switch & fusegear - voltimum · pdf fileswitch & fusegear 31 bill means business nf...
TRANSCRIPT
Switch & Fusegear
31
BILL MEANS BUSINESS� NF Distribution Fuseboards SPN & TPN
� Sovereign Surface Mounted Fuse-Switches
� Cable and Reverse Entry Boxes
� Masterlink Switch-Disconnectors & Switch-Disconnector-Fuses
� Insulated Switch - Disconnectors
� Changeover Switches
� Fireman’s Switches
� Street Lighting Cut-outs
� Busbar Chambers 100A to 800A
� Fused Combination Switches
� Form 4 LV Switchboards
� Talisman MPS
26905 Bill Cat intro pages 22/1/02 12:33 pm Page 3
NF Distribution FuseboardsSPN & TPN 20A to 200A
432
DIRECT SALES 0121 685 2004
1
FEATURES� Removable end plates offer
ingress protection to IP4X
� NF Fuseboard ratings are:SPN: 20A, 32ATPN: 20A, 32A, 63A, 100Aand 200A
� Robust construction
� Safety Carriers
� Lid locking 20A - 100A(cylinder type) Cat.No. NFLK1
� Lid locking 200A (brackettype) Cat.No. DLK4 andPadlock Cat. No. PL1250
� Double Pole Fuseboards canbe manufactured to order
� Reversible access doors
� Extended outgoing waysoption on 20A and 32A unitsup to 24 TPN ways
The NF Fully Shrouded Distribution Fuseboard range is suitable for systems with a ratedinsulation voltage up to 660V AC/500V DC and is available in a sheet steel enclosure.
The range complies with BS5486: Part 11 1989.
The 20A and 32A NF units have removable end plates incorporating conduit knockouts.Blank end plates can be supplied on request.
The 63A, 100A and 200A units have blank removable end plates.
All ratings accept HRC bolt-in fuselinks to BS88: Part 2 which should be selected from page 68.
NF FUSEBOARDS 20A-200A
CURRENT NO. SUITABLE SPARE DIMENSIONS** NFRATING & OF BILL HRC FUSE (MM) FUSEBOARD
POLES WAYS FUSELINKS CARRIER H W D CAT. NO.4 BNIT 94CARRIER 386 304 148 NFS204NLC
20A 6 BNIT 94CARRIER 386 304 148 NFS206NLCSPN 8 BNIT 94CARRIER 386 368 148 NFS208NLC
12 BNIT 94CARRIER 386 448 148 NFS2012NLC4 BNIT 94CARRIER 631 304 148 NFT204NLC
20A 6 BNIT 94CARRIER 631 304 148 NFT206NLCTPN 8 BNIT 94CARRIER 631 368 148 NFT208NLC
12 BNIT 94CARRIER 631 448 148 NFT2012NLC4 BTIA 95CARRIER 386 304 148 NFS304NLC
32A 6 BTIA 95CARRIER 386 304 148 NFS306NLCSPN 8 BTIA 95CARRIER 386 368 148 NFS308NLC
12 BTIA 95CARRIER 386 496 148 NFS3012NLC2 BTIA 95 CARRIER 386 368 148 NFT302NLC4 BTIA 95CARRIER 710 304 148 NFT304NLC
32A 6 BTIA 95CARRIER 710 304 148 NFT306NLC
TPN 8 BTIA 95CARRIER 710 368 148 NFT308NLC10 BTIA 95CARRIER 710 448 148 NFT3010NLC12 BTIA 95CARRIER 710 496 148 NFT3012NLC2 BTIS 96CARRIER 546 473 227 NFT602NLC
63A4 BTIS 96CARRIER 972 330 227 NFT604NLC
TPN6 BTIS 96CARRIER 972 330 227 NFT606NLC8 BTIS 96CARRIER 972 473 227 NFT608NLC10 BTIS 96CARRIER 972 473 227 NFT6010NLC2 BTCP* 97CARRIER* 546 549 227 NFT1002NLC3 BTCP* 97CARRIER* 1066 330 227 NFT1003NLC
100A4 BTCP* 97CARRIER* 1066 330 227 NFT1004NLCTPN6 BTCP* 97CARRIER* 1066 549 227 NFT1006NLC8 BTCP* 97CARRIER* 1066 549 227 NFT1008NLC2 BTF 98 CARRIER 1560 410 270 NFT2002NLC3 BTF 98 CARRIER 1560 410 270 NFT2003NLC200A4 BTF 98CARRIER 1560 529 270 NFT2004NLCTPN6 BTF 98CARRIER 1560 529 270 NFT2006NLC
For terminal capacities see page 33.
*BTIA (2A - 32A)
BTIS (40A - 63A)
Fuselinks can be fitted by use of adaptor kit Cat.No. NF100LK
**For detailed dimensions see page 34.
SAFETY CARRIERS
FUSEBOARD SAFETY CARRIERCURRENT RATING CARRIER
20A 101CARRIER
32A 102CARRIER
63A 103CARRIER
100A 104CARRIER
200A 105CARRIER
*26905 Bill Cat Sec.3 28/1/02 3:32 pm Page 1
SPN & TPN 20A to 200A
DIRECT SALES 0121 685 2004
33
Aper ture
320mm
35mm
12mm
50mm
EXTENDED OUTGOINGCIRCUITS20A and 32A boards can be mounted sideby side to extend outgoing circuits to 24way maximum.
Additional shrouds (one per phase) arerequired when using looping facility,Cat.No. NF32CS.
All phase looping connections must passthrough the same aperture.
Apertures should be dri l led in the positions shown.
DIVERSITY FACTORS
NO. OF MAXIMUM RATED CURRENT PER WAY
WAYS 200A 100A 63A 32A 20A
2 1.0 1.0 1.0 1.0 1.0
3 0.9 1.0 – – –
4 0.8 0.9 0.9 0.9 0.9
6 0.66 0.8 0.8 0.8 0.8
8 – 0.66 0.8 0.8 0.8
10 – – 0.66 0.66 0.66
12 – – – 0.66 0.66THEREFORE, INCOMER RATING =
2 400A 200A 126A 64A 40A
3 540A 300A – – –
4 640A 360A 227A 115A 72A
6 800A 480A 302A 154A 96A
8 – 528A 403A 205A 128A
10 – – 416A 211A 133A
12 – – – 253A 160A
TERMINAL/CABLE CAPACITIES
CURRENT MAIN EARTH BAR MAX. TERMINAL OUTGOINGRATING NO. TERMINAL CAPACITY MM2 TERMINAL
NF OF STUD MAIN (COPPER CABLES) BOREPOLES WAYS CAT. NO. SIZE STUD OUTGOING MAIN OUTGOING DIA. MM
4 NFS204NLC 9520A SPN
6 NFS206NLCM10 M10 10mm2 6 4
8 NFS208NLC12 NFS2012NLC
120
4 NFT204NLC95
20A TPN6 NFT206NLC
M10 M10 10mm2 6 48 NFT208NLC12 NFT2012NLC
120
4 NFS304NLC956 NFS306NLC
32A SPN8 NFS308NLC
M10 M10 10mm2 16 5.5
12 NFS3012NLC150
2 NFT302NLC * 354 NFT304NLC6 NFT306NLC
9532A TPN8 NFT308NLC
M10 M10 10mm2 16 5.5
10 NFT3010NLC 15012 NFT3012NLC2 NFT602NLC4 NFT604NLC M12 240
63A TPN 6 NFT606NLC M10 25mm2 35 88 NFT608NLC
M16 50010 NFT6010NLC2 NFT1002NLC3 NFT1003NLC M12 240
100A TPN 4 NFT1004NLC M10 25mm2 70 126 NFT1006NLC
M16 500**†
8 NFT1008NLC2 NFT2002NLC3 NFT2003NLC
200A TPN4 NFT2004NLC
M16 M19 70mm2 630**† 150 18
6 NFT2006NLC
* Tunnel terminal 35mm2 maximum.
** Cast cable socket, 1 hole fixing, suitable for 630mm2 stranded copper conductors availableseparately to order Cat. No. NF630SK.
† Can be adapted to allow fitment of 2–240mm2 maximum cable sockets with suitable copperspacing piece. (set of 4) Cat. No. NF240SP.
Adaptor clips (set of 2) enables the fitment of house service ferrule cap fuselinks to BS 1361
Type IIa (60A) NF63CL for 63A fuse carriers
Type IIb (100A) NF100CL for 100A fuse carriers
}}
}
}}
}
}
}
}
}
}}}
}}}
}
}
}
}
(8mmdia)
*Bill amended pages 28/1/02 3:43 pm Page 7
434
DIRECT SALES 0121 685 2004
NF FUSEBOARD
APPROX.CURRENT NUMBER WEIGHT
RATING POLES OF WAYS A B C D CRS E CRS F DIA KG2 368 255 8.54 304 191 3.2
20A SPN 6 386 304 148 252 191 8 7.58 368 255 9.512 448 335 11.04 304 191 13.4
20A TPN6
631304
148 442191
814.4
8 368 255 17.412 448 335 20.94 304 191 7.56 304 191 7.6
32A SPN8
386368
148 252255
88.5
12 496 383 11.54 304 191 13.76 304 191 14.2
32A TPN 8 710 368 148 576 255 8 18.710 448 335 22.212 496 383 24.22 546 473 458 369 21.94 330 226 26.0
63A TPN 6 972 330 227 884 226 10 31.08 473 369 41.010 473 369 44.02 546 549 458 445 28.93 330 226 34.8
100A TPN 41066
330227 978
22610
38.86 549 445 55.88 549 445 62.8
200A TPN
2 410 206 78.03 410 206 91.04
1560529
270 1334325
10107.0
6 529 325 123.0
4 off F dia. fixing holes
A
B C
D
E
NF Distribution FuseboardsDimensions (mm)
4 off F dia. fixing holes
*26905 Bill Cat Sec.3 28/1/02 3:32 pm Page 3
Sovereign Surface Mounted Fuse-Switches
DIRECT SALES 0121 685 2004
35
FEATURES � Robust steel enclosures to IP31
� Unique Pozi-slot design
� Versatile performance
� Positive contact indicator
� Lid locking
� Easy busbar connection
RANGE� Single Pole & Neutral
� Double Pole
� Triple Pole & Neutral
� Triple Pole & Switched Neutral
� All are supplied with 415V fuselinks to maximum rating
� Handle locking: 63A Padlock Cat.No. PL1250100 - 800A Padlock Cat.No. PL1251
� Figure locks can be factory fitted to 200 - 800A units
� An auxiliary switch can be fitted to 100 - 800A ratings
NOMINAL BS88 SINGLE POLE DOUBLE POLE TRIPLE POLE TRIPLE POLERATING FUSE LINK PHASE LINK & NEUTRAL & NEUTRAL & SW/NEU.
