transformer protections in thermal power plant
TRANSCRIPT
-
8/13/2019 Transformer Protections in Thermal Power Plant
1/45
27 December 2013 PMI Revision 00 1
TransformerProtections
-
8/13/2019 Transformer Protections in Thermal Power Plant
2/45
27 December 2013 PMI Revision 00 2
Presentation outline
Need of transformerTypes of Transformers
Transformers AccessoriesMajor Transformers in Power Plants
Protection of transformers
-
8/13/2019 Transformer Protections in Thermal Power Plant
3/45
27 December 2013 PMI Revision 00 3
TRANSFORMERS
-
8/13/2019 Transformer Protections in Thermal Power Plant
4/45
27 December 2013 PMI Revision 00 4
-
8/13/2019 Transformer Protections in Thermal Power Plant
5/45
27 December 2013 PMI Revision 00 5
WHY TRANSFORMER TO OPTIMISE COST OF BULK TRANSMISSION
OF POWER FROM GENERATORS TO
CONSUMERS
REDUCTION IN TRANSMISSION LOSS
TO REDUCE OR INCREASE VOLTAGE IN AC
SYSTEM
ENABLES SAFE SUPPLY VOLTAGE TOCONSUMERS
ISOLATION OF TWO SYSTEMS FOR VOLTAGE
REGULATION
-
8/13/2019 Transformer Protections in Thermal Power Plant
6/45
27 December 2013 PMI Revision 00 6
IEC 60076-1
A static piece of apparatus with two or more windingswhich, by electromagnetic induction, transforms asystem of alternating voltage and current into another
system of voltage and current usually of differentvalues and at the same frequency for the purpose oftransmitting electrical power.
IEEE C57.12.80-2002
A static device consisting of a winding, or two or morecoupled windings with or without a magnetic core forintroducing mutual coupling between electricalcircuits.
Definition of Transformer as per Stds
-
8/13/2019 Transformer Protections in Thermal Power Plant
7/45
27 December 2013 PMI Revision 00 7
What are the Types of
Transformers Power transformers : Used in transmissionnetwork of higher voltages, deployed for step-up
and step down transformer application (400 kV,200 kV, 110 kV, 66 kV, 33kV,22kV)
Distribution transformers : Used for lowervoltage distribution networks as a means to end
user connectivity. (11kV, 6.6 kV, 3.3 kV, 440V,230V)
-
8/13/2019 Transformer Protections in Thermal Power Plant
8/45
27 December 2013 PMI Revision 00 8
Classifications
Transformers are adapted to numerous engineeringapplications and may be classified in many ways:
By power level:(from fraction of a volt-ampere(VA) to over a thousand
MVA), By application:(power supply, impedance matching, circuit isolation),
By frequency range:
(power, audio, radio frequency(RF)) By voltage class:(a few volts to about 765 kilovolts)
-
8/13/2019 Transformer Protections in Thermal Power Plant
9/45
27 December 2013 PMI Revision 00 9
Classifications
By cooling type:(air cooled, oil filled, fan cooled, water cooled (Natural/Forced) etc.)
By purpose:(distribution, rectifier, arc furnace, amplifier output, etc.).
By ratio of the number of turns in the coilsStep-up The secondary has more turns than the primary.Step-down The secondary has fewer turns than the
primary.
Connection :Single phase, Star / star , Star delta etc
-
8/13/2019 Transformer Protections in Thermal Power Plant
10/45
27 December 2013 PMI Revision 00 10
Cur ren t con duc to r s P r im ary& Seco nd ary Wind ing s Magn et ic f lux co nd uc to r -
Laminated Steel Core Insula t ionCool ingProtec t ionSup po r t ing acc ess or ies
Basic Components of aTransformer
-
8/13/2019 Transformer Protections in Thermal Power Plant
11/45
27 December 2013 PMI Revision 00 11
Tap Changer(s)-(On load/Off
load) Tank Radiators cooling fans, oil pumps, oil to
water heat exchangers (CoolingONAN / ONAF/ OFAF/ OFWFexternal coolers)
Bushings
Accessories & Auxiliaries
-
8/13/2019 Transformer Protections in Thermal Power Plant
12/45
27 December 2013 PMI Revision 00 12
-
8/13/2019 Transformer Protections in Thermal Power Plant
13/45
Protection
Objective: To quickly isolate a faulty section fromboth ends so that the rest of the system can functionsatisfactorily.
