Ultrasonic Testing
Weld Inspection using AWS D1.1
![Page 2: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/2.jpg)
2
Introduction
This presentation will help students perform testing using the American Welding Society Structural Steel D1.1-2000 code and procedure.
It is important to remember that this is a general training program and the procedure should be referenced for specific information.
![Page 3: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/3.jpg)
3
What you will learn
Completing Form D-11 Determine the proper transducer(s) needed for
testing a weld. Calibration using an IIW, rumpus, and DSC
block. Scanning for discontinuities. Calculate size and location of a discontinuity. Accept/Reject evaluation of a discontinuity.
![Page 4: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/4.jpg)
4
Form D-11
Weld Identification Material Thickness Type of Weld Joint Welding Process Quality Requirements Section Number Year of AWS D1.1 Code used. Testing Date Inspected By
Some basic information should be completed on form D-11 prior to the inspection. This information includes the following:
![Page 5: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/5.jpg)
5
Step 1 – Specimen Measurement Measure the part thickness. From this thickness you will need to
calculate the skip distance. The skip distance is the area where you will scan the part with the proper angle transducer. Mark the end of the skip distance from the edge of the heat affected zone (HAZ). The area in red will be used to identify the heat affected zone.
![Page 6: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/6.jpg)
6
Step 2 – Inspection Layout The skip distance will equal the surface distance of the two legs.
You will need to know the distance of this area in order to perform a lamination scan followed by an angle beam examination
![Page 7: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/7.jpg)
7
Inspection Layout Identifying the skip distance from the edge of the
HAZ will ensure complete coverage of the weld when performing an angle beam examination.
![Page 8: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/8.jpg)
8
Step 3 – Lamination Scan A lamination scan will be performed in the area
where the angle beam inspection will take place. This scan is performed with a straight beam transducer.
![Page 9: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/9.jpg)
9
Lamination Scan Perform a lamination scan from face “A”. You will need
to see at least two plate thicknesses on the display. The first backwall reflection shall be 50 to 75% full screen height.
![Page 10: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/10.jpg)
10
Lamination Scan If any area of the base metal shows a total loss of
backwall reflection, or if an indication is equal or greater to the backwall reflection, the size and location and depth will be reported.
![Page 11: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/11.jpg)
11
Lamination Scan Move the transducer in all directions until the
amplitude of the signal is reduced by 50%. Mark the center of the transducer.
![Page 12: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/12.jpg)
12
Lamination Scan The area can be measured and included in the report. This
area should be avoided when performing an angle beam examination or an alternate scanning procedure shall be used.
![Page 13: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/13.jpg)
13
Lamination Scan Note the location and size of the lamination on report
form D-11 or write an additional report with a drawing showing its location.
![Page 14: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/14.jpg)
14
Step 4 – Transducer Angle Table 6.6 will list the transducer angles needed to test the weld.
For material 0.60” the transducer angle used will be 70 degrees and will be tested from face “A”. On Form D-11 record the transducer angle and face which you will be testing from. The face is determined from Table 6.6
![Page 15: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/15.jpg)
15
Step 5 – Screen Range Calculate the full V-path. This is determined by the
material thickness and transducer angle. Choose the appropriate screen range in order to see a minimum sound path of two legs.
![Page 16: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/16.jpg)
16
Step 6 – Screen Range Calculate the full V-path. This is determined by the
material thickness and transducer angle. Choose the appropriate screen range in order to see a minimum sound path of two legs.
![Page 17: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/17.jpg)
17
Transducer Verify the transducer is coupled to the wedge
and there are no air pockets between the two.
![Page 18: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/18.jpg)
18
Calibration - IIW Block All measurements are taken from where the signal
breaks the baseline of the ultrasonic screen.
![Page 19: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/19.jpg)
19
Screen Range – IIW Block Adjust the ultrasonic machine to obtain the proper
screen range. With an IIW type II block shown, the backwall reflections will be located at 2” and 4”.
Position of the signals with a 10” screen range.
![Page 20: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/20.jpg)
20
Screen Range – IIW Block The position of the 2” and 4” reflections when using a
5” screen range.
Position of the signals with a 5” screen range.
![Page 21: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/21.jpg)
21
Screen Range – DSC Block The distance and sensitivity calibration block (DSC) can be
used for calibration. With the transducer placed in the position shown, the reflections will take place at 1”, 5”, 9”, etc.
Position of the signals with a 10” screen range.
![Page 22: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/22.jpg)
22
Screen Range – DSC Block With the transducer placed in the position shown, the
reflections will take place at 1”, 5”, 9”, etc.
Position of the signals with a 5.0” screen range.
![Page 23: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/23.jpg)
23
Screen Range – DSC Block With the transducer placed in the position shown, the
reflections will take place at 3”, 7”, 11”, etc.
Position of the signals with a 10” screen range.
![Page 24: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/24.jpg)
24
Screen Range – DSC Block With the transducer placed in the position shown, the
reflections will take place at 3”, 7”, 11”, etc.
