technical catalog abb molded case circuit breakers · being able to equip such a small circuit...

229
Technical catalog ABB molded case circuit breakers UL 489 and CSA C22.2 Standard Preliminary - 1SDC210003D0202

Upload: vonhi

Post on 07-Aug-2019

222 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

Technical catalog ABBmolded casecircuit breakers

UL 489 and CSA C22.2 Standard

Preliminary - 1SDC210003D0202

Page 2: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

Tmax, Isomax, Emax: IndustrialIT enabled!

For further information, go to the Products and services/Industrial IT section on our web site: http://www.abb.com

* All product technical data and related documentation can be found inInternet and is accessible to the customer. The standard documentationis in English, but there are local language versions for each country wherea given product is marketed.

IndustrialIT is the solution developed by ABB for the all-

round integration of a company’s activities, where each

product is seen as part of a complete solution. Products

and technologies are grouped into

functional categories (Suites), each

of which measures,

controls, optimizes and

supports a specific

“block” of activities, and

they can ensure

coordinated interaction

thanks to the platform

created by ABB (AIP: Aspect Integrator Platform).

In addition to interactivity between certified products,

every certified product also guarantees the ready

availability of all the information needed for it to

function - technical characteristics, installation

instructions, use and maintenance instructions,

environmental certificates and declarations, all updated

to the latest version … a considerable advantage for the

user*.

The whole range of Tmax and Isomax molded case and

Emax power circuit breakers has obtained IndustrialIT

certification and is fully entitled to join the ProtectIT suite

of products.

These circuit breakers combine with about 700 products

in the ranges of distribution boards, thus

enabling complete switchboards to be

assembled using all IndustrialIT-certified

components. Moreover, T4 and T5

feature e-plug communication

interface, which allows Integration

to IndustrialIT systems.

Tmax, Isomax and Emax circuit

breaker can be integrated with the

configurable ABB products in a system: this

compatibility has always been a fundamental premise of

the ABB design process. Mass customization, i.e. the

mass production of components customized to meet a

given buyer’s specific needs is already feasible, as

IndustrialIT certification demonstrates.

Yet again, ABB is ahead of the field in offering a better

and better customer service!

Page 3: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

OVERVIEWMAINCHARACTERISTICS

THE RANGES

ACCESSORIES

CHARACTERISTIC CURVESAND TECHNICALINFORMATION

WIRING DIAGRAMS

OVERALLDIMENSIONS

Page 4: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new
Page 5: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

C O M P L E T E A N D P E R F E C T LY I N T E G R AT E D

In the range of molded case circuit breakers conforming with the UL 489 and CSA C22.2 Standard, ABB proposes an

entire range which covers current ratings between 15 A and 2500 A and interrupting ratings, at 480 V AC, which can

reach 150 kA.

The ranges available are as follows:

– circuit breakers for power distribution (fitted with thermomagnetic or electronic trip units starting from 100 A)

– circuit breakers with adjustable magnetic only trip units for motor protection (MCP: Motor Control Protection)

– molded case switches for use as isolators or switching devices for lines, busbars or parts of a plant (MCS:

Molded Case Switch)

With the introduction of the new Tmax UL series, a single-pole circuit breaker with interrupting rating of 18 kA

at 277 V AC is available on the American market for the first time.

4 8 0 V

All ABB circuit breakers in accordance with the

UL 489 and CSA C22.2 Standard can be

used in installations with wye or delta

distribution systems since use of the circuit

breaker at 480 V AC is guaranteed, even

for the smallest Tmax T1 size.

COMPACT D IMENSIONS

ABB molded case circuit breakers ensure

high performances in extremely small and

compact dimensions. Standardization of

the depth of the smaller sizes allows more

rational and less deep enclosure to be used

than in the past.

DOUBLE INSULATION

Thanks to the double insulation technique,

with all ABB molded case circuit breakers*

the electrical accessories can be mounted

directly on field with the circuit breaker

installed: this allows considerable savings in

time and therefore in costs.* Except for Isomax S8.

Page 6: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new
Page 7: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

TMAX.BE FREE. The Tmax T4 and T5 circuit

breakers have obtained theprestigious “INTEL Design 2003– Augusto Morello award” in theProduct Technologies andProduction processes section.

T GENERATIONTmax has grown. ABB

experience in designing and

manufacturing molded case

circuit breakers has made it

possible to create circuit breakers

which, up to 600 A, allow any application to be

faced practically and simply.

The new Tmax have been thought up to work

together, to help you carry out selections and

correct sizing, to make installation simpler, but

above all to give you top level performances.

The latest generation technology is present for

the first time even in the smallest sizes.

With Tmax you have everything you need at

hand to make your job easier, from all types of

accessories and terminals. The T Generation grows,

and so does freedom.

Page 8: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new
Page 9: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

TMAX.BE FREE TO

RIDE THE MOSTADVANCED

TECHNOLOGY.

It was not easy to find solutions which would allow the

Tmax circuit breakers to achieve such high performances

in such limited dimensions, but thanks to the

experience which has been recognised to a leader

such as ABB for decades, the objectives we had set

ourselves have been achieved. So this has meant

being able to equip such a small circuit breaker

as the T2 with an electronic trip unit, to fit the

circuit breakers with new arcing chambers

which allow the arc extinction time to be

reduced, or, still further, to provide double

insulation for ever greater safety right from the

smallest size. A complete series of latest

generation trip units is available, from the

electronic to the thermomagnetic or magnetic

only ones - all interchangeable.

The new Tmax T4 and T5 are an example of the

great technology expressed by this family of circuit

breakers with high breaking capacity and high

limitation of the specific let-through energy.

Being free is also all this.

TECHNOLOGY

Page 10: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new
Page 11: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

All the circuit breakers in the Tmax family come from

optimisation of installation sizing. With T1,T2 and T3

you can find the ideal product for sizing an installation

up to 225 A, and with T4 and T5 up to 600 A.

Furthermore, with the latter, high selectivity values

are obtained for optimal coordination with other

circuit breakers. You can also choose the best

solution for motor protection with the motor

control protection (MCP).

Higher performances in less space. More

applications up to 600 A. Easier selection of the

circuit breakers and accessories. Optimal sizing of

the installation and better protection of cables,

busbar ducts and supports. Less space required in

the switchgear and in the metal structures.

Less oversizing and therefore lower costs.

Less time for coordinating the installations.

Fewer stock complications. With Tmax, all the

solutions needed can be chosen, as well as that

of feeling freer to choose.

TMAX.BE FREE TO

CHOOSEOPTIMAL SIZING.

SIZING

Page 12: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new
Page 13: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

Having circuit breakers available with smaller dimensions

than all the others on the market undoubtedly offers

great advantages - more space for cabling operations and

simpler installation, therefore notable savings in time -

five sizes, just two depths - 2.76 inches (70 mm) for

T1, T2, T3 and 4.07 inches (103.5 mm) for T4

and T5, and the latter also have the same height.

They are also available in all the versions: fixed,

plug-in and draw out and, thanks to special kits,

passing from a fixed circuit breaker to a plug-in/

draw out one is child’s play. Flexibility of use over

the whole series is ensured by the complete range

of connection terminals and by the large number

of accessories.

Being free also means having much more time

for yourself.

TMAX.BE FREE TO

DRIBBLE ROUNDALL INSTALLATION

DIFFICULTIES.

INSTALLATION

Page 14: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new
Page 15: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

1 0 0 % U L R AT E D C I R C U I T B R E A K E R S

The 100% rated versions for Isomax circuit breakers are available thanks to the excellent thermal sizing of

the latter.

A L L T H E A P P L I C AT I O N SABB offers the right solution for any application up to 2500 A thanks to Isomax S6, S7 and S8 circuit

breakers, perfectly integrated with the Tmax family:

– MCCB: S6, S7 and S8 molded case circuit breakers for power distribution;

– MCP: S6, S7 and S8 circuit breakers with magnetic only trip unit for motor control protection;

– MCS: S6, S7 and S8 molded case switches for using as isolators or switching devices for lines, busbars or

parts of plants.

MAXIMUM VERSAT IL ITY

Isomax circuit breakers can be fitted with a wide range of

terminals for every kind of connections. Modular design

also makes installation and assembly extremely simple.

C O M P L E T E R A N G E O F A C C E S S O R I E S

Isomax circuit breakers are complemented by a

complete range of accessories to satisfy the widely

differing operational and automation requirements.

Accessories are standardized for groups of circuit

breakers to streamline storage logistics and simplify

installation.

Isomax circuit breakers can be customized as required

under conditions of absolute safety.

All the accessories can be mounted with simple

operations without exposing the main contacts (except for

the Isomax S8).

Page 16: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

Circuit breakers for power distributionElectrical characteristics

(1) In15A = 10kA @ 277 V AC(2) In15A = 35 kA @ 240 V AC, 14 kA @ 480 V AC(3) Please ask ABB for 600 A availability

Tmax T1 1P Tmax T1 Tmax T2 Tmax T3IEC 60947-2Rated uninterrupted current, Iu [A] 160 160 160 250

Number of poles [Nr] 1 3,4 3,4 3,4Rated service voltage, Ue AC (50-60Hz) [V] 240 690 690 690

DC [V] 125 500 500 500Rated ultimate short circuit breaking capacity, Icu B B C N N S H L N S

AC (50-60 Hz) 220/230 V [kA] 25 25 40 50 65 85 100 120 50 85380/415 V [kA] 16 25 36 36 50 70 85 36 50

440 V [kA] 10 15 22 30 45 55 75 25 40500 V [kA] 8 10 15 25 30 36 50 20 30

690 V [kA] 3 4 6 6 7 8 10 5 8DC 250V - 2 poles in series [kA] 16 25 36 36 50 70 85 36 50

250V - 3 poles in series [kA] 20 30 40 40 55 85 100 40 55500V - 2 poles in series [kA]

500V - 3 poles in series [kA] 16 25 36 36 50 70 85 36 50750V - 3 poles in series [kA]

Trip units TMF ■

TMD/TMA ■ ■ ■

ELT ■

MF ■

MA ■ ■

UL 489 CSA C22.2 and IEC 60947-2Dimensions H [in/mm] 5.12/130 5.12/130 5.12/130 5.9/150

W 1p or 3p [in/mm] 1/25.4 3/76 3.54/90 4.13/105W 4p [in/mm] 4/102 4.72/120 5.51/140

D [in/mm] 2.76/70 2.76/70 2.76/70 2.76/70Mechanical life [No.operations] 25000 25000 25000 25000

[No. Hourly operations] 240 240 240 240Electrical life @ 415 V AC [No.operations] 8000 8000 8000 8000

[No. Hourly operations] 120 120 120 120

Tmax T1 1P Tmax T1 Tmax T2 Tmax T3UL 489 CSA C22.2Frame size [A] 100 100 100 225

Number of poles [Nr] 1 3,4 3,4 3,4Rated voltage AC (50-60Hz) [V] 277 480 480 480

DC [V] 500 500Interrupting ratings B N S H N S

AC 240 V [kA] 50(2) 65 100 50 65277 V [kA] 18(1)

480 V [kA] 22(2) 35 65 25 35600 V [kA]

DC 250 V - 2 poles in series [kA] 25 25 35500 V - 3 poles in series [kA] 25 25 35

500 V - 2 poles in series [kA]600 V - 3 poles in series [kA]

Trip units TMF ■ ■ ■ ■

TMD/TMA

ELT ■

MA ■ ■

Versions MCCB ■ ■ ■ ■

MCS ■ ■

MCP ■ ■

TMF = Thermomagnetic trip unit with fixed thermaland magnetic threshold

TMD = Thermomagnetic trip unit with adjustablethermal threshold and fixed magneticthreshold

Page 17: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

Tmax T4 Tmax T5 Isomax S6 Isomax S7 Isomax S8

250 - 320 400 - 630 630 - 800 1250 - 1600 2000, 2500, 3200

3,4 3,4 3,4 3,4 3,4690 690 690 690 690

750 750 750N S H L V N S H L V N S H L S H L H V70 85 100 200 300 70 85 100 200 300 65 85 100 200 85 100 200 85 12036 50 70 120 200 36 50 70 120 200 35 50 65 100 50 65 100 85 120

30 40 65 100 180 30 40 65 100 180 30 45 50 80 40 55 80 70 10025 30 50 85 150 25 30 50 85 150 25 35 40 65 35 45 70 50 70

20 25 40 70 80 20 25 40 70 80 20 22 25 30 20 25 35 40 5036 50 70 120 200 36 50 70 120 200 35 50 65 100

25 36 50 70 100 25 36 50 70 100 20 35 50 65

16 25 36 50 70 16 25 36 50 70 16 20 35 50

■ ■ ■

■ ■ ■ ■ ■

8.07/205 8.07/205 10.55/268 15.98/406 15.75/400

4.13/105 5.51/140 8.27/210 8.27/210 15.98/4065.51/140 7.24/184 11.02/280 11.02/280 21.89/556

4.07/103.5 4.07/103.5 4.07/103.5 5.45/138.5 9.53/24220000 20000 20000 10000 10000

240 120 120 120 208000(250A)-6000(320A) 7000(400A)-5000(630A) 7000(630A)-5000(800A) 7000(1250A)-5000(1600A) 2500(2500A)-1500(3200A)

120 60 60 20 20(2500A)-10(3200A)

Tmax T4 Tmax T5 Isomax S6 Isomax S7 Isomax S8

250 400 - 600(3) 800 1200 1600, 2000, 2500

3,4 3,4 2,3,4 2,3,4 3600 600 600 600 600

600 600 600N S H L V N S H L V N H L H V65 100 150 200 200 65 100 150 200 200 65 150 200 100 125

25 35 65 100 150 25 35 65 100 150 50 65 100 65 10018 25 35 65 85 18 25 35 65 85 25 35 42 50 85

25 35 50 65 100 25 35 50 65 100 35 50 6516 25 35 50 65 16 25 35 50 65 20 35 50

■ ■ ■

■ ■ ■ ■ ■

■ ■ ■ ■ ■

■ ■ ■ ■ ■

■ ■ ■ ■ ■

TMA = Thermomagnetic trip unit with adjustablethermal and magnetic threshold

MF = Magnetic fixed trip unitMA = Magnetic adjustable trip unit

ELT = Electronic trip unit

Page 18: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

Circuit breakers for specificapplications in accordance withIEC 60947-2

Tmax T1 1P Tmax T1 Tmax T2 Tmax T3Circuit breakers for distribution AC-DCRated uninterrupted current [A] 160 160 160 225Numbers of poles Nr 1 3/4 3/4 3/4

Rated voltage (AC) 50-60Hz [V] 240 690 690 690Icu [kA rms] B B C N N S H L N S

380/415 V AC [kA rms] 25* 16 25 36 36 50 70 85 36 50440 V AC [kA rms] 10 15 22 30 45 55 75 25 40

690 V AC [kA rms] 3 4 6 6 7 8 10 5 8Ics/Icu @ 380/415 V AC % 100 100 50 100 100 100 75 75 50

Dimensions fixed version (3p) H [in-mm] 5.12-130 5.12-130 5.12-130 5.0-150W [in-mm] 1-25.4 3-76 3.54-90 4.13-105

D [in-mm] 2.76-70 2.76-70 2.76-70 2.76-70

T2 T3Circuit breakers for motor protectionIu [A] 160 250Poles 3 3

In [A] 1…100 100…200Ue [V] 690 690

Trip unit Adjustable magnetic only (6…12xIn) ■ ■

Electronic PR221DS-I ■

PR222/MP (IEC 60947-4-1)PR212/P-I

PR212/MP (IEC 60947-4-1)

T1D T3DSwitch-disconnectorsPoles [Nr] 3/4 3/4Ith [A] 160 250

Ue [V] 690 690Uimp [KV] 8 8

Ui [V] 800 800Icm [KA] 2.8 5.3

Icw (1s) [KA] 2 3.6

* For In 16A and In 20A: Icu @ 220/230 V AC = 16 KA

Page 19: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

Tmax T4 Tmax T5 Isomax S6 Isomax S7 Isomax S8

250 400-630 800 1250-1600 2000-2500-32003/4 3/4 3/4 3/4 3/4

690 690 690 690 690N S H L V N S H L V N S H L S H L H V36 50 70 120 200 36 50 70 120 200 35 50 65 100 50 65 100 85 12030 40 65 100 180 30 40 65 100 180 30 45 50 80 40 55 80 70 100

20 25 40 70 80 20 25 40 70 80 20 22 25 30 20 25 35 40 50100 100 100 100 100 100 100 100 100 100 100 100 100 75 100 75 50 50 50

8.07/205 8.07/205 14.25-268 16-406 15.75-4004.13/105 5.51/140 8.27-210 8.27-210 15.98-406

4.07/103.5 4.07-103.5 4.07-103.5 5.45-138.5 9.25-235

T4 T5 S7

250 400 1250-16003 3 3

80…250 320-400 1000…1600690 690 690

■ ■

■ ■

T4D T5D S6D S7D S8D

3/4 3/4 3/4 3/4 3/4250-320 400-630 800 1000-1250-1600 2000-2500-3200

690 690 690 690 6908 8 8 8 8

800 800 800 800 8005.3 11 30 52.5 85

3.6 6 15 25 40

Page 20: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

1

Page 21: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

1

ABB 1/1

Main characteristics

Index

General information ........................................................................................................... 1/3

Construction characteristics

Modularity of the series ....................................................................................................... 1/4

Distinguishing features of the series .................................................................................... 1/6

Page 22: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB

1

1/2

General information

22

21

23 20

14

15

16

17

6

5

8

9

11

12

10

13

2

7

3

7

14

18

19

Page 23: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB

1

1/3

1SD

C21

0141

F002

3

The ABB family of molded case circuit breakers in conformity withUL 489 and CSA C22.2 No. 5.1 Standard - Tmax and Isomax - isdivided into different, perfectly integrated, ranges (Tmax T1B 1p,T1, T2, T3, T4, T5 and Isomax S6, S7, S8), able to cover a rangeof service currents from 15 to 2500 A.The power distribution circuit breakers are available, with UL 489and CSA C22.2 approval, in the fixed, plug-in or draw out, two-pole, three-pole and four-pole versions.The Tmax T1 circuit breaker is also available in the single poleTmax T1B 1p version, with an interrupting rating of 18 kA at 277 VAC. The circuit breakers can be selected among different inter-rupting rating levels from 22 kA to 150 kA at 480 V AC and from18 kA up to 85 kA at 600 V AC.

Starting from the fixed version circuit breaker, all the other ver-sions used for various requirements are obtained by means ofmounting conversion kits.The following are available:– kit for converting a fixed circuit breaker into the moving part of

a plug-in and draw out one– circuit breaker fixed parts for plug-in and draw out circuit

breakers– conversion kit for the connection terminals.

Various accessories are also available:1. Breaking unit (1)

2. Trip units (1)

3. Front4. Auxiliary contacts - AUX (2)

5. Undervoltage release - UVR (2)

6. Shunt trip - SOR (2)

7. Terminal covers8. Front for lever operating mechanism - FLD9. Direct rotary handle - RHD (2)

10. Stored energy motor operator - MOE (2)

11. Key lock - KLF12. Early auxiliary contact - AUE13. Transmitted rotary handle - RHE (2)

14. Front terminal for copper cable - FC Cu15. Front extended terminal - EF16. Multi-cable terminal (only for T4) - MC17. Front terminal for copper-aluminium - FC CuAl (UL listed)18. Front extended spread terminal - ES19. Rear orientated terminal - R20. Conversion kit for plug-in/draw out versions (2)

21. Guide of fixed part in the draw out version (2)

22. Fixed part - FP (2)

23. Auxiliary position contact - AUP24. Phase separators25. PR010T26. TT127. Racking out crank28. Residual current release.

(1) UL file E93565(2) UL file E116596

24

25

26

27

28

Page 24: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB

1

1/4

Construction characteristicsDistinguishing features of the series

1SD

C21

0142

F002

3

Compliance with Standards and companyQuality SystemThe Tmax and Isomax circuit breakers and their electrical acces-sories conform to the UL 489 (Underwriters Laboratories Incorpo-rated) and CSA C22.2 No.5.1 (Canadian Standard Association)North American Standards, and to the international IEC 60947-2Standards and comply with the EC directive:– “Low Voltage Directives” (LVD) no. 73/23 EEC– “Electromagnetic Compatibility Directive” (EMC) no.89/336 EEC.Certification of conformity with the above-mentioned productStandards is carried out, in respect of the European EN 45011Standard, by the Italian certification body ACAE (Association forCertification of Electrical Apparatus), a member of the EuropeanLOVAG organization (Low Voltage Agreement Group).The ABB test laboratory is accredited by SINAL (certificate no.062/2002).The ABB Quality System complies with the international ISO 9001- 2000 Standard (model for quality assurance in design, develop-ment, construction, installation and service) and with the equiva-lent European EN ISO 9001 and Italian UNI EN ISO 9001 Stand-ards.The independent certifying Body is RINA S.p.A. ABB obtained itsfirst certification with three-year validity in 1990, and has nowreached its fourth reconfirmation.The new Tmax series has a hologram on the front, obtained usingspecial anti-imitation techniques, which guarantees the quality andthat the circuit breaker is an original ABB product.Attention to protection of the environment and to health and safetyin the work place is another priority commitment for ABB and, asconfirmation of this, the company environmental management sys-tem has been certified by RINA in 1997, in conformity with theinternational ISO 14001 Standard. This certification has been inte-grated in 1999 with the Management System for Healt and Safetyin the workplace, according to OHSAS 18001 (British Standards),obtaining one of the first certification of integrated managementSystem, QES (Quality, Environment, Safety) issued by RINA.ABB - the first industry in the electromechanical section in Italy toobtain this recognition - thanks to a revision of the production proc-ess with an eye to ecology, has been able to reduce the con-sumption of raw materials and waste from processing by 20%.ABB’s commitment to safeguarding the environment is also shownin a concrete way by the Life Cycle Assessments of its productscarried out directly by the ABB Research and Development in col-laboration with the ABB Research Center. Selection of materials,processes and packing materials is made optimising the true en-vironmental impact of the product, also foreseeing the possibilityof its being recycled.

Page 25: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB

1

1/5

Positive operationThe operating lever always indicates the exact positionof the circuit breaker moving contacts, therebyguaranteeing safe and reliable signals in compliancewith the prescriptions of the IEC 60417-2 Standard(I = Closed; O = Open; yellow-green line = Open due torelease trip). The circuit breaker operating mechanismhas trip free operation. Trip unit intervention automati-cally opens the moving contacts: to close them again,the operating mechanism must be reset by pushingthe operating lever from the intermediate position intothe lowest open position.

Double insulation*

This construction characteristic consists of the presence of double insulation between the live powerparts (excluding the terminals) and the front parts of the apparatus where the operator works duringnormal operation of the installation. The seat of each electrical accessory is completely segregatedfrom the power circuit, thereby preventing any risk of contact with live parts, and, in particular, theoperating mechanism unit is completely insulated in relation to the powered circuits. As a conse-quence most accessories are field installable.Furthermore, the insulation distances, both between the live internal parts and in the terminal con-nection area, comply with what is foreseen by the UL 489 Standard and are higher than thoserequired by the international IEC Standards.

* Except for Isomax S8

1SD

C21

0143

F002

3

1SD

C21

0144

F002

3

1SD

C21

0145

F002

3

Isolation behaviourIn the open position, the circuit breakerguarantees circuit isolation in compliancewith the IEC 60947-2 Standard. The over-sized insulating distances guarantee thereare no leakage currents and dielectricresistance to any overvoltages betweeninput and output. For plug in and draw outversion circuit breakers, in the racked-outposition, the power and auxiliary circuits areinsulated, guaranteeing that no part is live. By means of special socket-plugs, it is possible to carryout blank tests under these conditions, operating the circuit breaker in complete safety.

Page 26: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB

1

1/6

1SD

C21

0146

F002

3

Operating temperatureThe Tmax and Isomax circuit breakers can be used in ambientconditions where the surrounding air temperature varies between–13 °F and +158 °F (–25 °C and +70 °C) and stored in ambientwith temperatures between –40 °F and + 158 °F (–40 °C and+70 °C). The circuit breakers fitted with thermomagnetic trip unithave their thermal element set for a reference temperature of104 °F (40 °C).For temperatures other than 104 °F (40 °C), with the same setting,there is a variation of the thermal threshold as shown in the tableson page 4/36 and 4/37.The electronic PR211/P, PR212/P, PR221DS and the newPR222DS/P electronic trip units do not undergo any variations inperformance as the temperature varies but, in the case of tem-peratures exceeding 104 °F (40 °C), the maximum setting for pro-tection against overloads, L, must be reduced, as indicated in thederating graphs on page 4/35, to take into account the heatingphenomena which occur in the copper parts of the circuit breakerpassed through by the phase current. For temperature above158 °F (70 °C) the circuit breaker performances are not guaran-teed.

AltitudeUp to an altitude of 6600 ft (2000 m) the Isomax and Tmax do notundergo any alterations in their rated performances. As the alti-tude increases, the atmospheric properties are altered in terms ofcomposition, dielectric resistance, cooling capacity and pressure.For this reason, the rated voltage and the nominalcurrent at this altitudes must be derated to the values shown inthe table.

Construction characteristicsDistinguishing features of the series

Altitude [ft] 6600 9900 13200 16500

Ratedvoltage [V] 600 522 435 348

Continuouscurrentrating % 100 98 93 90

Page 27: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB

1

1/7

1SD

C21

0147

F002

3

1SD

C21

0148

F002

3

Electromagnetic compatibilityWith the use of the PR211/P, PR212/P, PR221DS and PR222DS/Pelectronic trip units and the RC211, RC212, RC221, RC222 andRC223 electronic residual current releases, operation of the protec-tions is guaranteed in the presence of interferences caused by elec-tronic apparatus, atmospheric disturbances or electrical discharges.No interference with other electronic apparatus near the placeof installation is generated either. This is in compliance with theIEC 60947-2 Appendix F Standards and European DirectiveNo. 89/336 regarding EMC – electromagnetic compatibility.

TropicalizationCircuit breakers and accessories in the ABB family of moldedcase circuit breakers have been tested in compliance with theIEC 60068-2-30 Standard, carrying out two cycles at 131 °F(55 °C) with the “variant 1” method (clause 6.3.3). The suitabilityof their use under the most severe environmental conditions istherefore ensured with the hot-humid climate defined inclimatograph 8 of the IEC 60721-2-1 Standards thanks to:– insulating cases made of synthetic resins reinforced with glass

fibers;– anti-corrosion treatment of the main metallic parts– Fe/Zn 12 galvanization (ISO 2081), protected by a conver-

sion layer mainly consisting of chromates (ISO 4520)– application of anti-condensation protection for electronic trip units and relative accessories.

Resistance to shocks and vibrationsThe circuit breakers are unaffected by vibrations generated mechanically and due to electromag-netic effects, in compliance with the IEC 60068-2-6 Standards and the regulations of the majorclassification organizations:– ABS (American Bureau of Shipping)*– RINA– Det Norske Veritas– Bureau Veritas– Lloyd’s register of shipping– Germanischer Lloyd.The Isomax and Tmax circuit breakers are also tested, according to the IEC 60068-2-27 Standard,to resist shocks up to 12g.Please contact ABB for information regarding the types of circuit breakers approved, the perform-ances approved and their relative validity.

*Most of ABB circuit breakers are certified with ABS approval, according to IEC 60947-2; the whole Tmax family has ABS

approval according both with IEC 60947-2 and UL 489.

Page 28: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB

1

1/8

1SD

C21

0152

F002

3

1SD

C21

0150

F002

3

(1) Isomax S8 can be mounted just in vertical position.(2) Isomax S8 can be supplied only from the top

InstallationMolded case circuit breakers can be installed inthe switchboards, mounted in any horizontal, ver-tical or lying down position on the back plate or onrails, without undergoing any derating of their ratedcharacteristics(1). ABB circuit breakers can be in-stalled easily in all types of switchboards, above allthanks to the possibility of being supplied either bytop or bottom terminals, without jeopardising theapparatus functionality(2).

Construction characteristicsDistinguishing features of the series

Racking-out with the door closedWith Tmax T4 and T5 and Isomax S6 and S7 in the draw out version, the circuit breaker can beracked-in and out with the compartment door closed, thereby increasing operator safety and allow-ing rationalisation of low voltage arc proof switchboards. Racking out can only be carried out with

the circuit breaker open (for obvi-ous safety reasons), using a spe-cial racking-out crank supplied withthe conversion kit from fixed circuitbreaker to moving part of draw outcircuit breaker.

Apart from fixing on the base plate, T1, T2 and T3 can also be installed on DIN 50022 rails, thanks tothe special fixing brackets. Furthermore, the depth of 2.76 inches (70 mm) takes Tmax T3 to thesame standard as the two smaller sizes, making assembly of circuit breakers up to 225 A in standardswitchboards even simpler. In fact, it is possible to prepare standardised support structures, facilitat-ing the design stage and construction of the switchboard metalwork.

1SD

C21

0151

F002

3

Page 29: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new
Page 30: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

2

ABB 2/1

The ranges

Index

Circuit breakers for power distribution

Electrical characteristics ........................................................................................................ 2/2

General characteristics .......................................................................................................... 2/4

Thermomagnetic trip units ..................................................................................................... 2/6

Electronic trip units ................................................................................................................ 2/8

Motor control protection circuit breakers: MCP

Magnetic and electronic overcurrent trip units .................................................................... 2/18

Molded case switches: MCS

Electrical characteristics ...................................................................................................... 2/20

Page 31: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

2

ABB2/2

Circuit breakers for power distributionElectrical characteristics

T1 1P T1 T2 T3Frame size [A] 100 100 100 225

Numbers of poles Nr 1 3-4 2-3-4 (3) 2-3-4 (3)

Rated voltage (AC) 50-60Hz [V] 277 480 480 480

(DC) [V] 500 500 500Test voltage (1min) 50-60 Hz [V] 3000 3000 3000 3000

Interrupting ratings [kA rms] B N S H N S240 V AC [kA rms] 50 (2) 65 150 50 65

277 V AC [kA rms] 18 (1)

480 V AC [kA rms] 22 35 65 25 35

600 V AC [kA rms]250 V DC (2 poles in series) [kA rms] 25 25 35

500 V DC (3 poles in series) [kA rms] 25 25 35500 V DC (2 poles in series) [kA rms]

600 V DC (3 poles in series) [kA rms]Trip units Thermomagnetic ■ ■ ■ ■

Electronic ■

Dimensions fixed version (3p) H [in-mm] 5.12-130 5.12-130 5.12-130 5.9-150

W [in-mm] 1-25.4 3-76 3.54-90 4.13-105D [in-mm] 2.76-70 2.76-70 2.76-70 2.76-70

Mechanical life [operations] 25000 25000 25000 25000Weights (fixed 3p) [lbs] 1.06 2.34 2.86 5.45

Note: for S6 4 poles only for N versions(1) In 15A = 10 KA @ 277 V AC(2) In 15A = 35 KA @ 240 V AC 14 KA @ 277/480 V AC(3) Ask ABB for two-pole version availability(4) Please ask ABB for 600 A availability

Page 32: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

2

ABB 2/3

T4 T5 S6 S7 S8250 400-600 (4) 800 1200 1600-2000-2500

2-3-4 (3) 2-3-4 (3) 2-3-4 2-3-4 3600 600 600 600 600

600 600 6003500 3500 3000 3000 3000

N S H L V N S H L V N H L H V65 100 150 200 200 65 100 150 200 200 65 150 200 100 125

25 35 65 100 150 25 35 65 100 150 50 65 100 65 100

18 25 35 65 85 18 25 35 65 85 25 35 42 50 85

25 35 50 65 100 25 35 50 65 100 35 50 65

16 25 35 50 65 16 25 35 50 65 20 35 50■ ■ ■

■ ■ ■ ■ ■

8.07/205 8.07/205 14.25-268 16-406 15.75-400

4.13/105 5.51/140 8.27-210 8.27-210 15.98-4064.07/103.5 4.07-103.5 4.07-103.5 5.45-138.5 9.25-235

20000 20000 20000 10000 100006.18 8.55 22 37.5 135

Page 33: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

2

ABB2/4

Circuit breakers for power distributionGeneral characteristics

General characteristicsThe ABB family of molded case circuit breakers, complying withthe UL 489 and CSA C22.2 No. 5.1 Standards, is divided intodifferent sizes, with an application range from 15 to 2500 A andinterrupting ratings up to 150 kA at 480 V AC.Selection of the size allows the basic electrical characteristics tobe identified simply and immediately, whereas selection of theovercurrent trip unit is made according to the type of applicationrequired.Furthermore, for the first time ABB has also developed a moldedcase circuit breaker with a single-pole construction characteristic:T1B 1p. This is a 100 A frame size circuit breaker, able to operateat rated voltages up to 277 V AC.For protection of alternating current networks, the following areavailable:– Tmax T1B 1p, T1, T2, T3 and T4 (15 A, 20 A) circuit breakers,

equipped with TMF thermomagnetic trip units, with fixed ther-mal and magnetic threshold (I3 = 10 x In);

– Tmax T4 (up to 50 A) circuit breaker equipped with TMDthermomagnetic trip units with adjustable thermal threshold(I1 = 0.7…1 x In) and fixed magnetic threshold (I3 = 10 x In).

– T4, T5 and Isomax S6 circuit breakers with TMA thermomag-netic trip units, with adjustable thermal threshold (I1 = 0.7…1 xIn) and adjustable magnetic threshold (I3 = 5…10 x In).

– T2 with PR221DS electronic trip unit– T4 and T5 with PR221DS, PR222DS/P and PR222DS/PD elec-

tronic trip unit– Isomax S6, S7 and S8 with PR211/P and PR212/P electronic

trip unit.