AMP REF. CAT. NO. CAT. NO. CAT. NO. CAT. NO. CAT. NO.63A A2 - A3 L60 SMM601N SMM602 SMM603N -100A B1 L100 SMM1001N SMM1002 SMM1003N SMM1003SN160A B1-B2 L160 SMM1601N SMM1602 SMM1603N SMM1603SN200A B1-B2 L200 SMM2001N SMM2002 SMM2003N SMM2003SN315A B1-B2 L300 - - SMM3003N SMM3003SN400A B3-B4 L400 - - SMM4003N SMM4003SN630A C1-C2 L600 - - SMM6003N SMM6003SN800A C1-C2-C3 L800 - - SMM8003N SMM8003SN
Add suffix LC for units without fuselinks fitted e.g. SMM2003NLC
63A to 800A, SPN, TPN and TPSN
*26905 Bill Cat Sec.3 28/1/02 3:32 pm Page 4
SovereignSurface Mounted Fuse-Switches
436
DIRECT SALES 0121 685 2004
FUSE-SWITCH, SWITCH AND ISOLATOR RATINGS TO BS 5419, IEC 408
NOMINAL RATING 63A 100A 160A 200A 315A 400A 630A 800ARated thermal current- fused amps 63 100 160 200 315 400 630 800- copper links amps 100 160 160 315 450 630 800 1000Rated operational voltage volts 550 550 415 550 550 550 550 550Rated Insulation voltage volts 660 660 660 660 660 660 660 660Rated frequency Hz 40-60 40-60 40-60 40-60 40-60 40-60 40-60 40-60Rated fuse short circuitcurrent at 550V* kA 63 63 63* 63 63 63 63 63Rated operational currentat 500V AC21* amps 100 160 160* 315 450 630 800 1000at 550V AC22* amps 63 100 160* 200 315 400 630 800at 415V AC23 amps 40 83 83 136 263 263 385 505
kW 22 45 45 75 150 150 225 300Approx. HP 30 60 60 100 200 200 300 400Fuse link BS88 form A2,A3 B1 - B1,B2 B1,B2 B1,B2 C1,C2 C1,C2
B3 B3,B4 C3Termination stud size M6 M8 M8 M10 M16 M16 M20 M20
*Rated fused short circuit current and rated operational current AC21, AC22 for 160 amp units are at 415 volts only.
SUITABLE HRC FUSELINKS
FUSE-SWITCH FORM SUITABLE BILLRATING - A BS 88 HRC FUSELINK AMPS
BTIA2 2BTIA4 4BTIA6 6
A2 offset tag BTIA10 102 hole fixing BTIA16 16
BTIA20 20BTIA25 25BTIA32 32
A3 BTIS40 40offset tag BTIS50 50
2 hole fixing BTIS63 63
100B1 BTC80 80
central tagBTC100 1002 hole fixing
B1-B2 BTC80 80
160 central tag BTC100 1002 hole fixing BTF125 125
BTF160 160
SUITABLE HRC FUSELINKSFUSE-SWITCH FORM SUITABLE BILL
RATING - A BS 88 HRC FUSELINK AMPSB1 BTC80 80
central tag BTC100 100200 2 hole fixing BTF125 125
B2 central tag BTF160 1602 hole fixing BTF200 200
B2 BTF125 125central tag BTF160 160
315 2 hole fixing BTF200 200B3 central tag BTKF250 2502 hole fixing BTKF315 315
B3 central tag BTKF250 250400 2 hole fixing BTKF315 315
B4 central tag BTMF355 3552 hole fixing BTMF400 400
C1 central tag BTM355 3554 hole fixing BTM400 400
630 BTTM450 450C2 central tagBTTM500 5004 hole fixingBTTM630 630
C1 central tagBTM355 355
4 hole fixingBTM400 400
BTTM450 450800 C2 central tag BTTM500 500
4 hole fixing BTTM630 630C3 central tag BTLM710 7104 hole fixing BTLM800 800
63A TO 800A, SPN, TPN AND TPSN
63
*26905 Bill Cat Sec.3 28/1/02 3:32 pm Page 5
Dimensions (mm)
DIRECT SALES 0121 685 2004
37
D
E
A
C
152
Type ‘A’
B
Fixing holes to take ‘G’ diameter bolts
H
F
‘H’ dimension applies whenarm is fully extended
C
B“ “
A
E
D
Type ‘B’
10mm
SOVEREIGN SURFACE MOUNTED FUSE-SWITCH DIMENSIONS (MM)
AMPS CAT. NO. POLES DESIGN TYPE A B C D E F G H.SMM601N SPN63SMM602 DP
SMM603N TPN‘A’ 163 140 336 196 86 180 M6 243
SMM1001N SPN100 SMM1002 DP
SMM1003N TPN‘A’ 150 190 356 262 101 210 M6 305
SMM1003SN TPSNSMM1601N SPN
160 SMM1602 DPSMM1603N TPN ‘A’ 150 190 356 262 101 210 M6 305
SMM1603SN TPSNSMM2001N SPN
200 SMM2002 DPSMM2003N TPN
‘B’ 266 226 348 340 41 252 M8 402
SMM2003SN TPSN
315SMM3003N TPN
SMM3003SN TPSN‘B’ 343 286 425 400 41 252 M8 402
400SMM4003N TPN
SMM4003SN TPSN
630SMM6003N TPN
SMM6003SN TPSN‘B’ 481 410 563 530 41 362 M10 612
800SMM8003N TPN
SMM8003SN TPSN
*26905 Bill Cat Sec.3 28/1/02 3:32 pm Page 6
SovereignAccessories
438
DIRECT SALES 0121 685 2004
Cable Entry Boxes
Cable sizes shown are copper cable sizes.It must be appreciated that many cablingvariations can be applied.
Enquiries for specific cable arrangementsare invited.
Cable Entry Box Assembly Kit
Comprises: front and rear panels, two sidepanels, fixing screws & instructions forassembly with existing top cover of theSMM fuse-switch are included. Cable boxesare only suitable for use with appropriateSovereign fuse-switches.
Reverse Entry Cable Boxes
200A and above reverse entry boxes aresupplied complete with the required numberof copper extension pieces.
A
CB
AD
B
C
CABLE AND REVERSE ENTRY BOXES
CABLE ENTRY BOXES
SHORT CABLE BOX LONG CABLE BOXAMPS TYPE OF SWITCH CAT.NO. CAT.NO.
SPN SMB63L63 DP will admit 4 core cables
TPN up to 50mm2
SPN Asymmetrical BoxSMB100L
100DP will admit cables up to will admit 4 core cables
TPN 35mm2 on one up to 95mm2sTPSN end onlySPN SMB100LDP will admit 4 core cables160
TPN up to 95mm2
TPSNSPN SMB200 SMB200L
200 DP will admit 4 core cables will admit 4 core cablesTPN up to 95mm2 up to 150mm2
TPSNSMB300 SMB300L
315TP/TPN
will admit 4 core cables will admit 4 core cablesTPSN
up to 240mm2 up to 300mm2
SMB600630 will admit 1, 4 core cable
TP/TPN up to 400mm2
TPSN +SMB600E800 will admit 2 x 4 core cables
up to 300mm2
SHORT AND LONG CABLE ENTRY BOXES - DIMENSIONS (MM)
Cat. No. SMB63L SMB100L SMB200 SMB200L SMB300 SMB300L SMB600A 98 98 120 183 237 287 286B 180 210 252 252 252 252 362C 196 262 340 340 400 400 530
REVERSE ENTRY CABLE ENTRY BOXES - DIMENSIONS (MM)
SIZE OF SWITCH TYPE OF CATALOGUEAMPS SWITCH NUMBER A B C D
SPN63 DP SRB603 98 108 – –
TPNSPN
100DP
SRB1004 102 171 36 226TPNTPSNSPN
160 TPN SRB1004 102 171 36 226TPSNSPNDP200
TPNSRB2004 122 205 36 370
TPSN
315 TPN SRB3004TPSN 122 205 36 370
400 TPN SRB4004TPSN
630 TPN SRB6004TPSN 200 389 36 490
800 TPN SRB8004TPSN
*26905 Bill Cat Sec.3 28/1/02 3:32 pm Page 7
MasterlinkSwitch-Disconnectors & Switch-Disconnector-Fuses
DIRECT SALES 0121 685 2004
39
20A TO 125A
FEATURES� Robust sheet steel enclosures to IP41
� Removable shields over fixed contacts
� Removable moving contact assemblies
� Removable end plates with threeconduit knockouts (blank end platesavailable on request)
� Easy busbar connection
� Can be factory fitted to the NF rangeof fuseboards complete with internal wiring
The 415V Masterlink range is of the quickmake, quick break type, suitable for useon AC or DC applications.
