transformer protections

Upload: ramesh-cherukuri

Post on 03-Apr-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 Transformer Protections

    1/41

    4/11/20

    TRANSFORMER

    PROTECTIONS

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

    http://www.docudesk.com/http://www.docudesk.com/
  • 7/28/2019 Transformer Protections

    2/41

    4/11/20

    The Types of faults that the transformers are

    subjected to are classified as:

    INTERNAL FAULTS

    EXTERNAL FAULTS

    ( THROUGH FAULTS)

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    3/41

    4/11/20

    INTERNAL FAULTS

    FAULTS ARISING IN THE TRANSFORMER ITSELF

    ELECTRICAL FAULTS: Faults which cause

    immediate serious damage such as

    1. Phase to earth fault

    2. Phase to phase faults on HV or LV windings

    3. Short circuit between turns on HV and LV

    winding (inter turn faults)

    4. Problem in tap changer gear

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    4/41

    4/11/20

    INCIPIENT FAULTS: Which are initially minor

    faults, causing slowly developing damage,

    such as1. Poor electrical connection of conductors

    2. Breakdown of insulation of laminations, core

    bolt faults, clampings.

    3. Coolant failure

    4. Continuous uneven load sharing betweentransformers in parallel causing overheating

    due to circulating current.

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    5/41

    4/11/20

    EXTERNAL FAULTS (through faults)

    The faults in the system to which the

    transformer is connected Due to external faults (like phase-phase, phase

    to earth) the effect is excessive over currentand electromagnetic stresses proportional tosquare of short circuit current.

    1. Short circuits: Phase to phase, phase to earth

    2. High Voltage disturbance3. High Frequency disturbance

    4. Earth faults

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    6/41

    4/11/20

    PROTECTION PRINCIPLE

    1. Circuit breaker

    2. Relay

    3. Trip coil of C.B

    5.Battery

    6.Relay contacts

    7.Bus bars

    8.Current T/F9.Pilot-wires

    a.Aux.switch of C.B

    x.Protected Power T/F

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    7/41

    4/11/20

    THE FOLLOWING RELAYS ARE EMPLOYED TO PROTECTTHE TRANSFORMER AGAINST DIFFERENT FAULTS

    1. Over load

    2. Over current3. Over voltage

    4. Restricted Earth Fault

    5. Differential protection

    6. Buchholz relay

    7. Pressure relief value (PRV)

    8. Winding temperature

    9. Oil temperature10. OLTC buchholz (oil surge relay)

    11. Over fluxing

    12. Over/Under frequency

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    8/41

    4/11/20

    OVER LOAD

    This protection is required for continuous over load ofthe transformer

    Protection is based on measurement of windingtemperature which is measured by thermal imagetechnique.

    Thermal sensing element is placed in small pocketlocated near the top transformer tank in the hot oil. Asmall terminal of one phase is also located in thispocket and produced a local temp, rise, similar to thatof main winding and proportional to copper losses,

    above general temp of oil. Winging temperature high alarm/trip is provided

    through mercury switches in the winding temp,indicators.

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    9/41

    4/11/20

    OVER LAOD PROTECTION The permissible overload and their duration

    depends upon the type of cooling andinsulation class of transformer. Higheroverloads are permissible for a shorterduration.

    Hence for most of the transformers, overloadprotection is generally arranged to initiatealarm.

    Overload % 125 150 175 200 300

    Duration

    (minutes)

    125 45 15 10 1

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    10/41

    4/11/20

    THERMAL OVER HEATING PROTECTION

    Thermo couples or RTD are kept near each

    winding to detect the temperature. When thetransformer temperature increases cooling

    system comes in to picture.

    Fans get ON : 60 0C OFF : 50 0C

    Alarm : 90 0C

    Trip : 104 0C

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    11/41

    4/11/20

    OVER CURRENT

    This protection is required for short circuit

    faults and earth faults IDMT relays should be chosen

    Instantaneous trip facility for high speedclearance of terminals short circuit should beprovided

    Setting depends on transformer reactance or

    percentage impedance, faults MVA. Setting of over current relays can be slightly

    higher than rated full load current (say 120percent of FL) with proper discrimination.