■ = complete circuit breaker already coded▲ = circuit breaker to be assembled (separate codes of the circuit breaker part plus trip unit)

Trip unitTMF TMD TMA

Circuit breakersIn [A] 15 20 30 40 50 80 100 125 150 200 250 300 400 600T4 250 ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■

T5 400 ■ ■

T5 600 ■

InterchangeabilityTmax T4 and T5 circuit break-ers can be equipped eitherwith TMD or TMA thermomag-netic trip units, PR221DS,

PR222DS/P and PR222DS/PDelectronic trip units. Thanks totheir simplicity of assembly, theend customer can, in fact,

change the type of trip unit ex-tremely rapidly, according totheir own requirements andneeds: in this case, correct as-

Page 34: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

2

ABB 2/5

Range of application of the alternating anddirect current circuit breakers

Trip unit Range [A]

ACT1B 1p TMF 15…100

T1 TMF 15…100T2 TMF 15…100

PR221DS 25…100T3 TMF 60…225T4 TMF/TMD/TMA 15…250

PR221DS 100…250PR222DS/P 100…250

PR222DS/PD 100…250T5 TMA 300-400-600

PR221DS 300-400-600PR222DS/P 300-400-600

PR222DS/PD 300-400-600S6 TMA 600-800

PR211/P 400…800PR212/P 400…800

S7 PR211/P 1000-1200PR212/P 1000-1200

S8 PR212/P 1600…2500

DCT1 TMF 15…100

T2 TMF 15…100T3 TMF 60…225T4 TMF/TMD/TMA 15…250T5 TMA 300-400-600S6 TMA 800

TMF = Fixed thermomagnetic trip unitTMD = Thermomagnetic trip unit with adjustable thermal and fixed magnetic thresholdTMA = Thermomagnetic trip unit with adjustable thermal and adjustable magnetic thresholdELT = Electronic trip unit

sembly is under the customer’sresponsibility. Above all, thismeans into increased flexibilityof use of the circuit breakers

with considerable savings interms of costs thanks to betterrationalisation of stock manage-ment.

Tmax T2 and T3 offer a magnetic-only trip unit: I3 = 6…12 x In.Finally, Tmax T1, T2, T3, T4 andT5 and Isomax S6 circuit break-ers fitted with thermomagnetictrip units can also be used indirect current plants, with an ap-plication range from 15 to 800 Aand a minimum operating voltageof 24 V DC.

PR221DS-LS/I or I PR222DS/P-LSI or LSIG PR222DS/PD-LSI or LSIG

100 150 250 300 400 600 100 150 250 300 400 600 100 150 250 300 400 600■ ■ ■ ■ ■ ■ ▲ ▲ ▲

■ ■ ■ ■ ▲ ▲

■ ■ ▲

Page 35: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

2

1SD

C21

0170

F002

3

ABB2/6

Circuit breakers for power distributionThermomagnetic trip units

Thermomagnetic trip unitsTmax T1B 1p, T1, T2, T3, T4 and T5, and Isomax S6 circuit breakerscan be fitted with thermomagnetic trip unit and are used in protectionof alternating current networks or direct current networks with a rangeof application from 15 A to 800 A. They allow protection against over-loads with a thermal device (fixed threshold for T1B 1P, T1, T2, T3, T4up to 20 A; adjustable threshold between 0.7÷1 x In for T4, T5 andS6), made using the bimetal technique, and protection against

TMF = thermomagnetic trip unit with fixedthermal threshold (I1 = In) and fixedmagnetic thresold (I3 = 10 x In).

TMD = thermomagnetic trip unit with adjustablethermal threshold (I1 = 0,7…1 x In) andfixed magnetic threshold (I3 = 10 x In).

TMA = thermomagnetic trip unit with adjustablethermal threshold (I1 = 0.7…1 x In)and adjustable magnetic threshold(I3 = 5…10 x In).

Thermal thresholdAdjustable from 0.7 to 1 x In

1SD

C21

0172

F002

3

Thermal thresholdAdjustable from 0.7 to 1 x In

Magnetic thresholdAdjustable from 5 to 10 x In

Thermomagnetic trip unit TMF, TMD and TMA

Magnetic thresholdFixed (I3 = 10 x In)

TMD

TMA

Page 36: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

2

ABB 2/7

short-circuit with a magnetic device (fixed threshold for T1 1P, T1, T2,T3 and T4 up to 50 A, adjustable threshold between 5÷10 x In for T4,T5 and S6; Isomax S6 can also offer a fixed magnetic threshold of2.5 x In).The four-pole circuit breakers are always supplied with the neutralprotected by the trip unit and protection of the neutral at 100% of thephase setting.

Thermomagnetic trip units

In [A] 15 20 25 30 35 40 50 60 70 80 90 100 125 150 175 200 225 250 300 400 600 800

Neutral [A] 15 20 25 30 35 40 50 60 70 80 90 100 125 150 175 200 225 250 300 400 600 800

T1 (I1=In) ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■

T2 (I1=In) ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■

T3 (I1=In) ■ ■ ■ ■ ■ ■ ■ ■ ■ ■

T4 (I1=In) ■ ■

T4 (I1=0.7...1xIn) ■ ■ ■ ■ ■ ■ ■ ■ ■

T5 400 (I1=0.7...1xIn) ■ ■

T5 600 (I1=0.7...1xIn) ■

S6 (I1=0.7...1 x In) ■ ■

T1

I3 [A] 1000 1000 1000 1000 1000 1500 1500 1500 1500 1500 1500

Neutral [A] 1000 1000 1000 1000 1000 1500 1500 1500 1500 1500 1500

T2, T3

I3 [A] 500 500 500 500 500 500 500 600 700 800 900 1000 1250 1500 1750 2000 2250

Neutral [A] 500 500 500 500 500 500 500 600 700 800 900 1000 1250 1500 1750 2000 2250

T4, T5, S6

I3 [A] 500 500 500 500 500 400 500 625 750 1000 1250 1500 2000 3000 4000800 1000 1250 1500 2000 2500 3000 4000 6000 8000

Neutral [A] 500 500 500 500 500 400 500 625 750 1000 1250 1500 2000 3000 4000800 1000 1250 1500 2000 2500 3000 4000 6000 8000

S6

I3 = 2.5 x In [A] 1500 2000

Page 37: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

2

ABB2/8

General characteristicsTmax T2, T4 and T5 circuit breakers for uses in alternating currentcan be equipped with PR221DS, the new PR222DS/P andPR222DS/PD electronic trip units. On the other hand, Isomax S6,S7 and S8 can be fitted with PR211/P and PR212/P. The elec-tronic technology used to realise these trip units guarantees greatreliability, trip precision and immunity to electromagnetic compo-nents in compliance with the standards on the matter. The powersupply required for correct operation is supplied directly by the tripunits current transformers and tripping is always guaranteed, evenunder single-phase load conditions and in correspondence withthe minimum setting.The protection trip units are made up of the current transformers(three or four depending on the number of conductors to beprotected), the protection unit (PR221DS, PR222DS/P,PR222DS/PD, PR211/P or PR212/P), and of a trip coil with de-magnetisation, which acts directly on the circuit breaker operatingmechanism unit. It is possible to test the trip coil by means of theTT1 device. A positive test will trip the breaker.The current transformers are housed inside the trip unit box andsupply the energy required for correct operation of the protectionand the signal needed to detect the current. They are availablewith primary rated current as indicated in the table.

Circuit breakers for power distributionElectronic trip units

Characteristics of PR221DS, PR222DS/P, PR211/P, PR212/P electronic trip unitsOperating temperature -13 °F...+158 °F (-25 °C...+70 °C)

Relative humidity 90%Service Frequency 45...66 Hz able to measure harmonics up to 550 Hz

Electromagnetic compatibility (LF and HF) IEC 60947-2 Annex FElectrostatic discharges IEC 61000-4-2

Radiated electromagnetic field IEC 61000-4-3Short-time transients IEC 61000-4-4

Mean time between failure (MTBF) 15 years (at 113 °F/45 °C)Characteristics of the signalling contact (for PR211/P and PR212/P only)

Maximum interrupted current 0.5 AMaximum interrupted voltage 24 V DC/AC

Breaking capacity 3W/VAContact/contact insulaton 500 V AC

Contact/coil insulation 1000 V AC

Page 38: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

2

ABB 2/9

Current transformers

PR221DS In [A] 25 60 100 150 250 300 400 600

T2 ■ ■ ■

T4 ■ ■ ■

T5 400 ■ ■

T5 600 ■

L 10…25 24…60 40…100 60…150 100…250 120…300 160…400 240…600S 25…250 60…600 100…1000 150…1500 250…2500 300…3000 400…4000 600…6000

I 25…250 60…600 100…1000 150…1500 250…2500 300…3000 400…4000 600…6000

PR222DS/P or In [A] 100 150 250 300 400 600PR222DS/PD T4 ■ ■ ■

T5 400 ■ ■

T5 600 ■

L 40…100 60…150 100…250 120…300 160…400 240…600

S 60…1000 90…1500 150…2500 180…3000 240…4000 360…6000I 150…1200 225…1800 375…3000 450…3600 600…4800 900…7200

G 20…100 30…150 50…250 60…300 80…400 120…600

PR211/P In [A] 400 600 800 1000 1200

S6 ■ ■ ■

S7 ■ ■

L 160…400 240…600 320…800 400…1000 480…1200

I 600…4800 900…7200 1200…9600 1500…12000 1800…14400

PR212/P In [A] 400 600 800 1000 1200 1600 2000 2500

S6 ■ ■ ■

S7 ■ ■

S8 ■ ■ ■

L 160…400 240…600 320…800 400…1000 480…1200 640…1600 800…2000 1000…2500

S 400…4000 600…6000 800…8000 1000…10000 1200…12000 1600…16000 2000…20000 2500…25000

I 600…4800 900…7200 1200…9600 1500…12000 1800…14400 2400…19200 3000…24000 3750…30000

G 80…400 120…600 160…800 200…1000 240…1200 320…1600 400…2000 500…2500

Page 39: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

2

1SD

C21

0173

F002

3

ABB2/10

Circuit-breakers for power distributionElectronic trip units

Protection LAgainst overload

Protection SAgainst short-circuit withdelayed trip

Protection IAgainst short-circuit with

instantaneous trip

Socket forTT1 test unit

PR221DS - Tmax T2, T4 and T5The PR221DS trip unit, available for T2, T4 and T5, provides protection functions against overload L,and short-circuit S or I (version PR221DS-LS/I): with this version, you can choose between protec-tion S or I simply by moving the dip-switch. Alternatively, the version with only the function of protec-tion against instantaneous short-circuit I is available (version PR221DS-I).The PR221DS for Tmax T2 has some differences if compared with the one used with T4 and T5.With Tmax T2, the trip unit is not interchangeable, protection against overload L can be set manuallyat I1 = 0.4…1 x In, with 16 thresholds by means of a dip switch on the front of the circuit breaker, andit is possible to select between 2 trip curves 3s at 6 x I1 and 6s at 6 x I1.On the other side, with Tmax T4 and T5, the trip unit is interchangeable; furthermore, protection Lcan be set manually at I1 = 0.4…1 x In with 16 thresholds by means of a dip switch and it is possibleto select between 2 different trip curves 3s at 6 x I1 and 12s at 6 x I1.

PR221DS-LS/I

Dip-switches for setting theneutral (only for T4 and T5)

Page 40: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

2

ABB 2/11

The protection function against short-circuit with delayed trip S, with inverse short time delay and tripcharacteristic with inverse time (I2t = const), can be set to I2 = 1…10 x In with 15 thresholds. Thisprotection is selectable as an alternative to protection function I. The protection time delay can beselected by adjusting the dip switches on one of the two available curves (0.1s at 8 x In, 0.25s at8 x In).The protection function against instantaneous short-circuit I can be adjusted to I3 = 1…10 x In with15 thresholds.Concerning to neutral protection, for Tmax T2 the protection of the neutral is set to 100% of thephase protection setting, whereas for T4 and T5 it is possible to select the protection threshold OFF,50% or 100% directly from the front of the trip unit by means of the specific dip switch.

PR221DS - Protection functions and settingsProtection functions Trip threshold Trip curves(1)

Against overload with long in-verse time delay trip and tripcharacteristic according to aninverse time curve (I2t=constant)

I1 = 0.40 - 0.44 - 0.48 - 0.52 -0.56 - 0.60 - 0.64 - 0.68 -0.72 - 0.76 - 0.80 - 0.84 -0.88 - 0.92 - 0.96 - 1 x In

Release between 1.1...1.3 x I1(IEC 60947-2 and UL 489)

at 6 x I1 at 6 x I1 at 6 x I1t1 = 3s t1 = 6s t1 = 12s

only for T2 only forT4, T5

Tolerance: ± 10% up to 6 x In;± 20% above 6 x In

CANNOT BEEXCLUDED

CAN BEEXCLUDED

CAN BEEXCLUDED

Against short-circuit with instan-taneous trip (selectable asan alternative to protection func-tion S)

Against short-circuit with inverseshort time delay trip and trip char-acteristic with inverse time(I2t=constant) (selectable as an al-ternative to protection function I)

(1) These tolerances hold in the following conditions:– self-powered relay at full power and/or auxiliary supply;– two or three-phase power supply.

istantaneous ≤ 25ms

I2 = 1 - 1,5 - 2 - 2,5 - 3 - 3,5 - 4,5 -5,5 - 6,5 - 7 - 7,5 - 8 - 8,5 - 9 -10 x In

Tolerance: ± 10% (T4-T5)± 10% up to 2 x In (T2)± 20% above 2 x In (T2)

I3 = 1 - 1,5 - 2 - 2,5 - 3 - 3,5 - 4,5 -5,5 - 6,5 - 7 - 7,5 - 8 - 8,5 - 9 -10 x In

Tolerance: ± 10% (T4-T5)± 20% (T2)

a 8 x In a 8 x Int2 = 0,1s t2 = 0,25s

Tolerance: ± 10% up to 6 x In (T4-T5)± 20% above 6 x In (T4-T5)± 20% (T2)

– peak factor peak = √2 (L and S with current ≥ 3 In; I)rms( )

Page 41: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

2

ABB2/12

PR222DS/P - Tmax T4 and T5The PR222DS/P trip unit, available for T4 and T5, has protectionfunctions against overload L, delayed S and instantaneous I short-circuit (version PR222DS/P-LSI) and, alternatively, as well as thefunctions L, S, I also has protection against earth fault G (versionPR222DS/P-LSIG).Function L, which cannot be excluded, can be set manually toI1 = 0.4…1 x In with 32 thresholds by means of the dip switches orelectronically by means of the PR010T test and configuration unit:in this case the thresholds are 61 (steps of 0.01 In). Furthermore,it is possible to select among 4 different trip curves: 3s at 6 x I1, 6sat 6 x I1, 9s at 6 x I1, 12s at 6 x I1 for T4 In = 250 A and T5 = 600 A,and 18s at 6 x I1 for all the other settings.The protection function against short-circuit with delayed trip S,with inverse short time delay and trip characteristic with inversetime (I2t = const) can be set to I2 = 0.6…10 x In with 15 thresholdsby means of the dip switches or electronically by means of thePR010T test and configuration unit, with 95 thresholds (steps of0.1 x In). The time delay of the protection can be selected eithermanually by adjusting the dip switch to one of the 4 curves avail-able (with delay of 0.05s at 8 x In, 0.1s at 8 x In, 0.25s at 8 x In or0.5s at 8 x In) or electronically by means of PR010T between 0.05and 0.5s at 8 x In with 46 thresholds (steps of 0.01s).The protection function against instantaneous short-circuit Ican be adjusted to I3

(1) = 1.5…12 x In with 15 thresholds, by meansof the dip switches or electronically by means of the PR010T testand configuration unit, with 86 thresholds (steps of 0.1 x In).The function of protection against earth fault G is adjustable eithermanually, by means of dip switches, to I4 = 0.2…1 x In, with7 thresholds or electronically with PR010T, with 81 thresholds (stepsof 0.01 In). It is also possible to select among 4 different trip curves:0.1 s at 3.25 x I4, 0.2s at 2.25 x I4, 0.4s at 1.6 x I4 and 0.8s at1.25 x I4, or to set the trip time electronically between 0.1 and 0.8swith 71 thresholds (steps of 0.01s).Concerning to neutral protection, it is possible to select the pro-tection threshold OFF, 50% or 100% directly from the front of therelease by means of the specific dip switch.Furthermore, on the front of the trip unit, signalling of pre-alarmand alarm of protection L is available. The pre-alarm thresholdvalue is equal to 0.9 x I1 (cannot be modified or excluded).

Circuit breakers for power distributionElectronic trip units

(1) For T5 In = 600 A ⇒ I3max = 10 x In

Page 42: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

2

ABB 2/13

PR222DS/PDplus the extra protection G(version PR222/PD-LSIG), thePR222DS/PD trip unit, availablefor T4 and T5, also has the dia-logue unit integrated with

Communication functions PR222DS/P PR222DS/PDProtocol Modbus RTU

standardPhysical medium EIA RS485

Speed (maximum) 19200bpsMeasurement functionsPhase currents ■ (1) ■

Neutral ■ (1) ■

Earth ■ (1) ■

Signalling functionsL pre-alarm and alarm LED ■ ■

L alarm output contact (2) ■ ■

Data availableState of the circuit-breaker (open, closed) ■

Mode (local, remote) ■

Protection parameters set ■ (1) ■

AlarmsProtections: L, S, I, G ■ (1) ■

Release control for failed fault ■ (1) ■

MaintenanceTotal number of operations ■

Total number of trips ■

Number of trip tests ■

Number of manual operations ■

Number of trips for each individualprotection function ■

Record of last trip data ■

CommandsCircuit breaker opening/closing(with motor operator) ■

Alarm reset ■

Circuit breaker reset (with motor operator) ■

Setting the protection curves and thresholds ■ (1) ■

Safety functionAutomatic opening in the case of failedrelease for fault (with motor operator) ■

EventsChanges in circuit breaker state,in the protections and all the alarams ■

(1) With PR010/T unit(2) Typical contact: MOS photo Vmax: 48 V DC/30 V AC

Imax: 50 mA DC/35 mA AC

Auxiliary power supply - Electrical characteristics

PR222DS/PDAuxiliary power supply (galvanically insulated) 24 V DC ± 20%

Maximum ripple 5%

Inrush current @ 24 V 1 A for 30 ms

Rated current @ 24 V 100 mA

Rated power @ 24 V 2.5 W

Modbus RTU protocol.PR222PD allows Tmax T4 andT5 circuit breakers to be inte-grated in a communication net-work based on the ModbusRTU protocol. The devices usethe EIA RS485 standard as thephysical means for data trans-mission at a maximum trans-mission speed of 19200 bit/sec.If the power for protection func-tion is supplied directly by thecurrent transformers of the re-lease, communication is onlypossible with an auxiliary powersupply of 24 V DC.All the information provided bythe trip unit (measurement func-tions, alarms, maintenancedata, state of the circuit breaker)can be consulted both locally,directly on the front of the cir-cuit breaker, and remotely bymeans of supervision and con-trol systems.The PR222DS/PD trip unit canbe associated with the AUX-Eauxiliary contacts in electronicversion, to know the state of thecircuit breaker (open/closed),and with AUX-E plus MOE-Emotor operator (the AUX-E arecompulsory when MOE-E is tobe used) to remotely control cir-cuit breaker opening and clos-ing as well.

Apart from the protection func-tions against overload L, de-layed S and instantaneous Ishort-circuit (version PR222DS/PD-LSI) or, alternatively,

Page 43: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

2

1SD

C21

0174

F002

31S

DC

2101

75F0

023

ABB2/14

Circuit breakers for power distributionElectronic trip units

PR222DS/PD

PR222DS/P

Protection LAgainst overload

Protection GAgainst earth fault

Dip-switches forsetting the neutral

Selection for electronicor manual setting

Socket for testTT1 test unit

Socket for connection ofPR010/T test unit

Protection LAgainst overload

Protection GAgainst earth fault

Dip-switches forsetting the neutral

Selection for localor remote setting

Socket for testTT1 test unit

Socket for connection ofPR010/T test unit

Protection SAgainst short-circuitwith delayed trip

Protection IAgainst short-circuit

with instantaneous trip

Protection SAgainst short-circuitwith delayed trip

Protection IAgainst short-circuit

with instantaneous trip

Selection for electronicor manual setting

Page 44: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

2

ABB 2/15

PR222DS/P and PR222DS/PD - Protection functions and settingsProtection functions Trip threshold Trip curves(1)

Against overload with long in-verse time delay trip and tripcharacteristic according to aninverse time curve (I2t= con-stant)

Manual settingI3 = 1.5 - 2.5 - 3 - 4 - 4.5 - 5 -

5.5 - 6.5 - 7 - 7.5 - 8 - 9 -9.5 - 10.5 - 12 x In (3)

Electronic settingI3 = 1.5…12 x In (step 0.1 x In) (3)

Tolerance: ± 10%

CANNOT BEEXCLUDED

CAN BEEXCLUDED

CAN BEEXCLUDED

Against short-circuit withinstantaneous trip

Against short-circuitwith inverse shorttime delay trip andtrip characteristicwith inverse time(I2t= constant) or defi-nite time

Manual settingI4 = 0.2 - 0.25 - 0.45 - 0.55 -

0.75 - 0.8 - 1 x In

Electronic settingI4 = 0.2…1 x In (step 0.01 x In)

Tolerance: ± 10%

CAN BEEXCLUDED

Against earth fault with inverseshort time delay trip and tripcharacteristic according to aninverse time curve (I2t= con-stant)

(1) These tolerances hold in the following conditions:– self-powered relay at full power and/or auxiliary supply;– two or three-phase power supply– sinusoidal wave forms with peak factor 1.41– peak factor peak = √2 (L ≥ 3 In; S, I, G)

rms

Manual settingI1 = 0.40 - 0.42 - 0.44 - 0.46 -

0.48 - 0.50 - 0.52 - 0.54 -0.56 - 0.58 - 0.60 - 0.62 -0.64 - 0.66 - 0.68 - 0.70 -0.72 - 0.74 - 0.76 - 0.78 -0.80 - 0.82 - 0.84 - 0.86 -0.88 - 0.90 - 0.92 - 0.94 -0.96 - 0.98 - 1 x In

Electronic settingI1= 0.40…1 x In (step 0.01 x In)

Release between 1.1...1.3 x I1(IEC 60947-2 and UL 489)

Manual settingat 6 x I1 at 6 x I1 at 6 x I1 at 6 x I1t1 = 3s t1 = 6s t1 = 9s t1 = 18s(2)

Electronic settingat 6 x I1 t1 = 3…18s (step 0.5s)(2)

Tolerance: ± 10%

Manual settingI2 = 0.6 - 1.2 - 1.8 - 2.4 - 3.0 -

3.6 - 4.2 - 5.8 - 6.4 - 7.0 -7.6 - 8.2 - 8.8 - 9.4 - 10 x In

Electronic settingI2 = 0.60…10 x In (step 0.1 x In)

Tolerance: ± 10%

Manual settingat 8 x In at 8 x In at 8 x In at 8 x Int2 = 0.05s t2 = 0.1s t2 = 0.25s t2 = 0.5s

Electronic settingat 8 x In t2 = 0.05…0.5s (step 0.01s)

Tolerance: ± 10% (4)

I2t=const ON

Manual settingI2 = 0.6 - 1.2 - 1.8 - 2.4 - 3.0 -

3.6 - 4.2 - 5.8 - 6.4 - 7.0 -7.6 - 8.2 - 8.8 - 9.4 - 10 x In

Electronic settingI2 = 0.60…10 x In (step 0.1 x In)

Tolerance: ± 10%

Manual settingt2 = 0.05s t2 = 0.1s t2 = 0.25s t2 = 0.5s

Electronic settingt2 =0.05…0.5s (step 0.01s)

Tolerance: ± 10%(4)

I2t=const OFF

Manual settingup to up to up to up to3.15 x I4 2.25 x I4 1.6 x I4 1.10 x I4 t4 = 0.1s t4 = 0.2s t4 = 0.4s t4 = 0.8s

Electronic settingt4 = 0.1...0.8 x In (step 0.01s)

Tolerance: ± 20%

istantaneous ≤ 25 ms

(2) for T4 In = 250 A and T5 In = 600 A ⇒ t1 = 12s(3) for T4 In = 250 A and T5 In = 600 A ⇒ I3max = 10 x In(4) tolerance: ± 10 ms up to t2 = 0.1s

( )

Page 45: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

2

PR211/P - Isomax S6 and S7PR211/P trip unit (available for Isomax S6 and S7) provides protection functions against overload Land instantaneous short-circuit I, and is available in the versions with functions I and LI.Function L, which cannot be excluded, can be set manually to I1 = 0.4…1 x In by means of the dipswitches on the front of the circuit-breaker. Furthermore, it is possible to select among 4 different tripcurves: 3s at 6 x I1, 6s at 6 x I1, 12s at 6 x I1 and 18s at 6 x I1.The protection function against instantaneous short-circuit I can be adjusted to I3 = 1.5…12 x In bymeans of the dip switches.Neutral protection is set to 50% of the phase protection. Ask ABB for the 100% version.

PR212/P - Isomax S6, S7 and S8PR212/P trip unit (available from Isomax S6 to S8) provides protection functions against overload L,delayed short-circuit S and instantaneous short-circuit I, and against earth fault G. It is available inthe versions PR212/P with functions LSI and LSIG.

ABB2/16

Circuit breakers for power distributionElectronic trip units

1SD

C21

0467

F000

3Protection LAgainst overload

Protection IAgainst short-circuit withinstantaneous trip

Socket forTT1 test unit

1SD

C21

0466

F000

3

Protection SAgainst short-circuitwith delayed trip

Protection GAgainst earth fault

Protection LAgainst overload

Protection IAgainst short-circuit withinstantaneous trip

Socket for connection ofPR010/T Test unit

Socket forTT1 test unit

Dip-switch forsetting the neutral

Selection for electronicor manual setting

PR211/P

PR212/P

Page 46: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

2

Function L, which cannot be excluded, can be set manually to I1 = 0.4…1 x In by means of the dipswitches on the front of the circuit-breaker. Furthermore, it is possible to select among 4 different tripcurves: 3s at 6 x I1, 6s at 6 x I1, 12s at 6 x I1 and 18s at 6 x I1.The protection function against short-circuit with delayed trip S, with inverse short time delay and tripcharacteristic with inverse time (I2t = const), can be set to I2 = 1…10 x In by means of the dipswitches or electronically by means of the PR010T test and configuration unit. The time delay of theprotection can be selected either manually by adjusting the dip switch to one of the 4 curves avail-able (with delay of 0.05s at 8 x In, 0.1s at 8 x In, 0.25s at 8 x In or 0.5s at 8 x In) or electronically bymeans of PR010T between 0.05 and 0.5s at 8 x In. The protection functions against instantaneousshort-circuit I and earth fault G can be adjusted respectively to I3 = 1.5…12 x In and I4 = 0.2…1 x In,by means of the dip switches or electronically by means of the PR010T.For four-pole circuit breakers, protection of the neutral can be set to 50% or 100% of the phaseprotection setting, by means of dip-switches on the front of the trip unit.Setting the adjustment parameters of the protection functions is carried out directly from the front ofthe trip unit or remotely, thanks to the use of the PR212/D (IEC only) dialogue unit, available withModbus or LON communication protocols.

ABB 2/17

I2t=constON

PR211/P and PR212/P - Protection functions and settings

Protection function Trip threshold Trip curvesA B C D

Against overload with in-verse long time delay andtrip characteristic accord-ing to a time dependentcurve (I2t = constant)

Against short-circuit withinverse short time delayand trip characteristicwith dependent time(I2t = constant) or inde-pendent time

Against short-circuit withadjustable instantaneoustrip

I1 = 0.4 - 0.5 - 0.6 - 0.7 - 0.8 - 0.95 -1 x In - PR211/P0.4 - 0.5 - 0.55 - 0.6 - 0.65 -0.7 - 0.75 - 0.8 - 0.85 - 0.875 -0.9 - 0.925 - 0.95 - 0.975 -1 x In - PR212/P

Release between 1.05…1.30 x I1(IEC 60947-2 and UL 489)

I2 = 1 - 2 - 3 - 4 - 6 - 8 - 10 x In

Tolerance ± 10%

I2 = 1 - 2 - 3 - 4 - 6 - 8 - 10 x In

Tolerance ± 10%

I3 = 1.5 - 2 - 4 - 6 - 8 - 10 - 12 x In

Tolerance ± 20%

CANNOT BEEXCLUDED

CAN BEEXCLUDED

CAN BEEXCLUDED

Against earth fault withshort inverse time delayand trip characteristic ac-cording to a dependenttime curve (I2t = constant)

I4 = 0.2 - 0.3 -0.4 - 0.6 - 0.8 - 0.9 -1xIn

Tolerance ± 20%CAN BE

EXCLUDED

at 6 x I1 at 6 x I1 at 6 x I1 at 6 x I1t1 = 3s t1 = 6s t1 = 12s t1 = 18s

(tolerance: + 10% up to 2 x In; + 20% above 2 x In)

at 8 x In at 8 x In at 8 x In at 8 x Int2 = 0.05s t2 = 0.1s t2 = 0.25s t2 = 0.5s

(tolerance: + 20% )

t2 = 0.05s t2 = 0.1s t2 = 0.25s t2 = 0.5s

(tolerance: + 20% )

up to up to up to up to3.25 x I4 2.25 x I4 1.6 x I4 1.25 x I4t4 = 100ms t4 = 200ms t4 = 400ms t4 = 800ms

(tolerance: + 20% )

I2t=constOFF

Page 47: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

2

General characteristicsMCP circuit breakers are used to protect three phase asynchro-nous motors.The traditional system used for this purpose is based on threedifferent devices: a circuit breaker for protection against short-cir-cuit, a thermal relay for protection against overload and phaseloss or unbalance of phase, and a contactor for motor switching.All this has to take into account the problems that arise at themoment of the motor starting.In particular, when selecting these devices, different factors mustbe taken into consideration, such as:– the motor power– the diagram and type of starting– the type of motor: with cage rotor or with wound rotor– the fault current at the point of the network where the motor is

installed.

Motor control protection circuit breakers: MCPMagnetic and electronic trip units

MCP T2 T3 T4 T5 S6 S7 S8

Frame size 100 225 250 400-600* 800 1200 1600-2000-2500

Poles 3 3 3 3 3 3 3Ratings 20…100 100…200 100-150-250 300-400-600 800 1000-1200 1600-2000-2500

Interrupting ratings S H S N S H L N S H L N H L H V240 V AC 65 150 65 65 100 150 200 65 100 150 200 65 150 200 100 120

480 V AC 35 65 35 25 35 65 100 25 35 65 100 50 65 100 65 100600 V AC 18 25 55 65 18 25 35 35 25 35 42 50 85

500 V DC 35600 V DC

Trip unitAdjustablemagnetic only (6…12 x In) ■ ■ ■

Electronic PR221DS-I ■ ■ ■ ■ ■ ■ ■ ■ ■ ■

PR211/P-I ■ ■ ■ ■ ■

ABB2/18

1SD

C21

0178

F002

3

* Please ask ABB for 600 A availability

Page 48: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

2

ABB offers two different protection types:– a magnetic only trip unit (MA) for Tmax T2 and T3, with adjust-

able threshold between 6…12 x In– an electronic trip unit with only an instantaneous short-circuit

protection function I, PR221DS-I for Tmax T2, T4 and T5, andPR211/P-I for Isomax S6, S7 and S8. For PR221DS-I, protec-tion I is adjustable between 1…10 x In, whereas the range forPR211/P is 1.5…12 x In.

Electronic trip units

In [A] 25 60 100 150 250 300 400 600 800 1000 1200 1600 2000 2500T2 ■ ■ ■

T4 ■ ■ ■

T5 ■ ■ ■

S6 ■

S7 ■ ■

S8 ■ ■ ■

Trip current function II3 [A] 25 60 100 150 250 300 400 600 1200 1500 1800 2400 3000 3750

÷ ÷ ÷ ÷ ÷ ÷ ÷ ÷ ÷ ÷ ÷ ÷ ÷ ÷250 600 1000 1500 2500 3000 4000 6000 1600 12000 14400 19200 24000 30000

MA - Magnetic only trip unit

I3 = 6…12 x In

In [A] 20 50 100 125 150 200

T2 ■ ■ ■

T3 ■ ■ ■ ■

I3 [A] 120…240 300…600 600…1200 750…1500 900…1800 1200…2400

PR211/P (Isomax S6…S8) - Protection functions and settings

Protection function Trip threshold

Against short-circuit with adjust-able instantaneous trip

I3 = 1.5 - 2 - 4 - 6 - 8 - 10 - 12 x In

Tolerance ± 20%

I2t=constON

PR221DS-I (Tmax T2, T4 and T5) - Protection functions and settings

Protection function Trip threshold

Against short-circuit with adjust-able instantaneous trip

I3 = 1 - 1.5 - 2 - 2.5 - 3 - 3.5 - 4.5 - 5.5 - 6.5 - 7 - 7.5 - 8 - 8.5 - 9 - 10 x In

Tolerance ± 20%

ABB 2/19

Page 49: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

2

General characteristicsThe MCS can be used as general circuit breakers in sub-switch-boards, as switching and isolation parts for lines, busbars or groupsof apparatus, or as bus-ties. They can be part of general isolationdevices of groups of machines or of complexes for motor opera-tion and protection.The MCS are derived from the corresponding circuit breakers, ofwhich they keep the overall dimensions, versions, fixing systemsand the possibility of mounting accessories.The MCS up to 1200 A are available in three-pole and four-poleversions, whereas the 2500 A size is only available in the three-pole version.All the molded case switches in accordance with UL 489 and CSAC22.2 Standards are self protected.

Molded case switches: MCSElectrical characteristics

MCS T1N-D T3S-D T3S-D T4H-D T5H-D S6H-D S7H-D S8V-D

Rating [A] 100 150 225 250 400 600* 800 1200 2500

Poles [No] 3-4 3-4 3-4 3-4 3-4 3-4 3-4 3Magnetic override [A] 1000 1500 2250 3000 5000 6000 10000 20000 35000

Rated VoltageAC (50-60 Hz) [V] 480 480 480 600 600 600 600 600

DC [V] 500 500 500 600 600 600 600 600

ABB2/20

* Please ask ABB for 600 A availability

Page 50: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

3

ABB 3/1

Accessories

Index

Versions and types .................................................................................................................. 3/3

Connection terminals .............................................................................................................. 3/7

Service releases .................................................................................................................... 3/14

Electrical signals .................................................................................................................... 3/20

Remote controls .................................................................................................................... 3/26

Operating mechanisms with locks ......................................................................................... 3/30

Residual current releases (IEC only) ....................................................................................... 3/37

Accessories for electronic trip units ....................................................................................... 3/41

Installation and testing accessories ....................................................................................... 3/46

Spare parts ........................................................................................................................... 3/47

Controller for automatic transfer switch - ATS010 (IEC only) .................................................. 3/48

Page 51: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB3/2

3

1SD

C21

0200

F002

3

Accessories

Page 52: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 3/3

3

1SD

C21

0201

F002

3

1SD

C21

0202

F002

3FixedFixed ABB molded case circuit breakers, in accordance withUL/CSA standards up to 2500 A, are available in the two-pole,three-pole and four-pole version up to 1200 A and only in thethree-pole version from 1600 A up to 2500 A.The circuit breakers have:– single depth of 2.76” (70 mm) up to 225 A and 4.07”

(103.5 mm) from 150 to 800 A– standardized front 1.77” (45 mm) up to 225 A– possibility of assembly on back plate or on DIN rail up to 225 A

(except T1B 1p)– thermomagnetic or electronic trip units– UL file: E93565 for circuit breakers and MCP; CSA file: LR54280– UL file: E116595 for MCS; CSA file: LR54280.

