H umidity Source Quality, Selection, Support MODEL BUS NOZZLE ATOMIZER HUMIDIFIER ULTRASONIC NOZZLE SYSTEM STAINLESS STEEL COMPRESSED AIR NOZZLE ON-OFF OR PROPORTIONAL CONTROL Model BUS Ultrasonic Nozzle Ideal for storage rooms, walk-in coolers, produce storage areas, wine cellars, humidors, laboratories & testing rooms Humidity Source, LLC 90 Dayton Ave. Suite 58, Passaic, New Jersey 07055 TEL 973-916-1001 FAX: 973-916-0770 1

Upload: others

Post on 03-Feb-2022

10 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

H

umidity Source Quality, Selection, Support

MODEL BUS NOZZLE ATOMIZER HUMIDIFIER

ULTRASONIC NOZZLE SYSTEM

STAINLESS STEEL COMPRESSED AIR NOZZLE ON-OFF OR PROPORTIONAL CONTROL

U

Ideal for storage rooms, walk-in coolers, produce storage areas, wine cellars, humidors, laboratories & testing rooms

90 Dayton Ave TEL 973-9

Humidity Source, LLC . Suite 58, Passaic, New Jersey 07055 16-1001 FAX: 973-916-0770

Model BUS ltrasonic Nozzle

1

Page 2: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

Duct Or Open Air Applications BUS Nozzle Atomizer

The Ultrasonic Nozzle The Ultrasonic Nozzle uses compressed air to atomize water by directing a high velocity stream of water particles at a target. The force of impact causes the target to resonate or vibrate at ultrasonic speeds, this action breaks up the water particles into an extremely fine fog-like like mist. Water particle sizes down to 5 micron are created by this method. Because most of the forward water particle velocity energy is dissipated in generating the fog, this nozzle is best suited for air handling units, air ducts and cold storage rooms where there is ample air motion. An integral fail-safe valve shuts off the nozzle water if the compressed air should fail. When the nozzle is shut off under normal operations, the main water supply valve is closed, the integral valve is shut off, and air is allowed to flow for a short time to purge the nozzle of residual water. This sequence insures a “no-drip” shut down of the nozzle.

Ultrasonic Nozzle Model BUS

The Ultrasonic nozzle system is also available on a pre-assembled mounting bar. An aluminum bar complete with stainless steel brackets, nozzles, plastic tubing and assembled connectors makes air handling units and air duct installations quick and easy. Special stainless steel end brackets mount on the inside of duct walls and support the nozzle bar. Mounting bars can be sized to fit most air duct applications.

BUS Mounting Bar

Particles So Fine They Stay Suspended Options √ Proportional Control The Fog System is available with proportional control that will modulate nozzle output proportional to room demand. The proportional control system responds to all standard proportional humidistat signals. The proportional control cabinet features a digital display showing set point, proportional band, and % RH at the sensor location. √ The Humidity Source Fog System of humidification control is a drip-less, safe, easy to install and economical way of maintaining any level of relative humidity. The pre-assembled nozzle bars offer additional benefits of quick and easy installation with minimum modifications to existing building structures.

2

Page 3: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

BUS ULTRASONIC NOZZLE CONTROL CABINETS

dFogSystem

12

45

7

8

9

10

FogSystem d

12

3

45

6

7

8

9

10

ON-OFF ONE ZONE (AC BUS A1 1Z)

ON-OFF TWO ZONE (AC BUS A1 2Z)

2

45

6

8

7

FogSystem

d

3

19

1-2-3 Electrical cable connections 4 Air inlet 5 Air outlet (Controls main air valve Zone 1) 6 Air outlet (Controls main air valve Zone 2)

7 ON/OFF switch 8 Humidification demand light 1 Zone = 1 light 2 Zones = 2 lights 9 Pressure gauge 1 per Zone 10 Adjustable air valve 1 per Zone

1 Main air inlet 2 Air regulator with gauge and filter 3 Air inlet port 4 Air outlet to main air valve 5 Humidistat port 6 Electrical power 7 Pressure control valve 8 ON/OFF switch 9 Digital display and set point buttons (Optional)

PROPORTIONAL ONE ZONE

3

Page 4: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

FogSystem Humidifiers

Ultrasonic Nozzles Air & Water Manifold

DRAIN

AIR REGULATOR

3/8” Water to Nozzles

¼” Tubes To Control Cabinet

OPTIONAL 10 MICRON

AIR & WATER FILTERS 3/8” Air to

Nozzles

AIR IN

WATER REGULATOR

WATER VALVES

CHECK VALVE

WATER IN

NOTE:

1. Adjust water pressure to 15 psi. less than air pressure. 2. Tube dimensions are O.D. 3. Increase tubing size to nozzle bar to

allow for distance from manifold to nozzles.

