    Operating Instructions

    Radar sensor for continuous level

    measurement of liquids

    VEGAPULS 624 … 20 mA/HART - two-wire

    Document ID: 36503

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    2/84

    2

    Quick start

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

     3   6   5   0  

     3  -E N-1  2  1   0  1  1  

    Quick start

    The quick start enables a quick setup with many applications. Youcan nd further information in the respective chapters of the operatinginstructions manual.

    1. Distance from the vessel wall > 200 mm, the antenna shouldprotrude > 10 mm into the vessel

       c   a .

        1    0   m   m

    > 200 mm(7.87")

    Fig. 1: Distance of the antenna to the vessel wall/vessel ceiling

    2. Note min. socket diameter depending on the socket length

    For further information see chapter "Mounting".

    1. Make sure that the power supply corresponds to the specica-tions on the type label.

    2. Connect the instrument according to the following illustration

    51   2+( ) (-)   6 7 8

    4...20mA

    2

    3

    4

    1

    Fig. 2: Electronics and connection compartment, single chamber housing

    1 Voltage supply, signal output  2 For indicating and adjustment module or interface adapter 3 For external indicating and adjustment unit 4 Ground terminal for connection of the cable screen

    For further information see chapter "Connecting to power supply ".1. Go via the indicating and adjustment module to the menu "Setup".

    2. In the menu item "Medium"you select the medium of your applica-tion, for example " Aqueous solution".

    Mounting

    Connect electrically

    Set parameters

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    3/84

    3

    Quick start

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

          3      6      5      0      3   -      E      N   -      1      2      1      0      1      1

    3. Select in the menu item " Application" the vessel, the applicationand the vessel form, for example, storage tank.

    4. Carry out the adjustment in the menu items "Min. adjustment " and"Max. adjustment ".

    The radar sensor measures the distance from the sensor to theproduct surface. For indication of the real level, an allocation of the

    measured distance to the percentage height must be carried out.

    100%

    0%

       0 ,   5   m

        (   1   9 .   6   8               "               )

       5   m

        (   1   9   6 .   9

                   "               )

    2

    1

    Fig. 3: Parameter adjustment example min./max. adjustment 

    1 Min. level = max. meas. distance 2 Max. level = min. meas. distance

    For this adjustment, the distance is entered with full and virtuallyempty vessel. If these values are not known, an adjustment withdistances, for example, of 10 % and 90 % is also possible. Startingpoint for these distance specications is always the seal surface ofthe thread or ange.

    1. In the menu " Additional settings", menu item "Damping" you haveto adjust the requested damping of the output signal.

    2. Select the output characteristics in the menu item "Current out- put ".

    The quick start is then nished. For further information see chapter"Parameter adjustment ".

    Parameterization example

    Further steps

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    4/84

    4

    Contents

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

     3   6   5   0  

     3  -E N-1  2  1   0  1  1  

    Contents

    1 About this document

    1.1 Function ............................................................................. 61.2 Target group ....................................................................... 6

    1.3 Symbolism used ................................................................. 6

    2 For your safety

    2.1 Authorised personnel ......................................................... 72.2 Appropriate use .................................................................. 72.3 Warning about incorrect use ............................................... 72.4 General safety instructions ................................................. 72.5 CE conformity ..................................................................... 82.6 NAMUR recommendations ................................................ 82.7 Radio license for Europe .................................................... 82.8 Radio license for USA/Canada ........................................... 8

    2.9 Environmental instructions ................................................. 93 Product description

    3.1 Conguration .................................................................... 103.2 Principle of operation ........................................................ 113.3 Packaging, transport and storage ..................................... 123.4 Accessories and replacement parts ................................. 12

    4 Mounting

    4.1 General instructions ......................................................... 144.2 Mounting preparations - Horn antenna ............................. 144.3 Mounting preparations - Parabolic antenna ...................... 154.4 Instructions for installation ................................................ 16

    5 Connecting to power supply

    5.1 Preparing the connection ................................................. 275.2 Connecting ....................................................................... 285.3 Wiring plan, single chamber housing ................................ 295.4 Wiring plan, double chamber housing .............................. 305.5 Wiring plan, Ex-d double chamber housing ...................... 315.6 Wiring plan - version IP 66/IP 68, 1 bar ............................. 325.7 Switch-on phase ............................................................... 32

    6 Set up with the indicating and adjustment module6.1 Insert indicating and adjustment module .......................... 346.2 Adjustment system ........................................................... 356.3 Parameter adjustment ...................................................... 366.4 Saving the parameter adjustment data ............................. 49

    7 Setup with PACTware

    7.1 Connect the PC ................................................................ 507.2 Parameter adjustment with PACTware .............................. 517.3 Saving the parameter adjustment data ............................. 52

    8 Set up with other systems

    8.1 DD adjustment programs ................................................. 538.2 Communicator 375, 475 ................................................... 53

    9 Diagnosis, Asset Management and service

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    5/84

    5

    Contents

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

          3      6      5      0      3   -      E      N   -      1      2      1      0      1      1

    9.1 Maintenance .................................................................... 549.2 Diagnosis memory ........................................................... 549.3 Asset Management function ............................................. 559.4 Rectify faults ..................................................................... 589.5 Exchanging the electronics module .................................. 62

    9.6 Software update ............................................................... 629.7 How to proceed in case of repair ...................................... 63

    10 Dismounting

    10.1 Dismounting steps ............................................................ 6410.2 Disposal ........................................................................... 64

    11 Supplement

    11.1 Technical data .................................................................. 6511.2 Dimensions ...................................................................... 73

    Safety instructions for Ex areas

    Please note the Ex-specic safety information for installation and op-eration in Ex areas. These safety instructions are part of the operatinginstructions manual and come with the Ex-approved instruments.

    Editing status: 2012-09-27

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    6/84

    6

    1 About this document

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

     3   6   5   0  

     3  -E N-1  2  1   0  1  1  

    1 About this document

    1.1 Function

    This operating instructions manual provides all the information you

    need for mounting, connection and setup as well as important instruc-tions for maintenance and fault rectication. Please read this informa-tion before putting the instrument into operation and keep this manualaccessible in the immediate vicinity of the device.

    1.2 Target group

    This operating instructions manual is directed to trained qualiedpersonnel. The contents of this manual should be made available tothese personnel and put into practice by them.

    1.3 Symbolism usedInformation, tip, noteThis symbol indicates helpful additional information.

    Caution: If this warning is ignored, faults or malfunctions can result.

    Warning: If this warning is ignored, injury to persons and/or seriousdamage to the instrument can result.

    Danger: If this warning is ignored, serious injury to persons and/ordestruction of the instrument can result.

    Ex applications

    This symbol indicates special instructions for Ex applications.• List

    The dot set in front indicates a list with no implied sequence.

    → ActionThis arrow indicates a single action.

    1 SequenceNumbers set in front indicate successive steps in a procedure.

    Battery disposalThis symbol indicates special information about the disposal of bat-teries and accumulators.

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    7/84

    7

    2 For your safety

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

          3      6      5      0      3   -      E      N   -      1      2      1      0      1      1

    2 For your safety

    2.1 Authorised personnel

    All operations described in this operating instructions manual must

    be carried out only by trained specialist personnel authorised by theplant operator.

    During work on and with the device the required personal protectiveequipment must always be worn.

    2.2 Appropriate use

    VEGAPULS 62 is a sensor for continuous level measurement.

    You can nd detailed information on the application range in chapter"Product description".

    Operational reliability is ensured only if the instrument is properly

    used according to the specications in the operating instructionsmanual as well as possible supplementary instructions.

    2.3 Warning about incorrect use

    Inappropriate or incorrect use of the instrument can give rise toapplication-specic hazards, e.g. vessel overll or damage to systemcomponents through incorrect mounting or adjustment.

    2.4 General safety instructions

    This is a state-of-the-art instrument complying with all prevailingregulations and guidelines. The instrument must only be operated in atechnically awless and reliable condition. The operator is responsiblefor the trouble-free operation of the instrument.

    During the entire duration of use, the user is obliged to determine thecompliance of the necessary occupational safety measures with thecurrent valid rules and regulations and also take note of new regula-tions.

