VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve Goodhew School of Engineering, Environmental Building Group, University of Plymouth Reynolds Building, Drake Circus, Plymouth Devon PL4 8AA United Kingdom Email: [email protected] Tel: + 44 (0) 1752 233695 Fax: + 44 (0) 1752 232638 * corresponding author ABSTRACT Most thermal properties of construction materials used in the analysis of building performance have been measured under laboratory conditions, using a guarded hot box or hot plate apparatus. As a consequence, these properties seldom reflect the impact of actual conditions (especially moisture content) on the values of conductivity and diffusivity. Hence there is a need to develop techniques that allow to take into account local conditions, and measure building material properties in situ. One option available is the use of a thermal probe. The thermal probe technique is based on creating a line source in a material sample, and measuring the temperature rise in the sample in reaction to heat being applied. Obviously the data analysis routines used to calculate thermal conductivity and thermal diffusivity based on the temperature rise observed are crucial to the success of the technique. Transient thermal simulation of a of a model representing a line source in an infinite material sample has been used to generate a set of numerical data sets to validate analysis routines in conjunction with an experimental thermal probe apparatus. Findings show that by careful application of these routines, a close agreement with simulation input values can be achieved, 1

Upload: others

Post on 27-Dec-2019

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: VALIDATION OF DATA ANALYSIS ROUTINES FOR A ...VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve

VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve Goodhew School of Engineering, Environmental Building Group, University of Plymouth Reynolds Building, Drake Circus, Plymouth Devon PL4 8AA United Kingdom Email: [email protected] Tel: + 44 (0) 1752 233695 Fax: + 44 (0) 1752 232638 * corresponding author

ABSTRACT

Most thermal properties of construction materials used in the analysis of building

performance have been measured under laboratory conditions, using a guarded hot box or hot

plate apparatus. As a consequence, these properties seldom reflect the impact of actual

conditions (especially moisture content) on the values of conductivity and diffusivity. Hence

there is a need to develop techniques that allow to take into account local conditions, and

measure building material properties in situ. One option available is the use of a thermal

probe. The thermal probe technique is based on creating a line source in a material sample,

and measuring the temperature rise in the sample in reaction to heat being applied. Obviously

the data analysis routines used to calculate thermal conductivity and thermal diffusivity based

on the temperature rise observed are crucial to the success of the technique.

Transient thermal simulation of a of a model representing a line source in an infinite material

sample has been used to generate a set of numerical data sets to validate analysis routines in

conjunction with an experimental thermal probe apparatus. Findings show that by careful

application of these routines, a close agreement with simulation input values can be achieved,

1

Page 2: VALIDATION OF DATA ANALYSIS ROUTINES FOR A ...VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve

with errors of less than one percent. This validates the analysis routines and provides a deeper

appreciation of the theoretical behaviour of a thermal probe.

KEYWORDS

Validation, thermal probe, measurement, analysis routines, transient simulation

LIST OF SYMBOLS

α thermal diffusivity of the specimen [m2s-1]

λ thermal conductivity of the specimen [Wm-1K-1]

ϑ temperature of the thermal probe [K]

m mass per unit length of the thermal probe [kgm-1]

cp specific heat capacity of the thermal probe [Jkg-1K-1]

r0 external radius of the themal probe [m]

r1 internal radius of the thermal probe [m]

αp thermal diffusivity of the thermal probe material [m2s-1]

H “outer conductivity” of the thermal probe [Wm-2K-1]

L length of the thermal probe [m]

Q heat supplied per unit length of the thermal probe [Wm-1]

T elapsed time of the measurements [s]

W rate of energy arrival, where W=Ql, [W]

INTRODUCTION TO THE THERMAL PROBE TECHNIQUE

Reliable data concerning the thermal properties of building materials, in particular the thermal

conductivity (λ) and thermal diffusivity (α), is needed for the proper simulation of the thermal

behavior of buildings, whether in a design stage, refurbishment project, or research context.

However, much of the data currently used in building performance simulation is obtained

2

Page 3: VALIDATION OF DATA ANALYSIS ROUTINES FOR A ...VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve

under laboratory conditions, which results in two main problems. Firstly, material properties

established using techniques like the guarded hot box method might reflect a dried-out

condition, which differs from material properties in actual use. Secondly, actual material

properties might be hard to obtain from a handbook due to the multitude of variants of any

material, for instance resulting from different manufacturing processes and differences in

ingredients.

An alternative to drawing on laboratory data sources is the use of in-situ measurements,

allowing the capture of actual thermal properties of materials in buildings in use. One

technique for measuring such data on site is the use of a thermal probe apparatus. Thermal

probes have been developed and used in other industries, such as geotechnics, food and

plastic manufacturing; they are only recently being applied to buildings.