Masterlink Switch-Disconnectors areavailable as follows:
DP: 20A, 32A, 63A, 100A, TPN: 20A, 32A, 63A, 100A, 125A
Masterlink Switch-Disconnector-Fuses areavailable as follows:
SPSN: 20A, 32A, 63A, 100A, DP: 20A, 32A, 63A, 100A, TPN: 20A, 32A, 63A, 100A, 125A
The range has been type tested inaccordance with BS EN 60947-3
Masterlink Switch-Disconnector-Fuses aresupplied with 415V fuses fitted to maximumrating (unless otherwise stated). Units aredesigned for use with offset contact HRCfuselinks to BS88: Part 2.
NOMINAL UTILISATION CATEGORY 250V DC DIMENSIONS* DOUBLE POLERATING AT UE 415V TO RATING TO (MM) SWITCH-DISCONNECTOR
IE BS EN 60947-3 BS 5419 CAT. NO
AC-22A H W D**20A 20A 20A DC22 159 193 127 ML15232A 32A 32A DC23 173 245 137 ML30263A 63A 63A DC23 230 310 173 ML602100A 100A 100A DC23 329 367 210 ML1002
NOMINAL UTILISATION CATEGORY 250V DC DIMENSIONS* TRIPLE POLE & NEUTRALRATING AT UE 415V TO RATING TO (MM) SWITCH-DISCONNECTOR
IE BS EN 60947-3 BS 5419 CAT. NO.AC-22A AC-23A H W D**
20A 20A 11A – 159 193 127 ML153N32A 32A 22A – 173 245 137 ML303N63A 63A 39A – 230 310 173 ML603N100A 100A 52A – 329 367 210 ML1003N125A 125A 52A – 329 367 210 ML1253N
NOMINAL UTILISATION 250V DC SUITABLE DIMENSIONS* SINGLE POLERATING CATEGORY AT RATING TO REPLACEMENT (MM) & NETURAL
IE UE 415V BS BS 5419 BILL HRC SWITCH -EN 60947-3 415V FUSELINKS DISCONNECTOR
FUSESAC-22A H W D** CAT.NO.
20A 20A 20A DC22 BNIT 219 193 127 EMLF151N32A 32A 32A DC23 BTIA 267 245 137 EMLF301N63A 63A 63A DC23 BTIS 351 310 173 EMLF601N100A 100A 100A DC23 BTCP/BTIS/BTIA 503 367 210 EMLF1001N
NOMINAL UTILISATION 250V DC SUITABLE DIMENSIONS* TRIPLE POLERATING CATEGORYAT RATING TO REPLACEMENT (MM) & NETURAL
IE UE 415V BS BS 5419 BILL HRC SWITCH -EN 60947-3 415V FUSELINKS DISCONNECTOR
FUSESAC-22A AC-23A H W D** CAT.NO.
20A 20A 11A – BNIT 219 193 127 EMLF153N32A 32A 22A – BTIA 267 245 137 EMLF303N63A 63A 39A – BTIS 351 310 173 EMLF603N100A 100A 52A – BTCP/BTIS/BTIA 503 367 210 EMLF1003N
125A 125A 52A – BTFP/BTCP/ 503 367 210 EMLF1253NBTIS/BTIA
*For detailed dimensions see page 41. For terminal cable capacities see page 40. **Depth dimension includes operating handle.
NOMINAL UTILISATION 250V DC SUITABLE DIMENSIONS* DOUBLE POLERATING CATEGORY AT RATING TO REPLACEMENT (MM) SWITCH -
IE UE 415V BS BS 5419 BILL HRC DISCONNECTOREN 60947-3 415V FUSELINKS FUSES
AC-22A H W D** CAT.NO.20A 20A 20A DC22 BNIT 219 193 127 EMLF15232A 32A 32A DC23 BTIA 267 245 137 EMLF30263A 63A 63A DC23 BTIS 351 310 173 EMLF602100A 100A 100A DC23 BTCP/BTIS/BTIA 503 367 210 EMLF1002
*26905 Bill Cat Sec.3 28/1/02 3:32 pm Page 8
MasterlinkSwitch Disconnectors & Switch Disconnector-Fuses
440
DIRECT SALES 0121 685 2004
PERFORMANCE VALUES
UNIT SHORT TIME SHORT CIRCUIT RATED CONDITIONALWITHSTAND CURRENT MAKING CAPACITY SHORT CIRCUIT CURRENT
(R.M.S. AMPS FOR (PEAK AMPS AT (PROSPECTIVE R.M.S.1 SECOND) ICW 415V AC) ICM AMPS AT 415V AC FUSED)
20A 640A 2.96kA 80kA32A 960A 5.12kA 80kA63A 2000A 6.62kA 80kA100A 3750A 8.42kA 80kA125A 3750A 8.42kA 80kA
Masterlink Fuseboard Isolators
Masterlink 63A, 100A or 125A switch-disconnectors or switch-disconnector-fuses can becombined with the NF range of distribution fuseboards. 20A and 32A boards can be supplied tospecial order, with a Masterlink isolator, complete with internal mains cabling.
CABLE CAPACITIES
MASTERLINK MAXIMUM COPPERSWITCH-DISCONNECTORS & CABLE SIZES
SWITCH-DISCONNECTOR-FUSES20A 6mm2
32A 10mm2
63A 35mm2
100A 70mm2
125A 70mm2
BLANK END PLATES
MASTERLINK BLANK END PLATESWITCH-DISCONNECTORS & CAT. NO.
SWITCH-DISCONNECTOR-FUSES20A BEP84232A BEP84263A BEP539100A BEP539125A BEP539
SPARE FUSE CARRIERS
MASTERLINK HRC FUSE CARRIERSWITCH-DISCONNECTOR-FUSES CAT. NO.
20A 77CARRIER32A 78CARRIER63A 79CARRIER100A 80CARRIER125A 108CARRIER
*26905 Bill Cat Sec.3 28/1/02 3:32 pm Page 9
Dimensions (mm)
DIRECT SALES 0121 685 2004
41
SWITCH-DISCONNECTORS & SWITCH-DISCONNECTOR-FUSES 20A TO 125A
RATING A* B C D E F G H J KSWITCH-DISCONNECTORS20A 159 193 92 127 112 114 onCL 5.6 38.5 3432A 173 245 101 137 116 114 114 6.4 38.5 3463A 230 310 129 173 152 168 168 6.7 58 54100A/125A 329 367 167 210 241 221 221 6.7 58 54SWITCH-DISCONNECTOR-FUSES20A 219 193 92 127 171 114 onCL 5.6 38.5 3432A 267 245 101 137 209 114 114 6.4 38.5 3463A 351 310 129 173 273 168 168 6.7 58 54100A/125A 503 367 167 210 416 221 221 6.7 58 54
* Not including removable endplates and fixing screws.
Conduit knockouts top and bottom
2–20mm20 and 32A1–25mm central
1–25mm63 and 100A/125A 1–32mm
1–40mm central
F
B
C
D
PadlockHole
H dia. fixing holes
G
* Not including removable endplatesand fixing screws
E
K
*ACL
J J
*26905 Bill Cat Sec.3 28/1/02 3:32 pm Page 10
LS Insulated Switch-Disconnectors
442
DIRECT SALES 0121 685 2004
TRIPLE POLE & NEUTRAL SWITCH-DISCONNECTORS 20A – 63A
UTILISATION CATEGORY ATRATED UE 415V (3 PHASE) DIMENSIONS* ACCESSORIES TRIPLE POLE & NEUTRAL
THERMAL TO BS EN 60947-3 (MM) SWITCHED AUXILIARY SWITCH-DISCONNECTORCURRENT AC-21A NEUTRAL CONTACT TO IP65
ITH AC-22A AC-23A H W D* POLE POLE CAT. NO.20A 20A 11A 100 80 106 – – LS203N25A 25A 14A 160 100 135 LSN25-32 LSA25-63 LS253N32A 32A 28A 160 100 135 LSN25-32 LSA25-63 LS323N63A 63A 55A 240 160 160 LSN63 LSA25-63 LS633N100A 100A 69A 280 200 160 LSN63 LSA25-63 LS1003N
*Depth dimension includes operating handle.
SHORT CIRCUIT PROTECTION
UNIT MAX. BS 88 FUSE RATEDCAT. NO. FOR SHORT CIRCUIT SHORT TIME
WITHSTAND100KA * * FOR 1 SEC.
LS203N 20A 20A 240ALS253N 25A 25A 640ALS323N 50A 32A 640ALS633N 80A 80A 1260ALS1003N 100A 100A 2000A
**6kA without contact welding (contacts closed).
OTHER RATINGS
RATED AC-23A AC-15* AC-15* AC-15* DC-21A DC-1 DC-3THERMAL 240V 240V 415V 500V 240V 30V DC-5CURRENT 1 PHASE 1 PHASE 1 PHASE 1 PHASE 24V
20A 11A 6A 4A 2A 1A 10A 10A25A 14A 6A 4A 2A – 25A 25A32A 28A 6A 4A 2A – 32A 25A63A 55A 6A 4A 2A – 63A 50A100A 69A 6A 4A 2A – 100A 50A
*Main Pole of LS253N. Auxiliary contact of LS253N – LS633N.
