1

Software driven Converter BasedIntegrated Variable Speed Generation Solutions

The Innovus Power Microgrid Platform

Innovus Power Proprietary- All Rights Reserved – June 2015

IPS Connect Maui 2018

Page 2: The Innovus Power Microgrid Platform - IPS Connect

2Innovus Power Proprietary- All Rights Reserved- Sept 2015

SolarPV

Wind

Software and Electronics for Power Generation

Why Not for Fossil Fuel Generation?

• Low Cost • High reliability• Extremely efficient• Proven & Bankable• Programmable and controllable

• Transient response• Grid Support

• Variable Speed Engine operation• Enables Highest Engine efficiency• Integrates 100% renewables• Programmable and controllable• Components Proven & Bankable

2

BatteryStorage

Page 3: The Innovus Power Microgrid Platform - IPS Connect

3Innovus Power Proprietary- All Rights Reserved- Sept 2015

Innovus Architecture- Converter Based VSG

Variable RPMFrequency/Volt

Power Hub50/60 Hz AC

Permanent Magnet

Generator

Diesel/NG Engine

3

MTU/Cat/SiemensDiesel/NG/Propane

• Decoupling Engine Speed and generator through Back to back conversion process fundamentally changes the characteristics of fuel based energy production

• Significantly improved response capabilities of the prime mover- predictive- not reactive

Page 4: The Innovus Power Microgrid Platform - IPS Connect

4Innovus Power Proprietary- All Rights Reserved- Sept 2015

• Converter provides Grid Support Features

• Generation Stability without Storage• Transient response• Frequency Regulation• VAR Support-100% • Virtual Spinning Reserve• Engine off operation

• Healthy LOW LOAD operation typical 10%• Dispatchable + Renewable Firming 24/7/365 • Cost effective transition Grids to 100% renewable with fossil back up

Inverter based Generation- Unlocking Benefits

Variable RPMFrequency/Volt

Power Hub

50/60 Hz AC

MTU/Cat/SiemensDiesel/NG Engine

Permanent Magnet

Generator

4

Page 5: The Innovus Power Microgrid Platform - IPS Connect

5Innovus Power Proprietary- All Rights Reserved- Sept 2015

• Bridges Energy from prime mover• Instantaneous response <20ms• Seamless Power Supply/Engine off• UPS response

Variable RPMFrequency/Volt

50/60 Hz AC

Cat/MTU/SiemensDiesel/NG Engine

Permanent Magnet

Generator

PowerBridge- An Innovus Integrated Solution

Ultracapacitors

Dynamic Resistor

PowerBridgeController

DC BUS

DC BUS

5

Stabilization at the Source

Page 6: The Innovus Power Microgrid Platform - IPS Connect

6Innovus Power Proprietary- All Rights Reserved- Sept 2015

• Only cost of Storage $/kWh –• $250-$300/kWh-• eliminates $/kW for Power Electronics

Variable RPMFrequency/Volt

50/60 Hz AC

Cat/MTU/SiemensDiesel/NG Engine

Permanent Magnet

Generator

Low Cost Storage Integration

Dynamic Resistor

PowerBridgeController

DC BUS

DC BUS

6

Low Cost Storage IntegrationBatteries

Page 7: The Innovus Power Microgrid Platform - IPS Connect

7

Disruptive Efficiency & Load Range

7

200

250

300

350

400

450

500

0 50 100 150 200 250 300 350 400 450 500 550 600 650

g/kW

h

kWe

C27 FSG

VSGC27

40%

20%

30%

15%

Page 8: The Innovus Power Microgrid Platform - IPS Connect

Aklavik, NT An NTPC Project

Innovus Power Proprietary- All Rights Reserved- Sept 20158

Peak Rating: VSG 590 kW Prime Power

System Configuration: Diesel Generation with Solar

Solar: Low Penetration 1st Phase-55kW

LT Goal: High penetration Renewables

Population: 590~

Households: 300

Access: Airport, road-Barge, Ice Road

Fuel savings: 80,000 litres/year

Emissions: 210 Tonnes GHG reduction

Page 9: The Innovus Power Microgrid Platform - IPS Connect

The Revolution in Power Generation starts in 2018

Innovus Power Proprietary- All Rights Reserved- Sept 20159

Peak Rating: VSG 590 kW Prime Power

Commission: Jan 2018

System Configuration: Diesel Generation with Solar

Solar: Low Penetration 1st Phase-55kW

Planned Renewable additions: Solar will be added to full Penetration as funding available