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    12/41

    4/11/20

    EARTH FAULT PROTECTIONThis protection is required for earth faults

    Combined over current and earth fault protection

    (un-restricted earth fault)

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    13/41

    4/11/20

    The increase in current of phases causes correspondingincrease in respective secondary currents. The secondarycurrent flows through respective relay units. Very oftenonly two phase relays are provided instead of three,

    because in case of phase faults current in at lease any twophases must increase. Hence two rely units are enough.The earth fault relay is residually connected

    Over current and Earth fault protections are used as a mainprotection for medium transformers where differentialprotection is not provided. Differential protection isgenerally uneconomical for power transformers below 1MVA. In such cases, over current protection is employed asmain protection against phase faults. For transformersabove 1 MVA, if differential protection is used as a mainprotection, over current protection is used in addition, as abackup for sustained through faults. Earth fault protectionis provided in addition to phase fault protection.

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    14/41

    4/11/20

    RESTRICTED EARTH FAULT PROTECTION

    Transformer earth fault protection should notoperate for faults beyond the transformerprotection zone. This is ensured by the restrictedearth fault protection. This protection operateson the principle of Kirchoofs law and requiresCTs of identical ratio and ratings as the phasesand neutral earth connection. For external earthfault, the associated CTs have dissimilar polaritiesforming a series connection. Thus, the resulting

    current through the relay is negligible. Forinternal fault, however, the CTs have similarpolarities, forming a parallels connection, thisadding up the current in the relay branch. Thisensures positive operation of the relay.

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    15/41

    4/11/20

    RELAY DOES NOT OPERATE FOR EXTERNAL EARTH FAULT

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    16/41

    4/11/20

    RELAY OPERATES FOR INTERNAL FAULT

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    17/41

    4/11/20

    EARTH FAUALT PROTECTION

    of transformers feeding through cables by zero

    sequence relay (core balance currenttransformer)

    In absence of an earth fault in the transformeror the supply cable, the current in thesecondary of zero sequence CT is negligible.Under balanced load and without earth fault

    Ir = (Ia + Ib + Ic ) = 0 During tan earth fault (Ia + Ib + Ic ) 0 flux

    in the core 0

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    18/41

    4/11/20

    CORE BALANCE CT

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    19/41

    4/11/20

    DIFFERENTIAL PROTECTION

    This protection is also for internal faults of the transformerand responds to the vector difference between two

    similar quantities. Two basic requirements that the differential relay

    connections are to be satisfied are:

    It must not operate for external faults It must operate for internal faults

    As on load tap change facilities are invariably provided inthe grid transformer may departure from the nominal tapposition will result in spill currents in the relay circuits.

    Further the CTs are often of different types and havedissimilar magnetization characteristics, again resulting inspill current during heavy through fault conditions.

    To avoid unwanted relays operation under the above twoconditions a percentage bias differential relays is used.

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    20/41

    4/11/20

    DIFFERENTIAL PROTECTION

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    21/41

    4/11/20

    DIFFERENTIAL PROTECTIONSTAR/STAR TRANSFORMER

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    22/41

    4/11/20

    DIFFERENTIAL PROTECTIONDELTA/STAR TRANSFORMER

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    23/41

    4/11/20

    The current flowing through the operating coil of the relayshould be nearly zero during normal operating conditionsand when external short circuit occurs.

    While setting the differential relay on a transformer, the( mismatch) current through differential element at normaltap and positive and negative extreme taps are to becomputed . Differential element pickup setting and/ orbias setting is adopted based on maximum percentagemismatch adding some safety margin.

    In this connection the CT secondarys are connected instar or delta and pilot wires are connected between the CTsof each end. The CT connections and CT ratios are such

    that currents fed into the pilot wires from both the endsare equal during normal conditions and for through faults.During the internal faults such as phase to phase or phaseto ground, the balance is disturbed

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    24/41

    4/11/20

    The out of balance current (I1- I2) flows throughthe relay operating coils (O.C). To avoidunwanted operation on through faults,

    restraining bias coils are provided in series withpilot wires. The ampere-turns provided bias coilor restraining coil or proportional to (I1- I2)/2, I1and I2 are vectors. Three sets of CTs primaries areconnected on primary side and 3 sets onsecondary side. CT secondarys on STAR side ofmain transformer are connected in DELTA , CTsecondarys on DELTA side of main transformerare connected in STAR. This ensures correct flowof circulating currents in pilot wires.

