user guide controlit - abb• three relay outputs: two for booster pump or divert valve control, one...

36
Control IT Booster Pump Controller C320 User Guide IM/C320_5

Upload: others

Post on 29-Jan-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

  • ControlIT

    Booster Pump Controller

    C320

    User GuideIM/C320_5

  • ABB

    EN ISO 9001:2000

    Cert. No. Q5907

    The CompanyWe are an established world force in the design and manufacture ofinstrumentation for industrial process control, flow measurement, gas andliquid analysis and environmental applications.

    As a part of ABB, a world leader in process automation technology, we offercustomers application expertise, service and support worldwide.

    We are committed to teamwork, high quality manufacturing, advancedtechnology and unrivalled service and support.

    The quality, accuracy and performance of the Company’s products resultfrom over 100 years experience, combined with a continuous program ofinnovative design and development to incorporate the latest technology.

    The UKAS Calibration Laboratory No. 0255 is just one of the ten flowcalibration plants operated by the Company, and is indicative of ourdedication to quality and accuracy.

    EN 29001 (ISO 9001)

    Lenno, Italy – Cert. No. 9/90A

    REGISTER

    ED

    Health and SafetyTo ensure that our products are safe and without risk to health, the following points must be noted:

    1. The relevant sections of these instructions must be read carefully before proceeding.

    2. Warning labels on containers and packages must be observed.

    3. Installation, operation, maintenance and servicing must only be carried out by suitably trained personnel andin accordance with the information given.

    4. Normal safety precautions must be taken to avoid the possibility of an accident occurring when operating inconditions of high pressure and/or temperature.

    5. Chemicals must be stored away from heat, protected from temperature extremes and powders kept dry.Normal safe handling procedures must be used.

    6. When disposing of chemicals ensure that no two chemicals are mixed.

    Safety advice concerning the use of the equipment described in this manual or any relevant hazard data sheets(where applicable) may be obtained from the Company address on the back cover, together with servicing andspares information.

    Electrical SafetyThis instrument complies with the requirements of CEI/IEC 61010-1:2001-2 "Safety requirements for electricalequipment for measurement, control, and laboratory use". If the instrument is used in a manner NOT specified bythe Company, the protection provided by the instrument may be impaired.

    SymbolsOne or more of the following symbols may appear on the instrument labelling:

    Information in this manual is intended only to assist our customers in the efficient operation of our equipment. Useof this manual for any other purpose is specifically prohibited and its contents are not to be reproduced in full or partwithout prior approval of the Technical Communications Department.

    Warning – Refer to the manual for instructions

    Caution – Risk of electric shock

    Protective earth (ground) terminal

    Earth (ground) terminal

    Direct current supply only

    Alternating current supply only

    Both direct and alternating current supply

    The equipment is protectedthrough double insulation

  • 1

    The COMMANDER 320 Booster Pump Controller acts as a differential pressure switch for usein the regeneration section of a pasteurizer. If the difference between pasteurized milkpressure and raw milk pressure falls below a preset level, the controller shuts down the rawmilk booster pump or alternatively, channels the pasteurized milk into the divert flow.

    The COMMANDER 320 has the following features:

    • Two 4 to 20mA analog inputs.• A transmitter power supply capable of powering the raw and pasteurized 2-wire

    pressure transmitters.• A digital display of the raw and pasteurized product pressures.• A bargraph display of the difference between the raw and pasteurized pressures.• A deviation alarm to detect when the difference between the raw and pasteurized

    pressures falls below a preset minimum.• A start-up alarm which allows the booster pump to remain off until the normal system

    operating back pressure is achieved.• A manual override facility which allows the booster pump to be turned off using a digital input.• Selectable pressure differential retransmission output.• Three relay outputs: two for booster pump or divert valve control, one to operate a

    warning light or horn.

    This manual is divided into 4 sections and contains all the information necessary to install,configure and operate the instrument.

    GETTING STARTED

    Symbol Identification and Contents of Sections

    Displays and Function Keys• Displays and function keys• LED Indication• Error Messages

    Operating Level• Operating Page• Operating Page Messages• Alarm Acknowledge Page• Security Access

    Configuration Level• Set Up Alarms• Set Up Inputs• Set Up Display• Scale Adjustment• Security Code Set Up• Commissioning

    Installation• Siting• Mounting• Electrical connections

  • 2

    Section Page

    CONTENTS

    1 DISPLAYS AND CONTROLS............................................................................. 31.1 Introduction .................................................................................................................31.2 Use of Controls ...........................................................................................................31.3 Displays and LED Indicators .......................................................................................4

    1.3.1 LED Indications, Relay and Alarm States ........................................................41.3.2 Deviation Bargraph ..........................................................................................5

    1.4 Instrument Power-up ...................................................................................................52 OPERATING LEVEL........................................................................................... 6

    2.1 Operating Page ...........................................................................................................62.2 Operating Page Messages .........................................................................................62.3 Alarm Acknowledge Page ...........................................................................................62.4 Security Access ..........................................................................................................7

    2.4.1 Security Code Page .........................................................................................83 CONFIGURATION LEVEL.................................................................................. 9