FairbanksAlaska

Aklavik NT

Page 10: The Innovus Power Microgrid Platform - IPS Connect

On the Shores of

Innovus Power Proprietary- All Rights Reserved- Sept 201510

-62 F+93 F

Page 11: The Innovus Power Microgrid Platform - IPS Connect

11Innovus Power Proprietary- All Rights Reserved- Sept 2015

• The conference theme will be "Optimizing our Resources" encompassing the following main topics:

• Human capacity development and management

• High efficiency diesel and alternative fuels generation

• Renewable energy integration

• Energy efficiency - system and end-use

Factory Tested, Modularized Containerized or Skidded Solutions600kW, 1.2MW, 1.8MWSIMPLE ON SITE CONNECTIONS

Page 12: The Innovus Power Microgrid Platform - IPS Connect

12Innovus Power Proprietary- All Rights Reserved- Sept 2015

Interior Arctic Containerized Package for NTPC-with subbase tank, roll end skid, plate frame heat exchanger

Page 13: The Innovus Power Microgrid Platform - IPS Connect

13Innovus Power Proprietary- All Rights Reserved- Sept 2015

Interior Electronics Room- Arctic Containerized Package for NTPC- Converter, and exterior mount HMI

Page 14: The Innovus Power Microgrid Platform - IPS Connect

Aklavik NWT- VSG Independently Powering Entire Community

Innovus Power Proprietary- All Rights Reserved- Sept 201514

Northwest Territories Power Corp is replacing their Synchronous Generation System with the Innovus Power Platform in Aklavik, NWT Canada

Status: Commissioned January 2018

Page 15: The Innovus Power Microgrid Platform - IPS Connect

NTPC Aklavik NWT- N+3 Generation Architecture

55kW Ground Mounted Solar

Aklavik Isolated Grid

550kW Peak

180kW min

350 Ave Load

Power

Converter590kW VSG

DD Series 60320kWQty 4

Page 16: The Innovus Power Microgrid Platform - IPS Connect

NTPC Aklavik NWT- Control Architecture

55kW Ground Mounted Solar

Power

Converter590kW VSG

DD Series 60320kWQty 4

WoodwardLoad Share Aklavik

Isolated Grid

Innovus MCU

PLC

Isochronous Frequency

Droop Voltage

Droop/isoch mode

Woodward on/off

VSG on/off

Page 17: The Innovus Power Microgrid Platform - IPS Connect

Aklavik NWT- Innovus Efficiency

Innovus Power Proprietary- All Rights Reserved- Sept 201517

Frequency Stability: Less than 0.5% deviation

- during normal operation AND solar ramp periods

0

0.5

1

1.5

2

2.5

3

3.5

4

4.5

0 50 100 150 200 250 300 350 400 450 500 550 600

Innovus MTU VSG590 kWh/L

kWh

/l

kW

Page 18: The Innovus Power Microgrid Platform - IPS Connect

18

Lance BrownVP of Marketing1.510.579.2

The Future of Microgrid Distributed Power

Paul Pauze, P.Eng

705-760-4466

Mahalo !

Page 19: The Innovus Power Microgrid Platform - IPS Connect

Transforming the Grid for today’s Needs- Fully Optimized CG and DG

Power Grid

Distributed Generation ‘DG’

Central Generation ‘CG’

DG Renewables

CG-DG Dispatchable Primary Power

• CG runs Base load increasing efficiency

• DG runs with CG efficiency and assures• Grid Resilience• High Quality Power• Renewable Optimization