Plug-inThe plug-in version circuit breaker consists of:– fixed part to be installed directly on the back plate of the

cubicle– moving part, obtained from the fixed circuit breaker with addi-

tion of the isolating contacts (in correspondence with the con-nection terminals), of the rear frame (for fixing the fixed part),and of the terminal covers.

Circuit breaker removal is carried out by unscrewing the top andbottom fixing screws. A special lock prevents circuit breaker rack-ing in and racking out with the contacts in the closed position.Tmax T2 T3, T4 and T5 circuit breakers, starting from the fixedversion, can be changed into the various types using the conver-sion kits.

AccessoriesVersions and types

Page 53: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB3/4

3

1SD

C21

0203

F002

3

Draw outThe draw out version circuit breaker consists of:– fixed part to be installed directly on the back plate of the cubi-

cle with the side group mounted on the fixed part to allow theracking-out/racking-in movement

– moving part, obtained from the fixed circuit breaker with addi-tion of the isolating contacts (in correspondence with the con-nection terminals), of the rear frame (for fixing the fixed part),and of the terminal covers

– accessory to be mounted on the front of the circuit breaker,with selection between front flange for lever operating mecha-nism, motor operator and rotary handle operating mechanism;application of one of these accessories allows the circuit breakerlock to be made in the withdrawn position.

Racking-in/racking-out of the moving part is carried out by meansof the special crank supplied with the conversion kit of the fixedcircuit breaker into moving part of draw out circuit breaker. Thespecial mechanism allows the circuit breaker to be racked out inthe isolated position (with power and auxiliary circuits disconnected)with the compartment door closed, increasing the safety of theoperation.Once racked out or removed, the circuit breaker can be operatedin open or closed position and, by means of the special connec-tors, blank operating tests of the auxiliary control circuits can becarried out.

AccessoriesVersions and types

Versions availableF P W

Fixed Plug-in Draw out

T1B 1p ■ – –

T1 ■ – –

T2 ■ ■ –

T3 ■ ■ –

T4 ■ ■ ■

T5 ■ ■ ■

S6 ■ – ■

S7 ■ – ■

S8 ■ – –

Page 54: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 3/5

3

1SD

C21

0206

F002

3

1SD

C21

0205

F002

3

1SD

C21

0208

F002

3

1SD

C21

0207

F002

3

1SD

C21

0209

F002

3

1SD

C21

0204

F002

3

T2-T3

T4-T5

T2-T3 T4-T5

Conversion kit into part of plug-in forT2, T3, T4 and T5(UL file: E116596)

Allows conversion of a fixed circuit breaker with front terminals intothe moving part of a plug-in circuit breaker. The kit consists of:– isolating contacts– anti-racking out safety device– assembly nuts and screws– terminals covers.The circuit breaker is completed with the fixed part.When the circuit breaker has electrical accessories mounted (SOR,UVR, MOS, AUX, AUE), the socket-plug connectors can also beordered for isolation of the relative auxiliary circuits.

Conversion kit into moving part of draw outcircuit breaker for Tmax T4, T5 and IsomaxS6 and S7This allows the fixed circuit breaker with front terminals tobe converted into the moving part of a draw out circuitbreaker. The kit consists of isolating contacts, frame, andassembly nuts and screws. The circuit breakers in the drawout version must be completed, alternatively, with one ofthe following accessories:– front for lever operating mechanism– rotary handle operating mechanism– motor operator– terminal coversin order to prevent the racking-out operation with the circuit breakerclosed. The circuit breaker is completed with the fixed part.

Page 55: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB3/6

3

1SD

C21

0210

F002

3

1SD

C21

0211

F002

3

1SD

C21

0212

F002

3

AccessoriesVersions and types

Conversion kit for fixed part of plug-in intofixed part of draw out for Tmax T4 and T5A guide for converting the fixed part of a plug-in version circuitbreaker into the fixed part of a draw out version circuit breaker isavailable for Tmax T4 and T5 circuit breakers.

Racking out crankThis allows racking out and racking in of the circuit breaker in thedraw out version into the fixed part, with the door closed. Thecrank handle is the same for the whole range of circuit breakersand is automatically supplied with the fixed part of draw out circuitbreakers or with the conversion kit for fixed part of plug-in intofixed part of draw out.

Fixed part(UL file: E116596)

The fixed part completes the circuit breaker in the plug-in or drawout version. For plug-in or draw out version circuit breakers, differ-ent positions are available:– plug-in: plugged-in, unplugged– draw out version: racked-in/racked-out, removed.The fixed part for draw out version is fitted with a guide for sup-porting the moving part during the isolation or withdrawal opera-tions. For Isomax S6 and S7 circuit breakers, there are two guides.For Tmax T2 and T3 circuit breakers, the fixed parts are available,in the standard version, with front terminals (F): a distinguishingcharacteristic of these two sizes of circuit breakers is the possibil-ity of equipping the fixed parts with the same kit of terminals, ter-minal covers and phase separators, used for the fixed circuit break-ers. With Tmax T4 and T5, codes of fixed parts are available withdifferent types of terminals (EF, HR, VR). The fixed parts with EFterminals, moreover, can be also equipped with ES, FC Cu andFC CuAl terminals.

Page 56: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 3/7

3

1SD

C21

0213

F002

3

1SD

C21

0214

F002

3

AccessoriesConnection terminals

The basic version of the circuit breakers is supplied with:– lugs for copper and aluminium cables (FC CuAl) for the Tmax T1 circuit breaker– front terminals (F) for Tmax T2, T3, T4, T5 and Isomax S6, S7 and S8 circuit breakers.Different types of terminals are also available and these can be combined in various ways (top of onetype, bottom of a different type), allowing the circuit breaker to be connected to the plant in the mostsuitable way for the installation requirements.The following distinctions can be made between:– front terminals, which allow connection of cables or busbars by acting directly from the front of

the circuit breaker– rear terminals, which allow installation in switchboards with rear access to both cable and busbar

connections. For Tmax T2, T3, T4 and T5 the rear terminals are adjustable.Terminals are available for direct connection of bare copper or aluminium cables (UL listed) andterminals for connection of busbars or cables terminated with cable terminals.An important feature of the Tmax T2 and T3 circuit breakers is that all the different types of terminalscan be mounted either on the fixed version circuit breaker or on the fixed part of the plug-in circuitbreaker. On the other hand, T4 and T5 fixed part can mount EF, HR or VR terminals, and, moreover,fixed part with EF terminals can be equipped also with ES, FC Cu and FC CuAl terminals.The information needed to make the connections is given for each type of terminal on page 3/9 andfollowing. The minimum and maximum cross-section of the cables, which can be tightened in theterminals and the diameter of the terminal, are indicated for connection with bare cables. Flat bars ofdifferent size and composition are recommended for connections with busbars. The required mini-mum depth is also indicated, if it is different to the one recommended.The torque values to be applied to the tightening screws for cable terminals and to the screws usedto connect the busbars to the flat bar terminals are given.

Insulating terminal coversThe terminal covers are applied to the terminals of the circuit breakerto prevent accidental contact with live parts.The following are available:– low terminal covers (LTC), which guarantee IP40 degree of

protection for fixed circuit breakers with rear terminals and formoving parts of plug-in or draw out circuit breakers

– high terminal covers (HTC), for fixed circuit breakers with front,front extended, front for cables and rear terminals; guaranteeIP40 degree of protection

– terminal covers for fixed parts, of plug-in or draw out circuitbreakers for T4, T5, S6 and S7 circuit breakers, guarantee IP40degree of protection on the front with moving part connected.They are available in a single version. The fixed parts of plug-inT2 and T3 circuit breakers can use the same terminal coversas the corresponding fixed circuit breakers. For fixed partsof T4 and T5 400, the proper terminal covers (TC-FP) areavailable.

The degrees of protection indicated are valid for circuit breakerinstalled in switchboards.

Page 57: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB3/8

3

1SD

C21

0216

F002

31S

DC

2102

17F0

023

1SD

C21

0215

F002

3

AccessoriesConnection terminals

Phase separating partitionsThese allow the insulation characteristics between the phases atthe connections to be increased. They are mounted from the front,even with the circuit breaker already installed.Two versions are available for Tmax circuit breakers:– 3.94” (100 mm) high– 7.87” (200 mm) high.The H = 3.94” (100 mm) phase separators are supplied as stand-ard with front extended type terminals (EF), whereas those withH = 7.87” (200 mm) are standard with the front extended spreadtype of terminals (ES).They are incompatible with both the high and low insulating termi-nal covers.The fixed parts of plug-in Tmax circuit breakers can use the samephase separating partitions as the corresponding fixed circuit break-ers. With the phase separating partitions mounted, a special kit isavailable on request to reach IP40 degree of protection from thefront of the circuit breaker.Moreover, it is possible to mount the phase separating partitionsbetween two circuit breakers or fixed parts side by side.Phase separating partitions must always be requested for IsomaxS6 and S7 circuit breakers. They are always an alternative to thehigh or low terminal covers.

Screws for sealing the terminal coversThese are applied to the terminal covers of fixed circuit breakersor to the moving parts of plug-in or draw out circuit breakers. Theyprevent removal of both the high and low terminal covers and canbe locked with a wire and lead seal.

Kit for taking up the auxiliary power supplySpecial kits are available with the Tmax T2, T3, T4 and T5 circuitbreakers for taking up the auxiliary power supply directly from theconnection terminals. They can only be combined with the frontterminals for copper cables (FC Cu) or with the front terminals (F)for T3, T4 and T5.

Page 58: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 3/9

3

Front forcopper andaluminiumcables(3)

Frontextended

spread

Frontfor copper

cables

Front Extendedfront

Connection terminals

T1 F F(2) F(2) FT2 F - P(2) F-P F-P F-P F-P F-PT3 F - P(2) F-P F-P F-P F-P F-PT4 F(2) F-P-W F-P-W F-P-W F-P-W F P-W P-W FT5 F(2) F-P-W F-P(5)-W(5) F-P-W F-P-W F P-W P-WS6 F(2) F-W F F F F W WS7 F(2) F-W F F F-W F-WS8 F(2) F(1) UL listed(2) Standard supply

Rear(4) Multi-cableterminals

Rearflat

horizontal

Rearflat

vertical

(3) External and standard versions(4) Orientated for Tmax and threaded for Isomax

A = Tightening the terminal onto the circuit breakerB = Tightening of the cable/busbar onto the terminalR = On requestS = Standard

F EF ES FC Cu FC CuAl(1) R RC HR VR MC

Rearfor Cu/Alcables

Front terminals - F

Allow connection of busbars or cables terminated with cable terminals

Type Version Pieces Busbars/cable terminals [in-mm] Tightening [Ibin-Nm] Terminal covers Phase separators

W H D Ø B high low fixed partT2 F - P 1 0.79-20 0.3-7.5 0.2-5 0.26-6.5 54-6 R R – R

T3 F - P 1 0.94-24 0.37-9.5 0.31-8 0.33-8.5 71-8 R R – RT4 F 1 0.98-25 0.37-9.5 0.31-8 0.33-8.5 161-18 R R – R

T5 F 1 1.38-35 0.43-11 0.40-10 0.41-10.5 250-28 R R – RS6 F 2 1.97-50 0.47-12 0.20-5 2 x 0.27-7 80-9 R R – R

S7 F 2 1.97-50 0.79-20 0.31-8 2 x 0.43-11 161-18 – R – RS8 2000 F 3 3.94-100 – 0.20-5 4 x 0.59-15 625-70 – R – –

S8 2500 F 4 3.94-100 – 0.20-5 4 x 0.59-15 625-70 – R – –

1SD

C21

0229

F002

3

S6

1SD

C21

0230

F002

3

S7

1SD

C21

0230

F002

3

T1-T5

F = FixedP = Plug-inW = Draw-out

(5) Only for T5 600

Page 59: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB3/10

3

A = Tightening the terminal onto the circuit breakerB = Tightening of the cable/busbar onto the terminalR = On requestS = Standard

AccessoriesConnection terminals

Front extended spread terminals - ES

Allow connection of busbars or cables terminated with cable terminals

Type Version Pieces Busbars [in-mm] Cable terminals [in-mm] Tightening [Ibin-Nm] Terminal covers Phase separators

W D Ø L Ø A B high low fixed partT2 F-P 1 1.18-30 0.16-4 0.41-10.5 1.18-30 0.41-10.5 54-6 161-18 – – – S

T3 F-P 1 1.18-30 0.16-4 0.41-10.5 1.18-30 0.41-10.5 71-8 161-18 – – – ST4 F-P-W 1 1.18-30 0.24-6 0.41-10.5 1.18-30 0.41-10.5 161-18 161-18 – – – S

T5 F-P(1)-W(1) 1 1.57-40 0.39-10 0.43-11 0.43-11 0.43-11 252-28 161-18 – – – SS6 F 1 3.54-90 0.31-8 3 x 0.51-13 4x1.77-45 0.51-13 80-9 268-30 – – – –

S7 F 1 3.54-90 0.59-15 3 x 0.51-13 4x1.77-45 0.51-13 402-45 179-30 – – – –

Front extended terminals - EF

Allow connection of busbars or cables terminated with cable terminals

Type Version Pieces Busbars [in-mm] Cable terminals [in-mm] Tightening [Ibin-Nm] Terminal covers Phase separatorsW D Ø L Ø A B(1) high low fixed part

T1 F 1 0.59-15 0.20-5 0.33-8.5 0.59-15 0.33-8.5 63-7 80-9 R – – S

T2 F-P 1 0.79-20 0.16-4 0.33-8.5 0.79-20 0.33-8.5 54-6 80-9 R – – ST3 F-P 1 0.79-20 0.24-6 0.39-10 0.79-20 0.39-10 71-8 161-18 R – – S

T4 F 1 0.79-20 0.39-10 0.39-10 0.79-20 0.39-10 161-18 161-18 R – – SP-W 1 0.79-20 0.39-10 0.31-8 0.79-20 0.31-8 – 80-9 – – R R

T5 F 2 1.18-30 0.27-7 0.43-11 1.18-30 0.43-11 252-28 161-18 R – – SP-W 2 1.18-30 0.59-15 0.39-10 1.18-30 0.39-10 – 161-18 – – R R

S6 F-W 2 1.97-50 0.20-5 0.55-14 1.97-50 0.55-14 80-9 268-30 R R – RS7 F-W 2 1.97-50 0.31-8 4 x 0.43-11 1.97-50 4 x 0.43-11 402-45 161-18 – R – R

1SD

C21

0231

F002

3

1SD

C21

0232

F002

3

S6 800

1SD

C21

0230

F002

3

S7

1SD

C21

0230

F002

3

PF S6

1SD

C21

0230

F002

3

PF S7

1SD

C21

0230

F002

3

T1-T5

S6 S7

1SD

C21

0230

F002

3

1SD

C21

0230

F002

3

T1-T5

(1) Only for T5 600

Page 60: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 3/11

3

A = Tightening the terminal onto the circuit breakerB = Tightening of the cable/busbar onto the terminalR = On requestS = Standard

Front terminals for copper cables - FC Cu

Allow connection of bare copper cables directly to the circuit breaker

Type Version Pieces Cable [AWG or Kcmil-mm2] Tightening [Ibin-Nm] Ø [in-mm] Terminal covers Phase separators

rigid flexible A B high low fixed partT1/T1P F 1 14…2/0-2.5…70 14…1-2.5…50 – 62-7 0.47-12 R R – R

F 2 – 14…1-2.5…50 – 62-7 0.47-12 R R – RT2 F-P 1 18…3/0-1…95 18…2/0-1…70 – 62-7 0.55-14 R R R R

F-P 2 – 18…0-1…50 – 62-7 0.55-14 R R R RT3 F-P 1 10…350-6…185 10…300-6…150 – 89-10 0.71-18 R R R R

F-P 2 – 10…2/0-6…70 – 89-10 0.71-18 R R R RT4 F-P-W 1 14…350-2.5…185 14…300-2.5…150 – 89-10 0.71-18 R R S R

F-P-W 2 – 14…3/0-2.5…95 – 89-10 0.71-18 R R S RT5 F-P-W 1 6…500-16…240 6…500-16…300 – 222-25 1.1-28 R R S R

F-P-W 2 – 6…300-16…150 – 222-25 1.1-28 R R S RF 2 – 1…350-50…185 161-18 279-31 0.85-21.5 S – – –

1SD

C21

0233

F002

3

1SD

C21

0235

F002

3

T4-T5 ExternalT2-T5 Standard

1SD

C21

0234

F002

3

S6 800 S7

1SD

C21

0236

F002

3

1SD

C21

0236

F002

3

Front terminals for copper/aluminium cables - FC CuAl (UL listed)

Allow connection of bare copper or aluminium cables directly to the circuit breaker (solid aluminium cables cannot be used)

Type Assembly Version PiecesCable

Tightening [Ibin-Nm] Ø [in-mm] Terminal covers Phase separators[AWG or Kcmil-mm2]rigid A B high low fixed part

T1 1P/T1 standard F 1 14…10-2.5…6 20-2.5 0.37-9.5 R R R

8.0-10 40-4.56…1/0-16…50 45-5

T2 standard F-P 1 14…1/0-2.5…50 80-9 50-5.6 R R R RT3 standard F-P 1 14…1/0-2.5…50 80-9 50-5.6 0.39-10 R R R R

standard F-P 1 4…300-25…150 80-9 200-22.6 0.67-17 R R R RT4 standard F-P-W 1 10…350-6…185 274-31 80-9 0.7-18 R R S R

standard F 1 14…1/0-2.5…50 50-5.6 80-9 0.39-9.9 R R RT5 external F 2 3/0…250-95…120 274-31 159-18 0.61-15.5 S R

external F 2 3/0…500-95…240 274-31 159-18 0.84-21.5 S Rstandard F-P-W 1 250…500-120…240 380-43 159-18 0.84-21.5 R R S R

S6 standard F 3 2/0…400-70…185 80-9 383-43 0.75-9 Sstandard F 2 250…500-120…240 44-5 276-31 0.87-22 S

S7 standard F 4 4/0…500-95…240 311-35 383-43 0.85-21.5 S

Page 61: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB3/12

3

A = Tightening the terminal onto the circuit breakerB = Tightening of the cable/busbar onto the terminalR = On requestS = Standard

AccessoriesConnection terminals

Rear orientated terminals for Tmax - R

Allow connection of busbars or cable terminal at the rear

Type Version Pieces Busbars [in-mm] Tightening [Ibin-Nm] Terminal covers Phase separators

W D Ø A B high low –T2 F-P 1 0.79-20 0.16-4 0.33-8.5 54-6 80-9 – S –

T3 F-P 1 0.79-20 0.24-6 0.33-8.5 54-6 80-9 – S –T4 F 1 0.79-20 0.39-10 0.33-8.5 54-6 80-9 – S –

T5 F 2 1.18-30 0.27-7 0.43-11 161-18 161-18 – S –

1SD

C21

0237

F002

3

Threaded rear terminals for Isomax - R

Allow connection of busbars at the rear

Type Version Pieces Busbars [in-mm] Cable terminals [in-mm] Tightening [Ibin-Nm] Terminal covers Phase separatorsW D Ø L Ø A B high low fixed part

S6 F 2 1.97-50 0.20-5 0.98-25 1.97-50 0.98-25 161-18 890-100 – S – –

1SD

C21

0236

F002

3

S6 800

1SD

C21

0236

F002

3

S6

Rear terminals for copper/aluminium cables for Isomax - RC

Allow connection of copper or aluminium cables directly to the circuit breaker

Type Version PiecesCable terminals

[AWG or Kcmil-mm2]Tightening [Ibin-Nm] Ø [in-mm] Terminal covers Phase separators

A B high low fixed partS6 F 3 2/0…300-70…150 80-9 276-31 0.689-17.5 S – – –

Page 62: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 3/13

3

A = Tightening the terminal onto the circuit breakerB = Tightening of the cable/busbar onto the terminalR = On requestS = Standard

Rear flat horizontal and verticalterminals - HR/VR

Allow connection of busbars at the rear.

Type Version Pieces Busbars [in-mm] Cable terminal [in-mm] Tightening [Ibin-Nm] Terminal covers Phase separatorsW D Ø L Ø A B high low fixed part

T1 F 1 0.55-14 0.20-5 0.24-6.2 0.55-14 0.24-6.2 63-7 45-5 – S – –

T4 P-W 1 0.79-20 0.39-10 0.39-10 0.79-20 0.39-10 161-18 – – – – –T5 400 P-W 1 0.98-25 0.39-10 0.47-12 0.98-25 0.47-12 161-18 – – – – –

T5 600 P-W 2 1.57-40 0.59-15 0.43-11 1.57-40 0.43-11 161-18 – – – – –S6 W 2 1.97-50 0.20-5 0.55-14 1.97-50 0.55-14 – 267-30 – – – –

S7 F-W 2 1.97-50 0.31-8 4 x 0.43-11 – – – 179-20 – S – –S8 2000 F 3 3.94-100 0.20-5 4 x 0.59-15 – – – 625-70 – – – –

S8 2500 F 4 3.94-100 0.20-5 4 x 0.59-15 – – – 625-70 – – – –

Multi-cable terminals for Tmax - MC

Allow connection of cables directly to the circuit breaker

Type Version Pieces Cable [AWG or Kcmil-mm2] Tightening [Ibin-Nm] Terminal covers Phase separatorsmax flexible rigid A B high low fixed part

T4 F 6 14…4-2.5…25 14…4-2.5…35 161-18 62-7 S – – –

1SD

C21

0240

F002

3

1SD

C21

0238

F002

3

1SD

C21

0239

F002

3

1SD

C21

0236

F002

3

1SD

C21

0236

F002

3

S7

1SD

C21

0236

F002

3

S6 S7

Note: for T1 and S8 only the terminals are available.

Page 63: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB3/14

3

1SD

C21

0243

F002

3

1SD

C21

0241

F002

3

1SD

C21

0244

F002

3

1SD

C21

0245

F002

3

S6-S7 S8

T1-T2-T3 T4-T5

1SD

C21

0242

F002

3

AccessoriesService releases

The shunt trip and undervoltage releases, housed and fixed in a slot on the left-hand side of thecircuit breaker, are always alternative to each other. They are supplied in the pre-cabled version with39.4” (1 m) long cables for Tmax T1, T2 and T3 circuit breakers, or socket-plug connectors, still with39.4” (1 m) long cables, for T4 and T5. For Isomax S6 and S7, the power supply is made by meansof special connectors.Assembly is carried out by pressure into the appropriate seat located in the left-hand part of thecircuit breaker and fixing with the screw provided.

SOR - Shunt trip(UL file: E116596)

This allows circuit breaker opening by means of an electricalcommand. Operation of the release is guaranteed for a voltagebetween 75% and 110% of the value of the rated power supplyvoltage Un, both in AC and DC. It is always fitted with an auxiliarylimit contact.Furthermore, PS-SOR opening coils with permanent operation arealso available for T4 and T5, with a much lower power consump-tion and these can be continuously supplied: in this case they arenot, in fact, fitted with an auxiliary limit contact. Again for thesecoils, either the pre-cabled or uncabled version can be selected.

Page 64: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 3/15

3

SOR - Electrical characteristicsAbsorbed power on inrush

Tmax T1, T2, T3 Tmax T4 and T5

Version AC [VA] DC [W] AC [VA] DC [W]

12 V DC – 50 – 150

24…30 V AC 50 50 150 150

48…60 V AC/DC 60 60 150 150

110…127 V AC-110…125 V DC 50 50 150 150

220…240 V AC-220…250 V DC 50 50 150 150

380…440 V AC 55 – 150 –

480…500 V AC 55 – 150 –

Opening times [ms] 15 15 15 15

Absorbed power on inrush

Isomax S6, S7 Isomax S8

Version AC [VA] DC [W] AC [VA] DC [W]

12 V DC – 150 – –

24 V AC/DC 150 150 200 150

30 V DC – – – 150

48 V AC/DC – 150 200 150

60 V DC – – – 150

100…127 V AC/DC – – 200 150

110…120 V AC-110…125 V DC 150 150 – –

127…150 V AC – – 200 –

160 V DC-150…180 V AC – – 200 150

200…250 V AC/DC – – 200 150

220…240 V AC-220…250 V DC 150 150 – –

480 V AC 150 – – –

380…500 V AC – – 200 –

Opening times [ms] ≤15 – – –

PS-SOR - Electrical characteristicsAbsorbed power on inrush

Tmax T4 and T5

Version AC [VA] DC [W]

24-30 V DC – 4

110…120 V AC 4 –

Page 65: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB3/16

3

1SD

C21

0243

F002

3

1SD

C21

0244

F002

3

1SD

C21

0248

F002

3

S6-S7 S8

T1-T2-T3 T4-T5

1SD

C21

0247

F002

3

1SD

C21

0246

F002

3

UVR - Undervoltage release(UL file: E116596)

This opens the circuit breaker due to a power supply failure of therelease or to voltage drops to values of less than 0.7 x Un with atrip range from 0.69 to 0.35 x Un.After tripping, the circuit breaker can be closed again starting froma voltage higher than 0.85 x Un. With the undervoltage releasede-energized, it is not possible to close the circuit breaker.

AccessoriesService releases

Page 66: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 3/17

3

UVR - Electrical characteristicsPower consumption during permanent operation

Tmax T1, T2, T3 Tmax T4 and T5

Version AC [VA] DC [W] AC [VA] DC [W]

24…30 V AC/DC 1.5 1.5 6 3

48 V AC/DC 1 1 6 3

60 V AC/DC 1 1 6 3

110…127 V AC-110…125 V DC 2 2 6 3

220…240 V AC-220…250 V DC 2.5 2.5 6 3

380…440 V AC 3 – 6 –

480…500 V AC 4 – 6 –

Opening times [ms] 15 15 ≤25 ≤25

Power consumption during permanent operation

Isomax S6, S7 Isomax S8

Version AC [VA] DC [W] AC [VA] DC [W]

24 V DC – 4 – 15

24 V AC 10 – 30 –

30 V DC – – – 15

30 V AC – – 30 (50 Hz) –

48 V AC 10 – 30 (50 Hz) –

48 V DC – 4 – 15

60 V DC – – – 15

60 V AC – – 30 (50 Hz) –

100 V AC – – 30 (50 Hz) –

110…115 V AC – – 30 (60 Hz) –

110…115 V AC – – 30 (50 Hz) –

125…127 V AC – – 30 (60 Hz) –

110…125 V DC – – – 15

120 V AC 10 – 30 –

127…130 V AC – – 30 (50 Hz) –

125 V DC – 4 – –

240 V AC 10 – – –

250 V DC – 4 – –

480 V AC 10 – – –

208…220 V AC – – 30 (60 Hz) –

220 V AC – – 30 (50 Hz) –

220…250 V DC – – – 15

230…240 V AC – – 30 (50 Hz) –

277 V AC – – 30 (60 Hz) –

240 V AC – – 30 –

380 V AC – – 30 (60 Hz) –

380…400 V AC – – 30 (50 Hz) –

440 V AC – – 30 (60 Hz) –

480 V AC – – 30 –

500 V AC – – 30 (50 Hz) –

Opening times [ms] ≤25 ≤25 ≤25 ≤25

Page 67: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB3/18

3

1SD

C21

0249

F002

3

1SD

C21

0250

F002

3

AccessoriesService releases

Closing coilUsed with Isomax S8 circuit breaker, this allows circuit breakerclosing by means of an electrical contact. Operation of the re-lease is guaranteed for a voltage between 80% and 110% of thevalue of the rated power supply voltage Un, both in AC and in DC.

Closing coilIsomax S8

Absorbed power on inrush

Version AC [VA] DC [W]

24 V DC 220

24 V AC (50Hz) 200

24 V AC (60Hz) 200

30 V DC 220

30 V AC (50Hz) 200

48 V DC 220

48 V AC (50Hz) 200

60 V DC 220

60 V AC (50Hz) 200

100 V AC (50Hz)-110…115 V AC (60Hz) 200

110…115 V AC (50Hz)-125…127 V AC (60Hz) 200

110…125 V DC 220

120 V AC (60Hz) 200

127…130 V AC (50Hz) 200

208…220 V AC (60Hz) 200

220 V AC (50Hz) 200

220…250 V DC 220

230…240 V AC (50Hz)-277 V AC (60Hz) 200

240 V AC (60Hz) 200

310 V DC 220

380 V AC (60Hz) 200

380…400 V AC (50Hz)-440 V AC (60Hz) 200

415…440 V AC-480 V AC (60Hz) 200

500 V AC (50Hz) 200

Opening times [ms] ≤ 25 ≤ 25

Page 68: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 3/19

3

1SD

C21

0252

F002

3

Extension for testing releasesAvailable for Tmax T4 and T5 and Isomax S6 and S7 circuit break-ers, this allows supply to the service releases with the circuit breakerin the racked out position. It is therefore possible to carry out blankoperating tests of the circuit breaker in safe conditions, i.e. iso-lated in relation to the power circuits.

UVD - Time delay device for undervoltagereleaseThe undervoltage release can be combined with an external elec-tronic power supply time delay device, which allows circuit breakeropening to be delayed in the case of a drop or failure in the powersupply voltage of the release itself, according to preset and ad-justable delays, in order to prevent unwarranted trips caused bytemporary malfunctions. The delay device must be combined withan undervoltage release with the same corresponding voltage. Thistime delay device can also be combined either with the TmaxT1…T5 or Isomax circuit breakers.

1SD

C21

0251

F002

31S

DC

2102

53F0

023

1SD

C21

0254

F002

3

1SD

C21

0255

F002

3

Connectors for service releases for IsomaxThese allow the shunt trip or undervoltage release to be connectedto the power supply circuit. They are available in the following ver-sions:– for Isomax S6 and S7 fixed circuit breakers– for Isomax S6 and S7 draw out circuit breakers.Assembly is by means of pressure into special slots in the left sideof the circuit breaker.Cables of different lengths (UL/CSA) are available.Socket-plugs with 3, 6 or 12 poles and cable kit (UL/CSA) with alength of 78.8’ (2 meters) are available for Tmax: the socket-plugsare necessary only for plug-in version.

Page 69: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB3/20

3

1SD

C21

0256

F002

3

AccessoriesElectrical signals

These allow information relative to the circuit breaker status to be taken outside the circuit breaker.Installation of these accessories takes place directly from the front of the circuit breaker, in specialslots on the right-hand side of the circuit breaker, completely segregated from the live parts, withincreased operator safety.They are supplied in the pre-cabled version with 39.4” (1 m) long cables for the T1, T2 and T3 circuitbreakers, or socket-plug connectors, still with 39.4” (1 m) long cables, for T4 and T5. For Isomax S6and S7, the power supply is made by means of special connectors.

AUX - Auxiliary contacts and bell alarm(UL file: E116596)

These carry out electrical signalling of the operating state of thecircuit breaker:– open/closed, which indicates the position of the main con-

tacts– bell alarm, which signals the circuit breaker open due to one

of the following reasons:– overload or short circuit– shunt trip– UVR– residual current release– emergency opening pushbutton of the motor operator– operation of the circuit breakers test pushbutton.

Auxiliary contacts can be supplied (according to the type) in thepre-cabled version with 1 m long cables for T1, T2 and T3 or withconnectors, still with 1m long cables, for T4, T5, S6 and S7.

Electrical characteristicsTmax T1, T2, T3

Power supply voltage Breaking capacity

AC (50 - 60Hz) [V] DC [V] Resistive load [A] Inductive load [A]

24 10 4

48 1.2 0.7

110 0.45 0.3

220 0.35 0.2

250 6 3

Isomax S6, S7

Power supply voltage Breaking capacity

AC (50 - 60Hz) [V] DC [V] Ohmic load [A]

125 0.3

250 0.15

250 6

400 3

Isomax S8

Power supply voltage Breaking capacity

AC (50 - 60Hz) [V] DC [V] Ohmic load [A]

220 1

380 6

500 3

Page 70: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 3/21

3

The auxiliary contacts are available for use with different voltages either in direct or alternating current:

T1, T2, T3, T4 and T5 (AUX) – 250 V AC/DCIn the pre-cabled and uncabled version:– 1 contact for signalling (on changeover) open/closed plus 1 contact (on changeover) for bell alarm– 3 contacts for signalling (on changeover) open/closed plus 1 contact (on changeover) for bell alarm.

T4 and T5 (AUX)– 400 V ACOnly in the pre-cabled version:– 1 contact for signalling (on changeover) open/closed plus 1 contact (on changeover) for bell alarm– 2 contacts for signalling (on changeover) open/closed.

T1, T2, T3, T4 and T5 (AUX) – 24 V DCGold-plated in the pre-cabled and uncabled version for T4 and T5 and only in the uncabled versionfor T1, T2 and T3:– 3 contacts for signalling (on changeover) open/closed plus 1 contact (on changeover) for bell alarm.

T4 and T5 with PR222DS/PD (AUX-SA) – 250 V ACOnly in the pre-cabled version:– 1 contact for bell alarm.

T4 and T5 (AUX-MO)Only in the pre-cabled version, to be combined with the MOE or MOE-E motor operator:– 1 contact for signalling the operating mode of the circuit breaker with the motor operator: manual

or remote.

T4 and T5 with PR222DS/PD electronic trip unit (AUX-E)Only in the pre-cabled version and only combined with the PR222DS/PD, they communicate thestate of the circuit breaker to the electronic trip unit.– 1 contact for signalling (on changeover) open/closed + 1 contact (on changeover) for bell alarm.

S6 and S7 (AUX) – 250-400 V AC/125-250 V DCIn the pre-cabled and uncabled version:– 1 contact during open/closed changeover + 1 bell alarm– 2 contacts for signalling (on changeover) open/closed– 1 open signal +1 closed signal +1 bell alarm.

