symmetrical short circuit-presentation

48
Ontoseno Penangsang 1) 1) Electrical Department, Sepuluh Nopember of Institute Technology Surabaya, 60111, Indonesia

Upload: fakhruddin-arrazi

Post on 22-Nov-2014

246 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: Symmetrical Short Circuit-presentation

Ontoseno Penangsang1)

1) Electrical Department, Sepuluh Nopember of Institute Technology

Surabaya, 60111, Indonesia

Page 2: Symmetrical Short Circuit-presentation

Short Circuit Objectives

Transient Phenomenon During Short Circuit

Thevenin Equivalent

Short Cicuit Capacity

Bus Admittance Matrix (Ybus)

Bus Impedance Matrix (Zbus)

Conclusions

Ontoseno Penangsang

[email protected]

Page 3: Symmetrical Short Circuit-presentation

Calculate system fault current duties and compare them with :

- the first cycle momentary or close-

and-latch ratings

- the interrupting ratings

of circuit- interrupting devices, such as circuit breakers and fuses

Ontoseno Penangsang

[email protected]

Page 4: Symmetrical Short Circuit-presentation

Calculate system fault current duties to compare with :

- short-time ratings

- withstand ratings

of system components, such as busway,cables, transformers, disconnect switches,etc

Ontoseno Penangsang

[email protected]

Page 5: Symmetrical Short Circuit-presentation

Selection ratings or settings of short-circuit protective devices, such as molded case breakers, solid-state trip units, fuses, relays.

Evaluate short-circuit current flow and voltage levels in the overall system for short-circuits in specific areas

Ontoseno Penangsang

[email protected]

Page 6: Symmetrical Short Circuit-presentation

Sources of Short Circuit Currents

Short Circuit Current from Induction Motor is

usually neglected

Synchronous generators

Synchronous motors and

condensers

Induction machines

Electric utility system

(Note : Power capacitors can also produce extremely high

transient fault or switching currents, but usually of short duration

and of natural frequency much higher than power frequency)

Ontoseno Penangsang

[email protected]

Page 7: Symmetrical Short Circuit-presentation

Assumptions in Short Circuit Current

Calculation

• Normal Loads, Line Charging Cpacitancs, Shunt Elements connected to ground are heglected.

• All System Internal Voltages have the same Magnitude and Phase Angle (1.0 0o)

• Series Resistance of Transmission Line and Transformer Impedance is neglected.

• All Transformers have Nominal Tap Position.

• Generators, Motors are represented by a constant Voltage Source connected in series with :

– Sub-Transient Reactance (The system is in a sub-transient condition)

– OR, Transient Reactance (The system is in a transient condition)

– OR, Synchronous Reactance (The system in a steady-state condition)

Ontoseno Penangsang

[email protected]

Page 8: Symmetrical Short Circuit-presentation

Basic Assumptions

To simplify the short-circuit calculations, a number of assumptions

are required.

The short-circuit current, during a three phase short-circuit, is assumed

to occur simultaneously on all three phases;

During the short-circuit, the number of phases involved does not

change, i.e. a three-phase fault remains three-phase and a phase-

to-earth fault remains phase-to-earth

For the entire duration of the shortcircuit, the voltages responsible

for the flow of the current and the short-circuit impedance do not

change significantly;

Ontoseno Penangsang

[email protected]

Page 9: Symmetrical Short Circuit-presentation

Transformer regulators or tap-changers are assumed to be set to a

medium position (if the short-circuit occurs away from the generator,

the actual position of the transformer regulator or tap-changers does

not need to be taken into account;

Arc resistances are not taken into account;

Basic Assumptions

All line capacitances are neglected;

Load currents are neglected;

All zero-sequence impedances are taken into account.

Ontoseno Penangsang

[email protected]

Page 10: Symmetrical Short Circuit-presentation

Transient Phenomenon During Short Circuit

Waktu

arus sinusoidal

arus

Short circuit current wave in a steady state condition is the

same as the current wave before the short circuit occurs

(sinusoidal), only the magnitude is different.