    3.1 Preparation for Changes to the Parameters ...............................................................93.2 Set Up Alarms Page .................................................................................................103.3 Set Up Inputs ............................................................................................................123.4 Set Up Display Page .................................................................................................143.5 Retransmission Output Page ....................................................................................153.6 Scale Adjustment Page .............................................................................................163.7 Access Page .............................................................................................................183.8 Commissioning .........................................................................................................19

    4 INSTALLATION ................................................................................................ 204.1 Checking the Code Number ......................................................................................204.2 Siting .........................................................................................................................214.3 Mounting ...................................................................................................................224.4 Access to Terminals ..................................................................................................234.5 Setting the Input Selector Links ................................................................................244.6 Setting the Isolated Output Link ................................................................................244.7 Cable Glands and Conduit Fixings ...........................................................................25

    4.7.1 Cable Glands (IEC – 20mm) ..........................................................................254.7.2 Conduit Adaptors (N. American – 0.5in) ........................................................254.7.3 Cable Glands (N. American – 0.5in) .............................................................. 26

    4.8 Connections Summary ..............................................................................................274.9 Input Connections .....................................................................................................29

    4.9.1 Current Input ..................................................................................................294.9.2 2-wire Transmitter ..........................................................................................29

    4.10 Output Connections ................................................................................................294.11 Logic Input Connection ...........................................................................................294.12 Relay Connections ..................................................................................................304.13 Power Supply Selection and AC Connections ........................................................31

    SPECIFICATION .................................................................................................... 32

  • 3

    1.1 Introduction – Fig. 1.1The Commander 320 front panel display, function keys and LED indicators are shown inFig. 1.1

    Note. Continued pressure on the and switches causes the

    rate of change of the displayedvalue to increase. To make smalladjustments operate the switchesmomentarily.

    Frame 1Frame 2Frame 3Frame 4

    Page 1

    Frame 1Frame 2Frame 3

    Page 2

    Frame 1

    Frame 2Frame 3

    Page X

    Frame 4

    Advance tonext Frame

    AdjustParameter Value

    Parameter XYZ

    Select

    Used to acknowledge alarm A1 and de-energise relay 3

    Fig. 1.2 Advancing to Next Page

    Fig. 1.3 Moving between Frames

    Fig. 1.4 Adjusting a Parameter Value

    Fig. 1.5 Selecting a Parameter Choice

    Fig. 1.6 Alarm Acknowledge Switch

    1.2 Use of Controls – Figs. 1.2 to 1.6

    1 DISPLAYS AND CONTROLS

    Fig. 1.1 Front Panel Display, Function Keys and LED Indicators

    'Enter' Switch LED

    Deviation BarGraph Display

    LED IndicatorsControls – Refer toFigs. 1.2 to 1.6

    Displays

    RAW

    PAS

    A1 A2 BP2BP1

    'Data Entry' Switch(use to enter settingsand values in frames)

  • 4

    1.3 Displays and LED IndicatorsThe displays, LED indicators and operation/programming controls are located on the faceplateon the front of the instrument. The displays comprise 2 rows of 6 characters.

    …1 DISPLAYS AND CONTROLS

    Table 1.2 LED Indications and Alarm States

    Display ConditionAlarm/Relay State

    A1 Active and ackd.

    A1 Active and unackd.

    A1 Inactive

    A2 Active

    A2 Inactive

    Relay 1 De-energised

    Relay 1 Energised

    Relay 2 De-energised

    Relay 2 Energised

    Relay 3 Energised

    Relay 3 De-energised

    Pasteurized I/P pressure: < Raw I/P pressure + divert trip level

    Pasteurized I/P pressure: ≥ Raw I/P pressure + divert trip level

    Displayed on power up.Active until Pasteurized I/P pressure ≥ Start up trip level then remains inactive untilpower is switched off and on.

    Either A1 or A2 active

    A1 and A2 inactive

    A1 active

    A1 inactive.

    A1 active and unacknowledged.

    A1 acknowledged.

    On

    Flashing

    Off

    On

    Off

    Off

    On

    Off

    On

    On

    Off

    LED

    A1

    A2

    BP1

    BP2

    1.3.1 LED Indications, Relay and Alarm StatesLED indications, relay and alarm states are shown in Table 1.2. For electrical connections –see section 4.12.

    AbC or cdEFGH or hIJK

    LMN or nO or oPQrStUVY

    ABCDEFGHIJK

    LMNOPQRSTUVY

    Table 1.1 Character Set

  • 5

    1 DISPLAYS AND CONTROLS…

    1.3.2 Deviation Bargraph – Fig. 1.7The deviation bargraph displays:a) The difference between the raw pressure and pasteurized pressure inputs.b) The deviation alarm trip value

    1.4 Instrument Power-up – Fig. 1.8

    Caution. Ensure all connections, including the earth stud, are made correctly.

    a) Check that the input sensors are installed correctly.b) Switch on the supply to the instrument, any power-operated control circuits and the input

    signals.c) The start-up sequence shown in Fig. 1.8 is displayed when the supply is first switched on.

