External Measurement of Internal Flow Technical Proposal PIOX S – Mass Flow Ultrasonic Measuring Prepared For: Contact name Company name Representative:

Upload: dothuy

Post on 03-May-2018

233 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: Technical Proposal - FLEXIMquotation.flexim.com/sales-docs/Proposal-Templates/PIOX... · Web viewfor flow measurement. Ultrasonic signals are emitted by a transducer installed on

External Measurement of Internal Flow

Technical Proposal

PIOX S – Mass Flow Ultrasonic Measuring

Prepared For:

Contact name

Company name

Representative:

Your name phone number , email address

Regional Sales Manager:

Page 2: Technical Proposal - FLEXIMquotation.flexim.com/sales-docs/Proposal-Templates/PIOX... · Web viewfor flow measurement. Ultrasonic signals are emitted by a transducer installed on

External Measurement of Internal Flow

Your regional sales manager Mike Kuvent, 832-922-9372, [email protected]

Product Manager:

David Popowitch, Flexim Process Analytics, 561-756-3255, [email protected]

Table of Contents

1. Introduction

2. Ultrasonic Flow & Concentration Measuring Principles

3. Measurement Requirements & Analysis

4. Description of the Proposed Ultrasonic Flowmeter

4.1 Features / Benefits

4.2 Technical Data for Instruments Offered

4.2.1 Transmitter PIOX – S Mass Flow

4.2.2 Transducer FSM

4.2.3 Transducer Mounting Fixture: PermaLok Mounting Solution

5. Installation

5.1 Proposed Installation Mode

6. Reference Installation Applications & Pictures

7. Bill of Materials/Price Proposal

8. Delivery & Warranty

Page 3: Technical Proposal - FLEXIMquotation.flexim.com/sales-docs/Proposal-Templates/PIOX... · Web viewfor flow measurement. Ultrasonic signals are emitted by a transducer installed on

External Measurement of Internal Flow

1 Introduction

FLEXIM Americas Corporation is a wholly owned subsidiary of Flexim GmbH, established in the United States in 2005 as the North & Central American Office to manage engineering, development, production Sales & Marketing and After-sale Services to our customer in the region. Since this time FLEXIM Americas has successfully delivered over 12,000 metering solutions for the most demanding of metering conditions.

2 Ultrasonic Flow & Concentration Measuring Principle

The PIOX - S measuring system employs the transit time difference principle for flow measurement. Ultrasonic signals are emitted by a transducer installed on one side of a pipe, reflected on the opposite side and received by a second transducer. These ultrasonic signals are emitted alternatively in the direction of flow and against it. As the medium in which the signals propagate is flowing, the transit time of the ultrasonic signals in the flow direction is shorter than against the flow direction.

The transit time difference Δt is measured and allows determining the average flow velocity on the propagation path of the ultrasonic signals. A flow profile correction is then performed in order to obtain the area average of the flow velocity, which is proportional to the volume flow.

Figure 1: Transit time difference correlation principle

The volumetric flow rate is calculated as follows:

Q = kRe . A . ka . Δt/(2 . tfl)where:Q - volumetric flow ratekRe - fluid mechanics calibration factorA - cross-sectional area of the pipeka - acoustical calibration factorΔt - transit time differencetfl - transit time in the medium

With transit time established, the ultrasonic sound speed through the fluid can then be calculated. As a characteristic of a fluid, sound speed can be measured to determine concentration and or density. Various fluids express different sound speed characteristics, as show in figure 2 below.

Page 4: Technical Proposal - FLEXIMquotation.flexim.com/sales-docs/Proposal-Templates/PIOX... · Web viewfor flow measurement. Ultrasonic signals are emitted by a transducer installed on

External Measurement of Internal Flow

Figure 2: Ultrasonic sound speed curve of acetic acid, with temperature compensation. The PIOX S measuring system measures both the temperature and sonic velocity of the fluid to determine the concentrations of fluids, as described in figure 3.

Figure 3: Utilizing ultrasonics and temperature to determine concentration and volume / mass flow.

