technical_handbook - oman cables.pdf
DESCRIPTION
Tech OMGTRANSCRIPT
OCI/PBTB/Rev-001/010909
1
Oman Cables Industry (SAOG)
In a journey spanning over two decades, Oman Cables Industry(SAOG) has always strived towards excellence and quality in all itsactivities. The various awards won by OCI bear testimony to this, beit being the five-time winner of His Majesty’s trophies for the bestindustry or the various Flame of Excellence and Exporter of the Yearawards. OCI exports its products across the globe to Europe, UK, FarEast, Asia, Middle East and the Pacific Rim. Having started with just10 employees and sales of 0.2 million USD in 1984, today OCI isproud of the fact that it employs 52% Omani nationals amongst its600 employees, and has a sales turnover of 800 million USD.
(´.´.Ω.¢T) á«fɪ©dG äÓHɵdG áYÉæ°U ácô°T
IÒ°ùe ‘ ¬à≤≤M Éà á«æW h ¬cô°ûc IQƒîa á«fɪ©dG äÓHɵdG áYÉæ°U ácô°T ∞≤J
øeõdG øe øjó≤Y.äRÉa √ójóY õFGƒéH êƒJ õ«ªàdG ƒëf ÜhDhódG »©°ùdG h ìÉéædG ¿G
¿É£∏°ùdG ádÓ÷G ÖMÉ°U IõFÉéH RƒØdGÉ¡ªgG øe ¿Éc h á∏jƒ£dG É¡JÒ°ùe ‘ ácô°ûdG É¡H
á«dÉààe äGƒæ°S ¢ùªÿ áYÉæ°üdG π°†aC’ ¬∏dG ¬¶ØM ¢SƒHÉb,ôjó°üà∏d ΩÉ©dG IõFÉL h.⁄ Q’hO ¿ƒ«∏e 0^2 ™«Hh 1984 ΩÉY ‘ ÚØXƒe Iô°û©H á©°VGƒàŸG ácô°ûdG ájGóH ¿G
ÚæWGƒŸG øe % 52 º¡æe ∞Xƒe 600 `H Ωƒ«dG h á«ŸÉ©∏d √Gó©J πH á«∏fi ô°üëàj
»µjôeCG Q’hO ¿ƒ«∏e 800 äÉ©«ÑŸG ºéM ≠∏H Ú«fɪ©dG.AÉëfCG ™«ª÷ á«ŸÉ©dG IOƒ÷G äGP É¡JÉéàæe á«fɪ©dG äÓHɵdG áYÉæ°U ácô°T Qó°üJ
¿Gó∏ÑdGh §°Sh’G ¥ô°ûdGh É«°SBGh ≈°übC’G ¥ô°ûdGh IóëàŸG áµ∏ªŸG ‹G ¢üN’ÉHh ⁄É©dG
ÇOÉ¡dG §«ÙG ≈∏Y á∏£ŸG.
Technical Book MZ 11/25/11 8:54 AM Page 1
OCI/PBTB/Rev-001/010909
Technical Book MZ 11/25/11 8:54 AM Page 2
OCI/PBTB/Rev-001/010909
3
Table of Contents
Sr. No. Details Page
1 Product Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2 Criteria for selection of Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
3 Conductor details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
4 Electric Field in MV cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
5 General characteristics of Insulating Materials . . . . . . . . . . . . . . . . . . . . . . . . .15
6 General characteristics of Sheathing Materials . . . . . . . . . . . . . . . . . . . . . . . .16
7 Continuous Current Ratings and rating factors . . . . . . . . . . . . . . . . . . . . . . . .20
8 Short Circuit Current ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
9 Cables Storage and Installation Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
10 Testing of Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
11 Insulation Resistance Test and significance . . . . . . . . . . . . . . . . . . . . . . . . . . .50
12 Voltage drop – utility and values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
13 Earthing and Bonding methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
14 PVC vs XLPE cables – Comparison . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
15 Overhead Conductor – Characteristics and Applications . . . . . . . . . . . . . . . . .61
16 Frequently Asked Questions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
17 Conversion Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
Technical Book MZ 11/25/11 8:54 AM Page 3
OCI/PBTB/Rev-001/010909
4
OCI Product Range
Oman Cables offers a wide range of cables for demands made upon electrical, mechanical and
thermal qualities. The products listed below are the most popular ones. However, OCI can meet
a customer’s special requirements.
1) Electric Wires:
a) Building wires from 1.5 mm2 to 630 mm2
b) Single core PVC and LSF insulated wires 450/750 Volts to BS 6004, BS 7211, IEC
60227
c) Multicore 300/500 Volts Circular, PVC Insulated, PVC Sheathed Wires to BS 6004,
IEC 60227
d) 2 Core, 3 Core Flat Wires with and without earth continuity conductor to BS 6004
e) PVC Insulated Flexible Cords to IEC 60227
f) 300/500 Volts Flexible Cables BS 6500, IEC 60227
2) 0.6/1 kv, XLPE and PVC insulated, PVC and LSF Sheathed Cables to IEC 60502-
1, BS 6346, BS 7889, BS 5467, BS 6724 and specific customer requirements
with:
a) Copper and Stranded Aluminium Conductors
b) Single core and multicore cables
c) Unarmoured cables
d) Aluminium wire armoured single core cables
e) Galvanized Steel Wire and Galvanized Steel Tape armoured multicore cables.
f) Control cables with and without armour, with and without screen (copper
tape/copper wire).
Technical Book MZ 11/25/11 8:54 AM Page 4
3. Medium Voltage XLPE insulated cables to IEC 60502-2, BS 6622, BS 7835, BS
7870 and specific customer requirements up to and including 46 kV:
Copper and Aluminium Conductors:
a) Single core cables 25 mm2 to 1000 mm2
b) Three core cables 25 mm2 to 500 mm2
c) Single core and Three core un-armoured cables with copper tape/copper wire screen.
d) Aluminium wire armoured single core cables.
e) Galvanized Steel Wire and Galvanized Steel Tape armoured multicore cables.
We can offer cables with Optional Features such as:
Watertight Conductors
Bonded or Strippable Insulation Screen
Copper Wire/Copper Tape Screen
Cables with longitudinal water barriers at screen and armour level.
Cables with Radial water barrier (PE Laminated Aluminium Tape).
Cables with LLDPE, MDPE, HDPE, FRRT, FRLS Outer Sheath.
4) Overhead Conductors to IEC, BS, ASTM, DIN, VDE, AS Standards
a) Bare and PVC/XLPE Insulated Hard Drawn Copper Conductors
b) Bare and PVC/XLPE insulated all Aluminium conductors (AAC, AAC/PVC,
AAC/XLPE).
c) All Aluminium Alloy conductors (AAAC)
d) Aluminium Conductors Steel Reinforced (ACSR)
e) Aluminium Conductors Aluminium Clad Steel Reinforced (ACSR/AW).
f) Aluminium Conductors Aluminium Alloy Reinforced (ACAR).
g) Aluminium Alloy Conductor Steel Reinforced (AACSR).
5
OCI/PBTB/Rev-001/010909
Technical Book MZ 11/25/11 8:54 AM Page 5
h) Galvanized Steel and Alumoweld Earth Wires.
i) Aerial Bundle Cables (Duplex, Triplex, Quadruplex).
5. Special Cables
a) Watertight Cables
b) Fire Retardant Cables to IEC 60332-3-24, IEC 60332-3-23, IEC 60332-3-22.
c) Cables with LLDPE, MDPE, HDPE, FRRT, FRLS Outer Sheath.
d) Cable with Oil Resistant and/or Termite Resistant and/or FRRT and/or FRLS Outer
Sheath.
e) Instrumentation Cables.
6) PVC Compounds for Insulation and Sheathing of Electric Cables. To name a few:
Type A,T11, T13, Type 6, Type 9, Type ST2, FR, FRLS, FRRT, ATR etc.
6
OCI/PBTB/Rev-001/010909
Technical Book MZ 11/25/11 8:54 AM Page 6
OCI/PBTB/Rev-001/010909
7
Criteria for selection of Power Cables
Cable Type and Size should be selected keeping in the view the following:1) Application2) Working Voltage, Earthed or Unearthed System3) Load Current, Duty Cycle, Frequency4) Installation methods and conditions5) Short time duty and system protection6) Acceptable Voltage drop7) Economics
How do these factors influence the choice of cables?
1) Application of the cable determines the basic factors for choice of cable type.
a) Conductor material – Copper is the virtually unchallenged material as a conductor.
Aluminium, can also be used as Conductor material as it is very economical.
b) Insulating Material – good insulating material should have low thermal resistivity and
low dielectric losses. Please refer to the chart for major characteristics of different
materials.
c) Power cables are usually with armour to carry earth fault current and to give
mechanical protection against damage during installation and service. For higher fault
rating and higher tensile strength steel wires are used in multicore cables. Single core
in AC circuits, use non magnetic material. Stainless steel is difficult to justify on cost
grounds and Aluminium is the normal choice.
d) External covering/sheaths are used over the armour. Polyethylene or PVC is material
most often used. Please refer to the chart for properties of sheathing material.
2) System voltage determines Voltage class of cables.
3) Current rating and intermittent load is the decisive factor for fixing conductor size. Factors
such as Ground & Air temperature, thermal resistivity of soil, depth of laying, number of
cables in circuit etc. affect specified current ratings.
4) Chemical substances in the environment might need special requirements on outer
covering. Cables are vulnerable to termite and rodent attacks.
Technical Book MZ 11/25/11 8:54 AM Page 7
OCI/PBTB/Rev-001/010909
5) The short circuit current and its duration determines the size of conductor and thermal
requirement of insulation.
6) Voltage drop is also major factor in deciding the conductor size of the cable. Voltage drop
of the cable for a given route length should not exceed the statutory requirements.
7) The design of the cable for a particular application must be optimised taking into account
all the above factors. In case expert guidance is desired, please contact OCI.
8
Technical Book MZ 11/25/11 8:54 AM Page 8
OCI/PBTB/Rev-001/010909
9
Class of Conductors:
Class 1: Solid Conductor - used in cables for fixed installations.
Class 2: Started Conductor - used in cables for fixed installations.
Class 5: Flexible conductor - used in flexible cables and cords.
Class 6: Flexible Conductor - used in flexible cables and cords. Conductors are more
flexible than Class 5 when more flexibility is required
Table – Class 1 solid conductors for single core and multicore cables
1 2 3 4
Nominal Maximum resistance of conductor at 20˚Ccross Circular, annealed copper Aluminium and aluminium
sectional conductors alloy conductors, circulararea Plain Metal-Coated or shapedm2 Ω/km Ω/km Ω/km
0.5 36.0 36.7 –
0.75 24.5 24.8 –
1.0 18.1 18.2 –
1.5 12.1 12.2 –
2.5 7.41 7.56 –
4 4.61 4.70 –
6 3.08 3.11 –
10 1.83 1.84 3.08(a
16 1.15 1.16 1.91(a
25 0.727(b – 1.20(a
35 0.524(b – 0.868(a
50 0.387(b – 0.641
70 0.268(b – 0.443
95 0.193(b – 0.320(d
120 0.153(b – 0.253(d
150 0.124(b – 0.206(d
185 0.101(b – 0.164(d
240 0.0775(b – 0.125(d
300 0.0620(b – 0.100(d
Technical Book MZ 11/25/11 8:54 AM Page 9
OCI/PBTB/Rev-001/010909
Table – Class 1 solid conductors for single core andmulticore cables
1 2 3 4
Nominal Maximum resistance of conductor at 20˚Ccross Circular, annealed copper Aluminium and aluminium
sectional conductors alloy conductors, circulararea Plain Metal-Coated or shapem2 Ω/km Ω/km Ω/km
400 0.0465(b – 0.0778
500 – – 0.0605
630 – – 0.0469
800 – – 0.0367
1000 – – 0.0291
1200 – – 0.0247
a) Aluminium conductors 10 mm2 to 35 mm2 circular only.
b) Solid copper conductors having nominal cross-sectional areas of 25mm2 and above areused for particular types of cable e.g., mineral insulated, and not for general purpose.
c) For solid aluminium alloy conductors having the same nominal cross-sectional area asan aluminium conductor, the resistance value should be multiplied by 1.162 unlessotherwise agreed between manufacturer and purchaser.
d) For single core cables, four sectoral shaped conductors may be assembled into a singlecircular conductor. The maximum resistance to the assembled conductor should be25% of that of the individual component conductors.