Many authors have researched thermal measurement techniques based on transient hot

wire/probe techniques. Schleiermacher (1888) first suggested and carried out measurements

followed by Niven (1905) who carried out experiments with a platinum wire acting as a line

source. Stalhane and Pyk (1931) developed a technique which cased the hot wire within a

tube and used a mercury thermometer to record the temperature rise of the tube. Following

the mathematical proofs contained in the seminal work, Carslaw and Jaeger (1947,) van der

Held and van Drunen (1949) outlined the basis for ‘non-stationary’, or transient, thermal

conductivity measurement. Their technique recorded the temperature at the midpoint of the

heating wire and plotted the temperature rise Δθ against the natural logarithm of time (t), the

thermal conductivity being deduced from the slope of this straight line Δθ/ln(t). Hooper and

Lepper (1950) recognised the limitations of the guarded hot plate method of measuring

thermal conductivity in their investigation concerning the thermal properties of moist soils.

3

Page 4: VALIDATION OF DATA ANALYSIS ROUTINES FOR A ...VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve

Not only did moisture migration have to be contended with but the physical structure of the

soils had to be disturbed to prepare samples, problems previously recognised by Patten

(1909). Blackwell and Misener (1951) studied the methodology developed by Hooper and

Lepper and deduced that the contact resistance between the probe and sample was significant.

Blackwell (1954) commented upon a number of issues concerning the thermal conductivity

probe, regarding heat losses through thermocouple wires affecting temperature measurements,

short time measurements and theoretical error levels for various probe length to diameter

ratios. De Vries and Peck (1958) developed the work of van der Held, Jaeger and Blackwell

and concluded that thermal conductivity values for soils and materials with similar thermal

properties could be measured to within 5% of the accepted values of the thermal properties of

these materials. Blackwell (1954) further offered a mathematical solution which potentially

allowed the calculation of the thermal diffusivity (α) of any material that could be measured

with a known thermal contact resistance (H) between probe and material. Vos (1955)

identified various causes for deviation from the linear including thermal capacity, reflection

and the effect of inhomogeneity. Niovichenok and Pikus (1975) used an uncased hot wire to

measure both the thermal conductivity and diffusivity of various oils, including petroleum

jelly. They recognised errors were caused by the limiting factors in their use of Blackwell’s

solution. Davis and Downs (1980) carried out a critical review of the hot wire transient line

source method, as applied to the measurement of thermal conductivity in insulating refractory

bricks with thermal conductivities in the region of 0.12 – 0.6 Wm-1K-1. Batty et al (1984a),

(1984b) carried out a review of the thermal probe technique and performed numerous trial

measurements. Jones (1988), following van der Held and van Drunen and Batty, worked on

obtaining thermal conductivity results from Δθ/ln(t) at early times, before linearity had

necessarily been reached, by finite element analysis. Campbell et al (1991) used two parallel

probes to measure thermal diffusivity in various soils, in a similar method to that used by

4

Page 5: VALIDATION OF DATA ANALYSIS ROUTINES FOR A ...VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve

Drury (1988) and Morabito (1989). Davies et al (2004), used dual thermal probes to measure

relative and fluctuating moisture content of building envelopes, assuming that the volumetric

heat capacity of soil could be measured within 1% of accepted values when using typical

probe geometries and heating times. Moisture content could then be calculated either by

comparing results with those of a dry sample or with values from accepted references.

Banaszkiewicz et al (1997), following Seiferlin et al (1996) and citing prior successes by de

Groot et al (1974) in gases, Sandberg et al (1977) in liquids, Buettner (1955) and Seiferlin et

al (1996) in solids, followed traditional line source models. Algorithms were developed

whereby, rather than using just two points as a linear asymptote of Δθ/ln(t), a least squares

optimisation process was carried out.

The authors of this article have been developing the thermal probe technique for a number of

years (Goodhew, 2000; Goodhew and Griffiths, 2003; Goodhew and Griffiths, 2004),

(Pilkington, 2008) following on the work by Batty et al (1984a, 1984b). Various probes were

manufactured using copper tubing of assorted diameters with a variety of fillers, such as

epoxy, containing a heater wire and thermocouples, before procuring commercially available

Hukseflux TP02 150mm probes, and then the shorter 70mm TP08 probes. An image of the

latest experimental thermal probe equipment is presented in figure 1.

5

Page 6: VALIDATION OF DATA ANALYSIS ROUTINES FOR A ...VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve

Figure 1. The thermal probe equipment during calibration phase, measuring agar

immobilized or stabilized water.

Goodhew (2000), recognised that the probe’s outer conductance, or contact resistance

between the probe and sample, termed H, was generating a greater influence on results for

thermal diffusivity than many previous researchers had accounted for. An iterative

optimization routine using the MS Excel add-in program Solver (2007) was developed, in line

with Batty’s arrangement of Blackwell’s work. Goodhew and Griffiths (2003) discussed the

appropriate time section of Δθ/ln(t) for analysis using the Solver routines. Thermal

conductivity was found via a regression analysis of the earliest available part of a linear

asymptote, before the effects of ‘thermal drift’ became significant. Goodhew and Griffiths

(2004), (2005) reported thermal conductivity, thermal diffusivity and volumetric heat capacity

values for mineral oil, magna, paraffin wax and PTFE, measured by thermal probes and using

the Solver analysis routines.