Page 5: Technical Proposal - FLEXIMquotation.flexim.com/sales-docs/Proposal-Templates/PIOX... · Web viewfor flow measurement. Ultrasonic signals are emitted by a transducer installed on

External Measurement of Internal Flow

3 Requirements of company name Acetic Acid Mass Flow Measuring

Discussion of the application determined that the fluid mixture is comprised of nearly at or pure acetic acid. The mass flow calculation will be determined by using known density calculations of acetic acid, and a two channel ultrasonic volume flow measurement for high precision live mass flow calculations.

Figure 4: Ultrasonic sound speed / density curve of application with temperature compensation – request from Flexim.

Application Analysis:

Application: Mass flow of acetic acid mixture.Measuring Range: At or near pure, per FAST form.Temperature: 30 to 190 C.Pipe Material and Diameter: 12” Zirconium

4 Description of the proposed ultrasonic flowmeter

4.1 Features/Benefits

The proposed ultrasonic flowmeter has the following features:

“Fit for Purpose” FLEXIM Transducers – Factory “matched” and calibrated Stainless Steel Transducers (hermetically sealed) and armored stainless steel cable delivers the robustness required of a portable or permanent device. “Intelligent” design – transducer contains a microchip read by the meter that contains the calibration information. Competing devices are error prone when the transducer type

Page 6: Technical Proposal - FLEXIMquotation.flexim.com/sales-docs/Proposal-Templates/PIOX... · Web viewfor flow measurement. Ultrasonic signals are emitted by a transducer installed on

External Measurement of Internal Flow

is not input correctly. Transducer Temperature Compensation – The only Clamp-on meter that employs an RTD inside the

transducer block as per ASME MFC 5M. A temperature algorithm compensates for calibration shifts due to temperature changes. Without this compensation the accuracy drift due to temperature change will 1% for a 30degF change.

PermaLok Track Mount System – For permanent installations the Stainless Steel PermaLok Track provides the highest level of transducer support and protection. Flexim has engineered a permanent solid coupling material for sonically coupling the transducer to the pipe. With the protection of the PermaLok track and the permanent coupling pads there is no need to periodically re-couple transducers.

Broadened Application Range – Flexim incorporates a dynamic power delivery scheme that delivers the power to the transducers required to get the signal through the liquid or gas stream.

Ease of Use – The meter is designed to be intuitive and is very easy to program. Installation of entire meter can be easily accomplished in less than 4 hours.

FLEXIM “Flexibility” – All Flexim meters can be configured to “adapt” to the application conditions at hand. If the upstream straight run is less than 10 diameters , the users may employ a number of mitigating techniques:

o ‘Multi-bounce’ transducer mounting allows the meter to average out local disturbances of the flow profile over a longer axial distance on the pipe. An even number of traverses (up to 8) simply cancels all cross-flow, non-axial influences on the flow velocity measured.

o Proper location of the interrogating sonic beam (in the plane of an upstream elbow for example) assures that the instrument will ‘see’ the fast flowing core of the liquid flow stream.

o Multi-beam interrogation of the flow stream through the use of two or more transducer pairs will tend to average out locally asymmetrical distribution of the flow velocity field.

Reduced Noise Susceptibility – All Flexim flow computers are fully shielded and utilize TRIAX cabling (provides for an additional armored outer shield) to prevent/minimize the influence of external noise sources.

Signal Detection – The signal processing of the transmitted signal is NOT based upon a ZERO crossing detection which relies heavily on a “match” between the wall thickness of the pipe and a selected transducer’s operating frequency. Rather FLEXIM employs a signal correlation function in which the entire receive signal is utilized resulting in a more robust signal detection process.

Application Guarantee – All meters sold. FLEXIM goes to great lengths to qualify each and every application and as such provides an application guarantee on each meter sold. We will ensure that satisfaction with ALL metering solutions provided by FLEXIM.

Support – In addition to FLEXIM’s full-service operation center on Long Island, New York, Regional Sales/Service office in San Ramon, CA and we have factory certified sales and service representatives throughout located throughout the US and Canada. Flexim provides a “free” telephone hotline for assistance “when you need it”, including after hours 7 days a week till 12AM.

Total Cost of Ownership – No need for recalibration, no wear mechanism, no pressure drop, no additional flanges, valving, by-pass, etc...

