Hazardous Materials Business Response and Contingency Plan
County of Yuba Underground Storage Tank Written Monitoring/Response PlanCertified Unified Program Agency
915 8th Street, Suite 123, Marysville, CA 95901
(530) 749-5450
FACILITY IDENTIFICATION/OPERATIONS OVERVIEW
Facility Name Facility ID# Date
Underground Storage Tank Written Monitoring / Response Plan
Applicability of Plan
Indicate tanks covered FORMCHECKBOX All tanks on-site.
by this monitoring plan. FORMCHECKBOX All Fuel Tanks
FORMCHECKBOX All Waste Oil Tanks
FORMCHECKBOX The following tanks only: Describe
(NOTE: More than one plan is
needed if tanks are
monitored differently.)
Designated Operator for Facility:Name/address: Phone:
Tank Leak Detection Monitoring
Monitoring MethodSpecify Manufacturer /Company NameSpecify Model Number and TypeFrequency of Monitoring
Single-contained Tanks FORMCHECKBOX Continuous in-tank leak detection with programmed leak threshold of 0.2gph.Leak results recorded:
FORMCHECKBOX Daily
FORMCHECKBOX Monthly
FORMCHECKBOX Automatic Tank Gauging with programmed leak threshold of 0.2gph.Leak test performed
FORMCHECKBOX Daily
FORMCHECKBOX Monthly
FORMCHECKBOX Manual Tank Gauging plus annual tank testing.Tank Tester: Gauging Period
FORMCHECKBOX 36 hours
FORMCHECKBOX 60 hours
FORMCHECKBOX Statistical Inventory Reconciliation plus Biennial tank testingSIR Company: Tank Tester:
FORMCHECKBOX Enhanced Leak detection
FORMCHECKBOX Other (Specify)
Double-contained Tanks FORMCHECKBOX Liquid Sensor in Annular Space with audible and visual alarm.Continuous
FORMCHECKBOX Discriminating sensor in Annular space with audible and visual alarmContinuous
FORMCHECKBOX Liquid float sensor in annular space with audible and visual alarm.Continuous
FORMCHECKBOX Vacuum on Annular Space.
FORMCHECKBOX Other (Specify)
Under-Dispenser Containment (UDC)
Dispenser Containment FORMCHECKBOX None- NO dispensers in system FORMCHECKBOX Dispenser Containment
FORMCHECKBOX SW UDC
FORMCHECKBOX DW UDC FORMCHECKBOX Float trips shear valve.
FORMCHECKBOX Sensor connected to audio-visual alarm. FORMCHECKBOX DW UDC monitored by Vacuum sensor
FORMCHECKBOX DW UDC monitored by Liquid sensor.
Facility Name Facility ID# Date
Underground Storage Tank Written Monitoring / Response Plan-(Continued)
Positive Turbine Shutdown
FORMCHECKBOX None FORMCHECKBOX At piping sump due to leak FORMCHECKBOX At dispenser due to leak FORMCHECKBOX Due to System Disconnect/ Failure
Shut down FORMCHECKBOX at piping sump FORMCHECKBOX at dispenser FORMCHECKBOX When sensed in primary piping
Piping Leak Detection
Monitoring MethodSpecify Manufacturer of Equipment /Company NameSpecify Model Number /Type of Sensors/EquipmentFrequency of Monitoring
Pressurized
SW Piping FORMCHECKBOX Electronic line leak detectors with programmed leak threshold of
FORMCHECKBOX 0.1 gph FORMCHECKBOX 0.2 gph FORMCHECKBOX 3 gph.
with positive turbine shutdownEvery pumping cycle
FORMCHECKBOX Piping test .2gph ORMonthly
FORMCHECKBOX Piping test .1ghpAnnual
Suction
SW Piping FORMCHECKBOX Daily Monitoring and Triennial Piping TestDaily
Triennial
FORMCHECKBOX Exempt from Monitoring
Gravity
SW Piping FORMCHECKBOX Piping Test .1gphBiennial
DW Pressurized
Monitoring FORMCHECKBOX Option 1: Continuous monitoring for UDC.