For the experimental thermal probe, a probe of length L, radius r and mass per unit length m

is inserted into a material with thermal conductivity λ , diffusivity α and density ρ. The probe

sample combination is allowed to reach thermal equilibrium. A constant power per unit length

Q Watts/m is applied to an axially mounted heater within the probe and the probe temperature

rise is Δθ after an elapsed heating time t seconds. This rise in probe temperature is recorded

and a graph of the rise is plotted against the natural logarithm of the elapsed time. Blackwell

(1954) gave a series expansion for the rise in temperature Δθ at the surface of a probe as a

function of time t:

Δθ = A { lnt + B + (1/t)[Clnt + D] + (1/t2)[Flnt + G] + ... } (1)

6

Page 7: VALIDATION OF DATA ANALYSIS ROUTINES FOR A ...VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve

After some time the terms in (1/t2) in this equation are ignored, and the first four terms give

Δθ(4) as:

Δθ(4) = A { lnt + B + (1/t)[Clnt + D]} (2)

At even longer times the terms in (1/t) can also be ignored, and the first two terms give:

Δθ(2) = A( lnt + B) (3)

where

A = Q/4π λ

B = ln(4α/r2) - γ + 2λ/rH

C = (r2/2α)[1 - αmcp/πr2Lλ] and

D = (r2/2α) [ln(4α/r2 ) - γ + 1 - Bαmcp/πr2Lλ]

Here γ is the Euler constant 0.5772, H is the probe to sample thermal conductance, and cp the

probe specific heat capacity. The graph of the rise in probe temperature versus the natural

logarithm of the elapsed heating time will be a straight line of slope S and intercept I, so that

by comparison with equation 2:

λ = Q / (4 π S) and (4)

α = (r2/4)*exp[(I/S) + γ −2λ/rH] (5)

Note that if the thermal contact between the probe and the sample is perfect then H is infinite

and the term 2λ/rH is zero.

The volumetric heat capacity of the sample ρC is given by the ratio of the thermal

conductivity to the diffusivity, or ρC = λ/α. For further discussion of the Blackwell

expressions see Goodhew and Griffiths (2004), and Batty et al (1984).

7

Page 8: VALIDATION OF DATA ANALYSIS ROUTINES FOR A ...VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve

When analysing probe data for each and every power per m, and probe - sample combination,

a fundamental question is that of which time series is to used. Or, in other words: to determine

when the Blackwell (1954) two constants expression be safely applied to the collected data.

A Solver routine employing the Blackwell four constants expression is used to determine

approximate values of sample conductivity and diffusivity, mainly as a guide, but more

importantly to determine the elapsed heating time required so that the error between the

Blackwell two constants approximation and the Blackwell four constants approximation is

less than 1%. The Solver routines were constructed using the readily available Microsoft

Excel Solver tool which uses the Generalized Reduced Gradient (GRG2) nonlinear

optimization code developed by Leon Lasdon, University of Texas at Austin, and Allan

Waren, Cleveland State University (Lasdon et al, 1978) Since the Blackwell expressions

contain individual terms with both conductivity and diffusivity a non-linear optimization code

was necessary. These Solver routines were developed, by Goodhew and Griffiths (2004), to

analyze the practical probe data, which was assumed to have three unknowns, namely (1) the

sample thermal conductivity, (2) the thermal diffusivity, and (3) the probe to sample

conductance H, which was assumed to be finite. Theoretical probe temperature rises with time

for a given probe and sample combination were calculated using both the Blackwell two

constant model, Δθ (2), using A and B from equation 3 above, and the Blackwell four

constant model, Δθ (4) using A, B, C and D from equation 2 above. The two Solver routines

were called Solver 2.3, a routine based upon the Blackwell approximation with two constants

and with the three unknowns, and Solver 4.3 a routine based upon the Blackwell

approximation with four constants and again the same three unknowns. For every second the

difference between the experimental probe rise temperature and the theoretical probe rise

temperature is determined, the difference is squared to remove the negative contributions, and

8

Page 9: VALIDATION OF DATA ANALYSIS ROUTINES FOR A ...VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve

the squared differences summed. Using an iterative process Solver then finds the minimum of

this sum and reports the optimum values of the sample conductivity, the diffusivity and the

probe conductance. It is still necessary to know at what time the data may be safely analyzed

so that the assumptions is valid.

In this article the model discussed is theoretical in nature and therefore assumes a close to

infinite probe conductance and therefore doesn’t require the third unknown within the four

constant Solver routine. Thus a Solver 4.2 rather than a Solver 4.3 routine is employed to

analyse the data from the model.

THE NEED FOR VALIDATION OF THE SOLVER ANALYSIS ROUTINES

The thermal probe equipment described in the previous section has been used to study a large

number of material samples in both laboratory conditions as well as in in field experiments on

real buildings (Pilkington et al, 2007; Pilkington, 2008). Initial analysis of the results suggests

that the conductivity values can mostly be identified with an accuracy of within ± 10%.

However, obtaining values for the thermal diffusivity proves more challenging. Moreover, the

number of possible practical measurements of the thermal properties of real materials is

limited due to constraints of numbers of suitable sample materials that exhibit properties that

lend themselves to being appropriate for the probe to measure. The lack of appropriate

reference data specific to some materials and the amount of cumulative time required are also

limiting factors when undertaking either in situ or laboratory measurements upon materials

that have a wide range of thermal properties.