S8 (AUX) – 380-500 V AC/220 V DCIn the pre-cabled and uncabled version:– 3 contacts during open/closed changeover + 1 bell alarm– 1 bell alarm.

SignalsT1, T2, T3 T4, T5 S6, S7 S8

2 open/closed contacts on changeover ■ ■

1 open/closed contact on changeover + 1 bell alarm ■ ■ ■

3 open/closed contacts on changeover + 1 bell alarm ■ ■

1 circuit breaker open signal + 1 circuit breaker closed signal + 1 bell alarm ■

3 open/closed contacts on changeover + 1 bell alarm ■

1 bell alarm ■

1 signalling electronic release trip (with PR222DS/PD-AUX-SA) ■

1 contact signalling manual/remote (AUX-MO) ■

early auxiliary contacts (AUE) (2 for Tmax, 1 for Isomax) ■ ■ ■

auxiliary position contacts for signalling circuit breaker racked-in/out (AUP)*(max 3 for Tmax; max 5 for Isomax) ■ ■ ■

1 open/closed contact on changeover + a contact(on changeover) for bell alarm (AUX-E; for PR222DS/PD, IEC only) ■

Page 71: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB3/22

3

AccessoriesElectrical signals

1SD

C21

0258

F002

3

AUX-C 250 V AC/DC

The auxiliary contacts for the Tmax circuit breakers and for IsomaxS6 and S7 are available, in accordance with IEC 60947-2 Stand-ard, also in the gold-plated version for digital signals.A change-over contact signalling residual current protection trip isalways supplied for the Tmax circuit breakers combined with theRC221 and RC222 residual current releases (in accordance withIEC 60947-2 Standard). Two change-over contacts for signallingpre-alarm and alarm are also available with RC222.

AUX - Electrical characteristicsAUX 250 V - T1, T2, T3, T4 and T5

Power supply voltage Service current In [A]

Category of utilisation (IEC 60947-5-1)

AC 14 DC 13

125 V 6 A 0.3 A

250 V 5 A 0.15 A

Protection with gG 10x38 type fuse (Imax 6 A)

AUX 400 V - T4, T5

Power supply voltage Service current In [A]

AC DC

125 V – 0.5

250 V 12 0.3

AUX 24 V - T1, T2, T3, T4 and T5

Power supply voltage Service current In [A]

AC DC

24 V 0.3 ≥ 0.75 mA

5 V – ≥ 1 mA

1SD

C21

0257

F002

3

T1-T2-T3 S6-S7

1SD

C21

0259

F002

3

T4

Page 72: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 3/23

3

1SD

C21

0260

F002

31S

DC

2102

63F0

023

1SD

C21

0261

F002

3

1SD

C21

0262

F002

3

Connectors for auxiliary contacts for IsomaxThese allow the auxiliary contacts to be connected to the relativepower supply circuit.For Isomax S6 and S7 circuit breakers, the auxiliary contacts(fitted with plug connector) can only be supplied by means of thespecific connectors to be ordered specifying the size and versionof the circuit breaker (fixed or plug-in/draw out).Assembly is carried out by mounting into special slots on the rightside of the circuit breaker.Socket-plugs with 3, 6 or 12 poles and cable kit (UL/CSA) with alength of 78.8” (2 m) are available. For Tmax: the socket-plugs arenecessary only for plug-in version.

Extension for testing auxiliary contactsAvailable for Tmax T4 and T5, and Isomax S6 and S7 circuitbreakers, this allows the auxiliary contacts to be connected to therelative power supply circuit with the circuit breaker in thewithdrawn position. With the circuit breaker in safe conditions, i.e.isolated in relation to the power circuits, blank tests of circuit breakeroperation can be carried out.

Page 73: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB3/24

3

AccessoriesElectrical signals

AUE - Early auxiliary contactsOne auxiliary contact for Isomax S6 and S7 and two contacts forTmax T1, T2, T3, T4 and T5 allow the undervoltage release or acontrol device to be supplied in advance, in relation to closing ofthe main contacts, in compliance with the IEC 60204-1, and VDE0113 Standards. They are mounted inside the direct rotary handleoperating mechanism.For Isomax S6 and S7, the contact is supplied complete with asocket connector with double slide for simultaneous connectionof the undervoltage release and of the consent contact itself. WithTmax T1, T2 and T3, the early contacts are supplied in the cabledversion with cables 39.4” (1 m) long, complete with socket-plugwith 6 poles, whereas for T4 and T5 early contacts are providedwith socket-plug connectors with 39.4” (1 m) cables.

1SD

C21

0264

F002

3

T1-T5

1SD

C21

0266

F002

3

1SD

C21

0265

F002

3

1SD

C21

0267

F002

3

S6…S7

Page 74: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 3/25

3

1SD

C21

0270

F002

3

1SD

C21

0272

F002

3

T2-T3 S6-S7

AUP - Auxiliary position contactsFor the fixed part of circuit breakers Tmax T2, T3, T4 and T5, andIsomax S6 and S7 they provide electrical signalling of the circuitbreaker position in relation to the fixed part: racked-in, drawn outand removed. They can only be connected by means of free wiresand are available in the following versions:– contacts signalling circuit breaker racked-in for Tmax and

Isomax circuit breakers– contacts signalling circuit breaker racked-out for Tmax T4 and

T5– contacts signalling circuit breaker racked-in for Tmax T4 and

T5 in 24 V DC– contacts signalling circuit breaker racked-out for Tmax T4 and

T5 in 24 V DC.– contacts signalling circuit breaker drawn-out for Isomax circuit

breakers.A maximum of three contacts for Tmax and a maximum of fivecontacts for S6 and S7, in any combination, can be installed onthe fixed part.The circuit breaker position contacts are also available in the gold-plated version for digital signals, also suitable for use for Un<24 Vvoltages with the same type of signaling and versions (for Isomax).

1SD

C21

0268

F002

3

1SD

C21

0269

F002

3

1SD

C21

0271

F002

3

T4-T5

Page 75: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB3/26

3

1SD

C21

0273

F002

3

AccessoriesRemote controls

MOS - Solenoid operating mechanism forTmax T1, T2 and T3(UL file: E116596)

This operates both opening and closing of the circuit breaker, act-ing directly on its lever. It is proposed in two versions, one “side-by-side” (IEC only), with T1 and T2, for installation on a panel orDIN rail, the other on the front of the circuit breaker (UL file:E116596), with T1, T2 and T3. The latter is complete with operat-ing handle. The front version can also be used with plug-in circuitbreakers.Coupling with the residual current release is only allowed for acircuit breaker with solenoid operator side-by-syde, to allow ac-cess to the user interface of the residual current release from thefront of the switchgear.Both versions can be used either in the three-pole or four-poleversion.The solenoid operator is supplied complete with free cables 39.4”(1 m) long and socket-plug connector with 3 poles just for thesuperimposed version.The table gives the power supply voltage values Un [V].

These allow remote control of circuit breaker opening and closing and are particularly suitable for usein electrical network supervision and control systems.A selector allows changeover from automatic to manual operation. They are always fitted with apadlock in the open position.

Rated voltage, Un

AC [V] 110…250DC [V] 48…60 / 110…250

Operating voltage 85…110% UnInrush power consumption 2500 [VA] / 1000 [W]

Time opening [s] < 0.1closing [s] < 0.1

Mechanical life [no. Operations] 25000[no. Operations/h] 240 (T1 and T2); 120 (T3)

Degree of protection, on the front IP30Minimum control impulsetime on opening and closing [ms] >100

1SD

C21

0274

F002

3

Page 76: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 3/27

3

1SD

C21

0275

F002

3

1SD

C21

0276

F002

3

MOE and MOE-E Tmax T4 and T5Rated voltage, Un AC [V] DC [V]

– 24

– 48…60

110…125 110…125

220…250 220…250

380 –

Operating voltage 85…110% Un 85…110% Un

Power consumption on inrush Ps ≤ 300 VA ≤ 300 W

Power consumption in service Pc ≤ 150 VA ≤ 150 W

Time opening [s] < 0.1

closing [s] 1.5

resetting [s] 3

Mechanical life [no. operations] 20000

Degree of protection, on the front IP30

Minimum opening andclosing control time [ms] ≤ 150

Stored energy motor operator for Tmax T4and T5 – MOE and MOE-E(MOE: UL file: E116596)

With the stored energy motor operator, it is possible to controlboth opening and closing of the circuit breaker on which it is in-stalled. During opening of the circuit breaker, the spring system isrecharged automatically: thestored energy is exploited in thisway to close the circuit breaker.The motor operator is alwayssupplied complete with socket-plug connectors with 39.4’’ (1m)long cables and is always fittedwith a padlock. The connectors,once inserted in the special sloton the right-hand side of the cir-cuit breaker, extend in relationto the outline of the circuitbreaker itself.The device can be fitted bothwith a key lock in the open po-sition (with the same MOL-Skeys for groups of circuit break-ers or different MOL-D keys) andwith a MOL-M key lock againstmanual operation: in the former case, the lock in the open positionis both of electrical and mechanical type, in the latter case, only ofmechanical type, i.e. only closing from the front of the circuit breaker(remote closing is allowed).The motor operator is always fitted with an auxiliary contact tosignal “auto” or “manual (not on changeover). On request, it canalso be fitted with an AUX-MO auxiliary contact (on changeover),which provides a signal of its service state: “auto” (remote controlof the circuit breaker) or “manual”.If the circuit breaker is fitted with PR222DS/PD electronic trip unit,instead of MOE, it is necessary to use MOE-E motor operator: forits use, the circuit breaker must be fitted with the AUX-E.

Page 77: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB3/28

3

1SD

C21

0278

F002

3

1SD

C21

0279

F002

3

Stored energy motor operator for IsomaxS6 and S7 circuit breakers(UL file: E116596)

With the stored energy operating mechanism, during circuit breakeropening the release mechanism automatically pre-charges asystem of springs: the stored energy is used for closing the circuitbreaker. It is supplied complete with shunt opening release(Ps=100VA/100W) and flange for the compartment door. Thetable shows the power supply voltages values Un [V].In case of interlocked circuit breakers, the key lock against manualoperation is necessary.

Motor operator for S6, S7

AC DC

Rated voltage, Un [V] 24

[V] 48

[V] 120 125

[V] 240 250

Operating frequency 50…60

Operating voltage 85…110% Un 85…110% Un

Power consumption on inrush Ps 660 VA 600 W

Power consumption in service Pc 180 VA 180 W

Time constant [ms] 22

Duration opening [s] 1.2

closing [s] 0.09

Mechanical life [no. operations] 10000 (S6) - 5000 (S7)

Degree of protection, on the front IP30

Minimum duration of the openingand closing command impulse [ms] ≥ 100

1SD

C21

0277

F002

3

AccessoriesRemote control

Page 78: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 3/29

3

1SD

C21

0283

F002

3

1SD

C21

0280

F002

3

1SD

C21

0281

F002

3

1SD

C21

0282

F002

3

Geared motor for Isomax S8 circuit breakerThis allows the springs of the circuit breaker closing mechanismto be charged automatically, immediately following a closingoperation. It includes a limit microswitch for electrical signalling ofclosing springs charged.

Connectors for Isomax S6 and S7 motoroperatorsThe motor operators for S6 and S7 can only be supplied by meansof the specific connectors. They are of the slide type and allowsimultaneous connection of both the motor operator and theauxiliary contacts to the relative power supply circuit. They arean alternative to the corresponding connectors for the auxiliarycontacts only since they are housed in the same seat. They mustbe ordered specifying the size and version of the circuit breaker(fixed or plug-in/draw out).

Extension for testing motor operatorsFor Tmax T4 and T5 and Isomax S6 and S7 circuit breakers, thisallows both motor operators and the auxiliary contacts to beconnected to the relative power supply circuit with the circuitbreaker in the racked-out position. With the circuit breaker in safeconditions, i.e. isolated in relation to the power circuits, blankoperating tests of the circuit breaker can be carried out. It must beordered specifying the size and version of the circuit breaker(fixed or plug-in/draw out) and automatically excludes the corre-sponding extension for testing the auxiliary contacts.

Page 79: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB3/30

3

1SD

C21

0284

F002

3

1SD

C21

0286

F002

3

1SD

C21

0285

F002

3

AccessoriesOperating mechanisms with locks

Rotary handle operating mechanism – RHD/RHE

Type of RH operating mechanism

T1, T2, T3 T4, T5 S6, S7

F/P F/P W F W

RHD Direct ■ ■ ■ ■ ■

RHD_EM Emergency direct ■ ■ – ■ ■

RHE Transmitted with adjustable distance 19.68" - 500 mm ■ ■ 19.68" - 500 mm 19.68" - 500 mm

RHE_EM Emergency transmitted with adjustable distance 19.68" - 500 mm ■ ■ 19.68" - 500 mm –

RHE_S Rod for transmitted adjustable handle 19.68" - 500 mm ■ – – –

RHE_B Base for circuit breaker ■ ■ ■ – –

RHE_H Handle for transmitted RH with adjustable distance ■ ■ ■ – –

RHE_H_EM Emergency handle for transmitted RH with adjustable distance ■ ■ ■ – –

(UL file: E116596 for Tmax)

The rotary handle operating mechanism facilitates operation thanksto its ergonomic handle. It is always fitted with a padlock in the openposition, which prevents the circuit breaker being closed. The pad-lock slot can take up to three padlocks – stem Ø 0.27”(7 mm) for T1, T2, T3 T4 and T5, and 0.24” (6 mm) for S6 and S7(not supplied).The rotary handle operating mechanism for Tmax is always fitted witha compartment door lock and, on request, can be supplied with akey lock in the open position; for S6 and S7, on request, it can besupplied with a compartment door lock or key lock in the open posi-tion.Application of the rotary handle operating mechanism is analternative to the motor operator and to the front interlocking plate forTmax T1, T2, T3 and to the front flange for the lever operating mecha-nism for Tmax T4, T5 and Isomax S6 and S7.The rotary handle operating mechanism is available in either the di-rect version and in the transmitted version on the compartment door.The position of the rotary handle indicates with certainty theposition of the contacts: open, closed and trip unit tripped. The tripunit settings and the nameplate data remain accessible to the user.For Isomax S6 and S7 circuit breakers, the direct rotary handle oper-ating mechanism on the circuit breaker is always supplied completewith flange for the compartment door.The rotary handle operating mechanism in the emergencyversion, complete with red-yellow handle and yellow plate,suitable for machine tool control, is also available for all the circuitbreakers. For Tmax circuit breakers, the rotary handle operatingmechanisms can be ordered by building up by ordering the followingthree devices:– rotary handle on the compartment door– transmission rod (19.68” / 500 mm)– base for circuit breakeror, alternatively, by using the code of the ready-configured version.

Page 80: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 3/31

31S

DC

2102

87F0

023

1SD

C21

0288

F002

3

T2-T3

S6-S7

1SD

C21

0291

F002

3

1SD

C21

0292

F002

3

IP54 protection for rotary handleAllows IP54 degree of protection to be obtained. It is available forthe transmitted rotary handle operating mechanism on the com-partment door (RHE) for the Tmax and Isomax circuit breakers.

1SD

C21

0290

F002

3

1SD

C21

0289

F002

3

T4-T5

Page 81: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB3/32

3

1SD

C21

0296

F002

3

1SD

C21

0293

F002

3

1SD

C21

0295

F002

3

1SD

C21

0294

F002

3

1SD

C21

0297

F002

31S

DC

2102

98F0

023

AccessoriesOperating mechanisms with locks

Key lock in open positionThis allows the mechanical closing operation of the circuit breakerto be locked.The following versions are available:– lock with different key for each circuit breaker– lock with the same key for groups of circuit breakers.For Isomax S6 and S7 circuit breakers, different locks are sup-plied, for stored energy motor operator, for rotary handle or frontfor lever operating mechanism.For Tmax T1, T2 and T3, the key lock is available for the rotaryhandle operating mechanism (RHL). Furthermore, it is also avail-able in the version which allows the lock both in the open and inthe closed position: the lock in the closed position does not pre-vent tripping of the mechanism following a fault or a remote con-trol command.For T4 and T5 key locks in the open position are available eitherwith different keys (KLF-D) or with the same keys (KLF-S): in thiscase, up to four different key numbering codes are available.

Front flange for lever operating mechanism- FLDThis can be installed on Tmax T4 and T5, and on Isomax S6 andS7 fixed, plug-in or draw out circuit breakers. In case of draw outcircuit breakers installed in compartments, it allows higher degreeof protection to be maintained for the whole isolation run of thecircuit breaker.It is always fitted with a padlock in the open position (stem Ø 0.24”- 6 mm up to three padlocks - not supplied) which prevents clos-ing of the circuit breaker.On request, it can be fitted with a key lock in the open position forone or more circuit breakers and with the compartment door lock.It is available in the following versions:– for fixed or plug-in circuit breaker– for draw out circuit breaker.The front flange for lever operating mechanism is always an alter-native to the motor operator, to the rotary handle and, for T4 andT5, to the front display unit FDU.

For Isomax S6 and S7 circuit breakers, it is alwayssupplied complete with flange for the compartmentdoor. For T4 and T5, the same flange for compart-ment door already supplied with the circuit breaker orthe one supplied with the conversion kit for draw outversion can be used.

S6-S7

Page 82: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 3/33

3

1SD

C21

0300

F002

3

1SD

C21

0301

F002

3

1SD

C21

0299

F002

3

KLC - Key lock on the circuit breakerAvailable for Tmax T1, T2 and T3, the key lock on the circuit breakerallows the mechanical closing operation of the circuit breaker tobe locked and is installed directly on the front inside the slot incorrespondence with the left pole. It cannot be mounted with afront operating mechanism, a rotary handle operating mechanism,a motor operator, or RC221/RC222 residual current releases and,only in the case of three-pole circuit breakers, with service releases(UVR, SOR).The key lock is the Ronis 622 type and is available in two versions:– standard type, with key only removable with the circuit breaker

locked (KLC)– special type, with key removable in both positions (KLC-S).

Compartment door lockThis prevents the compartment door being opened with the cir-cuit breaker closed. It can be used with Isomax S6 and S7 circuitbreakers in the fixed, plug-in or draw out version and fitted withrotary handle operating mechanism or front for lever operatingmechanism. It consists of two elements: one applied to the rotaryhandle operating mechanism or to the front for the lever operatingmechanism, the other, consisting of a metal striker, to be appliedonto the compartment door.For Tmax circuit breakers, the door lock is always supplied withthe rotary handle operating mechanism.

Page 83: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB3/34

3

1SD

C21

0302

F002

3

1SD

C21

0303

F002

3

1SD

C21

0304

F002

3

1SD

C21

0305

F002

3

AccessoriesOperating mechanisms with locks

Lock for fixed part of draw out circuitbreakers - Tmax T4, T5 and Isomax S6, S7Key locks or padlocks are available to be applied to the guide ofthe fixed part of a draw out circuit breaker to prevent the movingpart from being racked-in. The following different versions areavailable:– padlock, which can take up to three padlocks with stem Ø 0.24”

- 6 mm (not supplied);– key lock in the open position with different key for each circuit

breaker;– key lock in the open position between two or more circuit

breakers with the same key for groups of circuit breakers;– key lock of Ronis type (without key).For T4 and T5 draw out circuit brakers, key or padlocks-locks areavailable to be applied onto the rail of the fixed part, to preventracking-in of the withdrawable part.Selection can be made among the following:– key lock with different keys (KLF-D FP)– key lock with the same keys for groups of circuit breakers

(KLF-S FP)– padlock, which can take up to three padlocks with 6 mm stem

Ø, not supplied (PLL FP).

Page 84: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 3/35

3

1SD

C21

0306

F002

3

1SD

C21

0307

F002

3

1SD

C21

0308

F002

3

Operating mechanisms with locks

T1 T2 T3 T4 T5 S6 S7

Sealable lock of thermal adjustment ■ ■ ■

FDL_Key lock for fornt for lever operating mechanism ■ ■ ■ ■

RHL_Key lock for rotary handle operating mechanism ■ ■ ■ ■ ■

KLC_Key lock on the circuit breaker ■ ■ ■

Compartment door lock ■ ■ ■ ■ ■ ■ ■

KLF-FP and PLL-FP_locks in open position for fixed parts ■ ■ ■ ■

PLL_Padlock for operating lever ■ ■ ■

MOL-D and MOL-S_Key lock in open position for MOE and MOE-E ■ ■

MOL-M_Key lock against manual operation for MOE and MOE_E ■ ■

PLL - Padlock for operating lever for TmaxT1, T2, T3This is applied to the Tmax T1, T2 and T3 covers to prevent thelever closing or opening operations. It allows installation of up to amaximum of three padlocks Ø 0.24” - 7 mm (not supplied).It is available in the following versions:– locking device only of the closing operation (it is applied with

circuit breaker ON/OFF)– locking device on the closing and opening operation according

to its assembly position. The lock on the opening operationdoes not prevent release of the mechanism following a fault orremote control command.

* UL file E116596

*

Page 85: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB3/36

3

1SD

C21

0310

F002

3

S6-S7

S6-S7

1SD

C21

0312

F002

3

1SD

C21

0313

F002

3

T1-T2-T3

1SD

C21

0311

F002

3

Mechanical interlocks

T1 T2 T3 T4 T5 S6 S7

Front interlock between two fixed circuit breakers ■ ■ ■

Front interlock among three fixed circuit breakers ■ ■ ■

Rear interlock between two fixed or plug-in ordraw out circuit breakers side by side ■ ■ ■ ■

Rear interlock between two fixed or plug-in ordraw out circuit breakers superimposed ■ ■ ■ ■

Mechanical interlock between circuit breakers (for Tmax UL file E116596)

Tmax T1, T2, T3

For Tmax T1, T2 and T3 circuit breakers a front mechanical interlock (MIF) is available, which can beapplied on the front of two (UL file E116596) both three-pole and four-pole fixed version circuitbreakers, preventing simultaneous closing of the two circuit breakers. Fixing is carried out directly onthe back plate of the switchboard. The front interlocking plate allows installation of a padlock in orderto fix the position (possibility of fixing the O-O position as well). It is also possible to interlock threecircuit breakers, even of different sizes, by using a special plate, making the following interlockingcombinations: IOO-OIO-OOI-OOO.

Tmax T4, T5

The mechanical interlock for Tmax T4 and T5 allows installation of two circuit breakers on a single supportand, by means of special lever mechanism, makes them mechanically interdependent. Unlike the inter-lock used with T1, T2 and T3 which is frontal, this is a rear interlock consisting of a vertical or horizontalframe group (MIR-HB or MIR-VB), made up of a metal frame and of the leverisms to interlock, and of twoplates (MIR-P) on which the circuit breakers are housed.

Isomax S6, S7

For Isomax S6 and S7 circuit breakers, the rear mechanical interlock allows installation of two circuitbreakers on a single support and, by means of a walking beam mechanism, makes them mechanicallyinter-dependent. It prevents operation in parallel of two power supply sources (e.g.: normal - emergency).It consists of a kit with levers and assembly accessories and a metallic support.The mechanical interlock is available in the version for side-by-side circuit breakers and for superimposedcircuit breakers. Only circuit breakers of the same size and in the same version can be interlocked.

AccessoriesOperating mechanisms with locks

1SD

C21

0309

F002

3

Page 86: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 3/37

3

AccessoriesResidual current releases - IEC only

All the Tmax series of circuit breakers are preset for assembly combined with residual current re-leases. In particular, Tmax T1, T2 and T3 circuit breakers can be combined with the new version ofthe RC221 or RC222 residual current releases, and four-pole T4 and T5 can be combined withRC222 or RC223 to be installed below the circuit breaker.Apart from the protection against overloads and short-circuits typical of circuit breakers, the residualcurrent circuit breakers which are derived from them also guarantee protection of people and againstearth fault currents, thereby ensuring protection against direct earth contacts, indirect contacts andfire hazards.The use of residual current circuit breakers allows continual monitoring of the state of insulation ofthe plant, ensuring efficient protection against the risks of fire and explosion and, in the case ofdevices with I∆n ≤ 30 mA, ensuring the protection required by the Standards and by the accidentprevention prescriptions.The residual current releases are constructed in compliance with the following Standards:– IEC 60947-2 appendix B– IEC 60255-3 (RCQ) and IEC 61000: for protection against unwarranted trips– IEC 60755 (RCQ): for insensitivity to the direct current components.

RC221 and RC222 electronic residualcurrent releases for Tmax T1, T2 and T3The RC221 and RC222 residual current releases can be installedon the Tmax T1, T2 and T3 circuit breakers. The versions availablemake their use possible both with three-pole and four-pole fixedversion circuit breakers.They are constructed using electronic technology and act directlyon the circuit breaker by means of an opening solenoid, suppliedwith the residual current release, to be housed in the special slotmade in the area of the left pole.They do not require an auxiliary power supply since they are sup-plied directly from the network and their operation is guaranteedeven with only a single phase plus neutral or just two phases sup-plied with voltage and in the presence of one-direction pulsatingcurrents with continuous components.All the possible connections are allowed as long as the connec-tion of the neutral to the first pole on the left is guaranteed in thefour-pole version.The RC221 and RC222 releases can be fed either from the loador the line side.

1SD

C21

0314

F002

31S

DC

2103

15F0

023

Page 87: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB3/38

3

AccessoriesResidual current releases - IEC only

1SD

C21

0316

F002

31S

DC

2103

18F0

023

1SD

C21

0319

F002

3

1SD

C21

0317

F002

3

The residual current releases are supplied complete with:– an opening solenoid to be housed in the area of the third pole,

complete with an auxiliary contact signalling residual currentrelease trip

– a dedicated flange.The bracket for fixing onto DIN rail is available on request.The configuration contemplates insertion of the circuit breaker onthe structure of the corresponding residual current release, mak-ing access to the adjustments on the left-hand side of the circuitbreaker available, whilst the toroid is placed below.The type of cable connection, which is made directly on the circuitbreaker, once the residual current release has been mounted,thereby ensuring simplification and rationalization of the installa-tion procedure, provides a distinguishing characteristic.Only front terminals for copper cables (FC Cu) at the bottom aremounted on the residual current releases. For this reason, whenthe residual current release is ordered, the FCCu terminal semi-kitis always supplied. Furthermore, for four pole T1, a version of theRC222 residual current release is available in 200 mm modules.This release keeps the same technical characteristics as thenormal RC222 for T1, T2 and T3 but, thanks to its reduced height,allows installation in 200 mm modules. Its special shape alsoallows a reduction in the overall dimensions when two or moreunits are placed side by side.

RC222 residual current release for Tmax T4and T5With T4 and T5, in the four-pole version, it is possible to use anRC222 residual current release below the circuit breaker.This RC222 residual current release, in the fixed version, caneasily be converted into plug-in by adding the special conversionkit. The device is constructed using electronic technology and actsdirectly on the circuit breaker by means of an opening solenoid,supplied with the residual current release, to be housed in thespecial slot made in the left-hand pole area. It does not require anauxiliary power supply as it’s supplied directly by the network andits operation is guaranteed even with only a single phase plus neu-tral or two phases supplied with voltage and in the presence ofunidirectional pulsating currents with direct components.The four-pole circuit breaker with residual current release can befitted with the electrical accessories normally available for thecircuit breaker.

Page 88: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 3/39

3

1SD

C21

0320

F002

3

RC221 RC222

Circuit breakers size T1-T2-T3 T1-T2-T3 T4 and T5

Type “L” shaped “L” shaped Placed below

Technology microprocessor-based microprocessor-based microprocessor-based

Action with solenoid with solenoid with solenoid

Primary service voltage (1) [V] 85…500 85…500 85…500

Operating frequency [Hz] 45…66 45…66 45…66

Self-supply ■ ■ ■

Test operation range (1) 85…500 85…500 85…500

Rated service current [A] up to 250 A up to 250 A up to 630 A

Rated residual current trip [A] 0.03 - 0.1 - 0.3 - 0.03 - 0.05 - 0.1 - 0.3 - 0.03 - 0.05 - 0.1 -0.5 - 1 - 3 0.5 - 1 - 3 - 5 - 10 0.3 - 0.5 - 1 - 3 - 5 - 10

Time limt for non-trip [s] istantaneous istantaneous - 0.1 - 0.2 - istantaneous - 0.1 - 0.2 -0.3 - 0.5 - 1 - 2 - 3 0.3 - 0.5 - 1 - 2 - 3

Tolerance over trip times ± 20% ± 20%

Local trip signalling ■ ■ ■

Trip coil with changeover contact for trip signalling ■ ■ ■

Input for remote opening ■ ■

NO contact for pre-alarm signalling ■ ■

NO contact for alarm signalling ■ ■

Indication of pre-alarm from 25% I∆n (tollerance ±3%) ■ ■

Indication of alarm timing ■ ■

Automatic residual current reset ■ ■ ■

“A” type for pulsanting alternating current, AC for alternating current ■ ■ ■

Remote release device ■ ■

Selective type ■ ■

Button for insulation test ■ ■ ■

Power supply from above and below ■ ■ ■

Assembly with three-pole circuit breakers ■ ■

Assembly with four-pole circuit breakers ■ ■ ■

Kit for conversion of circuit breaker with residual current releasefrom fixed to plug-in ■(1) Operation up to 50 V Phase-Neutral

RC223 (B type) residual current release for T4Along with the family of residual current releases illustrated previ-ously, ABB has developed the RC223 (B type) residual currentrelease, which can only be combined with the Tmax T4 four-polecircuit breaker in the fixed or plug-in version. The range of opera-tion of the primary line-to-line voltage varies between 110 V and440 V, with operation starting from 55 V phase-neutral. It is char-acterised by the same types of reference as the RC222 (S andAE type) release, but can also boast conformity with type B opera-tion, which guarantees sensitivity to residual fault currents withalternating, alternating pulsating and direct current components.The reference Standards are: IEC 60947-1, IEC 60947-2 Appen-dix B, and IEC 60755. Apart from the signals and settings typicalof the RC222 residual current release, the RC223 also allows se-lection of the maximum threshold of sensitivity to the residual faultfrequency (3 steps: 400-700-1000 Hz).

Page 89: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB3/40

3

AccessoriesResidual current releases - IEC only

1SD

C21

0321

F002

3

RCQ residual current relayThe Tmax T1, T2, T3 T4 and T5, and Isomax S6 and S7 circuit breakers can be combined with theRCQ relay with separate toroid (to be installed externally on the line conductors) and these fulfillrequirements with thresholds up to 30 A trips and times up to 5 s or when the installation conditionsare particularly restrictive, such as with circuit breakers already installed, or limited space in thecircuit breaker compartment.Thanks to the wide range of settings, the RCQ relay is suitable for applications where a system ofresidual current protection coordinated with the various distribution levels. It is particularly recom-mended when low sensitivity residual current protection is required, such as in partial (current) ortotal (chronometric) selective chains, and for high sensitivity applications (physiological sensitivity).In case of drops in the auxiliary power supply voltage, the opening control intervenes after a mini-mum time of 100 ms and after the time set plus 100 ms.The RCQ relay is suitable for use in the presence of alternating currents only (Type AC), for alternatingand/or pulsating current with direct components (Type A) and allows residual current selectivity to beset up.The RCQ relay is of the type with indirect action and acts on the circuit breaker release mechanismby means of the shunt trip of the circuit breaker itself (to be ordered by the user), to be housed in thespecial slot made on the left-hand pole of the circuit breaker.

Residual current relay RCQ

Power supply voltage AC [V] 80…500

DC [V] 48…125

Operating frequency [Hz] 50 ÷ 60 Hz ± 10%

Trip threshold adjustment I∆n

1st range of adjustments [A] 0.03-0.05-0.1-0.3-0.5

2nd range of adjustments [A] 1-3-5-10-30

Trip time adjustment [s] 0-0.1-0.2-0.3-0;5-0.7-1-2-3-5

Pre-alarm threshold adjustment [%] x I∆n 25…75% x I∆n

Range of use of closed transformers

Toroidal transformer Ø 2.36” [60 mm] [A] 0.03…30

Toroidal transformer Ø 4.33” [110 mm] [A] 0.03…30

Toroidal transformer Ø 7.28” [185 mm] [A] 0.1…30

Range of use of transformers which can be opened

Toroidal transformer Ø 4.33” [110 mm] [A] 0.03…30

Toroidal transformer Ø 7.09” [180 mm] [A] 0.03…30

Toroidal transformer Ø 9.06” [230 mm] [A] 1…30

Signalling for alarm pre-threshold Yellow flashing LED 1 N.O. change-over contact

6 A - 250 V AC 50/60 Hz

Residual current relay trip signalling Yellow magnetic flag change-over contacts (N.O. N.C.; N.O.)

6 A - 250 V AC 50/60 Hz

Remote opening control N.O. contact

Trip time 15 ms

Connection to the toroidal transformer By means of 4 twisted conductors. Maximum length: 1270 in

Dimensions L x H x D [in] 3.78 x 3.78 x 5.18

Drilling for assembly on door [in] 3.62 x 3.62

Page 90: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 3/41

3

AccessoriesAccessories for electronic trip units

PR212/D-M Modbus and PR212/D-L Londialogue unit for S6 and S7- (IEC only)The dialogue unit is a device which allows two-way communica-tion from the circuit breaker to the outside and vice versa. ABBhas built two distinct dialogue units able to support two differentcommunication protocols: PR212/D-M (Modbus RTU protocol) andPR212/D-L (LonTalk protocol by Echelon). Both units are housedin external modules, which can be installed on DIN rails, and canbe used with the Isomax S6 and S7 circuit breakers fitted withPR212/P electronic trip unit, both in the LSI and LSIG versions.They must be supplied with a stabilized voltage of 24 V DC (±20%with maximum ripple ±5%) and be earthed. Communication to-wards the outside is generally addressed to a supervision andcontrol unit, which has the task of collecting and storing the infor-mation regarding the part of the plant controlled.In the case of an error in the serial communication due to a fault inthe dialogue unit or lack of auxiliary power supply, the PR212/Pprotection unit works according to the last parameters set and, inany case, in accordance with what has been set manually. ThePR212/D-M and PR212/D-L dialogue units are always fitted incombination with the PR212/T actuator unit, which allows remoteclosing or opening operation of the circuit breaker (Remote Con-trol) by means of two digital outputs which can be disabled thanksto the dip-switch (LOC/REM) positioned on LOC.

