type overview - kele

4
Sensor Datasheet 22D..C..-51 www.belimo.com 22D..C..-51 • en-us • 2017-06-14 • Subject to change 1 / 4 Duct Air Quality Sensor To measure CO₂ only or integrated temperature, humidity and VOC in one device. 0 to 5/10 V outputs and an optional LCD display. See options below for integrated sensor options. Type Overview Type Output Signal Active CO₂ Output Signal Active VOC Output Signal Active Temperature Output Signal Active Humidity Output Signal Active CO₂/VOC Display Type 22DC-51 DC 0...5 V, DC 0...10 V - - - - - 22DCK-51 DC 0...5 V, DC 0...10 V DC 0...5 V, DC 0...10 V DC 0...5 V, DC 0...10 V - DC 0...5 V, DC 0...10 V - 22DCM-51 DC 0...5 V, DC 0...10 V DC 0...5 V, DC 0...10 V DC 0...5 V, DC 0...10 V - - - 22DCV-51 DC 0...5 V, DC 0...10 V DC 0...5 V, DC 0...10 V - - - - 22DTC-51 DC 0...5 V, DC 0...10 V - DC 0...5 V, DC 0...10 V - - - 22DTM-51 DC 0...5 V, DC 0...10 V - DC 0...5 V, DC 0...10 V DC 0...5 V, DC 0...10 V - - 22DTM-5106 DC 0...5 V, DC 0...10 V - DC 0...5 V, DC 0...10 V DC 0...5 V, DC 0...10 V - LCD Technical Data Electrical Data Power Supply DC 15...24 V, ±10%, 1.5 W Power Supply AC 24 V, ±10%, 2.9 VA Cable Entry cable gland PG11 Ø6 to 10 mm, with strain relief Ø6 to 8 mm, 1/2" conduit adapter included Functional Data Sensor Technology NDIR (non dispersive infrared) with stainless steel wire mesh filter, dual channel calibration Output Signal Active Note output DC 0 to 5/10 V with jumper adjustable voltage output: min. 10 kΩ load Display LCD, measured values: CO₂, temperature, rH, VOC Media air Measuring Data Measured Values CO₂ VOC mix CO₂/VOC temperature relative humidity Measuring Range CO₂ 0 to 2000 ppm Measuring Range Humidity 0 to 100% RH Measuring Range Temperature Settings 32°F to 120°F [0°C to 50°C] Accuracy CO₂ ±75 ppm; >750 ppm: ±10% of measuring value Accuracy Humidity ±2% between 10 to 90% RH @ 70°F [21°C] Accuracy Temperature ±1% of measuring range @ 70°F [21°C] Operating Condition Air Flow min. 1 ft/s [0.3 m/s] max. 33 ft/s [10 m/s]

Upload: others

Post on 03-Oct-2021

5 views

Category:

Documents


0 download

TRANSCRIPT

Sensor Datasheet 22D..C..-51

www.belimo.com 22D..C..-51 • en-us • 2017-06-14 • Subject to change 1 / 4

Duct Air Quality Sensor

To measure CO₂ only or integrated temperature, humidity and VOC in one device. 0 to 5/10 V outputs and an optional LCD display. See options below for integrated sensor options.

Type Overview

Type Output Signal Active CO₂

Output Signal Active VOC

Output Signal Active

TemperatureOutput Signal

Active HumidityOutput Signal

Active CO₂/VOC Display Type

22DC-51 DC 0...5 V, DC 0...10 V

- - - - -

22DCK-51 DC 0...5 V, DC 0...10 V

DC 0...5 V, DC 0...10 V

DC 0...5 V, DC 0...10 V

- DC 0...5 V, DC 0...10 V

-

22DCM-51 DC 0...5 V, DC 0...10 V

DC 0...5 V, DC 0...10 V

DC 0...5 V, DC 0...10 V

- - -

22DCV-51 DC 0...5 V, DC 0...10 V

DC 0...5 V, DC 0...10 V

- - - -

22DTC-51 DC 0...5 V, DC 0...10 V

- DC 0...5 V, DC 0...10 V

- - -

22DTM-51 DC 0...5 V, DC 0...10 V

- DC 0...5 V, DC 0...10 V

DC 0...5 V, DC 0...10 V

- -

22DTM-5106 DC 0...5 V, DC 0...10 V

- DC 0...5 V, DC 0...10 V

DC 0...5 V, DC 0...10 V

- LCD

Technical DataElectrical Data Power Supply DC 15...24 V, ±10%, 1.5 W

Power Supply AC 24 V, ±10%, 2.9 VACable Entry cable gland PG11 Ø6 to 10 mm, with strain