TERMINAL CAPACITY – COPPER RIGID CONDUCTORS Note: Flexible conductors one size smaller
LS UNITRATED THERMAL MAXIMUM MINIMUM
CURRENT PHASE NEUTRAL AUXILIARY PHASE/N AUXILIARY20A 2 x 2.5mm2 2 x 2.5mm2 – 1.0mm2 –25A 2 x 6mm2 1 x 6mm2 2.5mm2 1.5mm2 0.75mm2
32A 2 x 6mm2 1 x 6mm2 2.5mm2 1.5mm2 0.75mm2
63A 1 x 35mm2 1 x 25mm2 2.5mm2 2.5mm2 0.75mm2
100A 1 x 35mm2 1 x 25mm2 2.5mm2 2.5mm2 0.75mm2
FEATURES� Units are intended for on-load switching of general
purpose loads and for motor isolation.
� IP65 rating
� Enclosures are rugged thermoplastic.
� Complies with BS EN 60947-3
� Padlocking handles as standard providing lock offfacilities for up to three padlocks, Cat.No. PL1250
� Excellent AC-23 ratings
� Add on switched neutral poles (available asaccessories)
� Separate earth terminal
� Minimum maintenance
*26905 Bill Cat Sec.3 28/1/02 3:32 pm Page 11
RadetteTP, 16A Switch-Disconnector Fuses
DIRECT SALES 0121 685 2004
43
16A TRIPLE POLE TP
NOMINAL SPARE FUSE SUITABLE APPROX. DIMENSIONS TRIPLE POLE (415V) TRIPLE POLE (415V)RATING CARRIER REPLACEMENT WEIGHT (MM) SWITCH- SWITCH-
IE CAT. NO. BILL HRC KG DISCONNECTOR DISCONNECTOR-FUSEFUSELINKS H W* D CAT. NO. CAT. NO.
16A 68 CARRIER BNIT 1.9 177 162 73 QX1426 EQX1438*Width dimension includes operating handle. Site fittable Neutral Terminal Cat. No, NL21; Padlock Cat. No. PL1250.NOTE: EQX1438 previously rated at 10A to BS 5419.
Switch contacts are of the quick make, quick break type.
Standards
The Radette range complieswith BS EN 60947-3.
Utilisation Category
16A TP Switch-Disconnector-Fuses.AC-21A, AC-22A, Ue 415V.Rated Insulation Voltage = 660V.Short Time Withstand = 200A r.m.s. for 1 second.
Operational Performance
In accordance with BS EN 60947-3, all units have beentested in excess of the values stated: Operating cycleswithout current 8500. Operating cycles at rated current 1500 Total = 10000.
3
0.8
3.5
9
31
62
0.5
3
9
08
ocking Slot
H. ide or 0mm onduit.
ar h e minal
ixing Holes.4 Dia.
*26905 Bill Cat Sec.3 28/1/02 3:32 pm Page 12
ConsulOn-load Changeover Switches
444
DIRECT SALES 0121 685 2004
RANGE� Surface mounted, 4 pole
on-load changeover switches.
� Suitable for on-load control of alternative supplies.
� 415V. Higher voltage ratings available, details on request.
FEATURES� Switches comply with BSEN60947-3.
� Double break blade & clip wiping action contact system ensures reduced contact bounce.
� Operator independent spring assisted mechanism ensures a positive and consistent switchingaction reducing arcing and contact wear.
� 32 - 200A units are provided with cable lugs and 400 - 800A with solid links suitable for use oneither side of the switch. Ample cable space is provided for both incoming and outgoing cables.
� Each unit is provided with an IP54 black handle and steel operating shaft.
� All handles are insulated and may be padlocked in the 'OFF' position.
� Clear 'ON' (I) and 'OFF' (O) indication is provided.
� Door interlocking is provided by the handle in the 'ON' position.
� Enclosures are finished in Bill light grey RAL 7032.
*Bill amended pages 28/1/02 3:43 pm Page 8
On-load Changeover Switches
DIRECT SALES 0121 685 2004
45
1. Polycarbonate inter-phase shields.
2. Fixed contacts.
3. 63-800A terminations are provided for easy attachment of cable lugs or solid copper connections.
4. Polycarbonate snap-fastening connection barriers.
5. Manually independent over centre spring switching mechanism.
6. Contact system provides four breaks in series per phase.
7. Moving contacts.
8. Fully interlocked rotary action operating handle. Interlock may be overridden by a competent operator for inspection and maintenance purposes.
9. Positive contact indicator shows contact position with door open.
NOMINAL A B C D WEIGHT LIST NO.RATING. IE (MM) (MM) (MM) (MM) KG
32A 320 372 170 225 9.6 304 COS63A 320 372 170 225 10.0 604 COS100A 370 372 170 225 10.6 1004 COS200A 474 460 320 375 25 2004 COS400A 800 550 245 300 46.4 4004 COS630A 800 650 245 300 47.0 6304 COS800A 800 650 245 300 51.0 8004 COS
Note: Dimensions C & D measured from bottom of foot detail.
1 2 3 4 5
9876
*26905 Bill Cat Sec.3 28/1/02 3:33 pm Page 14
Fireman’sSwitch-Disconnectors 20A, DP, 240V
446
DIRECT SALES 0121 685 2004
FIREMAN’S SWITCH-DISCONNECTORS
HOLES HOLES IP55TAPPED TAPPED DIMENSIONS FIREMANS’ SWITCH-
NOMINAL (MM) (MM) (MM) DISCONNECTORRATING TOP BOTTOM H W* D CAT. NO.20A DP 1 x 20 1 x 20 139.7 135 71.5 N15
32A TPN 1 x 25 1 x 25 173 216.8 83.6 N303N
FLUSH MOUNTING FIREMAN’S SWITCH-DISCONNECTORS
FLUSH MOUNTINGDIMENSIONS DOUBLE POLE FIREMAN’S
NOMINAL (MM) SWITCH-DISCONNECTORRATING H W D CAT. NO
20A 178 165 76 N202F
* Width dimension includes operating handle.
DIMENSIONS (MM)
Rating Cat. No. A B C D E F G H J K L20A N15 135 116.7 109.5 123.8 116.7 139.7 127 63.5 71.5 23.8 2032A N303N 216.8 198.3 138 205.4 145.3 173 158.7 140 83.6 24.6 25
FEATURES� Units are ‘quick make, quick break’ type.
� DP: 20A, AC22A at Ue 240V.
� TPN: 32A, AC22A at Ue 415V .
� All units comply with BS EN 60947-3.
� Surface mounted units in high grade cast iron enclosures to IP55
� Flush mounting units (available in 20A, 240V versions only) have cast aluminium bodies with rust protected sheet steel front plates.
� Pole operated ring handle, which automatically locks in OFF position
F G E
D
H6mm dia. Fixing Holes
J
C
CaTaTh
CL
A
B
K
Cable Entry HolesTapped Lmm ConduitThread (Top and Bottom)
CL
165mm
140mm
86mm
124mm
132mm
73mm
178m
m
152m
m
98m
m
136m
m
5mm G dia.Fixing Holeson Front Flange
5mm dia.Fixing Holes in Back
21mm dia. Conduit Hole(Top and Bottom)
Flush type
*Bill amended pages 28/1/02 3:43 pm Page 9
FEATURES� Designed to meet BS 7654 and includes requirements for use by Lighting
and Highway Authorities.� Robust construction manufactured from quality thermo-plastic injection moulded
material.� Single & double pole versions accept tag type fuselinks from 2A to 25A.� Compact dimensions – a narrow width of 74mm makes units suitable for
smaller columns.� Screw down carrier offering enhanced security.� Integral terminal shield shrouding both the live and neutral incoming terminals
of double pole cutouts when carrier is removed.� Padlocking facility to obstruct the insertion of the carrier during maintenance work.� Intergral wiring channel allows a fused spur up to 6mm2 to be taken from
the bottom of the units.
CUT-OUTS AND CABLE EXTENSION BOXES
LIVE, NEUTRAL & SEPARATE EARTH BS 7654 CUT-OUT CUT-OUT
CUT-OUT DESCRIPTION CLASSIFICATION CONFIGURATION CAT. NO.
Single pole one fuseway TYPE 1 SL3S1with PVC grommets
Single pole one fuseway - SL3S1Asteel wire armour versionDouble pole one fuseway TYPE 4 SL3D1
with PVC grommets
Double pole one fuseway - SL3D1Asteel wire armour version
Double pole two fuseways TYPE 6 SL3D2with PVC grommets
Double pole two fuseways - SL3D2Asteel wire armour version
Steel wire armour versions incorporate a gland/ferrule plate Cat.No. SL3A
SWA Gland/Ferrule PlatePVC Grommets Tapped Gland Plate –
see accessories(Compression Glandsnot supplied)
L1 E
L NSUPPLY
N
L1 N E
L NSUPPLY
L1 L2 N E
L NSUPPLY
SL3S1
SL3D1
SL3D2
CABLE ENTRY OPTIONS
DIRECT SALES 0121 685 2004
47
SL3Street Lighting Cut-Outs 25A, 240V AC
THE RANGELIVE, NEUTRAL & SEPARATE EARTH VERSIONS:
Single pole with 1 fuseway (Classification, type 1).Double pole with 1 fuseway (Classification, type 4).Double pole with 2 fuseways (Classification, type 6).The above are fitted with PVC grommets and are available with SWAgland/furrule plates
LIVE & COMBINED NEUTRAL / EARTH VERSIONS:
Single pole with 1 fuseway (Classification, type 2).Single pole with 2 fuseways (Classification, type 3).