Information available

– State of the circuit breaker: open; closed; tripped– installation alarms: pre-alarm L; tripped L-S-I-G-R-V-PTC– measurements: currents; N° operations; N° trips– reading and writing curves and trip thresholds: only manual read-

ing (MAN), electronic or remote reading and writing (ELT)– circuit breaker commands: opening; closing; reset.

Page 91: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB3/42

3

AccessoriesAccessories for electronic trip units

PR212/K signalling unit for S8The PR212/K signalling unit, only available for Isomax S8, is ableto convert the digital signals supplied by the PR212/P - (LSIG)protection unit into electric signals by means of normally openelectrical contacts. An auxiliary power supply is needed to oper-ate the unit. It is connected to the internal bus of the protectionunit by means of a dedicated serial line over which the informationregarding the state of activation of the protection functions passes,on the basis of which the relative power contacts are closed tosignal:– pre-alarm for protection function L (I>0.9 x I1)– protection function L, S, I, G trip– trip indication– communication error with protection unit.

1SD

C21

0324

F002

3

PR212/T actuator unit for S6 and S7The PR212/T actuator unit allows circuit breaker opening and closingby means of the motor operator mounted on the circuit breaker. It isalways supplied in combination with the PR212/D dialogue unit forIsomax S6 and S7. An auxiliary power supply with a stabilized volt-age of 24 V DC (±20%, with maximum ripple ±5%) and earthed isrequired for operation of the unit.The PR212/D dialogue unit sends the digital opening and closingcommands, received from the supervision and control system, to theinputs of the PR212/T actuator unit, which carries out circuit breakerclosing and opening by means of a power relay. The motor operatorof the circuit breaker (use the versions with power supply voltage at110 V AC/DC or 220 V AC) must be connected to these relays.

TT1 Test unitThis allows control of tripping of the PR211/P, PR212/P, PR221DSand PR222DS electronic trip unit and the trip test of the trip coil.The device is supplied by means of a 12 V replaceable battery andis fitted with a two-pole polarized connector-tracer point housedon the bottom of the box, which allows connection of the deviceto the test input bushings located on the bottom of the electronictrip unit.The limited dimensions of the accessory make it practically pocket-type.

1SD

C21

0322

F002

3

1SD

C21

0323

F002

3

Page 92: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 3/43

3

PR020/K signalling unitThe PR020/K signalling unit can convert the signals received viabus from the PR212/P (LSI or LSIG) or PR222DS/PD protectionunits into electric signals by means of normally open electrical powercontacts.An auxiliary power supply with a voltage stabilized at 24 V DC(±20% with maximum ripple ±5%) and earthed is needed to oper-ate the unit.It is connected to the Internal Bus of the protection unit by meansof a dedicated serial line over which the information regarding thestate of activation of the protection functions passes, on the basisof which the relative power contacts are closed.In particular, the following signals are available:

Alarm signalling remains active for the whole duration of the over-load up to any trip unit intervention.The protection trip signals remain active during the timing phaseand remain that way even after intervention of the trip unit.A Reset pushbutton on the front of the unit allows the state of allsignals to be reset.There are also two LEDs available on the unit for visually signallingthe following information:– “Power ON”: auxiliary power supply present– “TX (Int Bus)”: flashing synchronized with the communication

activity with the Internal Bus, and eight LEDs dedicated to in-ternal power releases status.

The table shows the characteristics of the signalling relays avail-able in the PR020/K unit.

PR212/P (LSI-LSIG) -PR222DS/PD (LSI-LSIG)K51 Signals

1 L alarm

2 S alarm

3 I alarm

4 G alarm

5 Bus K.O.

6 Trip indication

7 Trip indication

8 L pre-alarm

PR020/K

Maximum switching capacity 100 W / 1250 VA (resistive load)

Maximum switching voltage 130 V DC / 250 V AC

Maximum switching current 5A

Breaking power (UL/CSA) @ 30 V DC(resistive load) 3.3 A

Breaking power (UL/CSA) @ 250 V DC(resistive load) 5 A

Contact/coil insulation 2000 V efficient (1 min. @ 50 Hz)

Page 93: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB3/44

3

1SD

C21

0325

F002

3

AccessoriesAccessories for electronic trip units

1SD

C21

0326

F002

3

EP 010 - FBPIt is the “e-plug” interface which can connect T4 and T5, equippedwith the PR222DS/PD electronic trip unit, to the field bus plugsystem, allowing user to choose among several field bus system(ASI, Device Net, Profibus).It must be connected to the trip unit by means of the specific X3connector.

PR010/T Test and Configuration UnitThe PR010/T unit is an instru-ment able to carry out the Test,programming and parameterreadout functions for the protec-tion units which equip the Tmax,the Isomax S molded case cir-cuit breakers and the Emax aircircuit breakers.In particular, for circuit breakersfitted with PR212/P andPR222DS/P trip units, the test,programming and readout pa-rameter functions are available.All the functions mentioned canbe carried out ON BOARD byconnection of the PR010/T unitto the multipin front flange con-nector on the protection unit;connection is guaranteed bymeans of special interfacing ca-bles supplied as standard withthe unit.The human-machine interface isguaranteed by using a mem-brane keyboard and a multi-linealphanumerical display.There are also two LEDs on theunit which signal the following re-spectively:

– POWER-ON and STAND BYsituation

– situation of the battery charg-ing state.

Two different types of Testare provided: automatic andmanual.By means of connection to thePC (software provided), it is alsopossible to upgrade the SW ofthe PR010/T unit to allow adap-tation of the Test unit to evolu-tion of new products.The most relevant test resultscan also be stored in the unit it-self and sent to the PersonalComputer on explicit request for“issue of report”.Both in automatic and manualmode, the PR010/T unit is ableto test the following:– protection functions L, S, I, G– monitoring of correct opera-

tion of the microprocessor.The same Tests can also berepeated using the manualmethod.The PR010/T unit is of the port-able type and operates with re-

chargeable batteries and/or withan external power supply.In its standard supply, the unit in-cludes:– PR010/T Test unit complete

with rechargeable batteries– TT1 Test unit;– 100...240 V AC/12 V DC ex-

ternal power supply– connection cables between

the unit and the multipin con-nector present on the rangesof releases which equip theIsomax S and the Emax se-ries

– connection cable betweenthe unit and the PC (serialRS232)

– power supply cable– instruction manual and soft-

ware– plastic case.

Page 94: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 3/45

3

1SD

C21

0327

F002

3

Front display unit - FDUThe front display is a display unit of the setting currents, alarms andparameters of the PR222DS/P and PR222DS/PD electronic trip unitsof T4 and T5. The display unit can operate correctly with self-supplywith I ≥ 0.35 x In on at least one phase. If the display is used incombination with the PR222DS/PD trip unit, and therefore with anauxiliary power supply, it is also possible to detect the protection,which has caused the trip unit intervention and the fault current.It is not compatible with the front accessories: rotary handle operat-ing mechanism, motor operator and front for lever operating mecha-nism.

CT for external neutralThis is mounted onto the external neutral conductor and allowsprotection against earth faults with three-pole circuit breakers. Thecircuit breaker must be fitted with PR212/P – LSIG, PR222DS/Por PR222DS/PD trip units. The transformer must be connected tothe trip unit by means of the specific X3-X4 connectors, selectedaccording to the version of the circuit breaker and the type of pro-tection trip unit used.

CT extT4 T5[A] [A]

100 320

160 400

250 630

320

ConnectorsConnectors X3 and X4 allow connection of the electronic trip unitwith external plant units or components. In fact, they are used tomake the L alarm signal available outside or to realise connectionto the PR020/K signalling unit. Both connectors are available forfixed and plug-in or draw out version circuit breakers.

Connector Function Trip unit

X3 PR020/K PR222DS/PD and PR211/P, PR212/P

L alarm signal PR222DS/P, PR222DS/PD PR211/P, PR212/P

Dialogue PR222DS/PD, PR212/D

Auxiliary supply PR222DS/P, PR222DS/PD

EP 010 PR222DS/PD

X4 External neutral PR222DS/P, PR222DS/PD, PR212/P

Page 95: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB3/46

3

1SD

C21

0331

F002

3

1SD

C21

0332

F002

3

S6-S7 fixedT1-T5 S8S6-S7 draw out

1SD

C21

0333

F002

3

1SD

C21

0334

F002

3

1SD

C21

0335

F002

3

1SD

C21

0330

F002

3

1SD

C21

0328

F002

3

1SD

C21

0329

F002

3

Flange for compartment doorFor Isomax S6 and S7 circuit breakers with the rotary handle op-erating mechanism, front for lever operating mechanism and mo-tor operator, a special flange is supplied for the purpose.All the flanges of the Tmax series (to be ordered) are of new con-ception and do not require the use of screws for their installation:fixing is greatly simplified by means of a simple dove-tailing opera-tion.In the case of use of a rotary handle operating mechanism, sole-noid operating mechanism or residual current releases, a specialdedicated flange is supplied.For T4 and T5 draw out circuit breakers, the flange supplied withthe conversion kit must be used instead of the one supplied withthe fixed circuit breaker.

Bracket for fixing on DIN railThis is applied to the fixed circuit breaker and allows installation onDIN rails (1.38”/35 mm).It simplifies assembly of circuit breakers up to 225 A (Tmax T1, T2and T3, except for T1B 1p) in standard switchboards.The bracket for fixing onto DIN rails is also available for Tmaxcircuit breakers combined with RC221 and RC222 residualcurrent releases or with the solenoid operating mechanism of theside-by-side type.

AccessoriesInstallation and testing accessories

Page 96: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 3/47

3

Spare partsWith Tmax series, the following spare parts are available:– opening solenoid for the RC221 and RC222 residual current

releases– opening solenoid for PR221DS electronic trip unit– kit with washers, screws and plugs for assembly of the front

terminals (F)– flange for compartment door.For further details, please ask the Service Division of ABB for thespare parts catalogue.

AccessoriesSpare parts

Page 97: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB3/48

3

1SD

C21

0336

F002

3

AccessoriesController for automatic transfer switch - ATS010

Control for automatic transfer switch - ATS010 (IEC only)The ATS010 controller is the new network-group switching device offered by ABB. It is based onmicroprocessor technology in compliance with the leading electromagnetic compatibility and envi-ronmental standards (EN 50178, EN 50081-2, EN 50082-2, IEC 60068-2-1, IEC 60068-2-2, IEC60068-2-3).The device is able to manage the entire switching procedure between the normal line and emer-gency line circuit breakers automatically, allowing great flexibility of settings.In case of fault in the normal line voltage, in accordance with the delays set, the normal line circuitbreaker is opened, the generator started and the emergency line circuit breaker closed. Similarly,when the normal line returns to range, the reverse switching procedure is automatically controlled.It is especially suited for use in all emergency power supply systems requiring a solution that is readyto install, easy to use and reliable.Some of the main applications include: power supply for UPS (Uninterrupted Power Supply) units,operating rooms and primary hospital services, emergency power supply for civilian buildings, air-ports, hotels, data banks and telecommunications systems, power supply of industrial lines for con-tinuous processes.The switching system consists of the ATS010 unit connected to two motor-driven and mechanicallyinterlocked circuit breakers. Tmax T4 and T5, and Isomax S6 and S7 circuit breakers can be used.The built-in main sensor of the ATS010 device makes it possible to detect faults in the mains voltage.The three inputs may be directly connected to the three phases of the normal power supply line fornetworks with rated voltage up to 500 V AC. Networks with a higher voltage require the insertion ofpotential transformers (PT), setting a rated voltage for the device that matches their secondary volt-age (typically 100 V).Two change-over contacts for each circuit breaker connect directly to the motor operator. The circuitbreaker connection is completed by wiring the status contacts: Open/Closed, Relay tripped, Racked-in (for draw out/plug-in circuit breakers).That is why on every circuit breaker connected to the ATS010 unit, the following are included inaddition to the mechanical interlock accessories:– motor operator from 48 V to 110 V DC or up to 250 V AC– open/closed contact– relay tripped contact– racked-in contact (for draw out versions)– signal and mechanical lock for protection relay tripped.On the motor operator for S6 and S7, the key lock is needed.The ATS010 device is designed to ensure extremely high reliability for the system it controls. It con-tains various safety systems intrinsically related to software and hardware operation.For software safety, a special logic prevents undesired operations, while a constantly operative watch-dog system points out any microprocessor malfunctions via a LED on the front of the device.Hardware safety allows integration of an electrical interlock via power relay, so that there is no needto use an external electrical interlock system. The manual selector on the front of the device can alsocontrol the entire switching procedure, even in the event of a microprocessor fault, by working elec-tromechanically on the control relays.

Page 98: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 3/49

3

General specifications

Rated supply voltage 24 V DC ±20%(galvanically insulated from earth) 48 V DC ±10%

(maximum ripple ±5%)Maximum absorbed power 5 W @ 24 V DC

10 W @ 48 V DC

Rated power (mains present and circuit breakers not controlled) 1.8 W @ 24 V DC4.5 W @ 48 V DC

Operating temperature -25 °C…+70 °CMaximum humidity 90% without condensation

Storage temperature -25 °C…+80 °CProtection rating IP54 (front panel)

Protection rating [mm] 144 x 144 x 85

Weight [kg] 0.8

Setting range for thresholds and times

Minimum voltage Un Min -5%…-30% Un

Maximum voltage Un Max +5%…+30% Un

Fixed frequency thresholds 10%…+10% fn

t1: opening delay of the normal line circuit breaker due to network error (CB-N) 0…32s

t2: generator start-up delay due to network error 0…32s

t3: stopping delay of the generator 0…254s

t4: switching delay due to network stop 0…254s

t5: closing delay of the emergency line circuit breakerafter detecting the generator voltage (CB-E) 0…32s

VN ok

CB-N on

GE start

VE ok

CoCo on

CB-E on

LOAD off

CaptionVN Main voltageCB-N Normal line circuit breaker

closedGE GeneratorVE Emergency line voltageCoCo Enable switching to emergency

lineCB-E Emergency line circuit breaker

closedLOAD Disconnection of lower priority

connected loads

Operating sequence

t1

t2

t5t4

t3

Page 99: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB3/50

3

1

3

4

2

5

7

6

1

2

3

1SD

C21

0338

F002

3

1SD

C21

0337

F002

3

AccessoriesController for automatic transfer switch - ATS010

Caption1 Status of the ATS010 unit and logic2 Operating mode selector3 Normal line check4 Normal line circuit breaker status5 Voltage on the emergency line6 Emergency line circuit breaker status7 Generator status

Caption1 Selectors to set the under- and over-

voltage thresholds2 Dip-switches to set:

– rated voltage– normal single-phase or three-phase

line– mains frequency– switching strategy

3 Switching delay time settings forT1…T5

Side panel settings

Front panel

Page 100: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

4

ABB 4/1

Characteristic curves andtechnical information

Index

Characteristic curves

Examples of curve readout .................................................................................................. 4/2

Trip curves for distribution

Circuit breakers with thermomagnetic trip units .................................................................. 4/4

Circuit breakers with electronic trip units ............................................................................ 4/11

Trip curves for MCP

Circuit breakers with magnetic only trip units ...................................................................... 4/17

Circuit breakers with PR221DS-I electronic trip unit ........................................................... 4/18

Specific let-through energy curves (1)

240 V .................................................................................................................................... 4/19

480 V .................................................................................................................................... 4/22

600 V .................................................................................................................................... 4/25

Limitation curves

240 V .................................................................................................................................... 4/27

480 V .................................................................................................................................... 4/30

600 V .................................................................................................................................... 4/33

Technical information

Temperature performances

Circuit breakers with electronic trip units ............................................................................ 4/35

Circuit breakers with thermomagnetic trip units .................................................................. 4/36

Power losses ...................................................................................................................... 4/38

(1) For the T1 1P characteristic curves, please ask ABB directly

Page 101: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB4/2

4

Is [kA]3010

10-1

102

1

10

102

110-1 103

Ip [kA]63

12.2

50.8

Curve A

Curve B

t [s]

x I110

10-1

10-2

102

1

10

102

103

104

110-1

~885

~31

~141.6

2 x I1

T2H 100

S6 N 800

1SD

C21

0001

F002

31S

DC

2100

02F0

023

Examples of curve readout

Example 1

Trip curves fordistribution (thermo-magnetic trip unit)

Example 2

Current-limitingcurves

Considering a S6N 800 TMDIn = 800 A circuit breaker. By meansof the thermal adjustment trimmer,the current threshold I1 is selected,for example at 0.8 x In (640 A); themagnetic trip threshold I3, adjust-able from 5 to 10 x In, we select at8 x In, equal to 6400 A.It can be noted that, on the basis ofthe conditions in which the overloadis presented, i.e. with the circuitbreaker at thermal running or not,the thermal relay trip varies consid-erably. For example, for an overloadcurrent of 2 x I1, the trip time is be-tween 31 and 141.6 s for hot trip,and between 141.6 and 885 s forcold trip.For fault current values higher than6400 A, the circuit breaker trips in-stantaneously with the magneticprotection.

The following figure shows the trendof the Tmax T2H 100, In = 100 cir-cuit breaker current-limiting curves.The r.m.s. of the prospective sym-metrical short-circuit current is indi-cated on the abscissa of the dia-gram, whereas the peak short-cir-cuit current value is indicated on theordinates. The current-limiting effectcan be assessed by comparing, atthe same symmetrical short-circuitcurrent value, the correspondingpeak value at the prospective short-circuit current (curve A) with the lim-ited peak value (curve B).The T2H 100 circuit breaker with In100 thermomagnetic trip unit at avoltage of 480 V, limits the short-circuit current to 12.2 kA for a faultcurrent of 30 kA, with a reductionof about 50.8 kA compared with thepeak value of the 63 kA prospec-tive short-circuit current.

Page 102: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 4/3

4

Irms [kA]

1

10

10-1

10-2

0.7

1 10 102 103

I2t [(kA)2s]

T4V 250

1SD

C21

0003

F002

3

Example 3

Specific let-throughenergy curve

An example of reading the graph ofthe specific let-through energy curveof the T4V 250 In = 80 circuitbreaker at a voltage of 490 V is givenaside.The prospective symmetrical short-circuit current is indicated on theabscissa of the diagram, whereasthe ordinates show the specific let-through energy values expressed in[kA]2s.In correspondence with a short-cir-cuit current of 100 kA, the circuitbreaker lets through a value of I2tequal to 0.7 [kA] 2s (700000 A2s).

Abbreviations used

In = Ampère rating of the thermomagnetic or electronic trip unitI1 = Long-time pick-up settingI3 = instantaneous pick up settingIrms = prospective symmetrical short-circuit current

Page 103: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB4/4

4

1SD

C21

0004

F002

3

t [s]

1x I1

10

10-1

10-2

102

1

10

102

103

104

10-1

70A 50A

40A

30A

25A

20A

15A

60A

1SD

C21

0005

F002

3

t [s]

1x I1

10

10-1

10-2

102

1

10

102

103

104

10-1

90A

80A100A

Trip curves for distributionCircuit breakers with thermomagnetic trip units

T1 100 - T1 100 1P TMF

In = 15 ÷ 70 A

T1 100 - T1 100 1P TMF

In = 80 ÷ 100 A

Page 104: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 4/5

4

1SD

C21

0006

F002

31S

DC

2100

07F0

023

t [s]

1x I1

10

10-1

10-2

102

1

10

102

103

104

10-1

50A

40A

35A

30A

25A

20A

15A

t [s]

1x I1

10

10-1

10-2

102

1

10

102

103

104

10-1

T2 100 TMF

In = 15 ÷ 50 A

T2 100 TMF

In = 60 ÷ 100 A

Page 105: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB4/6

4

1SD

C21

0008

F002

3

t [s]

1x I1

10

10-1

10-2

102

1

10

102

103

104

10-1

60÷100A

1SD

C21

0009

F002

3

t [s]

1x I1

10

10-1

10-2

102

1

10

102

103

104

10-1

125÷225A

Trip curves for distributionCircuit breakers with thermomagnetic trip units

T3 225 TMF

In = 60 ÷ 100 A

T3 225 TMF

In = 125 ÷ 225 A

Page 106: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 4/7

4

1SD

C21

0010

F002

31S

DC

2100

11F0

023

t [s]

1x I1

10

10-1

10-2

102

1

10

102

103

104

10-1 103

In=15A I3=500AIn=20A I3=500AIn=30A I3=500AIn=40A I3=500AIn=50A I3=500A

t [s]

1x I1

10

10-1

10-2

102

1

10

102

103

104

10-1

I3=5…10 x In

T4 250 TMF/TMD

In = 20 ÷ 50 AIn = 15, 20 TMFIn = 30, 40, 50 TMD

T4 250 TMA

In = 80 ÷ 250 A

Page 107: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB4/8

4

1SD

C21

0013

F002

3

t [s]

1x I1

10

10-1

10-2

102

1

10

102

103

104

10-1

600A

t [s]

1x I1

10

10-1

10-2

102

1

10

102

103

104

10-1

I3=5…10 x In

1SD

C21

0012

F002

3

Trip curves for distributionCircuit breakers with thermomagnetic trip units

T5 400/600* TMA

In = 300 ÷ 600 A

* Please ask ABB for 600 A availability

S6 800 TMD

In = 600 AI3 = 2.5 In

Page 108: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 4/9

4

1SD

C21

0014

F002

3

t [s]

1x I1

10

10-1

10-2

102

1

10

102

103

104

10-1

600A

1SD

C21

0015

F002

3

t [s]

1x I1

10

10-1

10-2

102

1

10

102

103

104

10-1

800A

S6 800 TMD

In = 600 AI3 = 5 ÷ 10 In

S6 800 TMD

In = 800 AI3 = 2.5 In

Page 109: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB4/10

4

1SD

C21

0016

F002

3

t [s]

1x I1

10

10-1

10-2

102

1

10

102

103

104

10-1

800A

S6 800 TMD

In = 800 AI3 = 5 ÷ 10 In

Trip curves for distributionCircuit breakers with thermomagnetic trip units

Page 110: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 4/11

4

1SD

C21

0017

F002

31S

DC

2100

18F0

023

t [s]

1 10

10-1

10-2

1

10

102

103

104

10-110-3

10-1 1 10Iu [kA]

0,4-0,44-0,48-0,52-0,56-0,60-0,64-0,68-0,72-0,76-0,80-0,84-0,88-0,92-0,96-1

A

B

A

B

102

11,5

22,5

3

4,55,5

3,56,5 7 7,5 8 8,5 9 10

C

B

0,4 1

x In

t [s]

1 10

10-1

10-2

1

10

102

103

104

10-110-3

10-1 1 10Iu [kA]

87 7,5 96,5 8,5 10

A

B

A

0,4-0,44-0,48-0,52-0,56-0,60-0,64-0,68-0,72-0,76-0,80-0,84-0,88-0,92-0,96-1

0,4 1

B

1,5

22,5

33,5

4,55,5

1

102

x In

Trip curves for distributionCircuit breakers with electronic trip units

T2 100

PR221DS-LS

L-I Functions

T2 100

PR221DS-LS

L-S Functions

Page 111: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB4/12

4

1SD

C21

0019

F002

3

t [s]

1Iu [kA]

10

10-1

10-2

1

10

102

103

104

10-110-3

10-1 1 10

7 7,5 8 8,5 9 10

2,51,5 2 3,51 3 4,5 5,5

6,5

102

x In

Trip curves for distributionCircuit breakers with electronic trip units

t [s]

1 10

10-1

10-2

1

10

102

103

104

10-110-3

x In Iu [kA]

0,4-0,44-0,48-0,52-0,56-0,6-0,64-0,68-0,72-0,76-0,8-0,84-0,88-0,92-0,96-1

102

1 10

T4 T5

0,4 1 1,5 2 2,5 3 3,5 4,5 5,5 6,5 7 7,5 8 8,5 9 10

1

1SD

C21

0005

F000

4

T4 250 - T5 400/600*

PR221DS

L-I Functions

* Please ask ABB for 600 A availability

T2 100

PR221DS-I

I Function

Page 112: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 4/13

4

t [s]

1 10

10-1

10-2

1

10

102

103

104

10-110-3

x In Iu [kA]

0,4-0,44-0,48-0,52-0,56-0,6-0,64-0,68-0,72-0,76-0,8-0,84-0,88-0,92-0,96-1

102

1 10

T4 T5

0,4 1 1,5 2 2,5 3 3,5 4,5 5,5 6,5 7 7,5 8 8,5 9 10

1

1SD

C21

0021

F002

3

T4 250 - T5 400/600*

PR221DS

L-S Functions

* Please ask ABB for 600 A availability

t [s]

1 10

10-1

10-2

1

10

102

103

104

10-110-3

x In

I2t ON

Iu [kA]

0,4-0,42-0,44-0,46-0,48-0,5-0,52-0,54-0,56-0,58-0,6-0,62-0,64-0,66-0,68-0,7-0,72-0,74-0,76-0,78-0,8-0,82-0,84-0,86-0,88-0,9-0,92-0,94-0,96-0,98-1

10

T4 T5

0,4 1 1,2 1,8 2,4 3 3,6 4,2 5,8 6,4 7 7,6 8,2 8,8 9,4 10

0,6

5,5

6,5

7

7,5

8

9

9,5

10,5

12

1,5

2,5 3 4

4,5

5

102

1SD

C21

0022

F002

3

L-S-I Functions(I2t const = ON)

Note: For T5 In = 600 A ⇒ I3max = 10 x In.

* Please ask ABB for 600 A availability

T4 250 - T5 400/600*

PR222DS/P andPR222DS/PD

Page 113: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB4/14

4

t [s]

1 10

10-1

10-2

1

10

102

103

104

10-110-3

I2t OFF

x In10

Iu [kA]

0,4-0,42-0,44-0,46-0,48-0,5-0,52-0,54-0,56-0,58-0,6-0,62-0,64-0,66-0,68-0,7-0,72-0,74-0,76-0,78-0,8-0,82-0,84-0,86-0,88-0,9-0,92-0,94-0,96-0,98-1

T4 T5

0,4 1

1,2

1,8 2,4 3 3,6 4,2 5,8 6,4 7 7,6 8,2 8,8 9,4 10

0,6

5,5

6,5

7

7,5

8

9

9,5

10,5

12

1,5

2,5 3 4 4,5 5

102

1SD

C21

0023

F002

3

L-S-I Functions(I2t const = OFF)

Note: For T5 In = 600 A ⇒ I3max = 10 x In.

* Please ask ABB for 600 A availability

Trip curves for distributionCircuit breakers with electronic trip units

T4 250 - T5 400/600*

PR222DS/P andPR222DS/PD

t [s]

1 10

10-1

10-2

1

10

102

103

104

10-110-3

102

x In

0,2 0,25 0,45 0,55 0,75 1

0,8

1SD

C21

0024

F002

3

G Function

* Please ask ABB for 600 A availability

T4 250 - T5 400/600*

PR222DS/P andPR222DS/PD

I4=0.2…0.49 x In inhibition at 4 x InI4=0.5…0.79 x In inhibition at 6 x InI4=0.8…1.00 x In inhibition at 8 x In

Page 114: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 4/15

4

1SD

C21

0025

F002

3

t [s]

1 10

10-1

10-2

1

10

102

103

104

10-110-3

102

x In

0,410,5

0,6

0,7

0,8

0,9

0,95

A

B

CD

A

B

CD

1,5 2 4 6 8 10 12

1SD

C21

0026

F002

3

t [s]

1 10

10-1

10-2

1

10

102

103

104

10-110-3

102

x In

I2t ON

0,4 1

A

B

CD

0,4-0,5-0,55-0,6-0,65-0,7-0,75-0,8-0,85-0,875-0,9-0,925-0,95-0,975-1

A

B

CD

1,5 2 4 6 8 1210

C

B

A

D

12 3 4 6 8 10

S6 800 - S7 1200

PR211/P

LI-I Functions

S6 800 - S7 1200 -S8 1600/2000/2500

PR212/P

L-S (I2t ON)-I Functions

Page 115: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB4/16

4

1SD

C21

0028

F002

3

t [s]

1 10

10-1

10-2

1

10

102

103

104

10-110-3

102

x In

0,2 0,3 0,4 0,6 0,8 1

0,9

B

A

C

D

S6 800 - S7 1200 -S8 1600/2000/2500

PR212/P

G Function

Trip curves for distributionCircuit breakers with electronic trip units

1SD

C21

0027

F002

3

t [s]

1 10

10-1

10-2

1

10

102

103

104

10-110-3

102

x In

I2t OFF

3

0,4 1

A

B

CD

A

B

CD

12 4 6 8 10

1,5 2 4 6 8 1210

C

B

D

A

0,4-0,5-0,55-0,6-0,65-0,7-0,75-0,8-0,85-0,875-0,9-0,925-0,95-0,975-1

S6 800 - S7 1200 -S8 1600/2000/2500

PR212/P

L-S (I2t OFF)-I Functions

Page 116: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 4/17

4

1SD

C21

0029

F002

3

t [s]

1 10

10-1

10-2

1

10

102

103

104

10-110-3

102

x In

6 12

T2-T3 100 MCP

Adjustable magneticonly trip unitI3 = 6…12 x In

Trip curves for MCPCircuit breakers with magnetic only trip units

Page 117: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB4/18

4

Trip curves for MCPCircuit breakers with PR221DS-I electronic trip unit

t [s]

1Iu [kA]

10

10-1

10-2

1

10

102

103

104

10-110-3

10-1 1 10

7 7,5 8 8,5 9 102,51,5 2 3,51 3 4,5 5,5 6,5

102

x In

t [s]

1 10

10-1

10-2

1

10

102

103

104

10-110-3

1 1,7 2 2,5 3 3,5 4,5 5,2 6,5 8 107 7,5 8,5 9

Iu [kA]10-1 1 10

102

x In

1SD

C21

0047

F000

41S

DC

2100

06F0

004

T2 100

PR221DS-I

T4 250 - T5 400/600*

PR221DS-I

I Function

I Function

* Please ask ABB for 600 A availability

Overload limit

Overload limitT4 320 - T5 630

Overload limitT4 250 - T5 400

Page 118: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 4/19

4

1SD

C21

0033

F002

31S

DC

2100

34F0

023

10 102

10-1

10-3

103

1

1Irms [kA]

I2t [(kA)2s]

10-1

10-2

15A

20A

25÷35A

40-50A

70-80A

60A

90-100A

10 102

10-1

10-2

103

1

1Irms [kA]

I2t [(kA)2s]

20A

15A

90-100A

40-50-60A

70-80A

25-30A

Specific let-through energy curves

T1 100

240 V

T2 100

240 V

Page 119: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB4/20

4

Specific let-through energy curves

1SD

C21

0035

F002

3

10 102

10-1

103

1

1Irms [kA]

I2t [(kA)2s] 10

70-80A

60A

125A

175A

200A

225A

90-100A

1SD

C21

0036

F002

3

T3 225

240 V

T4 250

240 V

1Irms [kA]

10 102

1

10I2t [(kA)2s]

103

10-1

10-2

20-25A

40-50A

100-250A

80A

Page 120: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 4/21

4

T5 400/600*

240 V

* Please ask ABB for 600 A availability

1SD

C21

0038

F002

3

10 102

10-1

10-2

103

1

10

102

103

1Irms [kA]

I2t [(kA)2s]

S8

S7

S6

S6 800 - S7 1200 -S8 1600/2000/2500

240 V

1Irms [kA]

10 102

1

10

103

10-1

I2t [(kA)2s]

300-600A

1SD

C21

0037

F002

3

Page 121: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB4/22

4

Specific let-through energy curves

1SD

C21

0039

F002

3

10 102

10-1

1

1Irms [kA]

I2t [(kA)2s]

10-2

20A

15A

40-50-60A

70-80A

90-100A

25-30A

T1 100

480 V

1SD

C21

0040

F002

3

10 102

10-1

10-3

103

1

1Irms [kA]

I2t [(kA)2s]

10-1

10-2

15A

20A

25÷35A

40-50A

70-80A

60A

90-100A

T2 100

480 V

Page 122: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 4/23

4

1SD

C21

0041

F002

3

10 102

10-1

103

1

1Irms [kA]

I2t [(kA)2s] 10

125A

200A

225A

90-100A

60A

175A

70-80A

T3 225

480 V

T4 250

480 V

1Irms [kA]

10 102

1

10I2t [(kA)2s]

103

10-1

10-2

20-25A

40-50A

100-250A

80A

1SD

C21

0042

F002

3

Page 123: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB4/24

4

Specific let-through energy curves

T5 400/600*

480 V

* Please ask ABB for 600 A availability

1SD

C21

0044

F002

3

10 102

10-1

10-2

103

1

10

102

103

1Irms [kA]

I2t [(kA)2s]

S6

S7

S8

S6 800 - S7 1200 -S8 1600/2000/2500

480 V

1Irms [kA]

10 102

1

10

103

10-1

I2t [(kA)2s]

300-600A

1SD

C21

0043

F002

3

Page 124: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 4/25

4

1Irms [kA]

10 102

1

10I2t [(kA)2s]

103

10-1

10-2

20-25A

40-50A

100-250A

80A

1SD

C21

0045

F002

3

1Irms [kA]

10 102

1

10

103

10-1

I2t [(kA)2s]

300-600A

1SD

C21

0046

F002

3

T4 250

600 V

T5 400/600*

600 V

* Please ask ABB for 600 A availability

Page 125: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB4/26

4

1SD

C21

0047

F002

3

10 102

10-1

10-2

103

1

10

102

103

1Irms [kA]

I2t [(kA)2s]

S6

S7

S8

S6 800 - S7 1200 -S8 1600/2000/2500

600 V

Specific let-through energy curves

Page 126: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 4/27

4

Limitation curves

1SD

C21

0048

F002

31S

DC

2100

49F0

023

1Irms [kA]

10 102

1

10

Ip [kA]

103

102

10-1

10-1

90-100A

70-80A

60A

40-50A

25÷35A

20A

15A

1Irms [kA]

10 1021

10

102Ip [kA]

103

90-100A

70-80A

40-50-60A

20A

15A

25-30A

T1 100

240 V

T2 100

240 V

Page 127: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB4/28

4

Limitation curves

1SD

C21

0050

F002

3

1Irms [kA]

10 1021

10

102Ip [kA]

103

125A

175A

200A

225A

60A

90-100A

70-80A

1SD

C21

0051

F002

3

T3 225

240 V

T4 250

240 V

1Irms [kA]

10 102

1

10

Ip [kA]