    The safety instructions in this operating instructions manual, the na-tional installation standards as well as the valid safety regulations andaccident prevention rules must be observed by the user.

    For safety and warranty reasons, any invasive work on the devicebeyond that described in the operating instructions manual may becarried out only by personnel authorised by the manufacturer. Arbi-trary conversions or modications are explicitly forbidden.

    The safety approval markings and safety tips on the device must alsobe observed.

    Depending on the instrument version, the emitting frequencies are inthe C or K band range. The low emitting frequencies are far below theinternationally approved limit values. When used correctly, there is nodanger to health.

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    8/84

    8

    2 For your safety

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

     3   6   5   0  

     3  -E N-1  2  1   0  1  1  

    2.5 CE conformity

    The device fullls the legal requirements of the applicable EC guide-lines. By axing the CE marking, we conrm successful testing of theproduct.

    You can nd the conformity certicate in the download section of ourhomepage.

    Only with Ex-d-ia versionThe instrument is designed for use in an industrial environment.Nevertheless, electromagnetic interference from electrical conductorsand radiated emissions must be taken into account, as is usual with aclass A instrument according to EN 61326-1. If the instrument is usedin a dierent environment, its electromagnetic compatibility with otherdevices must be ensured by suitable measures.

    2.6 NAMUR recommendationsNAMUR is the automation technology user association in the processindustry in Germany. The published NAMUR recommendations areaccepted as the standard in eld instrumentation.

    The device fullls the requirements of the following NAMUR recom-mendations:

    • NE 21 – Electromagnetic compatibility of equipment• NE 43 – Signal level for malfunction information from measuring

    transducers

    • NE 53 – Compatibility of eld devices and indicating/adjustment

    components• NE 107 - Self-monitoring and diagnosis of eld devicesFor further information see www.namur.de.

    2.7 Radio license for Europe

    The instrument is approved according to EN 302372-1/2 (2006-04)for use in closed vessels.

    2.8 Radio license for USA/Canada

    The instrument is in conformity with part 15 of the FCC regulations.Take note of the following two regulations:

    • The instrument must not cause any interfering emissions• The device must be insensitive to interfering immissions, including

    those that may cause undesirable operating conditions

    Modications not expressly approved by the manufacturer will lead toexpiry of the operating licence according to FCC/IC.

    The instrument is in conformity with RSS-210 of the IC regulations.

    The instrument may only be used in closed vessels made of metal,concrete, or bre-reinforced plastic.

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    9/84

    9

    2 For your safety

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

          3      6      5      0      3   -      E      N   -      1      2      1      0      1      1

    2.9 Environmental instructions

    Protection of the environment is one of our most important duties.That is why we have introduced an environment management systemwith the goal of continuously improving company environmental pro-tection. The environment management system is certied according

    to DIN EN ISO 14001.Please help us full this obligation by observing the environmentalinstructions in this manual:

    • Chapter "Packaging, transport and storage"• Chapter "Disposal "

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    10/84

    10

    3 Product description

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

     3   6   5   0  

     3  -E N-1  2  1   0  1  1  

    3 Product description

    3.1 Conguration

    The type label contains the most important data for identication and

    use of the instrument:

    2

    1

    13

    14

    15

    16

    12

    11

    5

    3

    6

    4

    7

    8

    9

    10

    Fig. 4: Layout of the type label (example)

    1 Instrument type 2 Product code3 Approvals4 Power supply and signal output, electronics5 Protection rating6 Measuring range7 Process and ambient temperature, process pressure

    8 Material, wetted parts9 Hardware and software version10 Order number 11 Serial number of the instrument 12 Symbol of the device protection class13 ID numbers, instrument documentation14 Note to observe the instrument documentation15 Notied authority for CE marking16 Approval directive

    With the serial number of the instrument on the type label you haveaccess to the following data on our homepage:

    • Article number of the instrument (HTML)• Delivery date (HTML)• Order-specic instrument features (HTML)• Operating instructions at the time of shipment (PDF)• Order-specic sensor data for an electronics exchange (XML)• Test certicate "Measuring Accuracy" (PDF)For this purpose, move to www.vega.com and "VEGA Tools".

    This operating instructions manual applies to the following instrumentversions:

    • Hardware from 2.1.0• Software from 4.5.1

    Type label

    Serial number

    Scope of this operatinginstructions manual

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    11/84

    11

    3 Product description

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

          3      6      5      0      3   -      E      N   -      1      2      1      0      1      1

    The instrument is available in two dierent electronics versions. Eachversion can be identied via the product code on the type label aswell as on the electronics.

    • Standard electronics type PS60HK.-• Electronics with increased sensitivity type PS60HS.-

    The scope of delivery encompasses:

    • Radar sensor• Documentation

     – this operating instructions manual – Test certicate measuring accuracy (optional) – Operating instructions manual "Indicating and adjustment

    module" (optional) – Supplementary instructions "GSM/GPRS radio module"

    (optional)

     – Supplementary instructions manual "Heating for indicating andadjustment module" (optional) – Supplementary instructions manual "Plug connector for con-

    tinuously measuring sensors" (optional) – Ex-specic "Safety instructions" (with Ex versions) – if necessary, further certicates

    3.2 Principle of operation

    The VEGAPULS 62 radar sensor can be used in a wide variety of ap-plications for continuous level measurement of liquids. It is suitable for

    applications in storage vessels, reactors and process vessels, evenunder extremely dicult process conditions.

    Dependent on the application range, dierent versions are used:

    • Antenna – Small tanks and process vessels, measurement of virtually all

    products: Horn antenna ø 40 mm – Storage tanks and process vessels, measurement of products

    such as solvents, hydrocarbons and fuels under extremely dif-cult process conditions: Horn antenna ø 48 … 95 mm

     – Products with low εr value with large measuring distances:

    Parabolic antenna

    • Electronics – Products with an ε

    r value ≥1.8: Standard electronics

     – Products with an εr value < 1.8, ≥1.5; applications with very bad

    reective properties: Electronics with increased sensitivity

    The actual values that can be reached depend on the measurementconditions, the antenna system or the standpipe or bypass.

    The antenna of the radar sensor emits short radar pulses with aduration of approx. 1 ns. These pulses are reected by the productand received by the antenna as echoes. The transit time of the radar

    pulses from emission to reception is proportional to the distance andhence to the level. The determined level is converted into an appropri-ate output signal and outputted as measured value.

    Versions

    Scope of delivery

    Application area

    Functional principle

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    12/84

    12

    3 Product description

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

     3   6   5   0  

     3  -E N-1  2  1   0  1  1  

    3.3 Packaging, transport and storage

    Your instrument was protected by packaging during transport. Itscapacity to handle normal loads during transport is assured by a testaccording to DIN EN 24180.

    The packaging of standard instruments consists of environment-friendly, recyclable cardboard. For special versions, PE foam or PEfoil is also used. Dispose of the packaging material via specialisedrecycling companies.

    Transport must be carried out under consideration of the notes on thetransport packaging. Nonobservance of these instructions can causedamage to the device.

    The delivery must be checked for completeness and possible transitdamage immediately at receipt. Ascertained transit damage or con-

    cealed defects must be appropriately dealt with.

    Up to the time of installation, the packages must be left closed andstored according to the orientation and storage markings on theoutside.

    Unless otherwise indicated, the packages must be stored only underthe following conditions:

    • Not in the open• Dry and dust free• Not exposed to corrosive media

    •Protected against solar radiation

    • Avoiding mechanical shock and vibration

    • Storage and transport temperature see chapter "Supplement -Technical data - Ambient conditions"

    • Relative humidity 20 … 85 %

    3.4 Accessories and replacement parts

    The indicating and adjustment module PLICSCOM is used for meas-ured value indication, adjustment and diagnosis. It can be insertedinto the sensor and removed at any time.

    You can nd further information in the operating instructions "Indicat-ing and adjustment module PLICSCOM " (Document-ID 27835).

    The interface adapter VEGACONNECT enables the connection ofcommunication-capable instruments to the USB interface of a PC. Forparameter adjustment of these instruments, an adjustment softwaresuch as PACTware with VEGA-DTM is required.

    You can nd further information in the operating instructions "Interfaceadapter VEGACONNECT " (Document-ID 32628).

    VEGADIS 61 is an external indicating and adjustment unit for sensorswith single chamber housing and Ex-d double chamber housing.