10
Technical Book MZ 11/25/11 8:54 AM Page 10
OCI/PBTB/Rev-001/010909
11
mm2 Ω/km Ω/km Ω/km0.5 7 – – – 36.0 36.7 –
0.75 7 – – – 24.5 24.8 –1.0 7 – – – 18.1 18.2 –1.5 7 – 6 – 12.1 12.2 –2.5 7 – 6 – 7.41 7.56 –4 7 – 6 – 4.61 4.70 –6 7 – 6 – 3.08 3.11 –
10 7 7 6 6 – 1.83 1.84 3.0816 7 7 6 6 – 1.15 1.16 1.9125 7 7 6 6 6 6 0.727 0.734 1.2035 7 7 6 6 6 6 0.524 0.529 0.86850 19 19 6 6 6 6 0.387 0.391 0.64170 19 19 12 12 12 12 0.268 0.270 0.44395 19 19 15 15 15 15 0.193 0.195 0.320
120 37 37 18 15 18 15 0.153 0.154 0.253150 37 37 18 15 18 15 0.124 0.126 0.206185 37 37 30 30 30 30 0.0991 0.100 0.164240 37 37 34 30 34 30 0.0754 0.0762 0.125300 61 61 34 30 34 30 0.0601 0.0607 0.100400 61 61 53 53 53 53 0.0470 0.0475 0.0778500 61 61 53 53 53 53 0.0366 0.0369 0.0605630 91 91 53 53 53 53 0.0283 0.0286 0.0469800 91 91 53 53 – – 0.0221 0.0224 0.0367
1000 91 91 53 53 – – 0.0176 0.0177 0.02911200 b) – – 0.0151 0.0151 0.0247
1400 a b) 0.0129 0.0129 0.02121600 b) 0.0113 0.0113 0.0186
1800 a b) 0.0101 0.0101 0.01652000 b) 0.0090 0.0090 0.01492500 b) 0.0072 0.0072 0.0127a) These sizes are non-preferred. Other non-preferred sizes are recognized for some specialized applications but are
not within the scope of this standard
b) The minimum number of wires for these sizes is not specified. These sizes may be constructed from 4, 5 or 6equal segments (Milliken)
c) For stranded aluminium alloy conductors having the same nominal cross-sectional area as an aluminium conductorthe resistance value should be agreed between the manufacturer and the purchaser.
Class 2 stranded conductors for single-core and multi-core cables
1 2 3 4 5 6 7 8 9 10
Nominal
cross-sectional area
Minimum number of wires inthe conductor
CircularCircular
Compacted ShapedAnnealed copper
conductor
Plain wires
Metal-coatedwires
Aluminium oraluminium alloy
conductors Plain wires
Maximum resistance of conductor at 20˚C
Cu Al Cu Al Cu Al
Technical Book MZ 11/25/11 8:54 AM Page 11
OCI/PBTB/Rev-001/010909
Class 5 flexible copper conductors for single coreand multi-core cables
1 2 3 4
Nominal Maximum diameter of wires in Maximum resistance ofcross- conductor (mm) conductor at 20˚C
sectional areaClass 5 Class 6 Plain wires Metal-coated wires
mm2 Ω/km Ω/km
0.5 0.21 0.16 39.0 40.1
0.75 0.21 0.16 26.0 26.7
1.0 0.21 0.16 19.5 20.0
1.5 0.26 0.16 13.3 13.7
2.5 0.26 0.16 7.98 8.21
4 0.31 0.16 4.95 5.09
6 0.31 0.21 3.30 3.39
10 0.41 0.21 1.91 1.95
16 0.41 0.21 1.21 1.24
25 0.41 0.21 0.780 0.795
35 0.41 0.21 0.554 0.565
50 0.41 0.31 0.386 0.393
70 0.51 0.31 0.272 0.277
95 0.51 0.31 0.206 0.210
120 0.51 0.31 0.161 0.164
150 0.51 0.31 0.129 0.132
185 0.51 0.41 0.106 0.108
240 0.51 0.41 0.0801 0.0817
300 0.51 0.41 0.0641 0.0654
400 0.51 0.0486 0.0495
500 0.61 0.0384 0.0391
630 0.61 0.0287 0.0292
12
Technical Book MZ 11/25/11 8:54 AM Page 12
OCI/PBTB/Rev-001/010909
13
Electric Field in Medium Voltage XLPE Cables
As shown in the figure below, the electric field is the highest at conductor surface, reducingtowards the outer surface of the insulation.
Field distribution within a high voltage XLPE cable
Purpose of Semiconducting screens for such cables –Conductor Screening:-1. To provide uniform stress over the relatively rough stranded conductor surface.2. To provide close bonding between the conductor and adjacent insulation so as to exclude
any interspersed voids that may constitute sources of partial discharge.
Insulation Screening1. With the outer shield grounded, the electric field of the conductor attains radial symmetry
and is confined to Insulation for safety consideration.2. To distribute electrical stress uniformly along the periphery of the cable3. Intimate contact between Insulation and semiconducting layer prevents partial discharge.4. To prevent surface discharges and reduce electrical interferences
Please see the difference between shape of Electric field of shielded (screened) cable andunshielded cable
Non-Shielded Shielded
Technical Book MZ 11/25/11 8:54 AM Page 13
OCI/PBTB/Rev-001/010909
14
Outer Covering materials selection chart
Mechanical PVC Polyethylene
Abrasion Resistance Good ExcellentTensile Strength Excellent ExcellentElongation Good ExcellentCompression Resistance Good ExcellentFlexibility Good Fair
Environmental – –
Flame Good PoorMoisture – –Fresh or salt water Good ExceptionalPetroleum oils – –Motor oil – ExcellentFuel oil Good (Slight swellingCrude oil – above 60˚C)Creosote Poor GoodParaffinic Hydrocarbons – –Gasoline Good ExcellentKerosene – (Slight swelling at
higher temperatures)Alcohols – –Isopropyl – –Wood Fair GoodGrain – –Mineral Acids – –Sulfuric Acid – –Nitric Acid Excellent ExcellentHydrochloric Acid – –Fixed Alkalis Sodium hydroxide (lye) – –Potassium hydroxide (potash) – –Calcium hydroxide (lime) Good ExcellentKetones – –Acetone – –Methyl ethyl ketone (MEK) Poor GoodEsters – –Ethyl Acetate – –Most lacquer thinners Poor GoodHalogenated Hydrocarbons – –Chloroform – –Carbon Tetrachloride – –Methyl Chloride Poor Poor
General
Leaves protective residue after combustion Yes NoOxygen Index (ASTM D-2863) 23-30% 17-18%Halogen content – % Wt. 26 0Minimum installation temperature 14˚F (-10˚C) -40˚F (-40˚C)Dimensional stability under heat Fair FairMaximum operating temperature 80˚C 80˚C
Technical Book MZ 11/25/11 8:54 AM Page 14
OCI/PBTB/Rev-001/010909
15
Insulation Material Characteristics
Sl. Description Unit PVC XLPE LSFNo. (Type A) (0.6/1 kV) (0.45/.75 kV)1 Tensile Strength and Elongation at break
Min. tensile strength N/mm2 12.5 12.5 10Min. elongation at break % 150 200 125
2 Accelerated ageing for specified period at specified temp. followed by Tensile Strength and Elongation at breakNo. of days ageing Days 7 7 7Ageing temperature ˚C 100±2 135±3 135±3Max. variation of tensile strength from N/mm2 12.5 – –unaged specimen % ±25 ±25 ±30Max. variation of elongation from % 150 – –unaged specimen % ±25 ±25 ±30
3 Hot Set Test:– Temperature ˚C N/A 200±3 200±3– Time under load Minutes N/A 15 15– Mechanical stress N/cm2 N/A 20 20Max. elongation under load % N/A 175 100Max. permanent elongation after cooling % N/A 15 25
4 Low temperature bend test:Temperature at which specimen shall not crack ˚C -15±2 N/A -15±2
5 Low temperature elongation test:Test temperature ˚C -15±2 N/A -15±2Minimum Elongation % 20 N/A 30
6 Low temperature impact test:Temperature at which specimen shall not crack ˚C N/A N/A -15±2
7 Pressure test at high temperature:Test temperature ˚C 80±2 N/A 110±2Maximum indentation % 50 N/A 50
8 Loss of Mass (only for T11 insulation as per BS)Ageing: Number of days Days 7 N/A N/AAgeing Temperature ˚C 80±2 N/A N/AMaximum loss of mass mg/cm2 2.0 N/A N/A
9 Resistance to cracking (Heat shock test)Temperature at which the specimen shall not crack ˚C 150±2 N/A N/A
10 Water absorption – electrical methodTemperature at which specimen shall not crack ˚C 70±2 85±2 N/ADuration Hours 240 336 (14 days) N/AMaximum variation of mass mg/cm2 – 1.0 N/A
11 Maximum permissible shrinkage:– Temperature ˚C N/A 130±3 N/A– Duration Hours N/A 1 N/AMaximum permissible shrinkage % N/A 4 N/A
12 Insulation Resistance const (Ki) at max. rated temp. M.Ohm.Km 0.037 (70˚C) 3.67 (90˚C) 0.002 (90˚C)13 Volume Resistivity at maximum rated temperature Ohm.cm 1010(70˚C) 1012(90˚C) 1011(20˚C)14 Ozone Resistance test
Temperature at which specimen shall not crack ˚C N/A N/A 25±2Duration Hours N/A N/A 24Ozone Concentration ppm N/A N/A 250 to 300
15 Acidic (corrosive) gases evolvedLevel of HCl % N/A N/A <0.5pH (minimum) N/A N/A 4.3Conductivity (maximum) (µS/mm) N/A N/A 10
Technical Book MZ 11/25/11 8:54 AM Page 15
OCI/PBTB/Rev-001/010909
Sheathing MaterialCharacteristics
Sl. Description Unit PVC LSFNo. (ST2/Type 9)
1 Tensile Strength and Elongation at breakMin. tensile strength N/mm2 12.5 10Min. elongation at break % 150 100
2 Accelerated ageing for specified period at specified temp.followed by Tensile Strength and Elongation at breakNo. of days ageing Days 7 7Ageing temperature ˚C 100±2 100±2Minimum tensile strength after ageing N/mm2 12.5 10Max. variation of tensile strength from unaged specimen % ±25 40Minimum Elongation % 150 100Max. variation of elongation from unaged specimen % ±25 40
3 Low temperature bend test:Temperature at which specimen shall not crack ˚C -15±2 -15±2
4 Low temperature elongation test:Test temperature ˚C -15±2 -15±2Minimum Elongation % 20 30
5 Low temperature impact test:Temperature at which specimen shall not crack ˚C -15±2 -15±2
6 Pressure test at high temperature:Test temperature ˚C 90±2 80±2Maximum indentation % 50 50
7 Resistance to cracking (Heat shock test)Temperature at which the specimen shall not crack ˚C 150±2 N/A
8 Loss of MassAgeing: Number of days Days 7 N/AAgeing Temperature ˚C 100±2 N/AMaximum loss of mass mg/cm2 1.5 N/A
9 Water absorptionNo. of days ageing Hours N/A 24Aging Temperature ˚C N/A 70±2Maximum increase in mass mg/cm2 N/A 10
10 Tear Resistance test to B5 6469 (sec 99.1)Minimum Value N/mm N/A 5
11 Water immersion test to BS 6469 (sec. 99.1)Aging temperature ˚C N/A 7Number of days aging Days N/A 70±2Max variation in tensile strength % N/A 30Max. variation in elongation at break % N/A 30
12 Acidic (corrosive) gases evolvedLevel of Hcl % N/A <0.5pH (minimum) N/A 4.3Conductivity (maximum) (µS/mm) N/A 10
!) For Characteristics of PE Sheathing material, see Table in Page 202) For Special Characteristics of PVC Sheathing, see Table in Page 20
16
Technical Book MZ 11/25/11 8:54 AM Page 16
OCI/PBTB/Rev-001/010909
17
Special PVC Compounds with additional requirementsprovided by OCI:
Property Material
FR FRLS FRRT
Oxygen Index (Min.) 30 30 30Temperature Index (Min) 250 250 250Smoke Density (Max.) – 60 –Acid Gas Generation (Max.) – 20% 17%Flammability Test* IEC 60332-1 and IEC 60332-1 and IEC 60332-1 and
IEC 60332-3-24 IEC 60332-3-24 IEC 60332-3-24
*Based on specific requests, we can provide compounds which can meet flammability requirements of IEC 60332-3-23 andIEC 60332-3-22
Properties of Polyethylene Sheathing Material:
Properties LDPE MDPE HDPE
Dissipation factor60 Hz 0.0002 0.0002 0.0002103 Hz 0.0002 0.0002 0.0002106 Hz 0.0002 0.0002 0.0002
Arc resistance, s (ASTM D495) Melts Melts > 125
Density, g/cm3 0.910-0.925 0.926-0.940 0.941-0.965
Modulus of elasticity in tension, psi x 105 0.17-0.35 0.25-0.55 0.8-1.5
Percent elongation, % (ult.) (Max.) 300 300 400
Tensile strength, yield, psi x 102 14-19 19-26 26-45
Compressive strength, psi x 103 – – 2.4
Rockwell hardness R10 R15 R30-R50
Impact strength, ft-Ib/in. – – 1-23
Heat distortion temperature (at 66 psi), ˚F 105-121 120-150 140-185
Thermal conductivity, cal/cm.s. ˚C x 10-4 8 – 11-12
Thermal expansion, in./in. per ˚C x 10-5 11-30 15-30 15-30
Water absorption, % <0.02 <0.02 <0.01
Burning rate Slow Slow Slow
Technical Book MZ 11/25/11 8:54 AM Page 17
OCI/PBTB/Rev-001/010909
OCI can supply installing cables with special requirementsfor the following
Utility Voltage Rating Requirement
SEC-EOA 35 KV * Swellable tape under and over metallic screen.* Metal polyethylene laminate over metallic screen.* Polyethylene or PVC Outer Sheath.