Different factors can have an impact of the accuracy obtained in the experiments. The

measured data can be expected to be influenced by a number of physical factors like the

contact resistance between the probe and the sample, and heat losses at either end of the

9

Page 10: VALIDATION OF DATA ANALYSIS ROUTINES FOR A ...VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve

probe. Findings can also be influenced by the measurement procedure, for instance the value

of heating power provided to the probe. Furthermore, validation of the data analysis

techniques (the Solver 2.3 and Solver 4.3 routines) is crucial. It is acknowledged by Goodhew

and Griffith (2004) that they might need further improvement, especially regarding the

identification and selection of a suitable time window in which to determine the slope

Δθ/ln(t).

Consequently, the objective of the work described in this article is the use of a thermal

simulation model in for the validation of the data analysis routines. Studies with the thermal

model provide the opportunity to study the thermal probe from a theoretical point of view,

allowing a rigorous testing of the assumptions, mathematics and the data analysis procedures.

They allow a comparison of the effects of individual factors one by one, studying their impact

on the practical results obtained, something which is difficult in real experiments.

Furthermore the use of simulation allows the research to venture into ‘extreme’ situations,

thereby improving the understanding of the theoretical interaction between thermal

conductivity, thermal diffusivity, and various temperature rises employed. The advantage here

is that a simulation model can have hypothetical conductivity and diffusivity values that are

not readily found in real materials.

TRANSIENT SIMULATION FOR THE GENERATION OF NUMERICAL DATA SETS

The work described in this article addresses the simulation of an infinitely thin and long line

heat source in an almost infinite homogenous block of material. Numerical results thereby

represent a theoretically very small diameter line heat source, and do not show any effects

related to presence of a real probe. For the study, use has been made of the Physibel program

10

Page 11: VALIDATION OF DATA ANALYSIS ROUTINES FOR A ...VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve

Voltra that allows calculation of transient heat transfer using the energy balance technique

(Physibel, 2005).

Within Voltra, a model has been built of very large slice of a material sample with outer

dimensions of 2400 x 2400 mm, but with a thickness of only 1 mm. The boundary conditions

on both faces of this slice of material have been defined as adiabatic, rendering the material

infinite in the direction perpendicular to these faces. The line heat source is modeled at the

middle of this slice, again perpendicular to the faces, positioned at 1200 mm from the

boundaries of the sample. Voltra uses a rectangular grid, and gridlines have been put at 1 mm

apart closer to the line source in order to approximate the radial distribution of heat, gradually

widening the grid further away reaching 20 mm spacing at the outer edges, see figure 2. For

this model, various combinations of thermal conductivity λ and thermal diffusivity α have

been entered, with homogenous properties across the whole sample. The application of power

at the heart of the line source models an infinitesimal thin probe without any contact

resistance.

11

Page 12: VALIDATION OF DATA ANALYSIS ROUTINES FOR A ...VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve

Figure 2. The material sample model in Voltra. The line source is simulated at the origin,

perpendicular to the (adiabatic) face of the sample.

Each simulation experiment starts under steady state conditions, where the material sample is

at 20.0oC and sits in an environment of the same temperature. After an initial 60 seconds (for

acclimatisation) a step function is then used to apply a constant power of 3 W/m to the line

source. The temperatures are monitored at distances of 1, 2, 5, 10 and 50 mm away from the

line source. Simulation results then have been exported to Microsoft Excel, where the first 60

seconds (steady state situation at 20oC) has been discarded and the temperature rise

transformed to data for Δθ/ln(t). Regression analysis is then carried out, and the thermal

conductivity λ and thermal diffusivity α calculated using equations (4) and (5). The

volumetric heat capacity (VHC) or ρC is given by the ratio λ/α.

APPLICATION OF SOLVER ANALYSIS ROUTINES TO NUMERICAL DATA SETS

Numerical data sets have been generated in Voltra for two main categories: typical

construction materials and theoretical materials. For the typical construction materials,

properties for λ, ρ and C have been taken from the ASHRAE Handbook of Fundamentals

(2005). Subsequently a range of theoretical materials has been studied, varying values of λ

and ρC over a wide domain, allowing assessment over the whole range and including very

extreme cases, in order to see how these impact on results obtained.

TYPICAL CONSTRUCTION MATERIALS

Table 1 and 2 show the results of some of the simulation studies for the typical construction

materials. All the studies were conducted with a heater power of 3 W/m and the temperatures

12

Page 13: VALIDATION OF DATA ANALYSIS ROUTINES FOR A ...VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve

were recorded at 1mm from the simulated axial heater. Table 1 gives the model input data,

together with the Solver 4.3 error time for E% = 1, te seconds. These materials consisted of

three mineral samples and three vegetable samples. The input data for these six real samples

was taken from the ASHRAE Handbook of Fundamentals (2005). The Solver 4.3 routine was

used to determine the values of te and approximate values for the sample thermal conductivity

and diffusivity. Table 2 shows the results, the first column giving the time interval chosen for

the regression analysis, the final column the volumetric heat capacity of the samples. As can

be seen from comparing Table 1 and Table 2 there is reasonable agreement between the input

thermal data and the values obtained from the analysis routine. As the temperature

measurements were made to two decimal places, when the rise temperature was only 1C over

the time interval then the results would be expected to be uncertain by about 1%. This

uncertainty becomes more obvious in the values of the diffusivity as this quantity depends on

the intercept on the temperature axis. This is seen in the resulting values of the diffusivity

when the output values are compared with the input.