    Packaging

    Transport

    Transport inspection

    Storage

    Storage and transporttemperature

    Indicating and adjust-ment module

    Interface adapter

    External indicating andadjustment unit

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    13/84

    13

    3 Product description

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

          3      6      5      0      3   -      E      N   -      1      2      1      0      1      1

    It is suitable for measured value indication and adjustment of plics® sensors and is connected to the sensor with a four-wire standardcable up to 50 m long.

    You can nd further information in the operating instructions "VE-GADIS 61" (Document-ID 27720).

    VEGADIS 62 is suitable for measured value indication and adjustmentof sensors with HART protocol. It is looped into the 4 … 20 mA/HARTsignal cable.

    You can nd further information in the operating instructions "VE-GADIS 62 " (Document-ID 36469).

    The PLICSMOBILE T61 is an external GSM/GPRS radio unit fortransmission of measured values and for remote parameter adjust-ment of plics® sensors. The adjustment is carried out via PACTware/ 

    DTM by using the integrated USB connection.You can nd further information in the supplementary instructions"PLICSMOBILE T61" (Document-ID 36849).

    The protective cover protects the sensor housing against soiling andintense heat from solar radiation.

    You will nd additional information in the supplementary instructionsmanual "Protective cover " (Document-ID 34296).

    Screwed anges are available in dierent versions according to thefollowing standards: DIN 2501, EN 1092-1, ANSI B 16.5, JIS B 2210-

    1984, GOST 12821-80.

    You can nd additional information in the supplementary instructionsmanual "Flanges according to DIN-EN-ASME-JIS" (Document-ID31088).

    The electronics module VEGAPULS series 60 is a replacement partfor radar sensors of VEGAPULS series 60. There is a dierent versionavailable for each type of signal output.

    You can nd further information in the operating instructions "Elec-tronics module VEGAPULS series 60" (Document-ID 36801).

    The antenna impedance cone is used for optimum transmission ofmicrowaves and for sealing against the process.

    You nd further information in the operating instructions " Antennaimpedance cone VEGAPULS 62 and 68" (Document-ID 31381).

    External indicating andadjustment unit withHART protocol

    External radio unit

    Protective cover

    Flanges

    Electronics module

    Antenna impedance cone

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    14/84

    14

    4 Mounting

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

     3   6   5   0  

     3  -E N-1  2  1   0  1  1  

    4 Mounting

    4.1 General instructions

    With instruments with threaded process tting, suitable tools must be

    applied for tightening the hexagon.Warning:The housing must not be used to screw the instrument in! Applyingtightening force can damage internal parts of the housing.

    Use the recommended cables (see chapter "Connecting to powersupply ") and tighten the cable gland.

    You can give your instrument additional protection against moisturepenetration by leading the connection cable downward in front of thecable entry. Rain and condensation water can thus drain o. This ap-

    plies mainly to outdoor mounting as well as installation in areas wherehigh humidity is expected (e.g. through cleaning processes) or oncooled or heated vessels.

    Make sure that all parts of the instrument exposed to the process, inparticular the active measuring component, process seal and processtting, are suitable for the existing process conditions. These includeabove all the process pressure, process temperature as well as thechemical properties of the medium.

    You can nd the specications in chapter "Technical data" and on thetype label.

    4.2 Mounting preparations - Horn antenna

    The instrument is also available in versions with an antenna whosediameter is larger than the process tting (thread, ange). In suchcases the antenna must be disconnected from the process ttingbefore mounting. Proceed as follows:

    1. Loosen the hexagon socket screws (3) on the antenna socketwith an Allen wrench (size 3)

    2. Remove the antenna (4)

    Note:The plastic cone may not be pulled out of the antenna socket.

    3. Insert the antenna from below into the vessel socket and secure itagainst falling o

    4. Retighten the antenna with hexagon screws to the antennasocket; torque max. 2.5 Nm (1.8 lbf ft)

    Note:The radar sensor with rinsing air connection or antenna extensionis provided with a notch on the antenna socket. This notch must bealigned with the marking on the process tting (the marking species

    the position of the polarisation plane of the radar signal).

    Screwing in

    Moisture

    Suitability for the processconditions

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    15/84

    15

    4 Mounting

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

          3      6      5      0      3   -      E      N   -      1      2      1      0      1      1

    3

    4

    1

    2

    Fig. 5: Dismounting of the horn antenna

    1 Marking of the polarisation plane 2 Marking at the antenna socket 3 Hexagon screws on the antenna socket 4 Antenna

    4.3 Mounting preparations - Parabolic antenna

    The instrument is also available in versions where the antenna hasa diameter larger than the process tting (thread, ange). With suchversions the antenna must be disconnected from the process ttingbefore mounting. Proceed as follows:

    1. Clamp VEGAPULS 62 with the ange, e.g. in a bench vice2. Hold the connection piece (3) with a wrench on the at surfaces

    (width across ats 22 mm)

    3. Loosen counter nut (2) completely with a wrench (width acrossats 36 mm) in the direction of the antenna

    4. Loosen compression nut (1) completely with a wrench (widthacross ats 41 mm) in the direction of the antenna

    5. Remove the parabolic antenna (4) axially

    6. Mount sensor ange on the adapter ange and fasten it tightly

    7. Check if the O-ring seal is present on the connection piece andmake sure it is not damaged.

    Note:A damaged O-ring seal must be replaced: FKM (Viton) article no.2.28248, FFKM (Kalrez 6375) article no. 2.27351

    8. Remount the parabolic antenna (4)

    9. Fasten compression nut (1) with a wrench (width across ats 41),torque max. 50 Nm

    10. Fasten counter nut (2) with a wrench (width across ats 36),torque max. 40 Nm

    Note:On the version with rinsing air connection, make sure that the holesin the antenna and in the process tting coincide. This ensures a suf-

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    16/84

    16

    4 Mounting

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

     3   6   5   0  

     3  -E N-1  2  1   0  1  1  

    cient air ow (the air is led through the holes to the feed system. Arinsing of the whole parabolic antenna is not intended).

    1

    2

    3

    4

    Fig. 6: Dismounting, parabolic antenna

    1 Connection piece 2 Compression nut 

    3 Locknut 4 Parabolic antenna

    4.4 Instructions for installation

    The illustrations with the following mounting instructions show a radarsensor with horn antenna. The mounting instructions apply analo-gously also to the version with parabolic antenna.

    The emitted radar impulses of the radar sensor are electromagneticwaves. The polarisation plane is the direction of the electrical wave

    component. By turning the instrument in the connection ange ormounting boss, the polarisation can be used to reduce the eects offalse echoes.

    The position of the polarisation plane is marked on the process ttingof the instrument.

    1 2

    Fig. 7: Position of the polarisation level 

    1 Marking with screwed version 2 Marking with ange version

    When mounting the sensor, keep a distance of at least 200 mm(7.874 in) from the vessel wall. If the sensor is installed in the centerof dished or round vessel tops, multiple echoes can arise. However,

    these can be suppressed by an appropriate adjustment (see chapter"Setup").

    If you cannot keep this distance you should carry out a false echostorage before setup. This applies mainly if buildup on the vessel wall

    Horn and parabolicantenna

    Polarisation plane

    Installation position

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    17/84

    17

    4 Mounting

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

          3      6      5      0      3   -      E      N   -      1      2      1      0      1      1

    is expected. In this case, we recommend repeating a false echo stor-age later with existing buildup.

    > 200 mm

    (7.87")

    Fig. 8: Mounting of the radar sensor on round vessel tops

    In vessels with conical bottom it can be advantageous to mount thesensor in the center of the vessel, as measurement is then possibledown to the lowest point of the vessel bottom.

    Fig. 9: Mounting of the radar sensor on vessels with conical bottom

    Do not mount the instruments in or above the lling stream. Make sure

    that you detect the product surface, not the inowing product.

    Inowing medium

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    18/84

    18

    4 Mounting

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

     3   6   5   0  

     3  -E N-1  2  1   0  1  1  

    Fig. 10: Mounting of the radar sensor with inowing medium

    The socket piece should be dimensioned in such a way that theantenna end protrudes slightly out of the socket.

       c   a .