ARAMCO 10 kV to 35 kV Optional Requirement:* Watertight Conductor with TR-XLPE Insulation* Semi-conducting water blocking swellable tapes under
and over the metallic screen or concentric neutral.* Plastic coated laminated aluminium or copper tape under
the outer jacket and firmly bonded to it.
SABIC 5 to 35 kV * Water swellable tape over copper tape screen* Water Swellable tape over 3 core assembly* Polyethylene bedding under Armour and PVC Outer
Sheath
DEWA 11 and 33 kV Single Core:* Watertight Conductor* Swellable tape in metallic screen region.* Metal polyethylene laminate in metallic screen region.* Polyethylene Outer Sheath.Multi Core:* Watertight Conductor* Swellable tape in metallic screen region.* Metal polyethylene laminate in metallic screen region.* Polyethylene Outer Sheath over steel wire armour
FEWA 33 kV Single Core:* Watertight Conductor* Water swellable tape over insulation screen* Non-conductive water swellable tape over copper screen* Copolymer Coated Laminated Tape* Polyethylene Outer Sheath
ADWEA 33 kV 33 kV Cables 3 Core Cables:* Watertight conductor* TR-XLPE insulation.* Polyethylene inner sheath* Polyethylene outer sheath over steel tape armour
KAHRAMAA 0.6/1 kV * Armour: Galvanized steel + tinned copper wires.Conductivity of copper wires alone shall be at least 50%of any phase conductor at normal working temperatureand shall not be less than 25% of the total number ofarmour wires.
* Armour to be embedded and covered by material suitableto prevent movement of water traversely.
18
Technical Book MZ 11/25/11 8:54 AM Page 18
OCI/PBTB/Rev-001/010909
19
Utility Voltage Rating Requirement
KAHRAMAA 11 KV * Fillers of non-hygroscopic material to inhibit flow of water.* Armour to be embedded in or overlaid by substance or
material to inhibit flow of water.
KUWAIT 11 kV * 3 Core 11 kV Cable without Metallic Screen over individual cores.
* Steel Wire armour over Semi-conductivity bedding.
SYRIA 12 to 20 kV * Swellable tape under and over insulation screen* PVC outer sheath
IRAQ 11 to 33 kV Single Core:* Waterproof tape over metallic screen* PVC outer sheathThree core:* Extruded EPR fillers* Waterproof tape over bedding.* PVC outer sheath over steel tape armour
JORDAN 33 kV Single Core* Swellable tapes over metallic screen* PE (ST7) outer sheath
TUNISIA 10 to 30 kV Single Core:* Longitudinally watertight at metallic screen* Radial Watertightness to be ensured by Outer sheath.
Technical Book MZ 11/25/11 8:54 AM Page 19
OCI/PBTB/Rev-001/010909
Current Ratings for Voltage gradefrom 6 kV to 30 kV
Basic Assumption:- Conductor Material – Copper Single Core Cables (Unarmoured)Ground Temperature – 20˚CAir Temperature – 30˚CThermal resistivity of soil – 150˚C-cm/wDepth of Laying – 800 mmDouble point bonding, Flat spacing – 2 OD from centre to centre
Ground In Single way Duct In Air
Single core, Unarmoured Single core, Unarmoured Single core, Unarmoured
Size Amp Amp Amp Amp Amp Amp
Trefoil Flat spaced Trefoil Flat Touching Trefoil Flat Touchingduct
25 140 144 132 133 163 167
35 166 172 157 159 198 203
50 196 203 186 188 238 243
70 239 246 227 229 296 303
95 285 293 271 274 361 369
120 323 332 308 311 417 426
150 361 366 343 347 473 481
185 406 410 387 391 543 550
240 469 470 447 453 641 647
300 526 524 504 510 735 739
400 590 572 564 571 845 837
500 649 680 617 647 952 1000
630 718 766 683 728 1067 1154
800 796 842 757 801 1221 1310
1000 865 918 823 873 1346 1454
20
Technical Book MZ 11/25/11 8:54 AM Page 20
OCI/PBTB/Rev-001/010909
21
Current Ratings for Voltage grade from6 kV to 30 kV
Basic Assumption:- Conductor Material – Copper Single Core Cables (Armoured)Ground Temperature – 20˚CAir Temperature – 30˚CThermal resistivity of soil – 150˚C-cm/wDepth of Laying – 800 mmDouble point bonding, Flat spacing – 2 OD from centre to centre
Ground In Single way Duct In Air
Single core, Armoured Single core, Armoured Single core, Armoured
Size Amp Amp Amp Amp Amp Amp
Trefoil Flat spaced Trefoil Flat spaced Trefoil Flat spaced
25 126 130 119 120 147 150
35 149 155 141 143 178 183
50 176 183 167 169 214 219
70 215 221 204 206 266 273
95 257 264 244 247 325 332
120 291 299 277 280 375 383
150 325 329 309 312 426 433
185 365 369 348 352 489 495
240 422 423 402 408 577 582
300 473 472 454 459 662 665
400 531 515 508 514 761 753
500 584 612 556 582 857 900
630 646 689 615 656 961 1039
800 717 758 681 721 1099 1179
1000 779 826 741 786 1212 1309
Technical Book MZ 11/25/11 8:54 AM Page 21
OCI/PBTB/Rev-001/010909
22
Current Ratings for Voltage gradefrom 6 kV to 30 kV
Basic Assumption:- Conductor Material – Aluminium Single Core Cables (Unarmoured)Ground Temperature – 20˚CAir Temperature – 30˚CThermal resistivity of soil – 150˚C-cm/wDepth of Laying – 800 mmDouble point bonding, Flat spacing – 2 OD from centre to centre
Ground In Single way Duct In Air
Single core, Unarmoured Single core, Unarmoured Single core, Unarmoured
Size Amp Amp Amp Amp Amp Amp
Trefoil Flat spaced Trefoil Flat Touching Trefoil Flat Touchingduct
25 108 112 102 103 127 130
35 129 134 122 123 154 157
50 152 157 144 146 184 189
70 186 192 176 178 230 236
95 221 229 210 213 280 287
120 252 260 240 242 324 332
150 281 288 267 271 368 376
185 317 324 303 307 424 432
240 367 373 351 356 502 511
300 414 419 397 402 577 586
400 470 466 451 457 673 676
500 527 540 501 514 760 799
630 588 616 559 586 875 932
800 666 691 633 657 1019 1077
1000 735 766 699 728 1144 1221
Technical Book MZ 11/25/11 8:54 AM Page 22
OCI/PBTB/Rev-001/010909
23
Current Ratings for Voltage gradefrom 6 kV to 30 kV
Basic Assumption:- Conductor Material – Aluminium Single Core Cables (Armoured)Ground Temperature – 20˚CAir Temperature – 30˚CThermal resistivity of soil – 150˚C-cm/wDepth of Laying – 800 mmDouble point bonding, Flat spacing – 2 OD from centre to centre
Ground In Single way Duct In Air
Single core, Armoured Single core, Armoured Single core, Armoured
Size Amp Amp Amp Amp Amp Amp
Trefoil Flat spaced Trefoil Flat spaced Trefoil Flat spaced
25 97 101 92 93 114 117
35 116 121 110 111 139 141
50 137 141 130 131 166 170
70 167 173 158 160 207 212
95 199 206 189 192 252 258
120 227 234 216 218 292 299
150 253 259 240 244 331 338
185 285 292 273 276 382 389
240 330 336 316 320 452 460
300 373 377 357 362 519 527
400 423 419 406 411 606 608
500 474 486 451 462 684 719
630 529 554 503 527 788 839
800 599 622 570 591 917 969
1000 662 689 629 656 1030 1099
Technical Book MZ 11/25/11 8:54 AM Page 23
OCI/PBTB/Rev-001/010909
Current Ratings for Voltage gradefrom 6 kV to 30 kV
Basic Assumption:- Conductor Material – Copper Three Core CablesGround Temperature – 20˚C Armoured/UnarmouredAir Temperature – 30˚CThermal resistivity of soil – 150˚C-cm/wDepth of Laying – 800 mmDouble point bonding
Ground In Single way Duct In Air
Size Amp Amp Amp Amp Amp Amp
Unarmoured Armoured Unarmoured Armoured Unarmoured Armoured
25 129 129 112 112 142 143
35 153 154 133 134 170 172
50 181 181 158 158 204 205
70 221 220 193 194 253 253
95 262 263 231 232 304 307
120 298 298 264 264 351 352
150 334 332 297 296 398 397
185 377 374 336 335 455 453
240 434 431 390 387 531 529
300 489 482 441 435 606 599
400 553 541 501 492 696 683
24
Technical Book MZ 11/25/11 8:54 AM Page 24
OCI/PBTB/Rev-001/010909
25
Current Ratings for Voltage grade from 6 kV to 30 kV
Basic Assumption:- Conductor Material – Aluminium Three Core CablesGround Temperature – 20˚C Armoured/UnarmouredAir Temperature – 30˚CThermal resistivity of soil – 150˚C-cm/wDepth of Laying – 800 mmDouble point bonding
Ground In Single way Duct In Air
Size Amp Amp Amp Amp Amp Amp
Unarmoured Armoured Unarmoured Armoured Unarmoured Armoured
25 100 100 87 87 110 111
35 119 119 103 104 132 133
50 140 140 122 123 158 159
70 171 171 150 150 196 196
95 203 204 179 180 236 238
120 232 232 205 206 273 274
150 260 259 231 231 309 309
185 294 293 262 262 355 354
240 340 338 305 304 415 415
300 384 380 346 343 475 472
400 438 432 398 393 552 545
Technical Book MZ 11/25/11 8:54 AM Page 25
OCI/PBTB/Rev-001/010909
26
0.6/1 kV - 1C & 2 Core Copper, XLPE insulatedArmoured/Unarmoured Cables
Thermal Resistivity of Soil: 1.5 K.m/WGround temperature: 20˚C
Depth of laying: 0.8 mAmbient Air temperature: 30˚C
Area In Air In Ground In Duct
mm2
Single core Trefoil Two CoreSingle core
Two coreSingle core
Two coreTrefoil Trefoil
Unarmoured Armoured Unarm Armoured Armoured Armoured Armoured Armoured
1.5 27 27 27 30 28 34 27 29
2.5 37 37 37 39 38 43 37 38
4 48 48 48 53 50 57 48 49