13

Page 14: VALIDATION OF DATA ANALYSIS ROUTINES FOR A ...VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve

Table 1. Voltra simulation input data

Material

Density [kg/m3]

Conductivity [W/mK]

Diffusivity [*107 m2/s]

Specific heat capacity

[J/kgK]

Solver 4.2 error time te

[s] Fire clay brick 1790 1.00 6.73 830 80 Brick 1970 0.7 4.44 800 110 Sand 1520 0.33 2.71 800 260 Oak 750 0.18 1.00 2390 830 Fir 540 0.12 1.84 1210 420 Cellulose 54 0.057 8.12 1300 80

Table 2. Results from regression analysis (using Solver routines) of Voltra simulation output

Material

Interval for analysis

[s] Conductivity

[W/mK] Diffusivity [*107 m2/s]

Specific heat capacity

[J/kgK]

Volumetric heat capacity

[MJ/m3K] Fire clay brick 100 to 300 1.00 6.31 880 1.58 Brick 150 to 350 0.7 4.16 850 1.68 Sand 300 to 500 0.33 2.57 840 1.28 Oak 1300 to 1500 0.18 0.98 2400 1.81 Fir 500 to 1500 0.12 1.9 1190 0.64 Cellulose 100 to 500 0.058 8.36 1320 0.07

THEORETICAL MATERIALS

In order to get a better understanding of the impact of input parameters on computational

outcomes, a set of theoretical materials have been studied, varying the inputs of λ and ρC. The

following combinations have been reviewed, see table 3.

14

Page 15: VALIDATION OF DATA ANALYSIS ROUTINES FOR A ...VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve

Table 3. The three combination of the pairings of magnitude of λ and ρC

low λ

low ρC

average λ

low ρC

high λ

low ρC

low λ

average ρC

average λ

average ρC

high λ

average ρC

low λ

high ρC

average λ

high ρC

high λ

high ρC

The input for the Voltra simulations as shown in table 3 has been implemented by λ values of

0.01 (low), 0.6 (average) and 2.0 (high). Values for ρC have been varied by changing C only,

with ρ taken to be constant at 1000. Values used for C are 100 (low ρC), 2000 (average ρC)

and 6000 (high ρC). Note that “low”, “average” and “high” values are related to common

materials found in building construction. Most of the Voltra studies showed the characteristic

behaviour observed in previous measurements, (Goodhew and Griffiths, 2004) when the rise

in probe temperature was plotted against the natural logarithm of the elapsed heating time.

Values of the calculated thermal conductivity from the Voltra simulations generally agreed

with the values inputted to the model. However, with the low thermal conductivity study, with

conductivity as 0.01 W/m2K, and for the three associated values of the specific heat capacity,

(100, 2000 and 6000 J/kgK), and with the adopted heating input of 3 W/m, the rises in

temperature at 1mm from the heater were large compared with the laboratory studies. The

Voltra model showed typical temperature rises of 40 to100oC in 200 s, whereas in the

laboratory or field studies 6 to 9oC would be expected or used. To analyse the low thermal

conductivity data from the model studies provided an interesting vehicle for exploring the

analysis routine of Goodhew and Griffiths (2004). From the physical data it would be

15

Page 16: VALIDATION OF DATA ANALYSIS ROUTINES FOR A ...VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve

expected that the rise would take a long time, small conductivity, but the magnitude of the

rise in temperature would be large for materials with low specific heat capacity.

There are practical reasons for restricting the data analysis to 300 to 400 s when analysing

data from the laboratory and field. For example, when the increase in the rise in probe

temperature becomes too small for practical power inputs, there is considerable data scatter

and axial heat losses can depending upon the sample material being measured, mar the

results. However, the Voltra studies consider the heat flow in an infinite medium with no

physical probe and therefore the results provide an opportunity to view the thermal probe

technique from a simple theoretical stance, and to test the model, the assumptions, the

mathematics or theory and the data analysis strategies. As there is no physical probe in the

Voltra simulation the probe to sample conductance H is infinitely large and the thermal

capacity of the probe must be zero. This provides the opportunity to rigorously test the

analysis routine employing equations 3 and 4 with regression analysis to determine both the

thermal conductivity and the diffusivity.

As stated in the introduction, when analysing probe data for each and every power per m, and

probe - sample combination, it is crucial to determine when the Blackwell (1954) two

constants expression be safely applied to the collected data.

