TECHNICAL DATA& SERVICE MANUAL

OUTDOOR UNIT: GR9FI80R5I.

QUADRI SPLIT SYSTEM AIR CONDITIONER

.

Model No. Product Code No.

GR9FI80R5I 38.7107.104

0.8180.618.01 09/2012

0.8180.531.00 05/2007

IMPORTANT!Please read before installation

This air conditioning system meets strict safety and operatingstandards.For the installer or service person, it is important to install orservice the system so that it operates safely and efficiently.

For safe installation and trouble-free operation, you must:• Carefully read this instruction booklet before beginning.• Follow each installation or repair step exactly as shown.• Observe all local, state and national electrical codes.• Pay close attention to all warning and caution notices given in

this manual.•The unit must be supplied with a dedicated electrical line.

This symbol refers to a hazard or unsafe practice which can resultin severe personal injury or death.

This symbol refers to a hazard or unsafe practice which can resultin personal injury or product or property damage.

If necessary, get helpThese instructions are all you need for most installation sites andmaintenance conditions.If you require help for a special problem, contact our sale/serviceoutlet or your certified dealer for additional instructions.

In case of improper installationThe manufacturer shall in no way be responsible for improperinstallation or maintenance service, including failure to follow theinstructions in this document.

SPECIAL PRECAUTIONS

• During installation, connect before the refrigerant system andthen the wiring one; proceed in the reverse orden when removingthe units.

When wiring

ELECTRICAL SHOCK CAN CAUSE SEVEREPERSONAL INJURY OR DEATH. ONLY A QUALIFIED,EXPERIENCED ELECTRICIANS SHOULD ATTEMPTTO WIRE THIS SYSTEM.

• Do not supply power to the unit until all wiring and tubing arecompleted or reconnected and checked, to ensure the grounding.

• Highly dangerous electrical voltages are used in this system.Carefully refer to the wiring diagram and these instructions whenwiring.Improper connections and inadequate grounding can causeaccidental injury and death.

• Ground the unit following local electrical codes.• The Yellow/Green wire cannot be used for any connection

different from the ground connection.• Connect all wiring tightly. Loose wiring may cause overheating

at connection points and a possible fire hazard.• Do not allow wiring to touch the refrigerant tubing, compressor,

or any moving parts of the fan.• Do not use multi-core cable when wiring the power supply and

control lines. Use separate cables for each type of line.

When transportingBe careful when picking up and moving the indoor and outdoorunits. Get a partner to help, and bend your knees when lifting toreduce strain on your back. Sharp edges or thin aluminium fins onthe air conditioner can cut your fingers.

When installing...... In a ceiling or wallMake sure the ceiling/wall is strong enough to hold the unit-weight.It may be necessary to build a strong wooden or metal frame toprovide added support.

... In a roomProperly insulate any tubing run inside a room to prevent"sweating", which can cause dripping and water damage to wallsand floors.

... In moist or uneven locationsUse a raised concrete base to provide a solid level foundation forthe outdoor unit.This prevents damage and abnormal vibrations.

... In area with strong windsSecurely anchor the outdoor unit down with bolts and a metalframe. Provide a suitable air baffle.

... In a snowy area (for heat pump-type systems)Install the outdoor unit on a raised platform that is higher thandrifting snow. Provide snow vents.

When connecting refrigerant tubing• Keep all tubing runs as short as possible.• Use the flare method for connecting tubing.• Apply refrigerant lubricant to the matching surfaces of the flare

and union tubes before connecting them; screw by hand andthen tighten the nut with a torque wrench for a leak-freeconnection.

• Check carefully for leaks before starting the test run.

NOTE:Depending on the system type, liquid and gas lines may be eithernarrow or wide. Therefore, to avoid confusion, the refrigeranttubing for your particular model is specified as narrow tube forliquid, wide tube for gas.

