATION ONLY Viking Substrate Indicative Only A

Upload: others

Post on 19-Jun-2020

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Vented ridge or F11 Roofing ply · Viking CertainTeed Shingles Viking CertainTeed Underlay Truss or Rafter Nog to support edge of substrate Nail vent to Plywood @ 600mm centres Viking

Substrate Viking SuperStrandor F11 Roofing ply

Viking CertainTeed Underlayrefer CT17 and CT18 for

requirements

Truss or Rafter

Viking CertainTeed ShinglesNail fixed to Plywood or SuperStrand sarking

Refer to Viking CertainTeed specification for fixing details in required wind-zone

Step Flashingrefer CT09

Barge detailrefer CT06

Vented ridgerefer CT02

Drip-edgerefer CT01

Valley detailsrefer CT07 and CT08

Pipe penetrationrefer CT15

Viking CertainTeed ShinglesGeneral Roof details Details

17/11/2016

DRAWING STATUS

ISSUEDetail Ref:DATE

DRAWN

Not to Scale

DRAWING TITLE NOTES:

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

INFORMATION ONLY

Viking

Substrate Indicative OnlyA

Page 2: Vented ridge or F11 Roofing ply · Viking CertainTeed Shingles Viking CertainTeed Underlay Truss or Rafter Nog to support edge of substrate Nail vent to Plywood @ 600mm centres Viking

Metal drip-edge flashing

CertainTeed Shingles

Viking Underlay

Plywood or SuperStrand sarkingSubstrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

Timber nog required to support bottom edge of substratenot to restrict airflow for ventilation

Airflow gap 10mm above top of Fascia

Air flow for vented intake

30mm

10mm

Viking CertainTeed ShinglesVented Drip-edge Detail CT01 CT01

17/11/2016

DRAWING STATUS

ISSUEDetail Ref:DATE

DRAWN

Not to Scale

DRAWING TITLE NOTES:

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

INFORMATION ONLY

Viking

Substrate Indicative OnlyA

Page 3: Vented ridge or F11 Roofing ply · Viking CertainTeed Shingles Viking CertainTeed Underlay Truss or Rafter Nog to support edge of substrate Nail vent to Plywood @ 600mm centres Viking

AirflowAirflow

Air gap20mm

minimum

Air gapmin. 20mm

AirflowAirflow

Viking CertainTeedLow Profile Ridge Vent 16mm depth

Viking CertainTeed Shingles

Viking CertainTeed Underlay

Viking CertainTeed Ridge Vent 25mm depthwith ridge Cap installed

Plywood orSuperstrandsarking

Viking CertainTeed ShinglesRidge Vent Detail CT02 CT02

17/11/2016

DRAWING STATUS

ISSUEDetail Ref:DATE

DRAWN

Not to Scale

DRAWING TITLE NOTES:

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

INFORMATION ONLY

Viking

Substrate Indicative OnlyA

Page 4: Vented ridge or F11 Roofing ply · Viking CertainTeed Shingles Viking CertainTeed Underlay Truss or Rafter Nog to support edge of substrate Nail vent to Plywood @ 600mm centres Viking

Min. 20mm unrestricted Air flow

min. 20mm

Refer Table 7 E2/AS1

Viking CertainTeed Shingles

Viking CertainTeed Underlay

Truss or Rafter

Nog to support edgeof substrate

Nail vent to Plywood@ 600mm centres

Viking CertainTeed Ridge Vent DDE265divided in half

NOTE: Min. shingle roof pitch is 9°

Viking CertainTeed ShinglesMonopitch Ridge Vent Detail CT03 CT03

17/11/2016

DRAWING STATUS

ISSUEDetail Ref:DATE

DRAWN

Not to Scale

DRAWING TITLE NOTES:

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

INFORMATION ONLY

Viking

Substrate Indicative OnlyA

Page 5: Vented ridge or F11 Roofing ply · Viking CertainTeed Shingles Viking CertainTeed Underlay Truss or Rafter Nog to support edge of substrate Nail vent to Plywood @ 600mm centres Viking

Airflow uninhibited Roof Cavity (min 25mm)

Viking CertainTeed Shingles

Viking CertainTeed Underlay

Viking Shingle Nails32 x 3.2mm S/S 10mm round Flathead

Viking Waterproof MembraneDiscuss with Viking Roofspecbest option to secure to metal flashing

Optional Dress Shingle if required for astheticsadhered with Viking Pitched Roofing Sealant SES013Ø20mm @ 100mm centres

Metal Flashing with hemmed edgefor added strength to hold firm over vent

Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

* Alternative ventilationconsider venting through the membrane roof area if roof structure allows good unrestricted airflow.Allow additional cavity vent for every 50m2 pitched roof area

Air gap20mm Min.

