    INTRODUCTION

    A Transformer is electro static device used for transferring power from one circuit to another without change in frequency.

    Working principle of a transformer:-It works on the principle of mutual induction

    EMF equation of transformer:-

    ,

    RMS value of emf induced intransformer is ,

    E=4.44fNB mA

  • 8/6/2019 T.F Testing&Protection

    3/23

  • 8/6/2019 T.F Testing&Protection

    4/23

    (b) copper losses:-y C opp er loss (I2R plus str a y loss) is measured b y the

    sho rt- circuit test .Maximum eff icien c y of tr ans former occu rs when

    Iron loss=C opp er loss

    4

  • 8/6/2019 T.F Testing&Protection

    5/23

    5

    TRANS F OR ME R F AI L UR E S

    F ailures due to faults arising in the transformer called internalfailures.

    F ailures due to faults occurring on any part of the system beyondthe transformer called external failures.

    I nternal F ailures:-The causes for internal failureof transformer are due to

    1. Earth faults2.Phase to phase faults

    3 . Interterm faults4. Core faults5 . Tank faults

  • 8/6/2019 T.F Testing&Protection

    6/23

    winding in sulat ion fa ilure:-y Ins ula ti on is recognize d as one of the most impo rt ant

    constr ucti onal elements of a tr ans former. Its ch ief function is to con f ine the current to use ful pa ths, preventin g its flowint o ha rmful cha nne ls.

    y The mo st diff icult tr ans former win din g fault for which topro vide prote cti on is the fault tha t initi all y inv ol ves on l y one turn . Initi all y, the ins ula ti on breakdow n leads tointern al arcin g, which res ults int o a low cu rrent, high

    imp edance fault .

    6

  • 8/6/2019 T.F Testing&Protection

    7/23

    Ex ter n al Fa ilures:-y 1. O ver loady 2. O ver v oltage

    i) Trans ient Surge VoltageTransient o ver v oltage arise f rom s witch in g and

    lightnin g dist urbances and are liable to cau se inter-t urn faults .

    ii) Power Frequency over VoltagePower f req uen c y o ver v oltage causes bo th an in crease

    in stress on the ins ula ti on and a p ropo rti onate in crease in the workin g flux.

    7

  • 8/6/2019 T.F Testing&Protection

    8/23

    TRANS FORM ER TESTSy W ind ing res istance testy Load testy

    Open c ircu it testy Short c ircu it testy Polar ity test

    8

  • 8/6/2019 T.F Testing&Protection

    9/23

    W inding res ista n ce test:-y This is nothin g bu t the resist ance measurement of the win din gs b y appl ying a small d.c v oltage to the win din g andmeasurin g the current through the same.

    Load test:-y L oad Test helps to deter m ine the total loss tha t takes place,

    when the tr ans former is loaded.

    L oad test is used ma in l y ,

    1.to deter mine the rate d load of the mach ine and the te mp erature rise 2. to deter m ine the v oltage regulati on and eff icien c y of the tr ans former.

    9

  • 8/6/2019 T.F Testing&Protection

    10/23

    10

    O pen circuit test:-By conducting this test we can find out the core losses.

  • 8/6/2019 T.F Testing&Protection

    11/23

    Sh ort c ircu it test :-

    11

    B y conduc tin g this test we can f in d ou t the copp er losses .

  • 8/6/2019 T.F Testing&Protection

    12/23

    P olar ity test:-y

    This is nee ded for identi f ying the prima ry and secondary pha sor pola rities . It is a mu st for pol y pha se conne cti ons .Both a.c. a nd d.c m et hod s can be used for dete ctin g the pola rities of the in duced emf s.

    12

  • 8/6/2019 T.F Testing&Protection

    13/23

    TRANS FORM E R P ROTEC TI ON

    G as Operated (Buccholz ) R elay:-y The re la y serves as ma in prote ction for any min or or

    majo r faults t ha t ma y deve lop insi de a tr ans former.y Such faul ts alwa ys result in gener ation of gases, which

    causes t he operation of mercury s witches givin g signal

    for aud ible alarm o r isolates t he tr ans former f rom the

    net work.

    13

  • 8/6/2019 T.F Testing&Protection

    14/23

    14

  • 8/6/2019 T.F Testing&Protection

    15/23

    D iffere n t ial P rotect ion :-y The diff erenti al re la y is one t ha t operates when t he vector

    diff eren ce of t wo or mo re si m ilar e lectri cal quantitiesexceed a p re- deter mine d v alue.

    y Diff erenti al re la y of ty pe DTH 31/32 is emplo yed fortr ans former prote ction .

    y Nomen clatureD- Diff erenti al (op eratin g quantity )T Transist or (mo vement )H Harmoni c R estr aint (appl ication )DTH 31 F or t wo win din g power tr ans former.DTH 32 For t hree win din g power tr ans former.

    15

  • 8/6/2019 T.F Testing&Protection

    16/23

    16

  • 8/6/2019 T.F Testing&Protection

    17/23

    Over C urre n t a nd Eart h FaultP rotect ion :-

    y Dire ctional inverse ti me o ver current and eart h faul t re la ys of ty pe C DD is emplo yed for tr ans former prote cti on against o ver currents .

    Nomen clatureC C urrent operate d (op eratin g Qua ntity )D Induc ti on T y pe (Mo vement )

    D Dire ctional (Appl ication )y Dire ctional re la ys are a v ailable in sin gle pole versi on on l y .

    These pro vide backup fo r the ma in prote cti on of IC Ts.

    17

  • 8/6/2019 T.F Testing&Protection

    18/23

    18

  • 8/6/2019 T.F Testing&Protection

    19/23

    Restr icte d Eart h Fault P rotect ion :-y A simple o ver current and eart h faul t syste m will not

    give good p rote ction co ver for a st ar- conne cte d

    prima ry win din g, parti cula rl y if the ne utr al is eart hedthrough impen den ce.y The restri cte d eart h faul t prote ction schema tic shown

    in f igure imp ro ves the degree of prote ction very much.

    19

  • 8/6/2019 T.F Testing&Protection

    20/23

    20

  • 8/6/2019 T.F Testing&Protection

    21/23

    Conclusion:-

    From this project, it is clear t ha t t he powertr ans former is one of the very i mpo rt ant lin ks in a powertr ans missi on and d istri bu ti on syste m.

    A tr ans former fault will cause a large interr up tion inpower s uppl ies and the impac t is mo re seri ous than atr ans missi on line ou tage and also cau ses damag e to powersyste m st ab ility .