When servicing• Turn the power OFF at the main power board before opening

the unit to check or repair electrical parts and wiring.• Keep your fingers and clothing away from any moving parts.• Clean up the site after the work, remembering to check that no

metal scraps or bits of wiring have been left inside the unit beingserviced.

• Ventilate the room during the installation or testng the refrigerationsystem; make sure that, after the installation, no gas leaks arepresent, because this could produce toxic gas and dangerousif in contact with flames or heat-sources.

WARNING

CAUTION

WARNING

2

Page

1. OPERATING RANGE 4

2. SPECIFICATIONS 52-1 Unit Specifications 52-2 Major Component Specifications 62-3 Other Component Specifications 7

3. DIMENSIONAL DATA 8

4. REFRIGERANT FLOW DIAGRAM 9

5. PERFORMANCE DATA 105-1 Performance Charts 10

6. ELECTRICAL DATA 116-1 Electrical Characteristics 116-2 Electric Wiring Diagram 126-3 Quadri Split System Wiring Diagram 136-4 Trial Split System Wiring Diagram 136-5 Dual Split System Wiring Diagram 136-6 Mono Split System Wiring Diagram 13

7. FUNCTION 147-1 Diagnostic 14

Table of Contents

3

1. OPERATING RANGE

Outdoor Air Intake Temp.

Cooling Maximum 32°C D.B. / 23°C W.B. 43°C D.B.Minimum 10°C D.B. / 6°C W.B. -15°C D.B.

24°C D.B. / 18°C W.B.Minimum 5°C D.B. -15°C D.B.

GR9FI80R5I.

Heating Maximum 27°C D.B.

Temperature Indoor Air Intake Temp.

4

2. SPECIFICATIONS2-1 Unit Specifications

GR9FI80R5I

Power source

Voltage rating

Performance * MPA9FIB0R5I x1 + MTAFIA0R5I x3Capacity kW

BTU/hAir circulation (High) m³/hMoisture removal (High) Liters/h

Electrical RatingAvailable voltage range VRunning amperes APower input WPower factor %C.O.P. W/WCompressor locked rotor amperes A

FeaturesFan speedCompressorRefrigerant / Amount charged at shipment gRefrigerant controlPower noise level Hi dB-ARefrigerant tubing connectionsMax. allowable tubing length at shipment mRefrigerant Narrow tube mm(in.)tube diameter Wide tube mm(in.)

Dimensions & WeightUnit dimensions Height mm

Width mmDepth mm

Package dimensions Height mmWidth mmDepth mm

Weight Net kgShipping kg

Shipping volume m3

DATA SUBJECT TO CHANGE WITHOUT NOTICERemarks:

Rating Conditions are:Cooling: Indoor Air Temperature 27°C D.B. / 19°C W.B. Outdoor Air Temperature 35°C D.B. / 24°C W.B.Heating: Indoor Air Temperature 20°C D.B. Outdoor Air Temperature 7°C D.B. / 6°C W.B.

* For other INDOOR UNITS' MODELS, please refer to catalogue

R410A / 3000

27809 31426

220 - 240 V ~ 50 Hz

230 V

Heating8,15 9,21

Cooling

600

87,00,54

1190340/400

1015127042073,0

Electronic expansion valve

1,5 -

10,00198 ~ 264

9,952200

variable (300÷950 continuous)

95

Twin Rotary (Hermetic) DC inverter

835

Flare typesee installation instruction

67

9,52 (3/8) - 12,7 (1/2)6,35 (1/4)

- -

Cooling Heating

962180

3,70 4,22

5

2-2 Major Component Specifications

GR9FI80R5I

CompressorTypeCompressor modelNominal input (compressor rating condition) WCompressor oil…Amount ccCoil resistance (Ambient temp. 20°C) ΩOverload relaySafety devices Type