6 60 60 62 67 63 71 61 62
10 82 82 82 91 83 95 82 82
16 112 112 119 121 109 123 106 106
25 151 151 150 157 141 160 140 135
35 178 178 185 194 166 190 159 162
50 214 222 226 234 198 224 200 193
70 273 283 286 294 241 272 241 237
95 338 348 353 363 288 326 283 286
120 396 403 412 420 327 371 317 322
150 456 464 471 479 365 416 343 362
185 529 533 546 553 411 469 375 411
240 632 628 651 653 473 541 419 476
300 731 715 752 744 528 607 458 535
400 852 817 875 856 573 670 486 604
500 986 924 635 527
630 1139 1041 698 569
800 1293 1131 737 593
1000 1443 1227 782 623
Technical Book MZ 11/25/11 8:54 AM Page 26
OCI/PBTB/Rev-001/010909
27
0.6/1 kV - 1C & 2 Core Aluminium, XLPE insulatedArmoured/Unarmoured Cables
Thermal Resistivity of Soil: 1.5 K.m/WGround temperature: 20˚C
Depth of laying: 0.8 mAmbient Air temperature: 30˚C
Area In Air In Ground In Duct
mm2
Single core Trefoil Two CoreSingle core
Two coreSingle core
Two coreTrefoil Trefoil
Unarmoured Armoured Unarm Armoured Armoured Armoured Armoured Armoured
1.5 21 21 22 22 22 23 22 21
2.5 29 29 29 29 31 32 31 27
4 37 37 37 37 40 41 38 35
6 48 48 48 48 50 51 47 44
10 64 64 64 64 65 70 65 58
16 88 88 89 91 85 95 83 81
25 115 115 111 117 110 121 107 102
35 144 144 136 143 128 143 128 123
50 158 166 165 173 152 170 154 146
70 203 212 210 218 185 206 187 180
95 251 260 259 268 220 247 221 216
120 292 301 288 288 251 268 249 243
150 337 348 329 329 280 306 273 269
185 393 400 377 377 317 351 300 308
240 469 474 445 445 367 408 340 352
300 544 543 500 500 403 453 375 391
400 596 596 575 575 412 488 351 442
500 658 658 438 376
630 747 747 497 427
800 844 844 562 483
1000 948 948 631 542
Technical Book MZ 11/25/11 8:54 AM Page 27
OCI/PBTB/Rev-001/010909
28
0.6/1 kV - 3 and 4 Core Copper and Aluminium XLPE insulated cablesThermal Resistivity of Soil: 1.5 K.m/W
Ground temperature: 20˚CDepth of laying: 0.8 m
Ambient Air temperature: 30˚C
Area In Air In Ground In Duct
mm2 Unarmoured Armoured Armoured Armoured
Copper Aluminium Copper Aluminium Copper Aluminium Copper Aluminium
1.5 23 18 25 18 28 21 24 18
2.5 33 25 34 25 37 27 32 23
4 41 32 45 32 49 36 41 29
6 53 41 57 41 60 45 52 38
10 71 55 79 55 81 59 69 50
16 103 78 103 78 104 80 89 68
25 129 97 134 102 133 102 113 87
35 158 119 165 124 158 120 136 103
50 193 145 201 151 188 143 162 123
70 246 184 252 190 228 174 199 152
95 303 228 311 234 273 209 240 183
120 354 266 361 272 311 238 271 208
150 406 304 413 311 348 266 305 234
185 469 353 475 360 392 302 345 266
240 559 420 561 426 453 350 399 309
300 645 487 639 488 507 395 448 349
400 749 514 735 514 560 425 515 372
Technical Book MZ 11/25/11 8:54 AM Page 28
OCI/PBTB/Rev-001/010909
29
0.6/1 kV - 1C & 2 Core Copper, PVC insulated cablesThermal Resistivity of Soil: 1.5 K.m/W
Ground temperature: 20˚CDepth of laying: 0.8 m
Ambient Air temperature: 30˚C
Area In Air In Ground In Duct
mm2
Single core Trefoil Two CoreSingle core
Two coreSingle core
Two coreTrefoil Trefoil
Unarmoured Armoured Unarm Armoured Armoured Armoured Armoured Armoured
1.5 23 23 23 23 25 28 23 24
2.5 31 31 31 31 33 36 32 31
4 40 40 40 41 43 48 42 41
6 51 51 52 53 55 59 53 51
10 69 69 68 72 72 79 71 69
16 94 94 91 96 95 102 92 89
25 127 127 122 128 123 135 122 115
35 150 150 149 156 144 161 139 138
50 173 181 182 189 170 191 169 164
70 219 228 229 237 206 232 204 201
95 273 280 284 293 246 279 239 242
120 318 326 330 338 280 316 264 273
150 365 371 378 384 312 354 290 306
185 423 425 436 445 351 401 315 348
240 505 500 519 525 403 462 352 402
300 583 571 598 598 450 517 385 451
400 679 649 695 685 488 569 410 508
500 782 729 536 439
630 900 817 586 473
800 1018 881 614 493
1000 1134 949 648 516
Technical Book MZ 11/25/11 8:54 AM Page 29
OCI/PBTB/Rev-001/010909
30
0.6/1 kV - 1C & 2 Core Aluminium, PVC insulated cablesThermal Resistivity of Soil: 1.5 K.m/W
Ground temperature: 20˚CDepth of laying: 0.8 m
Ambient Air temperature: 30˚C
Area In Air In Ground In Duct
mm2
Single core Trefoil Two CoreSingle core
Two coreSingle core
Two coreTrefoil Trefoil
Unarmoured Armoured Unarm Armoured Armoured Armoured Armoured Armoured
16 74 74 70 72 74 78 72 68
25 97 97 90 92 96 101 93 86
35 121 121 110 113 111 120 111 103
50 129 133 134 136 129 142 133 122
70 164 166 169 174 156 175 163 152
95 202 205 209 213 188 210 192 182
120 236 239 242 242 213 233 216 212
150 271 272 276 276 239 266 240 234
185 315 317 316 316 271 305 262 267
240 376 375 374 374 313 355 298 306
300 436 431 420 420 352 394 329 340
400 500 500 483 483 359 425 305 384
500 552 552 381 327
630 627 627 432 371
800 709 709 489 420
1000 796 796 549 472
Technical Book MZ 11/25/11 8:54 AM Page 30
OCI/PBTB/Rev-001/010909
31
0.6/1 kV - 3C and 4 Core Copper and Aluminium PVC insulated cablesThermal Resistivity of Soil: 1.5 K.m/W
Ground temperature: 20˚CDepth of laying: 0.8 m
Ambient Air temperature: 30˚C
Area In Air In Ground In Duct
mm2 Unarmoured Armoured Armoured Armoured
Copper Aluminium Copper Aluminium Copper Aluminium Copper Aluminium
1.5 20 15 20 15 23 18 20 16
2.5 28 21 26 21 30 23 26 20
4 35 26 36 26 41 31 34 26
6 45 35 45 35 51 39 43 33
10 59 46 62 46 67 51 58 43
16 79 59 82 61 87 66 75 56
25 103 78 109 80 113 86 96 72
35 128 96 133 98 135 102 115 87
50 156 117 162 120 159 121 137 104
70 197 149 205 151 195 148 170 129
95 243 183 252 188 234 179 204 156
120 284 212 291 218 266 204 230 176
150 324 243 334 248 298 228 258 197
185 374 281 383 288 336 259 293 225
240 446 336 451 344 388 302 338 264
300 512 387 514 396 434 341 379 299
400 593 431 589 431 477 370 433 323
Technical Book MZ 11/25/11 8:54 AM Page 31
OCI/PBTB/Rev-001/010909
Table 1 – Correction factors for ambientair temperatures other than 30˚C
Maximum conductor Ambient air temperature
temperature ˚C˚C
20 25 35 40 45 50 55 60
90 1,08 1,04 0,96 0,91 0,87 0,82 0,76 0,71
Table 2 – Correction factors for ambient groundtemperatures other than 20˚C
Maximum conductor Ground temperaturetemperature ˚C
˚C10 15 25 30 35 40 45 50
90 1,07 1,04 0,96 0,93 0,89 0,85 0,80 0,76
Table 3 – Correction factors for depth of layingOther than 0.8 m for direct buried cables
Single-core cables
Depth of laying Nominal conductor size Three-corem cables
≤185 mm2 >185 mm2
0,5 1,04 1,06 1,04
0,6 1,02 1,04 1,03
1 0,98 0,97 0,981,25 0,96 0,95 0,961,5 0,95 0,93 0,95
1,75 0,94 0,91 0,942 0,93 0,90 0,93
2,5 0,91 0,88 0,913 0,90 0,86 0,90
32
Technical Book MZ 11/25/11 8:54 AM Page 32
OCI/PBTB/Rev-001/010909
33
Table 4 – Correction factors for depths of layingother than 0.8 m for cables in ducts
Single-core cables
Depth of laying Nominal conductor size Three-corem cables
≤185 mm2 >185 mm2
0,5 1,04 1,05 1,03
0,6 1,02 1,03 1,02
1 0,98 0,97 0,991,25 0,96 0,95 0,971,5 0,95 0,93 0,96
1,75 0,94 0,92 0,952 0,93 0,91 0,94
2,5 0,91 0,89 0,933 0,90 0,88 0,92
Table 5 – Correction factors for soil thermal resistivitiesother than 1,5 K.m/W for direct buried single-core cables
Nominal area Values of soil thermal resistivityof conductor K.m/W
mm20,7 0,8 0,9 1 2 2.5 3
16 1,29 1,24 1,19 1,15 0,89 0,82 0,7525 1,30 1,25 1,20 1,16 0,89 0,81 0,7535 1,30 1,25 1,21 1,16 0,89 0,81 0,7550 1,32 1,26 1,21 1,16 0,89 0,81 0,74
70 1,33 1,27 1,22 1,17 0,89 0,81 0,7495 1,34 1,28 1,22 1,18 0,89 0,80 0,74120 1,34 1,28 1,22 1,18 0,88 0,80 0,74150 1,35 1,28 1,23 1,18 0,88 0,80 0,74
185 1,35 1,29 1,23 1,18 0,88 0,80 0,74240 1,36 1,29 1,23 1,18 0,88 0,80 0,73300 1,36 1,30 1,24 1,19 0,88 0,80 0,73400 1,37 1,30 1,24 1,19 0,88 0,79 0,73
Technical Book MZ 11/25/11 8:54 AM Page 33
OCI/PBTB/Rev-001/010909
Table 6 – Correction factors for soil thermal resistivitiesother than 1,5 K.m/W single-core cables in buried ducts
Nominal area Values of soil thermal resistivityof conductor K.m/W
mm20,7 0,8 0,9 1 2 2.5 3
16 1,20 1,17 1,14 1,11 0,92 0,85 0,7925 1,21 1,17 1,14 1,12 0,91 0,85 0,7935 1,21 1,18 1,15 1,12 0,91 0,84 0,7950 1,21 1,18 1,15 1,12 0,91 0,84 0,78
70 1,22 1,19 1,15 1,12 0,91 0,84 0,7895 1,23 1,19 1,16 1,13 0,91 0,84 0,78120 1,23 1,20 1,16 1,13 0,91 0,84 0,78150 1,24 1,20 1,16 1,13 0,91 0,83 0,78
185 1,24 1,20 1,17 1,13 0,91 0,83 0,78240 1,25 1,21 1,17 1,14 0,90 0,83 0,77300 1,25 1,21 1,17 1,14 0,90 0,83 0,77400 1,25 1,21 1,17 1,14 0,90 0,83 0,77
Table 7 – Correction factors for soil thermal resistivitiesother than 1,5 K.m/W for direct buried three-core cables
Nominal area Values of soil thermal resistivityof conductor K.m/W
mm20,7 0,8 0,9 1 2 2.5 3
16 1,23 1,19 1,16 1,13 0,91 0,84 0,7825 1,24 1,20 1,16 1,13 0,91 0,84 0,7835 1,25 1,21 1,17 1,13 0,91 0,83 0,7850 1,25 1,21 1,17 1,14 0,91 0,83 0,77