Proven Reliability – 190 year calculated MTBF

Page 7: Technical Proposal - FLEXIMquotation.flexim.com/sales-docs/Proposal-Templates/PIOX... · Web viewfor flow measurement. Ultrasonic signals are emitted by a transducer installed on

External Measurement of Internal Flow

4.2 Technical Data of Instruments Offered

4.2.1 FLUXUS ADM7407 PIOX – S Mass Flow

FLUXUS ADM 7407 PIOX is designed especially for chemical processes and chemical distribution. By combining the attributes of FLEXIM’s highly accurate and reliable non-intrusive ultrasonic flow measurement with temperature, the integrated system is the ideal solution for chemical applications, where the fluid concentration can significantly vary over temperature.

The internal PIOX S flow computer allows the meter to report:

Concentration or density of the fluid

Volume or mass flow calculated from the density

User defined values for proprietary fluids

Ultrasonic velocity of the fluid, to determine presence of foreign fluid or phase detection

Figure 2: PIOX - S

Figure 3: External Dimension of ADM7407

Technical Data PIOX – S Mass FlowMeasureable flowvelocity: 0.03 to 82 ft/sec

Repeatability: 0.15 % of reading ±0.01 m/sAccuracy:NITS/PTB traceable wet flow calibration at factory

±1 % of reading ±0.01 m/s

Ultrasonic Velocity Resolution: 0.5 meters per second

Concentration Accuracy: 0.03 to 1.0 wt.% or M.%. Fluid concentration range dependent

Operating temperature: -20 to +50 °CIngress protection: IP66

Area Certification: FMC Class I-III, Div 2Power supply: 110 to 240 VAC or 9 to 36 VDCFlow measuring channels 1 or 2 Channel

Outputs:

2 x current output 4-20 mA active3 x RelayModbus RTURS-485Frequency

Page 8: Technical Proposal - FLEXIMquotation.flexim.com/sales-docs/Proposal-Templates/PIOX... · Web viewfor flow measurement. Ultrasonic signals are emitted by a transducer installed on

External Measurement of Internal Flow

Figure 4: Wall and 2 “Pipe Mounting Kit for ADM74074.2.2 Transducer FSM

The proposed FSMNF2 transducer is FM-C certified for use in Class 1 through 2, Div 2 hazardous area. The transducers together with the transmitter receive a NIST traceable wet flow calibration with water as medium. The proposed flowmeter is delivered with an NIST traceable calibration certificate.

4.2.3 Transducer Mounting Fixture: PermaLok Track

*Due to insulation over the pipe, only solid banding straps will be supplied for transducer mounting on the zirconium pipe.

The PermaLok mounting fixtures hold the transducers safely in place and ensure continuous and constant contact pressure between the transducers and the pipe surface, even if temperature variations cause the pipe diameter to change. Made of stainless steel, they are corrosion-proof and wear resistant. The transducers can be removed and remounted onto the PermaLok track without readjustment. Flexim has engineered a permanent solid coupling material for sonically coupling the transducer to the pipe.

Technical Data M Type

Technical Data FSM TransducersWave type: Shear WaveOperating frequency: 1.0 MHzOperating temperature: -40 ...+130 °CExplosion protection temperature -40 …+190 °C

Housing material: PPSU with Stainless Steel Cap 304

Cable Material: Stainless Steel CablingContact surface: PPSUClassification: FM C I – III D IIIngress protection: IP65

Page 9: Technical Proposal - FLEXIMquotation.flexim.com/sales-docs/Proposal-Templates/PIOX... · Web viewfor flow measurement. Ultrasonic signals are emitted by a transducer installed on

External Measurement of Internal Flow

material: Stainless steel 304Inner rail Length: 11.875 inchesDimension: 13.25 x 3.85 x 4 in

Figure 6: Transducer Mounting Rail: PermaLok

5 Installation

5.1 Installation Mode

The proposed installation mode will be that of a 2 PATH (REFLECT MOUNT) DUAL BEAM mounting

arrangement (Figure 7). This mounting arrangement is ideal for large pipes / limited straight run installations,

as well as high precision mass flow measuring. This metering solution not only mitigates the affect of poor

upstream piping conditions and large pipe profile, but ensures that more area of the flow profile is correctly

measured for increased accuracy.