*26905 Bill Cat Sec.3 28/1/02 3:33 pm Page 16
SL3Street Lighting Cut-Outs 25A, 240V AC
448
DIRECT SALES 0121 685 2004
CUT-OUT AND EXTENSION BOX TERMINAL CAPACITIES
MIN. TO MAX. CIRCULAR STRANDEDTERMINALS COPPER CONDUCTORS
SL3 cut-outsingle outgoing terminals
1.5mm2 up to 16mm2
SL3 cut-outtwin incoing terminals
1.5mm2 up to 25mm2
Extension box 1.5mm2 up to 25mm2
standard terminals (25mm2 shaped stranded)Extension box
M6lug type terminalsAuxiliary terminals 1.5mm2 up to 10mm2
LIVE & COMBINED NEUTRAL/EARTH BS 7654 CUT-OUT CUT-OUT
CUT-OUT DESCRIPTION CLASSIFICATION CONFIGURATION CAT. NO.
Single pole one fusewayTYPE 2 SL3S1NE
with PVC grommets
Single pole two fusewaysTYPE 3 SL3S2NE
with PVC grommets
EXTENSION BOX EXTENSION BOX
EXTENSION BOX DESCRIPTION CONFIGURATION CAT. NO.
Extension box without terminalsSL3B
for increased cabling space
Extension box with two main incoming(looping) terminals at opposite sides SL3B2*of the box, leaving the throat clear
Extension box with four terminals:two twin incoming (looping) terminals
SL3B4*two twin incoming, single ongoing
terminalsExtension box with four lug type
M6 terminalsSL3B4L*
the two central terminals incorporatea single ongoing tunnel terminal
*With the addition of auxiliary terminal SL3BAT an ongoing terminal can be added to either or boththe terminals positioned at the side of the extension box.
SL3S1NE
SL3S2NE
All extension boxes have a brassgland plate with:1 x 20mm dia. hole2 x 25mm dia. holes2 x M6 earth screws & 3 blank plugs.
Note: An alternative gland plate with3 x 25mm dia. holes is available,Cat. No. SL3BG.
CABLE EXTENSION BOXES
Cable extension boxes are availablein four basic configurations. Otherconfigurations can be supplied tospecial order.
*26905 Bill Cat Sec.3 28/1/02 3:33 pm Page 17
DIRECT SALES 0121 685 2004
49
SL3Accessories
GLAND PLATE ACCESSORIES FOR CUT-OUTS
DESCRIPTION CAT. NOSteel wire armour gland/ferrule plate to convert standard
cut-outs to an SWA incomer arrangement SL3Acables must be less than 18mm dia. under the armour
Tapped plate suitable for two 20mm dia. compression glands SL3G(not supplied)
PVC cap for an unused way in an SL3A gland plate SL3ACM20 plug for an unused way in Sl3G gland plate SL3GP
ACCESSORIES FOR EXTENSION BOXES
DESCRIPTION CAT. NOAuxiliary terminal 10mm2 SL3BAT
Alternative gland plate 3 x 25mm holes SL3BG20mm dia. blanking plug for gland plate SL3P2025mm dia blanking plug for gland plate SL3P25
SPARE FUSE CARRIERS
CARRIER DESCRIPTION SUITABLE FOR CUT-OUTS CAT. NOSingle pole one fuse SL3S1, SL3S1A, SL3S1NE SL3S1CSingle pole two fuses SL3S2NE SL3S2CDouble pole one fuse SL3D1, SL3D1A SL3D1CDouble pole two fuses SL3D2, SL3D2A SL3D2C
HRC FUSELINKS
RATING BILL HRC FUSELINKCAT. NO.
2A BLST24A BLST46A BLST610A BLST1015A BLST1620A BLST2025A BLST2532A BLST32
SL3A SL3G
SL3BAT SL3BG
SL3P20 SL3P25
SL3AC SL3GP
SL3 Streelighting Cut-OutsDimensions in millimetres, all versions.
49
70
21 18
150
74
ØA
ØB
ØB
50
M6EarthBolt
42
M6EarthBolt
104
131
88
SL3 Cable Extension BoxesDimensions in millimetres,all versions.
Standard Gland PlateDiameter ØA = 20mmDiameter ØB = 25mm
Alternative SL3BG Gland PlateDiameter ØA = 25mmDiameter ØB = 25mm
*Bill amended pages 28/1/02 3:43 pm Page 10
Busbar Chambers100A to 800A
450
DIRECT SALES 0121 685 2004
Suitable for mounting switch and distribution gear either against a load bearing vertical surface or on a pedestal fixed against a nonload bearing vertical surface.
Busbar Chambers (IP3X) are made from rust protected sheet steel finished in Bill light grey.
All models have the same compact profile dimensions of approximately 364mm high by 222mm deep.
The four pole twin busbars vary only in their profile depth from the rear of the case, according to their rating, but otherwise occupyexactly the same location position when viewed from the front of the chamber.
All have detachable end plates enabling them to be extended easily with the connection of another chamber.
Full top and bottom end plates are detachable.
Kits are available for the mounting of all appropriate Masterlink and Sovereign ranges.
Bill Busbar Chambers comply with BS EN60439-1: IEC60439 at a short time withstand of 20 times the rated current for 1 second.
The rated 3 phase fused short circuit current = 63kA r.m.s. 550V.
FEATURES� Four pole twin busbars to BS EN 60439-1, (IEC60439)
� 100A, 200A and 400A versions available in four lengths:550mm900mm1350mm1800mm
� 630A and 800A versions available in three lengths:900mm1350mm1800mm
� All units are extendable with busbar extension sets
� Switchgear mounting and connection sets
� Cable clamps and sockets
� Pedestal and back plate sets
BUSBAR CHAMBERS 100A TO 800A
BUSBAR BUSBAR BUSBARCHAMBER EXTENSION CHAMBERNOMINAL SETS
RATING LENGTH (MM) CAT. NO. CAT. NO.100A 550 200BCS F15BBC100A 900 200BCS F19BBC100A 1350 200BCS F113BBC100A 1800 200BCS F118BBC200A 550 200BCS F25BBC200A 900 200BCS F29BBC200A 1350 200BCS F213BBC200A 1800 200BCS F218BBC400A 550 400BCS F45BBC400A 900 400BCS F49BBC400A 1350 400BCS F413BBC400A 1800 400BCS F418BBC630A 900 800BCS F69BBC630A 1350 800BCS F613BBC630A 1800 800BCS F618BBC800A 900 800BCS F89BBC800A 1350 800BCS F813BBC800A 1800 800BCS F818BBC
*26905 Bill Cat Sec.3 28/1/02 3:33 pm Page 19
Accessories
DIRECT SALES 0121 685 2004
51
PEDESTAL AND BACK-PLATE SETS
The three largest busbar chamber lengths have a complementary pedestal and back-plate set which provides the base and supportsystem from which an industrial switchboard can be developed. It is recommended that such switchboards be backed and securedagainst a wall, although this need not be a load bearing wall. Sets are made from 2mm thick rust protected sheet steel and arefinished in Bill light grey.
BUSBAR CHAMBER NOMINAL LENGTH PEDESTAL AND BACK-PLATE SETCAT. NO.
550MM -900MM 9PMU1350MM 13PMU1800MM 18PMU
FORCABLE FOR 100A - 200A 400A - 800A
CONNECTOR CURRENT BORE DIA. CAPACITY BUSBARS BUSBARSTYPE RATING (MM) (MM) CAT. NO. CAT. NO.
U Clamp 20A - 60A - 25 1CCL 3CCLU Clamp 60A - 100A - 70 2CCL 4CCLU Clamp 100A - 200A - 120 5CCL 5CCLSocket 100A - 200A 16.7 150 1CSK 1CSKSocket 200A - 300A 19.0 185 - 2CSKSocket 300A - 400A 22.5 240 - 3CSK
SOVEREIGN FUSESWITCHES MOUNTING SETRATING CAT. NO.
63A 2SWMS100/160A 9SWMS
200A 4SWMS315/400A 5SWMS630/800A 6SWMS
MASTERLINK SWITCH-DISCONNECTOR-FUSE20/32A 7SWMS63/125A 8SWMS
BUSBAR CABLE CLAMPS AND SOCKETS
Cable clamps or sockets for the connection of the main incoming supply are not included with the busbar chamber because of thevariety of sizes and forms which might be required. However a selection can be made from the following table.
SWITCHGEAR MOUNTING SETS
Available for switchgear which is to be mounted above or below the busbar chamber. All Mounting sets comprise instructions andtemplate to guide the machining of the top or bottom plate of the busbar chamber, sheet channel supports ready pierced forfasteners, which are mounted across the depth of the busbar chamber to hold the switchgear, and all necessary fasteners.
*26905 Bill Cat Sec.3 28/1/02 3:33 pm Page 20
Accessories
452
DIRECT SALES 0121 685 2004
SOVEREIGN FUSESWITCHES CONNECTION SETRATING CAT. NO.
100/160A 7SWCS200A 2SWCS
315/400A 3SWCS630/800A 4SWCS
SWITCHGEAR CONNECTION SETS
For the connection of Sovereign fuseswitches of 100A or above, solid copper connection sets are recommended as listed opposite.These comprise pre-formed and insulated solid copper links in 4 pole sets together with the necessary clamps and fasteners.