Ontoseno Penangsang

[email protected]

Page 11: Symmetrical Short Circuit-presentation

dt

diLRitEm )sin(

)sin()( tEte m

Electrical Power System Network

Ideal Voltage Source

tL

R

m etZ

Eti )sin()sin()(

21

222 LRZ

R

L 1tan

tL

R

m

Z

E

)sin(

Differential Equations :

Short Circuit Current :

DC Component :

Ontoseno Penangsang

[email protected]

Page 12: Symmetrical Short Circuit-presentation

Waktu

Arus asimetris total

komponen DC

arus AC simetrisa

rus

The magnitude of a short circuit current is

maximum at the time when the short circuit occurs,

and decreasing exponentially to a steady state

value.

Total Asymmetrical Current

DC ComponentSymmetrical AC Current

Cu

rre

nt

Time

Ontoseno Penangsang

[email protected]

Page 13: Symmetrical Short Circuit-presentation

Short Circuit Current

from a Generator

Short Circuit Current

without DC Component

Reactance for Short Circuit

Current Calculation

Ontoseno Penangsang

[email protected]

Page 14: Symmetrical Short Circuit-presentation

Short Circuit Currents

in phase a, b and c with

DC Component ≠ 0

Ontoseno Penangsang

[email protected]

Page 15: Symmetrical Short Circuit-presentation

Notes :

• The occurance of a short circuit can not be predicted, therefore α is notknown.

• DC component vanishes very fast, usually in 8 to 10 cycles.

• The reactance of synchronous machines changes with time

• To calculate the short circuit current, the following synchronous reactancesare used:

"

dx Sub-Transient Reactance, to calculate the short circuit current in the

first cycle after the occurrance of a short circuit, i.e. within 0.05 - 0.1

seconds,

Transient Reactance, to calculate the short circuit current in a few

cycles after the occurrance of a short circuit, i.e. within 0.2 – 2

seconds,

Synchronous Reactance, to calculate the short circuit current after the

steady state condition is reached.

,

dx

dxOntoseno Penangsang

[email protected]

Page 16: Symmetrical Short Circuit-presentation

Fault Types

A. SHUNT FAULT (SHORT CIRCUIT)

1. SYMMETRICAL SHORT CIRCUIT

a. THREE PHASE (L-L-L)

b. THREE PHASE TO GROUND (L-L-L-G)

2. UNSYMMETRICAL SHORT CIRCUIT

a. ONE PHASE TO GROUND (1L-G)

b. PHASE TO PHASE (L-L)

c. TWOPHASA TO GROUND (2L-G)

B. SERIES FAULT (OPEN LINE)

1. ONE LINE OPEN (1L-O)

2. TWO LINES OPEN (2L-O)

3. UNBALANCED SERIES IMPEDANCE

C. SIMULTANEOUS FAULT

1. SHUNT - SHUNT

2. SHUNT - SERIES

3. SERIES - SERIESOntoseno Penangsang

[email protected]

Page 17: Symmetrical Short Circuit-presentation

a. One Phase to Ground

b. Phase to Phase

c. Two Phase to Ground

d. Three Phase to Ground

e. Three Phase

f. Three Phase to Ground

through Impedance

Ontoseno Penangsang

[email protected]

Page 18: Symmetrical Short Circuit-presentation

Thévenin equivalent

Represents passive network

• No-load voltage VTH

• Short-circuit impedance ZTH

• All sources zero for ZTH

Also for entire power system

+/0/- seq. equivalents

VTH

ZTH

~

Ontoseno Penangsang

[email protected]

Page 19: Symmetrical Short Circuit-presentation

Short-circuit current

– Z=0 connected at terminals

– Short-circuit current

• Limited by ZTH (good!)