THE FUNCTIONAL REQUIRMENTS OF THE RELAY:
1. Reliability :2. Selectivity:3. Sensitivity:
4. Speed :
-
8/13/2019 Transformer Protections in Thermal Power Plant
14/45
ELECRICAL FAULT OPEN CIRCUIT FAULT SHORT CIRCUIT FAULT THROUGH FAULT INTERNAL FAULT INCIPIENT FAULT
27 December 2013 PMI Revision 00 14
-
8/13/2019 Transformer Protections in Thermal Power Plant
15/45
Important Elements:
Switch gear:
Circuit breaker bulk oil, minimum oil,SF6 ,air blast , vacuum etc. depending
on medium used for quenching the arc.Different operating mechanism such assolenoid, spring, pneumatic,hydraulics etc. are employed.
.
-
8/13/2019 Transformer Protections in Thermal Power Plant
16/45
Protection Gear:
27 December 2013 PMI Revision 00 16
Relays(current , voltage,
impedance, power , frequencyetc. based on operatingparameter, definite time ,
stepped etc. as per operatingcharacteristic , logic wisesuch as differential , over
fluxing etc.
-
8/13/2019 Transformer Protections in Thermal Power Plant
17/45
-
8/13/2019 Transformer Protections in Thermal Power Plant
18/45
27 December 2013 PMI Revision 00 18
-
8/13/2019 Transformer Protections in Thermal Power Plant
19/45
27 December 2013 PMI Revision 00 19
-
8/13/2019 Transformer Protections in Thermal Power Plant
20/45
27 December 2013 PMI Revision 00 20
-
8/13/2019 Transformer Protections in Thermal Power Plant
21/45
NORMS OF PROTECTION FOR EHV CLASS POWERTRANSFORMER
Voltage ratio &capacity
HV side LV side Common relays
11/132 KV GT 3-non-dir O/L +1-non-dir E/LRelay and/or standbyE/F + REF
--- Differential or overalldifferential, overflux,buchholz, OLTCbuchholz, PRV ,OT , WT
13.8/220 KV15.75/220 KV18/400 KV21/400 KVGenerator T/Fs
3-non-dir O/L + 1-non-dirE/L relay and/or standbyE/F + REF
220/6.6 KV Station T/Fs 3-non-dir O/L + 1-non-dirE/L relay and/or standbyE/F + REF
3-non-dir. O/L relays Differential, overallbuchholz, OLTCBuchholz, PRV, OT, WT
Gen-volt/6.6KV UAT 3-non-dir O/L relays 3-non-dir O/L relays Differential, overallbuchholz, OLTCBuchholz, PRV, OT, WT
POWER STATION
-
8/13/2019 Transformer Protections in Thermal Power Plant
22/45
SUBSTATION
132/33/11 KV upto8 MVA
3 O/L relays + 1E/L relay 2 O/L relays + 1 E/Lrelay
Buchholz, OLTCBuchholz, OT, WT
132/33/11KV above8 MVA and below 31.5MVA
3 O/L relays + 1 dir. E/Lrelay
3 O/L relays + 1 E/Lrelay
Differential , Buchholz,OLTC Buchholz, OT, WT
132/33 KV, 31.5 MVA &above
3 O/L relays + 1 dir.E/Lrelay
3 O/L relays + 1 E/Lrelay
Differential , Buchholz,OLTC Buchholz, PRV,OT, WT
220/33 KV, 31.5MVA &50MVA 220/132KV ,100MVA
3 O/L relay + 1 dir. E/Lrelay
3 O/L relays + 1 E/Lrelay
Differential , Buchholz,OLTC Buchholz, PRV,OT, WT
400/220KV 315MVA 3 directional O/L relays(with dir.. Highest) + 1dir. E/L relays. RestrictedE/F relay + 3 dir. O/Lrelays for action.