40 40310 CRS
550
40 40450 CRS
900
40 40900 CRS
1350
40
40 40
1350 CRS
1800
40 40450 CRS
BUSBAR CHAMBER EXTENSION SETS
Busbar chambers can be extended in length, by the interconnection of another similar rated chamber from the range, using one ofthree basic extension sets.
Each extension set includes suitable copper links and all necessary clamps, washers and fasteners together with basic assembly instructions.
Extension sets are also available to connect new busbar chambers to existing installations which incorporate old pattern busbar chambers.
550mm LengthBusbar Chambers100A, 200A or 400A
900mm LengthBusbar Chambers100A, 200A or 400A,630A or 800A
1350mm LengthBusbar Chambers100A, 200A or 400A,630A or 800A
1800mm LengthBusbar Chambers100A, 200A or 400A,630A or 800A
*26905 Bill Cat Sec.3 28/1/02 3:33 pm Page 21
Busbar ChambersDimensions (mm)
Busbar Chamber
Pedastal Backplate
Mounting SetInsulated Shields
PedastalSideplate
PedastalFoot
200A Sovereign 800A Sovereign
400A Sovereign
Spacers FloorMounting Bolts
100A Masterlink
Busbar ChamberCover Plate(machined)
Mounting SetSwitch Filler Plate
Mounting Set Clamping Channels
205
300 CRS
360
30
60
99
745
1266
1630
283
E CRS
Nom. Length – Minus End Plates
C
B DCRS
G No. of Holes 9 dia.
A Overall Including Screw Heads
F CRS F CRS
DIMENSIONS (MM)
NOMINAL BUSBAR CHAMBERLENGTH DIMENSIONS
A B C D E F G550mm 562 364 222 280 474 – 4900mm 912 364 222 280 824 – 41350mm 1362 364 222 280 1274 – 41800mm 1812 364 222 280 1724 862 6
DIRECT SALES 0121 685 2004
53
*26905 Bill Cat Sec.3 28/1/02 3:33 pm Page 22
Fused Combination Switches32A to 800A
454
DIRECT SALES 0121 685 2004
1. Polycarbonate inter-phaseshields.
2. Fixed contacts.
3. 63A-800A terminations areprovided with bolts for easyattachment of cable lugs orsolid copper connections.
4. Polycarbonate snap-fasteningconnection barriers.
5. Manually independent overcentre spring switchingmechanism.
6. Contact system provides fourbreaks in series per phase.
7. Moving contacts.
8. Fully interlocked rotary actionoperating handle. Interlockmay be overridden by acompetent operator forinspection and maintenance.
9. Choice of switched (neutralmakes first, breaks last) orsolid neutrals.
10. Positive contact indicatorshows contact positionwith door open.
FEATURES � Six compact frame sizes
� SPN, SPSN, TP, TPN, TPSN pole configurations
� Accommodate BS88 HRC fuselinks
� Comply with BSEN 60947-3
� ASTA certified
� Superior performance AC22 and AC23 switch ratings
� Complete fuse isolation in the OFF position
� Double break wiping action contact system ensuresminimal contact wear
� Fuselinks remain stationary providing high reliabilityfor fuse and contact system
� Positive contact indication provided by the handleand the switch
� Operating handles provide IP54 protection and clearON / OFF indication
� Door interlocking is also provided by the handle
� Padlocks may be fitted in the OFF position
� Moulded handles up to 400A, cast metal above
� Supplied without fuselinks fitted
Mounting Positions
Switches may be mounted in the positions illustratedleft, without the need for de-rating.
1 2 3 4 5
108 976
*26905 Bill Cat Sec.3 28/1/02 3:33 pm Page 23
32A to 800A SPN, SPSN, TP
DIRECT SALES 0121 685 2004
55
*Dimensions are for switches withoutfuselinks, handles or covers.
For detailed dimensions see page 62.
BS FUSE VERSION, SPN STANDARD OPERATION SINGLE POLE & BOLTED NEUTRAL
AC-22A AC-23A ENCLOSED BS88 STANDARD APPROX SINGLE POLE &FRAME RATING, A RATING, A THERMAL FUSELINK DIMENSIONS* (MM) BOLTED NEUTRAL
SIZE @ 550V @ 550V RATING, A REF. H W D CAT. NO.1 32A 32A 32A A1 126.0 88.5 82.0 FCS321N2 63A 63A 63A A2-A3 145.0 110.5 107.0 FCS631N2 100A 100A 100A A2-A3 145.0 110.5 107.0 FCS1001N3 125A 125A 125A A2-A4 181.0 129.5 124.0 FCS1251N4 160A 160A 160A B1-B2 286.0 182.5 168.0 FCS1601N4 200A 200A 200A B1-B2 286.0 182.5 168.0 FCS2001N
BS FUSE VERSION, SPSN STANDARD OPERATION SINGLE POLE & SWITCHED NEUTRAL
AC-22A AC-23A ENCLOSED BS88 STANDARD APPROX SINGLE POLE &FRAME RATING, A RATING, A THERMAL FUSELINK DIMENSIONS* (MM) SWITCHED NEUTRAL
SIZE @ 550V @ 550V RATING, A REF. H W D CAT. NO.1 32A 32A 32A A1 126.0 88.5 82.0 FCS321SN2 63A 63A 63A A2-A3 145.0 110.5 107.0 FCS631SN2 100A 100A 100A A2-A3 145.0 110.5 107.0 FCS1001SN3 125A 125A 125A A2-A4 181.0 129.5 124.0 FCS1251SN4 160A 160A 160A B1-B2 286.0 182.5 168.0 FCS1601SN4 200A 200A 200A B1-B2 286.0 182.5 168.0 FCS2001SN
BS FUSE VERSION, TP STANDARD OPERATION TRIPLE POLE
AC-22A AC-23A ENCLOSED BS88 STANDARD APPROXFRAME RATING, A RATING, A THERMAL FUSELINK DIMENSIONS* (MM) TRIPLE POLE
SIZE @ 550V @ 550V RATING, A REF. H W D CAT. NO.1 32A 32A 32A A1 126.0 105.5 82.0 FCS3232 63A 63A 63A A2-A3 145.0 141.0 107.0 FCS6332 100A 100A 100A A2-A3 145.0 141.0 107.0 FCS10033 125A 125A 125A A2-A4 181.0 169.0 124.0 FCS12534 160A 160A 160A B1-B2 286.0 227.0 168.0 FCS16034 200A 200A 200A B1-B2 286.0 227.0 168.0 FCS20035 400A 315A 400A B1-B4 359.0 335.0 196.0 FCS31535 400A 400A 400A B1-B4 359.0 335.0 196.0 FCS40036 630A 630A 630A C1-C3 464.5 395.0 257.5 FCS63036 800A 710A 800A C1-C3 464.5 395.0 257.5 FCS8003
*26905 Bill Cat Sec.3 28/1/02 3:33 pm Page 24
Fused Combination SwitchesTPN & TPSN
456
DIRECT SALES 0121 685 2004
BS FUSE VERSION, TPN STANDARD OPERATION TRIPLE POLE & BOLTED NEUTRAL
AC-22A AC-23A ENCLOSED BS88 STANDARD APPROX TRIPLE POLE &FRAME RATING, A RATING, A THERMAL FUSELINK DIMENSIONS* (MM) SWITCHED NEUTRAL
SIZE @ 550V @ 550V RATING, A REF. H W D CAT. NO.1 32A 32A 32A A1 126.0 130.5 82.0 FCS323N2 63A 63A 63A A2-A3 145.0 172.5 107.0 FCS633N2 100A 100A 100A A2-A3 145.0 172.5 107.0 FCS1003N3 125A 125A 125A A2-A4 181.0 209.0 124.0 FCS1253N4 160A 160A 160A B1-B2 286.0 272.0 168.0 FCS1603N4 200A 200A 200A B1-B2 286.0 272.0 168.0 FCS2003N5 400A 315A 400A B1-B4 359.0 407.0 196.0 FCS3153N5 400A 400A 400A B1-B4 359.0 407.0 196.0 FCS4003N6 630A 630A 630A C1-C3 464.5 485.0 257.5 FCS6303N6 800A 710A 800A C1-C3 464.5 485.0 257.5 FCS8003N
BS FUSE VERSION, TPSN STANDARD OPERATION TRIPLE POLE & SWITCHED NEUTRAL
AC-22A AC-23A ENCLOSED BS88 STANDARD APPROX TRIPLE POLE &FRAME RATING, A RATING, A THERMAL FUSELINK DIMENSIONS* (MM) SWITCHED NEUTRAL
SIZE @ 550V @ 550V RATING, A REF. H W D CAT. NO.1 32A 32A 32A A1 126.0 130.5 82.0 FCS323SN2 63A 63A 63A A2-A3 145.0 172.5 107.0 FCS633SN2 100A 100A 100A A2-A3 145.0 172.5 107.0 FCS1003SN3 125A 125A 125A A2-A4 181.0 209.0 124.0 FCS1253SN4 160A 160A 160A B1-B2 286.0 272.0 168.0 FCS1603SN4 200A 200A 200A B1-B2 286.0 272.0 168.0 FCS2003SN5 400A 315A 400A B1-B4 359.0 407.0 196.0 FCS3153SN5 400A 400A 400A B1-B4 359.0 407.0 196.0 FCS4003SN6 630A 630A 630A C1-C3 464.5 485.0 257.5 FCS6303SN6 800A 710A 800A C1-C3 464.5 485.0 257.5 FCS8003SN
*26905 Bill Cat Sec.3 28/1/02 3:33 pm Page 25
DIRECT SALES 0121 685 2004
57
CONNECTOR SIZES AND TERMINATION TORQUE SETTINGS
MAXIMUM CONNECTOR TORQUE SETTING TORQUE SETTING TORQUE SETTINGFRAME SIZES MAXIMUM CABLE CABLE TERMINALS FUSE TERMINALS AUXILARY TERMINALSSIZES DIMENSION T DIMENSION U SIZES (NM) (NM) (NM)
1 Box Clamp up to 25mm2 cable 25mm2 3.0 (M5) 1.2 (M4) 0.5 (M3)2 10mm 19mm 35mm2 5.0 (M6) 2.0 (M5) 0.5 (M3)3 12mm 22mm 70mm2 12.0 (M8) 4.0/2.0 (M5/M6) 0.5 (M3)4 22mm 32mm 150mm2 25.0 (M10) 25.0 (M8) 0.5 (M3)5 22mm 58mm 500mm2 50.0 (M14) 50.0 (m8) 0.5 (M3)6 40mm 70mm 630mm2 100.0 (M20) 100.0 (M10) 0.5 (M3)
SUITABLE BILL HRC FUSELINKS AND PHASE LINKS
FRAME SIZE NORMAL RATING BS88 FUSELINK SUITABLE 415V BILL HRC SUITABLE SOLIDREF. FUSELINKS TO MAXIMUM RATING PHASE LINKS
CAT. NO. CAT. NO.