• ISC=VTH/ZTH≈1/ZTH p.u. (VTH≈1)

• Determines breaker rating

VTH

ZTH

~ ISC

Ontoseno Penangsang

[email protected]

Page 20: Symmetrical Short Circuit-presentation

Short-circuit power

– Short-circuit power

• Short-circuit capacity

• Fault level

– SSC=VTHISC≈ISC≈1/ZTH p.u.

– SSC not useful power

VTH

ZTH

~ ISC

Ontoseno Penangsang

[email protected]

Page 21: Symmetrical Short Circuit-presentation

Network strength

SLOAD relative to SSC

• SLOAD << SSC : strong

• SLOAD ≈ SSC/2 : weak

• SLOAD > SSC/2 : impossible VTH

ZTH

~ SLOAD

Ontoseno Penangsang

[email protected]

Page 22: Symmetrical Short Circuit-presentation

Bus admittance matrix Ybus

Admittance representation

Nodal current balances

I= Ybus Vbus

Reference bus removed

Ontoseno Penangsang

[email protected]

Page 23: Symmetrical Short Circuit-presentation

Example: Ybus

Ontoseno Penangsang

[email protected]

Page 24: Symmetrical Short Circuit-presentation

Ybus properties

• With reference

– Row and column sums zero

• Reference removed

– Dimensions N-1 x N-1

• One Ybus for each sequence

• Sparse and symmetric

• Compact network model

Ontoseno Penangsang

[email protected]

Page 25: Symmetrical Short Circuit-presentation

Bus impedance matrix Zbus

Vbus = Zbus I

If Ybus is invertible:

Zbus = Ybus-1

Zbus by inspection difficult

Ontoseno Penangsang

[email protected]

Page 26: Symmetrical Short Circuit-presentation

ZTH from Zbus

Element ii of Zbus

– Short-circuit impedance ZTH at bus i

• Conditions

– Zbus has neutral as reference

– Generators have internal impedance

– Loads can be included in Zbus

• Practical for large systemsOntoseno Penangsang

[email protected]

Page 27: Symmetrical Short Circuit-presentation

Simplified Machine Model

No Load Generator under Fault Condition

Internal Voltages of Loaded Machines under Fault Condition

Zbus Method

The Selection of Circuit BreakersOntoseno Penangsang

[email protected]

Page 28: Symmetrical Short Circuit-presentation

Simplified Machine Model

For steady-state operation, generators are represented

with a constant emf behind a synchronous reactance, XS

For salient-pole rotors, there is a direct axis and quadrature axis

Reactances

Under transient conditions, the machine reactance

changes due to the effect of the armature (transformer)

reaction and eddy currents in the damping circuits

For analysis it is useful to imagine the synchronous

reactance as three components

direct axis sub-transient reactance

direct axis transient reactance

direct axis steady-state reactance

these transient reactances have an associated time-constant

Ontoseno Penangsang

[email protected]

Page 29: Symmetrical Short Circuit-presentation

max

max

'

max

max'

"

max

max"

I

EX

I

EX

I

EX

d

d

d

NO LOAD GENERATORUNDER FAULT CONDITIONS

Emax : maximum line-neutral voltage of a Generator

Imax : maximum symmetrical short circuit current

Eg : rms line-neutral voltage of a Generator

I˝ : sub-transient current (rms, no DC component)

I΄ : transient current (rms, no DC component)

I : steady-state current ( rms)

d

g

d

g

d

g

X

EI

X

EI

X

EI

'

'

"

"

Ontoseno Penangsang

[email protected]

Page 30: Symmetrical Short Circuit-presentation

INTERNAL VOLTAGES OF LOADEDMACHINES UNDER FAULT CONDITIONS

Before a SC occurs After a SC occurs

After a SC occurs, sub-transient internal voltage ( E˝ ) OR transient internal

voltage ( E΄ ) is used

Generator : Eg˝ = Vt + j IL Xd˝

Eg΄ = Vt + j IL Xd΄

Motor : Em˝ = Vt – j IL Xd˝

Em΄ = Vt – j IL Xd΄ Ontoseno Penangsang

[email protected]