For the application of the Solver routines, the following criterion was suggested by Goodhew

and Griffiths (2004) to determine the time interval for the analysis of the data. The % Error

for the rise temperature using 2 (Δθ(2)) or 4 (Δθ(4)) constants, E%, was defined as:

E% = 100 [ Δθ(4) - Δθ(2) ] / Δθ(4) (6)

This was taken arbitrarily to be 1%, and the corresponding time te can be found from:

16

Page 17: VALIDATION OF DATA ANALYSIS ROUTINES FOR A ...VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve

1% = 100 { (1/te) [Clnte + D] / { lnte + B + (1/te)[Clnte +D]} (7)

A graph of E% versus time allows the time te to be determined, or alternatively the “goal

seek” routine in Excel may be used to solve the above expression for te. This allows the

appropriate time window for the regression analysis of the data, or the application of Solver

2.3, to be set. The analysis must start after te second has elapsed.

To illustrate this process a detail discussion of the analysis of one set of simulation data will

be described. The chosen set of data for this discussion is the Voltra study with thermal

conductivity 0.01 W/m2K, thermal capacity 100 J/kgK, and density 1000 kg/m3, giving a

diffusivity of 10-7 m2/s. The heater power was 3 W/m, with the temperature rise in the

medium measured at 1 mm from the line source. A graph of the rise in temperature versus the

natural logarithm of the elapsed heating time is shown in figure 3. Visual inspection of the

curve in figure 3 confirms that there is the characteristic “s” shape before the asymptotic

approach to the final straight line beyond natural logarithm time of 5.2, or beyond a time of

about 180 s. The temptation is to apply the regression analysis to this data from 30 to 1500 s,

or natural logarithm 3 to 7. Here, the resulting conductivity is 0.0103 W/m2K and diffusivity

1.12x10-7 m2/s. The conductivity is 3% above the true or input value, while the diffusivity is

12% above the input value. These errors are of similar magnitude to those often found in the

experimental laboratory and field work.

Following the recipe proposed by Goodhew and Griffiths (2004) a Solver 4.2 routine was

applied to this data over the time interval 1300 to 1500s. Solver 4.2 is a Blackwell 4 constant

expression with 2 variables, the sample thermal conductivity and diffusivity. The probe

conductance was set to 1016m2K/W or a large number, arrived at by saying 100 million is

large so that squared must be very large. The probe capacity is set to zero. Figure 4 shows the

17

Page 18: VALIDATION OF DATA ANALYSIS ROUTINES FOR A ...VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve

main graph from the Solver sheet. Here the Solver line describes the data only at times greater

than 400 to 500s. The Solver 4.2 routine gave low values of conductivity and diffusivity, but

the interesting feature here is that the time that must elapse before the error between the 2 and

4 constant expressions falls to below 1% is 780s, as can be seen in figure 5 the theoretical

0.01 curve. Therefore, the conclusion to be drawn is that the equations 4 and 5 cannot be

applied to this data set until the heating time exceeds 800s.

Applying the regression analysis to the Voltra data over the time interval 850 to 1500 s,

results in a thermal conductivity of 0.01002 W/m2K (+0.2%), and diffusivity 0.973x10-7m2/s

(-2.7%). These errors are calculated in terms of the known true values for conductivity and

diffusivity that were initially inputted into the Voltra package. With the Solver 2.2 routine,

(Solver 2.2 has the two constants A and B of equation 1 and the two unknowns conductivity λ

and diffusivity α with the probe to sample conductance H set to a very high number), and the

data set in the time window 850 to 1500 s, the resulting conductivity is 0.01002W/m2K,

(+0.2%), diffusivity 0.975x10-7 m2/s (-2.5%), again errors in terms of true values.

Finally, moving the Solver 2.2 time window to longer times, namely 1300 to 1500s, the

resulting conductivity is 0.01008 W/m2K, (+0.8%), diffusivity 1.01x10-7 m2/s (1%), again

errors in terms of true value. When the regression analysis was applied to the data set in the

time window 1300 to 1500s, the resulting conductivity was found to be 0.01007 W/m2K,

(+0.7%), and diffusivity 1.006x10-7 m2/s (0.6%). This represents close agreement between

model, theory and the Voltra simulation.

18

Page 19: VALIDATION OF DATA ANALYSIS ROUTINES FOR A ...VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve

0

20

40

60

80

100

120

140

160

0 1 2 3 4 5 6 7 8Natural logarithm of elasped heating time

Ris

e in

tem

pera

ture

/C

Figure 3: Graph of rise in probe temperature versus natural logarithm of elapsed heating

time for the Voltra simulation on a theoretical material with conductivity 0.01 W/mK, density

1000 kg/m3, and specific heat capacity 100 J/kgK. Temperature measured at 1mm from line

heat source.

0

20

40

60

80

100

120

1 10 100 1000Elapsed heating time /s

Ris

e in

tem

pera

ture

/C

experimental temp /C

theoretical temp /C

Figure 4: The Solver 4.2 predicted or theoretical temperature rise plotted with the Voltra

simulation results, here denoted as experimental temp /C, both as functions of the elapsed

heating time in seconds.

19

Page 20: VALIDATION OF DATA ANALYSIS ROUTINES FOR A ...VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve

0

1

2

3

4

5

0 200 400 600 800 1000

time /s

E%,

(or t

he %

erro

r 2 o

r 4 c

onst

ants

)

Theoretical 1.5SandFirTheoretical 0.01

Figure 5: Graph of E%, or the %error 2 or 4 constants plotted as a function of time for the

theoretical materials with conductivities 1.5 and 0.01 W/mK, and for the sand and fir

simulations. A 1% error or less is only possible ahter heating times of 70 s for Theoretical

material 1.5, 260 s for sand, 420 s for fir and 780 s for the Theoretical 0.01.