Figure 7: 2 PATH (REFLECT MOUNT) DUAL BEAM mounting arrangement.

Page 10: Technical Proposal - FLEXIMquotation.flexim.com/sales-docs/Proposal-Templates/PIOX... · Web viewfor flow measurement. Ultrasonic signals are emitted by a transducer installed on

External Measurement of Internal Flow

5.2 Spring Mounting

Zirconium Expansion vs. Stainless Steel

Due to the expansion / contraction of the zirconium pipe that will be experienced, Flexim is providing a spring tensioned mount solution. The thermal expansion coeff. of Zirconium is 5.7 to 5.9exp-6/K, whereas stainless steel comes with 18 exp-6/K. With this knowledge, the 12“ Zirconium pipe will expand approx. 1 mm while the SS would expand 3mm. In order to accomodate this effect, FLEXIM will be supplying our proven Spring Compensation mounting hardware (Figure 8). It also has been determined that the impact of the geometrical change of the pipe over the temperature range sited (30C to 195C) will have a negligible impact on measurement uncertainty.

Page 11: Technical Proposal - FLEXIMquotation.flexim.com/sales-docs/Proposal-Templates/PIOX... · Web viewfor flow measurement. Ultrasonic signals are emitted by a transducer installed on

External Measurement of Internal Flow

Figure 8: Spring expansion bolt mounted system.

Galvanic Corrosion Isolation

Providing a “Keep it simple” solution, Flexim will supply a similar elastomer we use for the couplant pads. All pieces of hardware that are to be normally in contact with the pipe will be isolated. This will be accomplished by utilizing strips of Viton that are 1/8” thick by 2” wide, cut to length, This includes the mounting bands, spring tensioners, permalok transducer enclosures, transducer cables, RTD, and RTD cable at a minimum. The Viton strips are rated to a maximum temperature exposure of 400 degrees F.

5.3 Accessories and Junction Boxes

Typical configuration for wiring and junction boxes includes mounting the transducer in an accessible area,

while connecting the necessary transducers and temperature measuring to the pipe (Figure 9).

Page 12: Technical Proposal - FLEXIMquotation.flexim.com/sales-docs/Proposal-Templates/PIOX... · Web viewfor flow measurement. Ultrasonic signals are emitted by a transducer installed on

External Measurement of Internal Flow

Figure 9: General Arrangement for Each of the Measurement Point

Page 13: Technical Proposal - FLEXIMquotation.flexim.com/sales-docs/Proposal-Templates/PIOX... · Web viewfor flow measurement. Ultrasonic signals are emitted by a transducer installed on

External Measurement of Internal Flow

6 Reference Installation / Applications and Pictures

Typical (8”) Installation in Sulfuric Acid Production

Typical Installation in (6”) Nitric Acid Production

Page 14: Technical Proposal - FLEXIMquotation.flexim.com/sales-docs/Proposal-Templates/PIOX... · Web viewfor flow measurement. Ultrasonic signals are emitted by a transducer installed on

External Measurement of Internal Flow

Typical Small Line (1”) Installation, 20% Caustic Soda

Typical Small Pipe (1”) Installation, Hydrofluoric Acid

Page 15: Technical Proposal - FLEXIMquotation.flexim.com/sales-docs/Proposal-Templates/PIOX... · Web viewfor flow measurement. Ultrasonic signals are emitted by a transducer installed on

External Measurement of Internal Flow

7 Bill of Materials / Price Proposal your quote attach here

Item Description Part Number Qty Unit Price Extension

TRANSMITTER ELECTRONICS1 PIOX-S 7407 Ultrasonic Mass Flow & Concentration

 - Dual Channel, NEMA 4X w/ LCD display & Keypad- 2 active 0-20 mA & 1 RTD temperature input- 2 active 0-20mA outputs, 3 solid state relay outputs- 100 to 240VAC, RS-232 & Datalogger standard