3 directional O/L relays(with dir.. Highest) + 1dir. E/L relays. RestrictedE/F relay
Differential , overflux,Buchholz, OLTCBuchholz, OT, WT andoverload (alarm) relay
-
8/13/2019 Transformer Protections in Thermal Power Plant
23/45
The following relays areemployed to protect the
transformer against internalfaults.
i. Buchholz Relays
ii.Differential Relays
iii.REF relays.
iv.Over fluxing relays
-
8/13/2019 Transformer Protections in Thermal Power Plant
24/45
27 December 2013 24
Buchholz Relay
-
8/13/2019 Transformer Protections in Thermal Power Plant
25/45
27 December 2013 PMI Revision 00 25
Buchholtz relay
-
8/13/2019 Transformer Protections in Thermal Power Plant
26/45
27 December 2013 PMI Revision 00 26
Alarm element Operates When a specified volume ofgas gets collected in Chamber during
Broken down core bolt insulation
Shorted Laminations
Bad Contacts
Overheating of winding parts
Trip element Operates by Oil surge in the event ofserious fault
Short Circuit between Winding Phases orwithin Windings
Puncture of Bushing
BUCHHOLZ PROTECTION
-
8/13/2019 Transformer Protections in Thermal Power Plant
27/45
-
8/13/2019 Transformer Protections in Thermal Power Plant
28/45
27 December 2013 PMI Revision 00 28
-
8/13/2019 Transformer Protections in Thermal Power Plant
29/45
27 December 2013 PMI Revision 00 29
Transformer connections :
- Delta/Starused in Generating stations forStep-up.
- Star/Deltaused in Receiving stations forStep-down
* All GTs are Delta/Star connected.
All Tie T/Fs are Star/Star connected.
-
8/13/2019 Transformer Protections in Thermal Power Plant
30/45
27 December 2013 PMI Revision 00 30
STAR / DELTA connection
STAR / STAR connection
-
8/13/2019 Transformer Protections in Thermal Power Plant
31/45
The relay is operative only for the internal faults of the transformerand thus fast operating time can be achieved.
-
8/13/2019 Transformer Protections in Thermal Power Plant
32/45
OTHER PROTECTIVE DEVICE PRESSURE RELIEF VALVE
WINDING TEMPERATURE
OIL TEMPRETURE
OLTC BUCHHOLZ LIGHTNINIG ARRESTER FIRE PROTECTION
27 December 2013 PMI Revision 00 32
-
8/13/2019 Transformer Protections in Thermal Power Plant
33/45
27 December 2013 PMI Revision 00 33
Accessories & AuxiliariesAccessories &
Auxiliaries
Oil Level Indicators Marshalling Box/Control
cubicle Oil Preservation Systems:
Conservators
gas sealed, BellowsBreathers
-
8/13/2019 Transformer Protections in Thermal Power Plant
34/45
27 December 2013 PMI Revision 00 34
SILICA GEL BREATHER
conservator
-
8/13/2019 Transformer Protections in Thermal Power Plant
35/45
27 December 2013 PMI Revision 00 35
Winding / Oil Temperature Indicator
-
8/13/2019 Transformer Protections in Thermal Power Plant
36/45
27 December 2013 36
Pressure Relief Device PRD)
-
8/13/2019 Transformer Protections in Thermal Power Plant
37/45
27 December 2013 PMI Revision 00 37
Different transformers in a power
Plant Generator Transformer (GT)
Station Transformer (ST)
Unit Auxiliary Transformer (UAT)Excitation TransformerNeutral Grounding Transformer
Auxiliary transformersTie / Auto transformer
-
8/13/2019 Transformer Protections in Thermal Power Plant
38/45
27 December 2013 PMI Revision 00 38
SPECIFICATION
STAGE -1 GT-VindhyachalRATED O/P 250MVARATED VOLT. (HV) 420KVRATED VOLT. (LV) 15.75KVRATED CURRENT(HV) 344ARATED CURRENT(LV) 9175AVECTOR GROUP Ynd11