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    25/41

    4/11/20

    COMBINED DIFFERENTIAL PROTECTION

    for Generator Main Transformer

    (Overall differential)The zone of combined differential

    protection may include generator statorwinding, main step up transformer and Unitauxiliary transformer. In addition to normaldifferential protection of generator, overall

    biased differential protection relay isconnected to protect the unit. This is asupplementary protection for individualdifferential protection of the generator.

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    26/41

  • 7/28/2019 Transformer Protections

    27/41

    4/11/20

    OVER VOLTAGE PROTECTION

    Two stage protection is provided. Thedelayed trip is set at 110 percent of the rated

    voltage with two second time delay and

    Instantaneous setting is kept at 115-120

    percent of the rated voltage. During voltage

    fluctuations the AVR (Automatic Voltage

    Regulator ) will care to avoid over voltagecondition if fluctuations are within its

    operating limits (for generator transformers).

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    28/41

    4/11/20

    SURGE ARRESTER PROTECTIONSurge arresters (lighting arresters) are connected

    between phase and earth near the terminal of each

    phase of the transformer. The surge arrester providesprotection against Lightning surges and switchingsurges. Lightning surges occur due to lightningstrokes on transmission line conductor. The surgetravels up to transformer and can damage thetransformer winding insulation. The surge arresterintercepts the surge and diverts it to the earth and

    protects the transformer. Switching surges originatein the system while opening of inductive currentsand closing of transmission lines. The surge arresterintercepts the switching surge and diverts it to the

    earth and protects the transformer.

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    29/41

    4/11/20

    POWER FREQUENCY TEMPORARY OVERVOLTAGEPROTECTION

    When load or line is thrown off (switched off )the power frequency (50 Hz) overvoltage occursat the bus bars of receiving substation. The onload tap changers act and bring down the voltageto permissible value. If overvoltage does notdrop in short time the transformers may fail. Thep.f voltage above 1.1 per unit is harmful totransformer. Inverse Definite Minimum Time

    over voltage relay is connected to secondary ofprotective bus PT. This relay is arranged to tripthe circuit breakers feeding the transformersinstantaneously for overvoltage of 1.3 p.u. Forover voltages of 1.2 p.u time delay provided.

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    30/41

    4/11/20

    OVERFLUXING PROTECTIONThe magnetic flux in the transformer core is

    proportional to V/f, where V is the voltage and f is the

    frequency. With rated voltage = Vr and ratedfrequency fr the V/f ratio is Vr / fr = 1 p.u . Transformercore can tolerate the V/f ratio of 1.1 p.u for longduration without harm. If V/f ratio is higher than 1.1the condition of over fluxing arises. The core gets hotand core insulation is damaged. The core loss4esincreases. The transformer becomes hot. The overfluxing condition in generator transformers and unitauxiliary transformers if the generator excitation is

    increased before reaching synchronous speed. Overfluxing relay is connected in generator excitationsystem. This relay does not allow the excitationcurrent of generator till synchronous speedcorresponding to the rated frequency is reached.

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    31/41

    4/11/20

    Over fluxing can occur in transformers of generator unit. Thiscondition arises during abnormal operating conditions i.e heavy

    voltage fluctuations at lower frequency conditions. This condition is

    experienced by the transformer during heavy power swings,cascade tripping of the generator sets and HT line in the grid,

    interstate system separation conditions and due to AVR

    malfunctioning during start up or shutting down in case of

    generator transformers. The power frequency over voltage cause

    both stress on insulation and proportionate increase in the

    magnetizing flux inside the transformer due to which the iron losses

    are increased and the core bolts get maximum component of flux,

    thereby rapidly heating and damaging its own insulation and coil

    insulation. Reduction in frequency during high voltage fluctuation

    has the same effect.