4. Optional Air & water filters should be used to keep the nozzles and control valves clean. Supplied by Humidity Source or by others.

4

Page 5: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

FogSystem Ultrasonic Nozzle Humidifiers

Adjusting the Resonator

D

The resonator is adjusted at the factory for maximum atomization. However, the user (or the installer) can adjust the width of the fog pattern if desired.

Moving the resonator closer to the sprayer will widen the pattern. Moving the resonator further from the sprayer will narrow the pattern.

In order to adjust the resonator;

1. Loosen screw “A” 2. Move the resonator a few millimeters in or out depending on the desired Pattern

changing the distance “D” from the sprayer. 3. After making an adjustment be sure the resonator tip is inline with the hole in the

sprayer by loosening screw “B” (see drawing “C” below).

Resonator

A

B

Hole In Sprayer

Resonator

View Of Nozzle ( Sprayer End)

C

D

5

Fog Pattern

Page 6: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

FogSystem Humidifiers H

umidity Source Quality, Selection, Support

BUS Ultrasonic Nozzles

Typical In-Duct & In-Air Handler Applications

BUS Nozzles Mounted on Nozzle Bar

Drain

Note: Not To Scale

Air/Water Control Lines

Supply Air

Water

Control Cabinet

208/240 VAC

Humidistat

Air Duct

Air Flow

Shown are the Main Co

Air /WaterManifold

mponents of a BUS Nozzle Humidifier System

6

Page 7: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

ULTRASONIC NOZZLE (BUS) CAPA Water Flow As A Function Of Air Pressure With C

0

5

10

15

20

25

30

25 33 40 47 55 62 69 76 84 91 99 105

AiPress

(ps

2943.58

72.87

Water Flow Lbs./Hour

Air Pressure (psi)

29 psi

43.5 psi

58 psi

7

CITY CHART

onstant Water Pressure

113 120 128 134 141 148 152

Water Pressure(psi)/Air Consumption (CFM)

r ure i) 14.5 29 43.5 58 72.5

2.45 2.75

2.85 3.1

3.5

Page 8: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

H umidity Source

Quality, Selection, Support

W351 Modular Electronic Proportional Humidity Sensor/Controller

With Digital Display Maximum Flexibility Remote Sensor Modular Construction Remote Display Proportional Control Remote Set Point

The W351 Electronic Controller and Humidity Sensor is designed to be used where electronic sensitivity is desired, for close tolerance humidity control, or for installations where the display or set point adjustment must be remotely located.

Sensor

Controller & Power Module

D

Applications

computer rooms clean rooms pharmaceutical manufacturing staged cooling & humidification schools hospitals laboratories office buildings photo processing paper storage printing plants bakeries

The WintegralVDC anequippeconstan10 to range o

Out

0 toVDC and

4 to 20 mA 10 to

8

igital Display (Optional)

W351 Electronic Humidity Proportional Control

351 is an electronic proportional plus humidity control with analog 0 to 10 d 4 to 20 mA outputs. The W351 is also d with three user-selectable integration ts, as well as a wide set point range of 90% RH and an adjustable throttling f 2 to 20%RH.

put Set Point Range

Throttling Range

10

Features: humidification and/or dehumidification adjustable differential and set point surface or DIN rail mounting no wiring between modules

90% RH 2 to 20% RH

Page 9: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

FogSystem Ultrasonic Nozzle Humidifiers

W351P PROPORTIONAL CONTROLLER & ELECTRONIC SENSOR

Notes: 1. 0 to 10 Volt wiring shown 2. Controller also accepts 4-20mA 3. De-humidification stages available 4. Initial settings: Set point: 50% Minimum output: 0 Throttling range: 10% Integration switches: #2 “on” Others “off” Operation mode: Reverse 5. Set S2, S3, and P-13 on Control Panel Prop. Board as sown here:

S2 On S3 P13 1 2 3 4 Off 1 2 3 4

Ground

Model “BUS” Nozzle Control Cabinet

Air Flow Switch

S + 9 8 7 6 5 4 20 19 18 3 2 1

208-240 VAC Power In

0 – 10 V Sensor

PWROUT COM

Power Module Y350R

Digital Display D351

Controller W351P

VD

C

SE

N

CO

M

V

9

Page 10: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

H umidity Source

Quality, Selection, Support

Controller W351

Sequence of Operation

Humidity controller (W351) powered by transformer (Y350) senses space humidity via room the sensor. (Example: Set point of 45% RH and differential at 4%RH) On drop in humidity to 41% RH W351 closes the contact between COM & NO to start the humidifier. As the humidity increases to 45% W351 opens the circuit and stops the humidifier. The digital display module (D351) shows continuous readout of space humidity.