Position of the signals with a 15” screen range.
![Page 25: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/25.jpg)
25
Screen Range – Rumpus Block The miniature calibration block or rumpus block can also be
used for calibration. With the transducer placed in the position shown, the reflections will take place at 1”, 4”, 7”, 10” etc.
Position of the signals with a 5” screen range.
![Page 26: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/26.jpg)
26
Screen Range – Rumpus Block With the transducer placed in the position shown, the
reflections will take place at 1”, 4”, 7”, 10” etc.
Position of the signals with a 10” screen range.
![Page 27: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/27.jpg)
27
Screen Range – Rumpus Block With the transducer placed in the position shown, the
reflections will take place at 2”, 5”, 8”, etc.
Position of the signals with a 5” screen range.
![Page 28: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/28.jpg)
28
Screen Range – Rumpus Block With the transducer placed in the position shown, the
reflections will take place at 2”, 5”, 8”, etc.
Position of the signals with a 10” screen range.
![Page 29: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/29.jpg)
29
Step 7 – Transducer Exit Point Determine the exit point of the transducer. Peak the signal on the
ultrasonic machine and verify that the index point on the plastic wedge matches the calibration block. You may use tape and a pen to mark the exit point. This will allow for easier measurements when measuring the surface distance.
![Page 30: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/30.jpg)
30
Exit Point – IIW Block The exit point and screen range can be performed at the same
time. Slide the transducer back and forth until the signal is maximized. The pictures below shows the location of the transducer when verifying the exit point using an IIW type II block.
![Page 31: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/31.jpg)
31
Exit Point – DSC Block The exit point and screen range can be performed at the same
time. Slide the transducer back and forth until the signal is maximized. The pictures below shows the location of the transducer when verifying the exit point.
![Page 32: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/32.jpg)
32
Exit Point – Rumpus Block The exit point and screen range can be performed at the same
time. Slide the transducer back and forth until the signal is maximized. The picture below shows the location of the transducer when verifying the exit point.
![Page 33: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/33.jpg)
33
Step 8 – Transducer Angle The angle of the transducer will need to be verified. It
shall be within plus or minus 2 degrees of the required angle.
![Page 34: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/34.jpg)
34
Angle – IIW Block Slide the transducer back and forth until the signal is
maximized. The picture below shows the location of the transducer when verifying the transducer angle.
![Page 35: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/35.jpg)
35
Angle – DSC Block Slide the transducer back and forth until the signal is
maximized. The picture below shows the location of the transducer when verifying the transducer angle.
![Page 36: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/36.jpg)
36
Angle – Rumpus Block Slide the transducer back and forth until the signal is
maximized. The picture below shows the location of the transducer when verifying the transducer angle.
![Page 37: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/37.jpg)
37
Step 9 – Transducer Resolution The resolution shall be checked with the instrument controls set at normal
test settings and the indications from the holes brought to midscreen height. Resolution shall be sufficient to identify the peaks of the three holes.
Position of the signals with a 5” screen range.
![Page 38: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/38.jpg)
38
Step 10 – Reference Level
The amplitude of a known size reflector will be adjusted from 50-75% full screen height. The dB will be recorded as the reference level on form D-11.
IIW blockDSC block
Rumpus block
![Page 39: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/39.jpg)
39
Reference Level – IIW Block The transducer shall be placed in the position shown and the signal
amplitude from the hole will be maximized. Adjust the dB in order to obtain a signal from 50 to 75% full screen height. This will be used as the reference level “b” on form D-11.
Position of the signals with a 10” screen range.
![Page 40: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/40.jpg)
40
Reference Level – DSC Block The transducer shall be placed in the position shown and the
signal amplitude from the notch will be maximized. Adjust the dB in order to obtain a signal from 50 to 75% full screen height. This will be used as the reference level “b” on form D-11.
Position of the signals with a 10” screen range.
![Page 41: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/41.jpg)
41
Reference Level – Rumpus Block The transducer shall be placed in the position shown and the
signal amplitude from the hole will be maximized. Adjust the dB in order to obtain a signal from 50 to 75% full screen height. This will be used as the reference level “b” on form D-11.
Position of the signals with a 5” screen range.
![Page 42: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/42.jpg)
42
Step 11 – Reference Level In this example the reference level “b” would be
recorded as 42 dB. The reference screen height used is 60% FSH.
![Page 43: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/43.jpg)
43
Step 12 – Scanning Level Scanning level is based on sound path distance and not
material thickness. If table 6.2 (Statically loaded nontubular connections) are tested, the following scanning levels will be used.
Above ZeroSound Path (in) Reference, dB0.0” to 2.5” 14>2.5” to 5” 19>5” to 10” 29>10” to 15” 39
![Page 44: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/44.jpg)
44
Scanning Level If table 6.3 (Cyclically loaded nontubular connections) are
tested, the following scanning levels will be used.