1 32A A1 BNIT32 -2 63A A2-A3 BTIS63 L602 100A A2-A3 BOS100 -3 125A A2-A4 BTFP125 -4 160A B1-B2 BTF160 L1604 200A B1-B2 BTF200 L2005 315A B1-B4 BTKF315 L3005 400A B1-B4 BTMF400 L4006 630A C1-C3 BTTM630 L6006 800A C1-C3 BTLM800 L800
U
T
*26905 Bill Cat Sec.3 28/1/02 3:33 pm Page 26
Fused Combination SwitchesTechnical Data
458
DIRECT SALES 0121 685 2004
1. The capacitor rating of the switch is limited by the fuselink fitted.
2. Some fuselinks limit these figures further. Starting current characteristics must be considered separately.
3. Units rated insulation voltage at 1000V available to special order.
The technical information given in this table applies to 3 and 4 pole fused combination switches.
FRAME SIZE 1 2 2 3 4 4 5 5 6 6NOMINAL RATING 32A 63A 100A 125A 160A 200A 315A 400A 630A 800A
Fused combination switch, nominal rating 32A 63A 100A 125A 160A 200A 315A 400A 630A 800ARated insulation voltage (3) 690V 690V 690V 690V 690V 690V 690V 690V 690V 690V
Rated thermal current and operational in open air 550V 32A 63A 100A 125A 200A 200A 400A 400A 630A 800Acurrent AC22, Ambient 40°C, free in enclosure 550V 32A 63A 100A 125A 200A 200A 400A 400A 630A 800Amounting position in enclosure with solid links 550V 45A 125A 125A 160A 200A 315A 630A 630A 800A 1000A
Rated operational voltage 550V 550V 550V 550V 550V 550V 550V 550V 550V 550VRated operational current in categories 220V 32A 63A 100A 125A 160A 200A 315A 400A 630A 710AAC23 and AC3. Time interval between 380V 32A 63A 100A 125A 160A 200A 315A 400A 630A 710Aoperations 30s in AC3 (2) 415V 32A 63A 100A 125A 160A 200A 315A 400A 630A 710A
500V 32A 63A 100A 125A 160A 200A 315A 400A – 710A550V 32A 63A 100A 125A 160A 200A 315A 400A – 710A
Rated operational current DC23 single pole 110V 32A 63A 63A 125A 160A 200A 315A 400A 630A 800Atwo poles in series 250V 32A 63A 63A 125A 160A 200A 315A 400A 630A 800Atwo poles in series 500V 32A 63A 63A 80A 160A 200A – – – –
Rated operational power in categories 220V 7.5kW 15kW 30kW 37kW 45kW 55kW 110kW 132kW 200kW 220kWAC23 and AC3. Time interval 380V 15kW 30kW 45kW 55kW 75kW 110kW 150kW 185kW 315kW 355kWbetween operations 30s in AC3 (2) 415V 15kW 30kW 55kW 60kW 90kW 110kW 150kW 225kW 375kW 410kW
500V 20kW 37kW 60kW 75kW – 130kW 185kW 280kW – 470kW550V 22kW 45kW 75kW 90kW – 150kW 225kW 300kW – 600kW
Rated breaking capacity AC, cos = 0.35 415V 250A 500A 800A 1000A 1280A 1600A 2500A 3200A 4000A 5680A500V 250A 500A 800A 1000A 1280A 1600A 2500A 3200A – 5680A550V 250A 500A 800A 1000A 1280A 1600A 2500A 3200A – 5680A
Rated breaking capacity DC, L/R = 15ms single pole 110V 128A 250A 250A 500A 640A 800A 1260A 1600A 2520A 2840Atwo poles in series 250V 128A 250A 250A 500A 640A 800A 1260A 1600A 2520A 2840Atwo poles in series 500V 128A 250A 250A 320A 640A 800A – – – –
Short circuit current in closed position R.M.S. value 415V 63kA 100kA 100kA 63kA 63kA 63kA 63kA 63kA 50kA 50kARated fused short circuit current and 500V 63kA 100kA 100kA 63kA 63kA 63kA 63kA 63kA – 50kA
550V 63kA 100kA 100kA 63kA 63kA 63kA 63kA 63kA – 50kAPeak value 550V 130kA 210kA 210kA 130kA 130kA 130kA 130kA 130kA – 105kA
making capacity on fault level . . . . R.M.S. value 415V 63kA 100kA 100kA 63kA 63kA 63kA 63kA 63kA 50kA 50kA500V 63kA 100kA 100kA 63kA 63kA 63kA 63kA 63kA 50kA 50kA550V 63kA 100kA 100kA 63kA 63kA 63kA 63kA 63kA – 50kA
Peak value 550V 130kA 210kA 210kA 130kA 130kA 130kA 130kA 130kA – 105kAMax. peak let through current 6kA 15kA 15kA 15kA 22kA 29kA 52kA 52kA 71kA 71kARated short–time withstand current, 1s. R.M.S. value 550V 1.5kA 3kA 3kA 5kA 5kA 5kA 10kA 10kA 12.6kA 16kARated capacitor power (1) (kVAr) 380V 21 41 50 82 100 130 180 180 250 310
(kVAr) 415V 24 45 55 90 120 140 200 200 270 340
Rated impulse withstand voltage peak value 10kV 12kV 12kV 12kV 12kV 12kV 12kV 12kV 12kV 15kV
Mechanical endurance (operations) 10000 10000 10000 10000 10000 10000 8000 8000 5000 5000Fuse types BS pattern BS88 ref. A1 A2–A3 A2–A3 A2–A4 B1–B2 B1–B2 B1–B4 B1–B4 C1–C3 C1–C3
Fuse fixing centres (mm) 44.5 73 73 73/94 111 111 111 111 133,184 133,184Solid copper links - BLK60 - - BLK160 BLK200 BLK300 BLK400 BLK600 BLK800Weight (cartoned) without HRC fuselinks SPN, SPSN 0.90kg 1.36kg 1.36kg 1.60kg 5.63kg 5.63kg – – – –
DP 0.90kg 1.36kg 1.36kg 1.90kg 5.63kg 5.63kg – – – –TP 1.04kg 1.57kg 1.57kg 2.51kg 6.70kg 6.70kg 18.5kg 18.5kg 38kg 38kgTPN, TPSN 1.20kg 1.81kg 1.81kg 2.78kg 7.50kg 7.50kg 19.5kg 19.5kg 41kg 41kg
*26905 Bill Cat Sec.3 28/1/02 3:33 pm Page 27
Accessories
DIRECT SALES 0121 685 2004
59
EXTENDED HANDLE SHAFTS
Extended operating shafts, 200mm extra length.
EXTENDED HANDLEFRAME FUSE-SWITCH SHAFTS
SIZE RATING, A CAT. NO.1-3 32A – 125A 3XS4 160A – 200A 4XS
5-6 315A – 800A 6XS
MECHANISM PADLOCKING
To lock switch in OFF position when an enclosure is open.
MECHANISMFRAME FUSE-SWITCH PADLOCKING PADLOCK
SIZE RATING, A DEVICE CAT. NO. CAT. NO.1-3 32A – 125A 3PLD PL12514 160A – 200A 4PLD PL1251
5-6 315A – 800A 6PLD PL1251
FIGURE LOCKING DEVICE
To provide locking ON, OFF and interlocking facility. The device is a shaft mounting interlockcam attachment for adaption to Castell or Fortress figure locks (Not supplied).
FRAME FUSE-SWITCH CAM ATTACHMENTSIZE RATING, A CAT. NO.1-3 32A – 125A 3FLD4 160A – 200A 4FLD
5-6 315A – 800A 6FLD
MULTI-PADLOCK DEVICE
To assist in the use of multi-padlock devices. The support is located under the handleduring assembly onto the compartment door.
FRAME FUSE-SWITCH MULTI-PADLOCKSIZE RATING, A DEVICE CAT. NO.1-4 32A – 200A 4MPD5 315A – 400A 5MPD6 630A – 800A 6MPD
SAFETY HANDLES
Red/Yellow safety handles (IP54) suitable for up to three padlocks in the OFF position.