Operating Temp. Open °CClose °C

Controller PCBPart No.ControlsControl circuit fuse

Expansion PCBPart No.ControlsControl circuit fuse

Fan & Fan MotorFan type

Q'ty ...ØFan motor type

modeln° of poles

rpmnominal output

Safety devices TypeOperating temp. Open °C

Close °C

Heat Exch. CoilCoilRowsFin pitch mmFace area m2

External FinishDATA SUBJECT TO CHANGE WITHOUT NOTICE

sac dci ODUMicroprocessor

6,3x32 - 25A

---

sac espansion multi dci---

Acrylic baked-on enamel finish

Aluminium plate fin / Copper tube2

1,40,81

-

8variables

automatic over current/heating protection-

Twin Rotary (Hermetic) DC inverterTNB220FLHMT

2200

---

FV50S …… 8700,64

Software Protection

90W

Propeller1…. Ø 490mm

brushless DC sinusoidal PWMSIC-71FW-D890-3

6

2-3 Other Component Specifications

GR9FI80R5I.

4-way Valve (20S)Coil ratingCoil resistance Ω (at 20°C)

Electronic Expansion Valve A - BPCoil ratingCoil resistance / phase Ω (at 20°C)

Electronic Expansion Valve B - C - DCoil ratingCoil resistance / phase Ω (at 20°C)

Defrost ValveCoil ratingCoil resistance Ω (at 20°C)

Thermistor (coil sensor)Resistance kΩ

Thermistor (compressor discharge sensor)Resistance kΩ

Thermistor (inlet air sensor)Resistance kΩ

Thermistor (wide tube A-B-C-D sensor)Resistance kΩ

Thermistor (narrow tube A-B-C-D sensor)Resistance kΩ

Crank case heaterResistance Ω (at 20°C)

Base heaterResistance Ω (at 20°C)

DATA SUBJECT TO CHANGE WITHOUT NOTICE

75W - FLEXELEC CSC2705 ± 10%

NTC-THERMISTOR10 at 25 °C

20W - RESISTANCE2640 ± 10%

NTC-THERMISTOR10 at 25 °C

NTC-THERMISTOR10 at 25 °C

NTC-THERMISTOR10 at 25 °C

NTC-THERMISTOR10 at 25 °C

FQ-235-RK (Coil) FDF6A-049-RK (Valve)

CAM-MD12EX(Coil) ZCAM-BD15EX (Valve)DC 12 V46 ± 4%

1600 ± 5%AC 220/240 V, 50 Hz

LDK-41 (Coil) V2-410060-300 (Valve)

AC 220/240 V - 50 Hz1273 ± 10%

UKV-U030E (Coil) UKV-18D31 (Valve)DC 12 V46 ± 3%

7

3. DIMENSIONAL DATA

GR9FI80R5I.

dimension [mm]

NARROW TUBE4x ø.6,35 (1/4")

4 - Ø10for anchor bolt

WIDE TUBE3x ø.9,52 (3/8")1x ø.12,7 (1/2")

8

4. REFRIGERANT FLOW DIAGRAM

Outdoor Unit: GR9FI80R5I Indoor Unit A: MPA9FIB0R5IIndoor Unit B: MTAFIA0R5IIndoor Unit C: MTAFIA0R5IIndoor Unit D: MTAFIA0R5I

Insulation of Refrigerant Tubing

IMPORTANTBecause expansion valve is used in the outdoor unit, both the wide and narrow tubes of thisair conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation,both tubes must be well insulated with a proper insulation material.The thickness of the insulation should be a min. 8mm.

CAUTIONAfter a tube has been insulated, never try to bend it into a narrow curvebecause it can cause the tube to break or crack.

9

5. PERFORMANCE DATA5-1 Performance charts

GR9FI80R5I

Cooling Characteristics Heating Characteristics

1

0.8180.531.00 05/2007

NoteOverload prevention operates to protect the air conditioner when outdoor ambient temperature reachesextremely high values in heating mode.