Cover Screws (Qty 4)

Operation Mode Jumper Positions Dehumidification Humidification

Relay

Modular Connector

Cabin

NC COM NO

Sensor

Set Point Dial

Differential Potentiometer Set on 4% RH

COM

VDC SEN

COM PWR OUT

9 8

FogSystem Humidifiers

W351 Wiring Diagram – ON/OFF Control

Digital Display D351

Power Module Y350R

Adjustments W351A

1. Remove the W351 cover by loosening the four captive cover screws.

2. Set the operation mode jumpers to the desired mode of operation (vertically for humidification).

3. Adjust the differential potentiometer to the desired setting. Clockwise increases differential.

4. Replace the cover and adjust the set point dial to the desired level.

5. If using the D351 display, press and hold the set point button while rotating the set point dial for most accurate settings.

Set Point Button

Display Window

GROUND

et Terminal Block

7 6 5 4 3 2 1

208-240 VAC

120/240 VAC

10

Page 11: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

SUGGESTED SPECIFICATIONS Humidity Source FOG-SYSTEM Humidifier

MODEL “BUS” ULTRASONIC HUMIDIFIERS

1.0 GENERAL. Humidifiers shall be Humidity Source Fog-System Model “BUS” compressed air and water ultrasonic nozzle type humidifiers. Humidifiers shall be capable of producing extremely fine , micron sized water particle mist for humidification from ordinary tap water, softened or not softened, de-mineralized, de-ionized, or reverse osmosis water. 2.0 OPERATION. The ultrasonic nozzle shall be able to accommodate water supplied under normal building water pressure and compressed air to atomize water by directing a high velocity stream of water at a tuned resonating target. The impact of this water stream causes the target to vibrate ultrasonically, breaking up the oncoming water stream into a fog like mist. The resulting partial size shall have arithmetical mean of 1.5 microns in diameter. 3.0 COMPONENTS. The main components of the humidifier system shall consist of ultrasonic (BUS) nozzles, pre-mounted nozzle bar, system control cabinet, air and water manifold and a relative humidity sensor. Optional components are modular humidity sensor, controller and digital display units. Air compressors, air and water mains, external tubing and fittings are to be supplied by others. 4.0 ULTRASONIC NOZZLES. 4.1 The nozzles shall be the Humidity source Fog-System Model “BUS” ultrasonic nozzle. Nozzles shall be constructed of all type 304 stainless steel body and stainless steel ultrasonic resonator. Nozzles shall be equipped with compressed air and water fittings and a separate connection port, with fitting, for the internal, fail-safe, water shut-off valve which shuts off water flow to the nozzle atomizer in the event of a compressed air failure. During normal nozzle shut down, the control cabinet will shut off water first, followed by short air purge time to clear the nozzle of residual water. This insures a “no drip” shut down. 4.2 All model “BUS” Fog-System ultrasonic nozzles shall be factory supplied on pre-mounted nozzle bars with all air and water tubing pre-installed for fast and easy installation. 5.0 AIR AND WATER MANIFOLD 5.1 The air and water manifold shall contain all valves, pressure regulators, pressure gauges, and a water check valve necessary for the proper operation of the system. The manifold shall receive air and water through respective filters and respond to control cabinet signals by regulating air and water flow to the

11

Page 12: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

nozzles. Regulation will be either on and off or modulated depending on the type of controller employed. 5.2 All valves, regulators, check valves and gauges shall mounted and pre-piped on a stainless steel mounting plate, pre-punched for easy installation. 5.3 Air and water filtration shall be supplied by 10 micron filters with housing and mounting brackets supplied with manifold. 6.0 CONTROL CABINET. 6.1 The control cabinet shall contain a state of the art electronics control board, all control function regulators, gauges, electric solenoids valves, on/off switches, and a terminal strip for electrical power and control connections. Air tubing connections shall be chrome plated brass push-in type fittings. The control cabinet shall be splash proof and rust proof with a rubber gasketed lockable access door, and be UL and CSA listed. 6.2 Control cabinets shall accept on-off or proportional control signals as specified in the controls section. 7.0 CONTROLS. The proper W351P modular type proportional + integral controller and sensor shall be supplied by the humidifier manufacturer. The controller module shall provide a 0-10 volt DC or 4-20 mA proportional control signal to the humidifier control cabinet. The controller, sensor and digital display modules can be mounted in the same location or remote from each other as indicated. Air flow switch model PC-301 and duct high humidity limit control model HC-201 shall be supply as required.