103

102

20-25A

40-50A

100-250A

80A

Page 128: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 4/29

4

T5 400/600*

240 V

* Please ask ABB for 600 A availability

1SD

C21

0053

F002

3

1Irms [kA]

10 1021

10

103Ip [kA]

103

102

S8

S7

S6

S6 800 - S7 1200 -

S8 1600/2000/2500

240 V

1Irms [kA]

10 102

1

10

Ip [kA]

103

102

300-600A

1SD

C21

0052

F002

3

Page 129: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB4/30

4

Limitation curves

1SD

C21

0030

F000

3

1Irms [kA]

10 1021

10

Ip [kA] 102

90-100A

70-80A

40-50-60A

20A

15A

25-30A

T1 100

480 V

1SD

C21

0031

F000

3

1Irms [kA]

10 102

1

10

Ip [kA]

103

102

10-1

10-1

90-100A

70-80A

60A

40-50A

20A

15A

25÷35A

T2 100

480 V

Page 130: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 4/31

4

1SD

C21

0056

F002

3

1Irms [kA]

10 1021

10

102Ip [kA]

103

60A

70-80A

90-100A

125A

175A

200A

225A

T3 225

480 V

T4 250

480 V

1Irms [kA]

10 1021

10

Ip [kA]

103

102

20-25A

40-50A

100-250A

80A

1SD

C21

0057

F002

3

Page 131: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB4/32

4

Limitation curves

T5 400/600*

480 V

* Please ask ABB for 600 A availability

1SD

C21

0059

F002

3

1Irms [kA]

10 1021

10

103Ip [kA]

103

102

S6

S8

S7

S6 800 - S7 1200 -S8 1600/2000/2500

480 V

1Irms [kA]

10 102

1

10

Ip [kA]

103

102

300-600A

1SD

C21

0058

F002

3

Page 132: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 4/33

4

1SD

C21

0060

F002

3

1Irms [kA]

10 102

1

10

Ip [kA]

103

102

20-25A

40-50A

100-250A

80A

1SD

C21

0061

F002

3

1Irms [kA]

10 102

1

10

Ip [kA]

103

102

300-600A

T4 250

600 V

T5 400/600*

600 V

* Please ask ABB for 600 A availability

Page 133: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB4/34

4

1SD

C21

0062

F002

3

1Irms [kA]

10 1021

10

103Ip [kA]

103

102

S6

S7

S8

Limitation curves

S6 800 - S7 1200 -S8 1600/2000/2500

600 V

Page 134: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 4/35

4

1SD

C21

0063

F002

3

95/35Ambient temperature [°F/°C]

104/40 113/45 122/50 131/55 140/60 149/65 158/700.6

0.65

0.7

0.75

0.8

0.85

0.9

0.95

1

1.05

Imax [xIn]

Temperature performancesCircuit breakers with electronic trip units

PR221DS

PR211/PPR212/PPR222DS

Page 135: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB4/36

4

Temperature performancesCircuit breakers with thermomagnetic trip units

Tmax T1 and T1 1P

In [A] 50 °F / 10 °C 68 °F / 20 °C 86 °F / 30 °C 104 °F / 40 °C 122 °F / 50 °C 140 °F / 60 °C

15 18 17 16 15 14 13

20 24 22 21 20 19 17

25 29 28 27 25 23 22

30 35 34 32 30 28 26

40 47 45 43 40 37 34

50 60 57 53 50 46 42

60 71 68 64 60 56 51

70 83 79 75 70 65 60

80 94 90 85 80 75 69

90 106 101 96 90 84 78

100 121 114 107 100 92 84

Tmax T2

In [A] 50 °F / 10 °C 68 °F / 20 °C 86 °F / 30 °C 104 °F / 40 °C 122 °F / 50 °C 140 °F / 60 °C

15 18 17 16 15 14 12

20 24 23 21 20 18 17

25 30 28 27 25 23 21

30 35 33 32 30 28 26

35 40 39 37 35 33 31

40 46 44 42 40 38 35

50 56 54 52 50 48 45

60 71 68 64 60 56 51

70 83 79 75 70 65 60

80 96 91 86 80 74 67

90 109 103 97 90 83 75

100 115 110 105 100 95 89

Tmax T3

In [A] 50 °F / 10 °C 68 °F / 20 °C 86 °F / 30 °C 104 °F / 40 °C 122 °F / 50 °C 140 °F / 60 °C

60 70 67 64 60 56 52

70 82 78 74 70 66 61

80 92 88 84 80 75 71

90 104 100 95 90 85 79

100 117 112 106 100 94 87

125 145 139 132 125 118 110

150 175 167 159 150 141 131

175 205 195 185 175 164 152

200 236 224 213 200 187 172

225 264 251 239 225 211 195

Page 136: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 4/37

4

Tmax T4

In [A] 50 °F / 10 °C 68 °F / 20 °C 86 °F / 30 °C 104 °F / 40 °C 122 °F / 50 °C 140 °F / 60 °C

20 24 22 21 20 19 17

25 30 28 27 25 23 21

40 47 44 42 40 37 34

50 59 56 53 50 47 43

80 94 90 85 80 75 68

100 118 112 106 100 95 85

125 148 140 133 125 119 106

150 177 168 159 150 143 127

200 236 224 212 200 190 170

250 266 252 239 225 214 191

Tmax T5 400/600*

In [A] 50 °F / 10 °C 68 °F / 20 °C 86 °F / 30 °C 104 °F / 40 °C 122 °F / 50 °C 140 °F / 60 °C

300 241…345 230…328 220…314 210…300 200…286 187…267

400 325…465 310…442 295…420 280…400 265…380 250…355

600 483…690 459…656 440…628 420…600 400…572 374…534

Isomax S6

In [A] 50 °F / 10 °C 68 °F / 20 °C 86 °F / 30 °C 104 °F / 40 °C 122 °F / 50 °C 140 °F / 60 °C

600 483…690 459…656 440…628 420…600 400…572 374…534

800 685…965 640…900 605…855 560…800 520…740 470…670

* Please ask ABB for 600 A availability

Page 137: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB4/38

4

Power losses

Type Trip unit In [A] P [W/pole]

15 1.3

20 1.3

25 2.0

30 1.8

40 2.6

T1 - T1B 1p TMF 50 3.7

60 3.9

70 5.3

80 4.8

90 6.1

100 6.8

15 1.0

20 1.7

25 1.6

30 2.4

35 3.0

TMF40 2.8

50 3.2

T2 60 4.6

70 4.7

80 5.4

90 6.9

100 7.7

10 0.5

ELT25 1.0

63 3.5

100 8.0

60 3.9

70 4.2

80 4.8

90 5.0

T3 TMF100 5.3

125 6.6

150 7.4

175 11.6

200 13.2

225 15.0

TMF15 3.6

20 3.6

30 3.6

TMD 40 3.8

50 3.9

80 4.6

T4100 5.2

TMA125 5.7

150 6.9

200 9.9

250 13.7

100 1.7

ELT 150 3.9

200 10.7

300 12.3

TMA 400 19.5

T5600* 40.1

300 9.3

ELT 400 16.5

600* 37.1* Please ask ABB for 600 A availability

Page 138: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 4/39

4

Type Trip unit In [A] P [W/pole]

TMD600 27.8

S6800 31.0

ELT600 27.2

800 32.0

S7 ELT 1200 49.2

1600 42.7

S8 ELT 2000 67.2

2500 101.7

Page 139: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new
Page 140: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 5/1

5

Wiring diagrams

Index

Wiring diagrams

Graphic symbols (IEC 60617 and CEI 3-14...3-26 Standards) .............................................. 5/2

Tmax T1…T5

Information for reading .......................................................................................................... 5/3

Circuit diagrams ..................................................................................................................... 5/7

Electrical accessories ............................................................................................................ 5/9

Isomax S6, S7 and S8

Information for reading ........................................................................................................ 5/12

Circuit diagrams ................................................................................................................... 5/15

Electrical accessories .......................................................................................................... 5/16

Page 141: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB5/2

5

M

M

Wiring diagramsGraphic symbols (IEC 60617 and CEI 3-14...3-26 Standards)

Differential current relay

Phase-failure detectionrelay in a three-phasesystem

Locked-rotor detectionrelay operating bycurrent sensing

Lamp, general symbol

Mechanical interlockbetween two devices

Operated by electricmotor

Motor with seriesenergization

Connection of conduc-tors

Terminal

Plug and socket (maleand female)

Position switch (limitswitch), break contact

Position switch (limitswitch) change-over breakbefore make contact

Contactor (contact openin the unoperatedposition)

Circuit breakerdisconnector withautomatic release

Switch-disconnector (on-load isolating switch)

Operating device(general symbol)

Thermal effect

Electromagnetic effect

Delay

Mechanical connection(link)

Manually operatedcontrol (general case)

Operated by turning

Operated by pushing

Operated by key

Operated by cam

Hearth, groung (generalsymbol)

Converter with galvanicseparator

Conductors in ascreened cable, twoconductors shown

Twisted conductors, twoconductors shown

Resistor (general symbol)

Temperature dependentresistor

Motor (general symbol)

Induction motor, three-phase, squirrel cage

Current transformer

Current transformer with fourthreaded winding and withone permanent winding withone tapping

Make contact

Break contact

Change-over breakbefore make contact

Position switch (limitswitch), make contact

Thermal relay

Instantaneousovercurrent or rate-of-rise relay

Overcurrent relay withadjustable short time-lagcharacteristic

Overcurrent relay withinverse short time-lagcharacteristic

Overcurrent relay withinverse long time-lagcharacteristic

Earth fault overcurrentrelay with inverse shorttime-lag characteristic

Phase-balance currentrelay

Page 142: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 5/3

5

Wiring diagramsInformation for reading – Tmax T1…T5

State of operation represented

The diagram is shown in the following conditions:– fixed, plug-in or draw out version circuit breaker (depending on type of circuit breaker), open and racked-in– contactor for motor starting open– circuits de-energized– releases not tripped– motor operator with springs charged (for T4 and T5).

Version

The diagram shows a circuit breaker or MCS in the plug-in version (only T2, T3, T4 and T5), but is also valid for thefixed and draw out version circuit breakers or MCS.With the fixed version circuit breakers or MCS, the applications indicated in figures 26-27-28-29-30-31 and 32cannot be provided.

Caption

= Figure number of the diagram* = See note indicated by the letterA1 = Circuit breaker applicationsA11 = FDU unit (front display)A12 = AUX-E type auxiliary contacts, with auxiliary relays for electrical signalling of circuit breaker

open and circuit breaker trippedA13 = PR020/K type signalling unit, with auxiliary relays for electrical signalling of the protection

functions of electronic trip unitA14 = MOE-E type actuation unit, with auxiliary relays for carrying out the commands coming from the

dialogue unitA15 = PR212/CI type contactor control unit for motor startingA2 = Applications of the solenoid operator or motor operatorA3 = Applications of the RC221 or RC222 type residual current releaseA4 = Indication apparatus and connections for control and signalling, outside the circuit breakerD = Electronic time-delay device of the undervoltage release (outside the circuit breaker)H, H1 = Signalling lampsK = Contactor for motor startingK51 = Electronic trip unit:

– PR221DS trip unit, with the following protection functions:- L against overload with inverse long time delay- S against short-circuit with inverse short time delay- I against short-circuit with tempo of instantaneous trip

– PR222DS/P or PR222DS/PD trip unit, with the following protection functions:- L against overload with inverse long time delay- S against short-circuit with inverse or definite short time delay- I against short-circuit with instantaneous trip time- G against earth fault with short time trip

M = Motor for circuit breaker opening and circuit breaker closing spring chargingM1 = Three-phase asynchronous motorQ = Main circuit breakerQ/1…3 = Auxiliary circuit breaker contactsR = Resistor (see note F)S1, S2 = Contacts controlled by the cam of the motor operatorS3 = Contact controlled by the key lock of the solenoid operator or motor operatorS4/1-2 = Contacts activated by the circuit breaker rotary handle (see note C)K51/1…8 = Contacts for electrical signalling of the protection functions of the electronic trip unitS51/S = Contact for electrical signalling of overload in progressS75I/1…3 = Contacts for electrical signalling of circuit breaker in racked-in position (only provided with circuit

breakers in plug-in version)S751S/1…3 = Contacts for electrical signalling of circuit breaker in racked-out position (only provided with

circuit breakers in plug-in version)

Page 143: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB5/4

5

Wiring diagramsInformation for reading – Tmax T1…T5

S87/1 = Contact for electrical signalling of RC222 type residual current release pre-alarmS87/2 = Contact for electrical signalling of RC222 type residual current release alarmS87/3 = Contact for electrical signalling of circuit breaker open due to RC221 or RC222 type residual

current release tripSC = Pushbutton or contact for closing the circuit breakerSC3 = Pushbutton for motor startingSO = Pushbutton or contact for opening the circuit breakerSO3 = Pushbutton for stopping the motorSQ = Contact for electrical signalling of circuit breaker openSY = Contact (bell alarm) for electrical signalling of circuit breaker open due to YO, YO1, YO2 or YU

thermomagnetic trip unit intervention (tripped position)TI = Toroidal current transformerTI/L1 = Current transformer placed on phase L1TI/L2 = Current transformer placed on phase L2TI/L3 = Current transformer placed on phase L3TI/N = Current transformer placed on the neutralW1 = Serial interface with the control system (EIA RS485 interface. See note D)X1,X2,X5…X9 = Connectors for the circuit breaker auxiliary circuits (in the case of circuit breakers in plug-in

version, removal of the connectors takes place simultaneously with that of the circuit breaker.See note E)

X11 = Back-up terminal boxX3,X4 = Connectors for the circuits of the electronic trip unit (in the case of circuit breakers in the plug-in

version, removal of the connectors takes place simultaneously with that of the circuit breaker)XA = Interfacing connector of the PR222DS/P or PR222DS/PD trip unitXA1 = Three-way connector for YO/YU (see note E)XA10 = Three-way connector for solenoid operatorXA2 = Twelve-way connector for auxiliary contacts (see note E)XA5 = Three-way connector for contact of electrical signalling of circuit breaker open due to trip

of the RC221 or RC222 type residual current release (see note E)XA6 = Three-way connector for contact of electrical signalling of circuit breaker open due to trip

of the overcurrent release (see note E)XA7 = Six-way connector for auxiliary contacts (see note E)XA8 = Six-way connector for contacts operated by the rotary handle or for the motor operator

(see note E)XA9 = Six-way connector for the electrical signalling of RC222 type residual current release pre-alarm

and alarm and for opening by means of the release itself (see note E)XB,XC,XE = Interfacing connectors of the AUX-E unitXD = Interfacing connector of the FDU unitXF = Interfacing connector of the MOE-E unitX0 = Connector for the YO1 trip coilX01 = Connector for the YO2 trip coilXV = Terminal boxes of the applicationsYC = Shunt closing release of the solenoid operator or motor operatorYO = Shunt tripYO1 = Shunt trip coil of the electronic trip unitYO2 = Shunt trip coil of the RC221 or RC222 type residual current releaseYO3 = Shunt trip of the solenoid operatorYU = Undervoltage release (see note B).

Page 144: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 5/5

5

Description of figures

Fig. 1 = Shunt trip.Fig. 2 = Permanent shunt trip.Fig. 3 = Instantaneous undervoltage release (see note B and F).Fig. 4 = Undervoltage release with electronic time-delay device outside the circuit breaker (see note B).Fig. 5 = Instantaneous undervoltage release in version for machine tools with one contact in series (see note

B, C, and F).Fig. 6 = Instantaneous undervoltage release in version for machine tools with two contacts in series (see note

B, C, and F).Fig. 7 = One changeover contact for electrical signalling of circuit breaker open due to RC221 or RC222

type residual current release trip.Fig. 8 = RC222 type residual current release.Fig. 9 = Two electrical signalling contacts for RC222 type residual current release pre-alarm and alarm.Fig. 10 = Solenoid operator.Fig. 11 = Stored energy motor operator.Fig. 12 = One changeover contact for electrical signalling of motor operator locked with key.Fig. 21 = Three changeover contacts for electrical signalling of circuit breaker open or closed and one

changeover contact for electrical signalling of circuit breaker open due to YO, YO1, YO2 and YUthermomagnetic trip unit intervention (tripped position).

Fig. 22 = One changeover contact for electrical signalling of circuit breaker open or closed and a changeovercontact for electrical signalling of circuit breaker open due to YO, YO1, YO2 or YU thermomagnetictrip unit intervention (tripped position).

Fig. 23 = Two changeover contacts for electrical signalling of circuit breaker open or closed.Fig. 24 = One changeover contact for electrical signalling of circuit breaker open due to trip unit intervention.Fig. 25 = One contact for electrical signalling of circuit breaker open due to trip unit intervention.Fig. 26 = First position of circuit breaker changeover contact, for electrical signalling of racked-in.Fig. 27 = Second position of circuit breaker changeover contact, for electrical signalling of racked-in.Fig. 28 = Third position of circuit breaker changeover contact, for electrical signalling of racked-in.Fig. 29 = First position of circuit breaker changeover contact, for electrical signalling of isolated.Fig. 30 = Second position of circuit breaker changeover contact, for electrical signalling of isolated.Fig. 31 = Third position of circuit breaker changeover contact, for electrical signalling of isolated.Fig. 32 = Circuit of the current transformer on neutral conductor outside the circuit breaker (for plug-in version

circuit breaker).Fig. 41 = Auxiliary circuits of the PR222DS/P electronic trip unit connected with FDU front display unit.

Page 145: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB5/6

5

Wiring diagramsInformation for reading – Tmax T1…T5

Incompatibility

The circuits indicated by the following figures cannot be supplied at the same time on the same circuit breaker:1 - 2 - 3 - 4 - 5 - 65 - 6 - 1110 - 1110 - 1221 - 22 - 2324 - 2526 - 32

Notes

A) The circuit breaker is supplied fitted with the applications specified in the ABB order confirmation.B) The undervoltage release is supplied for power supply branched on the supply side of the circuit breaker or

from an independent source: circuit breaker closing is only allowed with the release energised (the lock onclosing is made mechanically).

C) The S4/1 and S4/2 contacts shown in figures 5-6 open the circuit with the circuit breaker open and close itagain when a manual closing command is given by means of the rotary handle, in accordance with theStandards regarding machine tools (in any case, closing does not take place if the undervoltage release is notsupplied).

D) For connection of the EIA RS485 serial line, see the following documentation:– ITSCE-RH0199 for MODBUS communication.

E) Connectors XA1, XA2, XA5, XA6, XA7, XA8 and XA9 are supplied on request. They are always supplied withT2 and T3 circuit breakers in the plug-in version.Connectors X1, X2, X5, X6, X7, X8 and X9 are supplied on request. They are always supplied with circuitbreakers in the plug-in version and with T4 and T5 circuit breakers in the fixed version.

F) Additional external resistor for undervoltage release supplied at 250 V DC, 380/440 V AC and 480/500 V AC.G) In the case of fixed version circuit breaker with current transformer on external neutral conductor outside the

circuit breaker, when the circuit breaker is to be removed, it is necessary to short-circuit the terminals of theTI/N transformer.

H) With MOS 110…250 V AC, only use MOS-A for 200 V ≤ Un ≤ 250 V.I) SQ and SY are opto-insulated contacts.

Page 146: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 5/7

5

1SD

C21

0370

F002

3

1SD

C21

0370

F002

3

1SD

C21

0370

F002

3

1SD

C21

0370

F002

3

1SD

C21

0371

F002

3

1SD

C21

0371

F002

3

Wiring diagramsCircuit diagram – Tmax T1…T5

State of operation

Two pole, three-pole or four-polecircuit breaker with thermomagnetictrip unit

Three-pole circuit breaker withmagnetic trip unit

Three-pole or four-pole MCS(on-load isolating switch)

Three-pole or four-pole circuit breaker withPR222DS electronic trip unit

Three-pole or four-pole circuit breaker withPR222DS/P or PR222DS/PD electronictrip unit

Three-pole or four-pole circuit breaker withRC221 or RC222 residual current release

Tmax T1…T5

Page 147: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB5/8

5

1SD

C21

0372

F002

3

1SD

C21

0372

F002

3

Fixed version three-pole circuit breaker with current trans-former on neutral conductor, external to circuit breaker

Plug-in or draw out version three-pole circuit breaker with current transformeron neutral conductor, external to circuit breaker

Wiring diagramsCircuit diagram – Tmax T1…T5

Tmax T1…T5

Page 148: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 5/9

51S

DC

2103

73F0

023

1SD

C21

0374

F002

3

Wiring diagramsElectrical accessories – Tmax T1…T5

Shunt opening and undervoltage releases

Residual current releases and remote controls

Tmax T1…T5

Page 149: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB5/10

51S

DC

2103

75F0

023

1SD

C21

0376

F002

3

Wiring diagramsElectrical accessories – Tmax T1…T5

Auxiliary contacts

Position contacts

Tmax T1…T5

Page 150: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 5/11

5

FDU

1SD

C21

0377

F002

3

PR222DS/P electronic trip unit connected with the FDU frontdisplay unit

Page 151: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB5/12

5

State of the operation represented

The circuit is shown in the following conditions:– fixed, plug in or draw out circuit breaker (depending on type of circuit breaker), open and racked in– circuits de-energized– releases not tripped– motor operator with springs loaded (for S6-S7 circuit breakers).

Versions

The diagram indicates a circuit breaker or a MCS in draw out version but it may be applied to circuit breaker or aMCS in the fixed version too.Circuits given in figures 21-22-23-24-25-31-32-33-34-35 cannot be supplied with circuit breaker or MCS in fixedversion.

Caption

= Reference number of diagram figure* = See note indicated by the letterA1 = Circuit breaker accessoriesA2 = Motor operator accessoriesA4 = Indicative devices and connections for control and signallings, external to the circuit breakerA11 = Dialogue unit type PR212/D-L or PR212/D-M, for connection with a central control systemA12 = Actuating unit type PR212/T, with auxiliary relays for the execution of dialogue unit controlsA12/KC = Closing control of the actuating unitA12/KO = Opening control of the actuating unitA13 = Signalling unit type PR020/K, with auxiliary relays for electrical indication of the electronic trip

unit protective functionsD = Solid-state time-delaying device for undervoltage release (external to the circuit breaker)H1 = Signalling lampK51 = Electronic trip unit:

– PR211/P trip unit, with the following protective functions:- L against overload with inverse long time-delay trip- I against short-circuit with instantaneous trip

– PR212/P trip unit, with the following protective functions:- L against overload with inverse long time-delay trip- S against short-circuit with inverse or definite short time-delay trip- I against short-circuit with instantaneous trip- G against earth fault with inverse short time-delay trip

K51/1…B = Contacts for electrical indication of the electronic trip unit protective functionsK51/YO1 = Alarm indication of YO1 release tripped (bell alarm) for overcurrent and for “trip test”KO = Opening relay and spring charging device with a slay put make contact disengaged by a cam of

the motor operating mechanism when the circuit breaker reaches the open position and theclosing springs are charged

M = Motor for the circuit breaker opening and for the closing springs chargingM1 = Induction motorQ = Main circuit breakerQ/O…2 = Circuit breaker auxiliary contactsR1 = ThermistorS1 = Contact operated by the cam of the motor operating mechanism: it closes when the circuit

breaker is in closed position and it opens when the circuit breaker is in open position (it does notswitch when the circuit breaker is in tripped position)

S2 = Contact operated by the cam of the motor operating mechanism: it opens when the circuitbreaker is in closed position and it closes when the circuit breaker is in open position (it does notswitch when the circuit breaker is in tripped position). The contact is also operated by the keylock device (if provided)

S3 = Contact operated by the cam of the motor operating mechanism: it opens after closing ofcontact KO and it closes when the circuit breaker is in open position (it does not switch when thecircuit breaker is in tripped position

Wiring diagramsInformation for reading – Isomax S6, S7 and S8

Page 152: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 5/13

5

S75I/1…5 = Contacts signalling circuit breaker in the connected position (provided with circuit breaker indraw out version only. See note D)

S75S/1…5 = Contacts signalling circuit breaker in the isolated position (provided with circuit breaker in drawout version only. See note D)

SC = Pushbutton or contact for circuit breaker closingSC3 = Pushbutton for motor startSO = Pushbutton or contact for circuit breaker openingSO1,SO2 = Pushbutton or contact for circuit breaker openingSO3 = Pushbutton for motor stopSY = Contact signalling circuit breaker tripped through thermomagnetic, Y0, Y01, YU releases

operation (bell alarm)TI/L1 = Current transformer located on the phase L1TI/L2 = Current transformer located on the phase L2TI/L3 = Current transformer located on the phase L3TI/N = Current transformer located on neutralW1 = Serial interface with the remote supervision and control system (see note E)X1, X2 = Connectors for the circuit breaker auxiliary circuitsX3, X4 = Connectors for the electronic trip unit circuits (in case of circuit breaker in draw out plug-in

version the racking-out of the connectors occur simultaneoustly with the one of the circuit breaker)X5, X6 = Delivery terminal boards for the electronic trip unit circuitsXO = Connector for opening solenoid YO1XV = Terminal boards of the accessoriesYC = Closing coilYO = Shunt tripYO1 = Shunt trip of electronic trip unitYU = Undervoltage release (see note B).

Description of figures

Fig. 1 = Shunt tripFig. 4 = Instantaneous undervoltage release (see note B)Fig. 6 = Undervoltage release with solid-state time-delaying device external to the circuit breaker (see note B)Fig. 8 = Stored energy motor operatorFig. 11 = Two change-over contacts signalling circuit breaker on/offFig. 12 = One change-over contact signalling circuit breaker on/off and one change-over contact signalling

circuit breaker tripped through thermomagnetic YO, YO1, YU releases operation (bell alarm)Fig. 13 = One contact for electrical signalling of circuit breaker on, one contact for electrical signalling of circuit

breaker off and one contact for electrical signalling of circuit breaker not tripped throughthermomagnetic, YO, YO1, YU releases operation (not tripped position) to be used for example, forthe accept contact reported in fig. 8

Fig. 21 = First circuit breaker position contact, signalling the connected position (see note D)Fig. 22 = Second circuit breaker position contact, signalling the connected position (see note D)Fig. 23 = Third circuit breaker position contact, signalling the connected position (see note D)Fig. 24 = Fourth circuit breaker position contact, signalling the connected position (see note D)Fig. 25 = Fifth circuit breaker position contact, signalling the connected position (see note D)Fig. 31 = First circuit breaker position contact, signalling the isolated position (see note D)Fig. 32 = Second circuit breaker position contact, signalling the isolated position (see note D)Fig. 33 = Third circuit breaker position contact, signalling the isolated position (see note D)Fig. 34 = Fourth circuit breaker position contact, signalling the isolated position (see note D)Fig. 35 = Fifth circuit breaker position contact, signalling the isolated position (see note D)Fig. 41 = Contact signalling YO1 releases operated (for electrical characteristics of the contact see note G)Fig. 48 = Auxiliary circuits of the electronic trip unit PR212/P connected to the dialogue unit type PR212/D-L

or PR212/D-M and to the actuating unit type PR212/TFig. 49 = Auxiliary circuits of the electronic trip unit PR212/P connected to the dialogue unit type PR212/D-L

or PR212/D-M, to signalling unit type PR020/K and to the actuating unit type PR212/TFig. 50 = Auxiliary circuits of the electronic trip unit PR212/P connected to signalling unit type PR020/K.

Note: figures are always valid for S6 and S7; figures 1, 4, 41, 48, 49 and 50 are also valid for S8.

Page 153: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB5/14

5

Wiring diagramsInformation for reading – Isomax S6, S7 and S8

Incompatibility

The combinations of circuits given in the figures below are not possible on the same circuit breaker:1 - 4 - 611 - 12 - 1321 - 3122 - 3223 - 3324 - 3425 - 3548 - 49 - 50

Notes

A) Circuit breaker is supplied complete with the accessories listed in the ABB order acknowledgement only.B) Undervoltage release is suitable for circuit breaker supply side feeding or for feeding from an independent

source: circuit breaker closes only if the undervoltage release is energized (lock on closing is achieved me-chanically)

D) Circuit breaker can be equipped with S75I and S75S position contact, in whatever combination, with amaximum of 5 total contacts

E) To connect the serial communication line to the remote supervision and control system, see following docu-mentation:– ITSCE-RH0298.001 for Modbus– ITSCE-RH0297.001 for Lon

F) In case of circuit breaker in fixed version with current transformer on external conductor, in order to removethe circuit breaker it is necessary to short-circuit the terminals of TI/N current transformer

G) Contact signalling electronic trip unit operated (see fig. 41) has the following electrical characteristics:– rated voltage = 24 V– breaking capacity (resistive load) = 3 W/VA– maximum current interrupted = 0.5 A.

Page 154: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 5/15

51S

DC

2103

78F0

023

1SD

C21

0379

F002

3

Wiring diagramsCircuit diagrams – Isomax S6, S7 and S8

Isomax S6-S7-S8

State of operation

Two-pole, three-pole orfour-pole S6 circuitbreaker with ther-momagnetic trip unit

Two-pole, three-pole or four-pole S6-S7circuit breaker with PR211/P electronictrip unit

Two-pole, three-pole or four-pole S6-S7circuit breaker with PR212/P electronic tripunit

S6-S7-S8 MCP three-pole, withPR211/P (I) trip unit

S6-S7-S8 MCS three-pole and four-pole

Fixed version three-pole S6-S7-S8 circuit breaker withcurrent transformer on neutral conductor, external tocircuit breaker

Draw out version three-pole S6-S7 circuit breaker with current trans-former on neutral conductor, external to circuit breaker

Page 155: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB5/16

51S

DC

2103

80F0

023

1SD

C21

0381

F002

3

Wiring diagramsElectrical accessories – Isomax S6, S7 and S8

Isomax S6-S7-S8

Service releases, stored energy motor operator and auxiliary contacts

Auxiliary contacts

Page 156: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 5/17

51S

DC

2103

82F0

023

1SD

C21

0383

F002

3

PR212/P trip unit connected to the dialogue unit PR212/D and actuatorunit PR212/T

PR212/P trip unit connected to the dialogue unit PR212/D signallingunit PR020/K and actuator unit PR212/T

Page 157: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB5/18

5

1SD

C21

0384

F002

3

Wiring diagramsElectrical accessories – Isomax S6, S7 and S8

PR212/P trip unit connected to the signalling unit PR020/K

Isomax S6-S7-S8

Page 158: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/1

6

Overall dimensions

Index

Overall dimensions

Tmax T1 and single-pole Tmax T1Fixed circuit breaker/terminals ............................................................................................... 6/2

Tmax T2Fixed circuit breaker/terminals ............................................................................................... 6/4Plug-in circuit breaker/terminals ............................................................................................ 6/7

Tmax T3Fixed circuit breaker/terminals ............................................................................................. 6/10Plug-in circuit breaker/terminals .......................................................................................... 6/13

Tmax T4Fixed circuit breaker/terminals ............................................................................................. 6/16Plug-in circuit breaker/terminals .......................................................................................... 6/19Draw out circuit breaker/terminals ....................................................................................... 6/22

Tmax T5Fixed circuit breaker/terminals ............................................................................................. 6/24Plug-in circuit breaker/terminals .......................................................................................... 6/27Draw out circuit breaker/terminals ....................................................................................... 6/31

Isomax S6Fixed circuit breaker/terminals ............................................................................................. 6/35Draw out circuit breaker/terminals ....................................................................................... 6/37

Isomax S7Fixed circuit breaker/terminals ............................................................................................. 6/39Draw out circuit breaker/terminals ....................................................................................... 6/41

Isomax S8Fixed circuit breaker/terminals ............................................................................................. 6/43

Circuit breaker with residual current releaseT1, T2 and T3 with residual current release - RC221/RC222 .............................................. 6/44T4 and T5 with residual current release - RC221/RC222 .................................................... 6/47

AccessoriesTmax T1 - T2 - T3 ................................................................................................................ 6/49Tmax T4 - T5 ........................................................................................................................ 6/53Isomax S6 ............................................................................................................................ 6/60Isomax S7 ............................................................................................................................ 6/64Isomax S8 ............................................................................................................................ 6/68

Distances to be respectedTmax .................................................................................................................................... 6/69Isomax ................................................................................................................................. 6/70

Page 159: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/2

6

[mm/in]

5 Nm

1.4 Nm

1SD

C21

0400

F002

3

1SD

C21

0401

F002

3

1SD

C21

0407

F002

3

0.8 Nm1SD

C21

0403

F002

3

1SD

C21

0404

F002

3

1SD

C21

0406

F002

3

1SD

C21

0405

F002

3

1SD

C21

0409

F002

3

1SD

C21

0408

F002

3

1SD

C21

0402

F002

3

Overall dimensionsTmax T1 and single-pole Tmax T1

Fixed circuit breaker

Fixing on sheet Fixing on DIN EN 50022 rail

Caption

1 Depth of the switchboard in thecase of circuit breaker withface not extending from thecompartment door, with orwithout flange

2 Depth of the switchboard in thecase of circuit breaker withface extending from the com-partment door, without flange

3 Bracket for fixing onto rail

4 Bottom terminal covers withIP40 degree of protection

5 Insulating plate

Drilling templates for support sheetFor front terminals

3 POLES 4 POLES

Without inserts With inserts

T1 1P (SINGLE-POLE) T1 1P (SINGLE-POLE)

Without inserts With inserts

T1 1P (SINGLE-POLE)

Page 160: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/3

6

[mm/in]

1SD

C21

0411

F002

3

1SD

C21

0412

F002

3

1SD

C21

0413

F002

3

1SD

C21

0410

F002

3

>

X X

_

843.31

712.8

11.5

0.45

52 2.05

17 0.67

45 1.7710

44.