    Fig. 1.7 Deviation Bargraph

    Deviation alarm trip value

    Difference between raw and pasteurized inputpressures is less than the alarm trip value

    Difference between raw and pasteurized inputpressures is greater than the alarm trip value

    Note. Acknowledging error clears the error but does not rectify the fault, check theconfiguration.

    Instrument Test identifies the instrument type, C320 – see Table 4.1

    Flashing

    between

    Normal Display

    C320tESt

    A1 BP2A2 BP1

    RAW

    PAS

    A1 A2

    100.3

    200.5BP2BP1

    RAW

    PAS

    A1 A2

    CONFIGCHECK

    BP2BP1

    RAW

    PAS

    Conf igura t ion Check

    indicates configuration error,

    acknowledged by pressing

    the switch.

    Fig. 1.8 Instrument Displays at Power-up

  • 6

    Operating Page

    Pressure of raw product.Pressure of pasteurized product.

    If the difference between the two values falls below therequired level, i.e. Alarm 1 becomes Active, both values flashON and OFF.

    2 OPERATING LEVEL

    2.1 Operating Page

    Information. The instrument has a dedicated Operating page. This page is used for generalmonitoring of the process measurements and is not affected by the security system whichinhibits access to the alarm set up and programming pages – see section 3

    5.0010.00

    2.2 Operating Page Messages

    Table 2.1 Input Error Messages Displayed in the Operating Page

    Reason

    Failed Input – raw pressure input failure.

    Failed Input – pasturized pressure input failure.

    Message

    F-INPt

    F-INPt

    Page Header – Acknowledge Alarms

    Upper DisplayShows the alarm identity and type when an alarm condition ispresent.

    dEV-AL – deviation alarm A1 SU-AL – start up alarm A2

    Lower DisplayShows the trip level of the alarm identified in the upper display.When the alarm is acknowledged ( pressed ), ACKNGd isdisplayed.

    Note. If alarm A2 is active, SU-ALis displayed, but the alarmcannot be acknowledged.

    Return to top of page.

    2.3 Alarm Acknowledge Page

    ACKNLGALArMS

    dEV-AL100.5

    ACKNGddEV-AL

  • 7

    2 OPERATING LEVEL…

    2.4 Security Access – Figs 2.1 and 2.2A security system is used to prevent tampering with the program parameters by utilizing asecurity input together with an Alarm password and a Configuration password – see Figs. 2.1and 2.2. Two levels of security are provided:

    a) Security input secure – Alarm and configuration settings cannot be accessed.The security input may be protected by a tamper-proof seal – see Fig.2.3

    b) Security input insecure – Alarm and configuration settings can be accessed by use ofthe correct password.

    OperatingPage

    (Section 2.1)

    Alarm AcknowledgePage

    (Section 2.3)

    Security CodePage

    (Section 2.4)

    Security LinkINSECURE +configurationsecurity code

    Security Link SECURE

    Set Up AlarmsPage

    (Section 3.2)

    Configuration Level –see Section 3

    SEtUPALArMS

    SECOdEPAGE

    100.3110.5

    ACKNLGALArMS

    Security LinkINSECURE +alarm orconfigurationsecurity code

    Fig. 2.1 Security Access

    Fig. 2.2 Security Settings

    No security override onterminals 31 and 32

    323130

    Secure

    Security override onterminals 31 and 32

    323130

    Insecure

    Fig. 2.3 Tamper-proof Seal

  • 8

    2.4.1 Security Code Page

    Page Header – Security Code Page

    Set the correct Alarm or Configuration password using the and switches and press the switch to enter the

    code.

    The passwords are programmed in the Access Page – seeSection 3.7.

    Software versionThe Upper display indicates the EPROM series.

    The lower display indicates the version number.

    Return to top of page

    .

    …2 OPERATING LEVEL

    SECOdE

    VEr 22001

    0

  • 9

    3 CONFIGURATION LEVEL

    OperatingPage

    Section 2.1

    SEtUPALArMS

    COMMIMSSION

    SECOdEPAGE

    100.3110.5

    ACKNLGALArMS

    SEtUPINPUt

    dISPLYPAGE

    SCALEAdJUSt

    ACCESSPAGE

    Alarm AcknowledgePage

    Section 2.3

    Security codePage

    Section 2.4

    Set Up AlarmsPage

    Section 3.2

    Set Up InputsPage

    Section 3.3

    DisplayPage

    Section 3.4

    Scale AdjustPage

    Section 3.6

    AccessPage

    Section 3.7

    CommissioningPage

    Section 3.8

    Alarm Identities■

    Trip Levels

    Hysteresis

    ■ Broken SensorProtection Drive

    Fault DetectionLevel % PV I/P

    ■ ProgrammableFilter

    Mains Filter■

    Display High/LowLimits

    Decimal Point

    Bar Graph %Increment Per Bar

    Scale Adjust rawInput RangeHigh/Low Limits

    Scale AdjustPasteurized RangeHigh/Low Limits

    Alarm Password■

    ■ ConfigurationPassword

    Operating Level

    ■ IsolatedRetransmission

    rEtrANOUtPUt

    RetransmissionOutput PageSection 3.5

    Isolated and non-isolated outputsources

    Pressuredifferenceretransmissionrange

    Fig. 3.1 Configuration Level Overview

    3.1 Preparation for Changes to the ParametersEnsure that the external alarm/control circuits are isolated if inadvertent operation duringprogramming is undesirable.