*Viking CertainTeed RidgeVent DDE265 divided in half

Viking CertainTeed ShinglesMansard Vented edge Detail CT04 CT04

17/11/2016

DRAWING STATUS

ISSUEDetail Ref:DATE

DRAWN

Not to Scale

DRAWING TITLE NOTES:

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

INFORMATION ONLY

Viking

Substrate Indicative OnlyA

Page 6: Vented ridge or F11 Roofing ply · Viking CertainTeed Shingles Viking CertainTeed Underlay Truss or Rafter Nog to support edge of substrate Nail vent to Plywood @ 600mm centres Viking

Airflow Roof Cavity (min 25mm)

Nail to Substrate @ 600mm centres

Viking Skirt Vent DDE200

Viking CertainTeed Shingles

Viking CertainTeed Underlay

150mm

20mm

Viking CertainTeed ShinglesLower Vented Roof Detail CT05 CT05

17/11/2016

DRAWING STATUS

ISSUEDetail Ref:DATE

DRAWN

Not to Scale

DRAWING TITLE NOTES:

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

INFORMATION ONLY

Viking

Substrate Indicative OnlyA

Page 7: Vented ridge or F11 Roofing ply · Viking CertainTeed Shingles Viking CertainTeed Underlay Truss or Rafter Nog to support edge of substrate Nail vent to Plywood @ 600mm centres Viking

refer Table 7 E2/AS1

15mm overhang

70mm

Viking CertainTeed Shingles

Barge Flashing

Viking Pitched Roofing Sealant SES013

Viking CertainTeed Underlay

Viking CertainTeed ShinglesBarge edge Detail CT06 CT06

17/11/2016

DRAWING STATUS

ISSUEDetail Ref:DATE

DRAWN

Not to Scale

DRAWING TITLE NOTES:

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

INFORMATION ONLY

Viking

Substrate Indicative OnlyA

Page 8: Vented ridge or F11 Roofing ply · Viking CertainTeed Shingles Viking CertainTeed Underlay Truss or Rafter Nog to support edge of substrate Nail vent to Plywood @ 600mm centres Viking

250mm450mm

50mmNOTE: Valley Detail

refer also detail CT08iso

Viking CertainTeed Shingles

Viking Shingle Nails32 x 3.2mm S/S 10mm round Flathead

Viking CertainTeed Hip Cap Shingle

Viking CertainTeed Underlay

Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

Apply a full width (900mm) of VikingUnderlay vertical to Plywood Roofing

Substrate Valley

Viking Underlay applied over firstshingle layer. Minimum 50mmoverlap over Shingle required.

Viking CertainTeed UnderlayMinimum 150mm overlap

Pitched Roofing Sealantno nails within 150mm of Valley center line

Viking CertainTeed ShinglesHip & Valley Detail CT07 CT07

17/11/2016

DRAWING STATUS

ISSUEDetail Ref:DATE

DRAWN

Not to Scale

DRAWING TITLE NOTES:

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

INFORMATION ONLY

Viking

Substrate Indicative OnlyA

Page 9: Vented ridge or F11 Roofing ply · Viking CertainTeed Shingles Viking CertainTeed Underlay Truss or Rafter Nog to support edge of substrate Nail vent to Plywood @ 600mm centres Viking

DO NOT nail within 150mm of valley CentrelineViking Underlay Laps

Embed each shingle in 2 beads of

Viking Roofing Sealant SES013CUT (50mm) diagonally off upper corner

of trimmed shingle and removeREMOVEtrimmed shingle

cL

Line Valley by centering (914mm wide)

Viking Peel & Stick Underlay

NoteLay Shingles on smaller roof area,

across valley and onto adjoining

roof area at least 300mm

Viking CertainTeed ShinglesIsometric Valley Detail CT08iso CT08iso

17/11/2016

DRAWING STATUS

ISSUEDetail Ref:DATE

DRAWN

Not to Scale

DRAWING TITLE NOTES:

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

INFORMATION ONLY

Viking

Substrate Indicative OnlyA

Page 10: Vented ridge or F11 Roofing ply · Viking CertainTeed Shingles Viking CertainTeed Underlay Truss or Rafter Nog to support edge of substrate Nail vent to Plywood @ 600mm centres Viking

100mm Apron Flashing

10mm Gap for water runoff

Step-Flashing under every individual Shingle. withmin.100mm overlap between flashings.Flashings to be placed just above shingle sealant line

Viking CertainTeed Shingles

No nailing through step flashinguse 20mm compressed spots of sealant

Corner lap to be securedwith Viking 76mm Lap Tape

Viking Butylclad Waterproofing MembraneStep Flashing 150mm wide

Viking CertainTeed Shingles

Viking CertainTeed Underlay

Pitched Roofing Sealant SES013no nails through Step Flashings

150m

m150mm

Min. 100mm

150mm

150mm

Viking CertainTeed ShinglesUpstand with Step Flashing Detail CT09 CT09

17/11/2016

DRAWING STATUS

ISSUEDetail Ref:DATE

DRAWN

Not to Scale

DRAWING TITLE NOTES:

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

INFORMATION ONLY

Viking

Substrate Indicative OnlyA

Page 11: Vented ridge or F11 Roofing ply · Viking CertainTeed Shingles Viking CertainTeed Underlay Truss or Rafter Nog to support edge of substrate Nail vent to Plywood @ 600mm centres Viking

300mm wide Strip Butylclad Step-flashingminimum cover 150mm each on the upstand and shingle

Viking Kickout Flashing

Spouting

Viking CertainTeed ShinglesViking CertainTeed Underlay

Drip Edge Flashing

Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

Viking CertainTeed ShinglesDrip-edge with Diverter Detail CT10 CT10

17/11/2016

DRAWING STATUS

ISSUEDetail Ref:DATE

DRAWN

Not to Scale

DRAWING TITLE NOTES:

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

INFORMATION ONLY

Viking

Substrate Indicative OnlyA

Page 12: Vented ridge or F11 Roofing ply · Viking CertainTeed Shingles Viking CertainTeed Underlay Truss or Rafter Nog to support edge of substrate Nail vent to Plywood @ 600mm centres Viking

Viking CertainTeed selected Shingle

150m

m Ve

rtical

Heigh

t

150mm

Viking Waterproofing Membrane

Viking Waterproofing membrane detailover barge upstand

Dormer Roof

Viking CertainTeed ShinglesDormer to shingle junction Detail CT11 CT11

17/11/2016

DRAWING STATUS

ISSUEDetail Ref:DATE

DRAWN

Not to Scale

DRAWING TITLE NOTES:

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

INFORMATION ONLY

Viking

Substrate Indicative OnlyA

Page 13: Vented ridge or F11 Roofing ply · Viking CertainTeed Shingles Viking CertainTeed Underlay Truss or Rafter Nog to support edge of substrate Nail vent to Plywood @ 600mm centres Viking

Viking CertainTeed Shingles

Diverter Chased Apron Flashing by builder

Corner lap to be securedwith Viking 76mm Lap Tape

No nailing through step flashinguse 20mm compressed spots of CertainTeed sealant SES013 to secure

Step Flashing under ShinglesMinimum:100mm cover between flashings150mm upstand and 150mm on roof deck

Viking CertainTeed ShinglesChimney and Chase Flashing Detail CT12 CT12

17/11/2016

DRAWING STATUS

ISSUEDetail Ref:DATE

DRAWN

Not to Scale

DRAWING TITLE NOTES:

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

INFORMATION ONLY

Viking

Substrate Indicative OnlyA

Page 14: Vented ridge or F11 Roofing ply · Viking CertainTeed Shingles Viking CertainTeed Underlay Truss or Rafter Nog to support edge of substrate Nail vent to Plywood @ 600mm centres Viking

Viking CertainTeed Shingles

Chased Apron Flashing by builder

Corner lap to be securedwith Viking 76mm Lap Tape

No nailing through step flashinguse 20mm compressed spots of CertainTeed sealant SES013 to secure

Step Flashing under ShinglesMinimum:100mm cover between flashings150mm upstand and 150mm on roof deck

Diverter

Viking CertainTeed ShinglesAlternative Chimney Diverter CT12b CT12b

17/11/2016

DRAWING STATUS

ISSUEDetail Ref:DATE

DRAWN

Not to Scale

DRAWING TITLE NOTES:

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

INFORMATION ONLY

Viking

Substrate Indicative OnlyA

Page 15: Vented ridge or F11 Roofing ply · Viking CertainTeed Shingles Viking CertainTeed Underlay Truss or Rafter Nog to support edge of substrate Nail vent to Plywood @ 600mm centres Viking

Butylclad or metal Flashingrefer CT09 for side flashing

Viking CertainTeed Underlay

Viking CertainTeed Shingles

Aesthetic Tile adhered with 20mm spots ofSES013 CertainTeed Sealant

Generic skylight with proprietary cover flashings

min. 110mmupstand

Viking CertainTeed ShinglesSkylight Detail CT13 CT13

17/11/2016

DRAWING STATUS

ISSUEDetail Ref:DATE

DRAWN

Not to Scale

DRAWING TITLE NOTES:

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

INFORMATION ONLY

Viking

Substrate Indicative OnlyA

Page 16: Vented ridge or F11 Roofing ply · Viking CertainTeed Shingles Viking CertainTeed Underlay Truss or Rafter Nog to support edge of substrate Nail vent to Plywood @ 600mm centres Viking

Solar Panel fixing Bracket withsealed fasteners under Shingles

Solar Panel or similar

Viking CertainTeed Shinglesto cover brackets and fasteners

Structural support for fixing brackets

Viking CertainTeed ShinglesSolar Panel Fixings CT14 CT14

17/11/2016

DRAWING STATUS

ISSUEDetail Ref:DATE

DRAWN

Not to Scale

DRAWING TITLE NOTES:

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

INFORMATION ONLY

Viking

Substrate Indicative OnlyA

Page 17: Vented ridge or F11 Roofing ply · Viking CertainTeed Shingles Viking CertainTeed Underlay Truss or Rafter Nog to support edge of substrate Nail vent to Plywood @ 600mm centres Viking

Viking Pipe Boot placed over pipe and set inViking Roof sealant SES013

Upper and Side Shingles overlap flange andare set in Viking Roof sealant SES013

Plumber to overflash pipe boot

Lower Part of Flange overlaps lower ShinglesSpot seal with 20mm of pitched roofing sealant at 100mm centres

Step 1 Step 2

Viking CertainTeed ShinglesPipe Penetration Detail CT15 CT15

17/11/2016

DRAWING STATUS

ISSUEDetail Ref:DATE

DRAWN

Not to Scale

DRAWING TITLE NOTES:

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

INFORMATION ONLY

Viking

Substrate Indicative OnlyA

Page 18: Vented ridge or F11 Roofing ply · Viking CertainTeed Shingles Viking CertainTeed Underlay Truss or Rafter Nog to support edge of substrate Nail vent to Plywood @ 600mm centres Viking

Viking CertainTeed Shingles Viking CertainTeed Underlay

Truss or Rafter

Substrate as per Viking membrane specification

Viking GM torch-on2 Layer waterproofing System

50mm 200mm

upstandverticalheight

Viking CertainTeed Starter Shingle

Viking CertainTeed ShinglesMembrane roof to Pitched roof CT16 CT16

17/11/2016

DRAWING STATUS

ISSUEDetail Ref:DATE

DRAWN

Not to Scale

DRAWING TITLE NOTES:

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

INFORMATION ONLY

Viking

Substrate Indicative OnlyA

Page 19: Vented ridge or F11 Roofing ply · Viking CertainTeed Shingles Viking CertainTeed Underlay Truss or Rafter Nog to support edge of substrate Nail vent to Plywood @ 600mm centres Viking

Viking CertainTeed Shingles

Truss or Rafter

Viking CertainTeed Underlay

Viking Peel & Stickwaterproofing membrane 400mm minimum

Min. 200mm

Min. 20

0mm

Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

Viking Peel & StickNot to be placed over Shingle sealant line

*Min. 9° pitch fo

r shingle roofs

* Roof pitch 9°- 12° use only Viking Peel & Stick underlay.Roof Pitch 12°- 18°use either Viking Peel & Stick or double layer of Viking Synthetic UnderlayRoof Pitch 18° + single layer of Viking Synthetic Underlay is suitable

Viking CertainTeed ShinglesShingle Change in Pitch Detail CT17 CT17

17/11/2016

DRAWING STATUS

ISSUEDetail Ref:DATE

DRAWN

Not to Scale

DRAWING TITLE NOTES:

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

INFORMATION ONLY

Viking

Substrate Indicative OnlyA

Page 20: Vented ridge or F11 Roofing ply · Viking CertainTeed Shingles Viking CertainTeed Underlay Truss or Rafter Nog to support edge of substrate Nail vent to Plywood @ 600mm centres Viking

Viking CertainTeed underlay

Aesthetic Tile adhered with 20mm spots ofSES013 CertainTeed Sealant

0.55mm Colour Steel Flashing with Birdsbeakor 1mm Butyl rubber flashingrefer Table 7 E2/AS1 for coverage

Viking CertainTeed Shingles

*Min. 9° Pitch

* Roof pitch 9°- 12° use only Viking Peel & Stick underlay.Roof Pitch 12°- 18°use either Viking Peel & Stick or double layer of Viking Synthetic UnderlayRoof Pitch 18° + single layer of Viking Synthetic Underlay is suitable

Viking CertainTeed ShinglesNon-Vented Mansard / Change in Pitch CT18 CT18

17/11/2016

DRAWING STATUS

ISSUEDetail Ref:DATE

DRAWN

Not to Scale

DRAWING TITLE NOTES:

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

INFORMATION ONLY

Viking

Substrate Indicative OnlyA

Page 21: Vented ridge or F11 Roofing ply · Viking CertainTeed Shingles Viking CertainTeed Underlay Truss or Rafter Nog to support edge of substrate Nail vent to Plywood @ 600mm centres Viking

Viking CertainTeed Shingles

Metal Valley Flashing

Viking CertainTeed Underlay

Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

Structural framing

Valley Nogging

250mm

Viking CertainTeed ShinglesAlternative Open Valley Detail CT19 CT19

17/11/2016

DRAWING STATUS

ISSUEDetail Ref:DATE

DRAWN

Not to Scale

DRAWING TITLE NOTES:

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

INFORMATION ONLY

Viking

Substrate Indicative OnlyA

Page 22: Vented ridge or F11 Roofing ply · Viking CertainTeed Shingles Viking CertainTeed Underlay Truss or Rafter Nog to support edge of substrate Nail vent to Plywood @ 600mm centres Viking

MIN. 100mm Cover over membrane

Substrate to comply with current Viking Roofspec Masterspec specificationSubstrate Checksheet available from www.vikingroofspec.co.nz

Viking Waterproofing Membrane

Min fall in gutter 1:100 to external spoutingor specified Viking Proprietary outlet

Viking Membrane to provide150mm of vertical height

Note: No fixings through membrane below 150mm

Viking CertainTeed ShinglesMi

n. 15

0mm

upsta

nd

Viking CertainTeed ShinglesInternal Gutter CT20 CT20

17/11/2016

DRAWING STATUS

ISSUEDetail Ref:DATE

DRAWN

Not to Scale

DRAWING TITLE NOTES:

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

INFORMATION ONLY

Viking

Substrate Indicative OnlyA

Page 23: Vented ridge or F11 Roofing ply · Viking CertainTeed Shingles Viking CertainTeed Underlay Truss or Rafter Nog to support edge of substrate Nail vent to Plywood @ 600mm centres Viking

NOTE:This detail is to show a methodology forSaddle-flashings and kick-out diverters atjunctions.These Saddle-flashings are not supplied byViking Roofspec as they are fabricated forspecific junctions by others to fit variousjunctions and cladding needs.

Stage 1 Flexible Flashing tape adheredto wall underlay at rear of cavityminimum 50mm to all surfaces

Step 3Fabricated Saddle-flashing fitted over flexible

flashing tape behind the cavity.Size & depth of diverter to suit specified

cladding preventing water ingress enteringbehind cladding and cavity

150m

m

Min.

50mm

Cavity Battens and cladding overflashings.Note: NO nails through the flashings

NOTE: 2Refer Viking Typical details for vented apron details etc.

Barge Board

Barge Flashing

ExampleSaddle-flashing

refer table 7 of E2/AS1 for coverage

Viking CertainTeed ShinglesSaddle-flashing Methodology CT21 CT21

17/11/2016

DRAWING STATUS

ISSUEDetail Ref:DATE

DRAWN

Not to Scale

DRAWING TITLE NOTES:

Viking Roofspec, Otara, P.O.Box 14-541, Auckland 1741, New Zealand, Telephone 0800 729 799, Facsimile 0800 729 788, Website www.vikingroofspec.co.nz

INFORMATION ONLY

Viking

Substrate Indicative OnlyA