    WHY GROUNDING IS REQUIRED?

    GROUNDING PLAYS A VITAL ROLE INPOWER SYSTEM OPERATION. EFFECTIVE

    GROUNDING IS NECESSARY FOR THEPROPER OPERATION AND CO-ORDINATION OF PROTECTION

    SCHEMES IN THE POWER SYSTEM ASWELL AS FOR PERSONNEL SAFETY.

  • 8/23/2019 Transformer Neutral Earthing

    3/12

    PURPOSE OF EARTHING

  • 8/23/2019 Transformer Neutral Earthing

    4/12

    GENERAL REQUIREMENTS

    LOW VALUE OF EARTH RESISTANCE.

    ACCEPTABLE SURFACE POTENTIALGRADIENTS

  • 8/23/2019 Transformer Neutral Earthing

    5/12

    INDIAN ELECTRICITY RULES 1956.

    IS: 3043/1966, 1987 : CODE OF PRACTICE

    FOR EARTHING.

    BS : CP 1013:1965

    CBI & P RECOMMENDATIONSIGRE APPLICATION GUIDE

    ANSI / IEEE STD.80/ 1961,1967,1986.

  • 8/23/2019 Transformer Neutral Earthing

    6/12

    TYPES OF EARTHING SYSTEM EARTHING.

    PROTECTIVE EARTHIN

  • 8/23/2019 Transformer Neutral Earthing

    7/12

    SYSTEM EARTHING

    EFFECTIVELY EARTHED SYSTEM(Xo / X1) < 3

    (Ro / X1) < 1

    Xo= ZERO SEQUENCE REACTANCE.

    X1= POSITIVE SEQUENCE REACTANCE.

    Ro= ZERO SEQUENCE RESISTANCE.

    UNDER THE FAULT CONDITIONS THE VOLTAGES

    OF THE OTHER TWO HEALTHY PHASES WILLNEVER BE MORE THAN 80% OF THE LINE TO LINEVOLTAGE OF THE SYSTEM. THIS IS ALSO CALLEDCO-EFFICIENT OF EARTHING.

  • 8/23/2019 Transformer Neutral Earthing

    8/12

  • 8/23/2019 Transformer Neutral Earthing

    9/12

  • 8/23/2019 Transformer Neutral Earthing

    10/12

    BENEFITS Improved reliability

    Improved fault protection

    Fewer Faults.

    Simplification of locating faults.

    Greater Safety

    Limitation of transient over voltages.

    Lower cost and less maintenance.

  • 8/23/2019 Transformer Neutral Earthing

    11/12

    Function of Earthing

    Transformers Holding the neutral shift within limits.

    Permitting the circulation of unbalanced load current

    in the neutral. To limit the current during ling to earth fault.

    To earth the system.

    To provide single phase line to neutral load.

    Can be used with resistance / reactance / arc

    suppression coil.

  • 8/23/2019 Transformer Neutral Earthing

    12/12

    SPECIFICATION (IS:3151)Voltage : Line to Line voltage of the system.

    Current: The maximum neutral current.

    Time : 10 sec for protection 60sec for feeders.

    Reactance: This quantity is a function of thepositive sequence short circuit reactance of the

    power system or x1