    Any change to the operating parameters are implemented using the or switches – seeSection 2.

    Note. The instrument responds instantly to parameter changes which are saved when the switch is pressed.

  • 10

    …3 CONFIGURATION LEVEL

    3.2 Set Up Alarms Page

    Information.• Two alarms – identified A1 and A2 .• Adjustable hysteresis value to prevent oscillation of alarm state.

    Pasteurized pressureinput

    Divert HysteresisValue

    Alarm On

    Alarm Off

    Raw pressureinput

    Divert triplevel

    +

    Pasteurizedpressure input

    Alarm On

    Alarm Off

    Start Uptrip level

    Fig. 3.2 Deviation Alarm A1

    Information. From power up the alarm remains ACTIVE until the tripvalue is exceeded. The alarm then remains OFF until the controller ispowered down and up again.

    Fig. 3.3 Start Up Alarm A2

  • 11

    3 CONFIGURATION LEVEL…

    …3.2 Set Up Alarms Page

    Page Header – Set Up Alarms.

    Divert Trip LevelSet the trip level for alarm A1 in engineering units.

    Note.When alarm A1 is active, relays 1 and 2 are de-energised.Alarm A1 can be acknowledged by the operator.When A1 is active and unacknowledged relay 3 isenergised.When A1 is acknowledged relay 3 is de-energised.

    Divert Hysteresis LevelSet the hysteresis level for alarm A1 in engineering units.

    Start Up Trip LevelSet the trip level for alarm A2 in engineering units.

    Note.When alarm A2 is active, relay 1 is de-energised.Alarm A2 cannot be acknowledged by the operator.

    Return to top of page.

    SEtUPALArMS

    ––––dVtrIP

    ––––dVHYSt

    ––––SVtrIP

  • 12

    …3 CONFIGURATION LEVEL

    3.3 Set Up Inputs – Fig. 3.4

    Information.• All changes made apply to both the raw and pasteurized pressure inputs.• Both inputs are fixed, 4 to 20mA• Programmable fault levels and actions.• Digital filter reduces the effect of noise on inputs.

    Example – mA input, range 0 to 100 with 10% fault detection levels.

    Current

    110

    –10

    Input Type Display Range

    Fault

    Detection

    Level 10 %100

    0Fault

    Detection

    Level 10 %

    Display Range

    High

    Display Range

    Low

    ProgrammeFilter

    Value set to 0

    Value set low

    Value set high

    Fig. 3.4 Setting Up the Input

  • 13

    3 CONFIGURATION LEVEL…

    …3.3 Set Up Input Page

    Page Header – Set Up Process Variable Input.

    Broken Sensor Protection DriveIn the event of a fault being detected on the input, thedisplayed value is driven in the direction of the modeselected.

    Select the broken sensor drive required:NONE – No driveUP – Upscale drivedN – Downscale drive.

    Note. When a broken input sensor is detected, the unitswitches to Divert Mode and turns the booster pump OFF.

    Fault Detection Level Percentage,A fault level percentage can be set to detect a deviationabove or below the display limits, e.g. If set at 10.0%, thenif an input goes more than 10% above full scale value ormore than 10% below zero value, a fault is detected.

    On some ranges the input circuitry may saturate before thefault level set is reached. In this case an error is detected ata level below that which is set.

    Set the value required, between 0.0 and 100.0% in 0.1%increments.

    Programmable FilterThis filters the pressure inputs, i.e. if the input is stepped,it smooths the transition between steps and may also beused for some degree of cleaning of noisy inputs. The filtertime represents the time a step in the input takes to changethe displayed value from 10 to 90% of the step.

    Set value required, between 0 and 60 in 1 secondincrements.

    Mains FilterSet the frequency of the mains supply used (50 or 60Hz).

    Return to top of page.

    bSPd

    UPdN

    NONE

    SEtUPINPUt

    FdLP 10.0

    PrGFLt0

    FILtEr- -Hrt

  • 14

    …3 CONFIGURATION LEVEL

    3.4 Set Up Display Page

    Information.• Set up engineering ranges and units.• Programmable increments on deviation bargraph.• Adjust display brightness.

    Page header – Display Page.

    Display Full ScaleSet the display value which represents the maximumpressure input signal, between –9999 and +9999.

    Example – For an input range of 4 to 20mA representing apressure range of 0.0 to 20.0 psi,, set 200. The decimalpoint position is set at the next parameter.

    Decimal Point PositionSet the required number of decimal places for both thedisplay full scale and display zero values. In the exampleshown above, set the decimal point position to showincrements of 0.1 psi, i.e. 200.0.

    Display ZeroSet the display value which represents the minimumpressure input signal, between –9999 and +9999.In the example shown above, set 0.0. The decimal pointposition is set automatically.

    Increment Per Bar (Bargraph)This frame sets the deviation from the deviation alarm tripvalue that each bar of the Deviation Bargraph represents.Set the value required, in engineering units.

    The decimal point position is set automatically

    Brightness AdjustmentSelect the required display brightness between 4 and 7.