09

25.51

1034.06

30.12

9.5x9.50.37x0.37

>_

>_ 20.08>_

Terminals

Flange for the compartment door

Drilling templates of the compartment door

With flange andcircuit breaker face flushwith door (3-4 POLES)

Without flange andcircuit breaker face flushwith door (3-4 POLES)or extending (3 POLES)

Without flange andcircuit breaker faceextending (4 POLES)

Front for copper/aluminium cables - FC CuAl

(SINGLE-POLE)

Page 161: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/4

6

[mm/in]

0.8

Nm

0.8 Nm

1SD

C21

0414

F002

3

1SD

C21

0415

F002

3

1SD

C21

0416

F002

3

1SD

C21

0417

F002

3

1SD

C21

0418

F002

3

1SD

C21

0420

F002

3

1SD

C21

0419

F002

3

Overall dimensionsTmax T2

Fixed circuit breaker

Flange for thecompartment door

Fixing on sheet

Drilling templates of the compartment door

Drilling templates for support sheet

Fixing on DIN EN 50022 rail

With flange andcircuit breaker faceflush with door(3-4 POLES)

Without flange andcircuit breaker faceflush with door(3-4 POLES)

Without flange andcircuit breaker faceextending (3 POLES)

For front terminals

Caption

1 Depth of the switchboardin the case of circuit breakerwith face not extending fromthe compartment door, withor without flange

2 Depth of the switchboardin the case of circuit breakerwith face extending from thecompartment door, withoutflange

3 Bracket for fixing onto rail

4 Low terminal covers withdegree of protection IP40

5 Insulating plate

Without flange andcircuit breaker faceextending (4 POLES)

For rear terminals

3 POLES 4 POLES 3 POLES 4 POLES

Page 162: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/5

6

[mm/in]

6 Nm2

1

1

0.55x0.55

5.6 Nm

1

18 Nm

6 N

m

1SD

C21

0421

F002

3

1SD

C21

0422

F002

3

1SD

C21

0423

F002

3

1SD

C21

0424

F002

3

Terminals

Front for copper cables - FC Cu

Caption

1 Insulating base plate (com-pulsory)

2 Insulating barriers betweenphases (compulsory)

Front - F

Front for copper/aluminium cables -FC CuAl 1/0 AWG/50 mm2

Front extended spread - ESCaption

1 Insulating barriers betweenphases (compulsory)

2 Insulating plate

Page 163: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/6

6

[mm/in]

9 Nm

6 Nm

9 Nm

1SD

C21

0425

F002

3

1SD

C21

0426

F002

3

Overall dimensionsTmax T2

Terminals

Front extended - EFCaption

1 High terminal covers withdegree of protection IP40

2 Insulating barriers betweenphases (compulsory with-out 1)

Rear - RCaption

1 Low terminal covers withdegree of protection IP40

2 Insulating barriers betweenphases

Page 164: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/7

6

[mm/in]

1SD

C21

0427

F002

3

1SD

C21

0428

F002

3

1SD

C21

0429

F002

3

1SD

C21

0430

F002

3

1SD

C21

0431

F002

3

1SD

C21

0432

F002

3

Plug-in

circuit breaker

Flange forcompartment door

Fixing on sheet

Drilling templates of the compartment door

Drilling templates for support sheet

With flange andcircuit breaker faceflush with door(3-4 POLES)

Without flange andcircuit breaker faceflush with door(3-4 POLES)

Without flange andcircuit breaker faceextending (3 POLES)

For front terminals

Caption

1 Depth of the switchboard inthe case of circuit breakerwith face not extendingfrom the compartmentdoor, with or without flange

2 Depth of the switchboard inthe case of circuit breakerwith face extending fromthe compartment door,without flange

3 Fixed part

4 Moving part with terminalcovers, degree of protectionIP40

Without flange andcircuit breaker faceextending (4 POLES)

For rear terminals

3 POLES 4 POLES3 POLES 4 POLES

Page 165: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/8

6

[mm/in]

6 Nm

5.6 Nm

57.2

5

6 N

m 18 Nm

1SD

C21

0433

F002

3

1SD

C21

0434

F002

3

1SD

C21

0435

F002

3

1SD

C21

0436

F002

3

Terminals

Front for copper cables - FC Cu

Front - F

Front for copper/aluminium cables -FC CuAl 1/0 AWG/50 mm2

Front extended spread - ESCaption

1 Insulating barriers betweenphases (compulsory)

Overall dimensionsTmax T2

Page 166: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/9

6

[mm/in]

6 N

m

9 Nm

9 N

m

1SD

C21

0437

F002

3

1SD

C21

0438

F002

3

Front extended - EFCaption

1 High terminal covers withdegree of protection IP40

2 Insulating barriers betweenphases (compulsory with-out 1)

Rear - RCaption

1 Low terminal covers withdegree of protection IP40

Page 167: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/10

6

[mm/in]

1SD

C21

0440

F002

3

1SD

C21

0441

F002

3

1SD

C21

0442

F002

3

1SD

C21

0443

F002

3

1SD

C21

0444

F002

3

1SD

C21

0445

F002

3

Overall dimensionsTmax T3

Fixed circuit breaker

Flange forcompartment door

Fixing on sheet

Drilling templates of the compartment door

Drilling templates for support sheet

Fixing on DIN EN 50022 rail

With flange andcircuit breaker faceflush with door(3-4 POLES)

Without flange andcircuit breaker faceflush with door(3-4 POLES)

Without flange andcircuit breaker faceextending (3 POLES)

For front terminals

Caption

1 Depth of the switchboard in the case of circuit breaker with facenot extending from the compartment door, with or without flange

2 Depth of the switchboard in the case of circuit breaker with faceextending from the compartment door

Without flange andcircuit breaker faceextending (4 POLES)

For rear terminals

3 POLES 4 POLES3 POLES 4 POLES

3 Bracket for fixing on rail

4 Low terminal covers with degree of protection IP40

5 Insulating plate

1SD

C21

0439

F002

3

Page 168: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/11

6

[mm/in]

8 Nm

1

1

8 N

m

18 Nm

1SD

C21

0446

F002

3

1SD

C21

0447

F002

3

1SD

C21

0448

F002

3

1SD

C21

0449

F002

3

X X

FC CuAl1/0 - 14 AWG

FC CuAl

300 Kcmil - 4 AWG

,

843.3179

3.11712.8

6.2

0.24

116

4.57

58 2.28 9.

30.

37

45 1.77

12.5

0.49

≥3≥0.12

≥2≥0.08

1034.06

1

Terminals

Front for copper cables - FC Cu

Caption

1 Insulating base plate (com-pulsory)

Front - F

Front for copper/aluminium cables - FC CuAl

Front extended spread - ESCaption

1 Insulating barriers betweenphases (compulsory)

2 Insultating plate

Page 169: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/12

6

[mm/in]

8 Nm

8 Nm

9 Nm

6 Nm

1SD

C21

0450

F002

3

1SD

C21

0451

F002

3

Front extended - EFCaption

1 High terminal covers withdegree of protection IP40

2 Insulating barriers betweenphases (compulsory with-out 1)

3 Insulating plate

Rear - RCaption

1 Low terminal covers withdegree of protection IP40

2 Insulating plate

Overall dimensionsTmax T3

Terminals

Page 170: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/13

6

[mm/in]

1SD

C21

0452

F002

3

1SD

C21

0453

F002

3

1SD

C21

0454

F002

3

1SD

C21

0455

F002

3

1SD

C21

0457

F002

31SD

C21

0456

F002

3

Plug-in

circuit breaker

Flange forcompartment door

Fixing on sheet

Drilling templates of the compartment door

Drilling templates for support sheet

With flange andcircuit breaker faceflush with door(3-4 POLES)

Without flange andcircuit breaker faceflush with door(3-4 POLES)

Without flange andcircuit breaker faceextending (3 POLES)

For front terminals

Without flange andcircuit breaker faceextending (4 POLES)

For rear terminals

3 POLES 4 POLES

3 POLES 4 POLES

Caption

1 Depth of the switchboard inthe case of circuit breakerwith face not extendingfrom the compartmentdoor, with or without flange

2 Depth of the switchboard inthe case of circuit breakerwith face extending fromthe compartment door,without flange

3 Fixed part

4 Moving part with terminalcovers, degree of protectionIP40

Page 171: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/14

6

[mm/in]

8 Nm

100.39

8 N

m

18 Nm

1SD

C21

0458

F002

3

1SD

C21

0459

F002

3

1SD

C21

0460

F002

3

1SD

C21

0461

F002

3

Terminals

Front for copper cables - FC CuFront - F

Front for copper/aluminium cables -FC CuAl 1/0 AWG/50 mm2

Front extended spread - ESCaption

1 Insulating barriers betweenphases (compulsory)

Overall dimensionsTmax T3

Page 172: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/15

6

[mm/in]

8 N

m

18 Nm

6 Nm9 Nm

1SD

C21

0462

F002

31S

DC

2104

63F0

023

Front extended - EFCaption

1 High terminal covers withdegree of protection IP40

2 Insulating barriers betweenphases (compulsory with-out 1)

Rear - RCaption

1 Low terminal covers withdegree of protection IP40

Page 173: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/16

6

[mm/in]

1SD

C21

0464

F002

3

1SD

C21

0465

F002

3

1SD

C21

0466

F002

3

1SD

C21

0467

F002

3

1SD

C21

0468

F002

3

1SD

C21

0469

F002

3

1SD

C21

0470

F002

3

1SD

C21

0471

F002

3

1SD

C21

0472

F002

3

Overall dimensionsTmax T4

Fixed circuit breaker

Flange forcompartment door

Drilling templates of the compartment door

Drilling templates for support sheetFor front terminals For rear terminals

3 POLES 4 POLES 3 POLES 4 POLES

Fixing on sheet

Caption

1 Overall dimensions withcabled accessories mounted(SOR-C, UVR-C,RC221-222)

2 Overall dimensions withcabled auxiliary contactsmounted(only 3Q 1SY)

3-4 POLES 3-4 POLES

With flange Without flange

Page 174: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/17

6

[mm/in]

1SD

C21

0473

F002

3

1SD

C21

0474

F002

3

1SD

C21

0475

F002

3

1SD

C21

0476

F002

3

1SD

C21

0477

F002

3

1SD

C21

0478

F002

3

1SD

C21

0479

F002

3

1SD

C21

0480

F002

3

1SD

C21

0481

F002

3

1SD

C21

0482

F002

3

Terminals

Front for copper cables - FC Cu

Caption

1 Front terminals for cableconnection 2x150 mm2

2 Front terminals for multicableconnection

3 High terminal covers withdegree of protection IP40

Front - F

Front extended spread - ESCaption

1 Insulating barriers betweenphases (compulsory)

Front multicable - MC

Front for copper/aluminium cables - FC CuAl

Page 175: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/18

6

[mm/in]

1SD

C21

0483

F002

3

1SD

C21

0484

F002

3

1SD

C21

0485

F002

3

1SD

C21

0486

F002

3

1SD

C21

0487

F002

3

Overall dimensionsTmax T4

Terminals

Front extended - EFCaption

1 High terminal covers withdegree of protection IP40

2 Insulating barriers betweenphases (compulsory without 1)

Rear - RCaption

1 Low terminal covers withdegree of protection IP40

Page 176: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/19

6

[mm/in]

1SD

C21

0488

F002

3

1SD

C21

0489

F002

3

1SD

C21

0490

F002

3

1SD

C21

0491

F002

3

1SD

C21

0492

F002

3

1SD

C21

0493

F002

3

1SD

C21

0494

F002

3

1SD

C21

0495

F002

3

1SD

C21

0496

F002

3

Plug-in

circuit breaker

Flange forcompartment door

Fixing on sheet

Drilling templates of the compartment door

Caption

1 Fixed part

2 Moving part with terminalcovers, degree of protectionIP40

3 Overall dimensions withcabled accessories mounted(SOR-C, UVR-C,RC221-222)

4 Overall dimensions withcabled auxiliary contactsmounted(only 3Q 1SY)

With flange Without flange

Drilling templates for support sheetFor front terminals For rear terminals

3 POLES 4 POLES

3 POLES 4 POLES

Page 177: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/20

6

[mm/in]

1SD

C21

0497

F002

3

1SD

C21

0498

F002

3

1SD

C21

0499

F002

3

1SD

C21

0500

F002

3

Terminals

Front for copper cables - FC Cu or for copper/aluminium cables - FC CuAlCaption

1 For Cu cables

2 For Cu Al cables

3 High terminal covers withdegree of protection IP40

Front - EF

Overall dimensionsTmax T4

Page 178: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/21

6

[mm/in]

1SD

C21

0501

F002

3

1SD

C21

0502

F002

3

1SD

C21

0503

F002

3

1SD

C21

0504

F002

3

1SD

C21

0505

F002

3

1SD

C21

0506

F002

3

Rear flat horizontal - HR

Rear flat vertical - VR

3-4 POLES

3-4 POLES

Page 179: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/22

6

[mm/in]

1SD

C21

0509

F002

3

1SD

C21

0508

F002

3

1SD

C21

0507

F002

3

1SD

C21

0511

F002

31SD

C21

0510

F002

3

1SD

C21

0512

F002

3

1SD

C21

0513

F002

3

1SD

C21

0513

F002

3

1SD

C21

0514

F002

3

Overall dimensionsTmax T4

Draw out

circuit breaker

Flange for compartmentdoor

Fixing on sheet

Drilling templates of the compartment door

Caption

1 Fixed part

2 Moving part

3 Lock for compartment door(available on request)

4 Overall dimensions withcabled accessories mounted(SOR-C, UVR-C,RC221-222)

Drilling templates for support sheetFor front terminals For rear terminals

3 POLES 4 POLES

3 POLES 4 POLES

isolating distance

Page 180: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/23

6

[mm/in]

1SD

C21

0516

F002

3

1SD

C21

0517

F002

3

1SD

C21

0521

F002

3

1SD

C21

0520

F002

3

1SD

C21

0519

F002

3

1SD

C21

0518

F002

3

1SD

C21

0522

F002

3

1SD

C21

0523

F002

3

1SD

C21

0524

F002

3

1SD

C21

0525

F002

3

1SD

C21

0526

F002

3

1SD

C21

0527

F002

3

Terminals

Front - EF

Rear flat horizontal - HR

Front for copper cables - FC Cu Front for copper/aluminium cables - FC CuAl

Rear flat vertical - VR

3-4 POLES

3-4 POLES

Page 181: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/24

6

[mm/in]

1SD

C21

0528

F002

3

1SD

C21

0529

F002

3

1SD

C21

0530

F002

3

1SD

C21

0531

F002

3

1SD

C21

0532

F002

3

1SD

C21

0533

F002

3

1SD

C21

0534

F002

3

1SD

C21

0536

F002

3

1SD

C21

0535

F002

3

Overall dimensionsTmax T5 (400 A)

Fixed circuit breaker

Flange forcompartment door

Drilling templates of the compartment door

Drilling templates for support sheetFor front terminals For rear terminals

3 POLES 4 POLES

3 POLES 4 POLES

Fixing on sheet

Caption

1 Overall dimensions withcabled accessories mounted(SOR-C, UVR-C,RC221-222)

2 Overall dimensions withcabled auxiliary contactsmounted(only 3Q 1SY)

With flange (3-4 POLES) Without flange (3-4 POLES)

Page 182: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/25

6

[mm/in]

1SD

C21

0537

F002

3

1SD

C21

0538

F002

3

1SD

C21

0539

F002

3

1SD

C21

0540

F002

3

1SD

C21

0541

F002

3

1SD

C21

0542

F002

3

1SD

C21

0543

F002

3

1SD

C21

0544

F002

3

1SD

C21

0545

F002

3

Terminals

Caption

1 High terminal covers withdegree of protection IP40

Front - F

Front extended spread - ESCaption

1 Insulating barriers betweenphases (compulsory)

Front for copper/aluminium cablesCu/Al 300 mm2 FC CuAl

Front for copper cables - FC Cu

Front for copper/aluminium cables Cu/Al 2x240 mm2 - FC CuAl

Page 183: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/26

6

[mm/in]

1SD

C21

0546

F002

3

1SD

C21

0547

F002

3

1SD

C21

0548

F002

3

1SD

C21

0549

F002

3

1SD

C21

0550

F002

3

Front extended - EFCaption

1 High terminal covers withdegree of protection IP40

2 Insulating barriers betweenphases (compulsory without 1)

Rear - RCaption

1 Low terminal covers withdegree of protection IP40

Overall dimensionsTmax T5 (400 A)

Terminals

Page 184: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/27

6

[mm/in]

1SD

C21

0551

F002

3

1SD

C21

0552

F002

3

Plug-in

circuit breaker Fixing on sheet

Caption

1 Fixed part

2 Moving part with terminalcovers, degree of protectionIP40

3 Overall dimensions withcabled accessories mounted(SOR-C, UVR-C, RC221-222)

4 Overall dimensions withcabled auxiliary contactsmounted (only 3Q 1SY)

Page 185: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/28

6

[mm/in]

Overall dimensionsTmax T5 (400 A)

1SD

C21

0555

F002

3

1SD

C21

0556

F002

3

1SD

C21

0557

F002

3

1SD

C21

0558

F002

3

1SD

C21

0559

F002

3

1SD

C21

0560

F002

3

1SD

C21

0561

F002

3

Flange forcompartment door

Drilling templates of the compartment door

With flange Without flange

Drilling templates for support sheetFor front terminals

For rear terminals

3 POLES 4 POLES

3 POLES 4 POLES

A B C D E

32.5 128.5 143 172.5 64.51.28 5.06 5.63 6.79 2.54Rear 400 A

Plug-in

circuit breaker

Page 186: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/29

6

[mm/in]

1SD

C21

0562

F002

3

1SD

C21

0563

F002

3

1SD

C21

0566

F002

3

1SD

C21

0567

F002

3

Terminals

Front for cables Cu and Cu/Al - FC Cu - FC Cu/AlCaption

1 Front terminals for cables Cu

2 Front terminals for cablesCu/Al

3 High terminal covers withdegree of protection IP40

Extended front - EF

Page 187: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/30

6

[mm/in]

Overall dimensionsTmax T5 (400 A)

Terminals

1SD

C21

0573

F002

3

1SD

C21

0571

F002

3

1SD

C21

0572

F002

3

Rear flat horizontal - HR

1SD

C21

0576

F002

3

1SD

C21

0574

F002

3

1SD

C21

0575

F002

3

Rear vertical - VR

Page 188: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/31

6

[mm/in]

1SD

C21

0585

F002

3

1SD

C21

0584

F002

3

1SD

C21

0586

F002

3

Draw out

circuit breaker Fixing on sheet

Caption

1 Fixed part

2 Moving part with terminalcovers, degree of protectionIP40

3 Lock for compartment door(available on request)

4 Overall dimensions withcabled accessories mounted(SOR-C, UVR-C,RC221-222)

isolating distance

Page 189: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/32

6

[mm/in]

1SD

C21

0590

F002

3

1SD

C21

0591

F002

3

1SD

C21

0592

F002

3

1SD

C21

0593

F002

3

1SD

C21

0594

F002

3

1SD

C21

0595

F002

3

Flange for compartmentdoor

Drilling templates of the compartment door

Drilling templates for support sheetFor front terminals

For rear terminals

3 POLES 4 POLES

3 POLES 4 POLES

Draw out

circuit breaker

Overall dimensionsTmax T5 (400 A)

A B C D E

32.5 128.5 143 172.5 64.51.28 5.06 5.63 6.79 2.54Rear 400 A

Page 190: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/33

6

[mm/in]

1SD

C21

0596

F002

3

1SD

C21

0597

F002

3

1SD

C21

0600

F002

3

1SD

C21

0601

F002

3

Terminals

Caption

1 Front terminals for coppercables

2 Front terminals for copper/aluminium cables

3 Terminals with degree ofprotection IP40

Extended front - EF

Front for cables Cu and Cu/Al 400 A- FC Cu - FC Cu/Al

Page 191: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/34

6

[mm/in]

1SD

C21

0607

F002

31S

DC

2106

05F0

023

1SD

C21

0606

F002

3

1SD

C21

0610

F002

31S

DC

2106

08F0

023

1SD

C21

0609

F002

3

Overall dimensionsTmax T5 (400 A)

Rear flat horizontal - HR

Rear flat vertical - VR

Terminals

Page 192: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/35

6

[mm/in]

Y

X

1

X

Y

==

== 2

≥3≥0.12

=

=

16.50.65

(4 POLES)

(3 POLES)

1525.98

1405.51

2108.27

1074.21

1596.26

103.54.07

90.3514

0.55

101.54

20.08

120.47

125.

254.

93

161

6.34

241

9.49 10

54.

13

111.

754.

40

268

10.5

5

279.511

104.754.12

1SD

C21

0618

F002

3

1SD

C21

0619

F002

347 1.85

2.50.10

Y

Y

X X

M5/Ø 5.5Ø 0.22

(3 POLES)

(4 POLES)

702.761405.51

109.

754.

32

237

9.33

351.38

Y

X

Y

(3 POLES)

(4 POLES)

(3 POLES)

(4 POLES)

702.76

171.56.75

85.753.38

241.59.51

1405.51

351.38

M5/Ø 5.5Ø 0.22

R21.5R0.85

109.

754.

32

237

9.33

141.

755.

5830

111

.85

1SD

C21

0620

F002

3

1SD

C21

0621

F002

3

Y

Y

X

M5/Ø 5.5Ø 0.22

Ø 35Ø 1.38

Y

Y

X

3 POLES 4 POLES

109.

754.

32

237

9.33

241

9.4911

1.75

4.40

80.31

702.76

702.76

702.76

237

9.33 10

9.75

4.32

M5/Ø 5.5Ø 0.22

80.31

702.76

1054.13

351.38

702.76

702.76

Ø 35Ø 1.38

241

9.4911

1.75

4.40

1SD

C21

0622

F002

3

Y

Y

XX

= =

= =

=

=

=

=

Ø 7Ø 0.28

1475.79

112

4.41

142

5.59

1154.53

1SD

C21

0623

F002

3

Fixed circuit breaker

Overall dimensionsIsomax S6

Terminal covers(to be ordered when not included in the supply)

low high

Mounting onsheet metal

Caption

1 Flange for compartment door

2 Tightening torque 2 Nm

Template for drilling sheet metal support(minimum thickness of sheet metal: 0.12”/3 mm)

For rear threaded terminals - RFor rear Cu/Al cables terminals - RCFor terminals:Front - FFront extended - EFFront for Cu/Al cables - FC CuAl

Template for drilling compartment door and fitting flange(thickness of sheet metal: 0.08”/2 mm)

Page 193: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/36

6

[mm/in]

501.97

41.51.63Ø 14

Ø 0.55 80.31

20 0.79

67 2.64

53.5

2.11

47 1.85

Y1164.57

451.77

49.51.95

80.31 20

0.79

116.

54.

59

903.54 23

0.91

22.50.89

22.50.89

1164.57

1164.57

451.77

Ø 13Ø 0.51

22.5 ± 0.10.89 ± 0.04

401.57 23

0.91 5 min.

120.47

Ø 6.5Ø 0.26

M24x2

702.76

702.76

702.76

2.50.10

732.87

441.73

Ø 20Ø 0.79

592.32

16.750.66

Ø 17.5Ø 0.69

120.47

421.65

250.98

1SD

C21

0624

F002

3

1SD

C21

0625

F002

3

1SD

C21

0626

F002

3

1SD

C21

0627

F002

3

1SD

C21

0628

F002

3

Threaded rear - R(low terminal covers included in the supply)

Front - F

Front extended spread - ES

For rear Cu/Al cables - FCCuAl(IP20 high terminal covers included in thesupply)

Front for Cu/Al cables - FCCuAl(IP20 high terminal covers included in thesupply)

Terminals

Front extended - EF

Overall dimensionsIsomax S6

Page 194: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/37

6

[mm/in]

Y

Y

X X

Ø 8.5 (M8)Ø 0.33

(3 POLES)

(4 POLES

(4 POLES)

(4 POLES)

(3 POLES)

(4 POLES)

R2R0.08

1405.51

1074.21

2148.43284

11.18

77.5

3.05

120

4.72

45.5

1.7957

.52.

2686

.53.

4177

.53.

05

2108.27

702.76

Y

Y

X X

=

=

= =Ø 7

Ø 0.28

Ø 7Ø 0.28

Ø 4Ø 0.16

Nr. 5 Ø 8Ø 0.31

1706.69

80.53.17

451.77

90.

3539 1.54

160.63

R min 2007.87

1214.76

162.56.40

1013.98

19.750.78

90 3.54

177

6.97

161

6.34

1SD

C21

0630

F002

3

1SD

C21

0631

F002

3

Y

Y

X

1

X

24

3

=

=

(4 POLES)

(3 POLES)

Ø 5.5Ø 0.22

5

27.51.08

20.08

1676.57

195.57.70

1907.48

14.50.57

140

5.51

295

11.6

1

273

10.7

5

133

5.24

208

8.19

152

5.98

196

7.72

89.5

3.52

145

5.71

58 2.28

28011.02

963.78

1315.16136.55.37

123.54.86

193.57.62

2108.27

702.76

702.76

702.76

1SD

C21

0629

F002

3

Template for drilling sheet metalsupport(minimum thickness of sheet metal: 0.12”/3 mm)

Template for drilling compartmentdoor and fitting flange(thickness of sheet metal: 0.08”/2 mm)

Draw out

circuit breaker

isolating distanceCaption

1 Fixed part

2 Moving part

3 Flange for compartment door

4 Lock for compartment door(to order)

5 Tightening torque 9 Nm

Page 195: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/38

6

[mm/in]

X X XX

Ø 14Ø 0.5510

0.39

702.76

200.79

158

6.22

702.76

702.76

401.57

311.22 3

0.12

XXX X

100.39

80.53.1720

0.79

40 1.57

Ø 14Ø 0.55

30.12

1SD

C21

0632

F002

31S

DC

2106

33F0

023

Front for S6 - F

Horizontal or vertical rear flat bar for S6 - HR

Terminals

Overall dimensionsIsomax S6

Page 196: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/39

6

[mm/in]

Y

Y

X X

M5/Ø 5.5Ø 0.22

(3 POLES)

(4 POLES)

702.76

351.38

1405.51

378

14.8

8

203

7.99

Y

X X

Y

= =

=

=

1

2

=

=

X

(4 POLES)(3 POLES)

28011.02

406

15.9

8

161

6.34

326

12.8

3

105

4.13

37 1.46

37 1.46

177

6.97

30.5

1.207

0.28

70.

28

217

8.54

2108.27

1405.51

138.55.45

30.12

140.55.53

20.08

146.55.77

214.58.44

1525.98

702.76

702.76

702.76

70.28

1SD

C21

0634

F002

3

1SD

C21

0635

F002

3

X

Y

Y

Ø 3.6 H12Ø 0.14

Ø 3.6 H12Ø 0.14

= =

Ø 5.5 - M5Ø 0.22

Ø 5.5 - M5Ø 0.22

X

Y

Y

2208.66

R40R1.57

R40R1.57

702.76

702.76

1405.51

29011.42

702.76

702.76

702.76

702.76

50 1.97 50 1.97

378

14.8

8

378

14.8

8

203

7.99

203

7.99

315

12.4

0

315

12.4

0171.

56.

75

171.

56.

75

80 3.15 80 3.15

Y

Y

XX

= =

= =

=

=

=

=

Ø 7Ø 0.28

1475.79

112

4.41

142

5.59

1154.53

1SD

C21

0636

F002

3

1SD

C21

0637

F002

3

1SD

C21

0638

F002

3

Overall dimensionsIsomax S7

Fixed circuit breaker

low

Caption

1 Flange for compartment door

2 Tightening torque 2 Nm

Terminal covers

Template for drillingcompartment door andfitting flange(thickness of sheet metal:0.08”/2 mm)

Template for drilling sheet metal support(Minimum thickness of sheet metal: 0.12”/3 mm)

For flat rear terminals - RFor terminals:Front - FFront extended - EFFront for Cu/Al cables - FC CuAl

3 POLES 4 POLES

Page 197: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/40

6

[mm/in]

Overall dimensionsIsomax S7

Y

1405.51 33.5

1.32220.87

22 0.87 22 0.87

501.97

100.39

100.39

100.39

Ø 11Ø 0.43

Y70

2.76

391.54 15

0.59

107

4.21

71 2.80

22 0.8722

0.8750

1.97

702.76

702.76

Ø 11Ø 0.43

Ø 21.4Ø 0.84

Y702.76

702.76

702.76 38

1.50

572.24

783.07

973.82

37 1.46

30.5

1.20

Ø 13Ø 0.51

Y451.77

501.97

150.59

107

4.21

903.54

230.91

22.50.89

22.50.89

1164.57

1164.57

1164.57

451.77

Y

X X

A

B

Ø 11Ø 0.43

702.76

140.55

220.87

315

12.4

0

171.

56.

7516 0.63

22 0.87

50 1.97

853.35

702.76

702.76

1SD

C21

0639

F002

3

1SD

C21

0640

F002

31S

DC

2106

42F0

023

1SD

C21

0641

F002

3

1SD

C21

0643

F002

3

Front extended - EFFront - F

Raer horizontal or vertical flat terminals - HR or VR

Front for Cu/Al cables for S7 1250 - FC CuAl Front extended spreaded - ES

Terminals

Page 198: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/41

6

[mm/in]

X

Ø 5.5Ø 0.22

max

=

=

5

1

2

4

Y

Y

X

3

(4 POLES)

(3 POLES)241.59.51

28011.02

963.78

1315.16136.55.37

123.54.86

193.57.62

2108.271405.51

20.08

218.58.60

2479.7227.5

1.08

8.250.32

30.12

140

5.51

270

10.6

3

160

6.30 40

615

.98

196

7.72

143.

255.

64 211.

258.

32

1SD

C21

0644

F002

3

Y

Y

X XØ 8.5 (M8)Ø 0.33

(4 POLES)

(3 POLES)

(3 POLES)

(4 POLES)

1405.51

1074.21

2148.43284

11.18

2108.27

702.76

120.

54.

74

68.2

52.

69

120

4.72

92.5

3.64

76 2.99

120.

54.

74

Y

Y

X X

=

=

R min. 2007.87

Ø 4Ø 0.16

Ø 7Ø 0.28

Ø 7Ø 0.28

Nr.5 Ø 8Ø 0.31

= =

1706.69

160.63

19.750.78

1013.98

162.56.40

1214.76

161

6.34

90 3.54

177

6.97

90.

3539 1.54

80.53.17

451.77

1SD

C21

0645

F002

3 1SD

C21

0646

F002

3

Draw out

circuit breaker

isolating stroke

Caption

1 Fixed part

2 Moving part

3 Flange for compartment door

4 Lock for compartment door(to be ordered)

5 Tightening torque 9 Nm

Template for drilling sheet metalsupport or channel(Minimum thickness of sheet metal: 0.12”/3 mm)

Template for drilling compartmentdoor and fitting flange(thickness of sheet metal: 0.08”/2 mm)

Page 199: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/42

6

[mm/in]

Y

Ø 11Ø 0.43

XX

311.22

702.76

14 0.55

67 2.64

22 0.87

220.87

501.97

702.76

702.76

30.12

160.63

Y

XX

1084.25

30.12

Ø 11Ø 0.43 22 0.

8750 1.97

143.

255.

64

220.87

140.55

702.76

702.76

702.76

160.63

1SD

C21

0647

F002

3

1SD

C21

0648

F002

3

Front - F

Rear horizontal or vertical flat terminals - HR or VR

Terminals

Overall dimensionsIsomax S7

Page 200: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/43

6

[mm/in]

35614.02

50619.92

34113.43

53020.87

1787.01

1787.01

38014.96

161

6.34 20 0.

7920 0.79

280

11.0

2

20 0.79

327

12.8

7 135

5.31

344

13.5

4

20 0.79

280

11.0

2

309

12.1

716

16.

34

Nr. 8 Ø 9Ø 0.35

161

6.34

309

12.1

716

16.