Shuts down the pump OR
Stops the flow of the product at the dispenser when a leak is detected in the UDC. ANDContinuous monitoring for the pressurized piping located outside the UDC that is fail safe and shuts down the pump when a leak is detected .ANDA line leak detector (mechanical or electronic) that detects a 3 g/h release from the primary containment.Dispenser: Tank Sump: Continuous
FORMCHECKBOX Option 2: Continuous monitoring for both pressurized piping and UDC that activates an audible and visual alarm OR Stops the flow of the product at the dispenser when a leak is detected. AND
A line leak detector (mechanical or electronic) that detects a 3 gph release from the primary containment. AND
An annual piping test @ 0.1gph.Dispenser: Tank Sump:
Continuous
Annual
FORMCHECKBOX Emergency Generator: Continuous monitoring for both pressurized piping and UDC that activates an audible and visual alarm OR stops the flow of product at the dispenser when a leak is detected.
AND
Monitoring system is checked at least daily, by either remote access or on-site visual inspections with documentation logs
AND.
Annual piping test 0.1gphDispenser: Tank Sump: Continuous
Annual
Facility Name Facility ID# Date
Underground Storage Tank Written Monitoring / Response Plan-(Continued)
DW Suction FORMCHECKBOX Sloped back to collection sump and monitored with audible and visual alarm.Continuous
Vent Piping FORMCHECKBOX DW FORMCHECKBOX SW Sump Containment FORMCHECKBOX Vacuum Sensor FORMCHECKBOX Liquid SensorContinuous
Overfill Prevention
Check type of system. FORMCHECKBOX System alerts transfer operator when tank is 90% full by restricting flow into tank or triggering an audible and visual alarm. Does not allow for manual override.
FORMCHECKBOX External alarm OR
FORMCHECKBOX Flow Restrictor FORMCHECKBOX System provides positive shut-off of flow to tank when tank is filled to no more than 95% of capacity. Does not allow for manual override.
Fill tube valve/flapper FORMCHECKBOX System restricts delivery of flow to tank at least 30 minutes before tank overfill. Does not allow for tank override. Flow restriction occurs when tank is 95% of capacity, and activates audible alarm five minutes before tank overfills.
Ball float valve and external alarm. FORMCHECKBOX System provides positive shut-off of flow to tank so that none of the fittings located on top of the tank are exposed to product due to overfilling. Does not allow for manual override.
Fill tube valve /flapper.
Cathodic Protection
Type of systemLocationServicing CompanyDescribe Maintenance
FORMCHECKBOX None
FORMCHECKBOX Impressed Current
FORMCHECKBOX Sacrificial Anode
FORMCHECKBOX Galvanic System FORMCHECKBOX Tested triennially
FORMCHECKBOX Impressed current reading every 60 days.
FORMCHECKBOX Other
Other Monitoring
FORMCHECKBOX Visual Inspection
FORMCHECKBOX Daily FORMCHECKBOX Weekly FORMCHECKBOX Monthly of FORMCHECKBOX Fills FORMCHECKBOX Sumps
FORMCHECKBOX Dispenser Pans FORMCHECKBOX Other-Specify
Responsibility for Monitoring and Maintenance
Name/TitleDuties
1. FORMCHECKBOX routine monitoring
FORMCHECKBOX equipment inspections & record keeping FORMCHECKBOX scheduling annual equipment certification / testing
FORMCHECKBOX maintenance of monitoring records FORMCHECKBOX problem & alarm / leak reporting
FORMCHECKBOX Other: Specify
2. FORMCHECKBOX routine monitoring
FORMCHECKBOX equipment inspections & record keeping FORMCHECKBOX scheduling annual equipment certification / testing
FORMCHECKBOX maintenance of monitoring records FORMCHECKBOX problem & alarm / leak reporting
FORMCHECKBOX Other: Specify
3. FORMCHECKBOX routine monitoring
FORMCHECKBOX equipment inspections & record keeping FORMCHECKBOX scheduling annual equipment certification / testing
FORMCHECKBOX maintenance of monitoring records FORMCHECKBOX problem & alarm / leak reporting
FORMCHECKBOX Other: Specify
Facility Name Facility ID# Date
Underground Storage Tank Written Monitoring / Response Plan-(Continued)
Reporting Format/Monitoring Reports / Record Keeping
Type of Report/Record KeptUsed for Where kept Provided to CUPA
FORMCHECKBOX Daily Stick Readingsat inspection
FORMCHECKBOX Daily pump readingsat inspection
FORMCHECKBOX Alarm Log (Required)at inspection
FORMCHECKBOX Repair and Maintenance Log (Required)at inspection
FORMCHECKBOX Spill Log (Required)at inspection
FORMCHECKBOX Unauthorized Leak Report24 hours initial notification; 5 days for written report.