70 1,26 1,21 1,18 1,14 0,90 0,83 0,7795 1,26 1,22 1,18 1,14 0,90 0,83 0,77120 1,26 1,22 1,18 1,14 0,90 0,83 0,77150 1,27 1,22 1,18 1,15 0,90 0,83 0,77
185 1,27 1,23 1,18 1,15 0,90 0,83 0,77240 1,28 1,23 1,19 1,15 0,90 0,83 0,77300 1,28 1,23 1,19 1,15 0,90 0,82 0,77400 1,28 1,23 1,19 1,15 0,90 0,82 0,76
34
Technical Book MZ 11/25/11 8:54 AM Page 34
OCI/PBTB/Rev-001/010909
35
Table 8 – Correction factors for soil thermal resistivitiesother than 1,5 K.m/W for three-core cables in ducts
Nominal area Values of soil thermal resistivityof conductor K.m/W
mm20,7 0,8 0,9 1 2 2.5 3
16 1,12 1,11 1,09 1,08 0,94 0,89 0,8425 1,14 1,12 1,10 1,08 0,94 0,89 0,8435 1,14 1,12 1,10 1,08 0,94 0,88 0,8450 1,14 1,12 1,10 1,08 0,94 0,88 0,84
70 1,15 1,13 1,11 1,09 0,94 0,88 0,8395 1,15 1,13 1,11 1,09 0,94 0,88 0,83120 1,15 1,13 1,11 1,09 0,93 0,88 0,83150 1,16 1,13 1,11 1,09 0,93 0,88 0,83
185 1,16 1,14 1,11 1,09 0,93 0,87 0,83240 1,16 1,14 1,12 1,10 0,93 0,87 0,82300 1,17 1,14 1,12 1,10 0,93 0,87 0,82400 1,17 1,14 1,12 1,10 0,92 0,86 0,81
Table 9 – Correction factors for groups of three-core cablesIn horizontal formation laid direct in the ground
Number of Spacing between cable centrescables in mm
group Touching 200 400 600 800
2 0,80 0,86 0,90 0,92 0,94
3 0,69 0,77 0,82 0,86 0,89
4 0,62 0,72 0,79 0,83 0,87
5 0,57 0,68 0,76 0,81 0,85
6 0,54 0,65 0,74 0,80 0,84
7 0,51 0,63 0,72 0,78 0,83
8 0,49 0,61 0,71 0,78 –
9 0,47 0,60 0,70 0,77 –
10 0,46 0,59 0,69 – –
11 0,45 0,57 0,69 – –
12 0,43 0,56 0,68 – –
Technical Book MZ 11/25/11 8:54 AM Page 35
OCI/PBTB/Rev-001/010909
Table 10 – Correction factors for groups of three-phase circuitsof single-core cables laid direct in the ground
Number of Spacing between group centrescables in mm
group Touching 200 400 600 800
2 0,73 0,83 0,88 0,90 0.92
3 0,60 0,73 0,79 0,83 0,86
4 0,54 0,68 0,75 0,80 0,84
5 0,49 0,63 0,72 0,78 0,82
6 0,46 0,61 0,70 0,76 0,81
7 0,43 0,58 0,68 0,75 0,80
8 0,41 0,57 0,67 0,74 –
9 0,39 0,55 0,66 0,73 –
10 0,37 0,54 0,65 – –
11 0,36 0,53 0,64 – –
12 0,35 0,52 0,64 – –
Table 11 – Correction factors for groups of three-core cablesIn single way ducts in horizontal formation
Number of Spacing between duct centrescables in mm
group Touching 200 400 600 800
2 0,85 0,88 0,92 0,94 0,95
3 0,75 0,80 0,85 0,88 0,91
4 0,69 0,75 0,82 0,86 0,89
5 0,65 0,72 0,79 0,84 0,87
6 0,62 0,69 0,77 0,83 0,87
7 0,59 0,67 0,76 0,82 0,86
8 0,57 0,65 0,75 0,81 –
9 0,55 0,64 0,74 0,80 –
10 0,54 0,63 0,73 – –
11 0,52 0,62 0,73 – –
12 0,51 0,61 0,72 – –
36
Technical Book MZ 11/25/11 8:54 AM Page 36
OCI/PBTB/Rev-001/010909
37
Table 12 – Correction factors for groups of three-phase circuitsof single-core cables in single-way ducts
Number of Spacing between duct group centrescables in mm
group Touching 200 400 600 800
2 0,78 0,85 0,89 0,91 0,93
3 0,66 0,75 0,81 0,85 0,88
4 0,59 0,70 0,77 0,82 0,86
5 0,55 0,66 0,74 0,80 0,84
6 0,51 0,64 0,72 0,78 0,83
7 0,48 0,61 0,71 0,77 0,82
8 0,46 0,60 0,70 0,76 –
9 0,44 0,58 0,69 0,76 –
10 0,43 0,57 0,68 – –
11 0,42 0,56 0,67 – –
12 0,40 0,55 0,67 – –
Technical Book MZ 11/25/11 8:54 AM Page 37
OCI/PBTB/Rev-001/010909
Table 13 – Reduction factors for groups of more than one multi-core cable in air – To be applied to the current-carrying capacity
for one multi-core cable in free air
Method of Installation Number Number of cablesof trays 1 2 3 4 6 9
Touching 1 1,00 0,88 0,82 0,79 0,76 0,73
Cables on 2 1,00 0,87 0,80 0,77 0,73 0,68
perforated trays 3 1,00 0,86 0,79 0,76 0,71 0,66
Spaced 1 1,00 1,00 0,98 0,95 0,91 –
2 1,00 0,99 0,96 0,92 0,87 –
3 1,00 0,98 0,95 0,91 0,85 –
Touching 1 1,00 0,88 0,82 0,78 0,73 0,72
2 1,00 0,88 0,81 0,76 0,71 0,70
Cables on vertical
perforated trays
1 1,00 0,91 0,89 0,88 0,87 –Spaced 2 1,00 0,91 0,88 0,87 0,85 –
Touching 1 1,00 0,87 0,82 0,80 0,79 0,78
2 1,00 0,86 0,80 0,78 0,76 0,73
Cables on ladder 3 1,00 0,85 0,79 0,76 0,73 0,70
supports, cleats
etc. Spaced 1 1,00 1,00 1,00 1,00 1,00 –
2 1,00 0,99 0,98 0,97 0,96 –
3 1,00 0,98 0,97 0,96 0,93 –
NOTE 1: Values given are averages for the cable types and range of conductor sizes considered. Thespread of values is generally less than 5%.NOTE 2: Factors apply to single layer groups of cables as shown above and do not apply when cablesare installed in more than one layer touching each other. Values for such installations may besignificantly lower and must be determined by an appropriate method.NOTE 3: Values are given for vertical spacing between trays of 300 mm and at least 20 mm betweentrays and wall. For closer spacing, the factors should be reduced.NOTE 4: Values are given for horizontal spacing between trays of 225 mm with trays mounted back toback. For closer spacing, the factors should be reduced.
38
Technical Book MZ 11/25/11 8:54 AM Page 38
OCI/PBTB/Rev-001/010909
39
Table 14 – Reduction factors for groups of more than one circuit ofsingle-core cables (Note 2) –
To be applied to the current-carrying capacity for one circuit ofsingle-core cables in free air
Method of Installation Number ofNumber of three-phase Use as a
trayscircuits (Note 5) multiplier to
1 2 3 rating for
Touching 1 0,98 0,91 0,87 Three cables
Perforated trays in horizontal
(Note 3) 2 0,96 0,87 0,81 formation
3 0,95 0,85 0,78
Touching 1 1,00 0,97 0,96Ladder Three cables
supports, 2 0,98 0,93 0,89 in horizontalcleats etc. formation(Note 3) 3 0,97 0,90 0,86
Perforated 1 1,00 0,98 0,96trays 2 0,97 0,93 0,89
(Note 3) 3 0,96 0,92 0,86
Vertical 1 1,00 0,91 0,89Perforated Three cables
trays 2 1,00 0,90 0,86 in trefoil(Note 4)
Spacedformation
Ladder 1 1,00 1,00 1,00supports.
cleats, etc. 2 0,97 0,95 0,93(Note 3)
3 0,96 0,94 0,90
NOTE 1: Values given are averages for the cable types and range of conductor sizes considered. Thespread of values is generally less than 5%.NOTE 2: Factors are given for single layers of cables (or trefoil groups) as shown in the table and donot apply when cables are installed in more than one layer touching each other. Values for suchinstallations may be significantly lower and should be determined by an appropriate method.NOTE 3: Values are given for vertical spacings between trays of 300 mm. For closer spacing, the factorsshould be reduced.NOTE 4: Values are given for horizontal spacing between trays of 225 mm with trays mounted back toback. For closer spacing, the factors should be reduced.NOTE 5: For circuits having more than one cable in parallel per phase, each three phase set ofconductors should be considered as a circuit for the purpose of this table.
Technical Book MZ 11/25/11 8:54 AM Page 39
OCI/PBTB/Rev-001/010909
Permissible short-circuit temperatures and rated short-time currentdensities
1 2 3 4 5 6 7 8 9 10
Permissible short circuit Conductor temperature at the beginning of short circuit in ˚C
temperature in ˚C 90 80 70 60 50 40 30 20
Rated short-time current density in A/mm2 for a ratedshort-circuit duration of 1 second
Copper Conductors 250 143 149 154 159 165 170 176 181
Aluminium Conductors 250 94 98 102 105 109 113 116 120
1 2 3 4 5 6 7 8 9 10
Permissible short circuit Conductor temperature at the beginning of short circuit in ˚C
temperature in ˚C 90 80 70 60 50 40 30 20
Rated short-time current density in A/mm2 for a ratedshort-circuit duration of 1 second
≤ 300 mm2 160 – – 115 122 129 136 143 150
300 mm2 140 – – 103 111 118 126 133 140
40
Cables with(PVC Insulation)
Copper Conductor
Cables with(XLPE Insulation)
Technical Book MZ 11/25/11 8:54 AM Page 40
OCI/PBTB/Rev-001/010909
41
Permissible Short Circuit current of XLPEinsulated power cables (copper conductors)
Technical Book MZ 11/25/11 8:54 AM Page 41
OCI/PBTB/Rev-001/010909
42
Permissible Short Circuit current of XLPEinsulated power cables (Aluminum conductors)
Technical Book MZ 11/25/11 8:54 AM Page 42
OCI/PBTB/Rev-001/010909
43
Recommended Cables Storage Practices
Storage and Storage Maintenance:
1. Finished cables have no established shelf-life. Moisture and atmospheric conditions cancause exposed conductors to oxidize and discolor. Uncovered/unsheltered cable willdegrade due to exposure to direct sunlight and/or the elements. If the cables areprotected, there should be no degradation of the insulation.
2. In general, any cable for use indoors should be stored indoors. Any cable suitable forinstallation outdoors is suitable for storage outdoors. Cables stored outdoors shouldhave the ends sealed to prevent moisture ingress into the cable.