    Return to top of page.

    brIGHt 7

    dISPLYPAGE

    dIS–HI1000

    dEC–Pt1000

    dIS–LO0

    INCMNt 1

  • 15

    3 CONFIGURATION LEVEL…

    3.5 Retransmission Output Page

    Information.• Retransmission types – allows retransmission of any two signals, i.e. raw product

    pressure, pasteurised product pressure, pressure difference.• Adjustable pressure difference output range.• 4 to 20mA outputs.

    Page header – Retransmission Output Page.

    Retransmission TypesSelect the retransmission signals required.

    Pressure Difference Output High ValueSet the level of pressure difference at which 20mA outputis required (see Note).

    Set the value in engineering units between –9999 and9999 (the decimal point position is set automatically).

    Pressure Difference Output Low ValueSet the level of pressure difference at which 4mA output isrequired (see Note).

    Set the value in engineering units between –9999 and9999 (the decimal point position is set automatically).

    Note. The pressure difference is calculated as:pasteurized product pressure – raw product pressure.

    Therefore, a positive value = pasteurized product pressure> raw product pressure.

    A negative value = raw product pressure > pasteurizedproduct pressure.

    Return to top of page.

    r–d

    rEtrANOUtPUt

    diFFHI ––––

    diFFLO

    tYPE

    d–Pr–P

    ––––

    r–P

    r–dd– P

    epyT P/Odetalosi-noN P/OdetalosI

    91egapees)ON(degnahcretnitonstuptuO

    d–r erusserPtcudorPwaR erusserPdetaluclaC ecnereffiD

    P–d erusserPdetaluclaC ecnereffiDtcudorPdeziruetsaP

    erusserP

    P–r erusserPtcudorPwaR tcudorPdeziruetsaP erusserP

    91egapees)SEY(degnahcretnistuptuO

    d–r erusserPdetaluclaC ecnereffiD erusserPtcudorPwaR

    P–d tcudorPdeziruetsaP erusserPerusserPdetaluclaC

    ecnereffiD

    P–r tcudorPdeziruetsaP erusserP erusserPtcudorPwaR

  • 16

    …3 CONFIGURATION LEVEL

    3.6 Scale Adjustment Page

    Information.• Scale Adjustment Reset – removes any previously programmed offset or scale

    adjustment settings.• System offset errors – can be removed using Offset Adjustment.• System scale errors – can be removed using Span Adjustment.• Offset/Span Adjustment – can be used to perform spot calibration.

    Switch off the power supply. Connect accurate signal sources, suitable for simulation over theentire input ranges, in place of the raw product process connections (terminals 13 and 14) andpasteurized product process connections (terminals 16 and 17).

    As a general rule, spot calibration values should be:< 50% of range span value when using Offset Adjustment parameters.> 50% of range span value when using Span Adjustment parameters.

    Page header – Scale Adjustment

    Raw Input Scale Adjustment ResetSet YES and press to reset the process variable offsetand span values to their nominal values. dONE is displayedto indicate that these parameters have been reset.

    Raw Input Offset AdjustmentApply the correct input for the spot calibration required.

    Note. The displayed units are engineering units.Set the value required. The decimal point position is setautomatically.

    Example – If the display range is 0.0 to 20.0 and a spotcalibration is required at 5.0 and 15.0, inject a signalequivalent to 5.0 and set the display to 5.0.

    Raw Input Span AdjustmentProceed as for Raw Input Offset Adjustment and apply thecorrect input for the spot calibration required. Engineeringunits are displayed.

    Set the value required. The decimal point position is setautomatically.

    For the Example above inject a signal equivalent to 15.0and set the display to 15.0.

    Continued on next page.

    SCALE

    r–rSt

    AdJUSt

    no

    ––––r–OFS

    ––––r–SPN

  • 17

    3 CONFIGURATION LEVEL…

    …3.6 Scale Adjustment Page

    Pasteurized Input Scale Adjustment ResetSelect YES and press to reset the process variableoffset and span values to their nominal values. dONE isdisplayed to indicate that these parameters have beenreset.

    Pasteurized Input Offset AdjustmentApply the correct input for the spot calibration required.

    Note. The displayed units are engineering units.Set the value required. The decimal point position is setautomatically.

    Example – If the display range is 0.0 to 20.0 and a spotcalibration is required at 5.0 and 15.0 inject a signalequivalent to 5.0 and set the display to 5.0.

    Pasteurized Input Span AdjustmentProceed as for Raw Input Offset Adjustment and apply thecorrect input for the spot calibration required. Engineeringunits are displayed.

    Set the value required. The decimal point position is setautomatically.

    For the Example above inject a signal equivalent to 15.0and set the display to 15.0.

    Return to top of page.

    P–rStno

    ––––P–OFS

    ––––P–SPN

    from previous page

  • 18

    …3 CONFIGURATION LEVEL

    3.7 Access Page

    Information.• Alarm Password – protects the alarm settings.• Configuration Password – protects the controller configuration setup.

    Page Header – Access Page.

    Configuration PasswordThe configuration password enables access to allprogramming pages (Security Level 2).

    Note. The password has no effect if the security link is inthe 'secure' position – see Section 2.4

    Set the required password, between 0 and 1999.