12

Page 13: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

H

umidity Source Quality, Selection, Support

NOZZLE HUMIDIFIER ACCESSORIES

P-825 WALL MOUNTED HUMIDISTAT Line voltage, on/off, wall mounted Humidstat with human hair element. The best sensing element available at a low cost and a good selection for most applications. Humidstats with electronic sensors should be used for applications where R.H. is above 65%. W351 ELECTRONIC HUMIDISTAT With a polymer sensor for high humidity, high sensitivity applications. The W351 features fast response time and close tolerance (+/- 2%). Available in on/off or proportional control, wall or duct mounted, and with or with out digital display. Display shows set point and actual R.H. at sensor. Sensor may be remote from controller and display. Water Filters WF-100 & WF-200 High quality filters which remove small particles from the water. The 5 micron cartridges will stop particles as small as yeast, fungi, pollen, flour, etc. By comparison, a human hair is about 100 microns in diameter. These filters are used to prevent the internal parts of the system from clogging, but do not remove dissolved minerals which may contaminate the air in the humidifier area. For this reverse osmosis is required. Commercial Reverse Osmosis Reverse osmosis (RO) uses semi-permeable membrane technology to remove and reject impurities in the water far beyond the capabilities of normal filtration. Unlike ordinary filters, RO removes even dissolved minerals and produces water quality equal to distilled water.

Humidity Source, LLC 90 Dayton Ave. Suite 58, Passaic, New Jerse

TEL 973-916-1001 FAX: 973-916-07

13

y 07055 70

Page 14: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

14

Page 15: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

H umidity Source

Quality, Selection, Support FS FogSystem

ALL STAINLESS STEEL COMPRESSED AIR NOZZLE HUMIDIFIERS

Water In

Air In

Power In 120 VAC

Line Volt Humidistat

Air & Water Manifold

Models

FS-1 17.6 lbs/hr.

Through

FS-15 264 lbs/hr.

For in-duct or open air applications, walk-in coolers,

paint spray booths, printing shops and other applications where an extremely fine mist is required.

90 Dayton AvTEL 973

Humidity Source, LLC e. Suite 58, Passaic, New Jersey 07055 -916-1001 FAX: 973-916-0770

15

Page 16: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

H

umidity Source Quality, Selection, Support

Type FS Ultrasonic Nozzle Humidifiers

The Ultrasonic Nozzle The Ultrasonic Nozzle uses compressed air to atomize water by directing a high velocity stream of water particles at a target. The force of impact causes the target to resonate or vibrate at a high frequency, this action breaks up the water particles into an extremely fine fog-like like mist. Water particles in the range of 5 to 12 microns are created by this method Ultrasonic nozzles may be used in open areas such as factories, print shops, walk-in coolers, warehouses, etc. where there is ample space to absorb and dissipate the moisture produced.

The FS System The FS nozzle humidifier system consists of an integrated Air and Water Manifold (see Fig. 1) designed to feed up to 15 ultrasonic nozzles.

Nozzles are constructed on stainless steel, and have no moving parts. No routine or scheduled maintenance in not required but a 10 micron water filter is recommended as a precaution against particles of sand or rust in the water.

Nozzles are supplied individually with a stainless steel mounting bracket or may be pre-mounted on a distribution bar complete with integral air and water lines. Only one air and one water connection is necessary when installing a nozzle bar. The FS manifold operates with a simple on-off type control, using a line voltage humidistat such as our P-825 or the more sensitive W351 electronic control humidistat with optional digital display.

Fig. 1

Air & Water Manifold

Nozzles On Mounting Bar

Particles So Fine They Stay Suspended An air operated, internal fail-safe valve cuts the flow of water to prevent dripping upon shutdown or in the event of loss of air pressure. Nozzle resonators are adjusted at the factory for optimum operation, however, field adjustment may be necessary due to movement during shipping or to adjust spray pattern to varying applications. The nozzles may be used with ordinary municipal tap water, soft water, well water, or de-ionized (DI), de-mineralized water or water produced by reverse osmosis (RO). See the Accessories page for information on humidistats, electronic controllers, digital displays, water filters, de-mineralizers, reverse osmosis units, and air compressors.

16

Page 17: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

FogSystem Ultrasonic Nozzle Humidifiers

Adjusting the Resonator

D

The resonator is adjusted at the factory for maximum atomization. However, the user (or the installer) can adjust the width of the fog pattern if desired.

Moving the resonator closer to the sprayer will widen the pattern. Moving the resonator further from the sprayer will narrow the pattern.

In order to adjust the resonator;

4. Loosen screw “A” 5. Move the resonator a few millimeters in or out depending on the desired Pattern

changing the distance “D” from the sprayer. 6. After making an adjustment be sure the resonator tip is inline with the hole in the

sprayer by loosening screw “B” (see drawing “C” below).