3. Cables should be stored in a sheltered area. While on the reel, cable should be coveredwith Masonite or a dark film wrap (to block the sun’s rays and shield them from theelements).
4. Cable reels must remain in an upright position. Cable reels must not be stored on theirsides.Reels must not be stacked.
5. Cable reels should be stored with the protective covering or lagging in place. If a lengthof cable has been cut from the reel, the cable end should be immediately resealed toprevent moisture from entering it. If a part length is returned to storage, the reel’sprotective covering should be restored.
6. Wooden reels should be stored off the ground to prevent rotting. Reels should be storedon a flat, hard surface so that the flanges do not sink into the earth. The weight of thereel and cable must be carried at all times by the reel flanges.
7. Cable reels and lagging must not be stored in direct contact with water or dampnessfor extended periods of time. Timbers or metal supports must be placed under the reelflanges to provide elevated storage of the reels away from direct contact with water ordamp soil.
8. Reels should be stored in an area where construction equipment, falling or flyingobjects or other materials will not touch the cable.
9. Cable should be stored in an area where chemicals or petroleum products will not bespilled or sprayed on the cables.
10. Cables should be stored in an area away from open fires or sources of high heat.
11. If the cables are stored in a secure area and not exposed to the effects of the weather,an annual inspection should be satisfactory.
12. Where the reels are exposed to the weather, a bi-monthly inspection should beperformed to observe any sign of deterioration.
13. If the reels are exposed in a non-secure area, policing of the area at frequent intervalsmay be required depending on circumstances.
14. Records of delivery date, manufacturer, installation date, any extenuatingcircumstances, along with all test reports should be kept on file.
Technical Book MZ 11/25/11 8:54 AM Page 43
OCI/PBTB/Rev-001/010909
Guideline for permissible pulling force for laying of low voltageand medium voltage cables:
Means of pulling Type of Cables Formula Factor
With pulling head All types of Cables P = σ. A σ = 50 N/mm2 (Copper Conductor)attached to conductor σ = 30 N/mm2 (Aluminium Conductor)
With pulling stocking Unarmoured cable1) P = σ. A σ = 50 N/mm2 (Copper Conductor)σ = 30 N/mm2 (Aluminium Conductor)
All Wire armoured Cables P = K.D2 K = 9 N/mm2
1) when laying 3 single core cables simultaneously with a common pulling stocking, the samemaximum pulling force applies, whereas the pulling force for 3 laid-up single core cables is 3times that of a single-core and for 3 non-laid-up single core cables is 2 times that of a singlecore.
P = Pull in NewtonsA = total cross-sectional area in mm2 of all conductors (screen/concentric conductor not to beincluded)D = Overall diameter of cableσ = permissible tensile stress of conductor in N/mm2
K = empirically derived factor in N/mm2.
44
Technical Book MZ 11/25/11 8:54 AM Page 44
OCI/PBTB/Rev-001/010909
45
Minimum Installation Bending Radius
Cables for fixed wiring up to and including 450/750 V:
Insulation Conductors Construction Overall diameter Minimum(mm) radius
XLPE or PVC Copper and Aluminium, Unarmoured Upto 10 mm 3Da
Solid or Stranded circular 10 to 25 mm 4Db
Above 25 mm 6D
D = overall diametera 2D for single-core cables with circular stranded conductors installed in conduits, ducting ortrunking.b 3D for single-core cables with circular stranded conductors installed in conduits, ducting ortrunking.
XLPE and PVC insulated cables rated 0.6/1 kV and 1.9/3.3 kV:
Conductor Construction Minimumradius
Circular Copper Both Armoured and Unarmoured 6D
Shaped Copper Both Armoured and Unarmoured 8D
Solid Alumiuium Both Armoured and Unarmoured 8D
XLPE and insulated cables 6.6 kV to 33 kV:
Type of Cable Minimum Radius
During Laying Adjacent to joints orterminations
Single Core:(a) Unarmoured 20D 15D(b) Armoured 15D 12D
Three Core:(c) Unarmoured 15D 12D(d) Armoured 12D 10D
Technical Book MZ 11/25/11 8:54 AM Page 45
OCI/PBTB/Rev-001/010909
D.C. Voltage Test:The purpose of the test is to check that the cable laying has been done correctly. The cablemay, for example, have been accidentally damaged during shipping, handling, storing, pullingand backfilling. Since it can be assumed that the cable insulation has not been damaged as longas the jacket is intact, the same can be checked by a d.c. voltage-withstand test.
A direct voltage of 4 kV per millimeter of specified thickness of extruded oversheath shall beapplied with a maximum of 10 kV for a period of 1 minute between each metal sheath ormetallic screen and the ground.
For the test to be effective, it is necessary that the ground makes good contact with all of theouter surfaces of the oversheath. A conductive layer on the oversheath can assist in thisregard.
Electrical tests after installation
Voltage Test after installation:
1) Insulation test:
a) Test for 5 minutes with the phase to phase voltage of the system applied between theconductor and the metallic screen/sheath.
b) Test for 24 hours with the normal operating voltage of the system.
2) DC Testing:
As an alternative to a.c. test, a d.c. test as per IEC 60502-2 OR BS 6622 mentioned belowmay be applied for 15 minutes.
These tests are intended for cables immediately after installation and not for cables thathave been in service.
The test voltage is to be applied between each conductor and the armour and/or screensafter all terminating and jointing has been completed, but before connection to thesystem.
Cable Voltage Designation D.C. Voltage D.C. Voltageas per IEC 60502 (4Uo) as per BS 6622
kV kV kV
3.5/6 kV (IEC), 3.8/6.6 kV (BS) 14 15
6/10 kV (IEC), 6.35/11 kV (BS) 24 25
8.7/15 kV (IEC), 8.7/15 kV (BS) 35 37
12/20 kV (IEC) 12.7/22 kV (BS) 48 50
18/30 kV (IEC), 19/33 kV (BS) 72 76
Note 1: A d.c. test may endanger the insulation system under test.Note 2: For installations which have been in use, lower voltages and/or shorter durations may be used.Values should be negotiated taking into account the age, environment, history of breakdowns and thepurpose of carrying out the test.
46
Technical Book MZ 11/25/11 8:54 AM Page 46
OCI/PBTB/Rev-001/010909
47
Definition of Tests for Cables1) Routine Tests:
Tests made by the manufacturer on each manufactured length of cable to check that eachlength meets the specified requirements.
Tests:a) Measurement of electrical resistance of conductorsb) Voltage testsc) Partial Discharge test (for XLPE cables with rated voltages 6 kV and above)
2) Sample Tests:Tests made by the manufacturer on samples of completed length or components takenfrom a completed cable, at a frequency, to verify that the finished product meets thespecified requirements.
Tests:a) Conductor examinationb) Check of dimensionsc) 4 hour voltage test for cables with rated voltage 6 kV and aboved) Hot set test for XLPE insulation.
3) Type Tests:Tests made before supplying on a general commercial basis, a type of cable covered by IECstandard, in order to demonstrate satisfactory performance characteristics to meet theintended application.
Note: These tests are such that, after they have been made, need not be repeated, unlesschanges are made in the cable materials or manufacturing processes which might changethe performance characteristics.
Tests: Shall be as per attached Table for Cables.
Technical Book MZ 11/25/11 8:54 AM Page 47
OCI/PBTB/Rev-001/010909
48
List of Routine, Sample and Type tests for LV Cables
Test Designation
No. Description of the Test Routine Sample Type
Elec. NonElec.
1 Measurement of electrical resistance of conductor 3 3
2 Voltage test (2.5Uo + 2 kV) 3
3 Measurement of thickness of insulation and non-metallic sheaths 3 3
4 Measurement of Cable armour dimensions 3
5 Measurement of Cable overall diameter 3
6 Hot set test for XLPE insulation 3 3
7 Insulation resistance measurement at normal and operating temp. 3
8 Measurement of volume resistivity for XLPE insulation 3
9 4 hours voltage test (4Uo) 3
10 Determining the mechanical properties of insulation before and after ageing 3
11 Determining the mechanical properties of non-metallic sheath before and after ageing. 3
12 Ageing tests on pieces of complete cable to check compatibility 3
13 Loss of mass test on PVC sheath 3
14 Pressure test at high temperature on sheaths 3
15 Heat shock test for PVC sheaths 3
16 Tests on PVC sheaths at low temperature 3
17 Water absorption test for XLPE insulation 3
18 Shrinkage test for XLPE insulation 3
19 Carbon black content of PE sheaths 3
20 Test under fire conditions (if required) 3
21 Smoke emission test for Halogen free cables 3
22 Acid Gas emission test for Halogen free cables 3
23 pH, conductivity, fluorine content test for Halogen free cables 3
24 Water absorption test for halogen free sheath 3
Technical Book MZ 11/25/11 8:54 AM Page 48
OCI/PBTB/Rev-001/010909
49
List of Routine, Sample and Type tests for MV Cables
Test Designation
No. Description of the Test Routine Sample Type
Elec. NonElec.
1 Measurement of electrical resistance of conductor 3 3
2 Partial discharge test 3
3 Voltage test (3.5Uo) 3
4 Measurement of thickness of insulation and non-metallic sheaths 3 3
5 Measurement of armour dimensions 3
6 Measurement of Cable overall diameter 3
7 Hot set test for XLPE insulation 3 3
8 Bending test followed by partial discharge 3
9 Tangent Delta Measurement 3
10 Heating cycle voltage test, followed by partial discharge test 3
11 Impulse withstand test followed by a power frequency voltage test 3
12 4 hours Voltage test (4Uo) 3 3
13 Resistivity of semiconducting layers 3
14 Insulation resistance measurement at normal and operating temp. 3
15 Determining the mechanical properties of insulation before and after ageing 3
16 Determining the mechanical properties of non-metallic sheath before and after ageing 3
17 Ageing tests on pieces of complete cable to check compatibility 3
18 Loss of mass test on PVC sheath 3
19 Pressure test at high temperature on sheaths 3
20 Heat shock test for PVC sheaths 3
21 Tests on PVC sheaths at low temperature 3
22 Water absorption test for XLPE insulation 3
23 Shrinkage test for XLPE insulation 3
24 Shrinkage test for PE outer sheath 3
25 Strippability test (for strippable insulation screen only) 3
26 Carbon black content of PE sheaths 3
27 Test under fire conditions (if required) 3
28 Water penetration test (if required) 3
Technical Book MZ 11/25/11 8:54 AM Page 49
OCI/PBTB/Rev-001/010909
Insulation Resistance – Significance and Use
Insulation Resistance (IR) evaluates Insulation integrityIR is used as:
a) A Quality Tool at the time of manufacturing of cable
b) After installation, to check proper installation.
c) As a preventive maintenance task
d) For Trouble shooting
Method of MeasurementIR is measured by applying voltage (generally stabilised DC) cross a dielectric, measuring theamount of current flowing through the dielectric and then calculating resistance.Let’s clarify our use of the term “current.” We’re talking about leakage current. The resistancemeasurement is in megohms.
After connection, the test voltage is applied for 1 min. (This is a standard industry parameterthat allows the client to make relatively accurate comparisons of reading from past tests doneby other technicians.) During this interval, the resistance reading should drop or remainrelatively steady. Larger insulation systems will show a steady decrease; smaller systems willremain steady because the capacity and absorption currents drop to zero faster than on largesystems. After 1 minute the reading should be recorded.
Precautions –1) When performing insulation resistance testing, consistency must be maintained because
electrical insulation will exhibit dynamic behavior during the course of the test; whether thedielectric is “good” or “bad” To evaluate a number of test results on the same piece ofequipment, the test should be conducted the same way and under the relatively sameenvironmental parameters, each and every time.
2) Insulation resistance is temperature-sensitive. When temperature increases, insulationresistance decreases, and vice versa.
For a cable length of L,
IR = VR x Loge D
2πL dWhere VR = Volume Resistivity of Insulation in ohm – cm
D = Outer dia over insulation (mm)d = Inner dia of insulation. (mm)L = Length of cable in cm.IR = Insulation Resistance in ohms.