FORMCHECKBOX Visual inspection records at inspection
FORMCHECKBOX Owner/Operator Agreement (Required, if applicable)Provide to CUPA
FORMCHECKBOX Third-party Verification of monitoring equipment (Required-Attach to this plan.)Provide to CUPA
FORMCHECKBOX Monitoring Tapes / Printoutsat inspection
FORMCHECKBOX Annual Monitoring Summary Reports (SIR, ATG, etc.)annually within 30 days of end of report period
FORMCHECKBOX Certification reports within 30 days of testing
FORMCHECKBOX Other: Specify
Certification/ Maintenance Schedule
ItemFreq. Required/
Anniversary DateService Provider Name AddressPhone
FORMCHECKBOX Leak DetectorsAnnual/
FORMCHECKBOX Electronic Equipment/ATGAnnual/
FORMCHECKBOX Sensor ProbesAnnual/
FORMCHECKBOX Spill ContainmentAnnual/
FORMCHECKBOX Corrosion Protection SystemEvery three year/
FORMCHECKBOX Secondary Containment systemEvery three years/
FORMCHECKBOX Tank Lining of Upgraded TankEvery 5 Years/
FORMCHECKBOX Compliance InspectionAnnualto coincide with Monitor CertificationsEnvironmental Health Division: CUPA915 8th Street, Suite 123 Marysville, CA(530) 749-5450
Note: All certification reports must be submitted within 30 days to the CUPA.
Facility Name Facility ID# Date
Underground Storage Tank Written Monitoring / Response Plan-(Continued)
Site Map: Provide a site map with the following items:
Location of tanks
Location of all monitoring equipment: leak detectors, sensors, monitoring consoles.
Show ID numbers for sensors that correspond to the ID numbers on tape printout (if applicable).
Location of piping sumps and dispensers, emergency shut-off valves, and location of spill containers.
Response to Unauthorized Release
Methods used to confirm unauthorized release. FORMCHECKBOX Review monitoring / inventory records.
FORMCHECKBOX Conduct tank / piping test.
FORMCHECKBOX Check equipment used in monitoring and ensure proper operation. FORMCHECKBOX Have tank system inspected. FORMCHECKBOX Other
Initial abatement activities/ removal of hazardous materials from secondary containment. FORMCHECKBOX Remove contents of tank/ containment.
FORMCHECKBOX Determine if release to environment has occurred.
FORMCHECKBOX Contact service provider to provide assistance. FORMCHECKBOX Other
Other: Describe
Training
Describe training program for UST operators/owners.
FORMCHECKBOX State Certified owner/operator training program REQUIRED
FORMCHECKBOX Training conducted by UST service provider/manufacturers representatives.
FORMCHECKBOX Training provided by on-the-job-training.
FORMCHECKBOX Training provided by
FORMCHECKBOX Training plan is attached.Certify by signing that this has been completed.Date completed.
FORMCHECKBOX Facility personnel with UST monitoring responsibilities have been familiarized with all aspects of monitoring the tank system at this facility and are familiar with the laws and regulations.
FORMCHECKBOX Personnel responsible for maintaining UST monitoring records (i.e. logs, test reports, etc. 0 have been instructed that most records must be maintained on site for a minimum of three years, and some for 61/2 years.
FORMCHECKBOX Personnel responsible for performing visual or other inspections are trained to document inspections in a thorough manner. They are trained to distinguish proper equipment function, in proper procedures for reporting alarms, leaks equipment failure, and other problems.
Certification
I have reviewed this Underground Storage Tank Monitoring and Response Plan and have determined that it accurately describes monitoring of the designated underground storage tanks at this facility.
Owner/Operator Signature: Date:
Page 4
UST Monitoring Plan 10/04