Page 31: Symmetrical Short Circuit-presentation

Example 1 :

(sub-transient internal voltage ( E˝ ) is used)

MOTOR, GENERATOR : 30.000 kVA, 13.2 kV, X˝= 20 %

LINE : X = 10 % (BASE : MACHINE RATING)

THE MOTOR IS DRAWING 20.000 kW, p.f. : 0.8 LEADING

MOTOR TERMINAL VOLTAGE : 12.8 kV WHWN A

SYMMETRICAL THREE PHASE FAULT OCCURS AT THE

MOTOR TERMINALS.

Ontoseno Penangsang

[email protected]

Page 32: Symmetrical Short Circuit-presentation

puj

pu

Axx

I

Ax

I

puV

kVkVABASE

L

BASE

f

52,069,0

9,3686,0

9,3611288,1238,0

000.20

13122,133

000.30

097,02,13

8,12

2,13 , 000.30:

Ontoseno Penangsang

[email protected]

Page 33: Symmetrical Short Circuit-presentation

Aj

pujj

jI

puj

jjjE

pujjjV

Generator

g

g

t

3550905

71,269,03,0

207,0814,0

207,0814,0

)52,069,0(2,0069,0918,0

069,0918,0)52,069,0(1,097,0

:

"

"

Aj

pujj

jI

pujjjE

puVV

Motor

m

m

ft

7050905

37,569,02,0

138,0074,1

138,0074,1)52,069,0(2,097,0

097,0

:

"

"

Aj

puj

III

LocationFaultAt

mgf

10600

08,8

:

"""

Ontoseno Penangsang

[email protected]

Page 34: Symmetrical Short Circuit-presentation

puV

pujjj

jjZ

f

th

097,0

12,02,03,0

)2.0)(3,0(

Example 2 :

(Thevenin’s theorem is used)

08,8

12.0

097.0

:

0"

puj

jI

LocationFaultAt

f

Ontoseno Penangsang

[email protected]

Page 35: Symmetrical Short Circuit-presentation

pujjj

jI g 23,308,8

5,0

2,0"

pujjj

jIm 85,408,8

5,0

3,0"

From Generator :

From Motor :

Ontoseno Penangsang

[email protected]

Page 36: Symmetrical Short Circuit-presentation

Example 1

IL≠0

Example 2

IL=0

Example 2

+ IL

Ig” 0,69-j2,71 pu -j3,23 pu 0,69-j2,71 pu

Im” 0,69-j5,37 pu -j4,85 pu 0,69-j5,37 pu

If” -j8,08 pu -j8,08 pu -j8,08 pu

Ontoseno Penangsang

[email protected]

Page 37: Symmetrical Short Circuit-presentation

Zbus METHOD

Single Line Diagram

Impedance Diagram

Vf: Prefault

Voltage at

Bus 2

Three Phase Short

Circuit occurs on bus 2.

Ontoseno Penangsang

[email protected]

Page 38: Symmetrical Short Circuit-presentation

Admittance Diagram

If” : Short Circuit current

Vf – Vf = 0

Short Circuit

occurs on Bus 2

I = Ybus . VOntoseno Penangsang

[email protected]

Page 39: Symmetrical Short Circuit-presentation

4

3

1

"

67,20 33,3 0,10 33,3

33,3 67,11 33,3 0,0

0,10 33,3 67,16 33,3

33,3 0,0 33,3 0,10

0

0

0

V

V

V

V

I ff

Ybus MatrixOntoseno Penangsang

[email protected]

Page 40: Symmetrical Short Circuit-presentation

I = Ybus . V

V = [Ybus]-1 . I

V = Zbus . I

Zbus = [Ybus]-1

Ontoseno Penangsang

[email protected]