US-7407.MCPXMF 1 $9,050.00 $9,050.00

1a FM Class I Div II Flow Computer Certification US-7407.FMC1D2 1 $250.00 $250.001b 316 Stainless Steel Enclosure for 7407 US-7407.316SE 1 $750.00 $750.00

SENSORS2 Pair of High-Temp M Clamp-On Flow Transducers

- FM-C Class I Div. 2 Certified - Pipe diameter range 4" to 24", with 13.1' cable - Temperature -40 to +374 °F, includes coupling pads - Type: CDM2E52, inc. NIST traceable 5 pt wet flow calibration cert

FSM-EF2TS-000 2 $2,508.00 $5,016.00

3 SINGLE Clamp-On temperature sensor PT1000 for high temperature - 1000-ohm clamp-on platinum RTD, 4-wire, 20' cable - Measuring range -40 to +400 °C - 3' fiberglass extension rated to 400 °C, - Low profile/half-moon Brass design

US-TEMP.HT400 1 $395.00 $395.00

MOUNTING SOLUTION4 PermaLok Type M Mounting Track

- Stainless Steel SS304 Track & SOLID BAND Strap Kit - DIRECT/REFLECT Mount Installation - Pipe Diameter Range of 12" to 18"

MOU-PLM-DS-SBK4 2 $575.00 $1,150.00

5 Sensor Strap Mounting Kit (12" to 18" OD) - SS Strapping for FLOW or TEMP Sensors (2 Straps/kit)

US-MOU.SK4 1 $60.00 $60.00

6 Strap spring kit for Permalocks - High Temperature US-MOU.PLSPRING 3 $75.00 $225.00JUNCTION BOXES AND CABLES

7 DUAL TRIAX Xdcr Extension Cable (Price per Ft.) - Two inner conductor Triaxil shielded cable, 0.50" Max OD - Halogen free FRNC, ONE cable required per transducer pair - Full reel length 2000'

7710127-[xxx] 40 $4.00 $160.00

8 Ext. cable for temperature RTD's (Price per Ft) - 4-wire 18 AWG shielded, LS PVC Jacket, 0.188" OD - Plenum Rated, ONE cable required per temp sensor - Full reel length 1000'

US-TEMP-CBL1 20 $1.00 $20.00

9 Junction Box for Cable Extension of FLOW sensor - Stainless Steel SS304 Construction; Standard TS connection - IP 67 / NEMA 6 (Submersible to 1 meter)

751040-26 2 $195.00 $390.00

10 J-Box for Cable Extension of SUBMERSIBLE/5X07 sensor - Stainless Steel SS304 Construction; Flying-lead connection - IP 67 / NEMA 6 (Submersible to 1 meter)

751040-11 1 $212.00 $212.00

ACCESSORIES11 Permanent Coupling Pads Type VT-M

- Continuous operating temperature -40 to +400 °F, - Consists of 2 pads for M type transducers

990739-6 1 $11.00 $11.00

12 Pipe/Wall mounting kit for 7407 flow computer 721037-1 1 $225.00 $225.0013 Viton Mounting Pads For All Hardware , Electrolytic Isolation VITON KIT 2 $500.00 $1,000.00

$18,914.00TOTAL PRICE

Page 16: Technical Proposal - FLEXIMquotation.flexim.com/sales-docs/Proposal-Templates/PIOX... · Web viewfor flow measurement. Ultrasonic signals are emitted by a transducer installed on

External Measurement of Internal Flow

NOTE: Without a demonstration / feasibility test conducted for this application, should the meter not receive a signal after installation, a restocking fee will be required for the complete metering system if returned. Installation charges will not be credited.

Please Send Purchase Orders To:

FLEXIM Americas CorporationC/O Allesco14375 SommermyerHouston, Texas 77041

Terms: NET 30FOB: FactoryFreight: Pre-Pay and AddValidity: 90 Days

8 Delivery and Warranty

The terms of delivery shall be within 6 weeks from the date of order confirmation / technical clarification.

Flexim guarantee that the design, engineering and the instrument supplied shall be free from defects. All defective material shall be replaced free of charge within 18 months from the date of installation or 24 months from the date of delivery of the instruments whichever comes earlier.