tl parameters using tower type pf

14
Page 1 of 14 How to get transmission line parameters using Tower Type from DIgSILENT PowerFactory 1. Create a new project called Exp3, use 60 Hz for frequency 2. Open the data manager and select the Active Project 3. Push on the New Object icon 3.1. In Elements, select Types for Net Elements, and in Element, choose Tower Type (TypTow), then OK.

Upload: sarah-jenkins

Post on 04-Jan-2016

227 views

Category:

Documents


1 download

DESCRIPTION

Transmission line parameters calcultaion using typetower on PowerFactory

TRANSCRIPT

Page 1: TL Parameters Using Tower Type PF

Page 1 of 14

How to get transmission line parameters using Tower Type from DIgSILENT PowerFactory

1. Create a new project called Exp3, use 60 Hz for frequency 2. Open the data manager and select the Active Project

3. Push on the New Object icon 3.1. In Elements, select Types for Net Elements, and in Element, choose Tower Type (TypTow), then

OK.

Page 2: TL Parameters Using Tower Type PF

Page 2 of 14

3.2. The following window will be displayed where we will input all the required data.

4. Let’s start by filling out Name, Nominal Frequency, Number of Earth Wires, Number of Line Circuits,

Transposition, Input Mode, and Earth Conductivity as follows:

Page 3: TL Parameters Using Tower Type PF

Page 3 of 14

5. Now, let’s continue with Conductor Types of Line Circuits

5.1. Right click on Conductor Types TypCond of Circuit 1 and choose Select Element/Type…

5.2. The following screen will be displayed where one can create a new conductor type.

Page 4: TL Parameters Using Tower Type PF

Page 4 of 14

5.3. To do so, click on New Object where one can input the conductor data for each phase

5.4. Fill out the conductor type as follows:

Page 5: TL Parameters Using Tower Type PF

Page 5 of 14

6. Now, let’s input data for Types of Earth Conductors (shield conductors). To do so, follow similar

steps from5.1 to 5.4 filling out the appropriate data for Earth Conductor 1

Page 6: TL Parameters Using Tower Type PF

Page 6 of 14

7. For Earth Conductor 2 one can just copy and paste the Conductor Types TypCon from Earth Conductor 1.

Page 7: TL Parameters Using Tower Type PF

Page 7 of 14

8. The General Tab should look like this

9. Continue with the Geometry Tab, where one can input the location (geometry) of the line and earth

conductors, the x- and y-axis are located at earth level and at the center of the tower, respectively.

Page 8: TL Parameters Using Tower Type PF

Page 8 of 14

10. Input the Coordinate of Line Circuits [m]:

Page 9: TL Parameters Using Tower Type PF

Page 9 of 14

11. Input the Coordinate of Earth Conductors [m]:

Page 10: TL Parameters Using Tower Type PF

Page 10 of 14

12. Finally, push Calculate button. The results will be displayed on the Output Window.

13. Copy the results to the clip board. To do so, right click and choose copy where the following window

will be displayed:

Page 11: TL Parameters Using Tower Type PF

Page 11 of 14

The user can chose User Settings to select what message data should be copied.

Page 12: TL Parameters Using Tower Type PF

Page 12 of 14

Page 13: TL Parameters Using Tower Type PF

Page 13 of 14

DIgSI/info - Natural Impedance Matrix (R+jX) [ohm/km] DIgSI/info - Earth conductors first, followed by phase conductors in same order as the input. DIgSI/info - Rows follow R,X, R,X... in [ohm/km] 1.57987e+000 5.46605e-002 5.53438e-002 5.53334e-002 5.52890e-002 1.06836e+000 2.80620e-001 3.33192e-001 3.07684e-001 2.64865e-001 5.46605e-002 1.57987e+000 5.52890e-002 5.53334e-002 5.53438e-002 2.80620e-001 1.06836e+000 2.64865e-001 3.07684e-001 3.33192e-001 5.53438e-002 5.52890e-002 7.38320e-002 5.59891e-002 5.59336e-002 3.33192e-001 2.64865e-001 6.32752e-001 3.14778e-001 2.62534e-001 5.53334e-002 5.53334e-002 5.59891e-002 7.38320e-002 5.59891e-002 3.07684e-001 3.07684e-001 3.14778e-001 6.32752e-001 3.14778e-001 5.52890e-002 5.53438e-002 5.59336e-002 5.59891e-002 7.38320e-002 2.64865e-001 3.33192e-001 2.62534e-001 3.14778e-001 6.32752e-001 DIgSI/info - Reduced Impedance Matrix (R+jX) [ohm/km] DIgSI/info - Circuits (phases A,B,C...) follow in same order as the input. DIgSI/info - Rows follow R,X, R,X... in [ohm/km] 1.18700e-001 9.96129e-002 9.96129e-002 5.55096e-001 2.20348e-001 2.20348e-001 9.96129e-002 1.18700e-001 9.96129e-002 2.20348e-001 5.55096e-001 2.20348e-001 9.96129e-002 9.96129e-002 1.18700e-001 2.20348e-001 2.20348e-001 5.55096e-001

Page 14: TL Parameters Using Tower Type PF

Page 14 of 14

DIgSI/info - Symmetrical Impedance Matrix (R+jX) [ohm/km] DIgSI/info - Circuits (seq. 0,1,2...) follow in same order as the input. DIgSI/info - Rows follow R,X, R,X... in [ohm/km] 3.17925e-001 0.00000e+000 -1.38778e-017 9.95792e-001 0.00000e+000 0.00000e+000 0.00000e+000 1.90867e-002 1.38778e-017 0.00000e+000 3.34748e-001 -4.16334e-017 0.00000e+000 1.38778e-017 1.90867e-002 -2.77556e-017 -2.77556e-017 3.34748e-001 DIgSI/info - Reduced Admittance Matrix (G+jB) [uS/km] DIgSI/info - Circuits (phases A,B,C...) follow in same order as the input. DIgSI/info - Rows follow G,B, G,B... in [uS/km] 0.00000e+000 0.00000e+000 0.00000e+000 4.35968e+000 -5.84073e-001 -5.84073e-001 0.00000e+000 0.00000e+000 0.00000e+000 -5.84073e-001 4.35968e+000 -5.84073e-001 0.00000e+000 0.00000e+000 0.00000e+000 -5.84073e-001 -5.84073e-001 4.35968e+000 DIgSI/info - Symmetrical Admittance Matrix (G+jB) [uS/km] DIgSI/info - Circuits (seq. 0,1,2...) follow in same order as the input. DIgSI/info - Rows follow G,B, G,B... in [uS/km] 0.00000e+000 0.00000e+000 0.00000e+000 3.19153e+000 0.00000e+000 0.00000e+000 0.00000e+000 0.00000e+000 0.00000e+000 0.00000e+000 4.94375e+000 2.22045e-016 0.00000e+000 0.00000e+000 0.00000e+000 0.00000e+000 2.22045e-016 4.94375e+000