RED/YELLOWFRAME FUSE-SWITCH SAFETY HANDLES (IP54)
SIZE RATING, A CAT. NO.1-3 32A-125A 3SHN4 160A-200A 4SHN5 315A-400A 5SHN6 630A-800A 6SHN
*Bill amended pages 28/1/02 3:43 pm Page 11
Fused Combination SwitchesAccessories
460
DIRECT SALES 0121 685 2004
FUSE COVERS
Clear polycarbonate clip-on covers to protect all fuses (BS type) from unintentional contact.
FCS32 fuse-switches have finger protected main terminals.
*Fuse-switch rating refers to frame size 2, 100A units only.
CABLEFRAME FUSE-SWITCH POLE SHROUD
SIZE RATING, A CONFIGURATION CAT. NO.1 32A SPN, DP, TP, TPN 1TS4
63A-100A* SPN, SPSN, DP 2TS22 63A-100A* TP 2TS3
63A-100A* TPN, TPSN 2TS4125A SPN, SPSN, DP 3TS2
3 125A TP 3TS3125A TPN, TPSN 3TS4
160A-200A SPN, SPSN, DP 4TS24 160A-200A TP 4TS3
160A-200A TPN, TPSN 4TS4315A-400A TP 5TS3
5315A-400A TPN, TPSN 5TS4630A-800A TP 6TS3
6630A-800A TPN, TPSN 6TS4
FRAME FUSE-SWITCH POLE FUSE COVERSIZE RATING, A CONFIGURATION CAT. NO.
32A SPN, SPSN, DP 1FC21 32A TP, TPSN 1FC3
32A TPN 1FC463A-100A SPN, SPSN, DP 2FC2
2 63A-100A TP, TPSN 2FC363A-100A TPN 2FC4
125A SPN, SPSN, DP 3FC23 125A TP, TPSN 3FC3
125A TPN 3FC4160A-200A SPN, SPSN, DP 4FC2
4 160A-200A TP, TPSN 4FC3160A-200A TPN 4FC4315A-400A TP, TPSN 5FC3
5315A-400A TPN 5FC4630A-800A TP, TPSN 6FC3
6630A-800A TPN 6FC4
CABLE TERMINAL SHROUDS
Clear polycarbonate shrouds to protect the cable terminations from unintentionalcontact. (1 per pack).
*26905 Bill Cat Sec.3 28/1/02 3:33 pm Page 29
Accessories
DIRECT SALES 0121 685 2004
61
UE ACII DCII48V 10A -110V 10A -
220/240V 6A -380/440V 4A -
FRAME FUSE-SWITCH AUXILIARY SWITCH MOUNTING PACKSIZE RATING, A NO. OF CONTACTS CAT. NO. ADAPTOR CAT. NO.
2 c/o 1ASP1-3 32A-125A 4 c/o 2ASP + 3MP
6 c/o 3ASP8 c/o 4ASP2 c/o 1ASP4 c/o 2ASP
4 160A-200A 6 c/o 3ASP + 4MP8 c/o 4ASP12 c/o 6ASP2 c/o 1ASP4 c/o 2ASP
5-6 630A-800A 6 c/o 3ASP + 6MP8 c/o 4ASP12 c/o 6ASP
AUXILIARY SWITCHES
Each auxiliary pack contains two sets of changeover contacts. These moulded units havebeen designed to offer protection against accidental finger contact.
Auxiliary packs can be added to the drive shaft of any switch rating using the appropriatemounting pack adaptor. See table
(Applicable up to triple pole units).
TECHNICAL DATA, Ith-10A
*26905 Bill Cat Sec.3 28/1/02 3:33 pm Page 30
Fused Combination SwitchesStandard Operation Dimensions (mm)
462
DIRECT SALES 0121 685 2004
BS FUSE COMBINATION SWITCHES - STANDARD OPERATION
‘R’ dimension represents the maximum width across mechanism spring guides.‘T’ dimension = additional height of connecting barrier.
First auxiliary pack adds 24.5mm to side of the switch when attached; each additional auxiliary pack adds a further 10.5mm.
FRAME CAT A B1 B2 B3 C1 C2 C3 D E F1 F2 G1 G2* H1 H2* HR J1 J2 K L M N P Q R S T U1 U2 W1 W2 X Y Z1 Z2SIZE NO.
1FCS321N
88.5 67.5 6.3FCS321SNFCS323 109.5 82 84 81 98 126 - 83.5 88.5 56 - - - 16.7 - 175 32.5 20 21 81.5 65 5.5 - - 121 13 14 78 83 6 6 SQ 55 38 -
FCS323NFCS323SN
130.5 109.5
2FCS631N
110 88.5 6.3FCS631SN
FCS633 141 107 109 86 107 145 166 95 119.5 72 - 27 - 25.5 - 175 36.5 26.5 31 95.5 65 5.5 18 6 125 15 19 94 99 6.7 5.5 SQ 55 45 47
FCS633NFCS633SN
172 150.5
2FCS100N
110 88.5 6.3FCS1001SN
FCS1003 141 107 109 86 107 145 166 95 119.5 72 - 27 - 25.5 - 175 36.5 26.5 31 95.5 65 5.5 18 6 125 15 19 94 99 6.7 5.5 SQ 55 45 47FCS1003N
FCS1003SN172 150.5
3FCS1251N
129 104.5 6.3FCS1251SN
FCS1253 169 124 135.5 86 142 181 209.5120.5 144.5 80 - 23 - 21 - 175 41 30.5 40 123.5 65 5.5 22 8 125 15 19.5 120 125.5 7.5 7 SQ 55 45 47FCS1253N
FCS1253SN209 184.5
4FCS1601N
182 131 9.5FCS1601SN
FCS1603 227 198 190 141 196 286 297 182.5 176 120 - 34 - 31.5 - 250 63.5 37.5 45 167 130 6.5 32 10 266 22 45 154 159 10 15 SQ 55 57 69FCS1603N
FCS1603SN272 221
4FCS2001N
182 131 9.5FCS2001SN
FCS2003 227 168 190 141 196 286 297 182.5 176 120 - 34 - 31.5 - 250 63.5 37.5 45 167 130 6.5 32 10 266 22 45 154 159 10 15 SQ 55 57 69FCS2003N
FCS2003SN272 221
5 FCS3153 335 259 - - 14.5FCS3153N 407 196 206 165 225 359 365 164 331 95 139 43 43 18 40 350 64 53.2 72 188 210 8.5 45 14 - 26.5 67 174 179 9.5 2.5 SQ 52 65 83
FCS3153SN 407 331 - -5 FCS4003 335 259 - - 14.5
FCS4003N 407 196 206 165 225 359 365 164 331 95 139 43 43 18 40 350 64 53.2 72 188 210 8.5 45 14 - 26.5 67 174 179 9.5 2.5 SQ 52 65 83FCS4003SN 407 331 - -
6 FCS6303 395 319.5 - - 214 14.5FCS6303N 485 257.5 268 183 320 464.5 472.5 164 411.5 140 180 48.3 60.3 32.3 54 350 74.5 63 92 266.5 to 8.5 64 20 - 26.5 72 240 245.5 9.5 2 SQ 60 85 133
FCS6303SN 485 411.5 - - 3206 FCS8003 395 319.5 - - 214 14.5
FCS8003N 485 257.5 268 183 320 464.5 472.5 164 411.5 140 180 48.3 60.3 32.3 54 350 74.5 63 92 266.5 to 8.5 64 20 - 26.5 72 240 245.5 9.5 2 SQ 60 85 133FCS8003SN 485 411.5 - - 320
* Unless otherwise stated, all Bolted Neutral Terminations G2, H2 are the same as Phase Terminations G1, H1.
*26905 Bill Cat Sec.3 28/1/02 3:33 pm Page 31
Dimensions (mm)
DIRECT SALES 0121 685 2004
63
SWITCH A B CRATING, A BS BS
32A 170 100 18063A 230 130 225
100A, 125A 260 140 225160A, 200A 325 200 350315A, 400A 460 285 475630A, 800A 675 375 575
FRAME SIZE 1 2 3 4 5 6B 14.0 14.0 14.0 14.0 17.0 18.0
SHAFT LENGHT (MM) 200 200 200 300 200 200B
MAX. DEPTH OF 235 240 240 375 320 337ENCLOSURE WITHSTANDARD SHAFT
*Refer to ratings of fuse switches.
Note 1: First auxiliary pack with mounting plate adds 24.5mm to side of switch when attached. Each additional pack adds afurther 10.5mm.
INTERNAL ENCLOSURE DIMENSIONS
These enclosure dimensions are for guidance only as recommended minimum inside enclosuredimensions, for temperature rise considerations.Note: Larger dimensions may be necessary for the bending and termination of cables, copper, etc..
HANDLE OPERATING SHAFT
The cut length of the handle operating shaft must allow a distance of ‘A’ when the door is firmly closed, and any gasket is fully compressed.Dimension ‘A’; distance from outside of door to underside of interlock lug is shown below:-
*26905 Bill Cat Sec.3 28/1/02 3:34 pm Page 32
Dimensions (mm)
464
DIRECT SALES 0121 685 2004
HANDLE DIMENSIONS
FUSE SWITCH HANDLE FRAMERATING, A CAT. NO. A B C SIZE32A-125A 3HN 67 96.5 54 1-3160A-200A 4HN 67 159.5 54 4315A-400 5HN 76 245 52.4 5
630A-800A 6HN 90 260/365* 58.9 6
*Extended length
OPERATING HANDLE FIXING APERTURES
Handle aligned thus: Frame size 1-4
Frame size 5 Frame size 6
*26905 Bill Cat Sec.3 28/1/02 3:34 pm Page 33