Page 41: Symmetrical Short Circuit-presentation

0

0

0

"

44434241

34333231

24232221

14131211

4

3

1

ff I

zzzz

zzzz

zzzz

zzzz

V

V

V

V

V = Zbus . I

22

"

z

VI

f

f Short Circuit

current from

Bus 2

Ontoseno Penangsang

[email protected]

Page 42: Symmetrical Short Circuit-presentation

ff

ff

ff

Vz

zzIV

Vz

zzIV

Vz

zzIV

22

4242

"

4

22

3232

"

3

22

1212

"

1

42

"

44

32

"

33

2

12

"

11

0

zIVVVV

zIVVVV

VVV

zIVVVV

fff

fff

ff

fff

The changes of voltages

at Bus 1, 3 and 4

(Total) Voltage at

each bus.

Ontoseno Penangsang

[email protected]

Page 43: Symmetrical Short Circuit-presentation

kk

f

fz

VI

f

kk

nkfn V

z

zVV

Vf is assumed

(prefault current is neglected)

Three Phase Short Circuit

occurs on Bus k

Short Circuit

current from

Bus k

Voltage on

Bus n

pu00,1

Ontoseno Penangsang

[email protected]

Page 44: Symmetrical Short Circuit-presentation

1155,0 0602,0 0953,0 0702,0

0602,0 1226,0 0692,0 0431,0

0953,0 0692,0 1471,0 0807,0

0702,0 0431,0 0807,0 1502,0

jZbus

Three Phase Short Circuit

occurs on bus 2

Calculate Short

Circuit Current

flowing in each line

and from Generator

Example 3 :

Vf: Prefault

Voltage at

Bus 2

Impedance

Diagram

Ontoseno Penangsang

[email protected]

Page 45: Symmetrical Short Circuit-presentation

THE SELECTION OF CIRCUIT BREAKERS

The electric utility company

furnishes data to a customer who

must determine the fault current in

order to specify circuit breakers

properly for an industrial plant or

industrial power distribution system

connected to the utility system at a

certain point.

Ontoseno Penangsang

[email protected]

Page 46: Symmetrical Short Circuit-presentation

c

b

a

If

0

Time

In the short circuit calculation, we calculate the subtransient

current called the initial symmetrical current, which does not

include the component.

Ontoseno Penangsang

[email protected]

Page 47: Symmetrical Short Circuit-presentation

Devices

Types of

Short Circuit

current

Reactance used for SC calcMultplying

Factor

Synchr.

Generator

Synchr.

Motor

Induction

Motor

none

Molded

Case CB

Symmetrical

Ampere

Sub-

transient

(X”)

Sub-

transient

(X”)

Sub-

transient

(X”)

CB diatas

600 volt

8 cycles

Symmetrical

Interrupting

Ampere

Sub-

transient

(X”)

Transient

(X)neglected

Genera

l Case

Special

Case

1.0 1.1*)

Asymmetrical

Momentary

Ampere

Sub-

transient

(X”)

Sub-

transient

(X”)

Sub-

transient

(X”)

1.6 1.5**)

Fuse diatas

1500 volt

Asymmetrical

Interrupting

Ampere

Sub-

transient

(X”)

Sub-

transient

(X”)

Sub-

transient

(X”)

1.6 1.2***)

Multiplying Factor (standar ANSI/IEEE C37.5-1953)

Page 48: Symmetrical Short Circuit-presentation

WHERE :

Vpf : VOLTAGE (L-L) BEFORE THE SHORT CIRCUIT

OCCURS (VOLT)

I˝ : RMS VALUE OF THE INITIAL SYMMETRICAL

SHORT CIRCUIT CURRENT (AMPERE)

ξ : MULTIPLYING FACTOR

THE RATING OF CIRCUIT BREAKERS

I˝. ξ .10-3 kA

√3 Vpf . I˝ . ξ . 10-6 MVA

Ontoseno Penangsang

[email protected]