-
8/13/2019 Transformer Protections in Thermal Power Plant
39/45
27 December 2013 PMI Revision 00 39
GENERATOR
7UA 7UB
SA SB
GT (3X200 MVA)
Unit Tx 21/11 K.V. (50 MVA)
IN THE EVENT OF UNIT TRIPPING AUTO CHANGEOVERFROM UT TO STATION WILL TAKE PLACE
-
8/13/2019 Transformer Protections in Thermal Power Plant
40/45
40
TESTING OF TRANSFORMER
THE FOLLOWING TESTS ARE GENERALLY PERFORMED ON THETRANSFORMER REFERENCE STANDARD : IEC 60076
ROUTINE TESTS
MEASUREMENT OF WINDING RESISTANCE
MEASUREMENT OF VOLTAGE RATIO, POLARITY AND CHECK OFVOLTAGE VECTOR RELATIONSHIP
MEASUREMENT OF NO-LOAD LOSS AND EXCITATION CURRENT
MEASUREMENT OF INSULATION RESISTANCE
SWITCHING IMPULSE VOLTAGE WITHSTAND TEST
LIGHTNING IMPULSE VOLTAGE WITHSTAND TEST
-
8/13/2019 Transformer Protections in Thermal Power Plant
41/45
27 December 2013 PMI Revision 00 41
ON LINE MONITORING EQUIPMENT ON TRANSFORMER
1. DGA to be monitored on all transformers periodically.2. Probable Reason of gas3. Arcing
CoronaOver HeatingPartial Discharge
4. Advance warning of developing faults5. Determining the improper use of units6. Status checks on new and repaired units7. Convenient scheduling of repairs8. Monitoring of units under overload
http://www.nttworldwide.com/faults.htmhttp://www.nttworldwide.com/faults.htmhttp://www.nttworldwide.com/faults.htmhttp://www.nttworldwide.com/faults.htmhttp://www.nttworldwide.com/faults.htmhttp://www.nttworldwide.com/faults.htmhttp://www.nttworldwide.com/faults.htmhttp://www.nttworldwide.com/faults.htmhttp://www.nttworldwide.com/faults.htmhttp://www.nttworldwide.com/faults.htmhttp://www.nttworldwide.com/faults.htmhttp://www.nttworldwide.com/faults.htmhttp://www.nttworldwide.com/faults.htmhttp://www.nttworldwide.com/faults.htmhttp://www.nttworldwide.com/faults.htm -
8/13/2019 Transformer Protections in Thermal Power Plant
42/45
GASES IN DGA 1. Corona a. In Oil H 2 b. In Cellulose H 2 , CO , CO 2
Oil Low temperature CH 4 , C 2H6 Oil High temperature C 2H4 , H 2 ( CH 4 , C 2H6 Cellulose Low temperature CO 2 ( CO ) temperature CO ( CO 2 ) In Arcing H 2, C 2H2 (CH 4, C 2H6, C 2H4)
27 December 2013 PMI Revision 00 42
-
8/13/2019 Transformer Protections in Thermal Power Plant
43/45
27 December 2013 PMI Revision 00 43
7. ON LINE MONITORING EQUIPMENT ON TRANSFORMERContd.
3. Acoustic PD measurement.
In case DGA results indicate the presence of high dischargesAcoustic PD measurement is done. Acoustic PD detector consists of sensor which can sense soundvibrations produced due to occurrence of discharges in oil. The sensor has pre-amplifier and filter circuit to eliminateenvironmental noise
4 Infrared thermographyWith the help of infrared thermo-vision camera, the thermo-image
of transformer is preparedThis scanning helps in detecting overheated zones, loose &corroded connection.
-
8/13/2019 Transformer Protections in Thermal Power Plant
44/45
27 December 2013 PMI Revision 00 44
OFF LINE MONITORING1. Frequency Response Analysis
Short circuit forces could move the winding.
Can also change winding inductance andcapacitance.
Conventional tests are not sensitive to windingmovement
Such changes can be effectively detected byFRA
.
-
8/13/2019 Transformer Protections in Thermal Power Plant
45/45
THANK YOU