50
( )
Technical Book MZ 11/25/11 8:54 AM Page 50
OCI/PBTB/Rev-001/010909
51
Calculated Minimum Insulation ResistanceValues for
0.6/1 kV XLPE Insulated and PVC Insulated Cables:
Size PVC Insulated Cables XLPE Insulated Cablesmm2 (M.ohm-km) at 20˚C (M.ohm-km) at 20˚C
1.5 10 895
2.5 9 840
4 8 700
6 7 590
10 7 475
16 6 385
25 5 390
35 5 335
50 5 320
70 5 295
95 5 255
120 5 245
150 5 260
185 5 265
240 5 245
300 5 230
400 5 230
500 5 225
630 5 235
Technical Book MZ 11/25/11 8:54 AM Page 51
OCI/PBTB/Rev-001/010909
Calculated Minimum Insulation Resistance Values for Medium Voltage XLPE Insulated Cables:
SizeMinimum Insulation Resistance at 20˚C
(mm2)6 kV 10 kV 15 kV 20 kV 30 kV
M.ohm-km M.ohm-km M.ohm-km M.ohm-km M.ohm-km
25 845 1060 1300 – –
35 765 970 1185 1365 –
50 680 870 1075 1240 1590
70 600 770 955 1110 1435
95 530 685 855 995 1300
120 480 625 785 910 1205
150 445 580 730 855 1130
185 405 530 670 785 1045
240 370 470 600 705 945
300 360 430 550 650 875
400 345 385 495 590 795
500 330 350 450 535 725
630 295 310 400 480 655
52
Technical Book MZ 11/25/11 8:54 AM Page 52
OCI/PBTB/Rev-001/010909
53
What is voltage drop?
A voltage drop in an electrical circuit normally occurs when current is passedthrough the wire.
The greater the resistance of the circuit, the higher the voltage drop.
How much voltage drop is acceptable?
The National Electrical Code states that a voltage drop of 4% at the furthestreceptacle in a branch wiring circuit is acceptable for normal efficiency. In a120 volt 15 ampere circuit, this means that there should be no more than a4.8 volt drop (115.2 volts)
What causes “excess voltage drop” in a branch circuit?
The cause is usually:
1. High resistance connections at wiring junctions or outlet terminals,usually caused by:-• poor splices anywhere in the circuit• loose or intermittent connections anywhere in the circuit• corroded connections anywhere in the circuit• Inadequate seating of wire in the slot connection on backwired “push-
in-type” receptacles and switches.
2. The wire does not meet code standards (not heavy enough gauge for thelength of the run).
What are the consequences of “excess” voltage drop in a circuit?
Excess voltage drop can cause the following conditions:
1. Low voltage to the equipment being powered, causing improper, erratic,or no operation – and damage to the equipment.
2. Poor efficiency and wasted energy.
3. Heating at a high resistance connection/splice may result in a fire at highampere loads.
At what % of voltage drop, does a circuit become hazardous?That would depend on how much current is flowing through the highresistance connector; resistance of connector, and the following factors:-
1. Is the high resistance connection in contact with a combustible material?
2. Is there air flow to dissipate the heat?
3. Is the area around the connection insulated, so that heat cannot escape.
Technical Book MZ 11/25/11 8:54 AM Page 53
OCI/PBTB/Rev-001/010909
Voltage Drop
The size of every bare conductor or cable conductor should be such that the drop in voltagefrom consumer’s terminals to any point in the installation does not exceed 4% of the declaredor nominal voltage when the conductors are carrying full load, but disregarding the startingconditions. This requirement shall not apply to wiring fed from extra low voltage secondary ofa transformer. The approximate voltage drop in average circuits such as lighting and domesticheating loads for XLPE insulated cables is:
Conductor cross- Permissible Voltage Permissible Voltage Permissible Voltagesectional area Drop (Vp) Drop (Vp) Drop (Vp)
(Single Core Cables) (Two Core Cables) (3 & 4 Core Cables)
mm2 mV/A/m mV/A/m mV/A/m
1.5 – 30.86 26.72
2.5 – 18.9 16.36
4 – 11.76 10.18
6 – 7.86 6.804
10 4.05 4.67 4.04
16 2.55 2.94 2.54
25 1.618 1.86 1.612
35 1.173 1.348 1.166
50 0.874 1.0 0.866
70 0.616 0.702 0.607
95 0.456 0.516 0.446
120 0.373 0.418 0.362
150 0.316 0.351 0.304
185 0.267 0.295 0.255
240 0.223 0.244 0.211
300 0.197 – 0.185
400 0.179 – 0.165
500 0.165 – 0.151
630 0.162 – 0.142
800 0.15 – –
1000 0.144 – –
54
Technical Book MZ 11/25/11 8:54 AM Page 54
OCI/PBTB/Rev-001/010909
55
Selection of Cable Size Based on Voltage Drop:
Based on the required ampacity and installation conditions, a suitable cable size is chosen,cross-checked with the voltage drop as follows:
Vp x 1000 x VVcal =
I x L x 100
where:Vp = Max. permissible voltage drop (say 4%)V = System voltage (say 415 V)L = Length in metersI = Current in Amps
Suppose a 300 meters 3 core XLPE insulated cable is to carry 100 Amps and the supply voltageis 415 V then Vcal = 4 x 1000 x 415 = 0.553 mV/A/m. Therefore a cable size whose voltage
100 x 300 x 100drop is less than 0.553 is to be selected. Hence, for the case above , cable size 95 mm2 maybe selected.
Technical Book MZ 11/25/11 8:54 AM Page 55
OCI/PBTB/Rev-001/010909
Bonding and Earthing Methods
Method Induced Voltage at Sheath voltage ApplicationCable ends limiters required
Both Ends Bonded No No Substations, short lengthsSingle point bonded Yes Yes circuit length upto 1 Km.Cross Bonding Only at cross Yes Long length circuits
bonding points
Both Ends Bonded Single point bonded
Surge arresterEarth continuity wire
Induced Voltage Distribution Induced Voltage DistributionMost safe but due to circulating More ampacity. Surge arrester required at open end.current ampacity reduces Induced voltage is proportional to length of cable and
so limitations on circuit length.
Cross Bonding
Induced Voltage DistributionMost popular system of earthing for long circuits.Ampacity is like single point bonded system but costly installations due to requirement ofmore number of Surge limiters, each at crossing.
56
Technical Book MZ 11/25/11 8:54 AM Page 56
OCI/PBTB/Rev-001/010909
57
Comparison of XLPE & PVC Insulated Power Cables
PVC XLPE1. Operating Conductor Temperature: 70˚C Operating Conductor Temperature: 90˚C
2. Lower current carrying capacity. Higher current carrying capacity.
3. Maximum Temperature Limit under Maximum Temperature Limit undershort circuit: 160˚C short circuit: 250˚C
4. Lower emergency overload capacity. Higher emergency overload capacity.
5. Lower moisture resistance High moisture resistance.
6. Insulation Resistance Lower Insulation Resistance almost 1000 times higher
7. Inferior properties to withstand vibration & Higher properties to withstand vibrationheat impacts. and heat impacts.
8. Heavier as specific gravity is 1.42, Lighter as specific gravity is 0.92 and
therefore more difficult to install. easier to install.
9. Heat dissipation slower as Thermal Insulation dissipation heat faster as
Resistivity is 7˚C m/w. Thermal Resistivity is 3.5˚Cm/w.
10. Higher “Loss angle” of 0.01 Lower “Loss angle” of 0.004
11. Installation Technique: simple Installation Technique: simple.
Technical Book MZ 11/25/11 8:54 AM Page 57
OCI/PBTB/Rev-001/010909
Nominal thickness of PVC/A insulationas per IEC 60502-1
Nominal cross-sectional Nominal thickness of insulation at rated voltagearea of conductor Uo/U (Um)
0,6/1 (1,2) kV 1,8/3 (3,6) kvmm2 mm mm
1,5 and 2,5 0,8 –4 and 6 1,0 –
10 and 16 1,0 2,225 and 35 1,2 2,250 and 70 1,4 2,2
95 and 120 1,6 2,2150 1,8 2,2185 2,0 2,2240 2,2 2,2300 2,4 2,4
400 2,6 2,6
500 to 800 2,8 2,81000 3.0 3,0
Note: Any conductor cross-section smaller than those given in this table is not recommended
Nominal thickness of XLPE Insulation as per IEC 60502-1
Nominal cross-sectional Nominal thickness of insulation at rated voltagearea of conductor Uo/U (Um)
0,6/1 (1,2) kV 1,8/3 (3,6) kvmm2 mm mm
1,5 and 2,5 0,7 –4 and 6 0,7 –
10 and 16 0,7 2,025 and 35 0,9 2,0
50 1,0 2,070 and 95 1,1 2,0
120 1,2 2,0150 1,4 2,0185 1,6 2,0240 1,7 2,0300 1,8 2,0400 2,0 2,0500 2,2 2,2630 2,4 2,4800 2,6 2,6
1000 2,8 2,8
NOTE: Any conductor cross-section smaller than those given in this table is not recommended
58
Technical Book MZ 11/25/11 8:54 AM Page 58
OCI/PBTB/Rev-001/010909
59
Nominal thickness of XLPE insulationas per IEC 60502-2
Nominal cross Nominal thickness of insulation at rated voltagesectional area of Uo/U (Um)
conductor 3,6/6 (7,2) kV 6/10 (7,2) kV 8,7/15 (17,5) kV 12/20 (24) kV 18/30 (36) kVmm2 mm mm mm mm mm
10 2,5 – – – –
16 2,5 3,4 – – –
25 2,5 3,4 4,5 – –
35 2,5 3,4 4,5 5,5 –
50 to 185 2,5 3,4 4,5 5,5 8,0
240 2,6 3,4 4,5 5,5 8,0
300 2,8 3,4 4,5 5,5 8,0
400 3,0 3,4 4,5 5,5 8,0
500 to 1000 3,2 3,4 4,5 5,5 8,0
Note: Any smaller conductor cross-section than those given in this table is notrecommended. However, if a smaller cross-section is needed, either the diameter of theconductor shall be increased by a conductor screen, or the insulation thickness shall beincreased in order to limit, at the values calculated with the smallest conductor size givenin this table, the maximum electrical stresses applied to the insulation under test voltage.
Technical Book MZ 11/25/11 8:54 AM Page 59
OCI/PBTB/Rev-001/010909
Old and New Core BS Core Colours
BS 6004 (PVC insulated PVC Sheathed Cables)
Cable Type Old Core Colour New Core Colour
Single Core Red or Black Brown or Blue
Two Core Red, Black Brown, Blue
Three Core Red, Yellow, Blue Brown, Black, Grey
BS 6500
Cable Type Old Core Colour New Core Colour
Two Core Blue, Brown No Change
Three Core Green-Yellow, Blue, Brown No Change
Four Core Green-Yellow, Black, Blue, Brown Green-Yellow, Brown, Black, Greyor Green-Yellow, Blue, Brown,Black
Five Core Green-Yellow, Black, Blue, Brown, Green and Yellow, Blue, Brown,Black Black, Grey
BS 6346, BS 5467, BS 6724
Cable Type Old Core Colour New Core Colour
Single Core Red or Black Brown or Blue
Two Core Red, Black Brown, Blue
Three Core Red, Yellow, Blue Brown, Black, Grey
Four Core Red, Yellow, Blue, Black Blue, Brown, Black, Grey
Five Core Red, Yellow, Blue, Black, Green/Yellow, Blue, BrownGreen/Yellow Black, Grey
60
Technical Book MZ 11/25/11 8:54 AM Page 60
OCI/PBTB/Rev-001/010909
61
Overhead conductors are manufactured in a variety of sizes and strandings and several differentmaterials. This range of choices enables selection of specific line conductors withcharacteristics such as conductance, diameter, strength, weight & coefficient of thermalexpansion, stress strain, creep & thermal less of strength characteristics. Proper conductorselection takes into account the interaction of these characteristics with requirements oflines its voltage, capacity, load factor etc. These material are compared in the table givenbelow:
Material AAC AAAC ACSR Copper
Conductivity %IACS 61 53 20 97
Temperature co-efficientfor Resistance OHM-MM2/KM 0.00403 0.0036 0.0051 0.00331
Co-efficient of linear 10-6 23 23 12.96 17expansion per ˚C
Ultimate tensile strength Mpa 160-200 295 1100-1344 414
Modulus of elasticity Gpa 70 70 162 125
Typical applications Short ACSR Low sag and MaximumSpan replacement high tensile currentwith for strength capacity
maximum corrosive Severecurrent atmosphere loadingcapacity conditions
For Current ratings, size and dimensions, please refer to our catalogue. We also provide coveredconductors. Covered conductors with insulation are good for environments carrying pollutionand can withstand contact with conducting materials.