    Alarm PasswordThe alarm password enables access to the Alarm Set Uppage in addition to the Operating Page (Security Level 1).

    Note. The password has no effect if the security link is inthe 'secure' position – see Section 2.4

    Set the required password, between 0 and 1999.

    Return to top of page.

    ACCESS

    C–PASS0

    A–PASS0

    PAGE

  • 19

    3.8 Commissioning

    3 CONFIGURATION LEVEL

    Page header – Commissioning

    Isolated Retransmission OutputAllows the isolated and non-isolated retransmissionoutputs to be inter-changed.

    NO – Outputs not interchanged (see table on page 15).

    YES – Outputs interchanged (see table on page 15– isolated and non-isolated output sorces arereversed).

    Return to top of page.

    ISO_rt

    YESNO

    CO__I-SSION

  • 20

    4 INSTALLATION

    4.1 Checking the Code Number – Fig. 4.1

    COMMANDER 320 Booster Pump Controller C320/

    None 0

    115V AC *230V AC24V AC

    123

    0Standard

    Configured to Factory StandardsConfigured to Customers DetailsAgreed Special Feature

    STDCUSSPXX

    XXXXXX0X

    OptionBoard

    PowerSupply

    Build

    ConfigurationSpecial Features

    Fig. 4.1 Location of Code Number Label

    * 115V AC versions are fitted with 0.5in NPT gland entry fixings – see section 4.7.2

    Table 4.1 Identification of Instrument Code Number

    Code Number Label – see Table 4.1

    C320/0 X X X X X X X

  • 21

    4 INSTALLATION…

    EC Directive 89/336/EEC

    In order to meet the requirements of theEC Directive 89/336/EEC for EMCregulations, this product must not beused in a non-industrial environment.

    4.2 Siting – Figs. 4.2 and 4.3

    SensorKeep toMinimum

    A – Close to Sensor

    B – At Eye-level Location

    C – Avoid Vibration

    Fig. 4.2 General Requirements

    55°CMax.

    0°CMin.

    0 to 90% RH

    +

    Caution. Select a location away fromstrong electrical and magnetic fields.If these cannot be avoided,particularly in applications where‘walkie talkies’ are used, connectusing screened cables within earthedmetal conduit.

    A – Within Temperature Limits

    B – Within Humidity Limits

    C – Use Screened Cables

    Fig. 4.3 Evironmental Requirements

  • 22

    …4 INSTALLATION

    4.3 Mounting – Figs. 4.4 and 4.5The instrument is designed for wall-/pipe-mounting – see Fig. 4.5. Overall dimensions areshown in Fig. 4.4.

    2.68 (68)

    8.43(214)

    9.13(232)

    Fix

    ing

    Cen

    tres

    6.3 (160)

    9.84(250)

    2.72 (69)

    Fixing Centres

    Allowance forCable Bends7.9 (200)

    1.65(42)

    23/8 (61) O.D. vertical or horizontal post

    Fixing Holes(x3) 0.25 (6.5) Diaa

    Fig. 4.5 Wall-/Pipe-mounting Details

    Fig. 4.4 Overall Dimensions

    Position ‘U’ bolts on pipe

    Position plates over ‘U’ bolts

    Secure transmitter to mounting plate

    Secure plates

    Mark fixingcentres

    (see Fig. 4.4)

    Drill suitableholes

    Fix instrument towall using

    suitable fixing

    (Pipe Mounting Kit –part no. 4600/0138)

    1

    2

    3

    1

    2

    3

    4

  • 23

    Warning. Before making any connections, ensure that the power supply, any high voltage-operated control circuits and high common mode voltages are switched off.

    Note.• Always route signal leads and power cables separately, preferably in earthed metal

    conduit.• It is strongly recommended that screened cable is used for signal inputs and relay

    connections. Connect the screen to the ground stud.

    Information. Use cable appropriate for the load currents. The terminals accept cables up12AWG (2.5mm2).

    4.4 Access to Terminals – Fig. 4.6For access to terminals – refer to Fig. 4.6, steps 1 to 3.

    4 INSTALLATION…

    Slacken captive screws andremove protection cover

    Remove frontpanel screws

    Remove frontpanel

    Remove capand screw

    4

    6

    slidedown

    1

    Pull outslightly…

    …andslide off

    2

    2

    5

    3

    Fig. 4.6 Access to Terminals and Processor Board

  • 24

    …4 INSTALLATION…

    4.5 Setting the Input Selector Links – Fig. 4.7Remove the instrument front panel – see Fig. 4.6, steps 1 to 6.

    The positions of the input links is shown in Fig. 4.7 detail A.

    4.6 Setting the Isolated Output Link – Fig. 4.7The positions of the isolated output links is shown in Fig. 4.7 detail B.

    PL2Pasteurized

    pressure input

    PL1Raw pressure

    input

    PL

    2

    PL

    11 6

    12 7

    1 4

    8 5

    1

    2

    Identify Link PL7

    Set the links for the output

    PL71

    B – Isolated Output Links

    A – Input Links

    Note. The links are factory set and should not be moved from these positions.