    V/f over fluxing factor 1.1 1.2 1.25 1.3 1.4

    Duration of withstand

    limit (minutes)

    Contin

    uous

    2 1 0.5 0

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    32/41

    4/11/20

    BUCHHOLZ RELAYThe incipient faults in transformer tank below oil

    level actuate Buchholz relay so as to give an alarm. The

    arc due to fault causes decomposition of transformeroil. The product of decomposition contain more than70% of hydrogen gas. Which being light, rises upwardsand tries to go into the conservator, The Bnuchholzrelay is fitted in the pipe leading to the conservator.The gas gets collected in the upper portion of theBuchholz relay, thereby the oil level in the Buchholzrelay drops down. The float , floating in the oil in thebuchholz relay tilts down with the lowering oil level.

    While doing so the mercury switch attached to thefloat is closed and the mercury switch closes the alarmcircuit. Buchholz relay gives an alarm so that thetransformer can be disconnected before the incipientfault grows in to a serious one.

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    33/41

    4/11/20

    BUCHHOLZ RELAY

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    34/41

    4/11/20

    ARRANGEMENT OF BUCHHOLZ RELAY

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    35/41

    4/11/20

    PRESSURE RELIEF VALUE (PRV)This is different from rate of rise pressure relay.

    Pressure relief valve is mounted on transformer tank.It releases gas pressure to the atmosphere during

    1. High overload peaks

    2. Prolonged overloads

    3. Arcing faults within oil

    The PRV is spring loaded and has a seal seat. Whenpressure inside the tank increases above a certain

    value, the force on movable sub assembly exceeds thespring force and valve operates. The contacts areclosed. After release of PRV the valve may be resetmanually.

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    36/41

    4/11/20

    PRESSURE RELIEF VALUE (PRV)

    DURING NORMAL POSITION

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    37/41

    4/11/20

    PRESSURE RELIEF VALUE (PRV)

    DURING INTERNAL PRESSURE

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    38/41

    4/11/20

    OIL TEMPERATURE

    An oil thermometer, which is common with all oilfilled transformers, can be considered as a partiallyeffective protective device when equipped with alarmcontacts connected to give remote warning ofabnormally high oil temperature. Its location is suchthat it naturally monitors the hottest fluid that exists inthe transformer. The same thermo meter is often usedto start fan motors ON and OFF.

    WINDING TEMPERATURE

    The thermometer bulb is located in a pocket near

    the winding. The bulb is surrounded by hot circulatingoil. The bulb is also heated by a small heater connectedacross CT secondary . Thereby the heat given to thebulb is a function of load current as well as thetemperature of oil near winding.

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    39/41

    4/11/20

    PROTECTION CHART OF POWER TRANSFORMER

    Sl.

    No.

    ABNORMAL CONDITION PROTECTION REMARKS

    1. Incipient fault below oil level Buchholz relay (Gasactuated relay

    Buchholz relay fortransformers of rating 500

    kVA and above

    2. Large internal faults phase to phase, phase to

    ground

    1.Buchholz relay trips the

    circuit breaker

    2. Percentage differential

    Protection

    3.High speed high set over

    current relay

    Buchholz relay slow and

    less sensitive

    Percentage differential

    protection for

    transformers above 5

    MVA

    3. Saturation of Magnetic circuit 1.Overfluxing protection

    with

    voltage regulator

    2. Over voltage protection

    of

    Bus bars

    For generator transformer

    and unit auxiliary

    transformer

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    40/41

    4/11/20

    Sl.

    No.

    ABNORMAL CONDITION PROTECTION REMARKS

    4. Earth faults 1. Differential Protection

    and

    2. Earth fault relay in

    residually connected

    circuit

    For transformers of and

    above 5 MVA

    (a) Instantaneous

    restricted E/F

    Relay

    (b) Time lag E/F relay

    5. Through faults (External faults feeding through

    the transformer)

    1. Graded time lag over

    current relay

    2. HRC fuses

    Protection of transformers

    Small distribution

    transformers up to 500

    kVA

    6. Over loads 1. Thermal over load

    relays

    2. Temperature relays

    3. Over current relayswith

    inverse characteristic

    Fans started at certain

    temperature. Alarm and

    tripping actions later

    7. High voltage surges due to lightning switching 1. Horn gaps

    2.Surge arresters

    3.R.C surge suppressors

    Not favored for important

    transformers

    PDF Created with deskPDF PDF Writer - Trial :: http://www.docudesk.com

  • 7/28/2019 Transformer Protections

    41/41

    4/11/20