Technical Book MZ 11/25/11 8:54 AM Page 61
OCI/PBTB/Rev-001/010909
62
Frequently Asked Questions
Cables can be divided into a large number of types based on a combination of classificationsas follows:
Voltage ratings low voltage, high voltage, extra high voltage cables, etc.
Conductor material Copper conductor or Aluminium conductor.
Insulating material Paper Insulated, PVC insulated, Rubber insulated, XLPE insulated, etc.
Armoured or Unarmoured cables.
Sheathing material as PVC Sheathed, Rubber Sheathed, Lead Sheathed, Aluminium Sheathed,etc.
Number of cores as single core, two core, three core, three-and-a-half core, four core, multicore,etc.
Cross-section of the conductor.
Type of conductor, solid, stranded, sector shaped, etc.
The details of various cable types can be checked in catalogues.
Should cables be single core or 3-core?
Single core cables can be cost-effective where impedance earthed systems are used whichrequire relatively small screen sizes so that the cost for three core cables is economical. This isalso true for large conductor sized cables. Single core cables are more easily water-blacked.
For 10/11 kV systems the trend is for 3-phase cables. At higher voltages and higher fault levels,this issue of circulatory current in large screens of single core cables is a significant factor. Thesubject therefore of 3-core vs single core is an important issue.
Which is best system, direct-buried or in-conduit, and what is its impact on cabledesign?
In-conduit systems might enable simpler, low-cost cable designs to be used. In many denselypopulated cities conduit systems are the only appropriate form of cabling, as it is impossible totake advantage of longer drum lengths with direct-buried systems. Due to frequent presence ofwater in ducts, it becomes necessary to apply water barriers into the cable. On the other hand,there is an increasing interest in direct-burying using modern installation methods.
What are the factors which reduce cable life?
Voltage surges
As with any electrical insulation, life expectancy is reduced when the insulation is subjected to“over voltage”, in the form of surges and impulses. It is recommended that appropriateprotection devices be installed and the nature and frequency of all such occurrences bemonitored and recorded, so that protective measures can be installed.
Technical Book MZ 11/25/11 8:54 AM Page 62
OCI/PBTB/Rev-001/010909
63
Excess operating temperatures
The cables are designed for a maximum operating temperature with limited overload periods asdefined in the relevant Standard. Changes in the environment, depth of cover, adjacent servicesand micro biological effects in the soil, can increase operating temperatures and thus reducecable life time. The circuit protection system also needs to ensure adequate protection fromexcess current loading. The nature of frequency of all such occurrences should be monitoredand recorded.
To protect the investment and ensure the life of the cable, continuous monitoring of all keycircuits is required.
Adverse environmental conditions
Environmental conditions can adversely affect the conditions for the cable. Microbiologicaleffects from fungus and bacteria can induce increases in soil temperature thus affecting thetemperature of the cable and causing unseen overloads. Increases in the thermal conductivityof the soil must be monitored and recorded.
Poor installation practices
The lifetime of cables is dependent on the cable being installed correctly. Poorsupervision/management and adverse installation conditions may cause the cable to bedamaged, over tensioned, twisted, bendings radii exceeded, excessive sidewall pressureinduced, over compaction of backfill and other life threatening factors.
Compatibility of design for cable and accessories
Poor co-ordination of designs will result in incorrect/incompatible accessories, fixing methods,stresses induced by mechanical vibration, thermal movement and lack of compensation forseismic conditions. It is essential that correct methods of fixing and environmental assessmentbe undertaken to ensure the materials are not subjected to unforseen or unexpected stressesin service.
Technical Book MZ 11/25/11 8:54 AM Page 63
OCI/PBTB/Rev-001/010909
64
Conversion TablesTo Convert: Multiply by:Mils to millimetres (1,000 mils=one inch).......................................................................................0.0254Inches to centimetres ...............................................................................................................................2.540Centimetres to inches ............................................................................................................................0.3937Feet to metres ..........................................................................................................................................0.3048Metres to feet .............................................................................................................................................3.281Yards to metres........................................................................................................................................0.9144Metres to yards........................................................................................................................................1.0936Miles to kilometres..................................................................................................................................1.6093Kilometres to miles .................................................................................................................................0.6214Square inches to circular mils (circ. mils) ..................................................................................1,273,240Circular mils to square inches.....................................................................................................7854 x 106
Square inches to square millimetres .................................................................................................645.16Square millimetres to square inches...............................................................................................0.00155Circ. mils to mm2..........................................................................................................................0.00050671mm2 to circ. mils...................................................................................................................................1973.52Square yards to square metres...........................................................................................................0.8361Square metres to square yards..............................................................................................................1.196Cubic inches to cubic centimetres.....................................................................................................16.387Cubic centimetres to cubic inches.....................................................................................................0.0610Cubic yards to cubic metres ................................................................................................................0.7645Cubic metres to cubic yards...................................................................................................................1.308Pounds (lbs) to kilogrammes................................................................................................................0.4536Kilogrammes to pounds (lbs)..................................................................................................................2.205Tons (2240 lbs) to kilogrammes......................................................................................................1016.02Kilogrammes to tons (2240 lbs) ......................................................................................................0.00098Ounces (avoirdupois) to grammes ........................................................................................................28.35Grammes to ounces (avoirdupois)......................................................................................................0.0353Gallons (imp) to litres................................................................................................................................4.546Litres to gallons (imp)..................................................................................................................................0.22Horse-power to foot pounds per minute .......................................................................................33000.0Watts to foot pounds per minute .........................................................................................................44.24Horse-power to kilowatts.........................................................................................................................0.746Kilowatts to horse-power............................................................................................................................1.34lb/1000 yd to lb/mile.................................................................................................................................1.76lb/1000 yd to kg/km...................................................................................................................... 0.496053kg/km to lb/1000 yd..........................................................................................................................2.01591lb/inch2 to kg/mm2 .................................................................................................................. 0.00070307kg/mm2 to lb/inch2............................................................................................................................ 1422.33ohm/1000 yd to ohm/mile.......................................................................................................................1.76ohm/1000 yd to ohm/km.................................................................................................................1.09361ohm/km to ohm/1000 yd.................................................................................................................. 0.9144Temperature:
˚F to ˚C . . . . . . . . . . . . Subtract 32 and multiply by 5/9˚C to ˚F . . . . . . . . . . . . Multiply by 9/5 and add 32
Technical Book MZ 11/25/11 8:54 AM Page 64
OCI/PBTB/Rev-001/010909
65
Con
vers
ion
Tab
le
Un
itFo
ot-
Poun
ds
Metr
icS
yst
em
e,
Inte
rnati
on
al
d’
‘Un
its’
(S.I.) 1.Le
ngth
1fo
ot
0.3
04
8m
etre
0.3
04
8m
etre
3.2
80
84
feet
1m
etre
1m
etre
2.A
rea
1sq
.yd
0.8
36
13
sq.m
etre
0.8
36
13
sq.m
etre
1.1
95
99
sq.yd
.1
sq.m
etre
1sq
.m
etre
1sq
.in
ch6
.45
16
sq.m
m.
6.4
51
6sq
.m
m.
0.0
01
55
sq.in
ch1
sq.m
m1
sq.m
m.
3.V
olu
me
35
.29
cub
ft.
1cu
bm
etre
1cu
bm
etre
1c.
ft.
0.0
28
2cu
b.m
.0
.02
82
cub.m
.
4.Fo
rce
0.2
25
lbf
0.1
02
kgf.
1N
ewto
n2
.20
46
lbf.
1kg
f.9
.80
66
5N
1lb
f.0
.45
36
kgf.
4.4
48
N
5.Pre
ssure
1lb
/sq
inch
0.0
70
3kg
/sq.cm
0.6
89
4N
/sq.cm
14
.22
3lb
/sq.in
ch1
kg/s
qcm
.9
.80
66
5N
/sq.cm
.1
4.5
07
.46
lb/s
qin
ch1
02
0kg
/sq
cmN
/m2
6.Ele
ctric
Fiel
dStr
ength
1vo
lt/m
il3
9.3
volt/m
m3
9.3
volt/m
m0
.02
54
volt/m
il1
volt/m
m1
volt/m
m
7.R
esis
tance
1ohm
/10
00
yd1
.09
36
ohm
/km
1.0
93
6ohm
/km
0.9
14
4ohm
/10
00
yd1
ohm
/km
.1
ohm
/km
8.R
esis
tivi
ty3
9.3
7ohm
-inch
10
0ohm
-cm
1ohm
-met
re0
.39
37
ohm
-inch
1ohm
-cm
1x
10
2ohm
-met
re1
ohm
-inch
2.5
4ohm
-cm
0.0
25
4ohm
-met
re
9.Fr
equen
cy1
cps
(cyc
leper
seco
nd)
1cp
s(c
ycle
per
seco
nd)
1H
z(h
ertz
)
Technical Book MZ 11/25/11 8:54 AM Page 65
OCI/PBTB/Rev-001/010909
Basic Metric UnitsMagnitude (Powers of 10)
Prefix Symbol Multiplication Factors
tera T 1 000 000 000 000 = 1012
giga G 1 000 000 000 = 109
mega M 1 000 000 = 106
kilo k 1000 = 103
hecta h 100 = 102
deca da 10 = 101
– – 1 = 100
deci d 0.1 = 10-1
centi c 0.01 = 10-2
milli m 0.001 = 10-3
micro u 0.000 001 = 10-6
nano n 0.000 000 001 = 10-9
pico p 0.000 000 000 001 = 10-12
femto f 0.000 000 000 000 001 = 10-15
atto a 0.000 000 000 000 000 001 = 10-18
66
Technical Book MZ 11/25/11 8:54 AM Page 66
OCI/PBTB/Rev-001/010909
67
AWG-kcmil vs metric mm2
AWG kcmil mm2
14 4.11 2.0812 6.53 3.3110 10.38 5.2619 13.09 6.6318 16.51 8.3677 20.82 10.556 26.24 13.35 33.09 16.774 41.74 21.153 52.62 26.672 66.36 33.621 83.69 42.41
1/0 105.6 53.492/0 133.1 67.433/0 167.8 85.014/0 211.6 107.2
250.0 126.7300.3 152.0350.0 177.3400.0 202.7450.0 228.0500.0 253.4550 278.7600 304.0650 329.4700 354.7750 380.0800 405.4900 456.0
1000 506.71100 557.41200 608.11250 633.41300 658.71400 709.41500 760.11600 810.71700 861.41800 912.11900 962.72000 1013.4
Technical Book MZ 11/25/11 8:54 AM Page 67
OCI/PBTB/Rev-001/010909
68
Guidance for AWG to Standardmm2 conversion
AWG mm2
30 0.05
28 0.08
26 0.14
24 0.25
22 0.34
21 0.38
20 0.50
18 0.75
17 1.0
16 1.5
14 2.5
12 4
10 6
8 10
6 16
4 25
2 35
1 50
2/0 70
3/0 95
4/0 120
300 MCM 150
350 MCM 185
500 MCM 240
600 MCM 300
750 MCM 400
1000 MCM 500
Technical Book MZ 11/25/11 8:54 AM Page 68