Above ZeroSound Path (in) Reference, dB0.0” to 2.5” 20>2.5” to 5” 25>5” to 10” 35>10” to 15” 45
![Page 45: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/45.jpg)
45
Scanning Level This shows the screen presentation when using a
scanning level 14 dB above the reference level.
![Page 46: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/46.jpg)
46
Step 13 – Initial Information Scan
Perform an initial information scan marking the location of any suspected discontinuities.
![Page 47: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/47.jpg)
47
Weld Configuration You can draw a diagram of the weld on the ultrasonic screen
with a water based marker or grease pencil. The line is drawn at the end of the 1st, 2nd, and 3rd leg. This may help you visualize the location of the discontinuity in the weld.
![Page 48: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/48.jpg)
48
Step 14 – Surface Distance Calculate the surface distance in order to determine if
the signal is located in the weld.
![Page 49: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/49.jpg)
49
Step 15 – Discontinuity Depth Calculate the depth in order to determine if the signal
is located in the weld.
![Page 50: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/50.jpg)
50
Step 16 – Sound Path Move the transducer in all directions in order to peak
the signal from the discontinuity. Record the “Sound Path” on Form D-11.
![Page 51: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/51.jpg)
51
Step 17 – Sound Path Record the “Leg” on Form D-11.
![Page 52: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/52.jpg)
52
Step 18 – Indication Level Increase or decrease the dB until the screen height from the
discontinuity is equal to the reference level. Record the dB under indication level (column b).
dB reference level - 60% FSH.
![Page 53: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/53.jpg)
53
Step 19 – Attenuation Factor Subtract one inch from the sound path distance and multiply the
remainder by two. This number will be rounded to the nearest whole number. If the number is less than 0.5 dB it will be lowered to the nearest whole number. If the number is 0.5 or greater, it will be increased to the nearest whole number.
In this example, the sound path is 1.9”
1.9” – 1 = 0.90.9 x 2 = 1.8
Rounded to the nearest whole number - 2
![Page 54: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/54.jpg)
54
Attenuation Factor On Form D-11, fill out the attenuation factor. This is
located under “Decibels- Attenuation Factor.
In this example, the sound path is 1.0”
1.0 – 1 = 0.00.0 x 2 = 0.0
If the attenuation factor is less than 0.5, the attenuation factor will be zero.
![Page 55: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/55.jpg)
55
Step 20 – Indication Rating
The indication rating is calculated by taking the “Indication level” minus “Reference level” minus “Attenuation factor”. A-B-C=D
The answer “D” is your indication rating and can be positive or negative. Write this number in column “D” under “Decibels”, Indication Rating”
![Page 56: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/56.jpg)
56
Step 21 – Discontinuity Length
Maximize the signal amplitude from the discontinuity.
![Page 57: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/57.jpg)
57
Step 22 – Discontinuity Length Slide the transducer parallel with the weld until the
signal amplitude has reduced by 50%. Mark the location next to the weld aligned with the center of the transducer. Perform this procedure in both directions.
![Page 58: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/58.jpg)
58
Discontinuity LengthRecord the length on Form D-11.
![Page 59: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/59.jpg)
59
Step 23 – Discontinuity Class From Table 6.2 or 6.3, determine the Discontinuity
Severity Class. This is based on the Indication Rating and Length.
Class A (large discontinuity)Any indication in this category shall be rejected regardless of length
Class B (medium discontinuity)Any indication in this category having a length greater than ¾” shall be rejected.
Class C (small discontinuity)Any indication in this category having a length greater than 2” shall be rejected.
Class D (minor discontinuity)Any indication in this category shall be accepted regardless of length or location in the weld.
![Page 60: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/60.jpg)
60
Step 24 – Discontinuity Evaluation
On Form D-11 under “Discontinuity Evaluation” list the class of the discontinuity.
![Page 61: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/61.jpg)
61
Step 25 – Accept/Reject On Form D-11 under “Remarks” accept or reject the
discontinuity.
![Page 62: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/62.jpg)
62
Step 26 – Distance from “Y” One side of the plate or weld can be identified with a “Y”
location point. From the edge of the weld measure to the beginning of the discontinuity. Record “Distance from “Y” on Form D-11.
Distance from “Y” = 1.0” Distance from “Y” = 0.3”
![Page 63: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/63.jpg)
63
Step 27 – Distance from “X” From the center of the weld (marked in black), if the
discontinuity is located opposite the “Y” location mark, it will be measured as a positive number. This will be recorded under “Distance from X” on Form D-11.
Distance from X = 0.2”
![Page 64: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/64.jpg)
64
Step 28 – Distance from “X” From the center of the weld (marked in black), if the
discontinuity is located on the same side as the “Y” location mark, it will be measured as a negative number. This will be recorded under “Distance from X” on Form D-11.
Distance from X = -0.2”
![Page 65: Ultrasonics aws](https://reader036.vdocuments.site/reader036/viewer/2022062303/557aa84ad8b42a9f2e8b48b7/html5/thumbnails/65.jpg)
65
Step 29 – Scanning Level Return to the scanning level and locate the next
discontinuity for evaluation.