Resonator

B

C

AResonator

Hole In Sprayer

View Of Nozzle ( Sprayer End)

D

17

Fog Pattern

Page 18: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

FogSystem Ultrasonic Nozzle Humidifiers

Models FS-1 Thru FS-15

System Diagram-Including Air, Water, & Electrical Connections

Air In

Power In 120 VAC

Line Volt Humidistat

Water In

Air & Water Manifold

18

Page 19: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

Typical Installation Diagram

Models FS-1 To FS-15

Open Space Applications – On-Off Operation

BUS Nozzle

Humidistat Wall Mounted FS Manifold

Installation

1. Mount Air & Water Manifold in a convenient but protected location. 2. Mount the nozzle bar (or individual nozzles) on wall or suspended from ceiling. 3. Nozzles should be positioned so that they will not interfere with people or objects when in operation.

Usually high over head but not near ceiling. 4. The mist generated may project out 6 to 10 feet from nozzles. There should be no obstacle (beams,

pipes, ducts, etc.) within this area. 5. Connect ½” air and water lines to the input side of the manifold ( air and water filters are

recommended). Push-in fittings for 10mm (3/8”) OD plastic tubing are supplied with manifold. 6. Connect 10mm (3/8) OD tubing from manifold outlet to nozzles. If more than 50 ft., be sure to increase

the air line size to compensate for pressure drop. 7. Pressure regulators are preset at 75 psig for air and 60 psig for water. Higher or lower pressures are

OK, however, lower pressures result in lower output. Air pressure should be 15 psig higher than water pressure to start but may be changed if needed to adjust nozzle output.

8. Connect two wire, line volt, on-off humidistat to terminals 1 & 2 of electrical junction box on the manifold. Humidistat may be on any interior wall not subject to drafts or in the direct path of the mist. The optional electronic controller and digital display may be located outside the humidified room if desired.

9. Connect 120 VAC power and set the circuit breaker to the “on” position. 10. Raise humidistat set point to start the FS system.

90 Dayton AveTEL 973-9

Humidity Source, LLC . Suite 58, Passaic, New Jersey 07055 16-1001 FAX: 973-916-0770

19

Page 20: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

H

umidity Source Quality, Selection, Support

W351 Modular Electronic Proportional Humidity Sensor/Controller

With Digital Display

Sensor

Controller & Power Module

Digital Display (Optional)

Maximum Flexibility Remote Sensor

The W351 Electronic Controller and Humidity Sensor is designed to be used where electronic sensitivity is desired, for close tolerance humidity control, or for installations where the display or set point adjustment must be remotely located.

Modular Construction Remote Display Proportional Control Remote Set Point

Applications

computer rooms clean rooms pharmaceutical manufacturing staged cooling & humidification schools hospitals laboratories office buildings photo processing paper storage printing plants bakeries

The WintegralVDC anequippeconstan10 to range o

Out

0 toVDan

4 to 2

20

W351 Electronic Humidity Proportional Control

351 is an electronic proportional plus humidity control with analog 0 to 10 d 4 to 20 mA outputs. The W351 is also d with three user-selectable integration ts, as well as a wide set point range of 90% RH and an adjustable throttling f 2 to 20%RH.

put Set Point Range

Throttling Range

10

Features: humidification and/or dehumidification adjustable differential and set point surface or DIN rail mounting no wiring between modules

C d 0 mA

10 to 90% RH 2 to 20% RH

Page 21: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

FogSystem Humidifiers

W351 Wiring Diagram – ON/OFF Control

Controller W351A

Digital Display D351

Sequence of Operation

Humidity controller (W351A) powered btransformer (Y350) senses space humiroom the sensor. (For example, set poRH and differential at 4%RH) On drop in humidity to 41% RH W351Acontact between COM & NO to start the As the humidity increases to 45% W351circuit and stops the humidifier. The digmodule (D351) shows continuous readohumidity.

Co

O Mo P Dehumid Humid

Relay

ModulConne

NC COM NO

Sensor Differential Potentiometer Set on 4% RH

M

N

COM PWR OUT

Set Point Dial

Display Window

SE

VDC

CO

y dity via int of 45%

closes the humidifier.

opens the ital display ut of space

ver Screws (Qty 4)

peration de Jumper ositions

ification

ification

ar ctor

21

Power Module Y350R

Adjustments to W351A6. Remove the W351 cover by loosening the four

captive cover screws. 7. Set the operation mode jumpers to the desired mode

of operation (vertically for humidification). 8. Adjust the differential potentiometer to the desired

setting. Clockwise increases differential. 9. Replace the cover and adjust the set point dial to the

desired level. Note: Use the D351 Digital Display Module for the most accurate set point setting. If using the D351 display, press and hold the set point button while rotating the set point dial.