       1   0   m   m

    Fig. 11: Recommended socket mounting with horn antenna

       >    1    0   m   m

         (    0 .    3

        9    "    )

    Fig. 12: Recommended socket mounting with parabolic antenna

    When using a swivelling holder, keep in mind that the distancebetween antenna and socket gets smaller as the inclination of the

    Socket

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    19/84

    19

    4 Mounting

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

          3      6      5      0      3   -      E      N   -      1      2      1      0      1      1

    sensor increases. Additional false reections may be generated whichcan inuence the measuring result at close range.

    Fig. 13: Distance between antenna and socket with horn antenna

    Fig. 14: Distance between antenna and socket with parabolic antenna

    If the medium has good reective properties, VEGAPULS 62 withhorn antenna can also be mounted on a longer socket piece. Rec-ommended values for socket heights are specied in the followingillustration. You must carry out a false echo storage afterwards.

    d

         h    m    a    x .

    Fig. 15: Deviating socket dimensions

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    20/84

    20

    4 Mounting

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

     3   6   5   0  

     3  -E N-1  2  1   0  1  1  

    Socket diameter d Socket length h Recommended anten-

    na diameter

    40 mm 100 mm 40 mm

    50 mm 150 mm 48 mm

    80 mm 250 mm 75 mm

    100 mm 500 mm 95 mm

    150 mm 800 mm 95 mm

    Socket diameter d Socket length h Recommended anten-

    na diameter

    1½" 3.9 in 1½"

    2" 5.9 in 2"

    3" 9.8 in 3"

    4" 19.7 in 4"

    6" 31.5 in 4"

    Tip:

    The instrument is also optionally available with an antenna extension.The antenna length can be selected (either ex works or later) to allowthe antenna to protrude slightly out of the end of the mounting socket.Due to the antenna extension however, disturbing reections aregenerated in the close-up range. This can lead to an increase in therequired minimum distance, especially with poorly reecting mediasuch as plastic powder. In practice, a cleanly constructed mountingsocket, if necessary with rounded edges, introduces fewer disturbinginuences than an antenna extension.

    Align the sensor in liquids as vertical as possible to the product sur-face to achieve optimum measurement.

    Fig. 16: Alignment in liquids

    The mounting location of the radar sensor should be a place where noother equipment or xtures cross the path of the microwave signals.

    Vessel installations, such as e.g. ladders, limit switches, heating spi-rals, struts, etc., can cause false echoes and impair the useful echo.Make sure when planning your measuring site that the radar sensorhas a "clear view" to the measured product.

    In case of existing vessel installations, a false echo storage should be

    carried out during setup.If large vessel installations such as struts or supports cause falseechoes, these can be attenuated through supplementary measures.

    Sensor orientation

    Vessel installations

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    21/84

    21

    4 Mounting

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

          3      6      5      0      3   -      E      N   -      1      2      1      0      1      1

    Small, inclined sheet metal baes above the installations scatter theradar signals and prevent direct interfering reections.

    Fig. 17: Cover smooth proles with deectors

    If there are agitators in the vessel, a false signal suppression shouldbe carried out with the agitators in motion. This ensures that theinterfering reections from the agitators are saved with the blades indierent positions.

    Fig. 18: Agitators

    Through the action of lling, stirring and other processes in the vessel,compact foams that considerably damp the emitted signals may formon the product surface.

    If foams are causing measurement errors, the biggest possible radarantennas, the electronics with increased sensitivity or low frequencyradar sensors (C band) should be used.

    As an alternative, sensors with guided microwave can be used. Theseare unaected by foam generation and are best suited for such ap-plications.

    When using a surge pipe in a vessel, inuences from vessel installa-tions and turbulences can be excluded. Under these prerequisites,the measurement of products with low dielectric values (ε

    r value

    ≥ 1.6) is possible. In very adhesive products, measurement in a surgepipe is not recommended.

    Agitators

    Foam generation

    Measurement in a surgepipe

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    22/84

    22

    4 Mounting

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

     3   6   5   0  

     3  -E N-1  2  1   0  1  1  

    0%

    100%

    1

    2

    3

    1

    2

    3

    4

    5

    8

    6

    7

    9

    Fig. 19: Conguration surge pipe

    1 Radar sensor  2 Marking of the polarisation plane

    3 Thread or ange on the instrument 4 Vent hole5 Holes6 Weld joint 7 Welding neck ange8 Ball valve with complete opening9 Fastening of the surge pipe

    Instructions for orientation:

    • Note marking of the polarisation plane on the sensor• With threaded tting, the marking is on the hexagon, with ange

    connection between the two ange holes

    • The marking must show to the direction of the holes in the surgepipe

    Instructions for the measurement:

    • The 100 % point must be below the upper vent hole and theantenna edge

    • The 0 % point is the end of the surge pipe• For the parameter adjustment, select " Application standpipe" and

    enter the tube diameter to compensate errors due to running timeshift

    •A false signal suppression with integrated sensor is recommendedbut not mandatory

    • The measurement through a ball valve with complete run is pos-sible

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    23/84

    23

    4 Mounting

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

          3      6      5      0      3   -      E      N   -      1      2      1      0      1      1

    Constructional requirements on the surge pipe:

    • Material metal, smoother inner tube• Preferably pultruded or straight beaded stainless steel tube• Welded joint should be straight and lie in one axis with the holes• Flanges are welded to the tube according to the orientation of the

    polarisation level• In case of a extension with a welding neck ange or pipe collar

    as well as when a ball valve is used, the inner surfaces should bealigned and accurately joined together

    • Gap size with junctions ≤ 0.1 mm• Do not weld through the pipe wall. The surge pipe must remain

    smooth inside. Roughness and beads on the inside caused byunintentional penetration should be removed since they causestrong false echoes and encourage buildup

    • Surge pipes must extend all the way down to the requested min.level, as measurement is only possible within the tube

    • Diameter of holes ≤ 5 mm, any number OK, on one side or com-pletely through• The antenna diameter of the sensor should correspond to the

    inner diameter of the tube

    • Diameter should be constant over the complete length

    An alternative to measurement in a surge pipe is measurement in abypass tube outside of the vessel.

    0 %

    100 %

    1

    2

    5

    4

    3

    6

    Fig. 20: Conguration bypass

    1 Radar sensor  2 Marking of the polarisation plane3 Instrument ange

    4 Distance sensor reference plane to upper tube connection5 Distance of the tube connections6 Ball valve with complete opening

    Measurement in thebypass

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    24/84

    24

    4 Mounting

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

     3   6   5   0  

     3  -E N-1  2  1   0  1  1  

    Instructions for orientation:

    • Note marking of the polarisation plane on the sensor• With threaded tting, the marking is on the hexagon, with ange

    connection between the two ange holes

    • The marking must show to the direction of the tube connections tothe vessel

    Instructions for the measurement:

    • The 100 % point must not be above the upper tube connection tothe vessel

    • The 0 % point must not be below the lower tube connection to thevessel

    • Min. distance sensor reference plane to the upper edge uppertube connection > 300 mm

    • For the parameter adjustment, select " Application standpipe" andenter the tube diameter to compensate errors due to running time

    shift• A false signal suppression with integrated sensor is recommended

    but not mandatory

    • The measurement through a ball valve with complete run is pos-sible

    Constructional requirements on the bypass pipe:

    • Material metal, smoother inner tube• In case of an extremely rough tube inner surface, use an inserted

    tube (tube in tube) or a radar sensor with tube antenna

    • Flanges are welded to the tube according to the orientation of thepolarisation level

    • Gap size with junctions ≤ 0.1 mm, for example, when using a ballvalve or intermediate anges with single pipe sections

    • The antenna diameter of the sensor should correspond to theinner diameter of the tube

    • Diameter should be constant over the complete length

    Instruments for a temperature range up to 250 °C or up to 450 °Chave a distance piece between process tting and electronics hous-ing. Ths distance piece is used for thermal decoupling of the electron-ics against high process temperatures.

    Information:The distance piece must only be incorporaed up to max. 50 mm inthe vessel installation. Only then, a reliable temperature decoupling isguaranteed.

    Mounting in the vesselinsulation

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    25/84

    25

    4 Mounting

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

          3      6      5      0      3   -      E      N   -      1      2      1      0      1      1

      m  a  x .