The graph shown in Figure 5 where the input volumetric heat capacity is plotted as a function

of the time te, has an impact on the practical application of this probe technique to real

materials, both in the field and in the laboratory. Given that the results for oak and cellulose

do not follow the trend, as seen in Figure 5 there is a clear curve showing that as the

volumetric heat capacity of materials decreases the regression analysis time interval based

upon the te value increases to longer times. The values for oak may be due to the wood being

wet, or green, and the value for cellulose confused due to possible heat transfer by radiation

and convection within the sample.

20

Page 21: VALIDATION OF DATA ANALYSIS ROUTINES FOR A ...VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve

Other materials, from as yet unpublished work on real samples in the laboratory, show a

similar pattern, with agar or stabilized water having a volumetric heat capacity of 4.2

MJ/m3K and corresponding te of 9 seconds, for cob (earth walling in the West Country, UK)

1.2 MJ/m3K, 65s, and Celcon concrete block 0.63 MJ/m3K, 260s. These three values of te

were calculated with a finite probe conductance H of 650 W/m2K. The practical problem

arises due to axial conduction along the probe and therefore measurements need to be made

quickly and as near to the start as possible. For low volumetric heat capacity materials the

assumption that long times have been reached to satisfy the Blackwell equations may not be

possible without errors in the probe temperature rises caused by axial heat losses.

0

0.5

1

1.5

2

2.5

0 200 400 600 800 1000

Time te /s for E% = 1

Vol

umet

ric h

eat c

apac

ity /M

Jm-3

K-1

oak

cellulose

Figure 5: Graph of sample volumetric heat capacity against the E% = 1% times te.

21

Page 22: VALIDATION OF DATA ANALYSIS ROUTINES FOR A ...VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve

CONCLUSIONS AND REMARKS

This article describes the use of transient thermal simulation to validate analysis routines used

to process measurements conducted with an experimental thermal probe apparatus. The

following conclusions have been drawn from the work described:

1. Using the transient heat transfer program Voltra, a line source in an (almost) infinite

material sample has been modeled. The simulation model has been used to generate

datasets which have been analyzed for λ and α by means of the same analysis routines

(Solver 4.2, Solver 2.3) that are currently being used to process experimental data from

an actual thermal probe apparatus.

2. The Voltra model, the assumptions and the theory provided by Blackwell (1954) appear to

be satisfactorily describing the practical arrangements. Discrepancies between input data

inserted into the Voltra model and material properties obtained through application of the

Solver routines are in the order of 1%, which is in line with the fact that the Voltra model

has been set to report temperatures with two decimal places only.

3. The importance of selecting the appropriate power for the experimental work is

underlined, since long times also require measurable temperature rises, that is temperature

rises that are clearly above the experimental scatter.

4. Applying the regression analysis to data sets at inappropriate time windows, that is short

times, often leads to values for the thermal constants that appear of suitable magnitude,

but closer and more careful examination of the data can lead to more accurate values for

these thermal constants.

5. The Voltra study has validated the analysis routines as proposed by Goodhew and

Griffiths (2004) for a simplified model, that is a model with very large probe to sample

conductance and zero probe thermal capacity:

22

Page 23: VALIDATION OF DATA ANALYSIS ROUTINES FOR A ...VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve

• The Solver 4.3 routine has been demonstrated to provide crucial information needed to

select a correct time interval for the application of regression analysis to the measured

data, by allowing the error between the Blackwell 2 and 4 constant expressions to be

explored.

• The Solver 2.3 routine applied to the correct time window leads to accurate values of

both conductivity and diffusivity, which have been demonstrated to have an error of

less than 1%.

FUTURE WORK

Further work will be carried out to advance the understanding of the behaviour of an actual

thermal probe apparatus. This will involve modeling of a probes with finite dimensions,

specific probe materials, and various internal probe configurations, and inclusion of boundary

effects for both probe and measurement sample. Practical issues such as the timing of

measurements, the use and type of heat-sink materials used to allow good contact between the

body of the probe, increasing the probe conductance (H), and the sample materials can be

investigated. It is anticipated that through the use of dynamic simulation modeling, the time

span needed to further develop the thermal probe technique and it’s application to in-situ

measurements of the thermal properties of building materials will be considerably shortened.