Set Point Button

120 VA Powe

120/240 VAC

FS System Junction Box C r

12

Page 22: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

H

umidity Source Quality, Selection, Support

NOZZLE HUMIDIFIER ACCESSORIES

P-825 WALL MOUNTED HUMIDISTAT Line voltage, on/off, wall mounted Humidstat with human hair element. The best sensing element available at a low cost and a good selection for most applications. Humidstats with electronic sensors should be used for applications where R.H. is above 65%. W351 ELECTRONIC HUMIDISTAT With a polymer sensor for high humidity, high sensitivity applications. The W351 features fast response time and close tolerance (+/- 2%). Available in on/off or proportional control, wall or duct mounted, and with or with out digital display. Display shows set point and actual R.H. at sensor. Sensor may be remote from controller and display. Water Filters WF-100 & WF-200 High quality filters which remove small particles from the water. The 5 micron cartridges will stop particles as small as yeast, fungi, pollen, flour, etc. By comparison, a human hair is about 100 microns in diameter. These filters are used to prevent the internal parts of the system from clogging, but do not remove dissolved minerals which may contaminate the air in the humidifier area. For this reverse osmosis is required. Commercial Reverse Osmosis Reverse osmosis (RO) uses semi-permeable membrane technology to remove and reject impurities in the water far beyond the capabilities of normal filtration. Unlike ordinary filters, RO removes even dissolved minerals and produces water quality equal to distilled water.

Humidity Source, LLC 90 Dayton Ave. Suite 58, Passaic, New Jer

TEL 973-916-1001 FAX: 973-916-0

22

sey 07055 770

Page 23: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

H

umidity Source Quality, Selection, Support

MODEL BV NOZZLE ATOMIZER HUMIDIFIER

VENTURI NOZZLE SYSYTEM

ALL STAINLESS STEELCOMPRESSED AIR NOZZLE ON-OFF OR PROPORTIONAL CONTROL

Model BV Venturi Nozzle

“VENTURI” ACTION DESIGN ELIMINATES WATER DROPS IN-SPACE APPLICATIONS INCLUDE:

Factories Warehouses Greenhouses Food Storage

90 Dayton A TEL 9

Humidity Source, LLC ve. BLDG 1-D, Passaic, New Jersey 07055 73-916-1001 FAX: 973-916-0770

23

Page 24: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

FogSystem Nozzle Atomizer In-Space Applications The Fog System of humidification uses low maintenance, self cleaning stainless steel nozzles to dispense a very fine mist produced by a combination of compressed air and water.

The Venturi Nozzle

The Venturi Nozzle uses com-pressed air to atomize water into a fine stream of particles which are quickly absorbed by the air. As the compressed air is ejected through the nozzle venturi, a vacuum is created which con-stantly draws water up from a reservoir located below the nozzle level. This design offers the added security in that if the compressed air fails water can-not be drawn from the reservoir making the nozzle truly drip less. Each nozzle will produce up to 20pounds of water mist per hour and can be installed in multiples for high humidity demand situations Venturi Nozzle Model BV

Quick Pack System Pre-assembled for quick installation, the Quick Pack consists of up to 25 Venturi Nozzles, air and water valves and a constant level water reservoir all pre-mounted on a single bar. The bar is designed to be suspended from a ceiling and needs only to be connected with plastic air and water lines from the control cabinet to be operational.

Quick Pack System

Control Cabinet The Fog System control cabinet regulates air and water pressure to the nozzles, turns the nozzles on or off in response to the humidistat and actuates the adjustable automatic cleaning cycle. Since nozzle water flow is regulated through air actuated valves, no water is present in the cabinet for electrical safety. Proportional control is a Control Cabinet lso available.

24

Page 25: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

VENTURI NOZZLES - MODEL “BV”

2

4

1 3

1. MAIN AIR INLET. Main atomizing air supply to nozzle. 2. CLEANING AIR. Air connection to power cleaning needle. 3. MAIN WATER INLET. Main water supply for atomizing. 4. CLEANING NEEDLE. Cleans the nozzle atomizing orifice.

OPERATION The model “BV” nozzle draws water by venturi action from the constant level water reservoir. This nozzle is also equipped with an automatic nozzle orifice cleaning needle, which is controlled by a timer in the control cabinet. During the cleaning cycle a piston is advanced and retracted positively by air pressure. This is unique in that there are no springs, which can weaken over time, to operate the cleaning mechanism. Piston driven air pressure powers the cleaning needle in both directions. Because of the venture action, with no water pressure applied to the nozzle, the BV is essentially drip less. This feature makes it ideal for use in printing plants, photo processing, electronics fabrication, and many other applications where water drops are not tolerable.