       5   0  m

      m

     

       (   1 .   9

       7   "   )

    1

    2

    3

    Fig. 21: Mounting of the instrument with insulated vessels.

    1 Electronics housing 2 Distance piece3 Vessel insulation

    The short examples give you introductory information on the owmeasurement. Detailed planning information is available from umemanufacturers and in special literature.

    3 ... 4 hmax

    ≥ 50 mm

    90°

    2   3

    1

       h  m  a  x

       d  m   i  n

       ≥   2  m  m   x

       h  m  a  x

    90°

    42 3

    Fig. 22: Flow measurement with rectangular ume: d min.

     = min. distance of the

    sensor (see chapter "Technical data"); hmax. = max. lling of the rectangularume

    1 Overow orice (side view) 2 Headwater 3 Tail water 4 Overfall orice (view from bottom water)

    In general, the following points must be observed:

    • Install the sensor on the headwater side• Installation in the centre of the ume and vertical to the liquid

    surface

    • Distance to the overfall orice• Distance of orice opening above ground• Min. distance of the orice opening to bottom water• Min. distance of the sensor to max. storage level

    Flow measurement withrectangular ume

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    26/84

    26

    4 Mounting

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

     3   6   5   0  

     3  -E N-1  2  1   0  1  1  

    2

    3 ... 4 x hmax

    90°

    hmax

    d

    B1

    Fig. 23: Flow measurement with Khafagi-Venturi ume: d = Min. distance to sen -sor; h

    max. = max. lling of the ume; B = tightest constriction in the ume

    1 Position sensor  2 Venturi ume

    In general, the following points must be observed:

    • Installation of the sensor at the inlet side• Installation in the centre of the ume and vertical to the liquidsurface

    • Distance to the Venturi ume• Min. distance of the sensor to max. storage level

    Flow measurement withKhafagi Venturi ume

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    27/84

    27

    5 Connecting to power supply

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

          3      6      5      0      3   -      E      N   -      1      2      1      0      1      1

    5 Connecting to power supply

    5.1 Preparing the connection

    Always keep in mind the following safety instructions:

    • Connect only in the complete absence of line voltage• If overvoltage surges are expected, overvoltage arresters shouldbe installed

    Power supply and current signal are carried on the same two-wirecable. The voltage supply range can dier depending on the instru-ment version.

    The data for power supply are specied in chapter "Technical data".

    Provide a reliable separation between the supply circuit and themains circuits according to DIN VDE 0106 part 101.

    Keep in mind the following additional factors that inuence the operat-ing voltage:

    • Output voltage of the power supply unit can be lower under nomi-nal load (with a sensor current of 20.5 mA or 22 mA in case of faultmessage)

    • Inuence of additional instruments in the circuit (see load values inchapter "Technical data")

    The instrument is connected with standard two-wire cable withoutscreen. If electromagnetic interference is expected which is above the

    test values of EN 61326-1 for industrial areas, screened cable shouldbe used.

    For instruments with housing and cable gland, use cable with roundcross-section. A cable outer diameter of 5 … 9 mm (0.2 … 0.35 in)ensures the seal eect of the cable gland. If you are using cable witha dierent diameter, exchange the seal or use a suitable cable gland.

    We generally recommend the use of screened cable for HART multi-drop mode.

    With plastic housing, the NPT cable gland or the Conduit steel tube

    must be screwed without grease into the threaded insert.Max. torque for all housings see chapter "Technical data"

    If screened cable is necessary, connect the cable screen on bothends to ground potential. In the sensor, the screen must be connecteddirectly to the internal ground terminal. The ground terminal on theoutside of the housing must be connected to the potential equalisa-tion (low impedance).

    If potential equalisation currents are expected, the connection on theprocessing side must be made via a ceramic capacitor (e. g. 1 nF,1500 V). The low frequency potential equalisation currents are thussuppressed, but the protective eect against high frequency interfer-ence signals remains.

    Safety instructions

    Voltage supply

    Connection cable

    Cable gland ½ NPT

    Cable screening andgrounding

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    28/84

    28

    5 Connecting to power supply

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

     3   6   5   0  

     3  -E N-1  2  1   0  1  1  

    Warning:Signicant potential dierences exist inside galvanization plants aswell as on vessels with cathodic corrosion protection. Considerableequalisation currents can ow over the cable screen if the screen isgrounded on both ends.

    To avoid this in such applications, the cable screen must be connect-ed to ground potential only at one end (in the switching cabinet). Thecable screen must not be connected to the internal ground terminal inthe sensor and the outer ground terminal on the housing must not beconnected to the potential equalisation!

    Information:The metal parts of the instrument (process tting, transmitter, concen-tric tube, etc.) are conductively connected with the inner and outerground terminal on the housing. This connection exists either directlyvia connecting metallic parts or, in case of instruments with external

    electronics, via the screen of the special connection cable.You can nd specications on the potential connections inside theinstrument in chapter "Technical data".

    5.2 Connecting

    The voltage supply and signal output are connected via the spring-loaded terminals in the housing.

    The connection to the indicating and adjustment module or to theinterface adapter is carried out via contact pins in the housing.

    Information:The terminal block is pluggable and can be removed from the elec-tronics. To do this, lift the terminal block with a small screwdriver andpull it out. When inserting the terminal block again, you should hear itsnap in.

    Proceed as follows:

    1. Unscrew the housing cover

    2. If an indicating and adjustment module is installed, remove it byturning it slightly to the left.

    3. Loosen compression nut of the cable entry4. Remove approx. 10 cm (4 in) of the cable mantle, strip approx.

    1 cm (0.4 in) of insulation from the ends of the individual wires

    5. Insert the cable into the sensor through the cable entry

    Connection technology

    Connection procedure

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    29/84

    29

    5 Connecting to power supply

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

          3      6      5      0      3   -      E      N   -      1      2      1      0      1      1

    Fig. 24: Connection steps 5 and 6 

    6. Insert the wire ends into the terminals according to the wiring plan

    Information:Solid cores as well as exible cores with cable end sleeves areinserted directly into the terminal openings. In case of exible coreswithout end sleeves, press the terminal head with a small screwdriver;the terminal opening is freed. When the screwdriver is released, theterminal closes again.

    You can nd further information to the max. wire cross-section under"Technical data/Electromechanical data"

    7. Check the hold of the wires in the terminals by lightly pulling onthem

    8. Connect the screen to the internal ground terminal, connect theouter ground terminal to potential equalisation

    9. Tighten the compression nut of the cable entry. The seal ring mustcompletely encircle the cable

    10. Place probably existing indicating and adjustment module backon

    11. Screw the housing cover back on

    The electrical connection is hence nished.

    5.3 Wiring plan, single chamber housing

    The following illustration applies to the non-Ex as well as to the Ex-iaversion.

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    30/84

    30

    5 Connecting to power supply

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

     3   6   5   0  

     3  -E N-1  2  1   0  1  1  

    51   2+( ) (-)   6 7 8

    4...20mA

    2

    3

    4

    1

    Fig. 25: Electronics and connection compartment, single chamber housing

    1 Voltage supply, signal output  2 For indicating and adjustment module or interface adapter 3 For external indicating and adjustment unit 4 Ground terminal for connection of the cable screen

    5.4 Wiring plan, double chamber housing

    The following illustrations apply to the non-Ex as well as to the Ex-iaversion.

    5 6 7   8

    4...20mA

    2

    1   2+( ) (-)

    11

    Fig. 26: Electronics compartment, double chamber housing

    1 Internal connection to the connection compartment  2 For indicating and adjustment module or interface adapter 

    Information:The connection of an external indicating and adjustment unit is notpossible with this double chamber housing.

    Electronics compartment

    Electronics compartment

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    31/84

    31

    5 Connecting to power supply

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

          3      6      5      0      3   -      E      N   -      1      2      1      0      1      1

    4...20mA

    2

    31   2+( ) (-)

    1

    Fig. 27: Connection compartment, double chamber housing

    1 Voltage supply/Signal output  2 For indicating and adjustment module or interface adapter 3 Ground terminal for connection of the cable screen

    1

    Bus

    USB

    Status

     Test

    SIM-Card

    1   2+( ) (-)

    Fig. 28: CConnection of the voltage supply of the radio module

    1 Voltage supply 

    You can nd detailed information for connection in the supplementaryinstructions "PLICSMOBILE GSM/GPRS radio module".