    Fig. 4.7 Setting the Input and Output Links

  • 25

    4.7 Cable Glands and ConduitFixings

    4.7.1 Cable Glands (IEC – 20mm) –Fig. 4.8

    4 INSTALLATION…

    'O'-Ring

    Fig. 4.8 Cable Gland (Supplied as Standard)

    Ferrule

    Outer Nut

    Seal(Presentin O.Z.GedneyFittings)

    AlternativeFace Seal

    FaceSeal

    Hub

    Fig. 4.9 Conduit Adaptors

    4.7.2 Conduit Adaptors (N.American – 0.5in) – Fig. 4.9

    Warning.• Rigid conduit must NOT be fitted to the

    controller.• Controller adaptors must incorporate

    a face seal.• Torque settings for the hubs and outer

    nuts on the specified adaptors is20ft. lbs minimum, 25ft. lbs. maximum.

    Information.• Suitable adaptors for controller

    (mandatory for FM installations):APPLETONST-50 PLUS STG-50 or STB-50PLUS STG-50.Reusable ONLY with replacementferrule STF-50.O.Z. GEDNEY4Q-50, 4Q50T or 4Q-50TG.

  • 26

    …4 INSTALLATION

    Fittingsvaryslightlyfordifferentmakes

    Outer Nut

    AlternativeFace Seal

    FaceSeal

    Hub

    Illustrationtypical forO.Z.Gedney

    Fig. 4.10 Cable Glands

    4.7.3 Cable Glands (N. American –0.5in) – Fig. 4.10

    Warning.• Controller glands must be fitted with a

    face seal.• Torque settings (hubs only) – 20ft. lbs

    minimum, 25ft. lbs. maximum.• Outer nuts – hand tight plus a half turn

    only.

    Information.• Suitable Cable Glands: (mandatory for

    FM installations):O.Z. GEDNEYSR-50-375 or SR-504APPLETONCG 3150 or CG-3150S (and STG-50 sealing ring).THOMAS & BETTS2521.

    • When fitting cable glands to thecontroller, start with an outer glandand also temporarily fit a gland at theopposite end, to aid location of thetransmitter gland plate. Fit and tightenglands consecutively from initialgland.

  • 27

    4 INSTALLATION…

    Fig. 4.11 Terminal Block Identification

    3 4 5 6 7 8 9

    18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

    10 11 12 13 14 15

    1 2

    16 17

    PowerSupply

    Relay 1

    Relay 2

    Relay 3

    Non-isolatedRetransmission Output

    Raw Pressure Input

    Pasteurized Pressure Input

    Logic InputIsolatedRetransmission

    Output

    SecurityOverride

    Input

    4.8 Connections Summary – Fig. 4.11

    Information.Input impedance: Current 10Ω.

  • 28

    …4 INSTALLATION…

    Table 4.2 Electrical Connections

    Terminal Number

    12

    3 N/O4 C5 N/C

    6 N/O7 C8 N/C

    9 N/O10 C11 N/C

    121314

    151617

    1819202122

    23 +24 –

    25 +26 –

    272829

    303132

    2-wire TXInput 1+Input 1–

    Input 2+Input 2–

    Non-isolated 4 - 20mA Retransmission Output – see Fig 4.14

    Raw pressure Input – see Figs. 4.12 and 4.13

    Pasteurized pressure Input – see Figs. 4.12 and 4.13

    Relay 1 Output Booster pump or divert valve– see Fig. 4.14

    Relay 2 Output Booster pump or divert valve– see Fig. 4.14

    Relay 3 Output– see Fig. 4.16

    AC SupplyLN

    – see Fig. 4.17

    Alarm Annunciator

    Logic Input 1Security Override InputCommon for Logic Inputand Security Override Input

    Isolated 4 - 20mA Retransmission Output – see Fig 4.14

    24V, 115V or 230V a.c.

    see Fig. 4.15

    see Fig. 2.2

  • 29

    $£@&^%Pasteurized pressure input

    SleevedLink

    –+

    Raw pressure input

    Fig. 4.12 Current Input Connections

    Fig. 4.13 2-wire Transmitter Connections

    $£@&^Pasteurized pressure input

    Raw pressure input@

    TX+ –

    4 INSTALLATION…

    Fig. 4.14 Retransmission Output Connections

    Information.The isolated and non-isolated outputsmay be interchanged – see section 3.7

    Manual override

    Normal5V

    0VLogic switching

    Normal

    Manual Override

    Common

    Logic Input 130

    32

    323130

    Note. The manual overridede-energises Relay 1 allowing theoperator to turn the booster pump offmanually.