relief Ø6 to 8 mm, 1/2" conduit adapter included

Functional Data Sensor Technology NDIR (non dispersive infrared) with stainless steel wire mesh filter, dual channel calibration

Output Signal Active Note output DC 0 to 5/10 V with jumper adjustablevoltage output: min. 10 kΩ load

Display LCD, measured values: CO₂, temperature, rH, VOC

Media airMeasuring Data Measured Values CO₂

VOCmix CO₂/VOCtemperaturerelative humidity

Measuring Range CO₂ 0 to 2000 ppmMeasuring Range Humidity 0 to 100% RHMeasuring Range Temperature Settings 32°F to 120°F [0°C to 50°C]

Accuracy CO₂ ±75 ppm; >750 ppm: ±10% of measuring value

Accuracy Humidity ±2% between 10 to 90% RH @ 70°F [21°C]Accuracy Temperature ±1% of measuring range @ 70°F [21°C]Operating Condition Air Flow min. 1 ft/s [0.3 m/s]

max. 33 ft/s [10 m/s]

Sensor Datasheet 22D..C..-51

www.belimo.com 22D..C..-51 • en-us • 2017-06-14 • Subject to change 2 / 4

Materials Cable Gland PA6, blackHousing cover: lexan, Belimo orange NCS S0580-

Y6ORbase: lexan, Belimo orange NCS S0580-Y6ORseal: 0467 NBR70, black

Probe Material PA6, blackSafety Data Ambient Humidity 85% RH non-condensing

Ambient Temperature 32°F to 120°F [0°C to 50°C]Medium Temperature 32°F to 120°F [0°C to 50°C]Operating Condition Air Flow min. 1 ft/s [0.3 m/s]

max. 33 ft/s [10 m/s]Protection Class IEC/EN III safety extra-low voltage (selv)Protection Class UL UL Class 2 SupplyCertification IEC/EN IEC/EN 60730-1Certification UL pendingDegree of Protection IEC/EN IP65Degree of Protection NEMA/ UL NEMA 4XQuality Standard ISO 9001Weight 0.26 lbs

Safety NotesThe installation and assembly of electrical equipment should only be performed by authorized personnel.The product should only be used for the intended application. Unauthorized modifications are prohibited! The product must not be used in relation with any equipment that in case of a failure may threaten, directly or indirectly, human health or life or result in danger to human beings, animals or assets. Ensure all power is disconnected before installing. Do not connect to live/operating equipment.Please comply with • Local laws, health & safety regulations, technical standards and regulations • Condition of the device at the time of installation, to ensure safe installation • This data sheet and installation manual

RemarksAll gas sensors are subject to drift caused by components, resulting in regular re-calibration or replacement units. However the dual channel technology integrates automatic self-calibration technology vs common used ABC-Logic sensors. Dual channel self-calibration technology is ideally suited for applications operating 24/7 hours such as hosiptals or other commerical applications. Manual calibration is not required.

Accessoriesmounting flangecable gland nut conduit 1/2" NPT

Optional Accessories Description Typemounting flange for duct humidity and CO₂ sensor A-22D-A34

Information Self-Calibration Feature CO₂

Scope of Delivery

Sensor Datasheet 22D..C..-51

www.belimo.com 22D..C..-51 • en-us • 2017-06-14 • Subject to change 3 / 4

Wiring Diagram

Wiring diagram for 22DC-..1, 22DTC-..1

① Status LED

Sensor Datasheet 22D..C..-51

www.belimo.com 22D..C..-51 • en-us • 2017-06-14 • Subject to change 4 / 4

Dimensions