    5.5 Wiring plan, Ex-d double chamber housing

    5 6 7   81   2+( ) (-)

    31

    2

    4...20mA

    Fig. 29: Electronics compartment, double chamber housing

    1 Internal connection to the connection compartment  2 For indicating and adjustment module or interface adapter 3 Internal connection to the plug connector for external indicating and adjust-

    ment unit (optional)

    Connection compartment

    Radio module PLICSMO-BILE integrated in theconnection compartment

    Electronics compartment

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    32/84

    32

    5 Connecting to power supply

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

     3   6   5   0  

     3  -E N-1  2  1   0  1  1  

    4...20mA

    21   2+( ) (-)

    1

    Fig. 30: Connection compartment, Ex-d double chamber housing

    1 Voltage supply, signal output  2 Ground terminal for connection of the cable screen

    34

    1   2

    Fig. 31: Top view of the plug connector 

    1 Pin 1 2 Pin 2 3 Pin 34 Pin 4

    Contact pin Colour connection ca-ble in the sensor

    Terminal, electronicsmodule

    Pin 1 Brown 5

    Pin 2 White 6

    Pin 3 Blue 7

    Pin 4 Black 8

    5.6 Wiring plan - version IP 66/IP 68, 1 bar

    1

    2

    Fig. 32: Wire assignment x-connected connection cable

    1 brown (+) and blue (-) to power supply or to the processing system 2 Shielding

    5.7 Switch-on phase

    After connecting the instrument to power supply or after a voltagerecurrence, the instrument carries out a self-check for approx. 30 s:

    • Internal check of the electronics

    Connection compartment

    Plug M12 x 1 for external

    indicating and adjust-ment unit

    Wire assignment, con-nection cable

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    33/84

    33

    5 Connecting to power supply

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

          3      6      5      0      3   -      E      N   -      1      2      1      0      1      1

    • Indication of the instrument type, hardware and software version,measurement loop name on the display or PC

    • Indication of the status message "F 105 Determine measuredvalue" on the display or PC

    • The output signal jumps to the set error currentAs soon as a plausible measured value is found, the correspondingcurrent is outputted to the signal cable. The value corresponds to theactual level as well as the settings already carried out, e.g. factorysetting.

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    34/84

    34

    6 Set up with the indicating and adjustment module

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

     3   6   5   0  

     3  -E N-1  2  1   0  1  1  

    6 Set up with the indicating and adjustment

    module

    6.1 Insert indicating and adjustment module

    The indicating and adjustment module can be inserted into the sen-sor and removed any time. Four positions displaced by 90° can beselected. It is not necessary to interrupt the power supply.

    Proceed as follows:

    1. Unscrew the housing cover

    2. Place the indicating and adjustment module in the requestedposition onto the electronics and turn to the right until it snaps in

    3. Screw housing cover with inspection window tightly back on

    Removal is carried out in reverse order.

    The indicating and adjustment module is powered by the sensor, anadditional connection is not necessary.

    Fig. 33: Insertion of the indicating and adjustment module with single chamberhousing into the electronics compartment 

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    35/84

    35

    6 Set up with the indicating and adjustment module

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

          3      6      5      0      3   -      E      N   -      1      2      1      0      1      1

    1 2

    Fig. 34: Insertion of the indicating and adjustment module with double chamberhousing

    1 In the electronics compartment  2 In the connection compartment (with Ex-d-ia version not possible)

    Note:

    If you intend to retrot the instrument with an indicating and adjust-ment module for continuous measured value indication, a higher

    cover with an inspection glass is required.

    6.2 Adjustment system

    1

    2

    Fig. 35: Indicating and adjustment elements

    1 LC display  2 Adjustment keys

    •  [OK]  key: – Move to the menu overview – Conrm selected menu

    Key functions

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    36/84

    36

    6 Set up with the indicating and adjustment module

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

     3   6   5   0  

     3  -E N-1  2  1   0  1  1  

     – Edit parameter – Save value

    •  [->]  key: – Presentation change measured value – Select list entry – Select editing position

    •  [+]  key: – Change value of the parameter

    •  [ESC]  key: – interrupt input – Jump to next higher menu

    The sensor is adjusted via the four keys of the indicating and adjust-ment module. The LC display indicates the individual menu items. The

    functions of the individual keys are shown in the above illustration.Approx. 10 minutes after the last pressing of a key, an automatic resetto measured value indication is triggered. Any values not conrmedwith [OK]  will not be saved.

    6.3 Parameter adjustment

    Through the parameter adjustment the instrument is adapted to theapplication conditions. The parameter adjustment is carried out via anadjustment menu.

    The main menu is divided into ve sections with the following func-tions:

    Setup: Settings, e.g., for measurement loop name, medium, applica-tion, vessel, adjustment, signal output

    Display: Settings, e.g., for language, measured value display, lighting

    Diagnosis: Information, e.g. on the instrument status, pointer, reli-

    ability, simulation, echo curveFurther settings: Instrument unit, false signal suppression, linearisa-tion curve, reset, date/time, reset, copy function

    Info: Instrument name, hardware and software version, calibrationdate, instrument features

    Information:In this operating instructions manual, the instrument-specic param-eters in the menu sections "Setup", "Diagnosis" and " Additional set-tings" are described. The general parameters in these menu sectionare described in the operating instructions manual "Indicating andadjustment module".

    Adjustment system

    Main menu

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    37/84

    37

    6 Set up with the indicating and adjustment module

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

          3      6      5      0      3   -      E      N   -      1      2      1      0      1      1

    You can nd in the operating instructions manual "Indicating and ad- justment module" also the description of the menu sections "Display "and "Info".

    In the main menu point "Setup", the individual submenu points shouldbe selected subsequently and provided with the correct parameters

    to ensure the optimum adjustment of the measurement. The proce-dure is described in the following.

    Each medium has dierent reection properties. With liquids, furtherinterfering factors are uctuation product surface and foam genera-tion. With bulk solids, these are dust generation, material cone andadditional echoes from the vessel wall.

    To adapt the sensor to these dierent measuring conditions, theselection "Liquid " or "Bulk solid " should be made in this menu item.

    Through this selection, the sensor is adapted perfectly to the productand measurement reliability, particularly in products with poor reec-tive properties, is considerably increased.

    Enter the requested parameters via the appropriate keys, save yoursettings with  [OK]  and jump to the next menu item with the [ESC]  andthe  [->]  key.

    In addition to the medium, also the application, i.e. the measuring site,can inuence the measurement.

    With this menu item, the sensor can be adapted to the applications.The adjustment possibilities depend on the selection "Liquid " or "Bulksolid " under "Medium".

    The following options are available when "Liquid " is selected:

    Setup/Medium

    Setup/Application

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    38/84

    38

    6 Set up with the indicating and adjustment module

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

     3   6   5   0  

     3  -E N-1  2  1   0  1  1  

    The selection "Standpipe" opens a new window in which the innerdiameter of the applied standpipe is entered.