34

Nr. 8 Ø 9Ø 0.35190

7.481907.48

R. min. 30011.81

Ø 5Ø 0.20

R10

R0.39

R10R0.39

R10

R0.39

R10R0.39 R4R0.16

1SD

C21

0650

F002

3

XX

=

X

Y

Y

XX

Y

Y

X

=

==2

3 POLES 4 POLES

2 1

3

38014.96

40615.98

55621.89

2429.53

236.59.31

286.511.28

1505.91

1204.72

1204.72

2037.99

1204.72

1204.72

400

15.7

531

312

.32

15 0.59

20 0.79

20 0.79 20 0.79

20 0.79

280

11.0

2

280

11.0

240

015

.75

2.50.10

1SD

C21

0649

F002

3

Y Y

Y Y

Ø 15Ø 0.59

= == = =

=

32412.76

32412.76

1505.91

1204.72

1204.72

803.15

401.57 20

0.79

200.79

200.79

1204.721154.5385

3.3565

2.56

200.79

652.56

20 0.79

20 0.79

20 0.79

40 1.57

1505.91

1204.72

1204.72

803.15

401.57

803.15

20 0.79

40 1.57

40 1.57

150.59

401.57

Ø 15Ø 0.59

1SD

C21

0651

F002

3

Template for drilling sheet metal support(Minimum thickness of sheet metal: 0.12”/3 mm)

3 POLES 4 POLES

Template for drillingcompartment door andfitting flange(Minimum thickness of sheetmetal: < 0.10”/2.5 mm)

Fixed circuit breaker

Overall dimensionsIsomax S8

Caption

1 Flange for compartment door

2 Circuit breaker mounting holes

3 Internal side of compartmentdoor

Caption

1 Hole for rear terminals only

2 Minimum radius of rotation ofcompartment door

Terminals

Rear - RFront - F

[mm/in]

Page 201: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/44

6

[mm/in]

222

8.74

222

8.74

1SD

C21

0164

F000

3

1SD

C21

0165

F000

3

1SD

C21

0166

F000

3

Overall dimensionsT1, T2 and T3 with residual current release - RC221/RC222

Front - F, fixing on sheetCaption

1 Depth of the switchboardwith circuit breaker faceextending

2 Depth of the switchboardwith circuit breaker faceflush with door

3 Front terminals for cableconnection

4 Low terminal covers withdegree of protection IP40

5 Insulating plate

T1

T2

T3

Page 202: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/45

6

[mm/in]

1SD

C21

0655

F002

3

Flange for the compartment door

3 POLES

4 POLES

Drilling template for fixing sheet

3 POLES 4 POLES

T1 T2 T3

T1 - T2 - T3

A B C D E F

124 107 53.5 78.1 25 53.14.88 4.21 2.11 3.07 0.98 2.09

124 107 53.5 90 30 604.88 4.21 2.11 3.54 1.18 2.36

141.5 122 61 102.5 35 67.55.57 4.80 2.40 4.04 1.38 2.66

T1

T2

T3

Page 203: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/46

6

[mm/in]

T1 - T2 - T3 T1 T1 - T2 - T3

B

A

H

T2 - T3

T1 - T2 - T3 T1 - T2 - T3 T1 - T2 - T3

B

A

H

1SD

C21

0656

F002

3

Drilling templates of the compartment door

3 POLES

4 POLES

Without flangeface extending

Without flangeface not extending

With flangeface not extending

T1

T2

T3

A B C D E F G H

18 108.2 94.1 – 23.5 113 78.1 39.10.71 4.26 3.70 – 0.93 4.45 3.07 1.54

18 122 106 76 23.5 120 90 460.71 4.80 4.17 2.99 0.93 4.72 3.54 1.81

13.5 137 118.5 83.5 19 127.4 102.5 53.50.53 5.39 4.67 3.29 0.75 5.02 4.04 2.11

Overall dimensionsT1, T2 and T3 with residual current release - RC221/RC222

Page 204: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/47

6

[mm/in]

T4 T5 (400 A)

1SD

C21

0658

F002

3

1SD

C21

0657

F002

3

1SD

C21

0659

F002

3

1SD

C21

0660

F002

3

1SD

C21

0661

F002

3

1SD

C21

0662

F002

3

1SD

C21

0663

F002

3

1SD

C21

0664

F002

3

T4 T5

1SD

C21

0665

F002

3

1SD

C21

0666

F002

3

Front - F, fixing on sheet

Caption

1 Overall dimensions withcabled auxiliary contactsmounted (only 3Q 1SY)

Flange for thecompartment door

Drilling templates of compartment doorand fitting flange

Drilling templates for support sheet

For circuit breakers For residual currentrelease

With flange Without flange

Overall dimensionsT4 and T5 with residual current release - RC221/RC222

Fixed version

Page 205: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/48

6

[mm/in]

T4 T5 (400 A)

1SD

C21

0670

F002

3

1SD

C21

0669

F002

3

1SD

C21

0668

F002

3

1SD

C21

0667

F002

3

1SD

C21

0671

F002

3

1SD

C21

0672

F002

3

1SD

C21

0673

F002

3

1SD

C21

0674

F002

3

1SD

C21

0675

F002

3

1SD

C21

0676

F002

3

T4 T5

Plug-in version

Front - F, fixing on sheet

Caption

1 Fixed part

2 Mobile part

3 Overall dimensions with cabled auxiliary contacts mounted (only 3Q 1SY)

Flange for the compartment door Drilling templates of compartment door and fitting flange

With flange Without flange

Drilling templates for support sheet

For circuit breakers For residual currentrelease

Overall dimensionsT4 and T5 with residual current release - RC221/RC222

Page 206: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/49

6

[mm/in]

Overall dimensionsAccessories for Tmax T1 - T2 - T3

T1 T2

T3

1SD

C21

0677

F002

3

1SD

C21

0678

F002

3

1SD

C21

0679

F002

3

1SD

C21

0681

F002

3

1SD

C21

0680

F002

3

1SD

C21

0682

F002

3

1SD

C21

0683

F002

3

Flange for compartment door

Caption

1 Depth of the switchboardwith operating mechanismface extending

2 Depth of the switchboardwith operating mechanismface flush with door

3 Low terminal covers withdegree of protection IP40

4 Insulating plate

Solenoid operator superimposed

Drilling templates of the compartment door

Without flangeOperating mechanism faceextending

Without flangeOperating mechanism faceflush with door

With flangeOperating mechanism faceflush with door

T1

T2

T3

A B C

33.5 18 23.51.32 0.71 0.93

33.5 18 23.51.32 0.71 0.93

29 13.5 191.14 0.53 0.75

Page 207: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/50

6

[mm/in]

Overall dimensionsAccessories for Tmax T1 - T2 - T3

470.518.52

7.01 with

with

with

with60.52.38

1SD

C21

0684

F002

3

1SD

C21

0685

F002

3

1SD

C21

0686

F002

31S

DC

2106

87F0

023

Caption

1 Transmission unit

2 Rotary handle operatingmechanism on the com-partment door

3 Insulating plate

Rotary handle operating mechanism on the compartment door

Drilling template of the compartment door

Minimum rotation radius fordoor fulcrum

Heights for door with maximum distance

Heights for door with minimum distance

A B

28 141.10 0.55

32.5 9.51.28 0.37

T1-T2

T3

Page 208: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/51

6

[mm/in]

1SD

C21

0688

F002

3

1SD

C21

0689

F002

3

1SD

C21

0691

F002

3

1SD

C21

0690

F002

3

1SD

C21

0692

F002

3

Caption

1 Rotary handle operatingmechanism on circuitbreaker

2 Insulating plate

Rotary handle operating mechanism on circuit breaker

Drilling template of the compartment door

Flange for the compartment

Drilling: see detail “A”

A B C D

67.7 28 53.2 60.52.67 1.10 2.09 2.38

63.2 32.5 48.7 562.49 1.28 1.92 2.20

T1-T2

T3

Page 209: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/52

6

[mm/in]

30512.01

30712.09

47018.5

47218.52

1SD

C21

0693

F002

3

1SD

C21

0694

F002

3

1SD

C21

0695

F002

3

1SD

C21

0696

F002

3

1SD

C21

0697

F002

3

1SD

C21

0698

F002

3

Front interlocking plate between two circuit breakers

Front interlocking plate among three circuit breakers

Caption

1 Drilling templates of thecompartment door

2 Drilling templates for sup-port sheet

3 Insulating plate

Mechanical interlock between circuit breakers

A B C D E F

52.5 77.5 112.5 87.5 53.5 53.52.07 3.05 4.43 3.44 2.11 2.11

50 80 115 85 53.5 53.51.97 3.15 4.53 3.35 2.11 2.11

47.5 82.5 117.5 82.5 56.5 65.51.87 3.25 4.63 3.25 2.22 2.58

T1

T2

T3

Overall dimensionsAccessories for Tmax T1 - T2 - T3

Page 210: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/53

6

[mm/in]

1SD

C21

0705

F002

3

1SD

C21

0706

F002

3

1SD

C21

0707

F002

3

1SD

C21

0708

F002

3

1SD

C21

0699

F002

3

1SD

C21

0700

F002

3

1SD

C21

0701

F002

3

1SD

C21

0702

F002

3

1SD

C21

0703

F002

3

1SD

C21

0704

F002

3

Drilling template of the compartment door Flange for thecompartment door

Overall dimensionsAccessories for Tmax T4 - T5

Fixed version

Rotary handle operating mechanism on the compartment doorCaption

1 Transmission unit

2 Rotary handle assembly withdoor lock device

3 Padlock device for openposition (maximum 3padlocks to be provided bythe user)

4 IP54 protection (supplied onrequest)

5 Min…max distance from thefront of the door withoutaccessory 4

6 Min…max distance from thefront of the door withaccessory 4

7 Dimension with AUEconnector (early makingcontact)

Minimum rotation radius for doorfulcrum

Drilling of compartment door

Rotary handle operating mechanism on circuit breakerCaption

1 Rotary handle operatingmechanism on circuit breaker

2 Padlock device for openposition (maximum 3padlocks to be provided bythe user)

3 Dimension with AUEconnector (early makingcontact)

4 Compartment door lock

Det. “A”

Det. “A”

Page 211: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/54

6

[mm/in]

1SD

C21

0709

F002

3

1SD

C21

0710

F002

3

1SD

C21

0711

F002

3

1SD

C21

0712

F002

3

1SD

C21

0713

F002

3

1SD

C21

0714

F002

3

1SD

C21

0715

F002

3

1SD

C21

0716

F002

3

1SD

C21

0717

F002

3

1SD

C21

0718

F002

3

T4 T5

T4 T5

Overall dimensionsAccessories for Tmax T4 - T5

Fixed version

Motor operatorCaption

1 Overall dimensions withcabled auxiliary contactsmounted (only 3Q 1SY)

Flange for thecompartment door(supplied as standard)

Drilling template of the compartment door

With flange Without flange

Drilling template for support sheet

3 POLES 4 POLES 3 POLES 4 POLES

Page 212: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/55

6

[mm/in]

T4 T5

1SD

C21

0719

F002

3

1SD

C21

0720

F002

3

1SD

C21

0721

F002

3

1SD

C21

0722

F002

3

1SD

C21

0723

F002

3

1SD

C21

0724

F002

3

1SD

C21

0725

F002

3

1SD

C21

0726

F002

3

1SD

C21

0727

F002

3

Front for lever operating mechanismCaption

1 Front for lever operatingmechanism

2 Lock for the compartmentdoor (supplied on request)

Flange for thecompartment door(supplied as standard)

Drilling template for the compartment door

Drilling template for support sheet

With flange Without flange

3 POLES 4 POLES

Det. “A”

For drilling see detail “A” Det. “A”

A B C

T4 35 70 17.51.38 2.76 0.69

T5 46.5 93 23.251.83 3.66 0.92

Page 213: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/56

6

[mm/in]

1SD

C21

0728

F002

31S

DC

2107

29F0

023

1SD

C21

0730

F002

3

Overall dimensionsAccessories for Tmax T4 - T5

Fixed version

Interlock between two circuit breakers placed side by sideCaption

1 Interlocking mechanism

2 Circuit breaker coupling plate

Drilling templates for fixing the circuit breaker on the support sheetCaption

1 Drilling template for allversions with rear terminals

Page 214: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/57

6

[mm/in]

1SD

C21

0731

F002

3

1SD

C21

0732

F002

3

1SD

C21

0733

F002

3

1SD

C21

0734

F002

3

1SD

C21

0735

F002

3

1SD

C21

0736

F002

3

D FE

A B C

Interlock between two circuit breakers placed side by side

Type Circuit breakers

A N° 1 T4 (F-P-W)

N° 1 T4 (F-P-W)

B N° 1 T4 (F-P-W)

N° 1 T5/400 (F-P-W) or T5/600* (F)

C N° 1 T4 (F-P-W)

N° 1 T5/600* (P-W)

D N° 1 T5/400 (F-P-W) or T5/600* (F)

N° 1 T5/400 (F-P-W) or T5/600* (F)

E N° 1 T5/400 (F-P-W) or T5/600* (F)

N° 1 T5/600* (P-W)

F N° 1 T5/600* (P-W)

N° 1 T5/600* (P-W)

Note:(F) Fixed circuit breaker(P) Plug-in circuit breaker(W) Draw out circuit breaker* Please ask ABB for 600 A availability

Page 215: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/58

6

[mm/in]

1SD

C21

0737

F002

3

1SD

C21

0738

F002

3

1SD

C21

0739

F002

3

1SD

C21

0741

F002

3

1SD

C21

0742

F002

3

T4 T5 (400 A)

Overall dimensionsAccessories for Tmax T4 - T5

Motor operator

Flange for thecompartment door(supplied as standard)

Drilling templates for the compartmentdoor and fitting flange

Draw out

version

isolating distance

Page 216: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/59

6

[mm/in]

1SD

C21

0743

F002

3

1SD

C21

0744

F002

3

1SD

C21

0745

F002

3

1SD

C21

0746

F002

3

1SD

C21

0747

F002

3

1SD

C21

0743

F002

3

Det. “A”

Rotary handle operating mechanism on the circuit breakers

Caption

1 Padlock device for openposition (maximum 3padlocks to be provided bythe user)

2 Lock for compartment door(supplied on request)

3 Dimension with AUEconnector (early makingcontact)

Flange for thecompartment door

Drilling template for compartmentdoor and fitting flange

Det. “A”

For drillingsee detail “A”

isolating distance

Page 217: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/60

6

[mm/in]

Y

X

5

Y

X

Y

Y

1 4

2 3

==

=

=

=

=

=

=

= =

=

=

== 65025.59

702.76

702.76

702.76

702.76

702.76

702.76

1204.72

10.50.41

461.81 284

11.18

R30R1.18

52520.67

273

10.7

5

65 2.56

103.

54.

07

288

11.3

427

.51.

08

375

14.7

6

350

13.7

8

129

5.08

331

13.0

3

101

3.98

101

3.98

13.5

0.53

Ø 9Ø 0.35

1SD

C21

0748

F002

3.

1SD

C21

0749

F002

3

Y

X X

Y

Y

Y

1

4==

=

=

5

23

= =

=

=

Ø 9Ø 0.35

=

=

51.52.03

31012.20

28811.34

652.56

27.51.08

170.67

820

32.2

8

273

10.7

517

56.

8927

310

.75

702.76

702.76

29311.54

28011.02

525

20.6

7

109

4.29

109

4.29

109

4.29

109

4.29

101

3.98

129

5.08

129

5.08

779

30.6

7

261.02

261.02

702.76

48.51.91

R20R0.79

Interlock between two horizontally-installed circuit breakers

Interlock between two vertically-installed circuit breakers

isolating distance

Note See the various different ver-sions for the dimensions ofthe circuit breakers

Caption

1 Interlock device

2 Drilling template for mountingcircuit breaker on sheet metal

3 Drilling template for all versionswith rear terminals

4 Dimensions with draw out ver-sion mounted on right

5 Tightening torque 9 Nm

Note See the various different ver-sions for the dimensions ofthe circuit breakers

Caption

1 Interlock device

2 Drilling template for mountingcircuit breaker on sheet metal

3 Drilling template for all versionswith rear terminals

4 Dimensions with draw out ver-sion mounted on right

5 Tightening torque 9 Nm

Overall dimensionsAccessories for Isomax S6

isolating distance

Page 218: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/61

6

[mm/in]

Y

X

1

Y

3

= =

Y81.25±0.13.20±0.004

R. min. 200R. min. 7.87

81.25±0.13.20±0.004

Y

X

R8R0.31

2

222.58.76 198.5

7.8123.50.93

1746.85

122±0.14.80±0.004

20.08

22.750.90

19.750.78

96.53.80

1405.51215.58.48

285.511.24

91.53.60

192.

257.

57

125.

254.

93

111.

754.

4033

813

.31

67 2.64

319

12.5

6

159.

56.

2872.2

52.

84

304

11.9

7

102.

254.

03

94.7

53.

73

270

10.6

3

Ø 8Ø 0.31

Y

304

Y

XR

2

1

= =

Y

X

Y

27.51.08 91.5

3.60

1405.51

270

10.6

3

338

13.3

1

117.

54.

63 108

4.25

100.

53.

96

186.

57.

34

222.58.76

23.50.93

20.08

247.59.74

81.25±0.13.20±0.004

81.25±0.13.20±0.004

19.750.78

304

11.9

7

Ø 8Ø 0.31

R. min. 200R. min. 7.87

1746.85

122±0.14.80±0.004

22.750.90

319

12.5

6

159.

56.

2872.2

52.

84

1SD

C21

0750

F002

31S

DC

2107

51F0

023

Motor operator for fixed circuit breaker

Motor operator for draw out circuit breakers

isolating distance

Note See the various different ver-sions for the dimensions ofthe circuit breakers

Caption

1 Flange for compartment door

2 Template for drilling compart-ment door

3 Dimensions with connectors

Note See the various different ver-sions for the dimensions ofthe circuit breakers

Caption

1 Flange for compartment door

2 Template for drilling compart-ment door

Page 219: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/62

6

[mm/in]

104.755.54

103.54.07

1525.98

20.08

1154.531475.79

177

6.97

147

5.79

90 3.54

451.77

2.750.11

42.51.67

371.46

44.51.75

220.87

1405.51

140

5.51

237

9.33 10

64.

17

241

9.49 23

79.

33 106

4.17

241

9.49

133

5.24

133

5.24

104

4.09

196

7.72

R. min. 200R. min. 7.87

Ø 4Ø 16

Ø 7Ø 28

702.76

702.76

1054.13

351.38

702.76

702.76

702.76

702.76

80.31

80.31

104

4.09

M5/Ø 5.5Ø 0.22

M5/Ø 5.5Ø 0.22

Ø 35Ø 1.38

Ø 35Ø 1.38

3 POLES 4 POLES

Overall dimensionsAccessories for Isomax S6

4

R min 200

X

Y

X

2

7

3

1

6

Y

Y5

=

=

Y

X

Y

X

Y

1054.13

103.54.07

632.48

41.51.63

331.30

50.20

220.87

271.06 54

2.13

230.91 19

0.75

20.08

1686.61

41.51.63

311.22

105

4.13

36 1.42

28 1.10

R min 7.87

R min 200R min 7.87

281.10

46 1.81

Ø 35Ø 1.38

237

9.33 10

64.

17

241

9.49

133

5.24

104

4.09

702.76

702.76

702.76

80.31 Ø 35

Ø 1.38

237

9.33 10

64.

17

241

9.49

133

5.24

702.76

1054.13

351.38

702.76

702.76

80.31

104

4.09

M5/Ø 5.5Ø 0.22

M5/Ø 5.5Ø 0.22

3 POLES 4 POLES

1SD

C21

0752

F002

31S

DC

2107

53F0

023

Rotary handle operating mechanism on fixed circuit breaker

Compartment door-mounted rotary handle mechanism with adjustable depthfor fixed circuit breaker

Drilling only required for version with rear terminals

Drilling only required for version with rear terminals

Note See the various different ver-sions for the dimensions ofthe circuit breakers

Caption

1 Rotary handle operatingmechanism on circuit breaker

2 Lock for compartment door(to order)

3 Drilling of compartment door

4 Flange for compartment door

5 Tightening torque 2 Nm

Note See the various different ver-sions for the dimensions ofthe circuit breakers

Caption

1 Transmission assembly

2 Rotary handle assembly withdoor lock device

3 Padlock device (maximum 3padlocks max ø 0.24”/6 mmto be provided by customeronly for circuit breaker openposition)

4 Minimum radius of rotation forfulcrum of door

5 Drilling template for mountingcircuit breaker on sheet metal

6 2.83”…19.92”/72...506 mm(with IP54 protection min. 96)

7 Distance -0.16”/-4 mm(shaft length)

6

Page 220: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/63

6

[mm/in]

Y

X

4

=

=

= =

=

=

3

Y

= =

= =

=

=

=

=

2

1

5

X

Y

Y

1525.98

42.51.67

103.54.07

1154.531475.79

451.77

20.08

371.46

2.750.11

140

5.51 19

67.

72

177

6.97

90 3.54

147

5.79

1405.51

104.754.12

Ø 4Ø 0.16

Ø 7Ø 0.28

X X

Y

Y

==

=

Y

Y

X

1

2

3

=

2108.27

42.51.67

371.46

20.08

44.51.75

220.87

123.54.86

91.53.60

222.58.76 131

5.16136.55.37

151

5.94

196

7.72

90 3.54

161

6.34

R. min. 200R. min. 7.87

Ø 4Ø 0.16

1214.76

162.56.40

1013.98

19.750.78

Nr. 5 Ø 8Ø 0.31

1706.69

80.53.1745

1.77

90.35

391.54

177

6.97

In5 6 Line

Load

100 A

160 A

200 A

250 A

320 A

400 A

X

14

56

=

=

=

=

=

=

X

Y

X

X

X

YM5/Ø 5.5Ø 0.22

Ø 35Ø 1.38

M5/Ø 5.5Ø 0.22

Ø 35Ø 1.38 11

0.43

237

9.33

237

9.33

106

4.17

106

4.17

241

9.49

241

9.49

185

7.28 77 3.03 49 1.93 11

54.

5325 0.98

25 0.98

133

5.24

133

5.24

104

4.09

104

4.09

702.76

702.76

702.76

702.76

702.76

702.76

80.31

80.31

1054.13

351.38

752.95 115

4.5352.52.07

100.39

401.57

3 POLES

4 POLES

1SD

C21

0754

F002

3

1SD

C21

0755

F002

3

Rotary handle operating mechanism on draw out circuit breaker

Front flange for operating lever mechanism

External neutral

Drilling only required for versionwith rear terminals

Note See the various different ver-sions for the dimensions ofthe circuit breakers

Caption

1 Rotary handle on circuitbreaker

2 Lock for compartment door (toorder)

3 Padlock device for open posi-tion (maximum 3 padlocksmax. ø 0.24”/6 mm to be pro-vided by user)

Note See the various different ver-sions for the dimensions ofthe circuit breakers

Caption

1 Front flange for operating levermechanism

2 Lock for compartment door (toorder)

3 Drilling of compartment door

4 Flange for compartment door

5 Tightening torque 2 Nm

Page 221: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/64

6

[mm/in]

Y

5 1 4

==

=

=

Y

Y2 3

=

=

= =

Ø 9Ø 0.35

R20

R0.79

=

=

X X

Y

66025.98

301.18

55021.65

401.57

401.57

6.50.26

6.50.26

30011.81

30011.81

1204.72 7

0.28

70.

2845

017

.72

406

15.9

8

420

16.5

4

115

4.53

115

4.53

407

16.0

2

117

4.61

65 2.56

140.

55.

53

336

13.2

327

.51.

08

702.76

702.76

702.76

702.76

5.50.22

702.76

702.76

1

= =

=

=

=

=

=

=

=4

= =

=

=

Ø 9Ø 0.35

=

=

=

=

2 3

= =

R30R1.18

Y

Y

X X

Y

Y

1100

43.3

1

406

15.9

840

615

.98

166

6.54

70.

287

0.28

70.

287

0.28

702.76

702.76

702.76

34013.39

27.51.08336

13.23652.56

31512.40

29011.42

875

34.4

5

408

16.0

6

994

39.1

3

115

4.53

1SD

C21

0756

F002

3

1SD

C21

0757

F002

3

Overall dimensionsAccessories for Isomax S7

Note See the various different ver-sions for the dimensions ofthe circuit breakers

Caption

1 Interlock device

2 Drilling template for mountingcircuit breaker on sheet metal

3 Drilling template for all versionswith rear terminals

4 Dimensions with draw out ver-sion mounted on right

5 Tightening torque 9 Nm

Interlock between two horizontally-installed circuit breakers

Interlock between two vertically-installed circuit breakers

isolating distance

isolating distance

Note See the various different ver-sions for the dimensions ofthe circuit breakers

Caption

1 Interlock device

2 Drilling template for mountingcircuit breaker on sheet metal

3 Drilling template for all versionswith rear terminals

4 Tightening torque 9 Nm

Page 222: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/65

6

[mm/in]

Nr. 7 Ø 8Ø 0.31

Y81.25±0.13.20±0.004

81.25±0.13.20±0.004

122±0.14.80±0.004R. min. 200

7.87

Y

X

R8R0.31

2

Y

X

1

Y

3

= =

222.58.76

231.59.11

20.08

22.750.90

19.750.78

1746.85

23.50.93

913.58

70.

2821

78.

54

304

11.9

7

319

12.5

672.2

52.

84

159.

56.

28

98.7

53.

89

91.2

53.

59

215.58.48

285.511.24

1405.51

91.53.60

270

10.6

319

5.75

7.71

338

13.3

1

108.

254.

26

Y

1

Y

= =

X

Y

Y

X

R8R0.31

2

27.51.08

70.28 140

5.51

91.53.60

222.58.76

23.50.93

211.

258.

32

270

10.6

319

07.

48

338

13.3

1

304

11.9

7

114

4.49

295.511.632

0.08

Nr. 7 Ø 8Ø 0.31

81.25±0.13.20±0.004

81.25±0.13.20±0.004

122±0.14.80±0.004

R. min. 2007.87

22.750.90

19.750.78

1746.85

319

12.5

672.2

52.

84

159.

56.

28

104.

54.

11 97 3.82

1SD

C21

0758

F002

31S

DC

2107

59F0

023

Note See the various different ver-sions for the dimensions ofthe circuit breakers

Caption

1 Flange for compartment door

2 Template for drilling compart-ment doorl

3 Dimensions with connectors

Note See the various different ver-sions for the dimensions ofthe circuit breakers

Caption

1 Flange for compartment door

2 Template for drilling compart-ment door

Motor operator for fixed circuit breaker

Motor operator for draw out circuit breaker

isolating distance

Page 223: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/66

6

[mm/in]

Overall dimensionsAccessories for Isomax S7

3

Y

= =

= =

=

=

=

=

Y

Ø 4Ø 0.16

Ø 7Ø 0.28

Y

X

= =5

X

6

2

1

Ø 5.5 - M5Ø 0.22

Y

X

Y

X

4

R40R1.57

R40R1.57

1054.13

140.55.53

20.08

42.51.67

371.46

44.51.75

220.87

R. min. 2007.87

1154.531475.79

2.750.1117

76.

97

147

5.79

451.77

196

7.72

140

5.51

211.

258.

3240

615

.98

1525.98

1405.51

90 3.54

378

14.8

8

378

14.8

8197.

257.

77

197.

257.

77

315

12.4

0

315

12.4

0165.

756.

53

165.

756.

53702.76

501.97

351.38

Ø 5.5 - M5Ø 0.22

501.97

702.76

702.76

702.76

1405.51

702.76

702.76

3 POLES 4 POLES

Y

X

4Y

Y

3

8

71

X

=

=

5

Y

X

Y

X

6

90¥

Ø 3.6 H12Ø 0.14

Y Y

2

1054.13

105

4.13

28 1.10

36 1.42

406

15.9

8 28 1.10 46 1.

811054.13

2058.07

2208.66

29011.42

501.97

501.97

351.38

702.76

702.76

702.76

1405.51

702.76

702.76

702.76

20.08

632.48

41.51.63

271.06

331.30

542.13

50.2023

0.91

190.75

220.8731

1.2241.51.63

211.

258.

32

R. min. 2007.87

R. min. 2007.87

Ø 3.6 H12Ø 0.14

378

14.8

8

80 3.15 80 3.15

197.

257.

7731

512

.40 16

5.75

6.53

378

14.8

8 197.

257.

7731

512

.40 16

5.75

6.53

Ø 5.5 - M5Ø 0.22

Ø 5.5 - M5Ø 0.22

R40R1.57

R40R1.57

3 POLES 4 POLES

1SD

C21

0760

F002

3

1SD

C21

0761

F002

3

Rotary handle operating mechanism on fixed circuit breaker

Compartment door-mounted rotary handle operating mechanism for fixedcircuit breaker

Drilling only required for version with rear terminals

Drilling only required for version with rear terminalsNote See the various different ver-

sions for the dimensions ofthe circuit breakers

Caption

1 Rotary handle operatingmechanism on circuit breaker

2 Lock for compartment door(to order)

3 Drilling of compartment door

4 Drilling template for mountingcircuit breaker on sheet metal

5 Flange for compartment door

6 Tightening torque 2 Nm

Note See the various different ver-sions for the dimensions ofthe circuit breakers

Caption

1 Transmission assembly

2 Rotary handle assembly withdoor lock device

3 Padlock device (maximum 3padlocks max ø 0.24”/6 mmto be provided by customeronly for circuit breaker openposition)

4 Minimum radius of rotation forfulcrum of door

5 Template for drilling compart-ment door

6 Drilling template for mountingcircuit breaker on sheet metal

7 2.83”…19.92”/72 ... 506 mm(with IP54 protection min. 96)

8 Distance - 0.16”/4 mm(shaft lenght)

7

Page 224: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/67

6

[mm/in]

X X X

Y

Y

==

=

=

X

Y

==

=

=

1

2

3

Y

Ø 4Ø 0.16

Nr. 7 Ø 7Ø 0.28

2108.27

20.08

451.77

160.63

44.51.75

220.87

90.35

1706.69

1013.98

162.56.40

1214.76

R. min. 2007.87

80.53.17

371.46 42.5

1.67

222.58.76

91.53.60

1315.16

123.54.86

136.55.37

406

15.9

821

1.25

8.32

196

7.72

177

6.9716

16.

34

90 3.54

19.750.78

3

Y

= =

= =

=

=

=

=

Y

X

= =5 6

2

1

X

In5 6 Line

Load

100 A

160 A

200 A

250 A

320 A

400 A

X

14

56

=

=

=

=

=

=

Ø 5.5 - M5Ø 0.22

Ø 5.5 - M5Ø 0.22

Y

X

4

R40R1.57

Y

X

R40R1.57

Y

X

4

4 POLES

3 POLES

Y

Ø 4Ø 0.16

Ø 7Ø 0.28

X

1405.51

196

7.72

211.

258.

3240

615

.98

177

6.97

90 3.54

147

5.79

140

5.51

1054.13

140.55.53

20.08

451.77

361.42

2.750.11

1154.531475.79

42.51.67152

5.98

702.76

702.76

702.76

501.97

501.97

752.95 115

4.5352.52.07

100.39

110.43

185

7.28 11

54.

5325 0.98

25 0.98

77 3.03 49 1.93

401.57

351.38

702.76

1405.51

702.76

702.76

378

14.8

8 197.

257.

7731

512

.40 16

5.75

6.53

378

14.8

8 197.

257.

7731

512

.40 16

5.75

6.53

1SD

C21

0762

F002

3

1SD

C21

0763

F002

3

Note See the various different ver-sions for the dimensions ofthe circuit breakers

Caption

1 Rotary handle operatingmechanism on circuit breaker

2 Lock for compartment door(to order)

3 Padlock device for open posi-tion (maximum 3 padlocksmax. ø 0.24”/6 mm to be pro-vided by user)

Note See the various different ver-sions for the dimensions ofthe circuit breakers

Caption

1 Front flange for lever operatingmechanism

2 Lock for compartment door (toorder)

3 Drilling of compartment door

4 Drilling template for mountingcircuit breaker on sheet metal

5 Flange for compartment door

6 Tightening torque 2 Nm

Rotary handle operating mechanism on draw out circuit breaker

Front flange for operating lever mechanism

Drilling only required forversion with rear terminals

External neutral

Page 225: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/68

6

[mm/in]

1SD

C21

0764

F002

3

401.57 15

0.591104.33

1224.80

803.151204.72

70 2.76

Ø 1

0.5

9

160

6.30

200

7.87

Overall dimensionsAccessories for Isomax S8

External neutral

Page 226: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/69

6

[mm/in]

1SD

C21

0765

F002

31S

DC

2107

66F0

023

1SD

C21

0767

F002

3

T1 60/2.36

H [mm/in]

T2 90/3.54

T3 140/5.51

T4 160/6.30

T5 160/6.30

Overall dimensionsDistances to be respected - Tmax

Caption

1 Connection - not insulated

2 Insulated cable

3 Cable terminal

Insulation distances for installation in metallic cubicle

Minimum centre distance between two circuit breakers side by side or superimposedFor assembly side by side or superimposed, check that the connection busbars or cables do not reduce theair insulation distance

Minimum centre distance for superimposed circuit breakers

Minimum centre distance for two circuit breakers side by side

Note: The dimensions shown apply for operatingvoltage Ub up to 690 V. The dimensions to berespected must be added to the maximumdimensions of the various different versions ofthe circuit breakers, including the terminals.

T1 76/2.99 102/4.02 76/2.99 102/4.02

T2 90/3.54 120/4.72 90/3.54 120/4.72

T3 105/4.13 140/5.51 105/4.13 140/5.51

T4 105/4.13 140/5.51 105/4.13 140/5.51

T5 140/5.51 184/7.24 140/5.51 184/7.24

3 poles 4 poles 3 poles 4 poles

Circuit breaker width [mm/in] Centre distance I [mm/in]

A B C[mm/in] [mm/in] [mm/in]

(*) For Ub ≥ 440 V: distance A ⇒ 60 mm (2.36 inches);distance C ⇒ 45 mm (1.77 inches)

T1 25/0.98 20/0.79 20/0.79

T2 25/0.98 20/0.79 20/0.79

T3 50/1.97 25/0.98 20/0.79

T4 30*/1.18* 25/0.98 25*/0.98*

T5 30*/1.18* 25/0.98 25*/0.98*

Page 227: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB6/70

6

[mm/in]

I

O

o

off

B

A

C

1SD

C21

0768

F002

3

Overall dimensionsDistances to be respected - Isomax

Insulation distances for installation in insulated compartment

Insulation distances for installation in metal compartment with wall to chassisground or wall to chassis ground protected with insulating plate

(*) These distances are valid for operating voltages of > 440 V and forcircuit breakers with breaking capacity level L

Wall to chassis ground [mm/in]

S6 35 100 25 201.38 3.94 0.98 0.79

A A(*) B C(Ub ≤ 415 V) (Ub ≥ 440 V)

S7

S8

50 100 30 201.97 3.94 1.18 0.79

200 200 30 1207.87 7.87 1.18 4.72

The dimensions shown apply for operating voltages Ub of up to690 V.The dimensions to be respected must be added to the maximumdimensions of the various different versions of the circuit breakers, includingthe terminals.

Insulated wall [mm/in]

S6 35 10 201.38 0.39 0.79

A B C

S8

50 10 201.97 0.39 0.79

120 15 1204.72 0.59 4.72

S7

Page 228: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB 6/71

6

[mm/in]

on

off

Y

Y

on

off

Y

Y

l

1SD

C21

0769

F002

3

The distances between centres are for the installation of fixedand plug in circuit breakers. When installing draw out S6 or S7circuit breakers you should also take into account the dimen-sions of the metal supporting channel that needs to be fittedbetween the guides of the fixed parts of two adjacent circuitbreakers.

Minimum distance between centres for horizontally-installed circuit breakers

Minimum distance between centres for two horizontally or vertically-installedcircuit breakersFor horizontal or vertical installation, make sure that the connection busbars or cables don’t reduce the airinsulation distances.

S7

S8

(*) these are the distances to be respected for circuit breakers fittedwith a flange for the compartment door or side conductor outlets.

S6

Circuit breaker Iwidth [mm/in] [mm/in]

3 poles 4 poles 3 poles 4 poles

210 280 210 2808.27 11.02 8.27 11.02

210 280 210 2808.27 11.02 8.27 11.02

435 585 435 58517.13 23.03 17.13 23.03

Minimum distance between centres for vertically-installed circuit breakers

HHH

123

1SD

C21

0770

F002

3

1 Connection not insulated2 Insulated cable3 Cable terminals

S7

S8

S6

H [mm/in]

1807.09

1807.09

30011.81

Page 229: Technical catalog ABB molded case circuit breakers · being able to equip such a small circuit breaker as the T2 with an electronic trip unit, to fit the circuit breakers with new

ABB Inc.1206, Hatton RoadWichita Falls, TX 76302 - U.S.A.Tel.: (888) 385-1221 - (940) 397-7000Fax: (940) 397-7001

www.abb-control.com

Due to possible developments of standards as well as ofmaterials, the characteristics and dimensions specified in thepresent catalogue may only be considered binding afterconfirmation by ABB Inc. 1S

DC

2100

03D

0202

- 0

9/20

03P

rinte

d in

Ital

y20

00 -

CA

L

ABB Inc.3299, boul. J.B. DeschampsLachine, QC H8T 3E4 - CANADATel.: (514) 420-3100Fax: (514) 420-3137

www.abb.ca