The BV nozzles are available with wall mounting brackets as shown, or pre-mounted nozzle bars with all air and water tubing lines in place for easy installation.

25

Page 26: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

FogSystem Humidifiers

Venturi Nozzle System Diagram

Model “BV” Venturi Nozzle

Cleaning Air

Air

Water

Constant Level Water Supply Reservoir

Overflow Water out 3/8”

Water In ½”

Air to Nozzle 3/8” Air In ½”

Air to Control Cabinet

Humidistat

Control Cabinet

Power

To Main Air Valve ¼”

Cleaning Air

26

Page 27: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

The Venturi FogSystem Control Cabinets

CONTROL CABINET TYPES:

Proportional ON/OFF - One Zone ON/OFF – Two Zone ON/OFF – Three Zone

Typical Connections

1. Power

2. Humidistat

3. Air In

6

2

7

8

9

Air & Water Man

Water

Air

27

1

4. Cleaning Air Out

5. Air to Main Air Valve

6. ON/OFF Switch

7. Green Light

ON when humidifying

8. Pressure Gauge

9. Adjustment Valve

45

3

ifold

To Constant Level Water Tank

Main Air Control From Cabinet

Air To Nozzles

Page 28: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

VENTURI NOZZLE CONSTANT LEVEL WATER RESERVOIR

Air Regulator control

Filled Weight 55 lbs.

7

8

8 11/16”

4

5

1 2 26”

13 7/16” 11 13/16”

WATER AIR

3

6

1 9/16”

5. Stainless Steel Mounting Bracket 6. Main Air Supply 7. Water Regulator & Gauge 8. Air Regulator & Gauge

1. 2. 3. 4.

Over Flow

Water Outlet (male 3/8”)

Main Water Supply (male 3/8”)

Constant Level Water Tank

28

Page 29: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

FogSystem Humidifiers

Venturi Nozzles (BV) Quick Pack Connection Diagram

Air In 1/2”

Water In 1/2”

Power

Humidistat

Control Cabinet

Air & Water Manifold

Constant Level Water Tank

Nozzles Pre-Mounted On Nozzle Bar

29

Page 30: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

BV NOZZLE “QUICK PACK” Pre-Assembled Venturi Type Nozzle Installation

1. Quick Pack Pre-mounted Bar 3. Humidistat 2. Control Cabinet 4. Constant Level Water Tank

Nozzle Bars Can Be Suspended From Ceiling or Wall Mounted

Air & Water Lines4

3

1

2

INSTALLATION 1. Place system components in their approximate positions. 2. Install nozzles bars as high as possible by suspending from ceiling or wall mounting.

Position so mist cannot strike beams, pipes, light fixtures, conduits, etc. 3. Install constant level water tank high on wall eight to sixteen inches below the nozzle bar.

See capacity chart for placement details. 4. Install air and water filters and connect compressed air and water service. 5. Install nozzle air and water manifold and connect to filters. 6. Mount control cabinet on wall and connect 230 volt, 100VA electrical power. 7. Run two 1/4" plastic tubes from control cabinet to manifold (air in & air out). 8. Run one 1/4" plastic tube from control cabinet to nozzle bar (cleaning cycle air). 9. Run one 3/8” plastic tube from manifold to nozzle bar air fitting (main air). 10. Run one 3/8” plastic tube from manifold to constant level water tank inlet fitting ( main

water). 11. Connect constant water tank outlet to water fitting on nozzle bar. 12. Mount humidistat & connect to control cabinet.

30

Page 31: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

0

5

10

15

20

25

1 2 4 8 12 16 20 24 28 32

90 PSI75 PSI60 PSI45 PSI

BV NOZZLE OUTPUT VS. AIR PRESSURE AND HEIGHT ABOVE CONSTANT LEVEL WATER TANK

Out

put

lbs.

/hr.

Wat

er V

apor

Height “H” Inches

Air Pressure 90 PSI 75 PSI 60 PSI 45 PSI

VENTURI NOZZLE (BV) CAPACITY CHART

31

Nozzle Level

Water Tank O

utput Level

H

Page 32: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

H

umidity Source Quality, Selection, Support

W351 Modular Electronic On/Off Humidity Sensor/Controller With Optional Digital Display

Maximum Flexibility Remote Sensor Modular Construction Remote Display On/Off, Step, or Proportional Remote Set Point

The W351A Electronic Controller and Humidity Sensor is designed to be used where electronic sensitivity is desired, for close tolerance humidity control, or for installations where the display or set point adjustment must be remotely located.