    The following features form the basis of the applications:

    Storage tank:

    • Setup: large-volumed, upright cylindrical, spherical• Product speed: slow lling and emptying• Process/measurement conditions:

     – Condensation – Smooth product surface – Max. requirement to the measurement accuracy

    Storage tanke with product circulation:• Setup: large-volumed, upright cylindrical, spherical• Product speed: slow lling and emptying• Vessel: small laterally mounted or large top mounted stirrer• Process/measurement conditions:

     – Relatively smooth product surface – Max. requirement to the measurement accuracy – Condensation – Slight foam generation – Overlling possible

    Storage tank on ships (Cargo Tank):• Product speed: slow lling and emptying• Vessel:

     – Installations in the bottom section (bracers, heating spirals) – High sockets 200 … 500 mm, also with large diameters

    • Process/measurement conditions: – Condensation, buildup by movement – Max. requirement on measurement accuracy from 95 %

    Stirrer vessel (reactor):

    • Setup: all vessel sizes possible

    • Product speed: – Fast to slow lling possible – Vessel is very often lled and emptied

    • Vessel: – Socket available – Large agitator blades of metal – Vortex breakers, heating spirals

    • Process/measurement conditions: – Condensation, buildup by movement – Strong spout generation – Very agitated surface, foam generation

    Dosing vessel:

    • Setup: all vessel sizes possible• Product speed:

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    39/84

    39

    6 Set up with the indicating and adjustment module

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

          3      6      5      0      3   -      E      N   -      1      2      1      0      1      1

     – Fast lling and emptying – Vessel is very often lled and emptied

    • Vessel: narrow installation situation• Process/measurement conditions:

     – Condensation, buildup on the antenna

     – Foam generationStandpipe:

    • Product speed: very fast lling and emptying• Vessel:

     – Vent hole – Joins like anges, weld joints – Shifting of the running time in the tube

    • Process/measurement conditions: – Condensation – Buildup

    Bypass:

    • Product speed: – Fast up to slow lling with short up to long bypass tube possible – Often the level is hold via a control facility

    • Vessel: – Lateral outlets and inlets – Joins like anges, weld joints – Shifting of the running time in the tube

    • Process/measurement conditions: – Condensation

     – Buildup – Separation of oil and water possible – Overlling into the antenna possible

    Plastic tank:

    • Vessel: – Measurement x mounted or integrated – Measurement depending on the application through the vessel

    top – With empty vessel, the measurement can be carried out

    through the bottom

    • Process/measurement conditions: – Condensation on the plastic ceiling – In outside facilities water and snow on the vessel top possible

    Transportable plastic tank:

    • Vessel: – Material and thickness dierent – Measurement through the vessel top

    • Process/measurement conditions: – Measured value jump with vessel change

    Open water (gauge measurement):

    • Gauge rate of change: slow gauge change• Process/measurement conditions:

     – Distance sensor to water surface to big

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    40/84

    40

    6 Set up with the indicating and adjustment module

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

     3   6   5   0  

     3  -E N-1  2  1   0  1  1  

     – Extreme damping of output signal due to wave generation – Ice and condensation on the antenna possible – Spiders and insect nestle in the antennas – Floating material and animals sporadically on the water surface

    Open ume (ow measurement):

    • Gauge rate of change: slow gauge change• Process/measurement conditions:

     – Ice and condensation on the antenna possible – Spiders and insect nestle in the antennas – Smooth water surface – Exact measurement result required – Distance to the water surface normally relatively high

    Rain water overfall (weir):

    • Gauge rate of change: slow gauge change

    • Process/measurement conditions: – Ice and condensation on the antenna possible – Spiders and insect nestle in the antennas – Turbulent water surface – Sensor ooding possible

    Demonstration:

    • Adjustment for all applications which are not typically level meas-urement

    • Sensor accepts all measured value changes within the measuringrange immediately

    • Typical applications: – Instrument demonstration – Object recognition/monitoring (additional settings required)

    Caution:If a separation of liquids with dierent dielectric gure occurs in thevessel, for example through condensation, the radar sensor candetect under certain circumstances only the medium with the higherdielectric gure. Keep in mind that layer interfaces can cause faultymeasurements.

    If you want to measure the total height of both liquids reliably, please

    contact our service department or use an instrument specially de-signed for interface measurement.

    The following options are available when "Bulk solid " is selected:

    The following features form the basis of the applications:

    Silo (slim and high):

    • Vessel of metal: weld joints• Process/measurement conditions: – Filling too close to the sensor – System noise with completely empty silo increased

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    41/84

    41

    6 Set up with the indicating and adjustment module

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

          3      6      5      0      3   -      E      N   -      1      2      1      0      1      1

     – Automatic false signal suppression with partly lled vessel

    Bunker (large-volumed):

    • Vessel of concrete or metal: – Structured vessel walls

     – Installations present• Process/measurement conditions: – Large distance to the medium – Large angles of repose

    Bunker with fast lling:

    • Vessel of concrete or metal, also multiple chamber silo: – Structured vessel walls – Installations present

    • Process/measurement conditions: – Measured value jumps, e.g. by truck loading 

    – Large distance to the medium – Large angles of repose

    Heap:

    • Sensor mounting on movable conveyor belts• Detection of the heap prole• Height detection during lling• Process/measurement conditions:

     – Measured value jumps, e.g. by the prole of the heap or trav-erses

     – Large angles of repose 

    – Measurement near the lling streamCrusher:

    • Vessel: installations, wear and protective facilities available• Process/measurement conditions:

     – Measured value jumps, e.g. by truck loading – Fast reaction time – Large distance to the medium

    Demonstration:

    • Adjustment for all applications which are not typically level meas-urement

    • Sensor accepts all measured value changes within the measuringrange immediately

    • Typical applications: – Instrument demonstration – Object recognition/monitoring (additional settings required)

    Through this selection, the sensor is adapted optimally to the applica-tion or the location and measurement reliability under the variousbasic conditions is increased considerably.

    Enter the requested parameters via the appropriate keys, save yoursettings with  [OK]  and jump to the next menu item with the [ESC]  andthe  [->]  key.

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    42/84

    42

    6 Set up with the indicating and adjustment module

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

     3   6   5   0  

     3  -E N-1  2  1   0  1  1  

    Also the vessel form can inuence the measurement apart from themedium and the application. To adapt the sensor to these measure-ment conditions, this menu item oers you dierent options for vesselbottom and ceiling in case of certain applications.

    Enter the requested parameters via the appropriate keys, save yoursettings with  [OK]  and jump to the next menu item with the [ESC]  andthe [->]  key.

    With this selection, the operating range of the sensor is adapted tothe vessel height and the reliability with dierent frame conditions isincreased considerably.

    Independent from this, the min. adjustment must be carried out.

    Enter the requested parameters via the appropriate keys, save yoursettings with  [OK]  and jump to the next menu item with the [ESC]  andthe [->]  key.

    Since a radar sensor is a distance measuring instrument, the distancefrom the sensor to the product surface is measured. For indication ofthe real level, an allocation of the measured distance to the percent-age height must be carried out.

    To perform the adjustment, enter the distance with full and empty ves-sel, see the following example:

    Setup/Vessel form

    Setup/Vessel height,measuring range

    Setup/Adjustment

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    43/84

    43

    6 Set up with the indicating and adjustment module

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

          3      6      5      0      3   -      E      N   -      1      2      1      0      1      1

    100%

    0%

       0 ,   5   m

        (   1   9 .   6   8               "               )

       5   m

        (   1   9   6 .   9

                   "               )

    2

    1

    Fig. 36: Parameter adjustment example min./max. adjustment 

    1 Min. level = max. meas. distance 2 Max. level = min. meas. distance

    If these values are not known, an adjustment with the distances of forexample 10 % and 90 % is possible. Starting point for these distancespecications is always the seal surface of the thread or ange. Bymeans of these settings, the real level will be calculated.

    The real product level during this adjustment is not important, be-cause the min./max. adjustment is always carried out without chang-ing the product level. These settings can be made ahead of timewithout the instrument having to be installed.

    Proceed as follows:

    1. Select the menu item "Setup" with  [->]  and conrm with [OK] .Now select with  [->]  the menu item "Min. adjustment " and conrmwith [OK] .

    2. Edit the percentage value with [OK]  and set the cursor to therequested position with  [->] .

    3. Set the requested percentage value with [+]  and save with [OK] .The cursor jumps now to the distance value.

    Setup/Min. adjustment

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    44/84

    44

    6 Set up with the indicating and adjustment module

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

     3   6   5   0  

     3  -E N-1  2  1   0  1  1  

    4. Enter the suitable distance value in m for the empty vessel (e.g.distance from the sensor to the vessel bottom) corresponding tothe percentage value.

    5. Save settings with  [OK]  and move with  [ESC]  and [->]  to the max.adjustment.

    Proceed as follows:

    1. Select with  [->]  the menu item max. adjustment and conrm with [OK] .

    2. Prepare the percentage value for editing with [OK]  and set thecursor to the requested position with  [->] .

    3. Set the requested percentage value with [+]  and save with [OK] .The cursor jumps now to the distance value.

    4. Enter the appropriate distance value in m (corresponding to thepercentage value) for the full vessel. Keep in mind that the max.level must lie below the min. distance to the antenna edge.

    5. Save settings with  [OK] 

    The respective min. and max. measured value is saved in the sensor.The values are displayed in the menu item "Peak values".