    Fig. 4.15 Logic Input Functions

    4.9 Input Connections4.9.1 Current Input – Fig. 4.12

    4.9.2 2-wire Transmitter – Fig. 4.13

    4.10 Output Connections – Fig. 4.14

    4.11 Logic Input Connection – Fig.4.15

    Non-isolated 4 to 20mARetransmission O/P ofRaw Input

    Isolated 4 to 20mARetransmission O/P ofPasteurized Input

    23

    25

    24

    26

    –+

  • 30

    …4 INSTALLATION…

    Fig. 4.16 Relay Connections

    437609

    58!Relay 3

    Relay 2Relay 1

    Normally ClosedCommon

    Normally Open

    DeviationAlarm (A1)

    Start-upAlarm (A2)

    LogicInput 1

    Relaystate

    Relay 1for booster pumpor divert valvecontrol

    Relay 2for booster pumpor divert valvecontrol

    Relay 3for warning lightor horn

    ActiveXXInactive

    XActiveXInactive

    XXManual overrideNormal

    De-energisedDe-energisedDe-energisedEnergised

    ActiveInactive

    XX

    XX

    De-energisedEnergised

    Active & UnackActive & ackInactive

    XXX

    XXX

    EnergisedDe-energisedDe-energised

    * X = Don't careTable 4.3 Relay and Alarm States

    4.12 Relay Connections – Fig. 4.16See Table 4.3 for relay and alarm states.

  • 31

    4 INSTALLATION

    115

    Selector not fitted (24V AC)

    Code LabelDigit 7

    32

    1

    C32 x x xx x x x x x

    115

    230

    Remove plug tomake connection

    A – Selecting the Supply Voltage

    B – Power Supply Connections

    Line

    Neutral

    Ground

    230V

    115V

    Fuse

    Information.Fuse Rating – 5A Type T

    Fig. 4.17 Power Supply Selection and AC Connections

    4.13 Power Supply Selection and AC Connections – Fig. 4.17

  • 32

    SPECIFICATION

    Summary

    C320 Booster Pump Controller

    Two analog inputs

    Three relays

    Two analog outputs

    IP66 (NEMA 4X) housing

    OperationDisplay

    High-intensity, 7-segment, 0.56 in. (14mm),2 x 6 red LED display

    11-element l.e.d. deviation bargraph

    Configuration

    User-defined via front panel

    Analog InputsNumber

    Two 4 to 20mA signals

    Input sampling rate

    160ms per channel

    Input impedance

    10Ω

    Broken sensor protection

    Programmable Up/Downscale or None

    Input noise rejection

    Common mode rejection >140dB at 50/60Hz with 500Ωimbalance

    Series mode rejection >60dB at 50/60Hz

    Accuracy

    Measurement error

  • PRODUCTS & CUSTOMER SUPPORT

    ProductsAutomation Systems

    • for the following industries:– Chemical & Pharmaceutical– Food & Beverage– Manufacturing– Metals and Minerals– Oil, Gas & Petrochemical– Pulp and Paper

    Drives and Motors• AC and DC Drives, AC and DC Machines, AC

    motors to 1kV• Drive systems• Force Measurement• Servo Drives

    Controllers & Recorders• Single and Multi-loop Controllers• Circular Chart , Strip Chart and Paperless

    Recorders• Paperless Recorders• Process Indicators

    Flexible Automation• Industrial Robots and Robot Systems

    Flow Measurement• Electromagnetic Flowmeters• Mass Flow Meters• Turbine Flowmeters• Flow Elements

    Marine Systems & Turbochargers• Electrical Systems• Marine Equipment• Offshore Retrofit and Referbishment

    Process Analytics• Process Gas Analysis• Systems Integration

    Transmitters• Pressure• Temperature• Level• Interface Modules

    Valves, Actuators and Positioners• Control Valves• Actuators• Positioners

    Water, Gas & Industrial AnalyticsInstrumentation

    • pH, conductivity, and dissolved oxygentransmitters and sensors

    • ammonia, nitrate, phosphate, silica, sodium,chloride, fluoride, dissolved oxygen andhydrazine analyzers.

    • Zirconia oxygen analyzers, katharometers,hydrogen purity and purge-gas monitors,thermal conductivity.

    Customer SupportWe provide a comprehensive after sales service via aWorldwide Service Organization. Contact one of thefollowing offices for details on your nearest Service andRepair Centre.

    United KingdomABB LimitedTel: +44 (0)1480 475 321Fax: +44 (0)1480 217 948

    United States of AmericaABB IncTel: +1 215-674-6000Fax: +1 215-674-7183

    Client Warranty

    Prior to installation, the equipment referred to inthis manual must be stored in a clean, dryenvironment, in accordance with the Company'spublished specification.Periodic checks must be made on theequipment's condition. In the event of a failureunder warranty, the following documentation mustbe provided as substantiation:

    1. A listing evidencing process operation and alarmlogs at time of failure.

    2. Copies of all storage, installation, operating andmaintenance records relating to the allegedfaulty unit.

  • IM/C

    320

    Issu

    e 5

    The Company’s policy is one of continuous productimprovement and the right is reserved to modify the

    information contained herein without notice.

    Printed in UK (06.04)

    © ABB 2004

    ABB Inc.125 E. County Line RoadWarminster, PA 18974USA

    Tel: +1 215 674 6000Fax: +1 215-674 7183

    ABB LimitedHoward Road, St. NeotsCambridgeshire, PE19 8EUUK

    Tel: +44 (0)1480 475321Fax: +44 (0)1480 217948

    ABB has Sales & Customer Support expertisein over 100 countries worldwide

    www.abb.com

    GETTING STARTED1 DISPLAYS AND CONTROLS2 OPERATING LEVEL3 CONFIGURATION LEVEL4 INSTALLATIONSPECIFICATION