Sensor

Controller & Power Module

D

W351 Series Electronic Controllers Applications

computer rooms clean rooms pharmaceutical manufacturing staged cooling & humidification schools hospitals laboratories office buildings photo processing paper storage food storage printing plants bakeries humidors

W351A Electronic OnThe W351A Electronon/off humidity contrSingle-Pole, Double-LED indication. It feadehumidification moadjustable differentia

Set Point Range10 to 90% RH

Features:

humidification and adjustable differen surface or DIN rail no wiring between

32

igital Display (Optional)

Humidity Control – /Off ic Control is an electronic ol. The control output is a Throw (SPDT) relay with tures humidification and

des of operation and an l.

Differential 2 to 10% RH

/or dehumidification tial and set point mounting modules

Page 33: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

H umidity Source

Quality, Selection, Support

Sequence of Operation

Humidity controller (W351A) powered by transformer (Y350) senses space humidity via room the sensor. (Example: Set point of 45% RH and differential at 4%RH) On drop in humidity to 41% RH W351A closes the contact between COM & NO to start the humidifier. As the humidity increases to 45% W351 opens the circuit and stops the humidifier. The digital display module (D351) shows continuous readout of space humidity.

Cover Screws (Qty 4)

Operation Mode Jumper Positions Dehumidification Humidification

Relay

Modular Connector

Cabin

NC COM NO

Controller W351A

Sensor Differential Potentiometer Set on 4% RH

COM

VDC SEN

COM PWR OUT

9 8

Set Point Dial

FogSystem Humidifiers

Adjustments W351A

10. Remove the W351 cover by loosecaptive cover screws.

11. Set the operation mode jumpers toof operation (vertically for humidif

12. Adjust the differential potentiometesetting. Clockwise increases differ

13. Replace the cover and adjust the sdesired level.

14. If using the D351 display, press anbutton while rotating the set point daccurate settings.

GROUND

et Terminal Block

7 6 5 4 3 2 1

208-240

Digital Display D351

33

Display Window

Power Module Y350R

W351 Humidity Control System Wiring Diagram – ON/OFF Control

ning the four

the desired mode ication). r to the desired

ential. et point dial to the

d hold the set point ial for most

Set Point Button

VAC

120/240 VAC

Page 34: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

FogSystem Ultrasonic Nozzle Humidifiers

W351P PROPORTIONAL CONTROLLER & ELECTRONIC SENSOR

Notes: 5. 0 to 10 Volt wiring shown 6. Controller also accepts 4-20mA 7. De-humidification stages available 8. Initial settings: Set point: 50% Minimum output: 0 Throttling range: 10% Integration switches: #2 “on” Others “off” Operation mode: Reverse 5. Set S2, S3, and P-13 on Control Panel Prop. Board as sown here:

S2 On S3 P13 1 2 3 4 Off 1 2 3 4

Model “BUS” Nozzle Control Cabinet

Ground

208-240 VAC Power In

S + 9 8 7 6 5 4 20 19 18 3 2 1

Air Flow Switch

VD

C

SE

N

CO

M

V

Controller W351P

Digital Display D351

Power Module Y350R

PWROUT COM

0 – 10 V Sensor

34

Page 35: ULTRASONIC NOZZLE SYSTEM - Humidity Source LLC

H

umidity Source Quality, Selection, Support

NOZZLE HUMIDIFIER ACCESSORIES

P-825 WALL MOUNTED HUMIDISTAT Line voltage, on/off, wall mounted Humidstat with human hair element. The best sensing element available at a low cost and a good selection for most applications. Humidstats with electronic sensors should be used for applications where R.H. is above 65%. W351 ELECTRONIC HUMIDISTAT With a polymer sensor for high humidity, high sensitivity applications. The W351 features fast response time and close tolerance (+/- 2%). Available in on/off or proportional control, wall or duct mounted, and with or with out digital display. Display shows set point and actual R.H. at sensor. Sensor may be remote from controller and display. Water Filters WF-100 & WF-200 High quality filters which remove small particles from the water. The 5 micron cartridges will stop particles as small as yeast, fungi, pollen, flour, etc. By comparison, a human hair is about 100 microns in diameter. These filters are used to prevent the internal parts of the system from clogging, but do not remove dissolved minerals which may contaminate the air in the humidifier area. For this reverse osmosis is required. Commercial Reverse Osmosis Reverse osmosis (RO) uses semi-permeable membrane technology to remove and reject impurities in the water far beyond the capabilities of normal filtration. Unlike ordinary filters, RO removes even dissolved minerals and produces water quality equal to distilled water.

Humidity Source, LLC 90 Dayton Ave. Suite 58, Passaic, New Jerse

TEL 973-916-1001 FAX: 973-916-077

35