    When non-contact level sensors are used, the measurement can beinuenced by the respective process conditions. In this menu item,the measurement reliability of the level echo is displayed as dB value.The measurement reliability equals signal strength minus noise. Thehigher the value, the more reliable the measurement. With a function-ing measurement, the values are > 10 dB.

    Setup/Max. adjustment

    Diagnosis/Peak value

    Diagnosis/Measurementreliability

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    45/84

    45

    6 Set up with the indicating and adjustment module

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

          3      6      5      0      3   -      E      N   -      1      2      1      0      1      1

    The "Echo curve" shows the signal strength of the echoes over themeasuring range in dB. The signal strength enables an evaluation ofthe quality of the measurement.

    The "False signal suppression" displays the saved false echoes (seemenu " Additional settings") of the empty vessel with signal strength in"dB" over the measuring range.

    A comparison of echo curve and false signal suppression allows amore accurate conclusion on measurement reliability. The selected

    curve is continuously updated. With the  [OK]  key, a submenu withzoom functions is opened:

    • "X-Zoom": Zoom function for the meas. distance• "Y-Zoom": 1, 2, 5 and 10x signal magnication in "dB"• "Unzoom": Reset the presentation to the nominal measuring range

    with single magnication

    With the function "Echo curve memory " the echo curve can be savedat the time of setup. This is generally recommended; for using the As-set Management functions it is absolutely necessary. If possible, the

    curve should be saved with a low level in the vessel.With the adjustment software PACTware and the PC, the high resolu-tion echo curve can be displayed and used to recognize signalchanges over the operating time. In addition, the echo curve of thesetup can be also displayed in the echo curve window and comparedwith the actual echo curve.

    The following circumstances cause interfering reections and caninuence the measurement:

    • High sockets

    Diagnoses/Curve indica-tion

    Diagnostics/Echo curvememory

    Additional adjustments/ False signal suppression

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    46/84

    46

    6 Set up with the indicating and adjustment module

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

     3   6   5   0  

     3  -E N-1  2  1   0  1  1  

    • Vessel installations such as struts• Agitators• Buildup or welded joints on vessel walls

    Note:

    A false signal suppression detects, marks and saves these false sig-nals so that they are no longer taken into account for level measure-ment.

    This should be done with the low level so that all potential interferingreections can be detected.

    Proceed as follows:

    1. Select the menu item " Additional settins" with  [->]  and conrmwith [OK] . With [->]  you have to select the menu item "Falsesignal suppression" and conrm with [OK] .

    2. Conrm again with [OK] .

    3. Conrm again with [OK] .

    4. Conrm again with [OK]  and enter the actual distance from thesensor to the product surface.

    5. All interfering signals in this section are detected by the sensorand stored after conrming with  [OK] .

    Note:

    Check the distance to the product surface, because if an incorrect(too large) value is entered, the existing level will be saved as falsesignal. The lling level would then no longer be detectable in this area.

    If a false signal suppression has already been created in the sensor,the following menu window appears when selecting "False signalsuppression":

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    47/84

    47

    6 Set up with the indicating and adjustment module

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

          3      6      5      0      3   -      E      N   -      1      2      1      0      1      1

    The menu item "Delete" is used to completely delete an already cre-ated false signal suppression. This is useful if the saved false signalsuppression no longer matches the metrological conditions in thevessel.

    The menu item "Extend " is used to extend an already created false

    signal suppression. This is useful if a false signal suppression wascarried out with a too high level and not all false signals could be de-tected. When selecting "Extend ", the distance to the product surfaceof the created false signal suppression is displayed. This value cannow be changed and the false signal suppression can be extended tothis range.

    A linearization is necessary for all vessels in which the vessel volumedoes not increase linearly with the level - e.g. in a horizontal cylindri-cal or spherical tank - and the indication or output of the volume isrequired. Corresponding linearization curves are preprogrammed

    for these vessels. They represent the correlation between the levelpercentage and vessel volume.

    By activating the appropriate curve, the volume percentage of thevessel is displayed correctly. If the volume should not be displayed inpercent but e.g. in l or kg, a scaling can be also set in the menu item"Display ".

    Enter the requested parameters via the appropriate keys, save yoursettings and jump to the next menu item with the [ESC]  and [->]  key.

    Caution:Note the following if the instrument with corresponding approval isused as part of an overll protection system according to WHG:

    If a linearisation curve is selected, the measuring signal is no longerlinearly proportional to the level. This must be taken into considerationby the user, particularly when setting the switching point on the levelswitch.

    With a reset, certain parameter adjustments carried out by the userare reset.

    The following reset functions are available:

    Delivery status: Restoring the parameter settings at the time of ship-ment from the factory incl. the order-specic settings. A created false

    Additional adjustments/ Linearization curve

    Additional adjustments- Reset

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    48/84

    48

    6 Set up with the indicating and adjustment module

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

     3   6   5   0  

     3  -E N-1  2  1   0  1  1  

    signal suppression, user-programmable linearization curve as well asthe measured value memory will be deleted.

    Basic settings: Resetting the parameter settings incl. special andlaboratory parameters to the default values of the respective instru-ment. A created false signal suppression, user programmable lineari-

    zation curve as well as the measured value memory will be deleted.Setup: Resetting of the parameter settings to the default values of therespective instrument in the menu item Setup. User-generated falsesignal suppression, user-programmed linearization curve, measuredvalue memory as well as event memory remain untouched. Thelinearization is set to linear.

    False signal suppression: Deleting a previously created false signalsuppression. The false signal suppression created in the factoryremains active.

    Peak values measured value: Resetting of the measured min. and

    max. distances to the actual measured value.The following table shows the default values of the instrument. De-pending on the instrument version, not all menu items are available ordierently assigned:

    Menu Menu item Default value

    Setup Measurementloop name

    Sensor

    Medium Liquid/Water

    Bulk solids/Crushed stones, gravel

    Applications Storage tank

    Silo

    Vessel form Vessel bottom, dished boiler end

    Vessel top, dished boiler end

    Vesell height/ Measuring range

    Recommended measuring range, see"Technical data" in the supplement

    Min. adjustment Recommended measuring range, see"Technical data" in the supplement

    Max. adjustment 0,000 m(d)

    Damping 0.0 s

    Current outputmode

    4 … 20 mA, < 3.6 mA

    Current outputMin./Max.

    Min. current 3.8 mA, max. current20.5 mA

    Lock operation Released

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    49/84

    49

    6 Set up with the indicating and adjustment module

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

          3      6      5      0      3   -      E      N   -      1      2      1      0      1      1

    Menu Menu item Default value

    Display Language Like order

    Displayed value Distance

    Display unit m

    Scaling size Volume

    l

    Scaling 0.00 lin %, 0 l

    100.00 lin %, 100 l

    Backlight Switched o

    Additional adjust-ments

    Distance unit m

    Temperature unit °C

    Probe length Length of the standpipe Ex factory

    Linearisation

    curveLinear

    HART mode Standard

    Address 0

    6.4 Saving the parameter adjustment data

    We recommended noting the adjusted data, e.g. in this operatinginstructions manual, and archiving them afterwards. They are thusavailable for multiple use or service purposes.

    If the instrument is equipped with an indicating and adjustmentmodule, the data in the sensor can be saved in the indicating andadjustment module. The procedure is described in the operatinginstructions manual "Indicating and adjustment module" in the menuitem "Copy sensor data". The data remain there permanently even ifthe sensor power supply fails.

    The following data or settings for adjustment of the indicating andadjustment module are saved:

    • All data of the menu "Setup" and "Display "• In the menu " Additional adjustments" the items "Sensor-specic

    units, temperature unit and linearization"

    • The values of the user programmable linearisation curveThe function can also be used to transfer settings from one instru-ment to another instrument of the same type. If it is necessary toexchange a sensor, the indicating and adjustment module is insertedinto the replacement instrument and the data are likewise written intothe sensor via the menu item "Copy sensor data".

  • 8/19/2019 Vegapuls 62 Extended Range Manual – Up to 212 ft.pdf

    50/84

    50

    7 Setup with PACTware

    VEGAPULS 62 • 4 … 20 mA/HART - two-wire

     3   6   5   0