REFERENCES

ASHRAE. 2005. ASHRAE Handbook of Fundamentals, SI Edition. Atlanta: American Society of Heating, Refrigerating, and Air-Conditioning Engineers. Banaszkiewicz M, Seiferlin K, Spohn T, Kargl G, Kömle N (1997). A new method for the determination of thermal conductivity and thermal diffusivity from linear heat source measurements, Rev. Sci. Instruments, 68 (11), 4184-4190

23

Page 24: VALIDATION OF DATA ANALYSIS ROUTINES FOR A ...VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve

Batty WJ, O'Callaghan PW, Probert SD (1984a). Assessment of the thermal-probe technique for rapid, accurate measurements of effective thermal conductivities, Applied Energy, 16, 83-113 Batty WJ, Probert SD, Ball M, O'Callaghan PW (1984b.) Use of the thermal probe technique for the measurement of the apparent thermal conductivities of moist materials, Applied Energy, 18, 301-317 Blackwell JH, Misener AD (1951). Approximate Solution of a Transient Heat Flow Problem, Proc. Phys. Soc. A 64, 1132-1133 Blackwell JH (1954). A transient-flow method for determination of thermal constants of insulating materials in bulk. Part 1-Theory, Journal of Applied Physics, 25 (2), 137-144 Buettner K (1955). Evaluation of soil heat conductivity with cylindrical test bodies, Transactions, American Geophysical Union, 36 (5), 831-837 Campbell GS, Calissendorff C, Williams JH (1991). Probe for measuring soil specific heat using a heat-pulse method, Soil Sci. Soc. Am. J. 55, 291-293 Carslaw HS, Jaeger JC (1947). Conduction of heat in solids, University Press, Oxford. Davis WR, Downs A (1980). The hot wire test - a critical review and comparison with the BS 1902 panel test, Transactions British Ceramic Society, 79, 44-52 Drury MJ (1988. A simple needle-probe method for measuring thermal diffusivity of unconsolidated materials, Geothermics, 17, (5-6), 757-763 Goodhew SM (2000). The thermal properties of cob buildings of Devon, PhD Thesis. University of Plymouth (unpublished) Goodhew SM, Griffiths R (2003). Handbook giving practical details for thermal probe studies with iterative methods for data analysis using Solver routines, University of Plymouth, Joint Schools of the Built Environment, internal report, unpublished Goodhew SM, Griffiths R (2004). Analysis of thermal probe measurements using an iterative method to give sample conductivity and diffusivity data, Applied Energy, 77, 205-224 Goodhew SM, Griffiths R (2005). Sustainable walls to meet the building regulations, Energy and Buildings, 37, 451-459 de Groot JJ, Kestin J, Sookiazian H (1974). Instrument to measure the thermal conductivity of gases, Physica, 75, 454-482 Van der Held EFM; Van Drunen FG (1949). A method of measuring the thermal conductivity of liquids. Physica A, 15 (10), 865-881 Hooper FC, Lepper FR (1950). Transient heat flow apparatus for the determination of thermal conductivities, Transactions American Society of Heating and Ventilation Engineers 56, 309-324

24

Page 25: VALIDATION OF DATA ANALYSIS ROUTINES FOR A ...VALIDATION OF DATA ANALYSIS ROUTINES FOR A THERMAL PROBE APPARATUS USING NUMERICAL DATA SETS Pieter de Wilde*, Richard Griffiths and Steve

Jones BW (1988). Thermal conductivity probe: development of method and application to a coarse granular medium, J. Phys. E: Sci. Instrum. 21, 832-839 Lasdon ,LS Waren ,AD Jain ,A Ratner, M (1978) Design and Testing of a Generalized Reduced Gradient Code for Nonlinear Programming, ACM Transactions on Mathematical Software (TOMS), 4 (1), 34-50. Niven C (1905). On a Method of Finding the Conductivity for Heat, Proceedings of the Royal Society of London. Series A, Containing Papers of a Mathematical and Physical Character, 76, (507) 34-48 Niovichenok LN, Pikus Yu M (1975). Joint determination of thermal properties by a probe method, Journal of Engineering Physics and Thermophysics 29, .3,1116-1118 Pilkington, B., P. de Wilde, P., S. Goodhew, R. Griffiths, 2006. Development of a Probe for Measuring In-situ the Thermal Properties of Building Materials. Proceedings of PLEA'06, 23rd International Conference, Geneva, Switzerland, September 6-8 2006, 665-670 Pilkington, B., R. Griffiths, S. Goodhew, P. de Wilde, 2007. Thermal probe technology for buildings: the transition from laboratory to field measurements. Article under review for the ASCE Journal of Architectural Engineering Pilkington, B., 2008. In-Situ Measurements of Building Materials Using a Thermal Probe. PhD Thesis, University of Plymouth, to be submitted in February 2008 (unpublished). PHYSIBEL. 2005. Voltra and Sectra Manual, version 5.0w. Maldegem: Physibel Software.

Schleiermacher A (1888). On the thermal conduction of gas, Wiedeman Ann. Phys. 34, 623-646 Seiferlin K, Komle NI, Kargl G, Spohn T (1996). Line heat-source measurements of the thermal conductivity of porous H2O ice, CO2 ice and mineral powders under space conditions, Planet. Space Sci., 44 (7), 691-704 Stalhane B and Pyk S (1931). New method for measuring the thermal conductivity coefficients, Teknisk Tidskrift. 51. 389-96 Vos BH (1955). Measurements of thermal conductivity by a non-steady-state method, Appl. Sci. Res. Section A, 5, 425-438 de Vries DA, Peck AJ (1958). On the cylindrical probe method of measuring thermal conductivity with special reference to soils. 1. Extension of theory and discussion of probe characteristics, Australian Journal of Physics, 11, 255-271

25