Points of Rating condition Data referred to MPA9FIB0R5I x1 + MTAFIA0R5I x3

0,500

0,600

0,700

0,800

0,900

1,000

1,100

1,200

10 15 20 25 30 35 40

Outdoor inlet air D.B. temperature (°C)

Low

pre

ssur

e at

wid

e tu

be s

ervi

ce v

alve

MP

a

1,300

1,500

1,700

1,900

2,100

2,300

2,500

0 5 10 15 20

Outdoor inlet air D.B. temperature (°C)

Hig

h pr

essu

re a

t wid

e tu

be s

ervi

ce v

alve

Mpa

5,0

6,0

7,0

8,0

9,0

10,0

11,0

12,0

10 15 20 25 30 35 40

Outdoor inlet air D.B. temperature (°C)

Ope

ratin

g cu

rrent

(A)

Indoor inlet airD.B. (°C)

32

27

19

5,0

6,0

7,0

8,0

9,0

10,0

11,0

12,0

0 5 10 15 20

Outdoor inlet D.B. temperature (°C)

Ope

ratin

g cu

rrent

(A)

Indoor inlet airD.B. (°C) 25

20

15

Indoor inlet airD.B. (°C)

Indoor inlet airD.B. (°C) 25

20

15

32

27

19

7

7

32

27

19

10

6. ELECTRICAL DATA6-1 Electrical characteristics

Outdoor unit: GR9FI80R5I

COOLING

3 Indoor UnitFan Motor

Performance atRating conditions Running Amps. A 0,79 10,0

Power input kW 0,179 2,200

Rating Conditions: Indoor Air Temperature 27°C D.B. / 19°C W.B.Outdoor Air Temperature 35°C D.B. / 24°C W.B.

HEATING

3 Indoor Unit

Performance atRating conditions Running Amps. A 0,79 9,95

Power input kW 0,179 2,180

Rating Conditions: Indoor Air Temperature 20°C D.B.Outdoor Air Temperature 7°C D.B. / 6°C W.B.

NOTE: Data referred to 4 indoor unit, MPA9FIB0R5I x1 + MTAFIA0R5I x3 For other indoor unit models there could be some differences.

9,162,001

Outdoor unit

230 V - 1 Phase - 50 Hz

Outdoor unit

230 V - 1 Phase - 50 Hz

Fan Motor + Compressor

9,212,021

Complete Unit

Complete UnitFan Motor + Compressor

11

6-2 Electric Wiring Diagram

GR9FI80R5I

12

6-3 Quadri Split System Wiring DiagramOutdoor unit:

GR9FI80R5IIndoor unit:

MPA9FIB0R5I x1 + MTAFIA0R5I x3

6-4 Trial Split System Wiring DiagramOutdoor unit:

GR9FI80R5IIndoor unit:

MPA9FIB0R5I x1 + MTAFIA0R5I x2

6-5 Dual Split System Wiring DiagramOutdoor unit:

GR9FI80R5IIndoor unit:

MPA9FIB0R5I + MTAFIA0R5I

6-6 Mono Split System Wiring DiagramOutdoor unit:

GR9FI80R5IIndoor unit:

MPA9FIB0R5I

13

7. FUNCTION7-1 Diagnostic

With this feature is possible to have a visual signal that a trouble is occurring.This mode is always active and the signalling is made through the display board LEDS .In case of no troubles the LEDS status follows its normal function.The detected troubles are showed to the user/technician using the 3 (5) leds of the indoor unit receiverand the 5 leds on the outdoor pcb. For each fault there are different effects upon the operation of the A/C: NOTES The troubles are showed according to a priority list that is in case of more than one trouble present,

is always showed, at first, the one with the highest priority (3 2 1 etc). Sensor damaged means a situation where sensor is short-circuited or opened. In case of damaged sensors, the system (CM, FMO, FMI etc), if in OFF state, does not start.

System does not operate. To restart the system,power re-setting (off-on) is required. note: before restoring power, adjust the dip-switch status on indoor unit according to the connection pipes

system does not operate.as soon as fault is cleared, the system automatically restart after 3 minduring this time, the signalling is showed

EFFECTS

14